EN – Quick start-up guide 3
EN – Quick start-up guide
This guide describes how to start-up the drive using the First start assistant on the
Hand-Off-Auto control panel. For complete information on start-up, see ACH580 firmware
manual (3AXD50000027537 [English]).
Note:
Automatic selection of supply voltage is not supported in ACH580-31. You must select the
supply voltage manually using parameter 95.01. See steps for Commissioning with
parameters on page 9.
Start-up with the First start assistant on an Hand-Off-Auto
control panel
WARNING!
Do not start-up the drive unless you are a qualified electrician.
Read and obey the instructions in chapter Safety instructions at the beginning of the Hardware manual of the
drive. Ignoring the instructions can cause physical injury or death, or damage to the equipment.
EN – Quick start-up guide 3
EN
Safety
Check the installation. See chapter Installation checklist in the Hardware manual of the drive.
WARNING!
The drive will start up automatically at power-up if the external run command is on and the drive
is in the external control mode.
Check that the starting of the motor does not cause any danger.
De-couple the driven machine if
• there is a risk of damage in case of an incorrect direction of rotation, or
• a Normal ID run is required during the drive start-up, when the load torque is higher than 20% or the
machinery is not able to withstand the nominal torque transient during the ID run.
Hints on using the assistant control panel
The two commands at the bottom of the display (Options
and Menu in the figure on the right), show the functions of
the two softkeys and located below the display.
The commands assigned to the softkeys vary depending on
the context.
Use keys , , and to move the cursor and/or
change values depending on the active view.
Key shows a context-sensitive help page.
For more information, see ACS-AP-x assistant control panels
user’s manual (3AUA0000085685 [English]).
EN
4 EN – Quick start-up guide
1 – First start assistant guided settings:
Language, date and time, and motor nominal values
Have the motor name plate data at hand.
Power up the drive.
The First start assistant guides you through the first start-up.
The assistant begins automatically. Wait until the control
panel enters the view shown on the right.
Select the language you want to use by highlighting it (if not
already highlighted) and pressing (OK).
Note: After you have selected the language, it takes a few
minutes to download the language file to the control panel.
ACH580-31 drives: Select the supply voltage with parameter 95.01.
Select Commission the ACH580 and press (Next).
Select the localization you want to use and press (Next).
Change the units shown on the panel if needed.
•
Go to the edit view of a selected row by pressing .
•
Scroll the view with and .
Go to the next view by pressing (Next).
To select a value in an edit view:
•
Use and to select the value.
Press (Save) to accept the new setting, or press
(Cancel) to go back to the previous view without making
changes.
Set the date and time as well as date and time display
formats.
•
Go to the edit view of a selected row by pressing .
•
Scroll the view with and .
Go to the next view by pressing (Next).
EN – Quick start-up guide 5
EN
Refer to the motor nameplate for the following nominal value settings of the motor. Enter the values exactly
as shown on the motor nameplate.
Example of a nameplate of an induction (asynchronous) motor: