3Com 5017C, 5017C-LS User Manual

Page 1
®
ONline 17-Slot System
Concentrator Installation and
Operation Guide
Document Number 17-00417-3
Printed March 1995
Model Numbers: 5017C-LS
5017C
5017C with load sharing
Southborough, MA 01772-1886
U.S.A.
(508) 460-8900
FAX (508) 460-8950
Page 2
Federal Communications Commission Notice
This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation of this equipment in a residential area is likely to cause harmful interference, in which case you must correct the interference at your own expense.
Canadian Emissions Requirements
This Class A digital apparatus meets all requirements of the Canadian Interference-Causing Equipment Regulations.
Cet appareil numérique de la classe A respecte toutes les exigences du Règlement sur le matériel brouilleur du Canada.
VDE Class B Compliance
Hiermit wird bescheinigt, dass der 5017C und 5017C-LS in Üebereinstimmung mit den Bestimmungen der Vfg 243/1991 funkentstöert ist.
Der Deutschen Bundespost wurde das Inverkehrbringen dieses Geraetes angezeigt und die Berechtigung zur Üeberprüefung der Serie auf Einhaltung der Bestimmungen eingeräeumt.
Einhaltung mit betreffenden Bestimmugen kommt darauf an, dass geschirmte Ausfuehrungen gebraucht werden. Fuer die Beschaffung richtiger Ausfuehrungen ist der Betreiber verantwortlich.
This is to certify that the 5017C and 5017C-LS are shielded against radio interference in accordance with the provisions of Vfg 243/1991.
The German Postal Services have been advised that this equipment is being placed on the market and that they have been given the right to inspect the series for compliance with regulations.
Compliance with applicable regulations depends on the use of shielded cables. The user is responsible for procuring the appropriate cables.
EN55022/CISPR22 Compliance
This equipment conforms to the Class A emissions limits for a digital device as defined by EN55022 (CISPR22).
VCCI Class 1 Compliance
This equipment is in the 1st Class category (information equipment to be used in commercial or industrial areas) and conforms to the standards set by the Voluntary Control Council for Interference by Information Technology Equipment aimed at preventing radio interference in commercial or industrial areas.
Consequently, when the equipment is used in a residential area or in an adjacent area, radio interference may be caused to radio and TV receivers, and so on.
Read the instructions for correc t handling .
UK General Approval Statement
The ONcore Switching Hub, ONline System Concentrator, and ONsemble StackSystem Hub are manufactured to the International Safety Standard EN 60950 and are approved in the UK under the General Approval Number NS/G/12345/J/100003 for indirect connection to the public telecomm unication network.
Disclaimer
The information in this document is subject to change without notice and should not be construed as a commitment by 3Com Corporation. 3Com Corporation assumes no responsibility for any errors that may appear in this document.
Copyright State me nt
©
1995 by Chipcom Corporation , a subsidiar y of 3Com Corporation. Printed in U.S.A. All rights reserved. The information contained herein is the exclusive and confidential property of 3Com Corporation. No part of this manual may be disclosed or reproduced in whole or in part without permission from 3Com Corporation.
Trademarks
Because of the nature of this material, numerous hardware and software products are mentioned by name. In most, if not all cases, these product names are claimed as tradem arks by the companies that manufacture the products. It is not our intent to claim these names or trademarks as our own.
Artel, Chipcom, Ethermodem, Galactica, ONcore, ORnet, StarBridge, and TriChannel are registered trademarks of Chipcom Corporation, a subsidiary of 3Com Corporation.
Chipcom OpenHub, G-Man, LANsentry, MultiProbe, ONdemand, ONline, ONsemble, PowerRing, SL2000, SL3000, SL4000, StackJack, StackSystem, and SwitchCentral are trademarks of Chipcom Corporation, a subsidiary of 3Com Corporation.
ii ONline 17-Slot System Concentrator Installation and Operation Guide
Page 3
The Chipcom Multichannel Architecture Communications System is registered under U.S. Patent Number 5,301,303.
UNIX is a registered trademark in the U.S.A. and other countries licensed exclusively through X/Open Company, Ltd.
XNS is a trademark of Xerox Corporation. DEC, DECnet, the Digital logo, DELNI, POLYCENTER, VAX, VT100,
and VT220 are trademarks of Digital Equipment Corporation. 3ComFacts, Ask 3Com, CardFacts, NetFacts, and CardBoard are
service marks of 3Com Corporation. 3Com, LANplex, BoundaryRouting, LanScanner, LinkBuilder,
NETBuilder, NETBuilderII, ParallelTasking, ViewBuilder, EtherDisk, Etherl\Link, EtherLink Plus, EtherLink II, TokenLink, TokenLink Plus, and TokenDisk are registered trademarks of 3Com Corporation.
3ComLaser Library, 3TECH, CacheCard, FDDILink, FMS, NetProbe, SmartAgent, Star-Tek, and Transcend are trademarks of 3Com Corporation.
CompuServe is a registered trademark of CompuServe, Inc. 3Com registered trademarks are registered in the United States,
and may or may not be registered in other countries. Other brand and product names may be registered trademarks or trademarks of their respective holders.
Restricted Rights
Use, duplication, or disclosure b y the G overnm ent is subject to restrictions as set forth in subparagraph (c)(1) (ii) of the Rights in Technical Data and Computer Software clause at DFARS 252.227-7013.
Printed on recycle d paper.
ONline 17 -Slot System Concentrator Installation and Operation Guide iii
Page 4
iv ONline 17-Slot System Concentrator Installation and Operation Guide
Page 5
How to Use This Guide
Audience . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiii
Structure of This Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xiv
Docume nt Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xv
Related Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . xvi
3Com Doc uments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .xvii
Reference Documents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .xvii
Chapter 1 — Introduction
Introducing the ONline System Concentrator . . . . . . . . . . . . . . . . . . . . . . .1-1
Back Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
Front Panel . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-3
ONline System Concentrator Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-4
Modul ar Design . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-5
TriChannel Architecture . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-6
Port-Switching Technology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-6
Fault-Tolerance Capabilities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-8
Backup Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-8
Load Sharing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-8
Backup Controller Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-9
Redun dant Cable Links . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-9
Backup Concentrator . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-10
Hot Swa pping of Media Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-11
Synchronous Backplane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-12
Contents
Chapter 2 — Installation and Troubleshooting
Contents of the S hipping B ox . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
FCC Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-3
Site Se lection Consider ations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
ONline 17-Slot System Concentrator Installation and Operation Guide v
Page 6
Location Requirement s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-4
Power Requirem ents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-5
Rack Mount Installati on Require ments . . . . . . . . . . . . . . . . . . . . . . . . .2-5
Table Top Installation Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . .2-6
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-6
Inst alling the Cable Tray . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-7
Cabl e Tray Rack Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8
Cabl e Tray Table Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-10
Installing the ONline System Concentrator . . . . . . . . . . . . . . . . . . . . .2-11
Rack Mounting the ONline System Concentrator . . . . . . . . . . . . .2-11
Table Top Mounting the ONline Concentrator . . . . . . . . . . . . . . .2-13
Inst alling the Backup Power Supply (Optional) . . . . . . . . . . . . . . . . . .2-14
Selecting the Power Supp ly Voltage . . . . . . . . . . . . . . . . . . . . . . . . . .2-17
Inst alling ONline Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-19
Connecting Network Cables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-19
Power Up and Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-20
Fan Operation Verification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-21
Power Supply Operation Verification . . . . . . . . . . . . . . . . . . . . . .2-21
Technical Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-25
Where To G o F r om Here . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-26
Chapter 3 — Maintenance
Routine Maint enance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
Replacing the Power Supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-2
Replacing the Fan Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-7
ONline Module Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-9
Other System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-9
Appendix A — Specifications
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Environmental . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-1
Mechanical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Power Source . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Regulatory Compliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-2
Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . A-3
vi ONline 17-Slot System Concentrator Installation and Operation Guide
Page 7
Appendix B — Slot Usage Chart Appendix C — Technical Support
On-line Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-1
Email Technical Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C- 2
World Wide Web Site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-2
Support from Your Network Supplier . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-2
Support from 3Com . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-3
Returning Products for Repair . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-4
Accessing the 3 Com MIB . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-4
3Com Tec hnical Publicat ions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .C-5
Index
ONline 17-Slot System Concentrator Installation and Operation Guide vii
Page 8
viii ONline 17-Slot System Concentrator Installation and Operation Guide
Page 9
Figures
Figure 1-1. Multiple 17-Slot Concentrator Environment . . . . . . . . . . . .1-2
Figure 1-2. ONline System Concentrator Rear View . . . . . . . . . . . . . . .1-3
Figure 1-3. ONline System Concentrator Front View . . . . . . . . . . . . . . .1-4
Figure 1-4. Modular ONline Configuration . . . . . . . . . . . . . . . . . . . . . .1-5
Figure 1-5. ONline System Concentrator Using Multiple Networks . . . .1-7
Figure 1-6. Redunda nt Cable Lin k Configuration . . . . . . . . . . . . . . . .1-10
Figure 1-7. Backup Concentrator Configuration . . . . . . . . . . . . . . . . .1-11
Figure 2-1. ONline System Concentrator Shipping Box Contents . . . . . .2-2
Figure 2-2. Rack Mount Positions . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-9
Figure 2-3. Cable Tray Installation i n Rack . . . . . . . . . . . . . . . . . . . . .2-10
Figure 2-4. Attaching the Rack Mount Flanges . . . . . . . . . . . . . . . . . .2-12
Figure 2-5. Chassis Mounted in Rack . . . . . . . . . . . . . . . . . . . . . . . . .2-13
Figure 2-6. Removing Fan Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-14
Figure 2-7. U npluggi ng the Fan Unit . . . . . . . . . . . . . . . . . . . . . . . . .2-15
Figure 2-8. Power Su pply Conne ctors . . . . . . . . . . . . . . . . . . . . . . . . .2-16
Figure 2-9. Installing the B ackup Power Supply . . . . . . . . . . . . . . . . .2-16
Figure 2-10. Inst alled Backup Powe r Supply . . . . . . . . . . . . . . . . . . . . .2-17
Figure 2-11. Setting the Voltage Selector Switch . . . . . . . . . . . . . . . . .2-18
Figure 2-12. Networ k Cable Connectio ns . . . . . . . . . . . . . . . . . . . . . . .2-20
Figure 3-1. Removing the Power Su pply . . . . . . . . . . . . . . . . . . . . . . . .3-3
Figure 3-2. U npluggi ng the Power Supply . . . . . . . . . . . . . . . . . . . . . .3-4
Figure 3-3. Power Supply Plugs in ONline System Concentrator . . . . . .3-5
Figure 3-4. Backup Power Supply Install ed . . . . . . . . . . . . . . . . . . . . . .3-6
Figure 3-5. Removing the Fan Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-7
Figure 3-6. U npluggi ng the Fan Unit . . . . . . . . . . . . . . . . . . . . . . . . . .3-8
Figure 3-7. Fan Unit Install ed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-9
ONline Ethernet 10BASE- FL Module Installation and O peration Guide ix
Page 10
x ONline Ethernet 10BASE-FL Module Installation and Operation Guide
Page 11
Tables
Table 2-1. Steps for Installing the ONline System Concentrator . . . . . .2-6
Table 2-2. Rack Mount Settings. . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-8
Table 2-3. Controller Module LEDs After Proper Power-Up . . . . . . . . .2-21
Table 2-4. Troubleshooting with Controller Module LEDs . . . . . . . . . .2-22
Table B-1. Concentrator Slot Usage Chart . . . . . . . . . . . . . . . . . . . . . .B-1
ONline Ethernet 10BASE- FL Module Installation and O peration Guide xi
Page 12
Page 13
How to Use This Guide
This guide explains how to install, operate, and manage the following 3Com ONli ne™ 17-Slot System Co ncentrators.
5017C 5017C with load sh aring 5017C-LS
Keep this guide near the ONline System Concentrator

Audience

This guide is intended for the following people at your site:
Network manager or administrator Hardware installer
ONline 17-Slot System Concentrator Installation and Operation Guide xiii
Page 14

Structure of This Guide

This guide contains the following chapters: Chapter 1, Introduction – Introduces the principal features of the ONline
System Concentrator and provides a front and rear view of the unit. Chapter 2, Installation and Troubleshooting – Provides illustrated
procedures for installin g and verify ing the operation of the 17-Slo t ONline System Concentrator.
Chapter 3, Maintenance – Describes how to order and replace serviceable parts on the ONline Syste m Concentrator. These parts include the power supply, backup power supply, and fan units.
Appendix A, Specifications – Provides product dimensions, power requirements, and other specifications for the unit.
Appendix B, Slot Usage Chart – Provides a chart to record informatio n about which modules are installed in the 17 concentrator slots.
Appendix C - Technical Support – Lists the various methods for contacting the 3Com technical support organization and for accessing other product support services.
Index
ONline 17-Slot System Concentrator Installation and Operation Guide xiv
Page 15

Document Conve ntions

The following document conventions are used in this manual:
Convention Indicates Example
Courier text User input In the Agent Information Form,
enter MIS in the New Contact field.
System output After pressing the A pply
button, the sy stem displays the message Transmi tt in g da ta .
Bold command string
Italic text in braces User-substituted
Capitalized text in plain brackets
Italics Text emphasis,
Path names Before you begin, read the
identifiers
Keyboard entry by the user
docu me nt titles
readme.txt file located in /usr/snm/agents.
Use t he following command to show port details:
SHOW PORT {
Type your password and press [ENTER].
Ensure that you press the Apply button after you add the new search parameters.
slot
.all} VERBOSE
ONline 17-Slot System Concentrator Installation and Operation Guide xv
Page 16
Convention Indicates Example
Note: A Note. The
Caution: A Caution. A
Warning: A Warning. A

Related Docu me nts

This section provides information on supporting documentation, including:
3Com Documents
information is important
condition may damage software or hardware
condition may threaten personal safety
Note: Use STP lobe cables for yo ur s yste m.
Caution: Do not put your installation diskettes on a magnetic surface. This may damage the diskettes.
Warning: Wear eye protec tion when performing these maintenance procedures.
Reference Documents
xvi ONline 17-Slot System Concentrator Installation and Operation Guide
Page 17

3Com Documents

The following documents provide additional information on 3Com products:
17-Slot ONline System Concentrator Installation and Operation Guide – Explains how to install, operate, and manage the 3Com ONline
17-Slot Syste m Concentrator (Models 5017 C-LS and 5017C with load sharing) .
6-Slot ONline System Concentrator Installation and Operation Guide – Explains how to install, operate, and m anage the 3Com ONline
6-Slot System Concentrator. ONline To ken Ring Management Module User’s Guide – Explains how to
install, operate, and use the 3Com ONline Token Ring Management Module.
ONline Management Commands Guide – Provides an alphabetized reference resource describing all ONline management commands.
For a complete list of 3Com documents, contact your 3Com representative.

Reference Documents

The following documents supply related background information:
Case, J., Fedor, M., Scoffstall, M., an d J. Davin, The Simple Network Management Protocol, RFC 1157, University of Tennessee at Knoxville,
Performance Systems International and the MIT Laboratory for Computer Science, May 1990.
Rose, M., and K. McCloghrie , Structure and Identification of Management Information for TCP/IP-based Internets, RFC 1155,
Performance Systems International and Hughes LAN Systems, May 1990.
ONline 17-Slot System Concentrator Installation and Operation Guide xvii
Page 18
Page 19
Introduction
1
This chapter briefly describes the cap abilities and operation of the 3Com ONline™ System Concentrator. Chapter 2 provides important information for installing modules and verifying their operation.
If you are uncertain about legal network configurations when using the ONline System Concentrator, refer to the appropriate ONline media module manual.

Introducing the ONline Sys tem Conc e ntrat or

The ONline System Concentrator is a modular, fault-tolerant pl atform for facility networks. The concentra tor has a unique TriChannel® architecture that allows it to run three network protocols concurrently. It is capable of running Ethernet, Token Ring, and FDDI networks - all in the same concentrator.
Ethernet connectivity is available on a variety of major cable types including:
Fiber optic ca ble Unshielded and Shielded twisted pair wire Thin and Th ick coaxial cable
Introduction 1 - 1
Page 20
Figure 1-1 shows a mod el syst em that i nclud es ea ch of thes e cable t ypes. I n this diagram, an ONline Ethernet Repeater Module is connected to a 10BASE5 segment via an AUI cable and a transceiver. Also shown is the physical connection between an ONline Ethernet Fiber Module and a 10BASE2 segment, via a fibe r cable, fiber media access unit, and IEEE repeater. Unshielded and shielded twisted pair connections to-the-desk are also included in this sample configuration.
Figure 1-1. Multiple 17-Slot Concentrator Enviro nment
Network segments attach to the concentrator through media modules you install into the chassis. The ONline Controller Module, which provides re-timing and re-transmission of received signals, must be installed in one of the concentrator's seventeen slots. The remaining sixteen slots can be configured with any combination of media modules.
1 - 2 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 21

Back Panel

A power supp ly and DC fan unit are installed when you receive your concentrator. There is an On/O ff switch on the power supply. The power supply should be powered down when you install or remove it. Note that there is no need to power down the concentrator for installation or removal of the media modules. Add itionally, you can repl ace the fan unit with an optional backup power supply to provide power redundancy.
Figure 1-2. ONline System Concentrator Rear View

Front Panel

The concentrator is shipped with 15 blank faceplates and two empty slots. The two slots are left empty because you must install the ONline Controller Module and a t least one media module for the concentrator to be functional. As you add media modules to your unit, remove blank faceplates to provide additional slots for the new modules.
Introduction 1 - 3
Page 22
Figure 1-3. ONline System Co ncentrator Front View
A cable tray is provided with the concentrator so that c ables you attach to the media m odules can be run under the unit and out the back where they will not be in the way. A rack mount kit is also provided for the concentrator and for the cable tray so you can rack mount the enti re unit.

ONline System Concentrator Features

This section describes the major features of the ONline System Concentrator. The features include:
Modular Desi gn TriChannel® Architecture Port-Switching Technology Fault-Tolerance Capabiliti es Hot Swapping of Media Modules Synchronous Backplane
1 - 4 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 23

Modular Design

The ONline Concentrator's modular design lets you add different media modules (such as fiber, twisted pair, and coaxial) in any combination to connect different types of media segments. A possible configuration is shown in Figure 1-4. You can link segments of different protocols using Token Ring, FDDI, bridging and routing modules.
Every concentrator requires one Controller Module that controls communications between all modules. In addition, a Network Management Module provides sophisticated monitoring and control of the modules in the concentrator. As a rack-mounted unit, the ONline Concentrator can be connected to patch panels to simplify and manage your network cables.
Figure 1-4. Mod u lar ONline Config u ration
Introduction 1 - 5
Page 24

TriChannel Architecture

The ONline System Concentrator's TriChannel architecture lets you run Ethernet, Token Ring, and FDDI networks, al l in the same concentrator. This allows a single ONline unit to do the work of three conventional hubs. You can also run multiple Ethernet networks or mixture of Ethernet, Token Ring, and FDDI networks in any combination you want. This architecture is shown in Figure 1-5.
Any module you add to the concentrator can be assigned to any of three networks on its backpl ane and can be easily moved to another backplane network using either an on-board dip switch or remote network management.
Additionally, any module can be set to “isolated” mode whereby it acts as an isolated network - not connected to the concentrator backplane. This mode lets you isolate users from the main network. This can be useful for security or as a temporary situa tion to preve nt traffic from c ontaminating the network (for example, if some users are conducting network tests or running at very high loads.)

Port-Switching Technology

Available port-switching modules allow you to assign any port to any backplane network using a network management command. This allows you to perform moves, adds, and changes at the network console, saving costly and time-consuming trips to the wiring closet. It also allows you to get additional bandwidth on demand by switching users to lower volume networks during peak traffic periods.
1 - 6 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 25
Figure 1-5. ON line System Co ncentrator Using Multiple Networks
Introduction 1 - 7
Page 26

Fault-Tolerance Capabilities

The ONline System Concentrator provides fault tolerance through redundant features, such as an optional backup power supply, backup controller module, redundant cable links , and backup concentrator capability.

Backup Power Supply

An optional second power supply can be used to backup the primary power supply in case of a power failure. Should the primary power supply fail, the backup power supply takes over automatically. In addition, once a backup power supply has been installed, you ca n replace a faile d primary power supp ly without shutting down the system.

Load Sharing

The load-sharing func tion provi des uninterrupted power to modules installed in a concentrator with two power supplies. If the active power supply fails, the concentrator automatically switches to the other power supply without interrupting the network.
The following ONline 17-Slot System Concentrators have load-sharing capability:
Model 5017C-LS Model 5017C with load-sharing upgrade
To determine if your model 5017C concentrator has load-sharing hardware, check the rear of the concentrator chassis for a label reading “Upgraded w/30-0 286.” If this label is present, the concentrator has received the load-sharing upgrade.
In order for load shari ng to work, the Fault-Tolerant Controller Module model 5000M-RCLS must be installed. This co ntroller monitors the concentrator's load-sharing function.
1 - 8 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 27

Backup Controller Module

The controller is vital to the system because it performs important functions including:
synchronizing all modules monitoring concentrator conditions (temperature, power supply
status, etc.)
recognizing failures clocking and timing to the ONline Concentrator backplane
By using two 3Com Fault-Tolerant Controller Modules (5000M-RCLS) in your concentrator you can protect these critica l tasks if a controller fails.
Note: You cannot use the 5000M-RCTL or 5000M-CTL controller
in a load-sharing conc entrator (Model 5017C-LS or Model 5017C with load-sharing upgrade).

Redundant Cable Links

Cable breaks or failures are the most common problem in any network. Using the ONline Ethernet Fiber Module in your ONline System Concentrator enables you to implement full cable redundancy for your network's backbone. Thereafter, if one port should fail, or if a cable is disconnected or cut, the b ackup port will take over in 100 milliseconds. A sample redundant network connection is shown in Figure 1-6.
Introduction 1 - 9
Page 28
Figure 1-6. Redundant Cable Link Configuration

Backup Concentrator

A second concentrator or 3Com Fiber Ethernet Star Coupler may be used to backup the primary concentrator in a star-wired network. This provides full fault t olerance for a backbone c able plant.
1 - 10 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 29
Figure 1-7. Backup Concentrator Configuration

Hot Swapping of Media Modules

Media modules can be added, removed, and reconfigured without powering down the ONlin e System Conc entrator or affecting the rest of the network. This means that you can add entire new segments or make minor system adjustments during normal working hours withou t interrupting the entire system.
Introduction 1 - 11
Page 30

Synchronous Backplane

The ONline System Concentrator backplane is designed with all passive components to achieve the maximum reliability. The synchron ous backplane allows the concentrator to be connected (using the 3Com ONline Fiber Module) without the need for internal repeaters. This avoids the limitations of the Ethernet four-repeater rule and lets you connect up to 23 concentrators serially, without the need for an intervening repeater or bridge.
1 - 12 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 31
2
This chapter describes how to install the ONline System Concentrator, how to install ONline modules, and how to install the optional backup power supply into y our ONline uni t.
Warning: Do not turn the concentrator's power supply switch on until
Installation and
Troubleshooting
you are instructed to do so in the following procedures.
The information and procedure s contained in this chapter are to be used only by service personnel to install and maintain the ONline 17-Slot System Concentrator.

Contents of the Shipping Box

The ONline System Concentrator is a chassis that enables installation of media modules for network connection. The unit is shipped complete with the following parts:
Chassis containing:
singl e power supply – fan unit
Installation and Troubleshooting 2 - 1
Page 32
15 blank faceplates
Chassis rack mount kit Cable tray with rack mount kit ONline Fault-Tolerant Controller Module and ONline Fault-Tolerant
Controller Module Ins tallation Guide
Power cord This ONline System Concentrator Installation and Operation Guide
The pow er cord and hardware items are shown in Figure 2-1.
ONline System
Power Cord
Cable Tray Rack Mount Kit
Concentrator
Rack Mount
Controller
Figure 2-1. ONline System Concentrator Shipping Box Contents
2 - 2 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 33
If an y o f t h es e it ems are d amaged or mi ssing, c on ta ct your l oc al s up plier or a 3Com se rvice representative.
3Com suggests you keep the carton and anti-static shielding ba g in which your unit was shipped in case you later want to repackage the unit for storage or shipment.
We also suggest that you record the serial number of your Controller Module. We have provided a log for this and other information specific to modules under the Slot Usage Char t in Appendix B nea r the end of this manual.

FCC Regulations

FCC regulations require that blank faceplates cover slots that are not being used. To comply with this regulation, the concentrator is shippe d with 15 blank faceplates and two empty slots. These two slots are left empty becau se t he ONl in e Con tro ller Modu le an d at l ea st one media modu le mu st be installed for the concentrator to be functional.
Caution: Do not turn the concentrator's power supply switch on
until you have:
verified tha t the selected site meets the installation requirements
outlined in the following pages
completed each of the steps outlined in Table 2-1.
Be sure to verify that the correct voltage level has been
selected. An improper setting may damage the power supply.
Installation and Troubleshooting 2 - 3
Page 34

Site Selecti on Considerations

The concentrator can be placed almost anywhere within your company, including offices and computer rooms. In general, we recommend installation in a wiring closet. The unit has been designed for rac k mounting and come s with all the necessary hardware.

Location Requirements

The area where you install the ONline System Concentrator must meet the following conditions:
Temperature b etween 0° to 50° C (32° to 122° F) Relative humidity less than 95%, non-condensing AC power source withi n 6 feet (2 meters). Note that for installation
to have true backup power, two independent AC power sources are required
The tabl e or rac k wh er e the un it i s in st a ll ed sho ul d b e le ve l and n ot i n
direct sunlight or in an excessively dusty location

Ventilation

The concentrator fan units draw air in through the front and bottom of the chassis and exhausts air out the back. Make sure there are at least 6 inches (15 centimeters) between the fan vents at the back of the unit and the nearest surface to allow adequate airflow for cooling. This minimum distance is also required for access to the rear of the unit for maintenance.
The cable tray that comes standard with the concentrator helps prevent a tangle of cables at the front of the concentrator and also permits the required airflow to the unit. Make sure the cable tray is installed below the unit correctly before installing the concentrator.
2 - 4 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 35
Caution: The concentrator should have two fans running at all
times to cool the unit properly. You should therefore have: (A) a power supply (with b uil t-in fan) and a fan unit installed or (B) two power supplies installed.

Power Requirements

3Com recommends using a 15 ampere electrical wire (branch circuit) to supply power to the concentrator. This circuit must be grounded to a safety ground (protected earth ground), not to neutral that carries current back to the transformer. Do not use the electrical conduit pipe as the only means of grounding.

Rack Mount Installation Requirements

For rack mount installation of the ONline System Concentrator you need a standard nineteen-inch EIA config ured rack. The rack and its environment also should meet the following specifications:
If the rack has an open back and sides:
the rack must be bolted to the floor – the top of the rack may need to be braced to the wall
the rack must be grounded there must be 10.5" (26.7 cm) (6U) of vertical space in the rack for
each 17-slot concentrator
the unit location in the rack must be less than 6 feet (2 meters) from
the nearest AC outlet
patch panels should already be installed in the rack for easier cable
management
Installation and Troubleshooting 2 - 5
Page 36

Table Top Installation Requirements

For table top or shelf mount installation of the ONline System Concentrator you must make sure the table or shelf can suppo rt 100 pounds (45 kg) for a fully loaded 17-slot conc entrator. (The concentrator itself, fully loaded and with cable tray, weighs almost 75 pounds/34 kilograms.) The table/shelf als o must be less than 6 feet (2 me ters) from the ne arest AC outlet.
To ensure proper airflow to the un it, you should leave at least 1.75" (4.45cm) of space below the concentrator (provided by the installed rubber feet) and by installing the cable tray below the concentrator.

Installation

Table 2-1 prov id es a qui ck d es cr ipt i on of th e s tep s yo u m ust f ol lo w to i ns tall the ONline System Concentrator as well as reference to the section in this manual where the step is described. It is important that you perform the steps in the order ind icated, noting that Step 3 is optional.
Table 2-1 . Steps for Installing the ONline System Concentrator
Step Action Section
1 Install the cable tray into a
rack or place it on a table top.
2 Install the concentrator unit
into a rack or place it on a table top.
3 Install the backup power
supply in the concentrator.
2 - 6 ONline 17-Slot System Concentrator Installation and Operation Guide
Installing the Cable Tray”
Installing the ONline System Concentrator
Installing the Backup Power Supply (Optional)”
Page 37
Table 2-1 . Steps for Installing the ONline System Concentrator
(Continued)
4 Set up the power supply. Selecting the Power Supply
Voltage
5 Install the ONline Controller
Module in the concentrator.
6 Inst all media modules in the
concentrator.
7 Connect the network
cables to the media modules.
8 Power up all network
devices and verify the installation.

Installing the Cable Tray

The cable tray that comes standard with the concentrator helps to manage the cables that run from the front of the unit so they are fed under the unit and out through the back. The tray also provides the required space between the bottom of the unit and the next device in the rack (or the top of the table) so there is adequate air flow to cool the unit.
Installing ONline Modules”
Installing ONline Modules”
Connecting Network Cables”
Power Up and Verification”
Caution: If you choose not to use the c able tray beneath your
unit, you must ensure that 1 3/4" (4.45 cm) of space is open below the ONline unit to ensure adequate incoming airflow (provided by the installed feet).
Installation and Troubleshooting 2 - 7
Page 38

Cable Tray Rack Mounting

To install the concentrator in a rack , first install the cable tray and then install the concentrator above the tray. The cable tray can be mounted in four separate configurations in your rack depending on your preference. The options are described in Table 2-2 and shown in Figure 2-2.
Table 2-2. Rack Mount Settings
Option Rack Setting Function
1 Flush Mount Flush mounts the unit to the front of
the rack.
2 1/2" Recess Recesses the unit 1/2" (1 .3 cm) from
the front of the rack.
3 2 1/8" Recess Recesses the unit 2 1/8" (5.4 cm) in
a rack.
4 2 3/4" Rec ess Recesses the unit 2 3/4" (7.0 cm) in a
rack.
Note: The ONline System Concentrator is 18.3" (46.5 cm) deep.
Some shallow rack cabinets may only allow you to flush mount the unit. In addition, make sure you mount the unit so that cables connected to the media modules hav e enough room to bend (especially important for fiber cables).
2 - 8 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 39
Figure 2-2. Rack Mount Po sitions
Follow the steps below to mount the cable tray in yo ur rack:
1. Attach the two rack mount flanges to the cable tray in the position you want as shown in Fi gure 2-2 using th e eight (8) provided 8-32 x 1/4" flathead screws - four per side.
Note: You must tighte n the screws completely to be fl ush
with the rack mount flanges so the tray will fit in the rack.
2. Select a vacant position in the rack that is at least 10.5 inches (26.7 cm) from the top of the rack or the next higher unit in the rack.
3. Install the provided clip nuts onto the front of the rack where you want to attach the tray.
Installation and Troubleshooting 2 - 9
Page 40
Note: The function of the clip is to hold the nut in place behind
the rail. Be sure to install the clip onto the rail so that the nut is centered behind the hole through which you plan to insert the screw.
4. Place the tray in the rack and attach to the clip nuts through the front of the rack using the four (4) 10-32 x 5/8" truss-head screw s and as shown in Figure 2-3.
Figure 2-3. Cable Tray Installation in Rack

Cable Tray Table Mounting

To install the concentrator on a table top or on a shelf, place the cable tray on the surface first and then place the concentrator on top of the tray. Note that the four rubber feet must be installed on the concentrator before it is placed on the table top or on top of the cable tray. The feet fit into the four holes in the cable tray, which prevents the concentrator from moving.
2 - 10 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 41

Installing the ONline System Concentrator

The ONline System Concentrator can be placed on top of a table or a shelf, or mounted in a rack. Make sure the cable tray has been install ed first on the table or in the rack (or that 1 3/4" (4.5 cm) of vertical space has been provided below the unit for air flow) an d that the loc ation meets all the environmental considerations specified earlier in this chapter.
Caution: 3Com recommends that two people install the unit
since it weighs 38 lbs (17 kg) with one power supply and 46 lbs (24 kg) with the backup po wer supply installed.
3Com also recommends installing the backup power supply prior to rack mounting the unit (see the section titled Installing the Backup Power Supply later in this chapter). In some rack cabinets, the rear of the c abinet may interfere with installation or removal of the power supply and fan.

Rack Mounting the ONline System Concentrator

The ONline System Concentrator can be mounted in four different configurations in the rack. Use the same rack settings for both the cable tray and the concentrator. If you are not installing the cable tra y in the rack, you should select the concentrator mount setting at this time. Refer to Table 2-2 and Figure 2-2 in the “Cable Tray Rack Mounting” section for specifics about the four mounting settings.
Follow the steps below to mount the concentrator in your rack:
1. Attach the two rack mount flanges to the ONline concentrator unit in the position you want as shown in Figure 2-4 using the eight (8) provided 8-32 x 1/4" flathead screws - four per side.
Installation and Troubleshooting 2 - 11
Page 42
Caution: You must use the supplied 8-32 x 1/4" screws to attach
the rack mount flanges. A longer screw may extend too far into the ONline chassis and disrupt the installation of modules.
Figure 2-4 . A ttaching the Rack Mount Flanges
2. Install the provided clip nuts onto the front of the rack where you want to attach the unit. See Figure 2-3 for proper orientation.
3. Slide the unit in the rack above the installed cable tray until the rack mount flanges seat flush to the front of the rack.
Caution: While mounting the concentrator, do not leave the unit
resting on the mounted ca ble tray since the c able tray rack mounts may not support a fully-loaded concentrator.
4. Secure th e unit to the rack with the four (4) 10-32 x 5/8" truss-head screws as shown in Figure 2-5.
2 - 12 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 43
Figure 2-5. Chassi s Mounted i n Rack

Table Top Mounting the ONline Concentrator

You can set the ONline Concentrator directly on a table top or shelf that can support at least 100 pounds (45 kg). A fully load ed concentrator weigh s ab out 75 l bs ( 3 4 k g) . 3C om reco mme nd s yo u s et t he u nit on top of the ONline cable tray as the cable tray provides a central area for cable management and provides the required 1 3/4" (4.5 cm) of clearance for sufficient air flow. Regardless of whether the cable tray is used or not, the four (4) rubber feet must remain on the bottom of the unit.
If the cable tray is used, place the ONline unit on top of the cable tray and insert the rubber feet from the unit into the holes in the cable tray, which stabilizes the unit on the tray.
If the cable tray is not used, place the unit on the table or shelf.
Installation and Troubleshooting 2 - 13
Page 44

Installing the Backup Power Supply (Optional)

Install the backup power supp ly in the ONline System Concentrator (if ordered). This power sup ply provides p ower redundancy if the primary power supp ly should fail. Skip this section if you do not have a backup power supply.
To install the backup power supply, you must first remove the fan unit from the power supply slot in the back of the unit. Follow the steps below to install the backup power supply:
1. Remove and save the four screws that attach the fan unit to the rear of the concentrator as shown in Figure 2-6.
Figure 2-6. Removing Fan Unit
2. Carefully remove the fan unit and disconnec t the fan unit wiring harness from the connector inside the base of the ONline u nit as shown in Figure 2-7. Save this fa n unit in case a power s u pp ly s h ou ld fail at a later ti me and you need to reinstall the fan unit.
2 - 14 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 45
Figure 2-7. Unplugging the Fan Unit
Before you install the new power supply, chec k the label on the inside of the power supply bay that explains where each of the seven power leads from the power supply are connected in the concentrator chassis.
Power leads labeled P7, P8, and P9 fit in the back three raised connectors and they are “keyed” so they can be inserted only in the correct connector and only in one direction. Power leads labeled P10, P11, P12, and P13 fit in the front four recessed connectors and can be ins erted in only one direction. These connectors are shown in Figure 2-8.
Installation and Troubleshooting 2 - 15
Page 46
Figure 2-8. Power Supply Conne ct ors
3. Hold the backup power supply in one hand while using your other hand to plug in the seven (7) le ads from the power supply as shown in Figure 2 -9.
Figure 2-9. Installing the Backup Power Supply
2 - 16 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 47
4. Make sure the cable is pushed up to the right side and then slide the power supply into the b ack of the concentrator as shown in Figure 2-10. Then fasten with the four (4) s crews you removed earlier from th e fan unit.
Figure 2-10. Installed Backup Power Supply

Selecting the Power Supply Voltage

Before you plug in the power cord to the power connector on the power supply (and to the backup pow er supply, if you have one), you must verify that the voltage selector is correctly set for your country line voltage.
Caution: An incorrect voltage setting can damage the power
supply.
1. Set the power switch to the Off (O) position.
Installation and Troubleshooting 2 - 17
Page 48
2. Use a flat-blade screwdriver to move the voltage selector switch so the setting that is appropriate for your country's line voltage is showing: 100/120 Volts or 220/240 Volts, as shown in Figure 2-11.
Figure 2-11 . Setting the Voltage Selector Switch
3. Plug in the power cord to the power conn ector on the ba ck of the concentrator and connect the other end to an outlet. If you installed a backup power supply, make sure that power cord is connected to an outlet on an independent circ uit from that used for the primary power supp ly.
The power receptacle on the concentrator is an approved IEC connec tor. Make sur e the power cord you u se is appr opr iat e for you r country line voltage:
For 100/120 Volt operation, use only a power cord rated for 10
Amps, 125 Volts.
For 220/240 Volt op eration, use only use a power cord rated for
10 Amps, 250 Volts.
2 - 18 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 49
Warning: DO NOT use a 3-to-2 pronged adapter at the outlet since
this may result in elec trical shock and does not provide adequate grounding.

Installing ONline Modules

Warning: Only service personnel should install ONline modules.
Install the ONline Controller Module in the concentrator as described in the ONline Controller Module Installation Guide provide d with the Controller Module.
Install any ONline media modules in the ONline System C oncentrator as described in the manual provided with each module. Note that you do not need to turn off the concentrator when installing additional modules to your co nce n trator.
Use the chart in Append ix B to label the location of each module in the concentrator. At least one m edia module must be installed along with the Controller Module to m ake the conc entrator functional.

Connecting Network Cables

Connect the network cables betw een conce ntrators, patch panels , and transceivers.
Installation and Troubleshooting 2 - 19
Page 50
Figure 2-12. Network Cable Connections

Power Up and Verification

This section tells how to power up the concentrator and verify that it is working correctly.
Switch the power supply O n/Off switch to the On (|) pos ition . The Power Supply LED(s) on the ONline Controller Module light when the
unit is powered up correctly. The verification procedure i s split into the following areas:
fan operation power supply operation netwo rk operation
2 - 20 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 51

Fan Operation Verification

To verify that the fan unit and the power sup ply fan are functio ning correctly you need to visually inspect the fan unit(s) on the rear of the concentrator to make sure they are turning and that nothing is blocking their path.

Power Supply Operation Verification

Verify that the LEDs on the Controller Module appear as defined in Table 2-3 to check the operation of the power supply.
Table 2-3. Controller Module LEDs After Proper Power-Up
LED Proper State
Primary Power On. Backup Power On. A backup power supply is installed.
Off. No backup power supply is installed.
Temperature (TEMP) Off.
Installation and Troubleshooting 2 - 21
Page 52
If any of these LEDs are not lit as shown in this chart, refer to Table 2-4 to troubleshoot the problem.
Table 2-4. Troubleshooting with Controlle r Module LEDs
LED State
Primary Power
Off The Primary
Steady Blinking
Possible Problem
Power LED is broken.
The primary power supply is not properly installed.
The primary power supply has failed.
Troubleshooting
Suggestions
Press the LED Test button to verify that the LED is working properly.
Reinsta ll the primary power supply and turn it on.
Verify that the outle t is supplying power.
Verify that the voltage selection switch is set to the correct position for your country's line voltage.
Verify that the power cord is plugged in at both ends and that the cord is appropriate for your country's line voltage.
Verify that the power switch is turned on.
Replace the power supply.
2 - 22 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 53
Table 2-4. Troubleshooting with Controlle r Module LEDs
(Continued)
LED State
Primary Power (cont.)
Steady blinking (cont.)
Two blinks, then a pause (in unison with Backup Power LED)
Possible Problem
The primary power supply is not properly installed.
The pow er load-sharing hardware is in an error state.
Troubleshooting
Suggestions
Reinsta ll the primary power supply and turn it on.
If a management mod ule is installed, the concentrator should recover automatically from this condition. If it doesn't, reset the concentrator using the RESET CONCEN TRATOR command. If this fails to correct the condition, turn both power supplies OFF, then ON again.
If a management mod ule is not installed, turn both power su ppli es OFF, then ON agai n.
Backup Power
Off The Backup
Power LED is broken.
The backup power supply is not properly installed.
Installation and Troubleshooting 2 - 23
Press the LED Test button to verify that the LED is working properly.
Reinsta ll the backup power supply and turn it on.
Page 54
Table 2-4. Troubleshooting with Controlle r Module LEDs
(Continued)
LED State
Backup Power (cont.)
Temp Blinking The
Steady blinking (cont.)
Two blinks, then a pause (in unison with Primary Power LED)
The backup power supply has failed.
The backup power supply is not properly installed.
The pow er load-sharing hardware is in an error state.
temperature in the concentrator is too high.
Possible Problem
Troubleshooting
Suggestions
See Prima ry Power LED suggestions for same State and Possible Problem (above).
Reinsta ll the backup power supply and turn it on.
See Primary Power LED
suggestions for same State and Possible Problem (above).
Verify tha t the fan units are working and nothing is blocking airflow from the front and bottom of the concentrator.
Active Off The module is
in standby mode.
2 - 24 ONline 17-Slot System Concentrator Installation and Operation Guide
Verify at least 1 3/4"of space below the concentrator for proper air flow.
Lower the temperature in the room.
Verify tha t the Standby LED is illuminated.
Page 55
Table 2-4. Troubleshooting with Controlle r Module LEDs
(Continued)
LED State
Standby Off The mod ule is
Blin king There is a
Possible Problem
The Active LE D is broken.
in active mode. The Stand by
LED is broken.
hardware failure in the Standby module.
Troubleshooting
Suggestions
Press the LED Test button to see if the LED is working.
Verify that the Active LED is illuminated.
Press the LED Test button to see if the LED is working.
Reset the module. If this action does not correct the probl em, install the module in another slot.
If necessary, replace the module and contact 3Com Customer Support Organiza tion. See Technical A s sis ta nc e to follow.

Technical As sist anc e

You can receive assistance for installing and troubleshooting the 17-Slot concentrator by calling your dealer or 3Com Customer Support. Be prepared to supply a representative with th e following information:
a description of the problem the steps you have taken to try and correct the problem
Installation and Troubleshooting 2 - 25
Page 56
the configuration of your concentrator the screen information reporting the SHOW DEVICE command (if you
have an ONline management module installed in the concentrator) Refer to Ap pendix C for in structions how to contac t Technical
Support for your product.

Where To Go From Here

Once you have made the necessary concentrator connections, and have verified that communication has been established between all segments connected to the concentrator, no further installation procedures are required. Chap ter 3, Maintenance, discusses what to do in the event that the fan unit or power supply needs to be repla ced.
2 - 26 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 57
3
This chapter describes routine maintenance designed to keep your ONline System Conce ntrator working at its best . It also explains how to replace a failed power supply o r fan unit.
This chapte r explains the fo ll owing maintenance procedures:
Maintenance
Routine Maintenance Power Supply Replacement Fan Unit Replacement ONline Module Maintenance Other System Components
Warning: There are no serviceable parts on either the power supply
or the fan unit. If either of these parts fail, remove them as described in this chapter and return them to your reseller or to 3Com Corporation. You sho uld keep replacemen t power supply and fan units at your site so they are available if needed.
Maintenance 3 - 1
Page 58

Routine Maintenance

You should inspect your equipment to make sure that all of the following are true:
all the blank faceplates are on the fans are running there are no obstructions to the ventilation on the concentrator the ONline Controller Module and media module LEDs are registering
correctly

Replacing the Powe r Supp ly

Both the primary and backup power supplies in the ONline System Concentrator are removed and installed in exactly the same manner. If a power supply should fail and switch over automatically to the backup power supply (optional) you can replace the failed power supply while the unit is operating - without disrupting network operation.
Caution: Improper installation of the power supply could
damage the power supply.
Follow the steps below to replace a power supply unit:
1. Switch Off the failed power supply, then unplug the power cord from both the wall and from the back of the power supply.
2. Remove and save the four screws that attach the power supply to the rear of the concentrator as shown in Figure 3-1.
3 - 2 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 59
Figure 3-1. Removing the Power Supply
3. Carefully pull the power supply out from the concentrator and disconnect the seven (7) power leads from the conne cto rs inside the base of the ONline unit as shown in Figure 3-2.
Maintenance 3 - 3
Page 60
Figure 3-2. Unplugging the Power Supply
Note: Before you install the new power supply, check the label on
the inside of the power supply bay that explains where each of the seven power leads from the power supply are connected in the concentrator chassis.
Power leads labeled P7, P8, and P9 fit in the back three raised connectors and they are “keyed” so they can be inserted only in the correct connector and only in one direction. Power leads labeled P10, P11, P12, and P13 fit in the front four recessed connectors and can be inserted in only one direction.
4. Pick up the new power sup ply and plug in the seven (7) power leads from the power supply as shown in Figure 3-3.
3 - 4 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 61
Figure 3-3. Power Supply Plugs in ONline System Concentrator
5. Make sure the cable is pushed up to the right side and slide the power supply into the back of the concentrator and fasten it with the four (4) screws you removed from the defective unit as shown in Figure 3-4.
Maintenance 3 - 5
Page 62
Figure 3-4. Backup Power Supply Installed
6. Set the voltage selection switch on the back of the new power supply to the same setting as the old power supply (or as explained in the “Selecting the Power Supply Voltage” section in Chapter 2) and turn the power swit ch to the Off (0) position.
7. Plug in the power cord to the powe r supply and to the wall outlet, then turn the power switch to the On (|) position.
8. Check the power supply LEDs on the controller module to verify that the new power supply is working correctly. Make sure the fan on the power supply is running.
3 - 6 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 63

Replacing the Fan Unit

A fan installed in either the left or right bays is removed or installed in exactly the same manner as the power supply. Follow the steps below to replace a fan unit:
Caution: The concentrator must have two fans running at all
times to cool the unit. This is achieved through the power supply fan and the fan uni t that come standard with the concentrator, or by having two power supplies installed.
1. Remo ve and save the four screws that attach the fan to the rear of the concentrator as sh own in Figure 3-5.
Figure 3-5. Remov ing the Fan Unit
Maintenance 3 - 7
Page 64
2. Carefully pull the fan unit out from the concentrator and disconnect the wiring harness from the plug inside the base of the ONline unit as shown in Figure 3-6.
Figure 3-6. Unplugging the Fan Unit
3. Pick up the new fan unit and plug the fan power lead in the same connector in the base of the ONline unit from which you removed the old fan (plug P0).
4. Slide the new fan unit into the back of the concentrator and fasten it to the unit with the four (4) screw s you removed fro m the defective unit as shown in Figure3-7.
3 - 8 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 65
Figure 3-7. Fan Unit Installed

ONline Module Maintenance

Refer to the ONline installation guides that come with the modules for installation and operation i nformation.

Other System Components

For maintenance other than hot swap of power supply, fan, and modules described previously in this section, the following applies:
Caution: This unit may have one or two power supply cords.
Disconnect all power supply cords before servicing to avoid electrical shock.
Maintenance 3 - 9
Page 66
Vorsicht: Dieses gerät hat eine oder zwei netzverbindungen. Vor
wartung des gerätes alle netzstecker ziehen um elektroschock zu vermeiden.
3 - 10 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 67
A

General

Network Protocols Sup ported:
Ethernet/IEEE 802.3 over various media IEEE 802.5 Token Ring over various media ANSI FDDI

Environmental

Operating te mp erature: 0° to 50° C (32° to 122° F)
Specifications
Storage temperature: -30° to 65° C (-22° to 149° F) Operating humidity: less than 95%, non-condensing
Specifications A - 1
Page 68

Mechanical

Dimensions: 17.5"W x 18.3"D x 8.75"H (44.5 cm x 46.5 cm x 22.2 cm) Weight: unloaded, with one power supply: 38 lb. (17 kg.)

Power So urce

90-132 VAC, 6 Amps 180-264 VAC, 3 Amps, 47-63 Hz 325 Watts 1700 BTU/hr
unloaded, with two power supplies: 46 lb. (21 kg.) loaded, with two power supplies: 75 lb. (34 kg.)

Regulatory Compliance

Safety: UL, CSA, and TUV certified. Emissions: FCC/A, VDE/B, and VCCI/1 certified.
A - 2 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 69

Accessories

Cable Management Tray (5000CT): 17.5"W x 18.3"D x 1.75"H
Rack-Mount Kit (5017RM): 2.5 lb. (1.2 kg.) Backup Power Supply (5017PS-325): 8 lb. (3.6 kg.) Front Cover Panel (5017FC): .5 lb. (.23 kg.)
(44.5 cm x 46.5 cm x 4.5 cm) 8 lb. (3.6 kg.)
Specifications A - 3
Page 70
Page 71
B
Slot Usage Chart
The ONline System Concentrator has seventeen slots, sixteen of which are available slots for installing media modules (one slot is occupied by the ONline Controller Module). The slot on the far le ft is slot numb er 1 and runs to slot 17 on the far right. Use the chart on the next two pages to keep track of the following:
which module is installed in each slot which network (channel) each module is set for (or if it is isolated) any general remarks, such as module serial number or module
specific configuration settings
Store any oth er information on this chart tha t you think wi ll be helpful when ad ding new modu les or when di ag nosing network que stions.
Table B-1. Concentrator Slot Usage Chart
Slot
1
2
Module
Type
Network
or Isolated)
(#
Remarks
Slot Usage Chart B - 1
Page 72
Table B-1. Concentrator Slot Usage Chart (Continued)
Slot
3
4
5
6
7
8
Module
Type
Network
or Isolated)
(#
Remarks
9
10
11
12
B - 2 ONline 17-Slot System Concentrator Installation and Operation Guide
Page 73
Table B-1. Concentrator Slot Usage Chart (Continued)
Slot
Module
Type
Network
or Isolated)
(#
Remarks
13
14
15
16
17
Slot Usage Chart B - 3
Page 74
Page 75
Technical Support
C
3Com provides easy access to technical support information through a variety of services. This appendix describes the following services:
On-line Technical Services Support from Your Network Supplier Support from 3Com Returning Products for Repair

On-line Technical Support

3Com offers worldwide product support through the followin g on-line systems:
Email Technical Se rvice World Wide Web Site
Technical Suppo rt C - 1
Page 76

Email Technical Support

You can contact the Integrated Systems Division (formerly Chipcom) on the Internet for technical support using the e-mail address techsupp@chipcom.com.

World Wide Web Site

You can ac cess the latest networking information on the 3Com World Wide Web site by entering our URL into your Internet browser:
http://www.3Com.com/
This service features news and information about 3Com products, customer serv ic e and support, the 3Com latest news releases , selected articles from 3TECH™, the 3Com award-winning technical journal, and more.
You can contact the Integrated System s Division o n the World Wide Web by entering our URL into your Internet browser:
http://www.chipcom.com/
There are li nks between both WWW page s to view informatio n from all 3Com divisions.

Support from Your Network Supplier

If additional assistance is required, contact your network supplier. Many suppliers are authorized 3Com service partners who are qualified to provide a variety of services, including network planning, installation, hardware maintenance, application training, and support services.
C - 2 ONline 17_Slot System Concentrator Installation and Operation Guide
Page 77
When you contact your network supplier for assistance, have the following information ready:
Diagnostic error messages A list of system hardware and software, including revision levels Details about recent configuration changes, if applicable
If you are unable to contact your network supplier, see the following section on how to co ntact 3Com.

Support from 3Com

If you are unable to receiv e support from your network supplier, technical support contracts are a va il able from 3Co m.
For direct access to customer service for Integrated Systems Division products (formerly Chipco m) in:
U.S.A. and Canada - call (800) 724-2447 Asia Pacific - call (508) 787-5151 Europe - Refer to table below
Country Telephone Number Co untry Telephone Number Belgium 0800 71429 Netherlands 06 0227788 Denmark 800 17309 Norway 800 11376 Finland 0800 113153 Spain 900 983125 France 05 917959 Sweden 020 795482 Germany 0130 82 1502 U.K. 0800 966197 Ireland 1 800 553117 U.S. 800 876-3266 Italy 1678 79489
Technical Suppo rt C - 3
Page 78
For access to customer service for all 3 Com products, call (800) 876-3266. You can also contact the Integrated Systems Division (ISD) on the Internet
by using the e-mail address techsupp@chipcom.com.

Returning Produc ts for R epair

A product sent directly to 3Com for repair must first be assigned a Return Materials Authorization (RMA) number. A product sent to 3Com without an RMA number will be returned to the sender unopened, at the sender’s expense.
To obtain an RMA number for Integrated Systems Division products (formerly Chipcom ), use the following numbers .
Country Telephon e Number Fax Number U.S. and Canad a (800) 724-2447 (508) 787-34 00 Europe (44) (1442) 275860 No Fax Asia Pacific (508) 787-5296 (508) 787-3400

Accessing the 3Com MIB

The 3Com Management Information Base (MIB) for the Integrated Systems Division desc ribes commands that enable you to manage 3Com SNMP-based products. The MIB is available over the Internet on an anonymous FTP server. Updates to these MIBs are released as new 3Com products are introd uced.
To access Internet versions:
1. FTP to ftp.chipcom.com (151.104.9.65).
2. Enter the login name anonymous.
C - 4 ONline 17_Slot System Concentrator Installation and Operation Guide
Page 79
3. Enter your full Internet e-mail address as the password (for example, jdoe@company.com).
4. Change to the mib or schema directory using the cd /pub /mibs or cd /pub/ mi bs /s ch em as command.
5. To view the 3Com MIB, OID, or schema entries, enter the dir command.
To pause the display, press [CTRL-S]. To continue the display, press [CTRL-Q].
6. Copy the MIB, OID, or schema files to your current directory using the appropriate command (for example, get chipcom. mi b).
7. To exit the FTP session, invoke the quit command.

3Com Technical Publications

If you have comments or questions on 3Com Integrated Systems Division Techn ical Pu blic at ions docu me nts, p le ase cont act t he T ech nica l Pu bl icat ion s group by FAX (508) 229-1551.
Technical Suppo rt C - 5
Page 80
Page 81
Index
Numerics
3Com Bulletin Board Service (3ComBBS), C-3
A
Audience of Manua l, xiii
B
Back Panel, 1-3 Backup Power Supply
Installing
bulletin board ser vice , C-3
, 2-14
C
Cable Tr a y
Installing Rack Mount i ng , 2-8
Table Top Mount, 2-10 Cable Types, 1-1 Concentrat or Features, 1-4
, 2-7
E
Environment a l Co ndi tio ns, 2-4
F
Fan Unit
Removing
Replacing, 3-7 Fault Toleran c e, 1-8 FCC notic e, ii
, 2-14
Front Panel, 1-3
H
Hot Swap pi ng Mod ule s, 1-11
I
Installation, 2-1 Introduction, 1-1
L
Load Sharing, 1-8
M
Maintenance, 3-1
Modules, 3-9 MIB, C-4 Modul es, insta l ling, 2-19
N
Network Pr ot ocols Suppor t ed, A-1 network supplier suppo rt, C-2
O
on-line technical services, C-1
P
Passive D esi gn, 1-12 Power Requirements , 2-5
Index 1
Page 82
Power Supply
Load Shar in g Replacing, 3-2
, 1-8
Q
Quick Insta llation, 2-6
R
Rack Mount i ng , 2-11
Preparation, 2-5 Regulat o ry Co mp li an ce, A-2 returning product s for re pair, C-4 Rubb er Feet, Installing, 2-13
S
Shipping Cont ents, 2-1 Slot Usage Chart, B-1 SNMP Comma nds, C-4 Specifications
Environmental
General, A-1
Mechanical, A-2
, A-1
T
Table Top Installation, 2-13
Airflow, 2-6
Preparat ion, 2-6 technical support, C-1 TriChannel Architecture, 1-1, 1-6
V
VDE compliance, ii Ventilation, 2-4 Verifying Opera tio n, 2-20 Voltage Selection, 2-17
2 Index
Loading...