York DNX024, DNX036, DNX048 Installation Manual

Page 1
GZKDJRRJDGHZ2[JZFJR
R-410A AFFINITY SERIES
DNX024-048 2-4 Ton
TABLE OF CONTENTS
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rigging And Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ductwork. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Condensate Drain. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power And Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . 10
Compressors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Phasing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Gas Heat. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Flue Vent Hood. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Blower Speed Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Heating Sequence Of Operation. . . . . . . . . . . . . . . . . . . . 22
Cooling Sequence Of Operations . . . . . . . . . . . . . . . . . . . 24
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Adjustment of Temperature Rise . . . . . . . . . . . . . . . . . . . 27
Checking Gas Heat Input . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Natural Gas. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
LIST OF TABLES
1 Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Unit Accessory Weights . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
7 Natural Gas Pipe Sizing Chart . . . . . . . . . . . . . . . . . . . . 16
8 Propane (LP) Gas Pipe Sizing Chart . . . . . . . . . . . . . . . 16
9 Natural Gas Application Data-Single St age . . . . . . . . . . 17
10 Natural Gas Application Data-Two Stage . . . . . . . . . . . . 17
11 Propane (LP) Gas Application Data-Single St ag e . . . . . 17
12 Propane (LP) Gas Application Data-Two Stage . . . . . . . 17
13 Side Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
14 Bottom Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . 19
15 Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . 21
16 Indoor Blower Specifications . . . . . . . . . . . . . . . . . . . . . . 21
17 Delay Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
18 Ignition Control Board FLASH CODES . . . . . . . . . . . . . . 24
19 Gas Rate Cubic Feet Per Hour . . . . . . . . . . . . . . . . . . . . 27
ISO 9001
Certified Quality
LIST OF FIGURES
1 Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Dimensions Front and Bottom . . . . . . . . . . . . . . . . . . . . . 8
5 Dimensions Back and Bottom . . . . . . . . . . . . . . . . . . . . . 8
6 Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 Typical Field Control Wiring Diagram Single Stage
Thermostat - Single Stage Gas Heat . . . . . . . . . . . . . . . 10
8 Typical Field Control Wiring Diagram Single Stage
Thermostat - Two Stage Gas Heat . . . . . . . . . . . . . . . . 11
9 Typical Field Control Wiring Diagram Two Stage
Thermostat - Single Stage Gas Heat . . . . . . . . . . . . . . . 11
General
YORK® Affinity Model DNX units are cooling/heating air conditioners designed for outdoor installation. Only gas piping, electric power and duct connections are required at the point of installation.
The single or two stage gas-fired heaters have spark to pilot ignition. The tubular heat exchangers are aluminized steel.
The refrigerant system is fully charged with R-410A Refrigerant, and is tested and factory sealed.
10 Typical Field Control Wiring Diagram Two Stage
Thermostat - Two Stage Gas Heat . . . . . . . . . . . . . . . . 12
11 Typical Field Power Wiring Diagram . . . . . . . . . . . . . . . 12
12 External Supply Connection External Shut-Off . . . . . . . 15
13 Flue Vent Outlet Air Hood . . . . . . . . . . . . . . . . . . . . . . . 16
14 Control Board Speed Tap Location . . . . . . . . . . . . . . . . 22
15 Single Stage Gas Valve Front . . . . . . . . . . . . . . . . . . . . 25
16 Two Stage Gas Valve Front . . . . . . . . . . . . . . . . . . . . . . 26
17 Single Stage Gas Valve Rear . . . . . . . . . . . . . . . . . . . . 26
18 Two Stage Gas Valve Rear . . . . . . . . . . . . . . . . . . . . . . 26
19 Proper Flame Adjustment . . . . . . . . . . . . . . . . . . . . . . . 26
20 R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . . 36
Safety Considerations
This is a safety alert symbol . When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention the signal words
DANGER, WARNING or CAUTION. DANGER indicates an imminently hazardous situation, which,
if not avoided, will result in death or serious injury WARNING indicates a potentially hazardous situation, which,
if not avoided, could result in death or serious injury CAUTION indicates a potentially hazardous situation, which, if
not avoided may result in minor or moderate injury used to alert against unsafe practices and hazards involving only property damage.
.
.
. It is also
279550-YIM-A-0207
Page 2
Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified contractor, installer or service agency.
This product must be installed in strict compliance with the installation instructions and any applicable local, state and national codes including, but not limited to building, electrical, and mechanical codes.
Before performing service or maintenance operations on unit, turn off main power switch to unit. Electrical shock could cause personal injury. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual. For assistance or additional information consult a qualified installer, service agency or the gas supplier.
This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system. Gage sets, hoses, refrigerant containers and recovery systems must be designed to handle R-410A. If you are unsure, consult the equipment manufacturer. Failure to use R-410A compatible servicing equipment may result in property damage or injury.
279550-YIM-A-0207
Due to system pressure, moving parts, and electrical components, installation and servicing of air conditioning equipment can be hazardous. Only qualified, trained service personnel should install, repair, or service this equipment. Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters.
Observe all precautions in the literature, labels, and tags accompanying the equipment whenever working on air conditioning equipment. Be sure to follow all other applicable safety precautions and codes including ANSI Z223.1 or CSA­B149.1- latest edition.
Wear safety glasses and work gloves. Use quenching cloth and have a fire extinguisher available during brazing operations.
Inspection
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier’s freight bill. A separate request for inspection by the carrier’s agent should be made in writing.
This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state and national codes including, but not limited to, building, electrical, and mechanical codes.
The furnace and its individual shut-off valve must be disconnected from the gas supply piping system during any pressure testing at pressures in excess of 1/2 PSIG.
Pressures greater than 1/2 PSIG will cause gas valve damage resulting in a hazardous condition. If it is subjected to a pressure greater than 1/2 PSIG, the gas valve must be replaced.
The furnace must be isolated from the gas supply piping system by closing its individual manual shut-off valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 PSIG
If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or loss of life. Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance. WHAT TO DO IF YOU SMELL GAS: a. Do not try to light any appliance. b. Do not touch any electrical switch; do not use any
phone in your building.
c. Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
d. If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a qualified installer, service agency or the gas supplier.
2 Unitary Products Group
Reference
Additional information is available in the following reference forms:
• Technical Guide - DNX024-048, 291625
• General Installation - DNX024-048, 279550
Renewal Parts
®
Contact your local York
parts distribution center for authorized
replacement parts.
Approvals
Design certified by CSA as follows:
1. For use as a cooling only unit, cooling un it wi th
supplemental electric heat or a forced air furnace.
2. For outdoor installation only.
Page 3
279550-YIM-A-0207
3. For installation on combustible material and may be installed directly on combustible flooring or, in the U.S., on wood flooring or Class A, Class B or Class C roof covering materials.
4. For use with natural gas (convertible to LP with kit).
This product must be installed in strict compliance with the enclosed installation instructions and any applicable local, state, and national codes including, but not limited to, building, electrical, and mechanical codes.
Nomenclature
Improper installation may create a condition where the operation of the product could cause personal injury or property damage.
This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system.
Product Category
D = Single Package Air Conditioner
Product Generation
1 = 1st Generation 2 = 2nd Generation
NX = R-410A 15 SEER
D 1 036 036 06
Product Identifier
Gas Heat/Electric
NX
Factory Installed Gas Heat
N = Single Stage D = Two Stage
Nominal Cooling Capacity (MBH)
024 = 24,000 BTUH 036 = 36,000 BTUH
Installation
Installation Safety Information
Read these instructions before continuing this appliance installation. This is an outdoor combination heating and cooling unit. The installer must assure that these instructions are made available to the consumer and with instructions to retain them for future reference.
1. Refer to the unit rating plate for the approved type of gas for this product.
2. Install this unit only in a location and position as specified on Page 5 of these instructions.
3. Never test for gas leaks with an open flame. Use commercially available soap solution made specifically for the detection of leaks when checking all connections, as specified on Pages 3 and 16 of these instructions.
4. Always install furnace to operate within the furnace's intended temperature-rise range with the duct system and within the allowable external static pressure range, as specified on the unit name/rating plate, specified on Page 17 of these instructions.
5. This equipment is not to be used for temporary heating of buildings or structures under construction.
N
Voltage Code
06 = 208/230-1-60 25 = 208/230-3-60 46 = 460-3-60
Nominal Gas Heating Output Capacity
(Nominal Low Gas Heat Output Capacity)
036 = 36,000 BTUH 056 = 56,000 BTUH (36,400 BTUH) 065 = 65,000 BTUH 072 = 72,000 BTUH (46,800 BTUH) 090 = 90,000 BTUH (56,160 BTUH)
048 = 48,000 BTUH
FIRE OR EXPLOSION HAZARD Failure to follow the safety warning exactly could result
in serious injury, death or property damage. Never test for gas leaks with an open flame. use a
commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage, personal injury or loss of life.
Limitations
These units must be installed in accordance with the following: In U.S.A.:
1. National Electrical Code, ANSI/NFPA No. 70 - Latest Edition
2. National Fuel Gas Code, ANSI Z223.1 - Latest Edition
3. Gas-Fired Central Furnace Standard, ANSI Z21.47a. ­Latest Edition
4. Local building codes, and
5. Local gas utility requirements
110 = 110,000 BTUH (70,200 BTUH)
Unitary Products Group 3
Page 4
279550-YIM-A-0207
In Canada:
1. Canadian Electrical Code, CSA C22.1
2. Installation Codes, CSA - B149.1.
3. Local plumbing and waste water codes, and
4. Other applicable local codes. Refer to unit application data found in this document. After installation, gas fired units must be adjusted to obtain a
temperature rise within the range specified on the unit rating plate.
Blow-Through Design With
Reliable Aluminized Steel Tubular Heat Exchangers
Long Lasting Powder
Paint Finish
Rear and Bottom Return Air
and Supply Airduct Openings
If components are to be added to a unit to meet local codes, they are to be installed at the dealer’s and/or customer’s expense.
Size of unit for proposed installation should be based on heat loss/heat gain calculation made according to the methods of Air Conditioning Contractors of America (ACCA).
This furnace is not to be used for temporary heating of buildings or structures under construction.
Direct Drive
Condenser Fan Motor
Highly Efficient Enhanced Copper
Tube/Aluminum Fin Evaporator Coil
Highly Efficient Enhanced Copper
Tube/Aluminum Fin Condenser Coil
Decorative Protective
Coil Guard
High Efficiency
Compressor Rigidly
Mounted
Heavy Gauge
Removable Base Rails
Direct Drive Blower Motor With
Slide-Out Blower Assembly
Figure 1: Component Location Table 1: Unit Limitations
Size
(Tons)
024
(2.0)
036
(3.0)
048
(4.0)
Unit Voltage
208/230-1-60 187 252 115 208/230-1-60 187 252 115
208/230-3-60 187 252 115
460-3-60 432 504 115 208/230-1-60 187 252 115 208/230-3-60 187 252 115
460-3-60 432 504 115
Power Draft Motor
Min Max Max (°F)
Pilot Assembly
High Grade Aluminized In-Shot Burners
Low Voltage Terminal Block
Self-Diagnostic Controls
Automatic Gas Valve (1/2" - 14 NPTI)
High Voltage
Terminal Block
Unit Limitations
Applied Voltage Outdoor DB Temp
4 Unitary Products Group
Page 5
279550-YIM-A-0207
Location
Use the following guidelines to select a suitable location for these units:
1. Unit is designed for outdoor installation only.
2. Condenser coils must have an unlimited supply of air. Where a choice of location is possible, position the unit on either north or east side of building.
3. Suitable for mounting on roof curb.
4. For ground level installation, a level pad or slab should be used. The thickness and size of the pad or slab used should meet local codes and unit weight. Do not tie the slab to the building foundation.
5. Roof structures must be able to support the weight of the unit and its options/accessories. Unit must be installed on a solid, level roof curb or appropriate angle iron frame.
6. Maintain level tolerance to 1/8” across the entire width and length of unit.
Excessive exposure of this furnace to contaminated combustion air may result in equipment damage or personal injury. Typical contaminates include: permanent wave solution, chlorinated waxes and cleaners, chlorine based swimming pool chemicals, water softening chemicals, carbon tetrachloride, Halogen type refrigerants, cleaning solvents (e.g. perchloroethylene), printing inks, paint removers, varnishes, hydrochloric acid, cements and glues, antistatic fabric softeners for clothes dryers, masonry acid washing materials.
codes. Refer to Table 5 for clearances required for combustible construction, servicing, and proper unit operation.
Do not permit overhanging structures or shrubs to obstruct condenser air discharge outlet, combustion air inlet or vent outlets.
Rigging And Handling
Exercise care when moving the unit. Do not remove any packaging until the unit is near the place of installation. Rig the unit by attaching chain or cable slings to the lifting holes provided in the base rails. Spreader bars, whose length exceeds the largest dimension across the unit, MUST be used across the top of the unit.
If a unit is to be installed on a roof curb other than a York® roof curb, gasketing must be applied to all surfaces that come in contact with the unit underside.
Before lifting, make sure the unit weight is distributed equally on the rigging cables so it will lift evenly.
Units may be moved or lifted with a forklift. Slotted openings in the base rails are provided for this purpose.
Clearances
All units require particular clearances for proper operation and service. Installer must make provisions for adequate combustion and ventilation air in accordance with section 5.3 of Air for Combustion and Ventilation of the National Fuel Gas Code, ANSI Z223.1 – Latest Edition (in U.S.A.), or Sections 7.2,
7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 (in Canada) -
Latest Edition, and/or applicable provisions of the local building
Unitary Products Group 5
All panels must be secured in place when the unit is lifted.
The condenser coils should be protected from rigging cable damage with plywood or other suitable material.
Page 6
'
279550-YIM-A-0207
)5217
2)
81,7
$

Figure 2: Unit 4 Point Load Weight Table 2: Weights and Dimensions
Size
(Tons)
024
(2.0)
036
(3.0)
048
(4.0)
Weight (lbs.) Center of Gravity 4 Point Load Location (lbs.)
ShippingOperatingX YABCD
445 440 20 24.5 127 93 93 127
445 440 20 24.25 126 91 93 129
505 500 20 24 142 102 107 149
&(17(52)
*5$9,7<
&
;
%
<

Table 3: Unit Accessory Weights
Unit Accessory Model
Add Economizer All 45 40
Shipping Operating
Weight (lbs.)
6 Unitary Products Group
Page 7
279550-YIM-A-0207
*$66833/<
',$0(7(5+2/(
137,&211(&7,21
81,7&21'(16$7(
&211(&7,21137,
75$35(&200(1'('
+,*+92/7$*(
&211',$
.12&.287
*$66833/<
',$.12&.287
137,&211(&7,21
.12&.287[+2/(
%/2:(56(59,&($&&(66
%


/2:92/7$*(
&211',$
9(17$,5287/(7+22'
&203$570(173$1(/

29(5$//





&21'(16(5&2,/


29(5$//
$

5()5,*(5$17
&211(&7,216
&20%867,21$,5
,1/(7/289(56
)5217
*$6(/(&75,&&21752/
6(59,&($&&(66
&203$570(173$1(/
Figure 3: Unit Dimensions Table 4: Unit Dimensions
Unit Size
024 33-1/2 18-1/4
036, 048 41-1/2 23-1/8
Table 5: Unit Clearances1
Direction
3
Top Front 36 Left 24 Rear 0 Bottom
1. A 1" clearance must be provided between any combustible material and the supply air duct work.
2. The products of combustion must not be allowed to accumulate within a confined space and recirculate.
3. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
4. Units may be installed on combustable floors made from wood or class A, B or C roof covering materials.
“A” “B”
2
Distance
(in.)
36 Right 12
Dimensions
Direction
Distance
(in.)
4
0
Unitary Products Group 7
Page 8
+,*+92/7$*(
&211
',$.12&.287



)5217
279550-YIM-A-0207
*$66833/<
',$.12&.287
137,&211(&7,21
/2:92/7$*(
&211',$
.12&.287
&21'(16$7('
5$,1137,

Figure 4: Dimensions Front and Bottom
&21'(16(5
%277206833/<
$,523(1,1*
&2,/
6,'(6833/<
$,523(1,1*




%$&.

6,'(5(7851
$,523(1,1*


Figure 5: Dimensions Back and Bottom
8 Unitary Products Group




%277205(7851

$,523(1,1*



Page 9
279550-YIM-A-0207



5(&200(1'('
'8&76,=(
[



23(1,1*)25
5(7851$,5'8&7

Figure 6: Roof Curb

1
Ductwork
These units are adaptable to downflow use as well as rear supply and return air duct openings. To convert to downflow, use the following steps:
1. Remove the duct covers found in the bottom return and supply air duct openings. There are four (4) screws securing each duct cover (save these screws to use in Step 2).
2. Install the duct covers (removed in step one) to the rear supply and return air duct openings. Secure with the four (4) screws used in step one.
3. Seal duct covers with silicone caulk.
Duct work should be designed and sized according to the methods of the Air Conditioning Contractors of America (ACCA), as set forth in their Manual D.
A closed return duct system shall be used. This shall not preclude use of economizers or ventilation air intake. Flexible joints may be used in the supply and return duct work to minimize the transmission of noise.
NOTE: Be sure to note supply and return openings. Refer to Figures 4 and 5 for information concerning rear and
bottom supply and return air duct openings.

23(1,1*)25
6833/<$,5'8&7
5(&200(1'('
'8&76,=(
[
Roof Curb
On applications when a roof curb is used, the unit must be positioned on the curb so the front of the unit is tight against the curb.
Filters
Single phase units are shipped without a filter or filter racks. It is the responsibility of the installer to secure a filter in the return air ductwork or install a Filter/Frame Kit (1FF0110).
A filter rack and high velocity filters are standard on three phase units.
Filters must always be used and must be kept clean. When filters become dirt laden, insufficient air will be delivered by the blower, decreasing your units efficiency and increasing operating costs and wear-and-tear on the unit and controls.
Filters should be checked monthly; this is especially important since this unit is used for both heating and cooling.
Condensate Drain
A condensate trap is recommended to be installed in the condensate drain. The plumbing must conform to local codes.
Use a sealing compound on male pipe threads. Install the condensate drain line (3/4” NPTF) to spill into an open drain.
1. 8” Roof Curb also available.
Unitary Products Group 9
Page 10
279550-YIM-A-0207
Service Access
Access to all serviceable components is provided at the following locations:
• Blower compartment access panel
• Gas control/electrical access panel
• Refrigerant connections
Refer to Figure 3 for location of these access locations and minimum clearances in Table 5.
This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system. Gage sets, hoses, refrigerant containers and recovery systems must be designed to handle R-410A. If you are unsure, consult the equipment manufacturer. Failure to use R-410A compatible servicing equipment may result in property damage or injury.
Thermostat
The room thermostat should be located on an inside wall approximately 56" above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow manufacturer's instructions enclosed with the thermostat for general installation procedure. Color coded insulated wires (minimum #18 AWG) should be used to connect thermostat to unit. See Figures 7 thru 10.
Power And Control Wiring
Field wiring to the unit must conform to provisions of the current N.E.C. ANSI/NFPA No. 70 or C.E.C. and/or local ordinances. The unit must be electrically grounded in accordance with local codes or, in their absence, with the N.E.C./C.E.C. Voltage tolerances which must be maintained at the compressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 6.
The wiring entering the cabinet must be provided with mechanical strain relief.
A fused disconnect switch should be field provided for the unit. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram.
Wear safety glasses and gloves when handling refrigerants. Failure to follow this warning can cause serious personal injury.
Refer to Figure 20 for the R-410A Quick Reference Guide.
6,1*/(67$*(
7+(50267$7
 0LQLPXPZLUHVL]HRI$:* ZLUHVKRXOGEHXVHGIRUDOOILHOG LQVWDOOHGYROWZLUH
352*5$00$%/(
7+(50267$721/<
5
*
<
:
&
Electrical line must be sized properly to carry the load. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.
Refer to Figures 7 thru 11 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information.
127(+($7$17,&,3$725
81,7&21752/%2$5'
7(50,1$/675,3

<<
:
5
*
<
&
-803(51(('(')25)8//63(('
6+28/'%(6(7$7 $036)25$//02'(/6
&2035(662523(5$7,21
92/7
75$16)250(5
Figure 7: Typical Field Control Wiring Diagram Single Stage Thermostat - Single Stage Gas Heat
10 Unitary Products Group
Page 11
279550-YIM-A-0207
** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire.
SINGLE STAGE
THERMOSTAT
R
G
Y
UNIT CONTROL BOARD
TERMINAL STRIP
**
R
G
Y
1
NOTE: HEAT ANTICIPATOR SHOULD BE SET AT 0.35 AMPS FOR ALL MODELS.
JUMPER NEEDED FOR FULL SPEED
COMPRESSOR OPERATION
Y/Y
2
W
W
C
1
W
2
C
PROGRAMMABLE
THERMOSTAT ONLY
Figure 8: Typical Field Control Wiring Diagram Single Stage Thermo stat - Two Sta ge Gas Heat
127(+($7$17,&,3$725 6+28/'%(6(7$7 $036)25$//02'(/6
 0LQLPXPZLUHVL]HRI$:* ZLUHVKRXOGEHXVHGIRUDOOILHOG LQVWDOOHGYROWZLUH
67$*(
7+(50267$7
5
*
<
<
:
81,7&21752/%2$5'
7(50,1$/675,3

5
*
<
<<
:
24 VOLT
TRANSFORMER
92/7
75$16)250(5
352*5$00$%/(
7+(50267$721/<
Figure 9: Typical Field Control Wiring Diagram Two Stage Thermostat - Single Stage Gas Heat
Unitary Products Group 11
&
&
Page 12
** = Minimum wire size of 18 AWG wire should be used for all field installed 24 volt wire.
2 STAGE
THERMOSTAT
R
G
Y
1
UNIT CONTROL BOARD
TERMINAL STRIP
**
R
G
Y
1
279550-YIM-A-0207
NOTE: HEAT ANTICIPATOR SHOULD BE SET AT 0.35 AMPS FOR ALL MODELS.
Y
2
W
1
W
2
C
Y/Y
W
W
C
2
1
2
PROGRAMMABLE
THERMOSTAT ONLY
Figure 10: Typical Field Control Wiring Diagram Two Stage Thermostat - Two Stage Gas Hea t
Figure 11: Typical Field Power Wiring Diagram Table 6: Electrical Data
Size
(Tons)
024
(2.0)
036
(3.0)
048
(4.0)
Volt
208/230-1-60 10.2 52 16 1.4 4.3 18.1 25 208/230-1-60 16.6 82 26 0.9 9.1 30.7 40
208/230-3-60 11.1 58 17 0.9 9.1 23.8 30
460-3-60 4.5 29 7 0.5 4.6 10.7 15 208/230-1-60 21.1 96 33 1.8 9.1 36.3 45 208/230-3-60 13.4 88 21 1.8 9.1 26.7 35
460-3-60 6.4 41 10 0.9 4.6 13.0 15
Compressors
(each)
RLA LRA MCC FLA FLA
OD Fan
Motors
(each)
Supply Blower
Motor
MCA
(Amps)
1. Minimum Circuit Ampacity.
2. Maximum Over Current Protection per standard UL 1995.
3. Fuse or HACR circuit breaker size installed at factory or field installed.
1
Max
Fuse
Breaker
Size
(Amps)
2
/
3
24 VOLT
TRANSFORMER
12 Unitary Products Group
Page 13
279550-YIM-A-0207
DNX024-048 Single Stage Gas Heat
Component
Nominal Tonnage 2.0 3.0 4.0
ARI COOLING PERFORMANCE
Gross Capacity @ ARI A point (Btu) 24.6 38.4 50.0 ARI net capacity (Btu) 24.0 37.0 48.0 EER 11.5 12.3 11.2 SEER 15.0 16.5 15.0 Nominal CFM 800 1275 1550 System power (KW) 2.1 3.0 4.3 Refrigerant type R-410A R-410A R-410A Refrigerant charge (lb-oz) 7-8 9-12 9-8
ARI HEATING PERFORMANCE
Heating model 36 56 65 90 65 90 110 Heat input (K Btu) 45 70 80 108 80 108 135 Heat output (K Btu) 36 56 64 87 64 87 108 AFUE % 80.0 80.0 80.0 80.0 80.0 80.0 80.0 Steady state efficiency (%) 80808080808080 No. burners 2334345 No. stages 1111111 Temperature Rise Range (ºF) 25-55 30-60 25-55 45-75 25-55 35-65 45-75 Gas Limit Setting (ºF) 140 160 140 160 150 170 160 Gas piping connection (in.) 1/2 1/2 1/2
DIMENSIONS (inches)
Length 49 1/8 49 1/8 49 1/ 8 Width 47 1/4 47 1/4 47 1/4 Height 33 1/2 41 1/2 41 1/2
OPERATING WT. (lbs.) 440 480 500
COMPRESSORS
Type Scroll 2-spd Scroll 2-spd Scroll 2-spd Quantity 1 1 1
CONDENSER COIL DATA
Face area (Sq. Ft.) 11.7 14.7 14.7 Rows 2 2 2 Fins per inch 20 20 20 Tube diameter (in.) 3/8 3/8 3/8 Circuitry Type Interlaced Interlaced Interlaced
EVAPORATOR COIL DATA
Face area (Sq. Ft.) 3.4 4.4 4.4 Rows 2 3 3 Fins per inch 15 16 16 Tube diameter 3/8 3/8 3/8 Circuitry Type Interlaced Interlaced Interlaced Refrigerant control TXV TXV TXV
CONDENSER FAN DATA
Quantity 1 1 1 Fan diameter (Inch) 22 22 22 Type Prop Prop Prop Drive type Direct Direct Direct No. speeds 1 2 1 Number of motors 1 1 2 Motor HP each 1/4 1/3 1/3 RPM 1100 900/1100 900/1100 Nominal total CFM 2400 2400 3000
DIRECT DRIVE EVAP FAN DATA
Quantity 1 1 1 Fan Size (Inch) 10 x 8 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Motor HP each 1/2 1 1 RPM Variable Variable Variable Frame size 48 48 48
FILTERS
Quantity - Size 1 - 20 x 20 x 1 2 - 20 x 12 x 1 2 - 20 x 12 x 1
DNX024 DNX036 DNX048
Models
Unitary Products Group 13
Page 14
DNX024-048 Two Stage Gas Heat
Component
Nominal Tonnage 2.0 3.0 4.0
ARI COOLING PERFORMANCE
Gross Capacity @ ARI A point (Btu) 24.6 38.4 50.0 ARI net capacity (Btu) 24.0 37.0 48.0 EER 11.5 12.3 11.2 SEER 15.0 16.5 15.0 Nominal CFM 800 1275 1550 System power (KW) 2.1 3.0 4.3 Refrigerant type R-410A R-410A R-410A Refrigerant charge (lb-oz) 7-8 9-12 9-8
ARI HEATING PERFORMANCE
Heating model 56 90 90 110 Heat input (K Btu) 70/45.5 108/70.2 108/70.2 135/87.8 Heat output (K Btu) 56/36.4 87/56.2 87/56.2 108/70.2 AFUE % 80.0 80.0 80.0 80.0 Steady state efficiency (%) 80 80 80 80 No. burners 3 4 4 5 No. stages 2 2 2 2 Temperature Rise Range (ºF) 30-60 45-75 35-65 45-75 Gas Limit Setting (ºF) 160 175 170 160 Gas piping connection (in.) 1/2 1/2 1/2
DIMENSIONS (inches)
Length 49 1/8 49 1/8 49 1/8 Width 47 1/4 47 1/4 47 1/4 Height 33 1/2 41 1/2 41 1/2
OPERATING WT. (lbs.) 440 480 500
COMPRESSORS
Type Scroll 2-spd Scroll 2-spd Scroll 2-spd Quantity 1 1 1
CONDENSER COIL DATA
Face area (Sq. Ft.) 11.7 14.7 14.7 Rows 222 Fins per inch 20 20 20 Tube diameter (in.) 3/8 3/8 3/8 Circuitry Type Interlaced Interlaced Interlaced
EVAPORATOR COIL DATA
Face area (Sq. Ft.) 3.4 4.4 4.4 Rows 233 Fins per inch 15 16 16 Tube diameter 3/8 3/8 3/8 Circuitry Type Interlaced Interlaced Interlaced Refrigerant control TXV TXV TXV
CONDENSER FAN DATA
Quantity 1 1 1 Fan diameter (Inch) 22 22 22 Type Prop Prop Prop Drive type Direct Direct Direct No. speeds 1 2 1 Number of motors 1 1 2 Motor HP each 1/4 1/3 1/3 RPM 1100 900/1100 900/1100 Nominal total CFM 2400 2400 3000
DIRECT DRIVE EVAP FAN DATA
Quantity 1 1 1 Fan Size (Inch) 10 x 8 11 x 10 11 x 10 Type Centrifugal Centrifugal Centrifugal Motor HP each 1/2 1 1 RPM Variable Variable Variable Frame size 48 48 48
FILTERS
Quantity - Size 1 - 20 x 20 x 1 2 - 20 x 12 x 1 2 - 20 x 12 x 1
DNX024 DNX036 DNX048
Models
279550-YIM-A-0207
14 Unitary Products Group
Page 15
279550-YIM-A-0207
Compressors
The scroll compressor used in this product is specifically designed to operate with R-410A Refrigerant and cannot be interchanged.
This system uses R-410A Refrigerant which operates at higher pressures than R-22. No other refrigerant may be used in this system.
The compressor also uses a polyolester (POE oil), Mobil 3MA POE. This oil is extremely hydroscopic, meaning it absorbs water readily. POE oil can absorb 15 times as much water as other oils designed for HCFC and CFC refrigerants. Take all necessary precautions to avoid exposure of the oil to the atmosphere.
Do not leave the system open to the atmosphere. Unit damage could occur due to moisture being absorbed by the POE oil in the system. This type of oil is highly susceptible to moisture absorption
POE (polyolester) compressor lubricants are known to cause long term damage to some synthetic roofing materials.
Scroll compressors require proper rotation to operate properly. Failure to check and correct rotation may result in property damage.
Gas Heat
These single or two stage gas-fired heaters have aluminized­steel tubular heat exchangers with spark to pilot ignition.
Gas Piping
Proper sizing of gas piping depends on the cubic feet per hour of gas flow required, specific gravity of the gas and the length of run. National Fuel Gas Code Z223.1 or CSA B149.1 should be followed in all cases unless superseded by local codes or gas company requirements. Refer to Tables 7 and 8.
The heating value of the gas may differ with locality. The value should be checked with the local gas utility.
NOTE: There may be a local gas utility requirement specifying
a minimum diameter for gas piping. All units require a 1/2 inch pipe connection at the gas valve.
Gas Connection
The gas supply line can be routed through the hole located on the left side of the unit. Refer to Figure 3 to locate these access openings. Typical supply piping arrangements are shown in Figure 12.
Exposure, even if immediately cleaned up, may cause embrittlement (leading to cracking) to occur in one year or more. When performing any service that may risk exposure of compressor oil to the roof, take precautions to protect roofing.
Procedures which risk oil leakage include, but are not limited to, compressor replacement, repairing refrigerant leaks, replacing refrigerant components such as filter drier, pressure switch, metering device or coil.
Units are shipped with compressor mountings which are factory-adjusted and ready for operation.
Do not loosen compressor mounting bolts.
Phasing
Three-phase, scroll compressors operate in only one dire ction. If the scroll is drawing low amperage, has similar suction and discharge pressures, or is producing a high noise level, the scroll is misphased. Change the incoming line connection phasing to obtain the proper rotation.
Gas piping requirements:
1. A drip leg and a ground joint union must be installed in the gas piping.
2. When required by local codes, a manual shut-off valve may have to be installed outside of the unit.
3. Use wrought iron or steel pipe for all gas lines. Pipe dope should be applied sparingly to male threads only.
$8720$7,&*$69$/9(
[81,21
[*$6&2&.
137
'5,3/(*
Figure 12: External Supply Connection External Shut-Off
Unitary Products Group 15
Page 16
279550-YIM-A-0207
Table 7: Natural Gas Pipe Sizing Chart
Length In Feet
10 132 278 520 1,050 20 92 190 350 730 30 73 152 285 590 40 63 130 245 500 50 56 115 215 440 60 50 105 195 400 70 46 96 180 370 80 43 90 170 350 90 40 84 160 320
100 38 79 150 305
1. Maximum capacity of pipe in cubic feet of gas per hour (based upon a pressure drop of 0.3 inch water column and
0.6 specific gravity gas).
Nominal Inches Iron Pipe Size
1/2” 3/4” 1” 1-1/4”
1
Table 8: Propane (LP) Gas Pipe Sizing Chart
Length In Feet
10 275 567 1,071 2,205 20 189 393 732 1,496 30 152 315 590 1,212 40 129 267 504 1,039 50 114 237 448 913 60 103 217 409 834 70 96 196 378 771 80 89 185 346 724 90 83 173 322 677
100 78 162 307 630
1. Maximum capacity of pipe in thousands of BTU per hour (based upon a pressure drop of 0.5 inch water column).
Nominal Inches Iron Pipe Size
1/2” 3/4” 1” 1-1/4”
Limitations, shown on Page 3. After the gas connections have been completed, open the main shut-off valve admitting normal gas pressure to the mains. Check all joints for leaks with soap solution or other material suitable for the purpose. NEVER USE A FLAME.
FIRE OR EXPLOSION HAZARD Failure to follow the safety warning exactly could result
in serious injury, death or property damage. Never test for gas leaks with an open flame. use a
commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion may result causing property damage,
1
personal injury or loss of life.
6. The furnace must be isolated from the gas supply piping system by closing its individual manual shut-off valve before conducting any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.48 kPa).
Flue Vent Hood
The flue vent hood with screen is shipped loose. This hood must be installed to assure proper unit operation. The hood must be fastened to the outside of the side gas control/electrical compartment with the screws provided in the bag attached to the inside of the gas control/electrical compartment, see Figure 13.
If flexible stainless steel tubing is allowed by the authority having jurisdiction, wrought iron or steel pipe must be installed at the gas valve and extend a minimum of two (2) inches outside of the unit casing.
Natural gas may contain some propane. Propane being an excellent solvent, will quickly dissolve white lead or most standard commercial compounds. Therefore, a special pipe dope must be applied when wrought iron or steel pipe is used. Shellac base compounds such as gaskoloc or stalastic, and compounds such as rectorseal # 5, Clyde’s or John Crane may be used.
4. All piping should be cleaned of dirt and scale by hammering on the outside of the pipe and blowing out the loose dirt and scale. Before initial start-up, be sure that all of the gas lines external to the unit have been purged of air.
5. The gas supply should be a separate line and installed in accordance with all safety codes as prescribed under
Flue hood surfaces may be hot.
9(17287/(76&5((1
)/8(9(17287/(7
$,5+22'
Figure 13: Flue Vent Outlet Air Hood
The flue exhaust hood must be properly installed and within the recommended clearances. Further commu­nications and action must be given to the home or building owner(s) to eliminate any unauthorized human contact around this area during the heating cycle. Flue hood surface and the immediate area reach high tem­peratures during the heating cycle.
16 Unitary Products Group
Page 17
279550-YIM-A-0207
Table 9: Natural Gas Application Data-Single Stage
Temp. Rise ºF
At Full Input
Min. Max.
Available On Models
Input
(MBH)
1
Output
(MBH)
Gas Rate
Ft.3/Hr.
2
Number of
Burners
2 Ton 45 36 42 2 25 55 2 Ton 70 56 65 3 30 60
3,4 Ton 80 64 74 3 25 55
3 Ton 108 87 100 4 45 75 4 Ton 108 87 100 4 35 65 4 Ton 135 108 126 5 45 75
1. Heating capacity valid for elevations up to 2000 feet above sea level. For elevations above 2,000 feet, rated capacity should be reduced by 4% for each 1,000 feet above sea level.
2. Based on 1075 BTU/Ft.
3
.
3. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperature should not be below 55°F.
Table 10: Natural Gas Application Data-Two Stage
Ft.3/Hr.
2
Number of
Burners
Temp. Rise ºF
At Full Input
Min. Max.
Available On Models
Input
1
(MBH)
High Fire/Low Fire
Output
(MBH)
High Fire/Low Fire
Gas Rate
High Fire/Low Fire
2 Ton 70 / 45.5 56 / 36.4 65 / 42 3 30 60 3 Ton 108 / 70.2 87 / 56.2 100 / 65 4 45 75 4 Ton 108 / 70.2 87 / 56.2 100 / 65 4 35 65 4 Ton 135 / 87.75 108 / 70.2 126 / 82 5 45 75
1. Heating capacity valid for elevations up to 2000 feet above sea level. For elevations above 2,000 feet, rated capacity should be reduced by 4% for each 1,000 feet above sea level.
2. Based on 1075 BTU/Ft.
3
.
3. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperature should not be below 55°F.
Table 11: Propane1 (LP) Gas Application Data-Single Stage
Temp. Rise ºF
At Full Input
Min. Max.
Available On Models
Input Capacity
(Mbh)
2
Output Capacity
(Mbh)
Gas Rate
Ft.3/Hr.
3
Number of Burners
2 Ton 45 36 18 2 25 55 2 Ton 70 56 28 3 30 60
3,4 Ton 80 64 32 3 25 55
3 Ton 108 87 43 4 45 75 4 Ton 108 87 43 4 35 65 4 Ton 135 108 54 5 45 75
1. Propane applications are accomplished by field installation of a Propane Conversion A cce ssory, M odel 1 NP0807 f or 2 Ton u nit with 33-1 /2” tall cabinet and Model 1NP0808 for 3 and 4 To n un it s wit h 41 -1/2” tall cabinet s.
2. Heating capacity valid for elevations up to 2,000 feet above sea level. For elevations above 2,000 feet, rated capacity should be reduced by 4% for each 1,000 feet above sea level.
3. Based on 2500 BTU/Ft.
3
.
4. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperature should not be below 55°F.
Table 12: Propane1 (LP) Gas Application Data-Two Stage
Ft.3/Hr.
3
Number of Burners
Temp. Rise ºF
At Full Input
Min. Max.
Gas Rate
High Fire/Low Fire
Available On Models
Input Capacity
(Mbh)
2
High Fire/Low Fire
Output Capacity
(Mbh)
High Fire/Low Fire
2 Ton 70 / 45.5 56 / 36.4 28 / 18.2 3 30 60 3 Ton 108 / 70.2 87 / 56.2 43 / 27.95 4 45 75 4 Ton 108 / 70.2 87 / 56.2 43 / 27.95 4 35 65 4 Ton 135 / 87.75 108 / 70.2 54 / 35.1 5 45 75
1. Propane applications are accomplished by field installation of a Propane Conversion A cce ssory, M odel 1 NP0809 f or 2 Ton u nit with 33-1 /2” tall cabinet and Model 1NP0810 for 3 and 4 To n un it s wit h 41 -1/2” tall cabinet s.
2. Heating capacity valid for elevations up to 2,000 feet above sea level. For elevations above 2,000 feet, rated capacity should be reduced by 4% for each 1,000 feet above sea level.
3. Based on 2500 BTU/Ft.
3
.
4. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperature should not be below 55°F.
3
3
4
4
Unitary Products Group 17
Page 18
Airflow Performance
Table 13: Side Duct Application
Size
(Tons)
024
(2.0)
036
(3.0)
048
(4.0)
Mode
Cool
Heat
Cool
Heat
Cool
Low
High
N036
N056
D056
Low
High
N065
N090
D090
Low
High
Thermostat
Input
Y1 COOL-A 600 100 122 145 169 194 221 249 279 310 Y1 COOL-B 450 65 81 100 122 147 176 208 243 281 Y1 COOL-C 530 81 100 121 145 170 197 226 258 291
Y1 COOL-D 680 127 151 176 202 228 256 284 313 342 Y1+Y2 COOL-A 800 177 204 232 261 290 320 350 382 414 Y1+Y2 COOL-B 600 100 122 145 169 194 221 249 279 310 Y1+Y2 COOL-C 700 134 159 184 211 238 265 293 323 352 Y1+Y2 COOL-D 900 229 258 288 319 351 385 420 457 494
W1 HEAT-A 670 123 147 172 197 224 251 - - ­W1 HEAT-B 730 146 172 198 225 252 280 - - ­W1 HEAT-C 790 173 199 227 255 284 314 - - ­W1 HEAT-D 850 202 230 259 289 319 351 - - ­W1 HEAT-A 940 253 281 312 344 378 - - - ­W1 HEAT-B 975 274 303 334 368 403 - - - ­W1 HEAT-C 1000 290 319 351 385 422 - - - ­W1 HEAT-D 1050 324 353 386 422 461 - - - ­W1 HEAT-A 670 123 147 172 197 224 - - - ­W1 HEAT-B 690 130 155 180 206 233 - - - ­W1 HEAT-C 710 138 163 189 215 242 - - - -
W1 HEAT-D 750 155 181 207 235 262 - - - ­W1+W2 HEAT-A 940 253 281 312 344 378 - - - ­W1+W2 HEAT-B 970 271 300 331 364 400 - - - ­W1+W2 HEAT-C 1000 290 319 351 385 422 - - - ­W1+W2 HEAT-D 1050 324 353 386 422 461 - - - -
Y1 COOL-A 900 198 233 272 313 358 406 458 512 569 Y1 COOL-B 760 166 190 222 262 310 366 431 503 584 Y1 COOL-C 830 180 210 245 286 332 384 441 503 571
Y1 COOL-D 970 221 260 302 344 388 434 481 530 579 Y1+Y2 COOL-A 1250 361 408 454 501 548 594 640 687 733 Y1+Y2 COOL-B 1050 253 296 340 384 428 472 516 561 605 Y1+Y2 COOL-C 1150 302 348 394 439 484 528 571 615 657 Y1+Y2 COOL-D 1350 429 475 522 570 620 671 723 777 831
W1 HEAT-A 1200 330 377 423 469 515 560 - - ­W1 HEAT-B 1300 394 440 487 535 583 631 - - ­W1 HEAT-C 1400 467 511 558 607 659 713 - - ­W1 HEAT-D 1500 550 590 635 686 743 804 - - ­W1 HEAT-A 1150 302 348 394 439 484 528 - - ­W1 HEAT-B 1225 345 392 439 485 531 577 - - ­W1 HEAT-C 1275 377 424 471 518 565 612 - - ­W1 HEAT-D 1350 429 475 522 570 620 671 - - ­W1 HEAT-A 740 163 185 216 255 304 362 - - ­W1 HEAT-B 785 170 196 230 270 317 372 - - ­W1 HEAT-C 825 178 208 243 284 330 382 - - -
W1 HEAT-D 870 189 223 260 301 347 396 - - ­W1+W2 HEAT-A 1150 302 348 394 439 484 528 - - ­W1+W2 HEAT-B 1220 342 389 436 482 528 573 - - ­W1+W2 HEAT-C 1280 380 427 474 521 568 616 - - ­W1+W2 HEAT-D 1350 429 475 522 570 620 671 - - -
Y1 COOL-A 1030 237 280 323 367 411 455 499 543 588 Y1 COOL-B 930 192 237 282 326 369 413 455 497 539 Y1 COOL-C 1070 257 300 343 386 430 475 520 565 611
Y1 COOL-D 1130 289 332 375 419 463 509 555 602 649 Y1+Y2 COOL-A 1550 586 640 696 752 810 869 929 991 1053 Y1+Y2 COOL-B 1400 466 513 561 611 663 715 770 826 882 Y1+Y2 COOL-C 1600 630 687 745 804 864 926 988 1052 1116 Y1+Y2 COOL-D 1700 723 787 851 916 982 1049 1116 1185 -
Speed
Tap
CFM
0.20.30.40.50.60.70.80.91.0
Watts Watts Watts Watts Watts Watts Watts Watts Watts
External Static Pressure (Inch Water Gauge)
279550-YIM-A-0207
18 Unitary Products Group
Page 19
279550-YIM-A-0207
Table 13: Side Duct Application (Continued)
Size
(Tons)
048
(4.0)
Mode
Heat
N065
N090
D090
N110
D110
Thermostat
Input
W1 HEAT-A 1200 330 373 416 461 507 554 - - ­W1 HEAT-B 1300 394 439 484 531 579 629 - - ­W1 HEAT-C 1400 466 513 561 611 663 715 - - ­W1 HEAT-D 1500 544 596 648 702 758 815 - - ­W1 HEAT-A 1325 412 456 503 550 599 649 - - ­W1 HEAT-B 1400 466 513 561 611 663 715 - - ­W1 HEAT-C 1500 544 596 648 702 758 815 - - ­W1 HEAT-D 1600 630 687 745 804 864 926 - - ­W1 HEAT-A 870 168 215 261 306 350 393 - - ­W1 HEAT-B 920 188 233 278 322 366 409 - - ­W1 HEAT-C 985 216 260 303 347 391 434 - - -
W1 HEAT-D 1050 247 290 333 376 420 464 - - ­W1+W2 HEAT-A 1330 415 460 506 554 603 653 - - ­W1+W2 HEAT-B 1400 466 513 561 611 663 715 - - ­W1+W2 HEAT-C 1500 544 596 648 702 758 815 - - ­W1+W2 HEAT-D 1600 630 687 745 804 864 926 - - -
W1 HEAT-A1450504553604656-----
W1 HEAT-B1500544596648702-----
W1 HEAT-C1600630687745804-----
W1 HEAT-D1700723787851916-----
W1 HEAT-A940196241285329-----
W1 HEAT-B970209253297341-----
W1 HEAT-C1050247290333376-----
W1 HEAT-D1100273315358402----­W1+W2 HEAT-A1450504553604656----­W1+W2 HEAT-B1500544596648702----­W1+W2 HEAT-C1600630687745804----­W1+W2 HEAT-D1700723787851916-----
Speed
Tap
External Static Pressure (Inch Water Gauge)
CFM
0.20.30.40.50.60.70.80.91.0
Watts Watts Watts Watts Watts Watts Watts Watts Watts
Table 14: Bottom Duct Application
Size
(Tons)
024
(2.0)
Mode
Cool
Heat
Low
High
N036
N056
D056
Thermostat
Input
Y1 COOL-A 600 100 122 145 169 194 221 249 279 310 Y1 COOL-B 450 65 81 100 122 147 176 208 243 281 Y1 COOL-C 530 81 100 121 145 170 197 226 258 291
Y1 COOL-D 680 127 151 176 202 228 256 284 313 342 Y1+Y2 COOL-A 800 177 204 232 261 290 320 350 382 414 Y1+Y2 COOL-B 600 100 122 145 169 194 221 249 279 310 Y1+Y2 COOL-C 700 134 159 184 211 238 265 293 323 352 Y1+Y2 COOL-D 900 229 258 288 319 351 385 420 457 494
W1 HEAT-A 670 123 147 172 197 224 251 - - ­W1 HEAT-B 730 146 172 198 225 252 280 - - ­W1 HEAT-C 790 173 199 227 255 284 314 - - ­W1 HEAT-D 850 202 230 259 289 319 351 - - ­W1 HEAT-A 940 253 281 312 344 378 - - - ­W1 HEAT-B 975 274 303 334 368 403 - - - ­W1 HEAT-C 1000 290 319 351 385 422 - - - ­W1 HEAT-D 1050 324 353 386 422 461 - - - ­W1 HEAT-A 670 123 147 172 197 224 - - - ­W1 HEAT-B 690 130 155 180 206 233 - - - ­W1 HEAT-C 710 138 163 189 215 242 - - - -
W1 HEAT-D 750 155 181 207 235 262 - - - ­W1+W2 HEAT-A 940 253 281 312 344 378 - - - ­W1+W2 HEAT-B 970 271 300 331 364 400 - - - ­W1+W2 HEAT-C 1000 290 319 351 385 422 - - - ­W1+W2 HEAT-D 1050 324 353 386 422 461 - - - -
Speed
Tap
External Static Pressure (Inch Water Gauge)
CFM
0.20.30.40.50.60.70.80.91.0
Watts Watts Watts Watts Watts Watts Watts Watts Watts
Unitary Products Group 19
Page 20
Table 14: Bottom Duct Application (Continue d)
Size
(Tons)
036
(3.0)
048
(4.0)
Mode
Cool
Heat
Cool
Heat
Low
High
N065
N090
D090
Low
High
N065
N090
D090
N110
D110
Thermostat
Input
Y1 COOL-A 900 198 233 272 313 358 406 458 512 569 Y1 COOL-B 760 166 190 222 262 310 366 431 503 584 Y1 COOL-C 830 180 210 245 286 332 384 441 503 571
Y1 COOL-D 970 221 260 302 344 388 434 481 530 579 Y1+Y2 COOL-A 1250 361 408 454 501 548 594 640 687 733 Y1+Y2 COOL-B 1050 253 296 340 384 428 472 516 561 605 Y1+Y2 COOL-C 1150 302 348 394 439 484 528 571 615 657 Y1+Y2 COOL-D 1350 429 475 522 570 620 671 723 777 831
W1 HEAT-A 1200 330 377 423 469 515 560 - - ­W1 HEAT-B 1300 394 440 487 535 583 631 - - ­W1 HEAT-C 1400 467 511 558 607 659 713 - - ­W1 HEAT-D 1500 550 590 635 686 743 804 - - ­W1 HEAT-A 1150 302 348 394 439 484 528 - - ­W1 HEAT-B 1225 345 392 439 485 531 577 - - ­W1 HEAT-C 1275 377 424 471 518 565 612 - - ­W1 HEAT-D 1350 429 475 522 570 620 671 - - ­W1 HEAT-A 740 163 185 216 255 304 362 - - ­W1 HEAT-B 785 170 196 230 270 317 372 - - ­W1 HEAT-C 825 178 208 243 284 330 382 - - -
W1 HEAT-D 870 189 223 260 301 347 396 - - ­W1+W2 HEAT-A 1150 302 348 394 439 484 528 - - ­W1+W2 HEAT-B 1220 342 389 436 482 528 573 - - ­W1+W2 HEAT-C 1280 380 427 474 521 568 616 - - ­W1+W2 HEAT-D 1350 429 475 522 570 620 671 - - -
Y1 COOL-A 1030 237 280 323 367 411 455 499 543 588 Y1 COOL-B 930 192 237 282 326 369 413 455 497 539 Y1 COOL-C 1070 257 300 343 386 430 475 520 565 611
Y1 COOL-D 1130 289 332 375 419 463 509 555 602 649 Y1+Y2 COOL-A 1550 586 640 696 752 810 869 929 991 1053 Y1+Y2 COOL-B 1400 466 513 561 611 663 715 770 826 882 Y1+Y2 COOL-C 1600 630 687 745 804 864 926 988 1052 1116 Y1+Y2 COOL-D 1700 723 787 851 916 982 1049 1116 1185 -
W1 HEAT-A 1200 330 373 416 461 507 554 - - ­W1 HEAT-B 1300 394 439 484 531 579 629 - - ­W1 HEAT-C 1400 466 513 561 611 663 715 - - ­W1 HEAT-D 1500 544 596 648 702 758 815 - - ­W1 HEAT-A 1325 412 456 503 550 599 649 - - ­W1 HEAT-B 1400 466 513 561 611 663 715 - - ­W1 HEAT-C 1500 544 596 648 702 758 815 - - ­W1 HEAT-D 1600 630 687 745 804 864 926 - - ­W1 HEAT-A 870 168 215 261 306 350 393 - - ­W1 HEAT-B 920 188 233 278 322 366 409 - - ­W1 HEAT-C 985 216 260 303 347 391 434 - - -
W1 HEAT-D 1050 247 290 333 376 420 464 - - ­W1+W2 HEAT-A 1330 415 460 506 554 603 653 - - ­W1+W2 HEAT-B 1400 466 513 561 611 663 715 - - ­W1+W2 HEAT-C 1500 544 596 648 702 758 815 - - ­W1+W2 HEAT-D 1600 630 687 745 804 864 926 - - -
W1 HEAT-A1450504553604656-----
W1 HEAT-B1500544596648702-----
W1 HEAT-C1600630687745804-----
W1 HEAT-D1700723787851916-----
W1 HEAT-A940196241285329-----
W1 HEAT-B970209253297341-----
W1 HEAT-C1050247290333376-----
W1 HEAT-D1100273315358402----­W1+W2 HEAT-A1450504553604656----­W1+W2 HEAT-B1500544596648702----­W1+W2 HEAT-C1600630687745804----­W1+W2 HEAT-D1700723787851916-----
Speed
Tap
External Static Pressure (Inch Water Gauge)
CFM
0.20.30.40.50.60.70.80.91.0
Watts Watts Watts Watts Watts Watts Watts Watts Watts
279550-YIM-A-0207
20 Unitary Products Group
Page 21
279550-YIM-A-0207
Table 15: Additional Static Resistance
Size
(Tons)
024
(2.0)
036
(3.0)
048
(4.0)
CFM Wet Indoor Coil Economizer
500 0.01 0.00 0.01 ­600 0.01 0.00 0.02 ­700 0.01 0.00 0.04 ­800 0.02 0.01 0.06 -
900 0.03 0.01 0.08 ­1000 0.04 0.01 0.10 ­1100 0.05 0.01 0.13 ­1200 0.06 0.02 0.16 -
700 0.01 0.00 0.04 -
800 0.02 0.01 0.06 -
900 0.03 0.01 0.08 ­1000 0.04 0.01 0.10 ­1100 0.05 0.01 0.13 ­1200 0.06 0.02 0.16 ­1300 0.07 0.03 0.17 ­1400 0.08 0.04 0.18 ­1100 0.02 0.02 0.04 ­1200 0.03 0.02 0.04 ­1300 0.04 0.02 0.05 ­1400 0.05 0.03 0.05 ­1500 0.06 0.04 0.06 ­1600 0.07 0.04 0.07 ­1700 0.07 0.04 0.08 ­1800 0.08 0.04 0.09 ­1900 0.09 0.05 0.10 ­2000 0.09 0.05 0.11 -
1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
1
Filter/Frame Kit Electric Heat
Table 16: Indoor Blower Speci fications
Size
(Tons)
024
(2.0)
036
(3.0)
048
(4.0)
HP RPM Eff. SF Frame
1/2 Variable 0.8 1.0 48
1 Variable 0.8 1.0 48
1 Variable 0.8 1.0 48
Motor
Blower Speed Selection
The variable speed blowers are designed to deliver constant CFM regardless of the external static pressure (ESP) in the ductwork. Therefore, if too many supply registers are closed, a filter becomes clogged, or there is a restriction in the ductwork, the motor will automatically operate at a higher speed to compensate for the higher ESP. This may result in a higher operating sound level.
These units have variable speed motors that automatically adjust to provide constant CFM from 0.2" to 0.6" w.c. static pressure. From 0.6" to 1.0" static pressure, CFM is reduced by 2% per 0.1" increase in static. Operation on duct systems with greater than 1.0" w.c. external static pressure is not recommended.
To Set Cooling CFM for DNX Units:
Refer to Airflow Performance Tables 13 and 14 for the possible cooling speed CFM selections.
Set “COOL” and “ADJ” Jumpers on the CFM selection board as indicated in Tables 13, 14 and Figure 14.
NOTE: CFM indicator light flashes once for every 100 CFM
(i.e. 12 flashes = 1200 CFM).
Do not change the "ADJ" tab position on the CFM selection board as this will change your cooling CFM previously selected.
To Set Delay Profile: Every unit has multiple cooling “blower off delay” profiles to
optimize system performance and efficiency. Refer to Table 17 for the regional climate in your area. Place the “DELAY” jumper tap on the CFM selection board on the appropriate pin setting.
Factory Set Gas Heat CFM: The blower speed required for gas heat is different than for
cooling. The heating CFM is factory set, but is adjustable.
Unitary Products Group 21
Page 22
279550-YIM-A-0207
The “Heat” Jumper on the CFM selection board should be set to “A”.
Fan Only CFM: When the connection is made from “R” to “G”, the fan only
mode is activated. In this mode, the blower will deliver 75% of the cooling system CFM. This connection is factory set from the manufacturer, but can be field adjusted.
:
:
5
<<
<
Figure 14: Control Board Speed Tap Location Table 17: Delay Profile
Delay Tap Regional Climate Type
Jumper at “A” Standard Setting Jumper at “B” Humid Climate Jumper at “C” Dry Climate Jumper at “D” Temperate Climate
Operation
The unit is controlled by a conventional heating/coo ling thermostat common to this class of equipment.
Heating Sequence Of Operation
Heat
The control board begins a call for heat when W1 is energized (connected to R). The control ignores W2 until pilot ignition has been established.
The control checks to see if the pressure switch is open. If the pressure switch is closed, the control board flashes “3” on the LED and waits indefinitely for it to open. When the pressure switch is sensed as open, the control begins pressure switch proving period. If the call for heat is lost, the control goes back to Standby.
Pressure Switch Proving
The control board energizes the induced draft motor (High speed for 2 stage model) and waits for the low pressure switch
to close. When the low pressure switch closes, the control begins Pre-purge period. If the call for heat is lost, the control de-energizes the inducer without post-purge and returns to standby.
If the low pressure switch does not close within 10 seconds of inducer energizing, the control board flashes “2” on the LED. If the pressure switch does not close within 5 minutes of inducer energizing, the control shuts off the inducer for 30 seconds, then energizes the inducer for another 5 minute try to close the pressure switch. This cycle continues indefinitely until either the pressure switch is proved closed, or the call for heat ends.
Pre-purge
The control board monitors the low pressure switch and ensures it remains closed during pre-purge. If the pressure switch opens, the control goes back to pressure switch proving mode. The control waits for a 15 second pre-purge period, then begins the ignition trial
Ignition Trial Period
The control board energizes the pilot gas valve and spark outputs for an 85 second Ignition trial. The control de-energizes the spark when flame is sensed and enters a flame stabilization period.
If flame is not established within the ignition trial period, the control de-energizes the spark and gas valve and begins an inter-purge period before attempting another ignition trial.
If the call for heat is lost during an ignition trial period, the control immediately de-energizes spark and gas. The control runs the inducer motor through a post purge period before de­energizing.
If the pressure switch is lost during an ignition trial period, the control immediately de-energizes spark and gas. The control begins pressure switch proving before an inter-purge and re­ignition attempt.
Pilot Flame Stabilization Period
The control board de-energizes the spark output, and waits for a 2 second flame stabilization period before energizing the main gas valve.
If flame is lost during the flame stabilization period, the control board counts it as a flame loss and retries ignition or locks out flashing a “5” on the LED.
Heat Blower On Delay
The control board waits for 30 seconds and then energizes the indoor blower heat speed. Blower on delay time begins at the start of flame proving period in the trial for ignition.
If the thermostat demand for heat is removed, the control de­energizes the gas valve, energizes the blower on heat speed and initiates a post-purge and heat blower off delay.
22 Unitary Products Group
Page 23
279550-YIM-A-0207
Main Burner Operation
High Heat Warm-up Two stage models run high heat for the first 60 seconds
following Pilot Flame Stabilization period regardless of W2 demand. If W2 is not energized at the end of this 60 second period the control de energizes the high gas output and steps the inducer to low speed. If W2 is energized the control remains on high heat.
There is no high heat warm-up on single stage models. Low Heat
The control board keeps the pilot gas valve, main gas valve and induced draft motor energized while continuously monitoring the call for heat, low pressure switch, and flame status.
If the call for heat (W1) is lost, the control de-energizes the gas valve and begins post purge.
If low pressure switch opens, the control de-energizes the gas valve and begins pressure switch proving mode.
If flame is lost, the control de-energizes the gas valve within 2.0 second and counts the flame loss. If flame has been lost more than 16 times within the same call for heat, the control board locks out flashing “5” on the LED. If flame has been lost less than 16 times, the control attempts re-ignition after a 300 second inter-purge period.
High Heat If the W2 terminal was energized more than 1 second before
W1 at the start of the call for heat, and remains continuously energized through the call for heat, the control considers it to be connected to a single stage thermostat and implements a 10 minute Auto staging feature. The 2nd stage thermostat call is ignored until 10 minutes into steady heat (9 minutes after high heat warm-up ended).
The control recognizes a call for 2nd stage heat when W2 is energized (connected to “R”). The control energizes the high gas output and induced draft motor on high speed.
Heat Blower Off Delay
The control board de-energizes the indoor blower motor afte r a delay time as selected by movable shunt (60, 90, 120 or 180 seconds). Blower timing begins when the thermostat is satisfied or heat cycle was interrupted. The control returns to standby when the blower off delay is complete.
If the thermostat call for heat returns before the blower off delay is complete, the control begins an ignition sequence with pre­purge while the blower off delay continues.
Lockout
While in lockout, the control board keeps the pilot gas valve, main gas valve and induced draft motor de-energized.
Lockouts due to failed ignition or flame losses may be reset by removing the call for heat (W1) for more than 1 second, but less than 20 seconds, or by removing power from the control for over 0.25 seconds. The control will automatically reset lockout after 60 minutes.
Lockouts due to detected internal control faults will reset after 60 minutes or power interruption.
High Temperature Limit Switch
Any time the high temperature limit switch is open the control board will run the indoor blower motor on heat speed, the inducer (on high speed for 2 stage models), de-energize the gas valve, and flash “6” on the LED. When the high temperature switch closes, the control will restart the ignition sequence beginning with pre-purge.
Rollout Switch
If the rollout switch opens for more than 0.25 seconds, the control board will run the inducer (on high speed for 2 stage models) for a post-purge period, immediately de-energize the gas valve, and flash “7” on the LED. The blower output will be energized during an open rollout condition.
If the rollout switch closes, the control shall remain locked out until power removed or “W” is removed.
If the call for 2nd stage heat goes away and the 1st stage call remains, the control de energizes the high gas valve, drops inducer speed to low, and returns to low heat operation.
Response to loss of W1, low pressure switch, and flame are identical to low heat operation.
Post Purge
The control board runs the induced draft motor for a 30 second post-purge period, and then de-energizes the inducer. If a call for heat occurs during post-purge, the control finishes the post­purge, drops inducer out to re-prove open pressure switch before continuing with the heat cycle.
Unitary Products Group 23
Rollout switch lockout shall not reset automatically.
Power Interruptions
Power interruptions of any duration shall not cause lockout or any operation requiring manual intervention.
Flame present with Gas off
If flame is sensed for longer than 4.0 seconds during a period when the gas valve should be closed, the control will enter lockout flashing “8” on the LED. The control will turn on the inducer blower while the flame is present.
Page 24
279550-YIM-A-0207
Welded Gas Valve Relay Response.
If either or both Pilot and Main Gas valve outputs are sensed to be off for more than 1 seconds when commanded to be on the control board shuts off all outputs and enters a hard lockout
If the Pilot valve or Main valve output is sensed to be energized for more than 1 second when commanded to be off, the control de-energizes the induced draft motor (if flame is not present) to attempt to open the pressure switch to de-energize the gas valve. If the pilot or main gas valve is still sensed as energized after the inducer has been off for 5 seconds, the control re­energizes the inducer to attempt to vent the unburned gas. In either case, the control enters a hard lockout. If the pilot or main valve becomes Un-Welded the inducer will de-energize, but the control will remain in a hard lockout.
During a hard lockout, the control board LED will remain off and the control will not respond to any thermostat demands.
The only way to recover from a hard lockout is to remove and then reapply 24VAC power to the control board.
Safety Controls
The control circuit includes the following safety controls:
1. Limit Switch (LS) - This control is located inside the heat exchanger compartment and is set to open at the temperature indicated in the Temperature Controls Table of the unit wiring diagram. It resets automatically. The limit switch operates when a high temperature condition caused by inadequate supply air flow occurs, thus shutting down the ignition control and closing the main gas valve and energizing the blower.
2. Pressure Switch (PS) - If the draft motor should fail, the pressure switch prevents the ignition controls and gas valves from being energized.
3. Flame Sensor - The flame sensor and controls are located per Proper Flame Adjustment Figure 19. If an ignition control fails to detect a signal from the flame sensor indicating the pilot flame is properly ignited, then the main gas valve will not open.
4. Rollout Switch (RS) - This switch is located in the burner vestibule. In the event of a sustained main burner flame rollout, it shuts off the ignition control and closes the main gas valve.
NOTE: The manual reset Rollout Switch (RS) must be reset
before allowing furnace operation.
5. Auxiliary Limit Switch (ALS) - This control is located inside the heat exchanger compartment and is set to open at 160°F. It is a manual reset switch. If ALS trips, then the primary limit (LS) has not functioned correctly. Replace the primary limit LS.
Table 18: Ignition Control Boar d FLASH CODES
Flash Code Description
On Steady Control Failure - Replace Control Heart Beat Normal Operation
1 Flash Not Applicable 2 Flashes Pressure / Centrifugal Switch Open with Inducer On 3 Flashes Pressure / Centrifugal Switch Closed with Inducer Off 4 Flashes Not Applicable 5 Flashes Lock Out From Too Many Flame Losses 6 Flashes High Temperature Switch Open (Primary or Aux.) 7 Flashes Rollout Switch Open 8 Flashes Flame Present With Gas OFF
Cooling Sequence Of Operations
When the thermostat calls for first-stage cooling, the thermostat terminals G and Y1 energize, signaling the compressor, indoor blower and outdoor fan to operate. The indoor blower will operate according to the fan delay profile selected using Table 17.
When the thermostat calls for second-stage cooling the thermostat terminal Y2 energizes, signaling the compressor bypass ports to close and the indoor blower to increase speed. If the outdoor fan motor has an ECM controller, Y2 will also signal the motor to increase speed.
When the thermostat is satisfied, terminals G, Y1 and Y2 are de-energized, thus stopping operation of the compressor and outdoor fan. The indoor blower will remain on according to the fan delay profile selected using Table 17.
Safety Controls
The control circuit includes the following safety controls:
1. High Pressure Switch (HP)- This switch protects against excessive discharge pressures due to a blocked condenser coil or a condenser motor failure (opens at 625 ± 25 psig and resets at 500 ± 25 psig).
2. Low Pressure Switch (LP)- This switch protects against loss of refrigerant charge (opens at 7 ± 3 psig and resets at 22 ± 5 psig).
The above pressure switches are specifically designed to operate with R-410A systems. R-22 pressure switches must not be used as replacements for the R-410A pressure switches.
The ability to properly perform maintenance on this equipment requires certain expertise, mechanical skills, tools and equipment. If you do not possess these, do not attempt to perform any maintenance other than those procedures recommended in this Installation Manual. Failure to heed this warning could result in serious injury and possible damage to this equipment.
24 Unitary Products Group
Page 25
279550-YIM-A-0207
A
Circulating Fan
When the thermostat calls for FAN, the thermostat terminal G is energized signaling the circulating fan to run at the heat speed 2 seconds after the G terminal is energized.
If a call for HEAT occurs, the circulating fan continues to run at the heat speed.
If a call for COOL occurs, the circulating fan switches to cool speed according to the fan delay profile selected in Table 17.
When the thermostat ends the call for FAN, the thermostat terminal G is de-energized, de-energizing the circulating fan.
Start-Up
Prestart Check List
Complete the following checks before starting the unit.
1. Check the type of gas being supplied. Be sure that it is the same as listed on the unit nameplate.
2. Make sure that the vent outlet air hood has been properly installed.
Operating Instructions
1. STOP! Read the information on the unit safety label.
2. Set the thermostat to the OFF position.
3. Turn off all electrical power to the unit.
4. DO NOT try to light the burners by hand. This appliance is equipped with an ignition device which automatically lights the burners.
5. Remove the access panel.
6. Turn the gas valve switch to the OFF position.
7. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow B in the information on the unit safety label. If you don't smell gas, go to the next step.
8. Turn the gas valve switch to the ON position.
9. Replace the control access panel.
10. Turn on all electric power to the unit.
11. Set the thermostat to the desired setting.
12. If the unit will not operate, follow the instructions To Turn Off Gas To Appliance and call your service technician or gas supplier.
To Turn Off Gas To Unit
1. Set the thermostat to the OFF position.
2. Turn off all electric power to the appliance if service is to be performed.
3. Remove the control access panel.
4. Turn the gas valve switch to the OFF position. DO NOT FORCE.
5. Replace the control access panel.
Post Start Check List
After the entire control circuit has been energized and the heating section is operating, make the following checks:
1. Check for gas leaks in the unit piping as well as the supply piping.
2. Check for correct manifold gas pressures. See Checking Gas Input.
3. Check the supply gas pressure. It must be within the limits shown on rating nameplate. Supply pressure should be checked with all gas appliances in the building at full fire. At no time should the standby gas line pressure exceed 13.5", nor the operating pressure drop below 4.5" for natural gas units. If gas pressure is outside these limits, contact the local gas utility for corrective action.
Manifold Gas Pressure Adjustment
Small adjustments to the gas flow may be made by turning the pressure regulator adjusting screw on the automatic gas valve. Refer to Figures 15 and 16.
Manual Gas Switch
Pilot
djustment
(Remove Cap)
Manifold Pressure Adjustment (Remove Cap)
Pilot Gas Connection
Figure 15: Single Stage Gas Valve Front
Electrical Connection
½ NPT
(Outlet)
Manifold Pressure Tap
Unitary Products Group 25
Page 26
279550-YIM-A-0207
Hi Fire (2nd Stage) Manifold Pressure
Low Fire (1st Stage) Manifold Pressure
Manual
Adjustment
Gas Switch
Pilot Adjustment (Remove Cap)
Pilot Gas Connect
Figure 16: Two Stage Gas Valve Front
Electrical Connection
Manifold Pressure Tap
½ NPT
(Outlet)
3. To increase the gas pressure, turn the adjusting screw clockwise.
NOTE: The correct manifold pressure for natural gas furnaces
is 3.5 IWG high heat and 1.5 IWG low heat. The correct manifold pressure for propane (LP) is 10.0 IWG high heat and 4.5 IWG low heat.
Burner Instructions
To check or change the burners, CLOSE THE MAIN MANUAL SHUT-OFF VALVE AND SHUT OFF ALL POWER TO THE UNIT.
1. Remove the two (2) #8 screws holding each burner in place.
2. Remove the burner assembly from the manifold assembly by moving the burner assembly forward, turn at an angle and pull back.
3. Burners are now accessible for service.
Pilot Instruction
To adjust the pilot flame:
3
"
min.
8
Line
½
NPT
(Inlet)
Pressure Tap
Figure 17: Single Stage Gas Valve Rear
½ NPT
(Inlet)
Line Pressure Tap
Figure 18: Two Stage Gas Valve Rear
Adjust as follows:
1. Remove the cap from the valve body. See Figures 15 and 16 for location.
2. To decrease the gas pressure, turn the adjusting screw counterclockwise.
Spark Ignitor
Pilot
Flame Sensor
Figure 19: Proper Flame Adjustment
1. Remove the pilot adjustment cover screw.
2. Adjust the pilot adjustment screw to achieve the proper pilot flame.
3. The pilot flame should envelope 3/8” of the end of the flame sensor and not contain any yellow color, see Figure 19.
4. Replace the pilot adjustment cover screw after the pilot flame is set.
To check, adjust or remove the pilot assembly, CLOSE THE MAIN MANUAL SHUT-OFF VALVE AND SHUT OFF ALL POWER TO THE UNIT.
1. Disconnect the wiring from the control board to the pilot assembly.
2. Remove the two (2) #8 screws holding the pilot assembly in place.
3. Remove the pilot assembly.
26 Unitary Products Group
Page 27
279550-YIM-A-0207
Adjustment of Temperature Rise
After about 20 minutes of high heat operation, determine the furnace temperature rise. Take readings of both the return air and the heated air in the ducts about six feet from the furnace where they will not be affected by radiant heat.
The temperature rise (or temperature difference between the return air and the heated air from the furnace) must lie within the range shown on the rating plate and the data in Tables 9 and 11.
After the temperature rise has been determined, the CFM can be calculated as follows:
'HJUHHV)7HPS5LVH 
%78+2XWSXW
[&)0
25
&)0 
['HJUHHV)7HPS5LVH
Direct Drive Blower
All units have direct drive, constant CFM blower motors.
%78+2XWSXW
Checking Gas Heat Input
Natural Gas
1. Turn off all other gas appliances connected to the gas meter.
2. With the furnace turned on, measure the time needed for one revolution of the hand on the smallest dial on the meter. A typical gas meter usually has a 1/2 or a 1 cubic foot test dial.
3. Using the number of seconds for each revolution and the size of the test dial increment, find the cubic feet of gas consumed per hour from Table 19.
If the actual input is not within 5% of the furnace rating with allowance being made for the permissible range of the regulator setting, replace the orifice spuds with spuds of the proper size.
NOTE: To find the BTU input, multiply the number of cubic feet
of gas consumed per hour by the BTU content of the gas in your particular locality. (Contact your gas company for this information since it varies widely from city to city.)
Table 19: Gas Rate Cubic Feet Per Hour
Seconds for
One Rev.
10 180 360 12 150 300 14 129 257 16 113 225 18 100 200 20 90 180 22 82 164 24 75 150 26 69 138 28 64 129 30 60 120 32 56 113 34 53 106 36 50 100 38 47 95 40 45 90 42 43 86 44 41 82 46 39 78 48 37 75 50 36 72 52 35 69 54 34 67 56 32 64 58 31 62 60 30 60
1. EXAMPLE: By actual measurement, it takes 38 seconds for the hand on the 1-cubic foot dial to make a revolution with just a 100,000 BTUH furnace running. Using this information, locate 38 seconds in the first column of Table 19. Read across to the column headed “1 Cubic Foot,” where you will see that 95 cubic feet of gas per hour are consumed by th e furna ce at th at rate. Multiply 95 x 1050 (the BTU rating of the gas obta ined from the local gas company). The result is 99,750 BTUH, which is close to the 100,000 BTUH rating of the furnac e.
Size of Test Dial
1/2 cu. ft. 1 cu. ft.
1
Unitary Products Group 27
Page 28
Typical Wiring Diagrams
Typical DNX024 Cooling Unit with Single Stage Gas Heat 208/230-1-60 volt Wiring Diagram
279550-YIM-A-0207
28 Unitary Products Group
Page 29
279550-YIM-A-0207
Typical DNX024 Cooling Unit with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram
Unitary Products Group 29
Page 30
Typical DNX036-048 Cooling Unit with Single Stage Gas Heat 208/230-1-60 volt Wiring Diagram
279550-YIM-A-0207
30 Unitary Products Group
Page 31
279550-YIM-A-0207
Typical DNX036-048 Cooling Unit with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram
Unitary Products Group 31
Page 32
Typical DNX036-048 Cooling Unit with Single Stage Gas Heat 208/230-3-60 volt Wiring Diagram
279550-YIM-A-0207
32 Unitary Products Group
Page 33
279550-YIM-A-0207
Typical DNX036-048 Cooling Unit with Two Stage Gas Heat 208/230-3-60 volt Wiring Diagram
Unitary Products Group 33
Page 34
Typical DNX036-048 Cooling Unit with Single Stage Gas Heat 460-3-60 volt Wiring Diagram
279550-YIM-A-0207
34 Unitary Products Group
Page 35
279550-YIM-A-0207
Typical DNX036-048 Cooling Unit with Two Stage Gas Heat 460-3-60 volt Wiring Diagram
Unitary Products Group 35
Page 36
R-410A QUICK REFERENCE GUIDE
Refer to Installation Instructions for specific installation requirements.
R-410A Refrigerant operates at 50 - 70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A. R-410A Refrigerant cylinders are rose colored. Recovery cylinder service pressure rating must be 400 psig, DOT 4BA400, or DOT BW400. Recovery equipment must be rated for R-410A. Do Not use R-410A service equipment on R-22 systems. All hoses, gages, recovery cylinders, charging cylinders and recovery equipment must be dedicated for use on R-410A systems only. Manifold sets must be at least 700 psig high side, and 180 psig low side, with 550 psig retard. All hoses must have a service pressure rating of 800 psig. Leak detectors must be designed to detect HFC refrigerants. Systems must be charged with liquid refrigerant. Use a commercial type metering device in the manifold hose. R-410A can only be used with POE type oils. POE type oils rapidly absorb moisture from the atmosphere. Vacuum pumps will not remove moisture from POE type oils. Do not use liquid line driers with a rated working pressure rating less than 600 psig. Do not install suction line driers in the liquid line. A liquid line drier is required on every unit. Do not use a R-22 TXV. If a TXV is to be used, it must be a R-410A TXV. Never open system to atmosphere when under a vacuum. If system must be opened for service, evacuate system then break the vacuum with dry nitrogen and replace all filter driers.
Figure 20: R-410A Quick Reference Guide
Subject to change without notice. Printed in U.S.A. 279550-YIM-A-0207 Copyright © 2007 by Unitary Products Group. All rights reserved. Supersedes: 98811-YIM-C-1006
Unitary 5005 Norman Products York OK Group Drive 73069
Loading...