York DM 078 User Manual

TECHNICAL GUIDE
246645-YTG-C-0708
®

DESCRIPTION

®
YORK® Predator® units are convertible single packages with a common footprint cabinet and common roof curb for all 6-1/2 through 12-1/2 ton models. All units have two compressors with independent refrigeration circuits to pro­vide two stages of cooling. The units were designed for commercial applications and can be easily installed on a roof curb, slab, or frame.
STANDARD EFFICIENCY SINGLE PACKAGE AIR CONDITIONERS AND SINGLE PACKAGE GAS/ELECTRIC UNITS
DM 078, 090, 102, 120 and 150 6-1/2, 7-1/2, 8-1/2, 10 and 12-1/2 NOMINAL TONS
9.0 EER
®
All Predator rigid full perimeter base rails allowing for 3-way forklift access and overhead rigging. Every unit is completely charged, wired, piped, and tested at the factory to provide a quick and easy field installation.
All units are convertible between side and down airflow. A independent economizer design is used on side and down discharge applications, as well as all tonnage sizes.
Predator tions: cooling only, cooling with electric heat, and cooling with gas heat. Electric heaters are available as factory­installed options or field-installed accessories.
Tested in accordance with:
units are self-contained and assembled on
®
units are available in the following configura-
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
246645-YTG-C-0708

TABLE OF CONTENTS

DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3
FACTORY INSTALLED OPTIONS . . . . . . . . . . . . . . . . . . .5
FIELD INSTALLED ACCESSORIES . . . . . . . . . . . . . . . . . 6
NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . .46

LIST OF FIGURES

Fig. # Pg. #
1PREDATOR® COMPONENT LOCATION . . . . . . . . . . . . . 3
2 UNIT 4 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
3 UNIT CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . . 35
4 UNIT 6 POINT LOAD . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5 UNIT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
6PREDATOR 7 SUNLINE™ TO PREDATOR
CURBS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
8 BOTTOM DUCT OPENINGS (FROM ABOVE) . . . . . . . . 38
9 REAR DUCT DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . 39
10 DOWNFLOW ECONOMIZER HOOD DETAIL . . . . . . . . 39
11 FACTORY INSTALLED DOWNFLOW ECONOMIZER . . 40 12 FIELD INSTALLED DOWNFLOW ECONOMIZER
W/POWER EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
13 FIELD INSTALLED HORIZONTAL ECONOMIZER
W/POWER EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
14 SLAB ECONOMIZER DOWNFLOW W/POWER
EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
15 SLAB ECONOMIZER END RETURN W/POWER
EXHAUST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
16 COOLING UNIT WITH GAS HEAT WIRING 230 VOLT
DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
17 COOLING UNIT WITH/WITHOUT ELECTRIC HEAT
WIRING DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 44
18 COOLING UNIT WITH GAS HEAT WIRING 460, 575 VOLT
AND 50 HZ DIAGRAM . . . . . . . . . . . . . . . . . . . . . . . . . . 45
®
ROOF CURB DIMENSIONS . . . . . . . . . . 37
®
TRANSITION ROOF

LIST OF TABLES

Tbl. # Pg. #
1 ACCESSORIES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
2 DM PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
3 DM CAPACITY RATINGS . . . . . . . . . . . . . . . . . . . . . . . . . . .12
4 UNIT VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . . . . . .12
5 COOLING CAPACITY DM078 (6-1/2 TON) UNIT . . . . . . . .13
6 COOLING CAPACITY DM090 (7-1/2 TON) UNIT . . . . . . . .14
7 COOLING CAPACITY DM102 (8-1/2 TON) UNIT . . . . . . . .15
8 COOLING CAPACITY DM120 (10 TON) UNIT . . . . . . . . . .16
9 COOLING CAPACITY DM150 (12-1/2 TON) UNIT . . . . . . .17
10 ELECTRICAL DATA DM078 (6-1/2 TON) STD EFFICIENCY
W/O PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . . .18
Tbl. # Pg. #
11 ELECTRICAL DATA DM078 (6-1/2 TON) STD EFFICIENCY
WITH PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . 18
12 ELECTRICAL DATA - DM090 (7-1/2 TON) STANDARD
EFFICIENCY W/O PWRD CONV. OUTLET . . . . . . . . . . . . 19
13 ELECTRICAL DATA - DM090 (7-1/2 TON) STANDARD
EFFICIENCY W/PWRD CONV. OUTLET . . . . . . . . . . . . . . 19
14 ELECTRICAL DATA DM102 (8-1/2 TON) STD EFFICIENCY
W/O PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . . 20
15 ELECTRICAL DATA DM102 (8-1/2 TON) STD EFFICIENCY
WITH PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . 20
16 ELECTRICAL DATA DM120 (10 TON) STD EFFICIENCY W/
O PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . 21
17 ELECTRICAL DATA DM120 (10 TON) STD EFFICIENCY
WITH PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . 21
18 ELECTRICAL DATA DM150 (12-1/2 TON) STD EFFICIENCY
W/O PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . . 22
19 ELECTRICAL DATA DM150 (12-1/2 TON) STD EFFICIENCY
W/PWRD CONVENIENCE OUTLET . . . . . . . . . . . . . . . . . . 22
20 ELECTRIC HEAT MULTIPLIERS . . . . . . . . . . . . . . . . . . . . . 22
21 DM078 (6-1/2 TON) SIDE SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
22 DM090 (7-1/2 TON) SIDE SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
23 DM102 (8-1/2 TON) SIDE SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
24 DM120 (10 TON) SIDE SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
25 DM150 (12-1/2 TON) SIDE SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
26 DM078 (6-1/2 TON) DOWN SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
27 DM090 (7-1/2 TON) DOWN SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
28 DM102 (8-1/2 TON) DOWN SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
29 DM120 (10 TON) DOWN SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
30 DM150 (12-1/2 TON) DOWN SHOT BLOWER
PERFORMANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
31 ADDITIONAL STATIC RESISTANCE DM078, 120
AND 150 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
32 ADDITIONAL STATIC RESISTANCE DM090, 102 . . . . . . . 33
33 ELECTRIC HEAT MINIMUM SUPPLY AIR CFM . . . . . . . . 34
34 INDOOR BLOWER SPECIFICATIONS . . . . . . . . . . . . . . . . 34
35 POWER EXHAUST SPECIFICATIONS . . . . . . . . . . . . . . . . 34
36 4 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
37 6 POINT LOAD WEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
38 UNIT WEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
39 UNIT HEIGHT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
40 UNIT CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
41 ECONOMIZER USAGE . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
2 Johnson Controls Unitary Products
246645-YTG-C-0708
Simplicity™ control board w/screw connector for T-stat wiring and network connections
Terminal block for hi-voltage connection
Second model nameplate inside hinged access panel
Dual stage cooling for maximum comfort
Compressor #2 access (high efficiency compressor w/crankcase heater)
Base rails w/forklift slots (three sides) and lifting holes
Roof curbs in eight- and fourteen-inch heights. Roof curbs for transitioning from York Sunline™ footprint to the ZH Series footprints are also available (field-installed accessory)
-
Disconnect location (optional disconnect switch)
Toolless door latch
Side entry power and control wiring knockouts
Filter access (2” throw-away)
Slide-out drain pan with steel 3/4” NPT, female connection
Compressor #1 access (high-efficiency compressor w/crankcase heater)

FIGURE 1 - PREDATOR® COMPONENT LOCATION (DM 120 SHOWN)

Filter drier (solid core)
Condenser section
Slide-out motor and blower assembly for easy adjustment and service
Belt-drive blower motor
Power ventor motor
20-gauge alumi­nized steel tubular heat exchanger for long life (stainless steel option)
Two-stage gas heating to maintain warm, comfortable temperature
Intelligent control board for safe and efficient operation

FEATURES

Standard Efficiency– All standard efficiency units have a minimum EER of 9.0. Gas/electric units have elec­tronic spark ignition and power vented combustion with steady state efficiencies of 80%.
®
Service Friendly – The Predator ber of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common assembly. This facilit ates greater access to all the indoor airflow components, thus simplifying maintenance and adjustment.
Service time is reduced through the use of hinged, tool­less panels. Such panels provide access to frequently inspected components and areas, including the control box, compressors, filters, indoor motor & blower, and the heating section. The panels are screwed in place at the factory to prevent access by children or other una uthor­ized persons. It is recommended that the panels be secured with screws once service is complete.
incorporates a num-
Service windows have been placed in both condenser section walls. Rotation of the cover allows easy access to the condenser coils for cleaning or inspection.
Both the unit control board and ignition control board utilize flash codes to aid in diagnosis of unit malfunctions. Unique alarm codes quickly identify the source of the unit alarm.
All units use the same standard filter size. This stan­dardization removes any confusion on which filter sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to per­mit easy cleaning. The drain pan is accessed by remov­ing the drain pan cover plate on the rear of the unit. Once the plate is removed, the drain pan slides out through the rear of the unit.
®
All Predator
units have a second model nameplate located inside the control access door. This is to prevent deterioration of the nameplate through weathering.
Environmentally Aware – For improved Indoor Air Quality, foil faced insulation is used exclusively through­out the units.
Johnson Controls Unitary Products 3
246645-YTG-C-0708
Balanced Heating – The Predator® offers “Ultimate Heat­ing Comfort” with a balance between 1st and 2nd stage gas heating. The 1st stage of a gas heat Predator® unit provides 60% of the heating capacity. Balanced heating allows the unit to better maintain desired temperatures.
Convertible Airflow Design – The side duct openings are covered when they leave the factory. If a side sup­ply/return is desired, the installer simply removes the two side duct covers from the outside of the unit and installs them over the down shot openings. No panel cutting is required. Convertible airflow design allows maximum field flexibility and minimum inventory.
System Protection - Suction line freezestats are supplied on all units to protect against loss of charge and coil frost­ing when the economizer operates at low outdoor air tem­peratures while the compressors are running. Every unit has solid-core liquid line filter-driers and high and low­pressure switches. Internal compressor protection is stan­dard on all compressors. Crankcase heaters are standard on reciprocating compressors. Scroll compressors do not require crankcase heaters. Phase Monitors are standard on units with scroll compressors. This accessory monitors the incoming power to the unit and protects the unit from phase loss and reversed phase rotation.
Advanced Controls - Simplicity™ control boards have standardized a number of features previously available only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down to 0°F outdoor ambient without additional assis­tance. Optionally, the control board can be pro­grammed to lockout the compressors when the outdoor air temperature is low or when free cooling is available.
Anti-Short Cycle Protection - To aid compressor
life, an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured by programmable minimum run times. For testing, the anti-short cycle delay can be temporarily overridden with the push of a button.
Fan Delays - Fan on and fan off delays are fully pro-
grammable. Furthermore, the heating and cooling fan delay times are independent of one another. All units are programmed with default values based upon their configuration of cooling and heat.
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the gas valve, if applicable, and the temperature limit switch on gas and electric heat units. The unit con­trol board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a “three times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before th e unit control board will lock out the associated compressor.
On Board Diagnostics - Each alarm will energize a trouble light on the thermostat, if so equipped, and flash an alarm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own flash code. The control board saves the five most recent alarms in memory, and these alarms can be reviewed at any time. Alarms and programmed values are retained through the loss of power.
Reliable – From the beginning – All units undergo com­puter automated testing before they leave the factory. Units are tested for refrigerant charge and pressure, unit amperage, and 100% functionality. For the long term –
®
All Predator
units are painted with a long lasting, pow­der paint that stands up over the life of the unit. The paint used has been proven by a 1000 hour salt spray test.
Flexible Placement – All models and configurations share the same cabinet/footprint and thus the same roof curb. You have the flexibility to set one curb and choose the correct tonnage size and heating option after the internal loads have been determined.
To further simplify planning and installation, Predator cabinets are designed to fit your roof. With the optional roof curb, the unit ductwork is designed to fit around 24” on-center joists or between 48” on-center joists.
The drain pan can be rotated to drain to either the front or the rear of the unit. Additionally, the drain pan can be piped to drain through the roof curb. As it is sometimes difficult to have a level installation, the drain pan features a generous slope to ensure proper drainage.
Full Perimeter Base Rails – The permanently attached base rails provide a solid foundation for the entire unit and protect the unit during shipment. The rails offer fork­lift access from 3 sides, and rigging holes are available so that an overhead crane can be used to place the units on a roof.
Easy Installation – Gas and electric utility knockouts are supplied in the unit underside as well as the side of the unit. A clearly identified location is provided to mount a field supplied electrical disconnect switch. Utility con­nections can be made quickly and with a minimum amount of field labor.
All units are shipped with 2” filters installed.
Wide Range of Indoor Airflows – All indoor fan motors are belt-drive type providing maximum flexibility to han­dle most airflow requirements. For high static applica­tions, factory installed alternate indoor fan motors are available. With the optional indoor fan motor, all units can supply nominal airflow at a minimum of 1.5” ESP.
Warranty - All mo dels include a 1-year limited warranty on the complete unit. Compressors and electric heater elements each carry a 5-year warranty . Aluminized steel and stainless steel tubular heat exchangers carry an additional 10-year warranty.
®
4 Johnson Controls Unitary Products
246645-YTG-C-0708

FACTORY INSTALLED OPTIONS

YORK® offers several equipment options factory installed, for the Predator® line.
Optional Factory Installed Economizers - Predator units offer a variety of optional factory installed econo­mizers with low leak dampers. The outdoor air enthalpy sensor enables economizer operation if the outdoor enthalpy is less than the setpoint of the economizer logic module. See Table 41 to determine the correct econo­mizer for your application.
Downflow Economizer - (With barometric relief) -
The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type, and is shipped installed and wired. The installer needs only to assemble and mount the outdoor air hood (Pro­vided). The economizer has spring return, fully modu­lating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to econo­mizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the economizer control accepts an optional CO demand ventilation. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit provides a second input used to monitor the return air. With a dual input kit installed, the econ­omizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible.
Horizontal Economizer - (Without barometric
relief) - All features of the downflow economizer exist except you must order the duct mount baro­metric relief separately. Y ou must order a 1EH0408
if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizers only.
BAS Ready Economizer -(With barometric relief)
- The economizer is provided with a Belimo actuator that requires a 0-10V DC input from an external source (i.e., field installed building automation sys­tem controller). Power exhaust options are avail­able. The economizer is 2% low leakage type with spring return and fully modulating dampers capable of introducing up to 100% outside air. Also include 2” pleated filters.
Slab Economizer for Energy Recovery Ventilators-
(With barometric relief and Fresh Air Hood) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type, and is shipped installed and wired. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the outdoor air intake dampers open, the return air damp-
input for
2
ers close. The changeover from mechanical refrigera­tion to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. To meet regulated air standards, the economizer control accepts an optional
input for demand ventilation. With single enthalpy
CO
2
input, the economizer control monitors outdoor air. The dual enthalpy kit provides a second input used to mon­itor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible.
Power Exhaust (Downflow only) - This accessory installs in the unit with a down flow economizer.
Motorized Outdoor Air Damper - The motorized out­door air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The out­door air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.
Alternate Indoor Blower Motor - For applications with high static restrictions, units are offered with optional indoor motors that provide higher static output and/or higher airflow, depending upon the installer’s needs.
Aluminized Steel Gas Heat Exchanger - For applica­tions in non-corrosive environments.
Stainless Steel Gas Heat Exchanger - For applications in corrosive environments, this option provides a full stainless steel heat exchanger assembly.
Stainless Steel Drain Pan - An optional rust-proof stain­less steel drain pan is available to provide years of trou­ble-free operation in corrosive environments.
Electric Heaters - The electric heaters range from 9kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. All heaters are intended for single point power supply.
Disconnect Switch - For gas heat units and cooling units with electric heat, an HACR breaker sized to the unit is provided. For cooling only units, a switch sized to the largest electric heat available for the particular unit is provided. Factory installed option only.
Convenience Outlet - (Non-Powered /Powered) - This option locates a 120V single-phase GFCI outlet with cover, on the corner of the unit housing adjacent to the compressors. The “Non-powered” option requires the installer to provide the 120V single-phase power source and wiring. The “Powered” option is powered by a step­down transformer in the unit. Factory installed option only.
Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment. Avail abl e for both the supply and/or return air.
Johnson Controls Unitary Products 5
246645-YTG-C-0708
Factory installed smoke detectors in the return air, may be subjected to freezing temperatures during "off" times due to out side air infiltration. These smoke detectors have an operational limit of 32 °F to 131°F. Smoke detectors installed in areas that could be out side those limitations will have to be moved to prevent having false alarms.
Phase Monitors - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of phase condition. (Standard on unit s with Scroll Co mpressors.)
Coil Guard - Customers can purchase a coil guard kit to protect the condenser coil from damage. Additionally, this kit stops animals and foreign objects from entering the space between the inner condenser coil and the main cabinet. This is not a hail guard kit.
Dirty Filter Switch - This kit includes a differential pres­sure switch that energizes the fault light on the unit ther­mostat, indicating that there is an abnormally high pressure drop across the filters. Factory installed option or field installed accessory.
T echni coat C ondense r Coil s - The condenser coils are coated with a phenolic coating for protection against cor­rosion due to harsh environments.
Technicoat Evaporator Coil - The evaporator coils are coated with a phenolic coating for protection against cor­rosion due to harsh environments.
BAS - Building Automation System Controls Simplic-
ity™ INTELLI-Comfort™ Control - The York® Simplic­ity™ INTELLI-Comfort™ control is factory installed. It
includes a supply air sensor, a return air sensor, and an outside air sensor. There are provisions for a field installed dirty filter indicator switch, an air-proving switch, an Out­side Air Humidity sensor, a Return Air Humidity sensor, an Inside IAQ sensor, and an Outside Air IAQ sensor. Con­struction mode operation, 365-day real time clock with 7 day programming plus holiday scheduling is built-in. Two different modes of demand ventilation are achieved through the INTELLI-Comfort™ using CO uses an inside CO It can also use an Outside CO
sensor to perform Demand Ventilation.
2
sensor to perform Differen-
2
sensors. It
2
tial Demand Ventilation. It uses a Patented Comfort Venti­lation algorithm to provide comfortable ventilation air temperature. The patented economizer-loading algorithm will protect the equipment when harsh operating conditions exist. Humidity in the occupied space or return duct can be monitored and controlled via humidity sensors and the on­board connection for hot gas re-heat system. It uses the INTELLI-Start™ algorithm to maximize energy savings by recovering the building from the Unoccupied Setpoints to the Occupied Setpoints just in time for the Occupied Time Period to begin. The Simplicity™ INTELLI-Comfort™ bal­ances space temperature, ventilation air temperature, CO and humidity for ultimate comfort.
Simplicity™ INTELLI-Comfort™ with ModLINC Control - The York® Simplicity™ INTELLI-Comfort™ with ModLINC control is factory installed. It includes all the features of the INTELLI-Comfort™ control with an additional control to translate communications from MODBUS to the BACnet MSTP protocol.
Novar® BAS Control - The Novar® ETC-3 building automation system controller is factory installed. Incudes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
Johnson Controls BAS Control - The Johnson Control YK-UNT-1126 building automation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch, and air proving switch.
CPC BAS Control - The Computer Process Controls Model 810-3060 ARTC Advanced Rooftop building auto­mation system controller is factory installed. Includes supply air sensor, return air sensor, dirty filter indicator switch and air proving switch.
Honeywell BAS Control - The Honeywell W7750C building automation system controller is factory installed. Includes air supply sensor, return air sensor, dirty filter indicator switch, and air proving switch.
York Commercial Comfort System (YCCS) - Provides rooftop system integration for YCCS single zone and change-over bypass systems.

FIELD INSTALLED ACCESSORIES

YORK® offers several equipment accessories for field instal­lation, for the Predator
Downflow Economizer - (With barometric relief) - The economizer is provided with a single enthalpy input. The economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the out­door air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. T o meet regulated air standards, the economizer
control accepts an optional CO tion. With single enthalpy input, the economizer control
monitors outdoor air. The dual enthalpy kit provides a sec­ond input used to monitor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible
Horizontal Economizer - (Without barometric relief) - All features of the downflow economizer exist except you must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a power exhaust. You can order a 1RD0411 Barometric Relief for horizontal flow economizer.
Slab Economizer for Energy Recovery Ventilator-
2
(Without barometric relief or Fresh Air Hood) - The economizer is provided with a single enthalpy input. The
®
line.
input for demand ventila-
2
6 Johnson Controls Unitary Products
246645-YTG-C-0708
economizer is 2% low leakage type. The economizer has spring return, fully modulating damper actuators and is capable of introducing up to 100% outdoor air. As the out­door air intake dampers open, the return air dampers close. The changeover from mechanical refrigeration to economizer operation is regulated by the standard single enthalpy input. There is an optional input dual dry bulb available. T o meet regulated air standards, the economizer control accepts an optional CO
input for demand ventila-
2
tion. With single enthalpy input, the economizer control monitors outdoor air. The dual enthalpy kit provides a sec­ond input used to monitor the return air. With a dual input kit installed, the economizer control compares the values of the two enthalpy or temperature inputs and positions the dampers to provide the maximum efficiency possible.
You can order 1EH0409 Barometric Relief/FA Hood for field installations without an ERV.
Dual Enthalpy Control, Accessory - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
Barometric Relief Damper - Zero to 100% capacity barometric relief dampers for use with horizontal flow, or field installed slab economizers.
Power Exhaust - This accessory installs in the unit with a down flow economizer. Power exhaust plugs into the connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a hori­zontal flow application.
Manual Outdoor Air Damper - Like the motorized out- door air damper , each manual outdoor air damper includes a slide-in damper assembly with an outdoor air hood and filters. Customers have a choice of dampers with ranges of 0% to 100% or 0% to 35% outdoor air entry.
Motorized Outdoor Air Damper - The motorized out­door air damper includes a slide-in/plug-in damper assembly with an outdoor air hood and filters. The out­door air dampers open to the preset position when the indoor fan motor is energized. The damper has a range of 0% to 100% outdoor air entry. Factory installed option or field installed accessory.
Smoke Detectors - The smoke detectors stop operation of the unit by interrupting power to the control board if smoke is detected within the air compartment.
CO
Sensor - Senses CO2 levels and automatically
2
overrides the economizer when levels rise above the preset limits.
Dirty Filter Switch - This kit includes a differential pres­sure switch that energizes the fault light on the unit ther­mostat, indicating that there is an abnormally high pressure drop across the filters.
Coil Guard - Field installed decorative wire coil guard.
Hail Guard - This kit includes a sloped hood which installs over the outside condenser coil and prevents damage to the coil fins from hail strikes. Field installed accessory only.
Flue Exhaust Extension Kit - In locations with wind or weather conditions which may interfere with proper exhausting of furnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
-60°F Gas Heat Kit - For installations which require gas heat units to perform in low ambient temperatures, a gas section heating kit is available. This kit provides electric heat in the gas heat controls section to ensure the gas valve and controls will continue to function properly at extremely low temperatures.
Gas Heat High Altitude Kit - This kit converts a gas heat unit to operate at high altitudes, 2,000 to 6,000 feet. Con­version kits are available for natural gas and propane.
Gas Heat Propane Conversion Kit - This kit converts a gas-fired heater from natural gas to propane. It cont ains the main burner orifices and gas valve replacement springs.
Gas Piping Kit - Contains pipe nipples, fittings and gas cock required for gas supply connection with external shut off.
Electric Heaters - The electric heaters range from 9 kW to 54kW and are available in all the voltage options of the base units. All heaters are dual staged. Cooling units include an adapter panel for easy installation of the elec­tric heaters. Necessary hardware and connectors are included with the heaters. All heaters are intended for single point power supply.
Low Limit / Compressor Lockout Kit
1. Compressor Lockout (CLO): To prevent mechani-
cal (compressorized) operation of the unit during cold outdoor conditions where there is a risk of returning liquid refrigerant back to the compressors.
2. Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing the units first stage heating means when there is a demand for cooling during cold outside conditions.
Metal Frame Filter Kit - Metal frame with polyester filter medium.
Permanent Filters - Permanent filters are available.
Roof Curbs - The roof curbs have insulated decks and are shipped disassembled The roof curbs are available in 8” and 14” heights. For applications with security con­cerns, burglar bars are available for the duct openings of the roof curbs.
Roof Curb Transition - Single Piece Adapter (10” High) ­Roof curbs for transitioning from Sunline™ units to Preda-
®
units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
tor
Burglar Bars - Mount in the supply and return openings to prevent entry into the duct work.
Thermostat - The units are designed to operate with 24- volt electronic and electro-mechanical thermostats. All units (with or without an economizer) operate with two­stage heat/two-stage cool or two-stage cooling only ther­mostats, depending upon unit configuration.
Johnson Controls Unitary Products 7
246645-YTG-C-0708
TABLE 1: ACCESSORIES
Part Number Description Weight
1RC0470 Roof Curb, 8" Height ­1RC0471 Roof Curb, 14" Height ­1RC0472 Roof Curb, Transition (7.5 T through 12.5 T) ­1BD0408 Burglar Bars, Downflow ­2TP04520925 Electric Heat 9kW 230V ­2TP04521825 Electric Heat 18kW 230V ­2TP04522425 Electric Heat 24kW 230V ­2TP04523625 Electric Heat 36kW 230V ­2TP04525425 Electric Heat 54kW 230V ­2TP04520946 Electric Heat 9kW 460V ­2TP04521846 Electric Heat 18kW 460V ­2TP04522446 Electric Heat 24kW 460V ­2TP04523646 Electric Heat 36kW 460V ­2TP04525446 Electric Heat 54kW 460V ­2TP04520958 Electric Heat 9kW 575V ­2TP04521858 Electric Heat 18kW 575V ­2TP04522458 Electric Heat 24kW 575V ­2TP04523658 Electric Heat 36kW 575V ­2TP04525458 Electric Heat 54kW 575V ­2TP04540925 Electric Heat 9kW 230V, 42" Tall Cabinet ­2TP04541825 Electric Heat 18kW 230V, 42" Tall Cabinet ­2TP04542425 Electric Heat 24kW 230V, 42" Tall Cabinet ­2TP04543625 Electric Heat 36kW 230V, 42" Tall Cabinet ­2TP04540946 Electric Heat 9kW 460V, 42" Tall Cabinet ­2TP04541846 Electric Heat 18kW 460V, 42" Tall Cabinet ­2TP04542446 Electric Heat 24kW 460V, 42" Tall Cabinet ­2TP04543646 Electric Heat 36kW 460V, 42" Tall Cabinet ­2TP04540958 Electric Heat 9kW 575V, 42" Tall Cabinet ­2TP04541858 Electric Heat 18kW 575V, 42" Tall Cabinet ­2TP04542458 Electric Heat 24kW 575V, 42" Tall Cabinet ­2TP04543658 Electric Heat 36kW 575V, 42" Tall Cabinet ­1FA0411 Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief) ­1FA0412 Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief) ­2MD04702724 Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief) ­2MD04703324 Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief) 2EE04705424 Economizer, Downflow (Incl. Barometric Relief & All Hoods) 124 lbs. 2EE04705524 Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief) 97 lbs. 2EE04705224 Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief) 2EE04705624 "Downflow Economizer, Slab type for ERV (no Barometric Relief or FA hood)", 42" Tall Cabinet ­2PE04703225 Power Exhaust, Downflow, 230V (For Units with Economizer only) ­2PE04703246 Power Exhaust, Downflow, 460V(For Units with Economizer only) ­2PE04703258 Power Exhaust, Downflow, 580V (For Units with Economizer only) ­2EC04700924 Dual Enthalpy Control (Use with Single Enthalpy Economizer) ­1EH0407 Hood Kit, Downflow Economizer (Included with all Downflow Economizers) 1RD0411 Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood) 1EH0408 Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood) 25 lbs. 1EH0409 Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood) ­2AQ04700424 CO2 Detector Unit Mount ­2AQ04700324 CO2 Detector Space Mount ­2SD04700424 Smoke Detector, Supply or Return (Return Not Available with Horizontal Economizer) ­2MK04700624 Low Limit / Compressor Lockout Kit 1CG0419 Coil Guard (Electric / Electric & HP models) -
8 Johnson Controls Unitary Products
246645-YTG-C-0708
TABLE 1: ACCESSORIES (CONTINUED)
Part Number Description Weight
1CG0420 Coil Guard (Gas / Electric models) ­1CG0427 Coil Guard (Electric / Electric & HP Models), 42" Tall Cabinet ­1CG0428 Coil Guard (Gas / Electric Models), 42" Tall Cabinet ­1HG0411 Hail Guard Kit ­1HG0415 Hail Guard Kit, 42" Tall Cabinet ­1GP0405 Gas Piping Kit ­1NP0442 Propane Conversion Kit ­1HA0442 High Altitude Kit for Natural Gas ­1HA0443 High Altitude Kit for Propane ­1FE0412 Flue Exhaust Extension Kit ­2BC04700106 Gas Heat Kit, -60 deg F, 230V ­2BC04700151 Gas Heat Kit, -60 deg F, 460V ­2BC04700154 Gas Heat Kit, -60 deg F, 575V ­1FL0402 Permanent Filter Kit (Includes (4) Four Filters) ­1FL0423 Permanent Filter Kit, (Includes (4) Four Filters) 42" Tall Cabinet ­2DF0401 Dirty Filter Switch ­1FF0410 Filter Frame Kit, Metal ­1FF0411 Metal Filter Frame Kit, 42" Tall Cabinet -
Johnson Controls Unitary Products 9
246645-YTG-C-0708

NOMENCLATURE

D M 090 N10 A 2 A AA 3 0 1 2 4 A
6.5-12.5 Ton York® Model Number Nomenclature
Product Category
D = A/C, Single Pkg., R-22
Product Identifier
M = 9.0 EER A/C
Nominal Cooling Capacity
078 = 6.5 Ton 090 = 7.5 Ton 102 = 8.5 Ton 120 = 10.0 Ton 150 = 12.5 Ton
Heat Type and Nominal Heat Capacity
C00 = Cooling Only. No heat installed
N10 = 100 MBH Output Aluminized Steel N15 = 150 MBH Output Aluminized Steel N20 = 200 MBH Output Aluminized Steel S10 = 100 MBH Output Stainless Steel S15 = 150 MBH Output Stainless Steel S20 = 200 MBH Output Stainless Steel
E09 = 9 KW E18 = 18 KW E24 = 24 KW E36 = 36 KW E54 = 54 KW
Gas Heat Options
Electric Heat Options
Product Style
A = Style A B = Style B C = Style C
These four digits will not be assigned until a quote is requested, or an order placed.
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller UNT 1126 (N2 protocol), DFS, APS
Honeywell Controller, DFS, APS
Novar Controller, DFS, APS
Simplicity IntelliComfort Controller
Simplicity IntelliComfort Controller w/ModLinc
York Commercial Comfort System (YCCS) Rtu Controller
2" Pleated filters
BAS Ready Unit with Belimo Economizer
Shipping Bag
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
Product Generation
3 = Third Generation 4 = Fourth Generation
AA = None AB = Phase Monitor AC = Coil Guard AD = Dirty Filter Switch AE = Phase Monitor & Coil Guard AF = Phase Monitor & Dirty Filter Switch AG = Coil Guard & Dirty Filter Switch AH = Phase Monitor, Coil Guard & Dirty Filter Switch
Configuration Options (not required for all units)
Additional Options
RC = Coil Guard, Shipping Bag & American Flag TA = Technicoat Condenser Coil TJ = Technicoat Evaporator Coil TS = Technicoat Evaporator & Condenser Coils
Airflow
A = Std. Motor B = Std. Motor/Econo./Barometric Relief (Downflow
Only) C = Std. Motor/Econo./Power Exhaust (Downflow Only) D = Std. Motor/Motorized Damper (Downflow Only) E = Std. Motor/Horizontal Economizer (No Baro.) F = Std. Motor/Slab Econo./Power Exhaust
(Downflow Only)
G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only) N = Hi Static Mtr. P = Hi Static Mtr./Econo./Barometric Relief
(Downflow Only)
Q = Hi Static Mtr./Econo./Power Exhaust
(Downflow Only) R = Hi Static Mtr./Motorized Damper (Downflow Only) S = Hi Static Mtr./Horizontal Economizer (No Baro.) T = Hi Static Mtr./Slab Econo./Power Exhaust
(Downflow Only)
U = Hi Static Mtr./Slab Econo./Barometric Relief
(Downflow only)
Voltage
2 = 208/230-3-60 3 = 380-3-60 4 = 460-3-60 5 = 575-3-60
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4 & 5
Options
1 = Disconnect 2 = Non-Pwr'd Conv. Outlet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet
10 Johnson Controls Unitary Products

TABLE 2: DM PHYSICAL DATA

Component
Blower, Centrifugal (Dia. X Wd. in.) 15 x 15 12 x 12 12 X 12 15 x 15 15 x 15
Evaporator
Blower
Evaporator
Coil
Condenser
Fan
(2 per Unit)
Condenser
Coil
(2 per unit)
Refrigerant
Charge
Compressors
Air Filters
Motor, Standard (HP)
Motor, Optional (HP)
Fins per Inch
Height (in.)
Face Area (ft.
Propeller Dia. (in., each)
Motor (HP, each)
CFM, Nominal (each)
Rows (each)
Fins per Inch
Height (in. each)
Face Area (ft.
System 1 (lb./oz.) System 2 (lb./oz.)
Size (Wd. x Ht. x Thickness in.)
Number Per Unit
Rows
Quantity
Type
2
each)
2
each)
246645-YTG-C-0708
Models
078 090 102 120 150
1-1/2 2 3 2 3
2 3 3 3 5
2 2 3 2 3 15 15 15 15 15 30 32 32 40 40
9.9 10.67 10.67 13.2 13.2 24 24 24 24 24
1/3 3/4 3/4 3/4 3/4
1700 2200 2200 2200 2200
1 1 1 1 2 20 20 20 20 20 24 28 36 44 44
7.9 9.33 12 14.5 14.5 4/6 4/10 5/8 6/12 10/12 4/0 3/14 5/2 6/12 11/0
2 2 2 2 2
Recip Recip Recip. Recip Scroll
25x20x2 25x16x2 25x16x2 25x20x2 25x20x2
4 4 4 4 4
Johnson Controls Unitary Products 11
246645-YTG-C-0708

TABLE 3: DM CAPACITY RATINGS

Cooling Capacities
ARI Ratings
Size
(Tons)
Model
MBH EER IPLV
Cooling
Only
078
(6-1/2)
090
(7-1/2)
102
(8-1/2)
120 (10)
150
(12-1/2)
Electric
Heat Gas Heat - 120 96 80 20-50 3/4 Gas Heat - 180 144 80 35-65 3/4
Cooling
Only
Electric
Heat Gas Heat - 120 96 80 15-45 3/4 Gas Heat - 180 144 80 30-60 3/4
Cooling
Only
Electric
Heat Gas Heat - 120 96 80 15-45 3/4 Gas Heat - 180 144 80 30-60 3/4
Cooling
Only
Electric
Heat Gas Heat - 180 144 80 20-50 3/4 Gas Heat - 240 192 80 35-65 3/4
Cooling
Only
Electric
Heat Gas Heat - 180 144 80 10-40 3/4 Gas Heat - 240 192 80 25-55 3/4
* Rated at 95°F ambient 80°F dry bulb and 67°F wet bulb. † Rated in accordance with ARI 270 standard. ‡ See Table 20.
77 9.0 9.45 2600 84
86 9.0 9.2 2886 89
99 9.0 10.04 3400 90
120 9.0 9.10 4000 90
144 9.3 9.25 4500 90
*
CFM
Sound
Rating
(dB)
Nominal
Electric Heat
Capacity
9, 18, 24, 34 - - - - -
9, 18, 24, 34 - - - - -
9, 24, 34 54 - - - - -
9, 24, 34, 54 - - - - -
(kW)
------
------
18, 34 - - - - -
------
------
------
Input
(MBH)
Gas Heat Capacity
Output
(MBH)
Seasonal
Efficiency
(%)
Temp.
Rise
(°F)
Gas Line
(in. OD)
Size

TABLE 4: UNIT VOLTAGE LIMITATIONS

POWER RATING MIN. MAX.
208/230-3-60
460-3-60 575-3-60
12 Johnson Controls Unitary Products
187 252 432 504 540 630

TABLE 5: COOLING CAPACITY DM078 (6-1/2 TON) UNIT

Air On
Evap. Coil
CFM
1950
2275
2600
2925
3250
1950
2275
2600
2925
3250
1950
2275
2600
2925
3250
WB (°F)
72 87 6.8 49 43 37 32 26 - - 78 7.3 45 40 34 28 23 - ­67 80 6.7 61 55 50 44 38 33 27 73 7.1 57 52 46 41 35 29 24 62 71 6.4 71 66 61 55 50 44 39 63 6.9 63 61 56 50 45 39 33 57 66 6.4 66 66 61 56 50 44 39 59 6.8 59 59 54 49 43 37 32 72 91 6.9 54 47 41 34 28 - - 82 7.4 50 44 37 31 24 - ­67 83 6.7 67 61 54 47 41 34 28 76 7.2 64 57 51 44 38 31 24 62 74 6.5 74 72 66 60 53 47 40 66 6.9 66 65 61 55 48 42 35 57 69 6.5 69 69 67 60 54 47 40 62 6.9 62 62 60 53 46 40 33 72 94 7.0 59 52 44 37 29 - - 86 7.5 56 48 41 33 26 - ­67 87 6.8 74 66 58 51 43 36 28 80 7.3 70 63 55 48 40 33 25 62 77 6.6 77 77 72 64 57 49 42 69 7.0 69 69 67 59 52 44 37 57 72 6.6 72 72 72 65 57 49 42 65 7.0 65 65 65 57 50 42 35 72 95 7.0 63 55 46 37 29 - - 85 7.5 60 51 43 34 25 - ­67 88 6.8 78 70 61 52 44 35 26 79 7.3 74 66 58 49 40 32 23 62 77 6.6 77 77 75 66 58 49 40 69 7.1 69 69 67 59 50 42 33 57 73 6.6 73 73 73 64 56 47 38 64 7.0 64 64 64 56 47 39 30 72 96 7.0 67 58 48 38 29 - - 85 7.5 64 54 44 35 25 - ­67 89 6.8 83 73 64 54 44 35 25 78 7.3 78 70 60 50 41 31 21 62 78 6.6 78 78 78 68 59 49 39 68 7.1 68 68 68 58 49 39 29 57 74 6.6 74 74 74 64 54 45 35 64 7.1 64 64 64 54 45 35 25
72 73 7.8 43 37 31 26 20 - - 67 8.3 40 35 29 23 18 - ­67 66 7.5 54 48 43 37 32 26 21 58 7.9 51 45 40 34 29 23 17 62 64 7.4 61 57 52 46 41 35 30 66 7.9 59 54 48 42 37 31 26 57 54 7.3 54 54 48 43 37 32 26 48 7.8 48 48 43 37 31 26 20 72 76 7.9 48 41 34 28 21 - - 69 8.4 45 38 32 25 18 - ­67 68 7.6 60 54 47 40 34 27 21 60 8.0 56 50 43 37 30 24 17 62 67 7.5 65 62 57 50 44 37 31 67 8.0 64 59 52 46 39 33 26 57 56 7.4 56 56 53 46 40 33 27 49 7.9 49 49 46 40 33 27 20 72 78 8.0 53 45 38 30 22 - - 71 8.4 49 42 34 27 19 - ­67 71 7.7 66 59 51 44 36 28 21 61 8.1 61 55 47 39 32 24 17 62 69 7.5 69 67 62 54 47 39 31 69 8.0 69 64 57 49 42 34 26 57 58 7.5 58 58 58 50 42 35 27 50 7.9 50 50 50 43 35 28 20 72 78 8.0 57 48 40 31 23 - - 71 8.5 54 46 37 28 20 - ­67 70 7.7 68 62 54 46 37 28 20 62 8.2 62 58 51 42 33 25 16 62 69 7.6 69 68 64 56 47 38 30 69 8.1 69 67 61 53 44 35 27 57 58 7.5 58 58 58 49 40 32 23 51 8.0 51 51 51 42 33 25 16 72 78 8.1 61 52 42 32 23 - - 71 8.6 59 49 40 30 20 - ­67 70 7.8 70 66 57 48 38 28 19 62 8.3 62 62 55 45 35 25 16 62 69 7.6 69 69 67 57 48 38 28 70 8.2 70 70 66 56 46 37 27 57 57 7.6 57 57 57 48 38 28 19 51 8.1 51 51 51 41 31 22 12
72 62 8.8 3832272115 - ­67 51 8.4 48423731252014 62 67 8.4 57504439332722 57 42 8.3 42423731262015 72 63 8.8 4235292216 - ­67 52 8.4 52464033272013 62 68 8.5 63564841352822 57 43 8.3 43434033272014 72 63 8.9 4639312316 - ­67 52 8.5 52504335282012 62 69 8.5 69625244372921 57 43 8.4 43434335282013 72 64 9.0 5243342617 - ­67 53 8.6 53534739302113 62 70 8.6 70665850413224 57 44 8.5 444444352618 9 72 65 9.1 5747382818 - ­67 54 8.7 54545242322313 62 71 8.8 71716555453626 57 44 8.6 444444342515 5
Temperature of Air on Condenser Coil 85°F Temperature of Air on Condenser Coil 95°F
Tot.
Cap.
(MBH)
Tot.
*
Input
(kW)
Temperature of Air on Condenser Coil 105°F Temperature of Air on Condenser Coil 115°F
Temperature of Air on Condenser Coil 125°F
Sensible Capacity (MBH)
Return Dry Bulb (°F)
86 83 80 77 74 71 68 86 83 80 77 74 71 68
*
246645-YTG-C-0708
Tot.
Cap.
(MBH)
Tot.
*
Input
Sensible Capacity (MBH)
Return Dry Bulb (°F)
(kW)
* These capacities are gross ratings. For net
capacity, deduct air blower motor , MBH = 3.415 x kW. Refer to the appropriate Blower Perfor­mance Table for the kW of the supply air blower motor.
† These ratings include condenser fan motors
and the compressor motors but not the supply air blower motor.
*
Johnson Controls Unitary Products 13
246645-YTG-C-0708
TABLE 6: COOLING CAPACITY DM090 (7-1/2 TON) UNIT
Air on Evap-
orator Coil
WB
CFM
(°F)
Total
Cap.
(MBH)
Total
*
Input
(kW)
86 83 80 77 74 71 68 86 83 80 77 74 71 68
75°F 85°F
Sensible Capacity (MBH)
Return Dry Bulb (°F)
72 101.7 7.2 57.5 51.1 44.7 38.3 31.8 - - 96.7 7.8 55.8 49.4 43.0 36.6 30.1 - ­67 96.3 7.1 73.3 66.8 60.4 54.0 47.6 41.2 34.8 90.8 7.6 70.8 64.4 58.0 51.6 45.2 38.8 32.4
2250
62 89.4 7.0 89.4 80.1 73.7 67.3 60.9 54.4 48.0 83.5 7.5 83.5 77.4 71.0 64.5 58.1 51.7 45.3 57 88.6 6.9 88.6 85.9 79.5 73.1 66.7 60.3 53.8 83.7 7.5 83.7 81.9 75.5 69.0 62.6 56.2 49.8 72 105.2 7.3 63.7 56.2 48.6 41.0 33.4 - - 99.9 7.8 61.8 54.2 46.6 39.1 31.5 - ­67 99.6 7.2 80.9 73.3 65.7 58.1 50.5 43.0 35.4 93.8 7.7 78.1 70.6 63.0 55.4 47.8 40.2 32.6
2625
62 92.5 7.0 92.5 87.8 80.1 72.5 65.0 57.4 49.8 86.2 7.5 86.2 83.2 77.0 69.4 61.9 54.3 46.7 57 91.6 7.0 91.6 90.3 86.5 78.9 71.3 63.7 56.1 86.5 7.5 86.5 85.6 81.9 74.3 66.7 59.2 51.6 72 108.7 7.3 70.0 61.2 52.5 43.7 35.0 - - 103.1 7.9 67.8 59.1 50.3 41.6 32.8 - ­67 102.9 7.2 88.5 79.7 71.0 62.2 53.5 44.7 36.0 96.8 7.8 85.4 76.7 67.9 59.2 50.4 41.7 32.9
3000
62 95.6 7.1 95.6 95.6 86.6 77.8 69.1 60.3 51.6 89.0 7.6 89.0 89.0 83.1 74.3 65.6 56.8 48.1 57 94.7 7.0 94.7 94.7 93.4 84.6 75.9 67.2 58.4 89.2 7.6 89.2 89.2 88.4 79.6 70.9 62.1 53.4 72 110.1 7.3 74.1 64.1 54.2 44.2 34.3 - - 104.4 7.9 72.3 62.4 52.4 42.5 32.5 - ­67 104.2 7.2 93.8 83.3 73.3 63.3 53.4 43.4 33.5 98.0 7.8 90.7 80.7 70.8 60.8 50.8 40.9 30.9
3375
62 96.8 7.1 96.8 96.8 91.1 81.2 71.2 61.2 51.3 90.1 7.6 90.1 90.1 86.6 76.6 66.6 56.7 46.7 57 95.9 7.1 95.9 95.9 95.2 85.3 75.3 65.4 55.4 90.4 7.6 90.4 90.4 89.9 80.0 70.0 60.0 50.1 72 111.5 7.4 78.3 67.1 55.9 44.7 33.5 - - 105.7 7.9 76.9 65.7 54.5 43.3 32.2 - ­67 105.5 7.2 99.1 86.8 75.6 64.4 53.3 42.1 30.9 99.2 7.8 96.0 84.8 73.6 62.4 51.2 40.1 28.9
3750
62 98.0 7.1 98.0 98.0 95.7 84.5 73.3 62.1 51.0 91.2 7.6 91.2 91.2 90.0 78.8 67.7 56.5 45.3 57 97.1 7.1 97.1 97.1 97.1 85.9 74.7 63.6 52.4 91.5 7.6 91.5 91.5 91.5 80.3 69.1 57.9 46.8
95°F 105°F
72 91.8 8.4 54.1 47.7 41.3 34.9 28.4 - - 85.6 9.0 51.6 45.2 38.8 32.3 25.9 - ­67 85.3 8.2 68.4 62.0 55.6 49.2 42.8 36.3 29.9 78.0 8.7 65.4 59.0 52.6 46.2 39.8 33.4 26.9
2250
62 77.5 8.0 77.5 74.6 68.2 61.8 55.4 49.0 42.6 72.4 8.6 72.4 70.5 64.0 57.6 51.2 44.8 38.4 57 78.9 8.0 78.9 77.8 71.4 65.0 58.6 52.1 45.7 73.2 8.6 73.2 71.7 65.3 58.9 52.5 46.1 39.6 72 94.6 8.4 59.9 52.3 44.7 37.1 29.6 - - 87.9 9.0 57.1 49.6 42.0 34.4 26.8 - ­67 87.9 8.3 75.4 67.8 60.2 52.7 45.1 37.5 29.9 80.1 8.8 71.7 64.6 57.0 49.4 41.8 34.3 26.7
2625
62 79.9 8.1 79.9 78.5 73.9 66.3 58.8 51.2 43.6 74.3 8.6 74.3 73.3 69.4 61.8 54.2 46.6 39.1 57 81.3 8.1 81.3 80.8 77.4 69.8 62.2 54.6 47.0 75.2 8.7 75.2 74.4 70.7 63.2 55.6 48.0 40.4 72 97.5 8.5 65.7 56.9 48.2 39.4 30.7 - - 90.2 9.1 62.7 54.0 45.2 36.5 27.7 - ­67 90.6 8.3 82.4 73.6 64.9 56.1 47.4 38.6 29.9 82.1 8.9 78.0 70.1 61.4 52.6 43.9 35.1 26.4
3000
62 82.3 8.1 82.3 82.3 79.6 70.9 62.1 53.4 44.6 76.2 8.7 76.2 76.2 74.7 66.0 57.2 48.5 39.7 57 83.8 8.2 83.8 83.8 83.3 74.6 65.8 57.1 48.3 77.1 8.7 77.1 77.1 76.2 67.4 58.7 49.9 41.2 72 98.7 8.5 70.6 60.6 50.7 40.7 30.7 - - 91.5 9.1 67.7 57.7 47.8 37.8 27.8 - ­67 91.7 8.4 87.6 78.2 68.2 58.3 48.3 38.3 28.4 83.3 8.9 81.2 74.8 64.9 54.9 44.9 35.0 25.0
3375
62 83.3 8.2 83.3 83.3 82.0 72.0 62.1 52.1 42.1 77.3 8.8 77.3 77.3 76.6 66.6 56.6 46.7 36.7 57 84.8 8.2 84.8 84.8 84.6 74.6 64.7 54.7 44.7 78.2 8.8 78.2 78.2 77.8 67.8 57.8 47.9 37.9 72 99.9 8.5 75.5 64.3 53.1 42.0 30.8 - - 92.8 9.2 72.7 61.5 50.3 39.2 28.0 - ­67 92.8 8.4 92.8 82.7 71.6 60.4 49.2 38.0 26.9 84.5 8.9 84.5 79.4 68.3 57.2 46.0 34.8 23.6
3750
62 84.4 8.2 84.4 84.4 84.4 73.2 62.0 50.8 39.6 78.4 8.8 78.4 78.4 78.4 67.2 56.1 44.9 33.7 57 85.9 8.2 85.9 85.9 85.9 74.7 63.5 52.3 41.1 79.3 8.8 79.3 79.3 79.3 68.1 57.0 45.8 34.6
115°F 125°F
72 79.5 9.6 49.1 42.6 36.2 29.8 23.4 - - 73.4 10.1 46.5 40.1 33.7 27.3 20.9 - ­67 70.7 9.3 62.5 56.0 49.6 43.2 36.8 30.4 24.0 63.4 9.8 59.5 53.1 46.6 40.2 33.8 27.4 21.0
2250
62 67.3 9.1 67.3 66.3 59.9 53.4 47.0 40.6 34.2 62.2 9.7 62.2 62.1 55.7 49.2 42.8 36.4 30.0 57 67.6 9.1 67.6 65.6 59.2 52.8 46.4 40.0 33.5 61.9 9.7 61.9 59.5 53.1 46.7 40.3 33.9 27.4 72 81.2 9.6 54.4 46.8 39.2 31.7 24.1 - - 74.5 10.2 51.7 44.1 36.5 28.9 21.3 - ­67 72.2 9.4 68.1 61.3 53.8 46.2 38.6 31.0 23.4 64.3 9.9 64.3 58.1 50.5 42.9 35.4 27.8 20.2
2625
62 68.7 9.2 68.7 68.2 64.8 57.3 49.7 42.1 34.5 63.1 9.8 63.1 63.0 60.3 52.7 45.1 37.6 30.0 57 69.0 9.2 69.0 68.0 64.1 56.6 49.0 41.4 33.8 62.8 9.8 62.8 61.6 57.5 49.9 42.4 34.8 27.2 72 82.9 9.7 59.8 51.0 42.3 33.5 24.8 - - 75.5 10.3 56.8 48.1 39.3 30.6 21.8 - ­67 73.7 9.5 73.7 66.6 57.9 49.1 40.4 31.6 22.9 65.2 10.0 65.2 63.2 54.4 45.7 36.9 28.2 19.4
3000
62 70.1 9.3 70.1 70.1 69.8 61.1 52.3 43.6 34.8 64.0 9.9 64.0 64.0 64.0 56.2 47.4 38.7 29.9 57 70.4 9.3 70.4 70.4 69.1 60.3 51.6 42.8 34.1 63.7 9.9 63.7 63.7 62.0 53.2 44.5 35.7 27.0 72 84.3 9.8 64.8 54.9 44.9 34.9 25.0 - - 77.0 10.4 61.9 52.0 42.0 32.1 22.1 - ­67 74.9 9.5 74.9 71.4 61.5 51.5 41.6 31.6 21.6 66.5 10.0 66.5 66.5 58.1 48.2 38.2 28.2 18.3
3375
62 71.3 9.3 71.3 71.3 71.2 61.2 51.2 41.3 31.3 65.3 9.9 65.3 65.3 65.3 55.8 45.8 35.8 25.9 57 71.6 9.3 71.6 71.6 70.9 61.0 51.0 41.0 31.1 65.0 9.9 65.0 65.0 64.1 54.1 44.2 34.2 24.2 72 85.7 9.8 69.9 58.7 47.5 36.3 25.2 - - 78.6 10.4 67.1 55.9 44.7 33.5 22.4 - ­67 76.1 9.5 76.1 76.1 65.1 53.9 42.7 31.6 20.4 67.8 10.1 67.8 67.8 61.9 50.7 39.5 28.3 17.2
3750
62 72.5 9.4 72.5 72.5 72.5 61.3 50.1 38.9 27.8 66.5 10.0 66.5 66.5 66.5 55.4 44.2 33.0 21.8 57 72.8 9.4 72.8 72.8 72.8 61.6 50.4 39.3 28.1 66.2 9.9 66.2 66.2 66.2 55.1 43.9 32.7 21.5
* The capacities are gross ratings. For net capacity, deduct indoor blower mot or, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-
mance table for the kW of the supply air blower motor.
† These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
*
Total Cap.
(MBH)
Total
*
Input
(kW)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
*
14 Johnson Controls Unitary Products
246645-YTG-C-0708
TABLE 7: COOLING CAPACITY DM102 (8-1/2 TON) UNIT
Air on Evap-
orator Coil
WB
CFM
(°F)
Total
Cap.
(MBH)
Total
*
Input
(kW)
86 83 80 77 74 71 68 86 83 80 77 74 71 68
75°F 85°F
Sensible Capacity (MBH)
Return Dry Bulb (°F)
72 123.8 7.4 68.9 61.6 54.3 47.1 39.8 - - 114.8 8.0 65.3 58.0 50.8 43.5 36.2 - ­67 112.4 7.3 85.2 78.0 70.7 63.4 56.2 48.9 41.6 104.3 7.9 81.9 74.6 67.3 60.1 52.8 45.5 38.3
2550
62 106.9 7.1 106.9 95.5 88.1 80.8 73.5 66.3 59.0 96.4 7.7 96.4 90.7 83.5 76.2 68.9 61.6 54.4 57 99.3 7.1 99.3 98.9 91.5 84.2 76.9 69.7 62.4 93.2 7.7 93.2 92.9 85.7 78.4 71.1 63.9 56.6 72 127.6 7.4 75.6 67.0 58.5 49.9 41.3 - - 118.7 8.1 72.0 63.4 54.8 46.2 37.6 - ­67 115.9 7.3 93.2 84.6 76.0 67.4 58.8 50.2 41.7 107.8 7.9 89.9 81.3 72.7 64.1 55.5 46.9 38.3
2975
62 110.3 7.2 110.3 104.6 94.7 86.1 77.5 69.0 60.4 99.7 7.7 99.7 96.9 90.1 81.5 72.9 64.3 55.7 57 102.4 7.1 102.4 102.2 98.4 89.8 81.2 72.6 64.0 96.3 7.8 96.3 96.2 92.5 83.9 75.3 66.7 58.1 72 131.5 7.5 82.4 72.5 62.6 52.6 42.7 - - 122.6 8.2 78.7 68.7 58.8 48.9 39.0 - ­67 119.4 7.4 101.2 91.3 81.3 71.4 61.5 51.6 41.7 111.3 8.0 97.9 88.0 78.0 68.1 58.2 48.3 38.4
3400
62 113.7 7.2 113.7 113.7 101.4 91.5 81.5 71.6 61.7 103.0 7.8 103.0 103.0 96.7 86.8 76.9 67.0 57.1 57 105.5 7.2 105.5 105.5 105.3 95.4 85.5 75.5 65.6 99.5 7.8 99.5 99.5 99.3 89.4 79.5 69.5 59.6 72 134.7 7.5 88.7 77.5 66.2 54.9 43.6 - - 125.2 8.2 85.0 73.7 62.4 51.1 39.8 - ­67 122.3 7.4 110.0 97.3 86.0 74.7 63.4 52.1 40.9 113.7 8.0 105.4 94.1 82.8 71.5 60.2 48.9 37.6
3825
62 116.4 7.3 116.4 116.4 110.3 99.0 87.7 76.4 65.1 105.2 7.8 105.2 105.2 102.1 90.8 79.5 68.2 56.9 57 108.1 7.3 108.1 108.1 108.0 96.7 85.4 74.1 62.8 101.6 7.9 101.6 101.6 101.5 90.2 78.9 67.6 56.4 72 137.9 7.6 95.1 82.4 69.8 57.1 44.4 - - 127.8 8.3 91.3 78.7 66.0 53.3 40.7 - ­67 125.3 7.5 118.8 103.4 90.7 78.0 65.4 52.7 40.0 116.1 8.1 112.9 100.2 87.6 74.9 62.2 49.6 36.9
4250
62 119.2 7.3 119.2 119.2 119.2 106.5 93.8 81.2 68.5 107.4 7.9 107.4 107.4 107.4 94.8 82.1 69.4 56.8 57 110.7 7.3 110.7 110.7 110.7 98.0 85.3 72.6 60.0 103.8 7.9 103.8 103.8 103.8 91.1 78.4 65.8 53.1
95°F 105°F
72 105.8 8.7 61.7 54.5 47.2 39.9 32.6 - - 96.9 9.4 58.0 50.8 43.5 36.2 29.0 - ­67 96.1 8.5 78.5 71.3 64.0 56.7 49.5 42.2 34.9 86.6 9.1 74.3 67.0 59.7 52.5 45.2 37.9 30.7
2550
62 86.0 8.3 86.0 86.0 78.8 71.6 64.3 57.0 49.7 79.4 8.9 79.4 78.9 71.7 64.4 57.1 49.9 42.6 57 87.0 8.3 87.0 87.0 79.9 72.6 65.3 58.1 50.8 79.5 8.9 79.5 79.4 72.2 65.0 57.7 50.4 43.2 72 109.7 8.8 68.3 59.7 51.1 42.5 34.0 - - 100.5 9.4 64.6 56.0 47.4 38.8 30.2 - ­67 99.7 8.5 86.6 78.0 69.4 60.8 52.2 43.6 35.0 89.8 9.1 81.5 73.7 65.1 56.5 47.9 39.3 30.7
2975
62 89.1 8.3 89.1 89.1 85.4 76.8 68.3 59.7 51.1 82.3 9.0 82.3 82.1 78.1 69.5 60.9 52.3 43.7 57 90.2 8.4 90.2 90.2 86.6 78.0 69.4 60.8 52.2 82.5 9.0 82.5 82.4 78.7 70.1 61.5 52.9 44.3 72 113.6 8.8 74.9 65.0 55.1 45.2 35.3 - - 104.0 9.5 71.1 61.2 51.3 41.3 31.4 - ­67 103.2 8.6 94.6 84.7 74.7 64.8 54.9 45.0 35.1 93.0 9.2 88.7 80.3 70.4 60.5 50.6 40.7 30.8
3400
62 92.3 8.4 92.3 92.3 92.1 82.1 72.2 62.3 52.4 85.3 9.0 85.3 85.3 84.5 74.6 64.6 54.7 44.8 57 93.5 8.4 93.5 93.5 93.3 83.4 73.5 63.5 53.6 85.4 9.1 85.4 85.4 85.1 75.2 65.3 55.4 45.5 72 115.7 8.9 81.2 70.0 58.7 47.4 36.1 - - 105.6 9.5 77.4 66.1 54.8 43.5 32.2 - ­67 105.1 8.6 100.8 90.9 79.6 68.3 57.0 45.7 34.4 94.5 9.2 92.3 85.7 75.3 64.0 52.7 41.4 30.1
3825
62 94.0 8.4 94.0 94.0 93.9 82.6 71.3 60.0 48.7 86.6 9.1 86.6 86.6 86.2 74.9 63.6 52.3 41.0 57 95.2 8.5 95.2 95.2 95.1 83.8 72.5 61.2 49.9 86.7 9.1 86.7 86.7 86.6 75.3 64.0 52.7 41.4 72 117.7 8.9 87.6 74.9 62.2 49.6 36.9 - - 107.3 9.6 83.7 71.0 58.3 45.7 33.0 - ­67 107.0 8.7 107.0 97.1 84.4 71.8 59.1 46.4 33.7 95.9 9.3 95.9 91.0 80.2 67.5 54.8 42.1 29.5
4250
62 95.7 8.5 95.7 95.7 95.7 83.0 70.4 57.7 45.0 87.9 9.1 87.9 87.9 87.9 75.3 62.6 49.9 37.3 57 96.9 8.5 96.9 96.9 96.9 84.2 71.5 58.9 46.2 88.1 9.1 88.1 88.1 88.1 75.4 62.7 50.1 37.4
115°F 125°F
72 88.0 10.0 54.3 47.1 39.8 32.5 25.3 - - 79.1 10.7 50.7 43.4 36.1 28.8 21.6 - ­67 77.2 9.7 70.0 62.8 55.5 48.2 40.9 33.7 26.4 67.7 10.2 65.8 58.5 51.2 44.0 36.7 29.4 22.1
2550
62 72.9 9.6 72.9 71.8 64.5 57.3 50.0 42.7 35.5 66.3 10.2 66.3 64.7 57.4 50.1 42.9 35.6 28.3 57 72.1 9.6 72.1 71.9 64.6 57.3 50.1 42.8 35.5 64.6 10.2 64.6 64.3 57.0 49.7 42.4 35.2 27.9 72 91.2 10.1 60.8 52.2 43.6 35.0 26.4 - - 82.0 10.7 57.0 48.4 39.8 31.3 22.7 - ­67 80.0 9.7 76.4 69.4 60.8 52.2 43.6 35.0 26.4 70.2 10.3 70.2 65.1 56.5 47.9 39.3 30.7 22.1
2975
62 75.5 9.6 75.5 75.0 70.7 62.1 53.5 44.9 36.3 68.7 10.2 68.7 68.0 63.4 54.8 46.2 37.6 29.0 57 74.7 9.6 74.7 74.6 70.8 62.2 53.6 45.0 36.4 67.0 10.2 67.0 66.8 62.9 54.3 45.7 37.1 28.5 72 94.5 10.1 67.2 57.3 47.4 37.5 27.6 - - 84.9 10.8 63.4 53.5 43.6 33.7 23.7 - ­67 82.8 9.8 82.8 76.0 66.1 56.2 46.3 36.4 26.4 72.6 10.4 72.6 71.7 61.8 51.9 41.9 32.0 22.1
3400
62 78.2 9.7 78.2 78.2 76.9 67.0 57.1 47.1 37.2 71.2 10.3 71.2 71.2 69.3 59.4 49.5 39.6 29.6 57 77.4 9.7 77.4 77.4 77.0 67.1 57.1 47.2 37.3 69.3 10.3 69.3 69.3 68.8 58.9 49.0 39.1 29.2 72 95.6 10.2 73.5 62.2 50.9 39.6 28.3 - - 85.6 10.9 69.6 58.3 47.1 35.8 24.5 - ­67 83.9 9.8 83.9 80.4 71.0 59.7 48.4 37.1 25.8 73.2 10.4 73.2 73.2 66.7 55.4 44.1 32.8 21.5
3825
62 79.2 9.7 79.2 79.2 78.5 67.2 55.9 44.6 33.4 71.8 10.4 71.8 71.8 70.8 59.6 48.3 37.0 25.7 57 78.3 9.7 78.3 78.3 78.1 66.8 55.5 44.3 33.0 69.9 10.4 69.9 69.9 69.7 58.4 47.1 35.8 24.5 72 96.8 10.2 79.8 67.1 54.4 41.8 29.1 - - 86.3 10.9 75.9 63.2 50.5 37.9 25.2 - ­67 84.9 9.9 84.9 84.9 75.9 63.2 50.5 37.9 25.2 73.8 10.5 73.8 73.8 71.6 58.9 46.3 33.6 20.9
4250
62 80.2 9.8 80.2 80.2 80.2 67.5 54.8 42.1 29.5 72.4 10.4 72.4 72.4 72.4 59.7 47.0 34.4 21.7 57 79.3 9.8 79.3 79.3 79.3 66.6 53.9 41.3 28.6 70.5 10.4 70.5 70.5 70.5 57.8 45.1 32.5 19.8
* The capacit ies are gross ratings. For net capacity, deduct indoor blower motor, MBH=3.415 x kW. Refer to the appropriate Blower Perfor-
mance table for the kW of the supply air blo w er motor.
† These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Temperature of Air on Condenser Coil
*
Total
Cap.
(MBH)
Total
*
Input
(kW)
Sensible Capacity (MBH)
Return Dry Bulb (°F)
*
Johnson Controls Unitary Products 15