York DM 060 User Manual

Page 1
TECHNICAL GUIDE
036-21502-002-A-0303
DESCRIPTION
YORK Sunline 2000™ units are convertible single package air conditioners with a common cabinet and a common roof curb for the 3, 4, 5 and 6 ton sizes. The units were designed for light commercial and commercial appli cations. They can easily be installed on a roof curb, slab, ro of j ack or frame.
SINGLE PACKAGE GAS/ELECTRIC UNITS AND SINGLE PACKAGE AIR CONDITIONERS
DM 036, 048, 060 & 072
3, 4, 5 & 6 NOMINAL TONS
10.0 SEER (3, 4 & 5 TONS), 9.0 EER (6 TONS)
All units incl ude:
Powder Paint finish that meets ASTM-B-117 750 hour salt spray sta ndards
Permanently lubr icated motors
Bottom or side air discharge configurat ion capability (field convertible)
Manufactured under the quality standards of ISO9001
Simplicity
Copper tube/aluminum fin coils
Easy access to all components
Rigging holes in ba s e ra il s fo r li ftin g
Fork lift slots on three sides
Single point power connection
Complete factory package - tested, charged and wired
CSA agency listing on all units
WARRANTY
Factory Limited Parts Warranty
One-year parts warranty
TM
Control Board
A Five-year parts warranty on the compressor and electric heat elements.
Ten-year parts warranty on the gas-fired heat exchangers.
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
Page 2
TABLE OF CONTENTS
036-21502-002-A-0303
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
PRODUCT NOMENCLATURE. . . . . . . . . . . . . . . . . . 3
FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
FACTORY-INSTALLED OPTIONS . . . . . . . . . . . . . . 9
FIEL D - INSTAL LED A C C ESSO RIES . . . . . . . . . . . . 1 0
GUIDE SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . 38
LIST OF FIGURES
Fig. # Pg. #
1 UNIT CUTAWAY. . . . . . . . . . . . . . . . . . . . . . . . . . 9
2 TYPICAL FIELD POWER & CONTROL
WIRING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
3 UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/
ELECTRIC HEAT) FRONT VIEW. . . . . . . . . . . . 32
4 UNIT DIMENSIONS (3 - 6 TON COOLING/GAS
HEAT) FRONT VIEW . . . . . . . . . . . . . . . . . . . . . 32
5 UNIT WITH ECONOMIZER RAINHOOD . . . . . . 33
6 UNIT WITH FIXE D OU TD OOR AIR/MOTORIZED
DAMPER RAINHOOD. . . . . . . . . . . . . . . . . . . . . 33
7 UNIT DIMENSIONS (REAR VIEW). . . . . . . . . . . 34
8 DISCONNECT/BLOWER ACCESS LOCATION. 34
9 TYPICAL APPLICATIONS . . . . . . . . . . . . . . . . . 35
10 FOUR AND S IX POINT LOA D IN G . . . . . . . . . . . 36
11 ROOF CURB DIMENSIONS. . . . . . . . . . . . . . . . 37
9 SUPPLY AIR BLOWER PERFORMA N CE (4 TON
BELT DRIVE) - SIDE DUCT APPLICATION. . . . 17
10 SUPPLY AIR BL OWER PERFORMANCE (5 TON
BELT DRIVE) - SIDE DUCT APPLICATION. . . . 18
11 SUPPLY AIR BL OWER PERFORMANCE (6 TON
BELT DRIVE) - SIDE DUCT APPLICATION. . . . 19
12 SUPPLY AIR BL OWER PERFORMANCE (3 - 6
TON DIRECT DRIVE) . . . . . . . . . . . . . . . . . . . . 20
13 BELT DRIVE MOTOR AND DRIVE DATA . . . . . 20
14 STATIC RESISTANCES. . . . . . . . . . . . . . . . . . . 21
15 ELECTRIC HEATER CFM LIMITATIONS. . . . . . 21
16 ELECT DATA - DM036 & 048 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 22 17 ELECT DATA - DM060 & 072 DIRECT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 23 18 ELECTRICAL DATA - DM036 & 048 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 24 19 ELECTRICAL DATA - DM060 & 072 BELT DRIVE
WITHOUT POWR’D CONVENIENCE OUTLET . 25 20 ELECTRICAL DATA - DM036 & 048 DIRECT
DRIVE WITH POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
21 ELECTRICAL DATA - DM060 & 072 DIRECT
DRIVE WITH POWR’D CONVENIENCE
OUTLET . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
22 ELECTRICAL DATA - DM036 & 048 BELT DRIVE
WITH POWR’D CONVENIENCE OUTLET. . . . . 28
LIST OF T ABLES
Tbl. # Pg. #
WITH POWR’D CONVENIENCE OUTLET. . . . . 29
24 PHYSICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . 30
23 ELECTRICAL DATA - DM060 & 072 BELT DRIVE
1 SOUND POWER RATING . . . . . . . . . . . . . . . . . 11
2 CAPACITY RATINGS - (ARI 210/240) . . . . . . . . 11
3 GAS HEAT RATINGS. . . . . . . . . . . . . . . . . . . . . 11
4 DM036 COOLING CAPACITIES (3 TON). . . . . . 12
5 DM048 COOLING CAPACITIES (4 TON). . . . . . 13
6 DM060 COOLING CAPACITIES (5 TON). . . . . . 14
7 DM072 COOLING CAPACITIES (6 TON). . . . . . 15
8 SUPPLY AIR BLOWER PERFORMANCE (3 TON
25 ELECTRIC HEAT CORRECTION FACTORS . . 30
26 VOLTAGE LIMITATIONS . . . . . . . . . . . . . . . . . . 30
27 UTILITIES ENTRY . . . . . . . . . . . . . . . . . . . . . . . 34
28 MINIMUM CLEARANCES. . . . . . . . . . . . . . . . . . 34
29 DM 4 POINT LOADS WEIGHT DISTRIBUTION. 36 30 DM 6 POINT LOADS WEIGHT DISTRIBUTION. 36
31 CENTER OF GRAVITY . . . . . . . . . . . . . . . . . . . . 36
32 OPERATING WEIGHTS (LBS.) . . . . . . . . . . . . . 37
BELT DRIVE) - SIDE DUCT APPLICATION. . . . 16
2 Unitary Products Group
Page 3
036-21502-002-A-0303
3-6 Ton Sunline Model Number Nomenclature
D M N04
A2A
AA 1048
Product Catagory
D = Air Cond., Single Package B = Heat Pump, Single Package
Product Identifier
M = R-22 Standard Efficiency (DCG/DCE) F = R-22 Medium Efficiency (DEG/DEE) H = R-22 High Efficiency (DHG/DHE) Q = R-22 Std. Effic Heat Pump (BCH)
Airflow
A= Direct Drive B = Direct Drive/Single Input Econo D = Direct Drive/Motorized Damper L = Direct Drive/BAS Ready Econ (No BAS Contro ller)/2" Pleated Filters/Extra xfrmr & circuit bkr. N = Belt Drive P = Belt Drive/Single Input Econo R = Belt Drive/Motorized Damper Y = Belt Drive/BAS Ready Econ (No BAS Controller) w/2" Pleated Filters
Installation Options
A = No Options Installed B = Option 1 C = Option 2 D = Options 1 & 2 E = Option 3 F = Option 4 G = Options 1 & 3 H = Options 1 & 4 J = Options 1, 2 & 3 K = Options 1, 2, & 4 L = Options 1,3 & 4 M = Options 1, 2, 3, & 4 N = Options 2 & 3 P = Options 2 & 4 Q = Options 2, 3, & 4 R = Options 3 & 4 S = Option 5 T = Options 1 & 5 U = Options 1, 3, & 5 V = Options 1, 4, & 5 W = Options 1, 3, 4, & 5 X = Options 3 & 5 Y = Options 4 & 5 Z = Options 3, 4, & 5
Options
1 = Disconnect 2 = Non-Pwr'd Conv Oultet 3 = Smoke Detector S.A. 4 = Smoke Detector R.A. 5 = Pwr'd Conv. Outlet
Additional Options
(See Next Page)
Product Generation
1 = First Generation
Voltage
1 = 208/230-1-60 2 = 208/230-3-60 4 = 460-3-60 5 = 575-3-60
Nominal Cooling
Capacity - MBH
036 = 3 Ton 048 = 4 Ton 060 = 5 Ton 072 = 6 Ton
Heat Type & Nominal Heat Capacity
C00 = Cooling Only. Suitable for field installed electric heat
Gas Heat Options
N04 = 40 MBH Output Aluminized Steel (036) N06 = 60 MBH Output Aluminized Steel (048) N08 = 79 MBH Output Aluminized Steel (036,060,072) N10 = 99 MBH Output Aluminized Steel (048,060,072) S04 = 40 MBH Output Stainless Steel (036) S06 = 60 MBH Output Stainless Steel (048) S08 = 79 MBH Output Stainless Steel (036,060,072) S10 = 99 MBH Output Stainless Steel (048,060,072)
Electric Heat Options
E05 = 5 kW Electric Heat E07 = 7 kW Electric Heat E10 = 10 kW Electric Heat E15 = 15 kW Electric Heat E20 = 20 kW Electric Heat E30 = 30 kW Electric Heat
PRODUCT NOMENCLATURE
Unita ry P rod ucts Gro up 3
Page 4
036-21502-002-A-0303
PRODUCT NOMENCLATURE - Continued
3-6T Sunline Model Number Nome nclature
Additional Options
AA None AB Phase Monitor AC Coil Guard AD Dirty Filter Switch AE Phase Monitor & Coil Guard AF Phase Monitor & Dirty Filter Switch AG Coil Guard & Dirty Filter Switch AH Phase Monitor, Coil Guard, & Dirty Filter Switch AS Bottom Condensa te Pan BA Hinged Filter Door & Toolless Access Panels BB Phase Monitor, Hinged Filter Door & Toolless Access Panels BC Coil Guard, Hinged Filter Door & Toolless Access Panels BD Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels BE Ph ase Monitor & Coil Guard, Hinged Filter Door & Toolless Access Panels BF Phase Mon itor & Dirty Filter Switch, Hinged Filter Door & Tooll ess Access Panels BG Coil Guard & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels BH Phase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels CA CPC Controller with Dirty Filter Switch & Air Proving Switch CB CPC Controller, DFS, APS & Phase Monitor CC CPC Controller, DFS, APS & Coil Guard CD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard CE CPC Controller, DFS, APS & Technicoat Cond. Coil CF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor CG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard CH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard CJ CPC Controller, DFS, APS & Tech nico at Evap. Coil CK CPC Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor CL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard CM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard CN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils CP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor CQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard CR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard DA CPC Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels DB CPC Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels DC CPC Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels DD CPC Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels DE CPC Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolles s Access Panels DF CPC Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels DG CPC Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels DH CPC Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels DJ CPC Controller , DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels DK CPC Controller, DFS, APS, Technicoat Ev ap. Coil, & Phase M onitor, Hinged Filter Door & Toolless Access Panels DL CPC Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels DM CPC Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Acc ess Panels DN CPC Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels DP CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access Panels DQ CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Gu ard, Hinged Filt er Door & Toolless Access Panels DR CPC Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels
4 Unitary Products Group
Page 5
036-21502-002-A-0303
Additional O pti ons
EA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels EB Johnson UNT Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels EC Johnson UNT Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels ED Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels EE Johnson UNT Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels EF Johnson UNT Contro ller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Tool less Access Panels EG Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels EH Johnson UNT Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels EJ Johnson UNT Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels EK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels EL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels EM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels EN Johnson UNT Controller, DFS, APS & Te chnicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels EP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & To olless Access Panels EQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels ER J oh nson U NT Cont rol l er, DFS, APS, Technicoa t Evap. & Co nd Co il s, P has e Mo nit or, & Coil Guard, Hin ge d Fil t er D oor & Toolless Access
Panels GA Honeywell Excel 10 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels GB Honeywell Excel 10 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels GC Honeywell Excel 10 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels GD Honeywell Excel 10 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & T oolless Access Panels GE Honeywell Excel 10 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels GF Hon eyw e ll Excel 10 Contro ller, DFS, APS, Technicoat Cond. Coi l, & Phase Monito r, Hinged Filter Door & Toolless Access Panels GG Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels GH Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels GJ Honeywell Excel 10 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & Toolless Access Panels GK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels GL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & To olless Access Panels GM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels GN Honeywell Excel 10 Controller, DFS, APS & T e chnicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels GP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & Toolless Access
Panels GQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels GR Honeywell Excel 10 Controller, DFS, APS, T e chnicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & T oolless
Access Panels HA Honeywell Exce l 10 C on troller with D irt y Fil t er Sw it ch & Air P rov in g Switch HB Hon eywe ll Excel 10 Contro ller, DFS, APS & Phase Monitor HC Honeywell Excel 10 Controller, DFS, APS & Coil Guard HD Honeywell Excel 10 Contro ller, DFS, APS, Phase Monitor, & Coil Guard HE Hon eywe ll Excel 10 Controller, DFS, APS & Tech nico at Cond. Coil HF Honeywell Excel 10 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monito r HG Hon eywe ll Excel 10 Contro ller, DFS, APS, Technicoat Cond. Coi l, & Coil Guard HH Honeywell Exce l 10 Controlle r, DFS, APS, Technicoat Cond. Coil, Phas e Monit or, & Coil Guard HJ H oneyw ell Exce l 10 Controller, DFS, APS & Tech nico at Evap. Coil HK Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor HL Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard HM Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard HN Honeywell Excel 10 Controller, DFS, APS & Tech ni coat Evap . & Cond Coils HP Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor HQ Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard HR Honeywell Excel 10 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard
Unita ry P rod ucts Gro up 5
Page 6
036-21502-002-A-0303
Additional Options
JA Johnson UNT Controller with Dirty Filter Switch & Air Proving Switch JB Johnson UNT Controller, DFS, APS & Phase Monitor JC Johnson UNT Controller, DFS, APS & Coil Guard JD Johnson UNT Controller, DFS, APS, Phase Monitor, & Coil Guard JE Johnson UNT Controller, DFS, APS & Technicoat Con d. Coil JF Johns on UNT Controlle r, DFS, APS, Technicoat Cond. Coil, & Phase Mon ito r JG Johnson UNT Contro ller, DFS, APS, Technicoat Cond. Coil, & Coil Guard JH Jo hns on UNT Contro ller, DFS, APS, Technicoat Cond. Coi l, Phase Mo nitor, & Coil Guard JJ Jo hns on UNT Contro ller, DFS, APS & Tech nico at Evap. Coil JK Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Phase Monitor JL Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard JM Johnson UNT Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard JN Jo hns on UNT Contro ller, DFS, APS & Tech nicoat Ev ap. & Cond Coils JP Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor JQ Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard JR Johnson UNT Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard NA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch NB Novar ETC-3 Controller, DFS, APS & Phase Monitor NC Novar ETC-3 Controller, DFS, APS & Coil Guard ND Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard NE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil NF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor NG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard NH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard NJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil NK Nov ar ETC-3 Cont rolle r, DFS, APS, Te c hnic oat Evap. Coi l, & Phase Mon itor NL Novar ETC-3 Cont rolle r, DFS, APS, Te c hnic oat Evap. Coi l, & Coil Guard NM Novar ETC-3 Control ler, DFS, APS, Te c hn icoa t Evap. Coil, Pha se Monit or, & Coil Guard NN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils NP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor NQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard NR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard PA Novar ETC-3 Controller with Dirty Filter Switch & Air Proving Switch, Hinged Filter Door & Toolless Access Panels PB Novar ETC-3 Controller, DFS, APS & Phase Monitor, Hinged Filter Door & Toolless Access Panels PC Novar ETC-3 Controller, DFS, APS & Coil Guard, Hinged Filter Door & Toolless Access Panels PD Novar ETC-3 Controller, DFS, APS, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels PE Novar ETC-3 Controller, DFS, APS & Technicoat Cond. Coil, Hinged Filter Door & Toolless Access Panels PF Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Phase Monitor, Hinged Filter Door & Toolless Access Panels PG Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels PH Novar ETC-3 Controller, DFS, APS, Technicoat Cond. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels PJ Novar ETC-3 Controller, DFS, APS & Technicoat Evap. Coil, Hinged Filter Door & T oolless Access Panels PK Novar ETC-3 Controller, DFS, APS, Tec hn icoa t Evap. Coil, & Phase M onito r, Hinged Filter Door & To ol le ss Access Panels PL Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, & Coil Guard, Hinged Filter Door & Toolless Access Panels PM Novar ETC-3 Controller, DFS, APS, Technicoat Evap. Coil, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access Panels PN Novar ETC-3 Controller, DFS, APS & Technicoat Evap. & Cond Coils, Hinged Filter Door & Toolless Access Panels PP Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Phase Monitor, Hinged Filter Door & T oolless Access Panels PQ Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, & Coil Guard, Hinged Filter Door & Toolless Access Panels PR Novar ETC-3 Controller, DFS, APS, Technicoat Evap. & Cond Coils, Phase Monitor, & Coil Guard, Hinged Filter Door & Toolless Access
Panels TA T echnicoat Condenser Coil TB Technicoat Condenser Coil & Phase Monitor TC Technicoat Condenser Coil & Coil Guard
6 Unitary Products Group
Page 7
036-21502-002-A-0303
Additional O pti ons
TD Technicoat Condenser Coil & Dirty Filter Switch TE Technicoat Condenser Coil, Phase Monitor, & Coil Gu ard TF Technicoat Condenser Coil, Phase Monitor, & Dirty Filter Switch TG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch TH Technicoat Condenser Coi l, Phase Monitor, Coil Guard, & Dirty Filter Switch TJ Technicoat Evap orator Coil TK Technicoat Ev aporator Coil & Phase Monitor TL Technicoat Evaporator Coil & Coil Guard TM Technicoat Ev aporator Coil & Dirty Filter Switch TN Technicoat Evaporator Coil, Phase Monit or, & Coil Guard TP Technicoat Evaporator Coil, Phase Monitor, & Dirty Filter Switch TQ Technicoat Evaporator Coil, Coil Guard, & Dirty Filter Swit ch TR Technicoat Evaporator Coil, Phase Monit or, Coil Gua rd, & Dirty Filter Switch TS Technicoat E v aporator & Condenser Coils TT Technicoat Evaporator & Condenser Coils & Phase Monitor TU Technicoat Evaporator & Condenser Coils & Coil Guard TV Technicoat E v aporator & Cond enser Coils & Dirty Filter Switch TW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guard TX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirty Filter Switch TY Technicoat E v aporator & Cond enser Coils, Coil Guard, & Dirty Filter Switch TZ Technicoat Evaporator & Condenser Coils, Phase Monitor, Coil Guard, & Dirty F ilter Switch UA Technicoat Condenser Coil, Hinged Filter Door & Toolless Access Panels UB Technicoat Conde nser Coil & Phase Monitor, Hinged Filter Door & T oolless Access Panels UC Technicoat Condenser Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels UD Technicoat Condenser Coil & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UE Technicoat Conde nser Coil, Phase Monitor, & Coil Guard, Hinged Filter D oor & Toolless Access Panels UF Technicoat Conde nser Coil, Phase Mo nitor, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UG Technicoat Condenser Coil, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UH Technicoat Condenser Coil, P hase Monitor, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless A ccess Panels UJ Technicoat Evaporator Coil, Hinged Filter Door & Toolless Ac cess Panels UK Technicoat Evapor ator Coil & Phas e Monitor, Hinged Filter Door & Toolless Access Panels UL Technicoat Ev aporator Coil & Coil Guard, Hinged Filter Door & Toolless Access Panels UM Technicoat Evaporator Coil & Dirty Filter Switch, Hinge d Filter Door & Toolless Access Panels UN Technicoat Evaporator Coil, Phase Mo nitor, & Coi l G uard, Hinged Filter Door & Toolless Ac cess Panels UP Technicoat Evaporator Coil, Phas e Monitor, & D irty Filter Switch, Hinged Filter Door & Toolless Access Panels UQ T echnicoat Evapor ator Coil, Coil Guard, & Dirty Filter Swit ch, Hinged Filter Door & Toolless Access Panels UR Technicoat E v aporator Coil, Phase Monitor, Coil Guard, & Dirty Fi lter Switch, Hinged Filter Door & Toolless Access Panels US Technicoat Evapor ator & Condenser Coils, Hinged Filter Door & Toolless Access Panels UT Technicoat Evapor ator & Condenser Coils & Phase Monitor, Hinged Filter Door & Toolless Acce ss Panels UU Technicoat Evaporator & Condenser Coils & Coil Guard, Hinged Filter Door & Toolless Access Panels UV Technicoat Evapor ator & Condenser Coils & Dirty Filt er Switch, Hinged Filter Door & Toolles s Access Panels UW Technicoat Evaporator & Condenser Coils, Phase Monitor, & Coil Guar d, Hinged Filter Door & Toolless Access Panels UX Technicoat Evaporator & Condenser Coils, Phase Monitor, & Dirt y Filter Switch, Hinged Filter Door & Toolless Access Panels UY Technicoat Evapor ator & Condenser Coils, Coil Guard, & Dirty Filter Switch, Hinged Filter Door & Toolless Access Panels UZ Technicoat Evap ora to r & C onde nse r Co il s, Ph as e Moni to r, Coil Guard, & Dirt y Fi lte r Sw itch , Hing ed Fi lter Doo r & Toolle ss Access Panels
Unita ry P rod ucts Gro up 7
Page 8
036-21502-002-A-0303
FEATURES
All models are available with a wide variety of factory­mounted options such as stainless steel heat exchangers, phase monitor, dirty filter switc h, and coi l guard t o make them suitable for almost every appli cation.
All units are self-contained and assembled on full perimeter base rails with forklift holes on three sides and holes for over­head rigging. Every unit is completely piped, wired, charged and tested at the f act ory t o sim plify t he fiel d inst all atio n and to provide years of dependable operation.
All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. For bottom duct, remove the sheet metal pan els from the supply and return air openings through the base of the uni t. For horizon­tal duct, remove the supply and return ai r panels on the rear of the unit.
All models ar e avail able wi th the se “fac tory moun ted” outdoor air damper options:
Single enthal py economizer
Motorized out door air damper Supply air blowers are equippe d with ei ther a di rect drive or a
belt drive that can be adjusted to meet the exact require­ments of the job.
All compressors are equi pped with internal pressure relief. Every refrigeran t circuit include s a liquid line filter -drier , a high pressure switch and a suction line with a freezestat and low pressure/l oss of charge switch to prot ect all system compo­nents.
Simplicity
standardized a number of features previously available only as options or by utilizing additional controls.
Low Ambient - An integrated low-ambi ent control
Anti-Short Cycle Protecti on - To aid compr essor
Fan Delays - Fan on and fan off delays are fully pro-
Safety Monitoring - The control board monitors the
™ Controls -
allows all units to operate in the cooling mode down to 0ºF outdoor ambient without additional assis­tance. Opti onally, the control board can be pro­grammed to lockout the compressors when the outdoor ai r temperature is low or when free cooling is available.
life, an anti- short cycle del ay is inco rporat ed into t he standard controls. Compressor reliability is furt her ensured by programm able minimum run times. For testing, the anti short cycle del ay can be temporari ly overridden with the push of a button.
grammable and are independent of one another. All units are programmed with default valu es based upon their conf iguration of cooling and heat .
high and low-pr essure swi tches , the fr eezest ats , the
Simplicity
™ control boards have
gas valve, if applic able, and the temperatur e li m it switch on gas heat units. The unit control board will alarm on ignition fai lures, compressor lockouts and repeated limit swit ch trips.
Nuisance Trip Protection- To prevent nuisance trouble calls, th e control board uses a “three str ikes, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times within two hours before the uni t control board will lock out the compressor.
On Board Diagnostics - Each alarm wi ll ener gize a trouble light on the thermostat, if so equipped, and flash an al arm code on the control board LED. Each high and low-pressure switch alarm as well as each freezestat alarm has its own fl ash code. The control board saves the five most recent alarms in memory , and these alarms can be revi ewed at any time. Alarms and programmed valu es are retained through the loss of power.
All units have long l asting powder paint cabinets with 750 hour salt spray test appr oval under ASTM-B117 procedures.
All models are CSA listed.
Warranty - All models include a one-year limited parts warranty on the compl ete uni t. Compres sors and el ectri c heater elements carry a five-year warranty. Gas heat exchangers carry a 10-year parts war ranty .
Gas Heat Operation - All gas heat units have a mini- mum AFUE of 80%. Each section includes a durable heat exchanger with aluminized steel or optional stain­less steel tubes, a redundant gas valve, spark ignition, power venting, an ignition module for 100% shut-off and all of the safety controls required to meet th e latest ANSI standards.
The gas supply piping can be routed into the heating compartment through a hole in the base pan of the unit or through a knockout in the pi ping panel on the front of
the unit.
Electric Heat Operation - All electric heat models are wired for a single power source and include a bank of nickel chromium el em ents mounted at the discharge of the supply air blower to provide a high velocity and uni­form distributi on of air across the heating el em ents. Every element is fully protected agains t excessive tem­perature by thermal li m it switches.
The power supply wiring can be routed into the control box through a threaded pipe connection (field supplied) in the base pan of the unit or through a knockout in the wiring panel on the sid e of th e unit .
BAS Controls - York’s Sunline™ series units offer fac­tory mounted BAS controls suc h as Novar, Honeywell, Johnson, and CPC.
8 Unitary Products Group
Page 9
036-21502-002-A-0303
FIGURE 1: UNIT CUTAWAY
FACTORY-INSTALLED OPTIONS
SINGLE INPUT ELECTRONIC ENTHALPY ECONO­MIZERS - Includes a slide-in / plug-in damper assembly
with fully modulat ing spring-return motor actuator capa­ble of introduci ng up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor ai r and det ermines when the air is cool enough and dry enough to provide free cooling.
The rainhood is paint ed to match t he bas ic unit and must be field-asse mbled before installing.
MOTORIZED OUTDOOR AIR INTAKE DAMPER ­Includes a slide-in / plug-in damper assembly with a 2­position, spring return motor actuator which opens to a pre-set posi ti on whenever the supply air blower is oper­ating and will drive fully closed when the blower unit shuts down.
The rain hood is painted to match the basi c unit and must be field assembl ed before installing.
PHENOLIC COATED EVAPORATOR AND CON- DENSER COILS - Special coating process that ut ilizes
Technicoat 10-1 immersion of the compl e te coil for maximum protection.
TM
processes. Coati ng is applied by total
ELECTRIC HEATERS wired for si ngle point power sup- ply. These nickel chromium heater elements are pro­vided with limit and autom atic reset capability to prevent operation at exces sive temperatures.
FILTER OPTIONS - Standard units are shi pped with 1” throw-away filte rs installed. 2” ple ated filters are offered as a factory installed option.
CONVENIENCE OUTLET - This 110 volt outlet can be “powered” by the unit wi th a stepd own transf ormer or the unit may be ordered with a “non- powered” convenienc e outlet that can be wired in the f ield.
DISCONNECT SWITCH - For gas heat unit s and cool ing units with electric heat, a HACR breaker sized to th e unit is provided. For cooling only units, a switch sized to the largest electri c heat available for the particular unit is provided. Facto ry i nstalled option only .
BAS - See “Additional Options” section in the product nomenclature.
SMOKE DETECTORS - (supply air & ret u rn air ) The smoke detectors sto p operation of the unit by interrupt ing power to the co ntrol board i f sm oke is detect ed withi n the air compartment.
Unita ry P rod ucts Gro up 9
Page 10
036-21502-002-A-0303
COIL GUARD - Customers can purchase a coi l guar d kit to protect the condenser coil from damage. Thi s is not a hail guard kit.
STAINLESS STEEL HEAT EXCHANGER - For applica- tions in corrosive environments, this option pro vides a full sta inl ess steel heat exch anger assembly.
PHASE MONITORS - Designed to prevent unit damage. The phase monitor will shut the unit down in an out-of­phase condition.
DIRTY FILTER SWITCH - This kit includes a differential pressure swit ch that energizes the fau lt light on the unit thermostat, indicating that there is an abnormally hi gh pressure drop across the filters. Factory install ed option or field installed accessory.
HINGED FILTER DOOR/“TOOLLESS” BLOWER AND ACCESS P ANELS (not hinged) - This option allows for easy access and maintenance.
NOTE:Knobs are shipped inside the unit to prevent ship-
ping damage. These must be fi eld installed for tool-less operation.
FIELD-INSTALLED ACCESSORIES
SINGLE INPUT ELECTRONIC ENTHALPY ECONO­MIZERS - Includes a slide-in / plug- in damper assembly
with fully modulat ing spring-return motor actuator capa­ble of introduci ng up to 100% outdoor air with nominal 1% leakage type dampers.
The enthalpy system contains one sensor that monitors the outdoor ai r and det ermines when the air is cool enough and dry enough to provide free cooling.
The rainhood is paint ed to match t he bas ic unit and must be field-ass emb led before installing.
MOTORIZED OUTDOOR AIR INTAKE DAMPER ­Includes a slide-in / plug-in damper assembly with a 2­position, spring return motor actuator which opens to some pre-set position whenever the supply ai r blower is operating and will drive f ully closed when the blower unit shuts down.
The rain hood is painted to match the basi c unit and must be field assembl ed before installing.
ELECTRIC HEATERS wi red for single point power sup­ply. These nickel chromium heater elemen ts are pro­vided with limit and automatic reset capabi lity to prevent operation at ex cessive temperatures.
Roof curbs are designed to fit inside t he base rails of the unit and include both a wood nai li ng strip and duct hanger supports.
HIGH ALTITUDE NATURAL GAS - Burner orifices and pilot orifi ces are provided for proper furnace operation at altitudes up to 6,000 f eet.
PROPANE - Burner orifices, pilot orif ices and gas valve parts are prov ided to convert a natural gas furnace to propane.
HIGH ALTITUDE PROPANE - Burner orifices and pilot orifices are provi ded for proper furnace operation at alti­tudes up to 6,000 feet. This accessory supplement s the basic propane conversion kit.
LOW NOX KIT- Required t o reduce the emission of nitrogen oxides below 40 nanograms per joule.
POWER EXHAUST - Our single input economizer options are available with power exhaust. Whenever the outdoor air intake dampers are opened for free cooling, the exhaust fan will be ener gized to prevent the condi­tioned space from being over-pressurized during econo­mizer operation .
The power exhaust option can only be used on bot­tom duct configurations.
BAROMETRIC RELIEF DAMPER - This damper acces­sory can be used to relieve internal building air pressure on units with an econo mizer withou t power exha ust. This accessory includes a rain hood, a bird sc reen and a fully assembled damper. W ith bottom duct connections, the damper should be mounted over the opening in the return air panel. With h ori zontal ductwork, the accessory should be mounted on the ret urn ai r duct.
ENTHALPY ACCESSORY CONTROL KIT - This kit contains the required components to convert a single enthalpy economizer to dual enthalpy.
BURGLAR BARS - Mount in the supply and return openings to pr event entry into the duct work.
FLUE EXHAUST EXTENSION KIT - In locations with wind or weather conditions which may interfere with proper exhausti ng of fu rnace combustion products, this kit can be installed to prevent the flue exhaust from entering nearby fresh air intakes.
CO
SENSOR - Senses CO2 levels and automatically
2
overrides the econ om izer when levels rise above the present limits.
ROOF CURBS - Eight and fourteen-inch high roof c urbs provide a water-ti ght seal between the unit and the fin­ished roof. These full perimeter curbs meet the require­ments of the National Roofing Contractors Association (NRCA) and are shipped knocked-down for field assem­bly.
10 Unitary Products Group
COIL GUARD - Customers can purchase a coil guard kit to protect the condenser coil from damage. This is not a hail guard kit.
Page 11
036-21502-002-A-0303
TABL E 1: SOUND POWER RATING
UNIT SIZE
CFM
ESP BLOWER
IWG SPEED KW 63 125 250 500 1,000 2,000 4,000 8,000
1
SOUND POWER (db 10
Oct ave Band Centerline Frequency (Hz)
-12
Watts)
SWL
dB(A)
dB(A)
@
10Ft.
036 1,2000.6LOW0.6084847467696257527441 048 1,6000.55HIGH0.8085857568706358537542 060 2,0000.45HIGH1.0086867669716459547643 072 2,200 0.3 HIGH 1.35 87 87 77 70 72 65 60 55 77 44
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric\free field. The dBA values provided are to be used for refer ence only. C alculation of dBA values cover matters of system design and the fan manufacture has no way of kn owing the details of each sy stem. This constitutes and expect ation to any speci fication or guaran­tee requiring a dBA value or sound data in any other form than sound power level ratings.
2. At a distance of 10 feet from the blower.
TABL E 2: CAPACITY RATINGS - (ARI 210/240)
MODEL MBH
DM036
36.0 9.1 10.0
EER
2
1
SEER
3
DM048 47.4 9.0 10.0 DM060 59.0 9.1 10.0 DM072 72.0 9.0 -
1. 80/67°F Indoor and 95°F outdoor.
2. EER = Energy Efficiency Ratio at full load - the cooling capacity in Btu’s per hour (B tuh) divided by the power input in watts, expressed in Btuh per watt (Btuh/watt).
3. SEER = Seasonal Energy Efficiency Ratio.
2
TABL E 3: GAS HEAT RATINGS
MODEL
DM036N04 DM036N08
DM048N06 DM048N10
DM060N08 DM060N10
DM072N08 DM072N10
MBH
INPUT
50
100
75
125 100
125 100
125
1
MBH
OUTPUT
40 79
59 99
79 99
79 99
AFUE
(%)
80.9
80.5
80.9
80.3
80.5
80.3
80.5
80.3
TEMP
RISE ºF
15 - 45 40 - 70
25 - 55 45 - 75
25 - 55 35 - 65
25 - 55 35 - 65
1. All units are single-stage heating.
Unita ry P rod ucts Gro up 11
Page 12
TABLE 4: DM036 COOLING CAPACITIES (3 TON)
036-21502-002-A-0303
AIR ON
EVAPORATOR
COIL
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
85°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
TEMPERATURE OF AIR ON CONDENSER COIL
1
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
95°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
1
72 45 3.1 35 30 26 21 17 - - 43 3.3 35 30 26 21 17 - -
1750
67 43 3.0 43 38 34 29 25 20 16 41 3.3 41 38 34 29 25 21 16 62 39 3.0 39 39 39 34 30 25 21 36 3.3 36 36 36 32 27 23 18 57 40 2.9 40 40 40 35 31 26 22 38 3.2 38 38 38 33 29 24 20 72 44 3.1 31 28 24 20 16 - - 42 3.3 31 27 23 20 16 - -
1475
67 41 3.0 39 35 31 27 23 19 16 39 3.3 37 35 31 27 23 19 15 62 38 3.0 38 38 37 33 29 25 21 36 3.3 36 36 35 31 27 23 19 57 39 2.9 39 39 39 35 31 27 23 37 3.2 37 37 36 32 28 25 21 72 42 3.1 28 25 22 18 15 - - 41 3.3 28 24 21 18 14 - -
1200
67 40 3.0 35 32 28 25 22 18 15 38 3.2 34 31 28 25 21 18 15 62 36 3.0 36 36 35 31 28 25 21 35 3.3 35 35 34 30 27 24 20 57 37 2.9 37 37 37 34 31 27 24 36 3.2 36 36 35 32 28 25 22 72 41 3.1 26 23 20 17 14 - - 39 3.2 26 23 20 17 14 - -
1050
67 38 3.0 32 30 27 24 21 18 15 37 3.2 32 29 26 23 20 17 14 62 35 3.0 35 35 33 30 27 24 21 33 3.2 33 33 31 28 25 22 20 57 36 2.9 36 36 35 32 29 26 23 34 3.2 34 34 32 30 27 24 21 72 39 3.1 24 21 19 16 14 - - 38 3.2 23 21 18 16 13 - -
900
67 37 3.0 30 27 25 22 20 17 15 36 3.2 29 26 24 21 19 16 14 62 34 3.0 34 33 30 28 25 23 20 32 3.2 32 31 29 26 24 21 19 57 34 2.9 34 34 33 30 27 25 22 33 3.1 33 33 30 27 25 22 20
AIR ON
EVAPORATOR
COIL
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
105°F 115°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
TEMPERATURE OF AIR ON CONDENSER COIL
1
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
SENSIBLE CAPACITY
1
72 41 3.7 34 29 25 20 16 - - 39 4.1 33 28 24 19 15 - -
1750
67 38 3.7 38 37 33 28 24 19 15 36 4.0 36 36 32 27 23 18 14 62 34 3.7 34 34 34 30 25 21 16 32 4.0 32 32 32 27 23 18 14 57 35 3.6 35 35 35 31 26 22 17 33 4.0 33 33 33 28 24 19 15 72 40 3.7 30 26 23 19 15 - - 38 4.1 30 26 22 18 14 - -
1475
67 37 3.6 36 34 30 26 22 18 14 35 4.0 34 33 29 25 21 17 13 62 33 3.7 33 33 33 29 25 21 17 31 4.0 31 31 31 27 23 19 15 57 34 3.6 34 34 34 30 26 22 18 32 4.0 32 32 32 28 24 20 16 72 39 3.7 27 24 20 17 14 - - 37 4.1 26 23 20 16 13 - -
1200
67 36 3.6 34 30 27 24 20 17 14 34 4.0 33 30 26 23 20 16 13 62 32 3.6 32 32 32 29 25 22 19 30 4.0 30 30 30 27 24 20 17 57 33 3.6 33 33 33 29 26 23 19 31 3.9 31 31 31 27 24 21 17 72 37 3.6 25 22 19 16 13 - - 36 4.1 24 21 18 15 12 - -
1050
67 35 3.6 31 28 25 22 19 16 13 32 4.0 30 27 24 21 18 15 12 62 31 3.6 31 31 29 27 24 21 18 29 4.0 29 29 28 25 22 19 16 57 32 3.5 32 32 30 27 24 21 18 30 3.9 30 29 28 25 22 19 16 72 36 3.6 22 20 17 15 12 - - 34 4.0 21 19 16 14 11 - -
900
67 33 3.6 28 25 23 20 18 15 13 31 4.0 27 24 22 19 17 14 11 62 30 3.6 30 29 27 24 22 19 17 28 4.0 28 28 25 22 20 17 15 57 31 3.5 31 30 28 25 22 20 17 28 3.9 28 28 25 23 20 17 15
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
12 Unitary Products Group
Page 13
036-21502-002-A-0303
TABLE 5: DM048 COOLING CAPACITIES (4 TON)
AIR ON
EVAPORATOR
COIL
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
85°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
TEMPERATURE OF AIR ON CONDENSER COIL
1
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
95°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
1
72 60 4.1 44 39 33 28 23 - - 60 4.5 44 39 33 28 23 - -
2000
67 55 4.1 53 48 42 37 32 26 21 52 4.5 52 47 42 36 31 25 20 62 51 4.0 51 51 51 45 40 34 29 48 4.4 48 48 48 42 37 32 26 57 49 3.9 49 49 49 44 39 33 28 47 4.3 47 47 47 42 36 31 26 72 58 4.1 41 36 31 26 21 - - 57 4.5 41 36 31 26 21 - -
1800
67 53 4.1 49 45 40 35 30 25 20 50 4.5 49 44 39 34 29 24 19 62 49 4.0 49 49 48 43 38 33 28 46 4.4 46 46 46 41 36 31 26 57 47 3.9 47 47 47 43 38 33 28 45 4.3 45 45 45 40 36 31 26 72 56 4.1 38 34 29 25 20 - - 55 4.6 38 33 29 24 20 - -
1600
67 51 4.1 46 41 37 32 28 24 19 48 4.5 45 40 36 31 27 23 18 62 47 4.0 47 47 45 41 36 32 27 44 4.4 44 44 44 40 35 31 26 57 46 3.9 46 46 46 41 37 32 28 44 4.4 44 44 44 39 35 30 26 72 54 4.1 35 31 27 23 19 - - 53 4.5 35 31 27 23 19 - -
1400
67 49 4.1 42 38 34 30 26 22 19 47 4.5 41 38 34 30 26 22 18 62 45 4.0 45 45 42 38 34 30 26 43 4.4 43 43 41 37 33 29 25 57 44 3.9 44 44 43 39 35 31 27 42 4.3 42 42 41 37 33 29 25 72 52 4.1 32 29 25 22 18 - - 51 4.5 32 28 25 21 18 - -
1200
67 47 4.1 39 35 32 28 25 21 18 45 4.4 38 35 31 28 24 21 17 62 43 4.0 43 43 39 36 32 29 25 41 4.3 41 41 38 35 31 28 24 57 42 3.9 42 42 39 36 32 29 25 41 4.3 41 41 38 34 31 27 24
AIR ON
EVAPORATOR
COIL
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
105°F 115°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
TEMPERATURE OF AIR ON CONDENSER COIL
1
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
SENSIBLE CAPACITY
1
72 56 5.1 42 37 31 26 21 - - 53 5.6 40 35 29 24 19 - -
2000
67 49 5.0 49 46 40 35 29 24 19 46 5.5 46 44 39 33 28 23 17 62 45 4.9 45 45 45 39 34 28 23 41 5.4 41 41 41 36 30 25 20 57 44 4.9 44 44 44 39 33 28 22 41 5.4 41 41 41 35 30 25 19 72 55 5.0 39 34 29 24 20 - - 52 5.5 38 33 28 23 18 - -
1800
67 48 5.0 47 43 38 33 28 23 18 45 5.4 45 42 37 32 27 22 17 62 43 4.9 43 43 43 38 33 28 23 40 5.4 40 40 40 35 30 26 21 57 43 4.9 43 43 43 38 33 28 23 40 5.4 40 40 40 35 30 25 20 72 53 5.0 36 32 28 23 19 - - 51 5.5 35 31 26 22 17 - -
1600
67 46 4.9 44 40 35 31 26 22 17 44 5.4 44 39 35 30 26 21 17 62 42 4.9 42 42 42 37 33 28 24 39 5.3 39 39 39 35 30 26 21 57 41 4.8 41 41 41 37 32 28 23 39 5.3 39 39 39 34 30 25 21 72 51 5.0 33 29 26 22 18 - - 48 5.5 32 28 24 20 16 - -
1400
67 44 4.9 41 37 33 29 25 21 17 42 5.3 40 36 32 28 24 20 16 62 40 4.8 40 40 39 35 31 27 23 37 5.3 37 37 36 32 28 24 20 57 40 4.8 40 40 38 34 30 26 22 37 5.3 37 37 36 32 28 24 20 72 49 4.9 30 27 23 20 16 - - 46 5.4 29 26 22 19 15 - -
1200
67 42 4.9 37 34 30 27 23 20 16 39 5.3 36 33 29 26 22 19 15 62 38 4.8 38 38 36 32 29 25 22 35 5.3 35 35 33 29 26 22 19 57 38 4.8 38 38 35 32 28 25 21 35 5.3 35 35 33 29 26 22 19
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
Unita ry P rod ucts Gro up 13
Page 14
TABL E 6: DM060 COOLING CAPACITIES (5 TON)
036-21502-002-A-0303
AIR ON
EVAPORATOR
COIL
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
85°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
TEMPERATURE OF AIR ON CONDENSER COIL
1
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
95°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
1
72 68 4.9 50 44 38 32 25 - - 65 5.6 50 43 37 31 24 - -
2500
67 62 4.8 62 56 50 43 37 31 24 60 5.3 60 54 48 42 35 29 23 62 57 4.7 57 57 57 51 44 38 32 53 5.3 53 53 53 47 41 34 28 57 55 4.7 55 55 55 48 42 36 29 51 5.4 51 51 51 44 38 32 25 72 67 4.9 48 42 36 30 24 - - 65 5.4 47 41 35 29 23 - -
2250
67 62 4.8 59 53 47 41 35 30 24 59 5.2 57 51 45 40 34 28 22 62 56 4.7 56 56 56 50 45 39 33 53 5.2 53 53 53 47 41 35 29 57 54 4.7 54 54 54 48 42 36 31 50 5.3 50 50 50 44 39 33 27 72 66 4.9 45 39 34 29 23 - - 64 5.3 44 39 33 28 22 - -
2000
67 61 4.8 55 50 44 39 34 28 23 58 5.1 54 48 43 38 32 27 22 62 55 4.7 55 55 55 50 45 39 34 52 5.1 52 52 52 47 42 36 31 57 53 4.6 53 53 53 48 42 37 32 50 5.2 50 50 50 44 39 34 28 72 63 4.8 41 36 31 27 22 - - 61 5.4 40 35 31 26 21 - -
1750
67 58 4.7 51 46 41 36 32 27 22 56 5.1 49 44 39 35 30 25 21 62 53 4.6 53 53 51 47 42 37 32 50 5.2 50 50 48 43 39 34 29 57 51 4.6 51 51 49 44 40 35 30 47 5.2 47 47 46 41 36 32 27 72 60 4.8 37 33 29 25 21 - - 58 5.4 36 32 28 24 20 - -
1500
67 56 4.7 46 42 38 34 30 26 21 53 5.2 44 40 36 32 28 24 20 62 51 4.6 51 51 47 43 39 35 31 47 5.2 47 47 44 40 36 32 27 57 49 4.6 49 49 45 41 37 33 29 45 5.3 45 45 42 38 34 29 25
AIR ON
EVAPORATOR
COIL
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
105°F 115°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
TEMPERATURE OF AIR ON CONDENSER COIL
1
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
SENSIBLE CAPACITY
1
72 61 6.1 48 41 35 29 22 - - 57 6.7 46 39 33 27 20 - -
2500
67 55 5.9 55 52 46 39 33 27 20 50 6.6 50 50 43 37 31 24 18 62 49 5.9 49 49 49 42 36 30 23 44 6.5 44 44 44 38 31 25 19 57 47 5.9 47 47 47 40 34 28 21 42 6.5 42 42 42 36 30 23 17 72 61 6.0 45 39 33 28 22 - - 57 6.6 43 38 32 26 20 - -
2250
67 54 5.9 53 49 44 38 32 26 20 50 6.5 50 47 42 36 30 24 18 62 48 5.8 48 48 48 42 37 31 25 44 6.4 44 44 44 38 32 26 20 57 46 5.8 46 46 46 40 35 29 23 42 6.4 42 42 42 36 31 25 19 72 60 6.0 42 37 32 26 21 - - 57 6.6 41 36 30 25 20 - -
2000
67 54 5.8 52 47 41 36 31 25 20 50 6.5 50 45 40 34 29 24 18 62 48 5.7 48 48 48 43 37 32 27 44 6.4 44 44 44 38 33 28 22 57 46 5.8 46 46 46 41 35 30 25 42 6.3 42 42 42 37 32 26 21 72 57 6.0 38 34 29 24 19 - - 53 6.5 37 32 27 23 18 - -
1750
67 51 5.8 47 42 38 33 28 24 19 46 6.4 45 41 36 31 26 22 17 62 45 5.7 45 45 44 39 34 30 25 41 6.3 41 41 39 35 30 25 21 57 43 5.8 43 43 42 37 32 28 23 39 6.3 39 39 38 33 29 24 19 72 54 6.0 34 30 26 22 18 - - 49 6.5 33 28 24 20 16 - -
1500
67 48 5.8 42 38 34 30 26 22 18 43 6.4 40 36 32 28 24 20 16 62 43 5.7 43 43 39 35 31 27 23 38 6.3 38 38 35 31 27 23 19 57 41 5.8 41 41 38 34 30 26 21 37 6.2 37 37 34 30 26 22 18
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
14 Unitary Products Group
Page 15
036-21502-002-A-0303
TABL E 7: DM072 COOLING CAPACITIES (6 TON)
AIR ON
EVAPORATOR
COIL
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
85°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
TEMPERATURE OF AIR ON CONDENSER COIL
1
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
95°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F
1
72 80 5.7 63 55 47 40 32 - - 77 6.3 63 55 47 40 32 - -
2700
67 80 5.7 76 68 60 53 45 37 30 77 6.3 75 68 60 53 45 37 30 62 70 5.5 70 70 70 62 55 47 39 71 6.3 71 71 71 63 56 48 40 57 68 5.6 68 68 68 60 52 45 37 71 6.3 71 71 71 63 56 48 40 72 82 5.7 60 53 46 38 31 - - 76 6.3 60 53 46 39 31 - -
2550
67 82 5.7 73 65 58 51 43 36 29 76 6.3 73 66 58 51 44 36 29 62 71 5.5 71 71 70 62 55 48 41 70 6.3 70 70 69 62 55 48 40 57 69 5.6 69 69 69 62 55 47 40 70 6.3 70 70 70 62 55 48 40 72 83 5.7 58 51 44 37 30 - - 75 6.3 58 51 44 37 30 - -
2400
67 83 5.7 70 63 56 49 42 35 28 75 6.3 70 64 57 50 43 36 29 62 73 5.5 73 73 70 63 56 49 42 69 6.3 69 69 68 61 54 47 40 57 71 5.6 71 71 71 64 57 50 43 69 6.3 69 69 68 61 54 47 40 72 79 5.7 54 48 41 35 29 - - 73 6.3 53 47 41 35 29 - -
2100
67 79 5.7 65 59 53 47 40 34 28 73 6.3 65 59 52 46 40 34 28 62 69 5.5 69 69 66 60 54 47 41 67 6.3 67 66 63 57 51 45 38 57 67 5.6 67 67 67 61 54 48 42 67 6.3 67 66 63 57 51 45 39 72 74 5.6 50 44 39 34 28 - - 71 6.3 49 43 38 33 27 - -
1800
67 74 5.6 60 55 50 44 39 34 28 71 6.3 59 54 48 43 38 32 27 62 65 5.4 65 65 62 57 51 46 41 65 6.2 65 63 58 53 47 42 37 57 63 5.5 63 63 63 58 52 47 42 65 6.3 65 63 58 53 47 42 37
AIR ON
EVAPORATOR
COIL
CFM WB °F 86 83 80 77 74 71 68 86 83 80 77 74 71 68
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
105°F 115°F
SENSIBLE CAPACITY
ENTERING DRY BULB, °F ENTERING DRY BULB, °F
TEMPERATURE OF AIR ON CONDENSER COIL
1
TOTAL
CAP.
MBH
1
POWER
INPUT
2
kW
SENSIBLE CAPACITY
1
72 76 7.1 61 53 45 38 30 - - 75 7.9 59 51 43 36 28 - -
2700
67 71 7.1 70 66 58 50 43 35 27 65 7.8 65 64 56 48 41 33 25 62 64 7.0 64 64 64 56 49 41 34 57 7.8 57 57 57 50 42 34 27 57 64 7.0 64 64 64 56 49 41 34 57 7.7 57 57 57 50 42 34 27 72 76 7.1 59 51 44 37 29 - - 76 7.9 57 49 42 35 27 - -
2550
67 71 7.1 69 64 56 49 42 34 27 66 7.9 66 61 54 47 40 32 25 62 64 7.0 64 64 64 56 49 42 35 58 7.8 58 58 58 51 43 36 29 57 64 7.0 64 64 64 56 49 42 34 58 7.7 58 58 58 50 43 36 29 72 75 7.1 56 49 43 36 29 - - 76 8.0 55 48 41 34 27 - -
2400
67 70 7.1 68 61 54 48 41 34 27 66 7.9 66 59 52 45 38 32 25 62 64 7.0 64 64 63 56 49 42 35 59 7.8 59 59 59 52 45 38 31 57 64 7.0 64 64 63 56 49 42 35 59 7.7 59 59 58 51 44 37 30 72 73 7.1 52 45 39 33 27 - - 73 7.9 50 44 37 31 25 - -
2100
67 68 7.1 63 56 50 44 38 32 26 63 7.8 61 54 48 42 36 30 24 62 61 7.0 61 61 58 52 46 40 34 56 7.7 56 56 54 48 42 35 29 57 61 7.0 61 61 58 52 46 40 34 56 7.7 56 56 53 47 41 35 29 72 70 7.1 47 41 36 31 25 - - 69 7.8 45 40 34 29 23 - -
1800
67 65 7.0 57 51 46 41 35 30 25 60 7.8 55 49 44 39 33 28 23 62 59 7.0 59 58 54 48 43 38 32 53 7.7 53 53 49 44 39 33 28 57 59 6.9 59 58 53 48 43 37 32 53 7.6 53 53 49 44 38 33 27
1. These capacities are gross ratings. For net capacity, determine the kW of the supply air blower motor from the SUPPLY AIR BLOWER PERFORMANCE Table, multiply this value by 3.415 MBH/kW to determine the motor heat, and deduct this heat from the gross capacity of the unit.
2. These ratings include the compressor and the condenser fan motors but not the supply air blower motor. The total condenser fan motor power input is 0.36kW. Refer to the SUPPLY AIR BLOWER PERFORMANCE Table for the kW of the supply air blower motor.
NOMINAL RATING
Unita ry P rod ucts Gro up 15
Page 16
036-21502-002-A-0303
TABL E 8: SUPPLY AIR BLOWER PERFORMANCE (3 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
SIZE
(MBH)
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
0.20 0.30 0.40 0.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3
0.60 0.70 0.80
1700 835 705 880 745 923 795 969 860 1013 970 ----
1600 811 655 854 695 898 740 942 790 986 840 1029 900 - -
1500 782 610 827 650 871 685 917 730 960 775 1003 825 1046 905
1400 - - 798 595 844 640 889 680 932 720 975 765 1018 790
1 2
036
1300 ----816590862635907675951715995750
1200 ------834585881630927665970705
1100 ------809550855590900625942665
1000 ------782510829545872858919625
900--------797500843540890580
UNIT
SIZE
(MBH)
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
0.90 1.00 1.10 1.20 1.30 1.40 1.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3
1700 --------------
1600 --------------
1500 --------------
1400 1055 875 ------------
1 2
036
1300 1036 780 1066 850 ----------
1200 1011 735 1047 765 1075 800 --------
1100 987 690 1028 720 1060 750 1084 775 ------
1000 963 655 1005 680 1040 695 1068 715 1089 735 ----
900 936 615 980 645 1020 660 1050 670 1053 680 1090 690 - -
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows.
16 Unitary Products Group
Page 17
036-21502-002-A-0303
TABL E 9: SUPPLY AIR BLOWER PERFORMANCE (4 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT SIZE
(MBH)
1 2
048
UNIT SIZE
(MBH)
1 2
048
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
0.20 0.30 0.40 0.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3
0.60 0.70 0.80
2000 843 860 880 925 919 1005 956 1065 993 1145 1030 1195 1067 1235
1900 817 775 854 850 893 920 930 995 970 1065 1008 1125 1046 1170
1800 790 700 828 760 867 840 906 905 944 980 985 1040 1025 1100
1700 - - 802 670 840 745 881 815 920 900 961 970 1001 1030
1600 ----818665858740898820940890980950
1500 ------842695882755922835962895
1400 ------833650867705904765942820
1300 --------858665893725932785
1200 --------847640880680916730
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
0.90 1.00 1.10 1.20 1.30 1.40 1.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3
2000 1103 1270 ------------
1900 1085 1210 ------------
1800 1064 1145 1102 1180 ----------
1700 1040 1075 1081 1115 1121 1140 --------
1600 1020 1005 1060 1050 1100 1085 --------
1500 1003 945 1044 995 1086 1035 --------
1400 982 880 1024 920 1067 965 1107 1000 ------
1300 970 835 1010 870 1053 920 1099 960 ------
1200 953 780 992 815 1034 855 1080 905 ------
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows.
Unita ry P rod ucts Gro up 17
Page 18
036-21502-002-A-0303
TABL E 10: SUPPLY AIR BLOWER PERFORMANCE (5 TON BELT DRIVE) - SIDE DUCT APPLICATION
UNIT
SIZE
(MBH)
060
UNIT
SIZE
(MBH)
060
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
0.20 0.30 0.40 0.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3
0.60 0.70 0.80
2500 1059 1560 1077 1590 1095 1630 1114 1650 1134 1660 1158 1685 1181 1720
2400 1032 1405 1054 1470 1074 1525 1094 1560 1116 1595 1140 1620 1167 1640
2300 1005 1260 1024 1275 1049 1370 1069 1440 1090 1475 1116 1505 1142 1535
2200 980 1160 1002 1170 1022 1190 1044 1250 1066 1350 1090 1410 1117 1440
2100 930 1060 957 1070 983 1080 1010 1100 1039 1160 1064 1260 1092 1340
1 2
2000 877 950 908 975 941 1000 976 1020 1009 1050 1040 1100 1070 1225
1900 ----8948859409409809801014 1020 1047 1095
1800 ----8558159038609509059889401022 970
1700 ------8848159258509648801001 910
1600 ------864770908805948835987870
1500 --------882740926780965830
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
0.90 1.00 1.10 1.20 1.30 1.40 1.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3
2500 --------------
2400 1193 1665 ------------
2300 1170 1580 1202 1620 ----------
2200 1148 1480 1180 1530 ----------
2100 1121 1385 1155 1425 1190 1475 --------
1 2
2000 1100 1285 1133 1340 1169 1385 1205 1445 ------
1900 1079 1180 1110 1240 1143 1280 1178 1330 1222 1375 ----
1800 1058 1060 1090 1135 1122 1190 1158 1240 1196 1295 ----
1700 1035 960 1071 1030 1103 1100 1134 1140 1164 1175 1197 1205 - -
1600 1020 900 1056 965 1088 1035 1118 1065 1145 1105 1170 1130 1198 1150
1500 1004 860 1038 880 1070 925 1101 980 1130 1045 1158 1075 1184 1110
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows.
18 Unitary Products Group
Page 19
036-21502-002-A-0303
TABL E 11: SUPPLY AIR BLOWER PERFORMANCE (6 TON BEL T DRIVE) - SIDE DUCT APPLICATION
UNIT SIZE
(MBH)
1 2
072
UNIT SIZE
(MBH)
1 2
072
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
0.20 0.30 0.40 0.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3
0.60 0.70 0.80
3200 1150 2325 1182 2425 1212 2525 --------
3000 1100 2010 1129 2090 1157 2150 1185 2225 1215 2290 1242 2360 - -
2800 1045 1700 1074 1780 1102 1850 1131 1940 1160 2025 1190 2075 1217 2130
2600 985 1425 1015 1475 1045 1540 1075 1630 1103 1715 1135 1760 1163 1825
2400 930 1240 958 1300 990 1350 1020 1400 1051 1430 1081 1490 1111 1600
2200 - - 905 1070 933 1160 965 1210 997 1250 1028 1285 1060 1325
2000 ------9191025 950 1100 982 1130 1014 1160
1800 --------9099259391005 968 1030
AIR
FLOW
CFM
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
0.90 1.00 1.10 1.20 1.30 1.40 1.50
RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS RPM WATTS
3
3200 --------------
3000 --------------
2800 1245 2190 ------------
2600 1193 1920 1222 1990 1250 2060 --------
2400 1142 1675 1173 1730 1205 1800 1234 1885 ------
2200 1090 1380 1124 1450 1155 1550 1186 1640 1217 1710 1249 1775 - -
2000 1045 1175 1077 1200 1109 1275 1140 1360 1170 1460 1205 1545 1235 1600
1800 998 1050 1028 1060 1058 1060 1087 1075 1118 1150 1148 1250 1176 1360
1. 230/460/575 Volts
2. For 208 Volts multiply values by 0.95.
3. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to ACCESSORY STATIC RESISTANCE Table for resistance values on applications other than gas / electric units with side duct airflows.
Unita ry P rod ucts Gro up 19
Page 20
036-21502-002-A-0303
TABLE 12: SUPPLY AIR BLOWER PERFORMANCE (3 - 6 T O N DIRECT DRIVE) - SIDE DUCT APPLICATION
UNIT SIZE
(MBH)
1
036
1
048
1
060
1
072
UNIT SIZE
(MBH)
1
036
1
048
1
060
1
072
MOTOR SPEED
HI
MED
LOW
HI
MED
LOW
HI
MED
LOW
HI
MOTOR SPEED
HI
MED
LOW
HI
MED
LOW
HI
MED
LOW
HI
CFM WATTS CFM WATTS CFM WATTS CFM WATTS CFM WATTS
----1699 825 1650 785 1570 755
1684 800 1631 780 1582 750 1524 720 1410 690
1487 710 1464 690 1421 670 1367 650 1315 620
1996 960 1933 936 1868 910 1795 880 1722 845
1804 838 1765 810 1714 785 1650 765 1589 735
1681 760 1640 738 1604 715 1541 695 1490 670
2400 1155 2338 1125 2274 1095 2167 1045 2096 1010
2290 1105 2214 1065 2145 1030 2071 990 1990 950
2150 1020 2100 990 2029 950 1965 910 1905 880
2461 1480 2402 1440 2361 1395 2260 1350 2178 1305
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
0.70
CFM WATTS CFM WATTS CFM WATTS CFM WATTS
1430 725 1360 700 1280 680 1180 655
1324 650 1260 630 1185 610 1100 590
1246 605 1185 590 1110 570 1020 545
1635 820 1544 790 1419 765 1300 740
1508 705 1407 675 1306 645 1195 625
1416 645 1337 620 1230 595 1120 575
1990 980 1887 945 1771 905 1629 855
1911 920 1828 885 1724 835 1604 798
1816 838 1724 800 1644 770 1531 710
2101 1260 2000 1205 1914 1155 1830 1110
AVAILABLE EXTERNAL STATIC PRESSURE-IWG
2
0.900.80 1.00
1. Side Duct application (230/460/575 Volts)
2. Includes allowances for a wet evaporator coil, 1” filters, and the heat exchangers. Refer to STATIC RESISTANCES Table for resistance values
2
0.600.20 0.30 0.40 0.50
TABL E 13: BELT DRIVE BLOWER MOTOR AND DRIVE DATA
BELT
(NOTCHED)
PITCH
LENGTH
(IN.)
MODEL
SIZE
BLOWER
RANGE
(RPM)
1
MOTOR
HP FRAME
ADJUSTABLE MOTOR PULLEY FIXED BLOWER PULLEY
DESIG­NATION
OUTSIDE
DIA. (IN.)
PITCH
DIA. (IN.)
BORE
(IN.)
DESIG-
NATION
OUTSIDE
DIA. (IN.)
PITCH
DIA. (IN.)
BORE
(IN.)
DESIG-
NATION
3 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1 4 TON 790/1120 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK61 5.9 5.7 1 A36 37.3 1 5 TON 850/1220 1 1/2 56 1VL40 2.7-3.7 2.4-3.4 5/8 AK56 5.4 5.2 1 A36 37.3 1 6 TON 900/1250 1 1/2 56 1VL44 3.1-4.1 2.8-3.8 7/8 AK56 5.4 5.2 1 A36 37.3 1
1. All motors have solid bases and are inherently protected. these motors can be selected to operate into their service factor because they are located in the moving air, upstream of any heating device.
QTY.
20 Unitary Products Group
Page 21
036-21502-002-A-0303
TABL E 14: STATIC RESISTANCES
DESCRIPTION
ECONOMIZER
ELECTRIC
HEATERS
BOTTOM DUCT CONNECTIONS
3
COOLING ONLY
1. Deduct these resistance values from the available external static pressure shown in SUPPLY AIR BLOWER PERFORMANCE Tables.
2. The pressure through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct system is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation.
3. Add these resistance values to the available static resistance values on SUPPLY AIR BLOWER PERFORMANCE Tables.
1 2
5-15KW 0.04 0.05 0.06 0.07 0.08 0.10 0.12 0.14 0.16 0.19 0.22
20-30KW 0.06 0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26
2
1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000
0.07 0.08 0.09 0.11 0.13 0.15 0.17 0.20 0.23 0.26 0.30
1
0.06 0.07 0.08 0.09 0.10 0.11 0.12 0.14 0.16 0.19 0.22
0.08 0.10 0.12 0.14 0.16 0.18 0.20 0.23 0.26 0.29 0.32
TABL E 15: ELECTRIC HEATER CFM LIMITATIONS
RESISTANCE, IWG
CFM
UNIT MODEL SIZE NOMINAL
TONS
3
4
5
6
MINIMUM SUPPLY AIR CFM
VOLTAGE
5 7 10 15 20 30
208/230-1-60 1100 1100 1200 1200 1300 -
208/230-3-60 1100 1100 1200 1200 1300 -
460-3-60 - 1100 1200 1200 1300 -
575-3-60 - - 1200 1200 1300 -
208/230-1-60 1300 1300 1300 1300 1300 -
208/230-3-60 1300 1300 1300 1300 1300 -
460-3-60 - 1300 1300 1300 1300 -
575-3-60 - - 1300 1300 1400 -
208/230-1-60 1600 1600 1600 1600 1600 1600
208/230-3-60 1600 1600 1600 1600 1600 1600
460-3-60 - 1600 1600 1600 1600 1600
575-3-60 - - 1600 1600 1600 1800
208/230-1-60 1800 1800 1800 1800 1800 1800
208/230-3-60 1800 1800 1800 1800 1800 1800
460-3-60 - 1800 1800 1800 1800 1800
575-3-60 - - 1800 1800 1800 1800
HEATER SIZE NOMINAL KW
Unita ry P rod ucts Gro up 21
Page 22
036-21502-002-A-0303
TABL E 16: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
208-1-60 19.2 87
230-1-60 19.2 87 2.3 4.4 0.0
208-3-60 14.1 110
230-3-60 14.1 110 2.3 4.4 0.0
460-3-60 7.1 54
575-3-60 5.8 44 1.3 2.2 0.0
208-1-60 25.0 135
230-1-60 25.0 135 2.3 5.0 0.0
208-3-60 14.7 130
230-3-60 14.7 130 2.3 5.0 0.0
460-3-60 7.7 64
575-3-60 6.4 52 1.3 2.2 0.0
RLA
Each
Each
Compressors
LRA
OD Fan
ID Blower
Motor
FLA
2.3 4.4 0.0
2.3 4.4 0.0
1.3 2.2 0.0
2.3 5.0 0.0
2.3 5.0 0.0
1.3 2.2 0.0
Motor
FLA
Conv Outlet Amps
Electric Heater
Heater
Model No.
NONE 0.0 0.0 30.7 45 2CE04510506 4.0 19.2 30.7 45 2CE04510706 5.6 26.9 39.2 45 2CE04511006 8.0 38.5 53.6 60 2CE04511506 11.9 57.2 77.0 80 2CE04512006 15.9 76.4 101.1 110
NONE 0.0 0.0 30.7 45 2CE04510506 5.3 22.1 33.1 45 2CE04510706 7.5 31.3 44.6 45 2CE04511006 10.6 44.2 60.7 70 2CE04511506 15.9 66.3 88.3 90 2CE04512006 21.2 88.3 115.9 125
NONE 0.0 0.0 24.3 35
2CE04510525 2CE04510725
2CE04511025 8.0 22.2 33.3 35 2CE04511525 11.9 33.0 46.8 50 2CE04512025 15.9 44.1 60.7 70
2CE04510525 5.3 12.7 24.3 35
2CE04510525 2CE04510725
2CE04511525 15.9 38.2 53.3 60 2CE04512025 21.2 51.0 69.2 70
2CE04510746 2CE04511046 2CE04511546 2CE04512046
2CE04511058 10.6 10.2 14.9 15 2CE04511558 15.9 15.3 21.3 25 2CE04512058 21.2 20.4 27.7 30
2CE04510506 4.0 19.2 38.5 60 2CE04510706 5.6 26.9 39.9 60 2CE04511006 8.0 38.5 54.3 60 2CE04511506 11.9 57.2 77.8 80 2CE04512006 15.9 76.4 101.8 110
2CE04510506 5.3 22.1 38.5 60 2CE04510706 7.5 31.3 45.3 60 2CE04511006 10.6 44.2 61.5 70 2CE04511506 15.9 66.3 89.1 90 2CE04512006 21.2 88.3 116.7 125
2CE04510525 2CE04510725
2CE04511025 8.0 22.2 34.0 40 2CE04511525 11.9 33.0 47.5 50 2CE04512025 15.9 44.1 61.4 70
2CE04510525 2CE04510725
2CE04511025 10.6 25.5 38.1 40 2CE04511525 15.9 38.2 54.1 60 2CE04512025 21.2 51.0 70.0 70
2CE04510746 2CE04511046 2CE04511546 2CE04512046
2CE04511058 10.6 10.2 14.9 15 2CE04511558 15.9 15.3 21.3 25 2CE04512058 21.2 20.4 27.7 30
2
2
NONE 0.0 0.0 24.3 35
2
2
NONE 0.0 0.0 12.4 15
2
2
2
2
NONE 0.0 0.0 10.1 15
NONE 0.0 0.0 38.5 60
NONE 0.0 0.0 38.5 60
NONE 0.0 0.0 25.7 40
2
2
NONE 0.0 0.0 25.7 40
2
2
NONE 0.0 0.0 13.1 20
2
2
2
2
NONE 0.0 0.0 10.8 15
Heater
Amps
kW
4.0 11.1 24.3 35
5.6 15.5 24.9 35
7.5 18.0 28.1 35
10.6 25.5 37.4 40
6.8 8.2 13.0 15
10.1 12.1 17.9 20
13.6 16.4 23.2 25
19.5 23.5 32.1 35
4.0 11.1 25.7 40
5.6 15.5 25.7 40
5.3 12.7 25.7 40
7.5 18.0 28.8 40
6.8 8.2 13.1 20
10.1 12.1 17.9 20
13.6 16.4 23.2 25
19.5 23.5 32.1 35
Minimum
Circuit
Ampacity
Amps
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
1
BRKR
Size
Amps
22 Unitary Products Group
Page 23
036-21502-002-A-0303
TABL E 17: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
6
Voltage
208-1-60
230-1-60 28.9
208-3-60 16.0
230-3-60 16.0 125 1.3
460-3-60 8.0
575-3-60 6.4 50 0.8 3.3 0.0
208-3-60 146
230-3-60 18.9 146
460-3-60 9.5 73
575-3-60 7.6 58.4 0.8
RLA
Each
28.9
18.9
Each
Compressors
OD Fan
LRA
Motor
165
165 1.3
125
66.5
ID Blower
Motor
FLA
1.3
1.3
0.8
1.3 6.8 0.0
1.3
0.8 3.6 0.0
FLA
6.6
6.6 0.0
6.6 0.0
6.6 0.0
3.3 0.0
6.8 0.0
3.6 0.0
Conv Outlet Amps
0.0
Electric Heater
Heater
Model No.
NONE 0.0 0.0 44.0 70 2CE04510506 4.0 19.2 44.0 70 2CE04510706 5.6 26.9 44.0 70 2CE04511006 8.0 38.5 56.3 70 2CE04511506 11.9 57.2 79.8 80 2CE04512006 15.9 76.4 103.8 110 2CE04513006 22.2 106.7 141.7 150
NONE 0.0 0.0 44.0 70 2CE04510506 5.3 22.1 44.0 70 2CE04510706 7.5 31.3 47.3 70 2CE04511006 10.6 44.2 63.5 70 2CE04511506 15.9 66.3 91.1 100 2CE04512006 21.2 88.3 118.7 125 2CE04513006 29.6 123.3 162.4 175
NONE 0.0 0.0 27.9 40 2CE04510525 2CE04510725
2CE04511025 8.0 22.2 36.0 40 2CE04511525 11.9 33.0 49.5 50 2CE04512025 15.9 44.1 63.4 70 2CE04513025 22.2 61.6 85.3 90
2CE04510525 2CE04510725 2CE04511025 10.6 25.5 40.1 45 2CE04511525 15.9 38.2 56.1 60 2CE04512025 21.2 51.0 72.0 80 2CE04513025 29.6 71.2 97.3 100
2CE04510746 2CE04511046 2CE04511546 2CE04512046 2CE04513046
2CE04511058 10.6 10.2 16.0 20 2CE04511558 15.9 15.3 22.4 25 2CE04512058 21.2 20.4 28.8 30 2CE04513058 30.4 29.3 39.9 40
2CE04510525 2CE04510725 2CE04511025 8.0 22.2 36.3 50 2CE04511525 11.9 33.0 49.8 50 2CE04512025 15.9 44.1 63.7 70 2CE04513025 22.2 61.6 85.5 90
2CE04510525 2CE04510725 2CE04511025 10.6 25.5 40.4 50 2CE04511525 15.9 38.2 56.3 60 2CE04512025 21.2 51.0 72.2 80 2CE04513025 29.6 71.2 97.5 100
2CE04510746 2CE04511046 2CE04511546 2CE04512046 2CE04513046
2CE04511058 10.6 10.2 16.3 20 2CE04511558 15.9 15.3 22.7 25 2CE04512058 21.2 20.4 29.1 30 2CE04513058 30.4 29.3 40.2 40
2
2
NONE 0.0 0.0 27.9 40
2
2
NONE 0.0 0.0 14.1 20
2
2
2
2
2
NONE 0.0 0.0 11.3 15
NONE 0.0 0.0 31.7 50
2
2
NONE 0.0 0.0 31.7 50
2
2
NONE 0.0 0.0 16.3 25
2
2
2
2
2
NONE 0.0 0.0 13.0 15
Heater
Amps
kW
4.0 11.1 27.9 40
5.6 15.5 27.9 40
5.3 12.7 27.9 40
7.5 18.0 30.8 40
6.8 8.2 14.3 20
10.1 12.1 19.3 20
13.6 16.4 24.6 25
19.5 23.5 33.4 35
28.8 34.6 47.4 50
4.0 11.1 31.7 50
5.6 15.5 31.7 50
5.3 12.7 31.7 50
7.5 18.0 31.7 50
6.8 8.2 16.3 25
10.1 12.1 19.7 25
13.6 16.4 24.9 25
19.5 23.5 33.8 35
28.8 34.6 47.8 50
Minimum
Circuit
Ampacity
Amps
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
1
BRKR
Size
Amps
Unita ry P rod ucts Gro up 23
Page 24
036-21502-002-A-0303
TABLE 18: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
RLA
Each
208-1-60 18.0 105
230-1-60 18.0 105 1.3 7.6 0.0
208-3-60 11.4 90
230-3-60 11.4 90 1.3 5.2 0.0
460-3-60 6.2 45
575-3-60 5.0 36 0.8 2 0.0
Compressors
208-1-60
230-1-60 24.4 140 1.3 7.6 0.0
208-3-60
230-3-60 14.1 105 1.3 5.2 0.0
460-3-60 7.1
575-3-60 5.8 44 0.8 2 0.0
24.4 140
14.1 105
OD Fan
LRA
Each
55
ID Blower
Motor
FLA
1.3 7.6 0.0
1.3 5.2 0.0
0.8 2.6 0.0
1.3
1.3
0.8
Motor
FLA
7.6 0.0
5.2 0.0
2.6 0.0
Conv Outlet Amps
Electric Heater
Model No.
NONE 0.0 0.0 31.4 45 2CE04510506 4.0 19.2 33.5 45 2CE04510706 5.6 26.9 43.2 45 2CE04511006 8.0 38.5 57.6 60 2CE04511506 11.9 57.2 81.0 90 2CE04512006 15.9 76.4 105.1 110
NONE 0.0 0.0 31.4 45 2CE04510506 5.3 22.1 37.1 45 2CE04510706 7.5 31.3 48.6 50 2CE04511006 10.6 44.2 64.7 70 2CE04511506 15.9 66.3 92.3 100 2CE04512006 21.2 88.3 119.9 125
NONE 0.0 0.0 20.8 30
2CE04510525 2CE04510725
2CE04511025 8.0 22.2 34.3 35 2CE04511525 11.9 33.0 47.8 50 2CE04512025 15.9 44.1 61.7 70
NONE 0.0 0.0 20.8 30
2CE04510525 2CE04510725
2CE04511025 10.6 25.5 38.4 40 2CE04511525 15.9 38.2 54.3 60 2CE04512025 21.2 51.0 70.2 80
NONE 0.0 0.0 11.1 15
2CE04510746 2CE04511046 2CE04511546 2CE04512046
NONE 0.0 0.0 8.5 15 2CE04511058 10.6 10.2 14.7 15 2CE04511558 15.9 15.3 21.1 25 2CE04512058 21.2 20.4 27.5 30
NONE 0.0 0.0 39.4 60 2CE04510506 4.0 19.2 39.4 60 2CE04510706 5.6 26.9 43.2 60 2CE04511006 8.0 38.5 57.6 60 2CE04511506 11.9 57.2 81.0 90 2CE04512006 15.9 76.4 105.1 110
NONE 0.0 0.0 39.4 60 2CE04510506 5.3 22.1 39.4 60 2CE04510706 7.5 31.3 48.6 60 2CE04511006 10.6 44.2 64.7 70 2CE04511506 15.9 66.3 92.3 100 2CE04512006 21.2 88.3 119.9 125
NONE 0.0 0.0 24.1 35
2CE04510525 2CE04510725
2CE04511025 8.0 22.2 34.3 35 2CE04511525 11.9 33.0 47.8 50 2CE04512025 15.9 44.1 61.7 70
NONE 0.0 0.0 24.1 35
2CE04510525 2CE04510725
2CE04511025 10.6 25.5 38.4 40 2CE04511525 15.9 38.2 54.3 60 2CE04512025 21.2 51.0 70.2 80
NONE 0.0 0.0 12.3 15
2CE04510746 2CE04511046 2CE04511546 2CE04512046
NONE 0.0 0.0 9.5 15 2CE04511058 10.6 10.2 14.7 15 2CE04511558 15.9 15.3 21.1 25 2CE04512058 21.2 20.4 27.5 30
Heater
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Heater
kW
Amps
4.0 11.1 20.8 30
5.6 15.5 25.9 30
5.3 12.7 22.4 30
7.5 18.0 29.1 30
6.8 8.2 13.5 15
10.1 12.1 18.4 20
13.6 16.4 23.7 25
19.5 23.5 32.6 35
4.0 11.1 24.1 35
5.6 15.5 25.9 35
5.3 12.7 24.1 35
7.5 18.0 29.1 35
6.8 8.2 13.5 15
10.1 12.1 18.4 20
13.6 16.4 23.7 25
19.5 23.5 32.6 35
Minimum
Circuit
Ampacity
Amps
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
1
BRKR
Size
Amps
24 Unitary Products Group
Page 25
036-21502-002-A-0303
TABLE 19: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITHOUT POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
6
Voltage
230-1-60 28.9 165 1.3 7.6 0.0
208-3-60 16.0 1.3
230-3-60 16.0 125 1.3 5.2 0.0
460-3-60
575-3-60 6.4 50 0.8 2 0.0
208-3-60
230-3-60
460-3-60
575-3-60 7.6 58.4
RLA
Each
Each
8.0 66.5
18.9 146
18.9
9.5 73
Compressors
OD Fan
LRA
165
125
146 1.3 5.0 0.0
ID Blower
Motor
FLA
1.3 7.6208-1-60 28.9
0.8 2.6
1.3 5.0 0.0
0.8 2.5 0.0
0.8 2 0.0
Motor
FLA
5.2
Conv Outlet Amps
0.0
0.0
0.0
Electric Heater
Heater
Model No.
NONE 0.0 0.0 45.0 70 2CE04510506 4.0 19.2 45.0 70 2CE04510706 5.6 26.9 45.0 70 2CE04511006 8.0 38.5 57.6 70 2CE04511506 11.9 57.2 81.0 90 2CE04512006 15.9 76.4 105.1 110 2CE04513006 22.2 106.7 142.9 150
NONE 0.0 0.0 45.0 70 2CE04510506 5.3 22.1 45.0 70 2CE04510706 7.5 31.3 48.6 70 2CE04511006 10.6 44.2 64.7 70 2CE04511506 15.9 66.3 92.3 100 2CE04512006 21.2 88.3 119.9 125 2CE04513006 29.6 123.3 163.7 175
NONE 0.0 0.0 26.5 40 2CE04510525 2CE04510725
2CE04511025 8.0 22.2 34.3 40 2CE04511525 11.9 33.0 47.8 50 2CE04512025 15.9 44.1 61.7 70 2CE04513025 22.2 61.6 83.5 90
2CE04510525 2CE04510725 2CE04511025 10.6 25.5 38.4 40 2CE04511525 15.9 38.2 54.3 60 2CE04512025 21.2 51.0 70.2 80 2CE04513025 29.6 71.2 95.5 100
2CE04510746 2CE04511046 2CE04511546 2CE04512046 2CE04513046
2CE04511058 10.6 10.2 14.7 15 2CE04511558 15.9 15.3 21.1 25 2CE04512058 21.2 20.4 27.5 30 2CE04513058 30.4 29.3 38.6 40
2CE04510525 2CE04510725 2CE04511025 8.0 22.2 34.0 45 2CE04511525 11.9 33.0 47.5 50 2CE04512025 15.9 44.1 61.4 70 2CE04513025 22.2 61.6 83.3 90
2CE04510525 2CE04510725 2CE04511025 10.6 25.5 38.1 45 2CE04511525 15.9 38.2 54.1 60 2CE04512025 21.2 51.0 70.0 70 2CE04513025 29.6 71.2 95.3 100
2CE04510746 2CE04511046 2CE04511546 2CE04512046 2CE04513046
2CE04511058 10.6 10.2 14.7 15 2CE04511558 15.9 15.3 21.1 25 2CE04512058 21.2 20.4 27.5 30 2CE04513058 30.4 29.3 38.6 40
2
2
NONE 0.0 0.0 26.5 40
2
2
NONE 0.0 0.0 13.4 20
2
2
2
2
2
NONE 0.0 0.0 10.2 15
NONE 0.0 0.0 29.9 45
2
2
NONE 0.0 0.0 29.9 45
2
2
NONE 0.0 0.0 15.2 20
2
2
2
2
2
NONE 0.0 0.0 11.7 15
Heater
Amps
kW
4.0 11.1 26.5 40
5.6 15.5 26.5 40
5.3 12.7 26.5 40
7.5 18.0 29.1 40
6.8 8.2 13.5 20
10.1 12.1 18.4 20
13.6 16.4 23.7 25
19.5 23.5 32.6 35
28.8 34.6 46.6 50
4.0 11.1 29.9 45
5.6 15.5 29.9 45
5.3 12.7 29.9 45
7.5 18.0 29.9 45
6.8 8.2 15.2 20
10.1 12.1 18.3 20
13.6 16.4 23.6 25
19.5 23.5 32.4 35
28.8 34.6 46.4 50
Minimum
Circuit
Ampacity
Amps
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
1
BRKR
Size
Amps
Unita ry P rod ucts Gro up 25
Page 26
036-21502-002-A-0303
TABL E 20: ELECTRICAL DATA - DM036 & 048 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
RLA
Each
208-1-60 18.0
230-1-60 18.0 105 1.3 4.4 10.0
208-3-60
230-3-60 11.4 90 1.3 4.4 10.0
460-3-60 6.2 45
575-3-60 5.0 36 0.8
Compressors
208-1-60
230-1-60 24.4
230-3-60 14.1
460-3-60 7.1
575-3-60 5.8 44 0.8 2.2 4.0
24.4
OD Fan
LRA
Each
9011.4 4.4
140 5.0 10.01.3
140 1.3
105 1.3
55
ID Blower
Motor
FLA
1.3105
1.3
0.8 2.2
1.3 5.0 10.0208-3-60 14.1 105
0.8 2.2
Motor
FLA
4.4 10.0
2.2 4.0
5.0
5.0
Conv Outlet Amps
10.0
5.0
10.0
10.0
5.0
Electric Heater
Model No.
NONE 0.0 0.0 38.2 50 2CE04510506 4.0 19.2 42.0 50 2CE04510706 5.6 26.9 51.7 60 2CE04511006 8.0 38.5 66.1 70 2CE04511506 11.9 57.2 89.5 90 2CE04512006 15.9 76.4 113.6 125
NONE 0.0 0.0 38.2 50 2CE04510506 5.3 22.1 45.6 50 2CE04510706 7.5 31.3 57.1 60 2CE04511006 10.6 44.2 73.2 80 2CE04511506 15.9 66.3 100.8 110 2CE04512006 21.2 88.3 128.4 150
NONE 0.0 0.0 29.9 40
2CE04510525 2CE04510725
2CE04511025 8.0 22.2 45.8 50 2CE04511525 11.9 33.0 59.3 60 2CE04512025 15.9 44.1 73.2 80
NONE 0.0 0.0 29.9 40
2CE04510525 2CE04510725
2CE04511025 10.6 25.5 49.9 50 2CE04511525 15.9 38.2 65.8 70 2CE04512025 21.2 51.0 81.7 90
NONE 0.0 0.0 15.8 20
2CE04510746 2CE04511046 2CE04511546 2CE04512046
NONE 0.0 0.0 12.7 15 2CE04511058 10.6 10.2 19.9 20 2CE04511558 15.9 15.3 26.3 30 2CE04512058 21.2 20.4 32.7 35
NONE 0.0 0.0 46.8 70 2CE04510506 4.0 19.2 46.8 70 2CE04510706 5.6 26.9 52.4 70 2CE04511006 8.0 38.5 66.8 70 2CE04511506 11.9 57.2 90.3 100 2CE04512006 15.9 76.4 114.3 125
NONE 0.0 0.0 46.8 70 2CE04510506 5.3 22.1 46.8 70 2CE04510706 7.5 31.3 57.8 70 2CE04511006 10.6 44.2 74.0 80 2CE04511506 15.9 66.3 101.6 110 2CE04512006 21.2 88.3 129.2 150
NONE 0.0 0.0 33.9 45
2CE04510525 2CE04510725
2CE04511025 8.0 22.2 46.5 50 2CE04511525 11.9 33.0 60.0 70 2CE04512025 15.9 44.1 73.9 80
NONE 0.0 0.0 33.9 45
2CE04510525 2CE04510725
2CE04511025 10.6 25.5 50.6 60 2CE04511525 15.9 38.2 66.6 70 2CE04512025 21.2 51.0 82.5 90
NONE 0.0 0.0 16.9 20
2CE04510746 2CE04511046 2CE04511546 2CE04512046
NONE 0.0 0.0 13.7 15 2CE04511058 10.6 10.2 19.9 20 2CE04511558 15.9 15.3 26.3 30 2CE04512058 21.2 20.4 32.7 35
Heater
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Heater
kW
Amps
4.0 11.1 31.9 40
5.6 15.5 37.4 40
5.3 12.7 33.9 40
7.5 18.0 40.6 45
6.8 8.2 19.2 20
10.1 12.1 24.2 25
13.6 16.4 29.4 30
19.5 23.5 38.3 40
4.0 11.1 33.9 45
5.6 15.5 38.2 45
5.3 12.7 34.7 45
7.5 18.0 41.3 45
6.8 8.2 19.2 20
10.1 12.1 24.2 25
13.6 16.4 29.4 30
19.5 23.5 38.3 40
Minimum
Circuit
Ampacity
Amps
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
1
BRKR
Size
Amps
26 Unitary Products Group
Page 27
036-21502-002-A-0303
TABL E 21: ELECTRICAL DATA - DM060 & 072 DIRECT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
6
Voltage
230-1-60
230-3-60 16.0 125 1.3
460-3-60
575-3-60
208-3-60
230-3-60 18.9 146 1.3
460-3-60 0.8 3.6
575-3-60 7.6
RLA
Each
Each
28.9 165 1.3
6.4 50
18.9
9.5
Compressors
LRA
66.58.0
146
73
OD Fan
ID Blower
Motor
FLA
1.316528.9208-1-60
1.3125
0.8 3.3 5.0
0.8 3.3
1.3
0.8
Motor
FLA
6.6 10.0
6.6 10.0208-3-60 16.0
6.6 10.0
6.8
6.8 10.0
3.6
Conv Outlet Amps
10.06.6
4.0
10.0
5.0
4.058.4
Electric Heater
Model No.
NONE 0.0 0.0 54.0 80 2CE04510506 4.0 19.2 54.0 80 2CE04510706 5.6 26.9 54.4 80 2CE04511006 8.0 38.5 68.8 80 2CE04511506 11.9 57.2 92.3 100 2CE04512006 15.9 76.4 116.3 125 2CE04513006 22.2 106.7 154.2 175
NONE 0.0 0.0 54.0 80 2CE04510506 5.3 22.1 54.0 80 2CE04510706 7.5 31.3 59.8 80 2CE04511006 10.6 44.2 76.0 80 2CE04511506 15.9 66.3 103.6 110 2CE04512006 21.2 88.3 131.2 150 2CE04513006 29.6 123.3 174.9 175
NONE 0.0 0.0 37.9 50 2CE04510525 2CE04510725
2CE04511025 8.0 22.2 48.5 50 2CE04511525 11.9 33.0 62.0 70 2CE04512025 15.9 44.1 75.9 80 2CE04513025 22.2 61.6 97.8 100
NONE 0.0 0.0 37.9 50 2CE04510525 2CE04510725
2CE04511025 10.6 25.5 52.6 60 2CE04511525 15.9 38.2 68.6 70 2CE04512025 21.2 51.0 84.5 90 2CE04513025 29.6 71.2 109.8 110
NONE 0.0 0.0 19.1 25 2CE04510746 2CE04511046 2CE04511546 2CE04512046 2CE04513046
NONE 0.0 0.0 15.3 20 2CE04511058 10.6 10.2 21.0 25 2CE04511558 15.9 15.3 27.4 30 2CE04512058 21.2 20.4 33.8 35 2CE04513058 30.4 29.3 44.9 45
NONE 0.0 0.0 41.7 60 2CE04510525 2CE04510725
2CE04511025 8.0 22.2 48.8 60 2CE04511525 11.9 33.0 62.3 70 2CE04512025 15.9 44.1 76.2 80 2CE04513025 22.2 61.6 98.0 100
NONE 0.0 0.0 41.7 60 2CE04510525 2CE04510725
2CE04511025 10.6 25.5 52.9 60 2CE04511525 15.9 38.2 68.8 70 2CE04512025 21.2 51.0 84.7 90 2CE04513025 29.6 71.2 110.0 125
NONE 0.0 0.0 21.3 30 2CE04510746 2CE04511046 2CE04511546 2CE04512046 2CE04513046
NONE 0.0 0.0 17.0 20 2CE04511058 10.6 10.2 21.3 25 2CE04511558 15.9 15.3 27.7 30 2CE04512058 21.2 20.4 34.1 35 2CE04513058 30.4 29.3 45.2 45
Heater
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Heater
kW
Amps
4.0 11.1 37.9 50
5.6 15.5 40.2 50
5.3 12.7 37.9 50
7.5 18.0 43.3 50
6.8 8.2 20.6 25
10.1 12.1 25.6 30
13.6 16.4 30.8 35
19.5 23.5 39.7 40
28.8 34.6 53.7 60
4.0 11.1 41.7 60
5.6 15.5 41.7 60
5.3 12.7 41.7 60
7.5 18.0 43.6 60
6.8 8.2 21.3 30
10.1 12.1 25.9 30
13.6 16.4 31.2 35
19.5 23.5 40.1 45
28.8 34.6 54.1 60
Minimum
Circuit
Ampacity
Amps
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
1
BRKR
Size
Amps
Unita ry P rod ucts Gro up 27
Page 28
036-21502-002-A-0303
TABLE 22: ELECTRICAL DATA - DM036 & 048 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
3
4
Voltage
RLA
Each
208-1-60 18.0 105
230-1-60 18.0 105 1.3 7.6 10.0
208-3-60 11.4 90
230-3-60 11.4 90 1.3 5.2 10.0
460-3-60 6.2 45
575-3-60 5.0 36 0.8 2 4.0
Compressors
208-1-60
230-1-60 24.4 140 1.3 7.6 10.0
208-3-60
230-3-60 14.1 105 1.3 5.2 10.0
460-3-60 7.1 0.8
575-3-60 5.8 44 0.8 2 4.0
24.4 140
14.1 105
LRA
Each
55
OD Fan
ID Blower
Motor
FLA
1.3 7.6 10.0
1.3 5.2 10.0
0.8 2.6 5.0
1.3
1.3
Motor
FLA
7.6 10.0
5.2 10.0
2.6 5.0
Conv Outlet Amps
Electric Heater
Model No.
NONE 0.0 0.0 41.4 50 2CE04510506 4.0 19.2 46.0 50 2CE04510706 5.6 26.9 55.7 60 2CE04511006 8.0 38.5 70.1 80 2CE04511506 11.9 57.2 93.5 100 2CE04512006 15.9 76.4 117.6 125
NONE 0.0 0.0 41.4 50 2CE04510506 5.3 22.1 49.6 50 2CE04510706 7.5 31.3 61.1 70 2CE04511006 10.6 44.2 77.2 80 2CE04511506 15.9 66.3 104.8 110 2CE04512006 21.2 88.3 132.4 150
NONE 0.0 0.0 30.8 40
2CE04510525 2CE04510725
2CE04511025 8.0 22.2 46.8 50 2CE04511525 11.9 33.0 60.3 70 2CE04512025 15.9 44.1 74.2 80
NONE 0.0 0.0 30.8 40
2CE04510525 2CE04510725
2CE04511025 10.6 25.5 50.9 60 2CE04511525 15.9 38.2 66.8 70 2CE04512025 21.2 51.0 82.7 90
NONE 0.0 0.0 16.1 20
2CE04510746 2CE04511046 2CE04511546 2CE04512046
NONE 0.0 0.0 12.5 15 2CE04511058 10.6 10.2 19.7 20 2CE04511558 15.9 15.3 26.1 30 2CE04512058 21.2 20.4 32.5 35
NONE 0.0 0.0 49.4 70 2CE04510506 4.0 19.2 49.4 70 2CE04510706 5.6 26.9 55.7 70 2CE04511006 8.0 38.5 70.1 80 2CE04511506 11.9 57.2 93.5 100 2CE04512006 15.9 76.4 117.6 125
NONE 0.0 0.0 49.4 70 2CE04510506 5.3 22.1 49.6 70 2CE04510706 7.5 31.3 61.1 70 2CE04511006 10.6 44.2 77.2 80 2CE04511506 15.9 66.3 104.8 110 2CE04512006 21.2 88.3 132.4 150
NONE 0.0 0.0 34.1 45
2CE04510525 2CE04510725
2CE04511025 8.0 22.2 46.8 50 2CE04511525 11.9 33.0 60.3 70 2CE04512025 15.9 44.1 74.2 80
NONE 0.0 0.0 34.1 45
2CE04510525 2CE04510725
2CE04511025 10.6 25.5 50.9 60 2CE04511525 15.9 38.2 66.8 70 2CE04512025 21.2 51.0 82.7 90
NONE 0.0 0.0 17.3 20
2CE04510746 2CE04511046 2CE04511546 2CE04512046
NONE 0.0 0.0 13.5 15 2CE04511058 10.6 10.2 19.7 20 2CE04511558 15.9 15.3 26.1 30 2CE04512058 21.2 20.4 32.5 35
Heater
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Heater
Amps
kW
4.0 11.1 32.9 40
5.6 15.5 38.4 40
5.3 12.7 34.9 40
7.5 18.0 41.6 45
6.8 8.2 19.7 20
10.1 12.1 24.7 25
13.6 16.4 29.9 30
19.5 23.5 38.8 40
4.0 11.1 34.1 45
5.6 15.5 38.4 45
5.3 12.7 34.9 45
7.5 18.0 41.6 45
6.8 8.2 19.7 20
10.1 12.1 24.7 25
13.6 16.4 29.9 30
19.5 23.5 38.8 40
Minimum
Circuit
Ampacity
Amps
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
1
BRKR
Size
Amps
28 Unitary Products Group
Page 29
036-21502-002-A-0303
TABLE 23: ELECTRICAL DATA - DM060 & 072 BELT DRIVE WITH POWR’D CONVENIENCE OUTLET
Model
Tonnage
5
6
Voltage
230-1-60 28.9 165 1.3 7.6 10.0
208-3-60 16.0 1.3
230-3-60 16.0 125 1.3 5.2 10.0
460-3-60
575-3-60 6.4 50 0.8
208-3-60
230-3-60 18.9 146 1.3 5.0 10.0
460-3-60
575-3-60 7.6 58.4 0.8 2 4.0
RLA
Each
Each
28.9
8.0 66.5
18.9 146
9.5 73
Compressors
LRA
165
125
OD Fan
ID Blower
Motor
FLA
1.3 7.6208-1-60
0.8 2.6
1.3 5.0 10.0
0.8 2.5 5.0
Motor
FLA
5.2
2 4.0
Conv Outlet Amps
10.0
10.0
5.0
Electric Heater
Model No.
NONE 0.0 0.0 55.0 80 2CE04510506 4.0 19.2 55.0 80 2CE04510706 5.6 26.9 55.7 80 2CE04511006 8.0 38.5 70.1 80 2CE04511506 11.9 57.2 93.5 100 2CE04512006 15.9 76.4 117.6 125 2CE04513006 22.2 106.7 155.4 175
NONE 0.0 0.0 55.0 80 2CE04510506 5.3 22.1 55.0 80 2CE04510706 7.5 31.3 61.1 80 2CE04511006 10.6 44.2 77.2 80 2CE04511506 15.9 66.3 104.8 110 2CE04512006 21.2 88.3 132.4 150 2CE04513006 29.6 123.3 176.2 200
NONE 0.0 0.0 36.5 50 2CE04510525 2CE04510725
2CE04511025 8.0 22.2 46.8 50 2CE04511525 11.9 33.0 60.3 70 2CE04512025 15.9 44.1 74.2 80 2CE04513025 22.2 61.6 96.0 100
NONE 0.0 0.0 36.5 50 2CE04510525 2CE04510725
2CE04511025 10.6 25.5 50.9 60 2CE04511525 15.9 38.2 66.8 70 2CE04512025 21.2 51.0 82.7 90 2CE04513025 29.6 71.2 108.0 110
NONE 0.0 0.0 18.4 25 2CE04510746 2CE04511046 2CE04511546 2CE04512046 2CE04513046
NONE 0.0 0.0 14.2 20 2CE04511058 10.6 10.2 19.7 20 2CE04511558 15.9 15.3 26.1 30 2CE04512058 21.2 20.4 32.5 35 2CE04513058 30.4 29.3 43.6 45
NONE 0.0 0.0 39.9 50 2CE04510525 2CE04510725
2CE04511025 8.0 22.2 46.5 50 2CE04511525 11.9 33.0 60.0 70 2CE04512025 15.9 44.1 73.9 80 2CE04513025 22.2 61.6 95.8 100
NONE 0.0 0.0 39.9 50 2CE04510525 2CE04510725
2CE04511025 10.6 25.5 50.6 60 2CE04511525 15.9 38.2 66.6 70 2CE04512025 21.2 51.0 82.5 90 2CE04513025 29.6 71.2 107.8 110
NONE 0.0 0.0 20.2 25 2CE04510746 2CE04511046 2CE04511546 2CE04512046 2CE04513046
NONE 0.0 0.0 15.7 20 2CE04511058 10.6 10.2 19.7 20 2CE04511558 15.9 15.3 26.1 30 2CE04512058 21.2 20.4 32.5 35 2CE04513058 30.4 29.3 43.6 45
Heater
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
Heater
kW
Amps
4.0 11.1 36.5 50
5.6 15.5 38.4 50
5.3 12.7 36.5 50
7.5 18.0 41.6 50
6.8 8.2 19.7 25
10.1 12.1 24.7 25
13.6 16.4 29.9 30
19.5 23.5 38.8 40
28.8 34.6 52.8 60
4.0 11.1 39.9 50
5.6 15.5 39.9 50
5.3 12.7 39.9 50
7.5 18.0 41.3 50
6.8 8.2 20.2 25
10.1 12.1 24.6 25
13.6 16.4 29.8 30
19.5 23.5 38.7 40
28.8 34.6 52.7 60
Minimum
Circuit
Ampacity
Amps
1. HACR Type per NEC.
2. These electric heaters DO NOT include a fuse box. If a fuse box is required to meet a local code (i.e. Chicago), the fuse block accessories 2FB04700825 and 2FB04700846 are available for field installation.
Max Fuse /
1
BRKR
Size
Amps
Unita ry P rod ucts Gro up 29
Page 30
TABL E 24: PHYSICAL DATA
EVAPORATOR
BLOWER
EVAPORATOR
COIL
CONDENSER
FANS
CONDENSER
COILS
COMPRESSOR
(Qty. Per Unit)
AIR
FILTERS
CHARGE
036-21502-002-A-0303
MODELS
Centrifugal Blower (Di a. x Wd. in.) 12 X 10 12 X 10 12 X 10 12 X 11
Fan Motor HP (Direct Drive) 1/2 3/4 1 1
Fan Motor HP (Belt Driv e) 1 1/2 1 1/2 1 1/2 1 1/2
Rows Deep 3 3 3 4
Fins Per Inch 13 13 13 13
Face Area (Sq. Ft.) 3.6 4.3 5.1 5.1
Propeller Dia. (in.) 24 24 24 24
Fan Motor Hp 1/4 1/4 1/4 1/4
Nom. CFM 3400 3400 3400 3400
Rows Deep 1 1 1 2
Fins Per Inch 16 16 22 16
Face Area (Sq. Ft.) 17.1 17.1 17.1 16.7
Scroll Type 1111
Quantity Pe r Unit (15” X 20” X 1” or 2“) 2 2 2 2 Quantity Pe r Unit (14” X 25” X 1” or 2“) 1 1 1 1
Total Face Area (sq. ft.) 6.3 6.3 6.3 6.3
Refrigerant 22
(lbs./oz.)
036 048 060 072
5/8 6/8 6/8 10/0
DM
T ABLE 25: ELECTRIC HEAT CORRECTION FACTORS
NOMINAL VOLTAGE VOLTAGE
208 240 480 600
208 1.00 230 0.92 460 0.92 575 0.92
kW CAP. MULTI-
PLIER
TA B LE 26: VOLTAGE LI MITATIONS
POWER SUPPLY
208/230-3-60
460-3-60 575-3-60
1. Utilization R ange “A” in accordance with ARI Standard
110.
MIN. MAX.
187 253 414 506
518 506
1
VOLTAGE
30 Unitary Products Group
Page 31
036-21502-002-A-0303
THERMOSTAT
1
TERMINALS
UNIT TERMINAL
STRIP TB1
24 VOLT
TRANSFORMER
ADD
JUMPER
ADD
JUMPER
1
ELECTRONIC PROGRAMMABLE THEROMSTAT 2TH04700224 (INCLUDES SUBBASE).
2
SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.
3
SECOND STAGE HEATING IS ONLY R EQUIRED ON UNITS WITH A TWO STAGE ELECTRIC HEATER.
TO REMOTE SENSOR
2TH040702224 IF USED
RC
RH
Y1
Y2 W1
W2
G
B LED 1
LED 2
COM
A1
A2
T
T
R
Y1 Y2
W1
W2
G C
X
OCC
4
3
2
4
NOT USED
COOLING / HEATING (ELECTRONIC THEROMSTAT)
MULTI STAGE
REFER TO THE ELECTRICAL DATA TABLES TO SIZE THE DISCONNECT SWITCH, OVERCURRENT PROTEC­TION AND WIRING.
COOLING ONLY (24 VOLT THERMOSTAT)
1
THERMOSTAT
TERMINALS
RV
YC
GF
1
24 VOLT THERMOSTAT 2TH07701024. TO CONTROL THE ECONOMIZER
ON SECOND STAGE COOLING, USE THE T HERMOSTAT 2TH0401224.
UNIT TERMINAL
STRIP TB1
R
Y1
Y2
G
C
24 VOLT
TRANSFORMER
TYPICAL POWER WIRING
TYPICAL CONTROL WIRING
COOLING / HEATING (24 VOLT THERMOSTAT)
THERMOSTAT
TERMINALS
ADD
JUMPER
RH
RC
Y
W
G
1
UNIT TERMINAL
STRIP TB1
R
Y1
Y2
W1
W2
G
C
24 VOLT
TRANSFORMER
FIGURE 2: TYPICAL FIELD POWER & CONTROL WIRING
Unita ry P rod ucts Gro up 31
1
24 VOLT THEROMSTAT 2ET07701024. TO CONTROL THE ECONOMIZER ON THE SECOND STAGE COOLING OR TO HAVE AN EL ECTRIC HEAT ACCESSORY W ITH TWO STAGES OF HEAT, USE THERMOSTAT 2TH0471024.
COOLING / HEATING (ELECTRONIC THEROMSTAT)
SINGLE STAGE
RH
RC
1
UNIT TERMINAL
STRIP TB1
Y
W
G
Y1
W1
R
G
C
24 VOLT
TRANSFORMER
THERMOSTAT
TERMINALS
ADD
JUMPER
1
ELECTRONIC PROGRAMMABLE THEROMSTAT 2ET07701024 (INCLUDES SUBBASE). TO CONTROL THE ECONOMIZER ON SECOND STAGE COOLING, US E THERMOSTAT 2TH04700224.
Page 32
036-21502-002-A-0303
FIGURE 3: UNIT DIMENSIONS (3 - 6 TON COOLING ONLY/ELECTRIC HEAT ) FRONT VIEW
FIGURE 4: UNIT DIMENSIONS (3 - 6 TON COOLING/GAS HEAT) FRONT VIEW
32 Unitary Products Group
Page 33
036-21502-002-A-0303
FIGURE 5: UNIT WITH ECONOMIZER RAINHOOD
DETAIL “A”
DETAIL “B”
FIGURE 6: UNIT WITH FIXED OUTDOOR AIR/MOTORIZED DAMPER RAINHOOD
Unita ry P rod ucts Gro up 33
Page 34
FIGURE 7: UNIT DIMENSIONS (REAR VIEW)
FILTER ACCESS
BLOWER MOTOR ACCESS
FIELD-SUPPLIED DISCONNECT SWITCH LOCATION
MOUNTING BRACKET FOR DICONNECT SWITCH (Shipped attached to the
blower housing inside the blower compartment)
DISCONNECT SWITCH LOCATION AND MOTOR ACCESS PANEL FOR UNIT WITH “BELT-DRIVE” OPTION
A,B WIRING ENTRY (See Detail “B”)
CONTROL BOX ACCESS
FIGURE 8: DISCONNECT/BLOWER ACCESS
LOCATION
036-21502-002-A-0303
TABL E 28: MINIMUM CLEARANCES
LOCATION
Front
Back
Left Side (Filter Access)
Right Side (Cond. Coil)
Below Unit Above Unit
1
2
1. Units may be installed on combustible floors made from wood or class A, B, or C roof covering material.
2. Units must be installed outdoors. Overhanging struc­ture s or sh r ub s should not ob struct condenser air di s­charge outlet.
CLEARANCE
24” (Cooling/Electric Heat)
32” (Gas Heat)
12” (Less Economizer)
36” (With Ec onomizer or Fixed
Air/Motorized Damper) 24” (Less Economizer)
36” (With Economizer)
72” (For
Conden ser Air Discharge)
24”
0”
TABL E 27: UTILITIES ENTRY
HOLE OPENING SIZE (DIA.) USED FOR
A
B C
D
1
7/8” KO
2” KO
1
Control Wiring
Power Wiring
1-5/8” KO Gas Piping (Front) 1-1/2” KO
Gas Piping (Bottom)
1. Opening i n the bottom to the unit can be located by the side in the insulation.
2. Do not remove the 2” knockout ring.
34 Unitary Products Group
Side
2
Bottom
Side
Bottom
Page 35
036-21502-002-A-0303
FIGURE 9: TYPICAL APPLICATIONS
Unita ry P rod ucts Gro up 35
Page 36
036-21502-002-A-0303
447/
8
D
X
APPROXIMATE CENTER OF GRAVITY
A
FRONT OF UNIT
BACK OF UNIT
821/
4
C
447/
8
A
F
X
B
CONDENSER COIL
Y
END OF UNIT
APPROXIMATE CENTER OF GRAVITY
FRONT OF UNIT
E
BACK OF UNIT
B
D
821/
4
Y
FIGURE 10: FOUR AND SIX POINT LOADING TABL E 29: DM 4 POINT LOADS WEIGHT DISTRIBUTION
UNIT TOTALABCD DM036 Co oling/ Electric DM036N04 625 140 133 172 180
DM036N08 635 140 138 177 180 DM048 Co oling/ Electric 615 137 135 170 173 DM048N06 675 152 145 185 193 DM048N10 685 152 150 190 193 DM060 Co oling/ Electric 640 143 140 177 180 DM060N08 700 158 150 192 200 DM060N10 710 158 155 197 200 DM072 Co oling/ Electric 720 164 189 196 171 DM072N08 775 179 201 209 186 DM072N10 785 179 206 214 186
565 125 123 157 160
C
CONDENSER COIL END OF UNIT
TABL E 30: DM 6 POINT LOADS WEIGHT DISTRIBUTION
UNIT TOTALABCDEF DM036 Co oling/ Electric DM036N04
DM036N08 DM048 Co oling/ Electric DM048N06 DM048N10 DM060 Co oling/ Electric DM060N08 DM060N10 DM072 Co oling/ Electric DM072N08 DM072N10
565 84 83 82 104 105 107 625 93 92 91 115 117 118
635 94 93 92 117 119 120 615 91 90 89 113 115 116 675 100 99 98 124 126 128 685 102 100 99 126 128 129 640 95 94 93 118 119 121 700 104 103 101 129 131 132 710 105 104 103 131 133 134 720 107 117 129 134 122 111 775 115 126 139 144 131 120 785 117 128 141 146 133 121
TABL E 31: CENTER OF GRAVITY
DIMENSION 3 - 5 TON 6 TON
X 40-¾” 44” Y 19-¾” 22”
36 Unitary Products Group
Page 37
036-21502-002-A-0303
TABL E 32: OPERATING WEIGHTS (LBS.)
MODEL SIZE 3 TO N 4 TON 5 TO N 6 TO N
BASIC
UNIT
OPTIONS
ACCY.
DM
(Gas/Electric)
Electric Heater
Barometric Relief / Fixed Air Damper 10
DM (Cooli ng Only) 565 615 640 720
N04 625 - - ­N06 - 675 - ­N08 635 - 700 775 N10 - 685 710 785
Economizer 50
Motorized Damper 26
5 - 7 kW 18 10 - 15 kW 23 20 - 30 kW 28
Roof Curb 92
Belt-Dri ve Blower 5
FIGURE 11: ROOF CURB DIMENSIONS
Unita ry P rod ucts Gro up 37
Page 38
036-21502-002-A-0303
GUIDE SPECIFICATIONS
GENERAL
Units shall be ma nufactured by York Int ernational Unit ary Products Group in an ISO 9001 certified faci lity.
York's Sunline 2000 units. Although the units are prim arily designed for curb mounting on a roof, they can als o be slab-mounted at ground level or set on steel beams above a finished roof. Cooling only, cooling with gas heat and cooling with electric heat models are available with a wide variety of factory-mounted options and field-installed acces sories to make t hem suitable for almost every appli cation. All units are self-contained and assembled on full perimeter base rails with hol es in the four corners for overhead rigging. Every unit is completely piped, wired, charged and tested at the f actory to simplify the field installation and to provide years of dependable oper ation. All models (including those with an economizer) are suitable for either bottom or horizontal duct connections. Models with power exhaust are suitable for bottom duct connections only. For bottom duct, remove the sheet metal p anels from the supply and retur n air openings through the base of the unit. For horizontal duct, remove the supply and return ai r panels on the rear of the unit.
All non-Scroll compr essors i nclude cr ankcase he ate rs and all compressors have internal pressure relief. Every ref ri gerant circuit incl udes a liquid line fil ter-drier , a discharge line high pressure switch and a suction line with a freezestat and low pressure/loss of charge switch.The unit control circuit includes a 75 VA transformer, a 24-volt circuit breaker and a relay board w ith a compre ssor lockout circuit, a terminal strip for thermost at wiring, plus an additio nal set of pin connectors to simplify the i nterface of additional field controls. All units have long lasting powder paint cabinets with 750 hour salt spray test ap proval under ASTMB117 procedures. All models are CSA listed. All models include a 1-year limit ed warranty on the complete unit. Compressors and electric heater ele­ments carry a 5-y ear warranty . Aluminized st eel and S tainle ss steel tubular heat exchangers carry a 10- year warranty.
DESCRIPTION
Units shall be factory-asse mb led, single package d, Electric Cooling/Gas Heat, Elec tric Cooling/Optional El ectric Heat and designed for out door mounted installation.
The 3 thru 5 ton units shall have mi nimum SEER ratings of
10.0 and the 6 ton units shall have minimum EER rating s of
9.0. They shall have built -in field convert ible duct connect ions for down discharge supply/re turn or horizontal discharge sup­ply/return, and be available with factory installed options or field installed accessories. The units shall be factory wired, piped, charged with R-22 refrigerant and fac tor y tested prior to shipment. All uni t wi ri ng shall be both numbered and color coded. All units the cooling perfo rmance shall be rated in accordance with DOE and ARI test procedures. Unit s shall be CSA listed, classified to ANSI Z21.47, UL 1995/CSA No. 236 standards.
TM
units are convertible single package-
UNIT CABINET
Unit cabinet shall be constructed of G90 galvanized steel, with exterior surfaces coated with a non-chalking, powdered paint finish, certified at 750 hours salt spray test per ASTMB117 standards. Indoor blower section shall be insu­lated with a minimum 1/2 thick insulation, coated on the air­side. Aluminum foil f aced insulation shall be used in the furnace compart me nt and be fastened with ridged fasteners to prevent insulation from entering the ai r st ream. Cabinet panels shall be “large” siz e, easily removable for servicing and maintenance. Ful l perimeter base rails shal l be provided to assure reliable transit of equipment, overhead rigging and proper seali ng on roof curb applications. Di sposable 1" fil ters shall be furnished and be accessible through a removable access door, sealed airtight. Units f il ter track shall be designed to accommod ate ei ther 1 or 2 filters. Fan perfor­mance measuring ports shall be provided on the outside of the cabinet t o allo w accurat e air mea sur ement s of ev aporato r fan performance without removing panels or creat ing air by­pass of the coils. Condensate pan shall be internally sloped and conform to ASHRAE 62-89 self -dr aining standards. Con­densate connecti on shall be a minimum of 3/4 I.D. female and be a ridged mount connection.
INDOOR (EVAPORATOR) FAN ASSEMBLY
The indoor fan shall be direct drive, multi -speed, or a factor y installed belt drive assembly that includ es an adjustable pitch motor pulley. Job site selected (B.H.P.) brake hors epower shall not exceed the motor s nameplate horsepower rating, plus the service factor. Units shall be designed not to operat e above service factor. Fan wheel shall be double-inlet type with forward-curved blades, dynamically ba lanced to operate smoothly througho ut the entire range of operation. Airflow design shall be cons tant air vol ume. Beari ngs shall be sealed and permanently lubricated for longer life and no mainte­nance.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fan shal l be of the di rect-driven propeller type, discharge air vertically, have aluminum blades riveted to a corrosion resistant steel spider bracket and shall be dynam i­cally balanced for smooth operation. The outdoor fan motor shall be totally enclosed with permanently lubricated bear­ings, internal ly protected against overload conditions and staged independently.
REFRIGERANT COMPONENTS
Compressor:
a. Shall be internally protected with internal high-p res-
sure relief and over temperature protection.
b. Shall have internal spring isolation and sound muf-
fling to minimize vi bration and noise, and be exter­nally isolated on a dedi cated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have alumi-
num plate fins mechanicall y bonded to seamless
38 Unitary Products Group
Page 39
036-21502-002-A-0303
internally enhanced copper tubes wit h all joints brazed. Special Phenolic coating shall be avail able as a factor y option.
b. Evaporator and Conden ser coils shall be of the
direct expansion, draw-thru, design.
Refrigerant Cir cui t and Refrigerant Safety Components shall include:
a. Independent fixed-orifice expansion devices. b. Filter drier/strainer to eliminate any moisture or for-
eign matter.
c. Accessible service gage connect ions on both suc-
tion and liquid lines to charge, evacua te, and m ea­sure refrigerant pressure during any necessary servicing or tro ubleshooting without losing charge.
d. The refrigerat ion system shall provide at least 15°F
of sub-cooling at design conditions .
UNIT CONTROLS
a. Unit shall be complete with self-contained low-volt-
age control ci rcuit protected by a resetable circuit breaker on the 24-v olt transformer side.
b. Unit shall incorporate a lockout circ uit which pro-
vides reset capability at the space thermostat or base unit, should any of the following standard
safety devic es trip and shut off compr essor. c. Loss-of-charge/Low-pr essure switch. d. High-pressure switch. e. Freeze-protecti on thermostat, evaporator coil. f. I f any of the above safety devices trip, a LED (light-
emitting diode) indicator shall flash a diagnostic
code that indicates which safety switch has tripped. g. Unit shall incorporate AUTO RESET compressor
over temperatur e, over current prot ection. h. Unit shall operate with conventional thermostat
designs and have a low voltage terminal str ip for
easy hook-up. i. Unit control board shall have on-board diagnostics
and fault code display. j. Standard controls shall include anti-short cycl e and
low voltag e protection, and permit coolin g operation
down to 0°F. k. Control board shall monitor each refrigerant safety
switch independently. l. Control board sha ll retain last 5 faul t codes in non
volatile memo ry, which will not be lost i n the event of
a power loss.
dant main gas valve. Venter wheel shall be constructed of stainless steel for corrosion resistance. The heat exchanger shall be of the tubular type, constructed of T1-40 aluminized steel for corrosion resistance and allowing minimum mixed air entering temperature of 25°F. Burners shall be of the inshot type, constructed of aluminum coated steel and con­tain air mixtu re ad justment s. Al l gas pi ping s hall en ter th e unit cabinet at a single loc ation through either the si de or curb, without any field modifications. An integrated cont rol board shall provide timed control of evaporator fan functioni ng and burner ignition. Heating section shall be provided with the fol­lowing minimum protection:
a. Primary and auxiliary high-temperature limit
switches.
b. Induced draft motor speed sensor. c. Flame roll out switch (manual reset). d. Flame proving controls.
ELECTRIC HEATING SECTI ON
An electric heating section, with nickel chromium elements, shall be provided in a range of 5 thru 30 KW, offering t wo stages of capacity - 16 KW and above on 208/230 volt heat­ers and 20 KW and above on 460 and 575 volt heaters. The heating section shall have a primary limi t control(s) and aut o­matic reset to prevent the heating element system from oper­ating at an excessive temperature. The heating section assembly sha ll slide out of the unit for easy maintenance and service. Units with Electric Heati ng shall be wired for a single point power supply with br anch circuit fusing (where required).
UNIT OPERATING CHARACTERISTICS
a. Unit shall be capable of st arting and running at
125°F outdoor temper ature, exceeding maximum load criteria of ARI Standard 210/240. The compres­sor, with standard co ntrols, shall be capable of oper ­ation down to 0°F outdoor t emperat ure. Uni t sh all b e provided with fan time delay to prevent cold air delivery before hea t exchange r war ms up (Gas he at only).
ELECTRICAL REQUIREMENTS
All unit power wi rin g sha ll en ter unit cab inet a t a si ngle f actor y provided location and be capable of side or bot tom entry, to minimize roof penetrations and avoid unit field modificati ons. Separate side and bot tom openings shall be provided for the control wiring.
ST ANDARD LIMITED WARRANTIES
Compressor 5 Years
Heat Exchanger 10 Years
GAS HEAT ING SECTION
Shall be designed with induced draft combustion with post
Electric Heat Element 5 Years
Other Parts 1 Year
purge logic, energy saving direct sp ark ignition, and re dun-
Unita ry P rod ucts Gro up 39
Page 40
OPTIONAL OUTDOOR AIR (Shal l be m ade ava i labl e b y either/or):
ELECTRONIC ENTHALPY AUTOMATIC ECONO­MIZER- Outdoor and return air dampers that are inter-
locked and posit ioned by a fully-modulating, spring return damper act uator. The maximum leakage rate for the outdoor ai r i ntake dampers shall not exceed 2% when dampers are fully closed and operating against a pressure differential of 0.5 IWG. A unit-mounted potenti­ometer shall be prov ide d to adj ust t he out door and ret urn air damper assembly to take in CFM of outdoor air to meet the minimum ventilation requirement of the condi­tioned space during normal operation. During econo­mizer operat ion, a mixed-air t emperature control shall modulate the outdoor and return ai r damper assembly to prevent the supply air temperature fr om droppi ng below 55°F. Changeover from compressor to economizer oper­ation shal l be provided by an integral electronic ent halpy control that feeds input into the basic module. The out­door intake opening shall be covered with a rain hood that matches the ext erior of the unit. Water eliminator/fil­ters shall be provi ded. Simultane ous economizer/com­pressor operat ion is also possible. Dampers shall fully close on power loss.
MOTORIZED OUTDOOR AIR DAMPERS - Outdoor air dampers are positioned by a 2-position, spring-return damper actuator. The maximum leakage rate for the out­door air intake dampers shall not exceed 2% when dampers are full y closed and operating against a pres­sure differential of 0.5 IWG. A unit-mounted potenti ome­ter shall be provided to adjust the outdoor damper assembly to take in the design CFM of outdoor air to meet the ventil ati on requirement s of the conditioned space during no rmal oper ation. Whenever the indo or fan motor is energized, the dampers open up to one of two pre-select ed positions - regardless of the outdoor air enthalpy. Dampers return to the fully closed position when the indoor fan motor is de-energized. Dampers shall fully cl ose on power loss.
HIGH ALTITUDE - PROPANE GAS - Contains orifices required for appli cations between 2000 and 6000 feet altitude. Must be used with propane convers ion kit.
LOW NOX - Required to reduce the emission of nitr ogen oxides below 40 nanograms per joule.
GAS PIPING - Contains 1/2 pipe nipples, fittings and gas cock (including panel assess gaskets) required for bottom gas supply connection with external shut off.
POWER EXHAUST OPTION - To work in conj unction with economizers.
ELECTRIC HEATERS
ECONOMIZER/MOTORIZED DAMPER RAIN HOOD ­Contains all hood panel s and the hardware for assem­bling.
MANUAL OUTDOOR AIR DAMPER
COIL GUARD KIT - Guard for cooling coil.
HAIL GUARD
FLUE EXHAUST EXTENSION
OTHER FACTORY INSTALLED OPTIONS
POWER EXHAUST OPTION - To work in conj unction with economizers.
STAINLESS STEEL HEAT EXCHANGER
TECHNICOAT PHENOLIC COATED CONDENSER
AND EVAPORATOR COI L
ELECTRONIC SINGLE ENTHALPY ECONOMIZER
DIRTY FILTER SWITCH
PHASE MONITOR
COIL GUARD
POWERED GFI CONVENIENCE OUTLET
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
ROOF CURB - 14"a nd 8 high, full perimeter curb with wood nailer (shipped knocked-down).
BAROMETRIC RELIEF DAMPER - Contains a rain hood, air inlet screen, exhaust damper and mounting hardware. Used to reli eve internal air pressure through the unit.
PROPANE CONVERSION KIT - Contains new orifices and gas valve parts to convert from natural to L.P. gas. One per unit required.
HIGH ALTITUDE - NATURAL GAS - Contains orifices required for applications between 2000 and 6000 feet altitude.
Subject to change witho ut not ice. Printed in U.S.A. 036-21502-002-A-0303 Copyright © by Unitary Products 2003. All rights reserved. Supersedes: 036-21502-001-A-0103
Unitary 5005 Norman Products York OK Group Drive 73069
NON-POWERED GFI CONVENIENCE OUTLET
BAS CONTROLS (CPC, JOHNSON, HONEYWELL,
NOVAR)
BAS READY ECONOMIZER (BELIMO ACTUATOR WITHOUT A CONTROLLER)
HINGED FILTER DOOR ACCESS AND TOOLESS ACCESS PANELS
2" PLEATED FILTERS
DISCONNECT SWITCH
SUPPLY AIR SMOKE DETECTOR
RETURN AIR SMOKE DETECTOR
Loading...