Yokogawa UT35A, UT32A Specifications

<<Contents>> <<Index>>
General
Specications
UT35A/UT32A Digital Indicating Controllers
n Overview
The UT35A/UT32A digital indicating controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT35A/UT32A also support open networks such as Ethernet communication.
nFeatures
• A 14-segment, active (PV display color changing function) color LCD display is employed.
Two ve-digit, high-resolution displays are possible. Alphabet letters can be displayed in an easy-to-read
manner. The guide display shows parameter names.
• Easy to operate Navigation keys (SET/ENTER and Up/Down/Left/ Right arrow keys) are employed to facilitate making settings.
• 65 mm depth
The small depth enables the mounting in a thin and
small instrumented panel.
• Ladder sequence function is included as standard. This function allows for creating a simple sequence control. Dedicated LL50A Parameter Setting Software (sold separatly) allows for performing programming using a ladder language.
• Various built-in open network functions such as Eth­ernet are available. Easy connection with various vendors’ PLCs is possible.
• Quick setting function Setting only the minimum necessary parameters for operation is possible.
• Equipped with a multitude of functions Universal I/O are included as standard. PID control,
heating/cooling control, etc. are available.
[Style:S2]
UT35A UT32A
TableofNumberofInputsandOutputs
Modeland
sufxcode
(Seethe
modelcode)
UT35A
UT32A
*1: Excluding control output *2: In the case of cooling control output is analog output, it
*3: Excluding control output relays
Number
ofanalog
input
points
-×0×
-×1× 1 1 4 5
-×2× 1 1 (*2) 7 8
-×0× 1 1 2 3
-×1× 1 1 2 3
-×2× 1 1 (*2) 4 5
can not be used for transmission output.
1 1 2 3
Number
ofanalog
output
points(*1)
Number
ofcontact
input
points
Numberof
points(*3)
contact
output
nFunctionalSpecications
ControlSpecications
(1)ControlMode
Single-loop control
(
2)Controlperiod
200 ms
nControlComputationFunction
(1)Typesofcontrol
• PID control
• ON/OFF control (*4)
• Two-position two-level control (*5)
• Heating and cooling control (*5)
*4: Not selectable for Position proportional type *5: Selectable for heating and cooling control
Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-7179 Fax.: 81-422-52-6619
GS 05P01D31-01EN
1st Edition Nov.30, 2009 (KP)
2nd Edition Jun.11, 2010 (KP)
2
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 05P01D31-01EN
(2)ControlComputationFunction
(a) Target setting point and the number of PID param-
eter groups
Respectively, four sets of target setpoints, alarm
setpoints, and PID parameters can be set.
(b) Selecting the PID parameter group
The following PID parameter groups can be selected.
• Target setpoint number (SPNO) (The PID number can be set arbitrarily.)
• Measured input zone PID
• Target setpoint zone PID
• Reached target setpoint zone PID
(c) Auto-tuning
• Tuning results can be selected from two options, Normal or Stable.
• Tuning output limit can be set. (It cannot be used in
heating/cooling control.)
(d) “Super” function: Overshoot-suppressing function (e) “Super 2” function: Hunting-suppressing function (f) STOP preset output function (g) Input ERROR preset output function (h) MANUAL preset output function
(3)OperationModeSwitching
Operationmode
switching
AUTO/MANUAL and RUN/STOP switching REMOTE/LOCAL switching (only model with communication option)
(4)ControlParameterSettingRange
Proportional
band
Integraltime 1 to 6000 sec. or OFF (using manual reset)
Derivativetime 1 to 6000 sec. or OFF
ON/OFFcontrol hysteresis(one
ortwohysteresis
points)
Presetoutput
value
High/lowoutput
limiter
Tightshut
function
Rate-of-change
limiterofoutput
Output
deadband
0.1 to 999.9%
0.0 to 100.0% of measured input range width
-5.0 to 105.0% (however, 0 mA or less
cannot be output)
-5.0 to 105.0% Low limit setpoint < high limit setpoint
When manual control is carried out with
4 to 20 mA output, control output can be reduced to about 0 mA.
0.1 to 100.0%/sec., OFF
For heating and cooling control: -100.0 to
50.0% For position proportional control: 1.0 to
10.0%
(5)Laddercomputationperiod
Ladder computation period is the same as control period.
AlarmFunctions
• Types of Alarm
Measuredvalue
alarm Deviationalarm Rate-of-change
alarm
Setpointalarm
Outputalarm
Otheralarms
PV (measured value) high/low limit alarm Deviation high/low limit alarm Deviation high and low limits alarm Deviation within high and low limits alarm Analog input PV high/low limit alarm
Feedback input high/low limit alarm
PV rate-of-change alarm SP (setpoint) high/low limit alarm
Target SP high/low limit alarm Target SP deviation high/low limit alarm Target SP deviation high and low limits alarm Target SP deviation within high and low limits alarm
Control output high/low limit alarm Cooling control output high/low limit alarm
Heater disconnection alarm (for /HA option) Self-diagnosis alarm FAIL
• Alarm Functions
Alarmoutput
action
Numberofalarm
settings
Numberofalarm
outputpoints
Alarm stand-by action
Alarm latch (forced reset) function Alarm hysteresis Alarm ON/OFF delay timer
4
Up to 8 (differs by model code)
ContactI/OFunction
This function allows for allocating the input error condition, operation condition, alarm condition or other conditions to the contact input and contact output.
AUTO/MANUAL switching REMOTE/LOCAL switching (only model
with communication option) STOP/START switching Switching to AUTO Switching to MANUAL Switching to REMOTE (only model with
Contactinput
Contactoutput
communication option) Switching to LOCAL (only model with
communication option) AUTO-TUNING START/STOP switching
LCD backlight ON/OFF switching
Message interrupt displays 1 through 4
SP number specication PID number specication Manual preset output number specication
Alarms 1 through 4 Status output
LadderSequenceFunction
(1) NumberofI/OPoints
UT35A UT32A
Numberofdigitalinputpoints Up to 7 Up to 4
Numberofdigitaloutputpoints Up to 8 Up to 5
This is limited by the number of contact I/O signal
points. (See the model code.)
Jun.11, 2010-00
<<Contents>> <<Index>>
3
(2) Types of Command
Number of
commands
Number of basic command types
Number of appli­cation command types
13
73
Remark
Load, AND, OR, Timer, Counter, etc.
Comparison, reverse, addition/subtraction/ multiplication/division, logic operation, high/low limiter, etc.
(3) Sequence Device
Types of device Number of points
Digital I/O
Internal device
Special device Special relay (bit data) 12
Input relay 7 (max) Output relay 8 (max) M relay (bit data) 256 DAT register (data) 28 P register (parameter) 10 K register (constant)
30
Process data and process relay can be used besides the above-mentioned.
(4) Program capacity
Max Program capacity: 300 steps *
*: Available number of steps differs according to the
parameters and using command.
Communication Function
Function Method Interface Targets Max connection
Modbus/TCP
Modbus (RTU/ASCII)
PROFIBUS-DP
CC-Link
Peer to peer
Coordinated Communication
PC link
Ladder
*1: UT digital indicating controller, Signal conditioner JUXTA, Power monitor POWERCERT can be connected. *2: UT digital indication controllers can be connected.
A standard industry protocol allowing communications between the controller and devices such as PCs, PLCs, and DCSs.
Used for communication between PLCs and remote I/O, enabling high­speed data transmission.
A protocol allowing multiple controllers to send and receive data between one another. The Ladder Program is used. A protocol to coordinate the operation of two or more instruments controlling the same process. The proprietary Yokogawa protocol allowing communications to PCs, PLCs and touch panels. A protocol to communicate to PLCs.
Server Ethernet PLC and others 2 connections
Gateway
Slave RS-485
Slave RS-485 PLC and others
Modbus master
function
Slave RS-485 PLC and others
Modbus master
function
Multi-drop
Master/Slave RS-485
Slave RS-485
Ethernet
+RS-485
RS-485
RS-485
RS-485
(2 wire
only)
RS-485:
UT55A/UT52A
UT35A/UT32A (*1)
PLC and others,
UT55A/UT52A
UT35A/UT32A (*2)
UT55A/UT52A UT35A/UT32A
UT55A/UT52A/
UT35A/UT32A
UT55A/UT52A UT35A/UT32A
UT55A/UT52A
UT35A/UT32A (*2)
PC and others, UT55A/UT52A
UT35A/UT32A (*2)
Number of nodes:
(Main Controller
is included.)
Number of nodes:
42 (Remote device)
(Main Controller
is included.)
Read/Write: 4
Read only : 28
Master : 1 unit
Slave : 31 units
31 units
31 units
126
31 Units
31 Units
units
units
31units
Physical interface
Ethernet Standard : IEEE802.3 (10BASE-T, 100BASE-TX) Max segment length : 100m
Max.ConnectingCongguration:CascadeMax.4level(10BASE-T),Max.2level(100BASE-TX)
RS-485 Standard : EIA RS-485 Communication method : Two-wire harf-duplex or four-wire harf-duplex, start-stop synchoronization, and non-procedural
Baud rate : 600,1200,2400,4800,9600,19200 or 38400bps Peer to peer communication is only 19200bps
Maximum communication distance : 1200m
Terminatingresistor:220Ω(External)
PROFIBUS-DP Standard : Field bus (IEC61158) Corresponding version : DP V0 Baud rate : 9.6k, 19.2k, 45.45k, 93.75k, 187.5k, 0.5M, 1.5M, 3M, 6M, 12M
, AUTO (*3)
Communication distance : 1200m (9.6k to 93.75k) 1000m (187.5k)
400m (0.5M) 200m (1.5M)
100m (3M to 12M)
*3: AUTO automatically sets the baud rate to that of the host controller (PROFIBUS-DP master).
CC-Link Supported on version : Remote device (Ver.1.10, Ver.2.00) Baud rate : 156k, 625k, 2.5M, 5M, 10M bps Transmission distance : 1.2km (156k bps), 600m (625k bps), 200m (2.5M bps), 150m (5M bps),
100m (10M bps)
When used optical repeater : 7.6 km (156k) to 4.3 km (10M)
Communication
Data
PV, SP, OUT,
ALM etc
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
GS 05P01D31-01EN
Jun.11, 2010-00
4
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 05P01D31-01EN
nHardwareSpecications
DisplaySpecications
• PV display 5-digit, 14-segment active color LCD (white/red)
Character height: 21.5 mm for UT35A and 13.0 mm for UT32A
• Data display 5-digit, 11-segment color LCD (orange)
• Bar graph display 12-segment color LCD (orange)
UniversalInputSpecications
• Number of input points: 1
• Types of input, instrument range, and measurement
accuracy (see the table below)
Typesofinput
-270.0 to 1370.0°C -450.0 to 2500.0°F ±0.1% of instrument
K
-270.0 to 1000.0°C -450.0 to 2300.0°F
-200.0 to 500.0°C -200.0 to 1000.0°F
J -200.0 to 1200.0°C -300.0 to 2300.0°F
-270.0 to 400.0°C -450.0 to 750.0°F
T
0.0 to 400.0°C -200.0 to 750.0°F
B 0.0 to 1800.0°C 32 to 3300°F
S 0.0 to 1700.0°C 32 to 3100°F R 0.0 to 1700.0°C 32 to 3100°F
N -200.0 to 1300.0°C -300.0 to 2400.0°F
E -270.0 to 1000.0°C -450.0 to 1800.0°F ±0.1% of instrument
Thermocouple
L -200.0 to 900.0°C -300.0 to 1600.0°F
-200.0 to 400.0°C -300.0 to 750.0°F
U
0.0 to 400.0°C -200.0 to 1000.0°F
W(*2) 0.0 to 2300.0°C 32 to 4200°F
Platinel
0.0 to 1390.0°C 32.0 to 2500.0°F
2
PR20-40 0.0 to 1900.0°C 32 to 3400°F
W97
Re3-W75
0.0 to 2000.0°C 32 to 3600°F
Re25
-200.0 to 500.0°C -300.0 to 1000.0°F
JPt100
-150.00 to 150.00°C -200.0 to 300.0°F
-200.0 to 850.0°C -300.0 to 1560.0°F
(RTD)3-wire
Resistance-temperature
detector
Standard
signal
DCvoltage
DCcurrent 0.00 to 20.00 mA -
-200.0 to 500.0°C -300.0 to 1000.0°F
Pt100
-150.00 to 150.00°C -200.0 to 300.0°F
0.400 to 2.0000 V -
1.000 to 5.000 V -
4.00 to 20.00 mA -
0.000 to 2.000 V -
0.00 to 10.00 V -
-10.00 to 20.00 mV -
Instrumentrange
°C °F
Accuracy
range ±1 digit for 0°C or more ±0.2% of instrument range ±1 digit for less than 0°C However, ±2% of instrument range ±1 digit for less than
-200°C of thermocouple K ±1% of instrument range ±1 digit for less than -200°C of thermo­couple T ±0.15% of instrument range ±1 digit for 400°C or more ±5% of instrument range ±1 digit for less than 400°C ±0.15% of instrument range ±1 digit ±0.1% of instrument range ±1 digit ±0.25% of instrument range ±1 digit for less than 0°C
range ±1 digit for 0°C or more ±0.2% of instrument range ±1 digit for less than 0°C However, ±1.5% of instrument range ±1 digit for less than -200.0°C of thermocouple E ±0.2% of instrument range ±1 digit ±0.1% of instrument range ±1 digit ±0.5% of instrument range ±1 digit for 800°C or more Accuracy not guaran­teed for less than 800°C
±0.2% of instrument range ±1 digit
±0.1%
of instrument range ±1 digit ±0.1% of instrument range ±1 digit ±0.1% range ±1 digit
±0.1% of instrument range ±1 digit
±0.1% of instrument range ±1 digit
(*1)
of instrument
(*1)
The accuracy is that in the standard operating condi­tions: 23 ±2°C, 55 ±10%RH, and power frequency at 50/60 Hz.
*1:
±0.3°C and ±1 digit in the range between 0 and 100°C ±0.5°C ±1 digit in the range between -100 and 200°C
*2:
W-5% Re/W-26% Re (Hoskins Mfg.Co.), ASTM E988 ASTM E988ASTM E988
Applicable standards: JIS, IEC and DIN (ITS-90) for ther­mocouples and resistance-temperature detectors (RTD)
• Input sampling period: Synchronized to control period
• Burnout detection Upscale and downscale of function, and OFF can be specied for the standard signal of thermocou­ple and resistance-temperature detector (RTD). For integrated signal input, 0.1 V or 0.4 mA or less
is judged as a burnout.
• Input bias current: 0.05 μA (for thermocouple and
resistance-temperature detector (RTD))
• Resistance-temperature detector (RTD) measured
current: About 0.16 mA
• Input resistance
1 MΩ or more for thermocouple/mV input About 1 MΩ for voltage input
About 250 Ω for current input (with built-in shunt
resistance)
• Allowable signal source resistance
250 Ω or less for thermocouple/mV input
Effect of signal source resistance: 0.1 μV/Ω or less 2 kΩ or less for DC voltage input Effect of signal source resistance: about
0.01%/100 Ω
• Allowable wiring resistance Up to 150 Ω per line for resistance-temperature
detector (RTD) input (conductor resistance
between the three lines shall be equal)
Effect of wiring resistance: ±0.1°C/10 Ω
• Allowable input voltage/current
±10 V DC for thermocouple/mV/mA or resistance­ temperature detector (RTD) input ±20 V DC for V input ±40 mA DC for mA input
• Noise reduction ratio 40 dB or more (at 50/60 Hz) in normal mode 120 dB or more (at 50/60 Hz) in common mode
• Reference junction compensation error ±1.0°C (15 to 35°C) ±1.5°C (-10 to 5°C and 35 to 50°C)
Jun.11, 2010-00
<<Contents>> <<Index>>
5
AnalogOutputSpecications
• Number of points
Control output (heating-side output): 1 point (standard), which is shared with transmission output Cooling-side output: 1 point, which is shared with transmission output
• Output functions Current output or voltage pulse output
• Current output 4 to 20 mA DC or 0 to 20 mA DC/load resistance
600 Ω or less
• Current output accuracy ±0.1% of span (however, ±5% of span for 1 mA or less) The accuracy is that in the standard operating conditions: 23 ±2°C, 55 ±10%RH, and power frequency at 50/60 Hz
• Voltage pulse output Application: time proportional output ON voltage: 12 V or more/load resistance of 600
Ω or more
OFF voltage: 0.1 V DC or less Time resolution: 10 ms or 0.1% of output value, whichever is larger
RelayContactOutputSpecications
• Types of contact and number of points
Control relay output: one 1c-contact point Control output of heating and cooling control: 2 1a-contact points Alarm output: 3 1a-contact points (Common is
separated)
• Contact rating 1c-contact: 3 A at 250 V AC or 3 A at 30 V DC (resistance load) 1a-contact: For alarm output: 1 A at 240 V AC or 1 A at 30 V DC (resistance load) For output of heating and cooling control
relay output: 3 A at
240 V AC or 3 A at 30 V DC (resistance load)
*: This cannot be used for a small load of 10 mA or less.
• Application: time proportional output, alarm output, FAIL output, etc.
• Time resolution for control output: 10 ms or 0.1% of output value, whichever is larger
StepResponseTimeSpecications
1 s (Response time at 63% of transmission output when a
change is made stepwise in the range between 10 and
90% of input span)
PositionProportionalOutputSpecications
• Position signal input
Slide resistance: 100 Ω to 2.5 kΩ of total resistance
100% side and slide line: with disconnection detection 0% side: without disconnection detection Current input: 4 to 20 mA DC (with disconnection detection)
• Sampling period: 50 ms
• Measurement resolution: 0.1% of input span
• Position proportional relay output UT35A: Two 1a-contact points , 3 A at 250 V AC or 3A at 30 V DC (resistance load) UT32A: Two 1a-contact points , 3 A at 240 V AC or 3A at 30 V DC (resistance load)
*:
This cannot be used for a small load of 10 mA or less.
RetransmissionOutputSpecications
• Number of points: 1 point (standard), which is shared
with 15 V DC loop power supply
Additional 1 points when analog control output are
not used
• Output function: current output 4 to 20 mA DC or 0 to 20 mA DC/load
resistance 600 Ω or less
• Current output accuracy: ±0.1% of span (however,
±5% of span for 1 mA or less)
The accuracy is that in the basic operating
conditions: 23 ±2°C, 55 ±10%RH, and power frequency at 50/60 Hz
15VDCLoopPowerSupply Specications
• Number of points: 1 point (standard), which is shared
with retransmission output
Control output (1 point) can also be used.
• Supply voltage: 14.5 to 18.0 V DC
• Maximum supply current: about 21 mA (with short-cir-
cuit current limiting circuit)
ContactInputSpecications
• Number of points: 2 points (standard) For the maximum number of points, see the model and sufx code table.
• Input type: no-voltage contact input or transistor con-
tact input
• Input contact capacity: 12 V DC, 10 mA or more Be sure to use a contact with a minimum ON current of 1 mA or more
• ON/OFF detection For no-voltage contact input:
Contact resistance 1 kΩ or less in ON state
Contact resistance 50 kΩ or more in OFF state
Transistor contact input:
2 V or less in ON state
Leak current 100 μ A or less in OFF state
• Status detection minimum hold time: control period + 50 ms
• Application: SP switching, operation mode switching,
event input
TransistorContactOutputSpecications
• Number of points:
• Output form: open collector (sink current)
• Output contact capacity: Up to 24 V DC, 50 mA
• Output time resolution: min 200 ms
see the model and sufx code table
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
GS 05P01D31-01EN
Jun.11, 2010-00
6
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 05P01D31-01EN
The circuits divided by lines are insulated mutually.
Control and transmission (analog) output terminal (not isolated between the analog output terminals) Valve position (feedback) input terminal
PV (universal) input terminal
Control relay (c-contact or 2 a-contact) output terminal
Alarm-1 relay (a-contact) output terminal
Alarm-2 relay (a-contact) output terminal
Alarm-3 relay (a-contact) output terminal
Position proportional relay output terminal
Internal circuits
Power supply
Contact input terminal (All) RS485 communication terminal (2 ports)
24 V DC loop power supply terminal
Ethernet/PROFIBUS-DP/CC-Link communication terminal
Current transformer input terminal
Contact output (transistor) terminal
HeaterBreakAlarmSpecications(for/HAOption)
• Function: Measures the heater current using an external current transformer (CT) and generates a
heater break alarm when the measured value is less
than the disconnection detection value.
• Number of input points: 2 points
• Number of output points: 2 points (transistor contract
output)
• CT input resistance: about 9.4 Ω
• CT input range: 0.0 to 0.1 Arms (0.12 Arms or more
cannot be applied)
• Heater current alarm setting range: OFF, 0.1 to 300.0 Arms
Heater current measured value display range: 0.0 to
360.0 Arms
*: The CT ratio can be set. CT ratio setting range: 1 to 3300
• Recommended CT: CT from URD Co. Ltd.
CTL-6-S-H: CT ratio 800, measurable current
range: 0.1 to 80.0 Arms
CTL-12L-30: CT ratio 3000, measurable current
range: 0.1 to 180.0 Arms
• Heater current measurement period: 200 ms
• Heater current measurement accuracy: ±5% of CT input range span ±1 digit (CT error is not included)
• Heater current detection resolution: Within 1/250 of CT input range span
• Disconnection detection ON time: Minimum 200 ms. (for time proportional output)
24VDCLoopPower SupplySpecications
(for/LPOption)
Application: Power is supplied to the 2-wire transmitter.
• Supply voltage: 21.6 to 28.0 V DC
• Rated current: 4 to 20 mA DC
• Maximum supply current: About 30 mA (with short-cir­cuit current limiting circuit)
SafetyandEMCStandards
• Safety:
Compliant with IEC/EN61010-1 (CE), approved by
CAN/CSA C22.2 No. 61010-1 (CSA), UL61010-1. Installation category: CAT. II Pollution degree: 2 Measurement category: I (CAT. I) Rated measurement input voltage: Max. 10 V DC Rated transient overvoltage: 1500 V (*)
*:
This is a reference safety standard value for measure­ment category I of IEC/EN/CSA/UL61010-1. This value is not necessarily a guarantee of instrument performance.
• EMC standards:
Compliant with CE marking
EN 61326-1 Class A, Table 2 (For use in industrial
locations), EN 61326-2-3 EN 55011 Class A, Group 1 EN 61000-3-2 Class A EN 61000-3-3 C-tick mark EN 55011 Class A, Group 1
The instrument continues to operate at a measure
ment
accuracy of within ±20% of the range during
testing.
• RoHS regulation: Compliant
PowerSupplySpecicationsandIsolation
• Power supply Rated voltage: 100 to 240 V AC (+10%/-15%), 50/60 Hz
24 V AC/DC (+10%/-15%) (When the
/DC option is specied)
• Power consumption: UT35A: 18 VA (For the /DC
option. DC: 9 VA, AC: 14 VA) UT32A: 15 VA (For the /DC option. DC: 7 VA, AC: 11 VA)
• Storage: Nonvolatile memory
Allowable power interruption time: 20 ms (at 100 V AC)
• Withstanding voltage
2300 V AC for 1 minute between primary and
secondary terminals
1500 V AC for 1 minute between primary terminals 500 V AC for 1 minute between secondary
terminals (Primary terminals = Power (*) and relay output terminals, Secondary terminals = Analog I/O signal terminals, contact input terminals, communication terminals, and functional grounding terminals.)
*: Power terminals for 24 V AC/DC models are the
secondary terminals.
• Insulation resistance
Between power supply terminals and a grounding
terminal: 20 MΩ or more at 500 V DC
• Isolation specications
EnvironmentalConditions
Normaloperatingconditions
• Ambient temperature: -10 to 50°C (-10 to 40°C for side-by-side mounting of controllers)
• Ambient humidity: 20 to 90% RH (no condensation)
• Magnetic eld: 400 A/m or less
• Continuous vibration (at 5 to 9 Hz) Half amplitude of
1.5 mm or less (at 9 to 150 Hz) 4.9 m/s2 or less, 1 oct/min for 90 min­utes each in the three axis directions
• Rapid vibration: 14.7 m/s2, 15 s or less
• Impact: 98 m/s2 or less, 11 msec.
• Installation altitude: 2,000 m or less above sea level
• Warm-up time: 30 minutes or more after the power is turned on
• Start-up time within 10 s
Jun.11, 2010-00
<<Contents>> <<Index>>
Target setpoints 1 to 4
Output limiter
Manual operation
Manual preset output
Input error preset output
Preset output
AUTO (ON)/MAN (OFF) switch
STOP (ON)/RUN (OFF) switch
LOCALREMOTE
AUTO
When sensor burnout occurs
Normal
MAN
RUNSTOP
SP ramp rate
SP limiter
PV
Input type
Input unit
Input range/scale
PV input bias
PV input filter
Ratio bias computation
Output limiter
BS
FL
CNT ALG
UPR, DNR TMU
SPNO SP
RT RBS
R/L
SPH, SPL
UNIT
IN
RH, RL SDP SH, SL
EPO
OH, OL
OH, OL OLMT
PO
S/R
MPON
OT
Equipped as standard
Equipped as standard
For optional suffix code /HA
Heater break alarm
HAL2HAL1
Heater break
alarm 1
Heater break
alarm 2
Current or voltage pulseRelay
LPS
24 V loop
power supply
Current
OUTOUT RET AL3AL2AL1
For optional suffix code /LP
OUT retransmission output
O1RS
RET retransmission output
RTS
* After the control output terminal is specified by the parameter OT, other current output terminals can be used as retransmission output.
Alarm
Output terminal assignment
DI2DI1
A/M
Control computation
(Current when retransmission output)
Communication
PV input Contact inputs
Equipped as standard
Equipped as standard.
Terminal Parameter Function
Analog signal Contact signal Front panel key
Legend
Alarm 1
(PV high limit)
Alarm 2
(PV low limit)
Alarm 3
(PV high limit)
PV display SP display
Input ladder calculation program (signal goes to the control computation as is when without ladder program). For ladder program, see the LL50A Parameters Setting Software User’s Manual.
Output ladder calculation program (signal goes to the output as is when without ladder program). For ladder program, see the LL50A Parameter Setting Software User’s Manual.
7
TransportationandStorageConditions
• Temperature: -25 to 70°C
• Temperature change rate: 20°C per hour or less
• Humidity: 5 to 95%RH (no condensation)
EffectsofOperatingConditions
• Effect of ambient temperature
For voltage or TC input:
±1 μ V/°C or ±0.01% of F.S. (instrument range)/
°C, whichever is greater
For RTD input:
±0.05°C/°C (ambient temperature) or less
For current input: ±0.01% of F.S. (instrument range)/°C For analog output:
±0.02% of F.S./°C or less
• Effect of power supply uctuation:
For analog input: ±0.05% of F.S. (instrument range)
or less
For analog output: ±0.05% of F.S. or less
(Each within rated voltage range)
nBlockDiagram
SingleLoopControl
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
GS 05P01D31-01EN
Jun.11, 2010-00
8
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 05P01D31-01EN
E4-terminal area
E3-terminal area
PV
VALV
E1-terminal area
PV input
TC input RTD input
Voltage (mV, V) input
A
Current (mA) input
B
b
(Suffix code: Type1=-1)
(Suffix code: Type 1=-2)
(Suffix code: Type 1=-2)
(24 V AC/DC power supply: Optional suffix code /DC)
(Equipped as standard)
Power supply
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
401
408
409
410
411
412
301
302
303
304
305
306
201
202
203
204
205
206
207
208
210
211
212
Cooling-side control output
Position proportional control output
Resistance: 100 Ω to 2.5 kΩ
Feedback input
100%
0%
101
-112
501
-512
401
-412
301
-306
201
-212
ALM
(Equipped as standard)
Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Alarm-3 output (PV high limit)
Alarm-2 output
( PV low limit)
Alarm-1 output (PV high limit)
Common
Common
Common
UT
104
105
106
107
108
109
100-240 V AC power supply
N
L
Allowable range: 100-240 V AC (±10%) (free voltage) 50/60 Hz shared
110
111
24 V AC/DC power supply
110
111
Relay contact output
HIGH (direct)
LOW (reverse)
COM
Contact rating: 250 V AC, 3A 30 V DC, 3 A (resistance load)
507
508
509
510
511
512
-
Feedback input
Current (mA) input
When feedback input is current
510
511
512
202
203
201
202
203
202
203
203
204
RET/OUT2
Current/voltage pulse output
0-20 mA DC, 4-20 mA DC, Voltage pulse (12V)
205
206
Factory default: PV input type is undefined.
OUT
(Suffix code: Type1=-0)
Control output
101
102
Relay contact output
103
NC
NO
COM
Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)
Terminal wiring differs in Heating/cooling control and Position proportional control. Refer to the terminals of Position proportional control output and Heating/cooling control output below. Factory default: Control output is relay.
OUT
Current/voltage pulse output
0-20 mA DC, 4-20 mA DC, Voltage pulse (12 V)
Retransmission output
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC, 4-20 mA DC
Control output
(Suffix code: Type1=-0, -1 or -2)
15 V DC loop power supply
14.5-18.0 V DC (Max. 21 mA DC)
207
208
207
208
207
208
Can be used for retransmission output or 15 V DC loop power supply when current/voltage pulse output is not used for control output. Current output range can be changed. In Position proportional type, can be used for retransmission output or 15 V DC loop power supply.
RET
Retransmission output
4-20 mA DC or 0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC (Max. 21 mA DC)
Default: 4-20 mA DC
Default: PV retransmission
Load resistance 600 Ω or less
Retransmission output
(Equipped as standard)
205
206
205
206
Can be used for 15 V DC loop power supply when not used for retransmission output.
DI
(Equipped as standard)
Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI2
DI1
COM
AUTO when DI1=ON MAN when DI1=OFF
STOP when DI2=ON RUN when DI2=OFF
Common
DI2
DI1
COM
+5V
+5V
No-voltage contact
Transistor contact
UT
UT
210
211
212
210
211
212
Function can be assigned to the terminals with no function.
+
HBA
(Optional suffix code /HA)
Heater break alarm
Heater current detection input
CT1
CT2
COM
External contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
Heater break alarm-1
output
Heater break alarm-2
output
Common
510
511
512
HAL1
HAL2
COM
UT
507
508
509
112
112
112
N
L
Can not be used for retransmission output or 15 V DC loop power supply when current/voltage pulse output is used. Can be used for retransmission output or 15 V DC loop power supply when control output is not used. Current output range can be changed.
Heating/cooling control output
Heating/cooling relay contact output
NO
Heating
-side
Cooling
-side
NO
COM
Contact rating: 240 V AC, 3 A 30 V DC, 3 A (resistance load)
101
102
103
OUT
OUT2
nTerminalArrangement
TerminalArrangementforUT35ASingle LoopControl
Jun.11, 2010-00
<<Contents>> <<Index>>
(Suffix code: Type 2=2)
Contact input
External contact input
DI11
DI12
DI13
DI14
DI15
COM
Common
DI11
DI12
COM
+5V
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
DI13
+5V
DI14
+5V
DI15
+5V
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UT UT
301
302
303
304
305
306
301
302
303
304
305
306
Function can be assigned to the terminals with no function.
DI
E1-Terminal Area
301-306
(Suffix code: Type 2=1)
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO12
DO11
COM
Common
UT
Contact input / Contact output
External contact input
DI11
DI12
COM
Common
DI11
DI12
COM
+5V
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UT UT
301
302
303
301
302
303
304
305
306
DI/DO
Function can be assigned to the terminals with no function.
+
24 V DC loop power supply
21.6-28.0 V DC (Max. 30 mA DC)
24 V DC loop power supply
505
506
LPS24
(Optional suffix code /LP)
(Suffix code: Type 2=2)
Contact output
External contact output
DO42
DO41
DO43
DO44
DO45
COM
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
Common
UT
501
502
503
504
505
506
DO
Transistor contact rating: 24 V DC, 50 mA
Function can be assigned to the terminals with no function.
E4-Terminal Area
501-506
E4-terminal area
E3-terminal area
E1-terminal area
101
102
103
104
105
106
107
108
109
110
111
501
502
503
504
505
506
507
508
509
510
511
512
407
401
408
409
410
411
412
301
302
303
304
305
306
201
202
203
204
205
206
207
208
210
211
212
101
-112
501
-512
401
-412
301
-306
201
-212
112
(Suffix code: Type 3=2)
Ethernet communication (with gateway function)
10BASE-T/100BASE-TX RJ45 connector
Color
Lit
Unlit
Amber
100M bps
10M bps
Green
Linked
Active
Link failure
Color
Lit
Blink
Unlit
Upper side LED (baud rate)
Lower side LED (link activity)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
ETHR
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication
(Suffix code: Type 3=1)
407
408
409
410
411
RS485
(Suffix code: Type 3=4)
PROFIBUS-DP communication (with Modbus master)
Pin
1
2
Signal name Description
VP
RxD/TxD-P
3 RxD/TxD-N
4 DGND
5 SHIELD
+5V bus power
Data signal (positive data receive/transmit)
Data signal (negative data recive/transmit)
Signal ground
Shield ground
RS-485
RSB(+)
RSA(-)
SG
407
408
409
PROF
If the UT is located at the end of a segment for the PROFIBUS communication wiring, terminating resistors are separately needed. These are to be prepared by
users. (390 Ω: 2 pcs. 220 Ω:
1 pc., or an active terminator.)
VP
RxD/TxD-P
Data line
Data line
390Ω
220Ω
390Ω
RxD/TxD-N
DGND
CHK
RDY
ERR
LED
CHK (red)
RDY
(green)
Lit Unlit
ERR (red)
User profile error Normal
Normal
Not connected, or communication failure (flashing)
Normal Communicating successfully
No power, or Communication failure
E3-Terminal Area
401-412
1
2
3
4
5
(Suffix code: Type 3=3)
CC-Link communication (with Modbus master)
RS-485
RSB(+)
RSA(-)
SG
407
408
409
CC-L
If the UT is located at the end of a segment for the CC-Link communication wiring, terminating resistors are separately needed. These are to be prepared by users.
(110 Ω: 1 pc.)
DA
DB
110Ω
LED
CHK (red)
L ERR
(red)
L RUN (green)
Lit
Unlit
CHK
L RUN
L ERR
User profile error/ Address error
Normal
Normal
Pin
1
2
Signal name Description
DA
DB
3 DG
4
SLD
5
FG
RX/TX + signal
RX/TX - signal
Flame ground
RX/TX signal ground
Shield
Normal Communicating successfully
Communication failure (CRC error)
No carrier detected/ Communication timeout
1
2
3
4
5
9
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
GS 05P01D31-01EN
Jun.11, 2010-00
10
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 05P01D31-01EN
(Suffix code: Type1=-1)
(Suffix code: Type 1=-2)
(Suffix code: Type1=-0)
Retransmission output
4-20 mA DC or 0-20 mA DC
15 V DC loop power supply
14.5-18.0 V DC (Max. 21 mA DC)
Default: 4-20 mA DC
Default: PV retransmission
Load resistance 600 Ω or less
Retransmission output
(Equipped as standard)
PV input
TC input RTD input
Voltage (mV, V) input
A
Current (mA) input
B
b
(Equipped as standard)
Control output
Relay contact output
NC
NO
COM
Contact rating: 250 V AC, 3 A 30 V DC, 3 A (resistance load)
111
301
302
303
304
305
306
307
308
309
310
311
312
201
202
203
204
205
206
207
208
210
101
102
103
104
105
106
107
108
109
110
211
212
Current/voltage pulse output
0-20 mA DC, 4-20 mA DC, Voltage pulse (12 V)
Heating/cooling control output
(Suffix code: Type 1=-2)
Cooling-side control output
Heating/cooling relay contact output
NO
Heating
-side
Cooling
-side
NO
COM
Contact rating: 240 V AC, 3 A 30 V DC, 3 A (resistance load)
Position proportional control output
Resistance: 100 Ω to 2.5 kΩ
Feedback input
100%
0%
Relay contact output
HIGH (direct)
LOW
(reverse)
COM
Contact rating: 240 V AC, 3A 30 V DC, 3 A (resistance load)
Feedback input
Current (mA) input
When feedback input is current
E1-terminal area
101
-112
301
-312
201
-212
101
102
103
101
102
103
310
311
312
310
311
312
202
203
201
202
203
202
203
203
204
205
206
205
206
101
102
103
205
206
Terminal wiring differs in Heating/cooling control and Position proportional control. Refer to the terminals of Position proportional control output and Heating/cooling control output below. Factory default: Control output is relay.
Can be used for 15 V DC loop power supply when not used for retransmission output.
PV
RET
(Equipped as standard)
Contact input
Contact rating: 12 V DC, 10 mA or more
External contact input
DI2
DI1
COM
AUTO when DI1=ON MAN when DI1=OFF
STOP when DI2=ON RUN when DI2=OFF
Common
DI2
DI1
COM
+5V
+5V
No-voltage contact
Transistor contact
UT
UT
210
211
212
210
211
212
Function can be assigned to the terminals with no function.
DI
VALV
(Equipped as standard)
Contact output
External contact output (relay)
AL3
AL2
AL1
Relay contact rating: 240 V AC, 1 A
30 V DC, 1 A (resistance load)
Alarm-3 output (PV high limit)
Alarm-2 output
(PV low limit)
Alarm-1 output (PV high limit)
Common
Common
Common
UT
104
105
106
107
108
109
ALM
OUT
OUT
RET/OUT2
Factory default: PV input type is undefined.
(Optional suffix code /HA)
Heater break alarm
Heater current detection input
CT1
CT2
COM
310
311
312
HBA
External contact output (transistor)
Transistor contact rating: 24 V DC, 50 mA
Heater break alarm-1
output
Heater break alarm-2
output
Common
HAL1
HAL2
COM
UT
307
308
309
Current/voltage pulse output
0-20 mA DC, 4-20 mA DC, Voltage pulse (12 V)
Retransmission output
Default: 4-20 mA DC
Default: Undefined
0-20 mA DC, 4-20 mA DC
Control output
(Suffix code: Type1=-0, -1 or -2)
15 V DC loop power supply
14.5-18.0 V DC (Max. 21 mA DC)
207
208
207
208
207
208
Can be used for retransmission output or 15 V DC loop power suppy when current/voltage pulse output is not used for control output. Current output range can be changed. In Position proportional type, can be used for retransmission output or 15 V DC loop power supply.
OUT
OUT2
112
Power supply
24 V AC/DC power supply
100-240 V AC power supply
Allowable range: 100-240 V AC (±10%) (free voltage) 50/60 Hz shared
N
L
(24 V AC/DC power supply: Optional suffix code /DC)
110
111
110
111
112
112
N
L
Can not be used for retransmission output or 15 V DC loop power suppy when current/voltage pulse output is used for control output. Can be used for retransmission output or 15 V DC loop power suppy when control output is not used. Current output range can be changed.
24 V DC loop power supply
21.6-28.0 V DC (Max. 30 mA DC)
24 V DC loop power supply
(Suffix code: Type 2=0 and optional suffix code /LP)
305
306
LPS24
(Suffix code: Type 2=2)
External contact output
Transistor contact rating: 24 V DC, 50 mA
DO12
DO11
COM
Common
UT
Contact input / Contact output
External contact input
DI11
DI12
COM
Common
DI11
DI12
COM
+5V
+5V
No-voltage contact
Transistor contact
Contact rating: 12 V DC, 10 mA or more
Factory default: No function
Factory default: No function
Factory default: No function
Factory default: No function
UT UT
301
302
303
301
302
303
304
305
306
DI/DO
Function can be assigned to the terminals with no function.
E1-Terminal Area
301-306
RS-485
SDB(+)
SDA(-)
RDB(+)
RDA(-)
SG
RS-485 communication
(Suffix code: Type 2=1)
301
302
303
304
305
RS485
RS-485
RSB(+)
RSA(-)
SG
RS-485 communication/24 V DC loop power supply
24 V DC loop power supply
21.6-28.0 V DC (Max. 30 mA DC)
301
302
303
305
306
RS485/LPS24
(Suffix code: Type 2=1 and optional suffix code /LP)
TerminalArrangementforUT32ASingle LoopControl
Jun.11, 2010-00
<<Contents>> <<Index>>
(25)
(53)
[(N-1)×96+92]
117 min.
145
min.
+0.8
0
+0.8
0
92
+0.8
0
92
+0.8
0
92
“N” stands for the number of controllers to be installed.
However, the measured value applies if N≥5.
65
20
11
1 to 10 mm (panel thickness)
Bracket
Bracket
94.6
91.6
105.2
96
96
• General mounting • Side-by-side close mounting
Terminal cover (option)
Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2
[(N-1)×48+45]
+0.6
0
+0.8
0
92
65
48
11
1 to 10 mm (panel thickness)
Bracket
Bracket
Terminal cover (option)
94.6
96
105.2
70 min.
(25)
145 min.
+0.6
0
45
(53)
+0.8
0
92
• General mounting
• Side-by-side close mounting
20
91.6
“N” stands for the number of controllers to be installed. However, the measured value applies if N5.
Normal tolerance: ±(value of JIS B 0401-1998 tolerance class IT18)/2
nExternalDimensionsandPanelCutoutDimensions
UT35A
11
Unit:mm
UT32A
nConstruction,Mounting,andWiring
• Dust-proof and drip-proof: IP56 (Front panel) (Except
for side-by-side close mounting)/NEMA4 *
*: Hose down test only
Material: Polycarbonate resin (Flame retardancy: UL94 V-0)
• Case color: Light gray
• Weight: 0.5 kg or less
• External dimensions (mm): UT35A: 96 (width) x 96 (height) x 65 (depth from the
panel surface)
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
Unit:mm
UT32A: 48 (width) x 96 (height) x 65 (depth from the
panel surface)
• Mounting: Direct panel mounting; mounting bracket,
one each for upper and lower mounting
• Panel cutout dimensions (mm):
UT35A: 92+ UT32A: 45+
0.8/0
(width) x 92+
0.6/0
(width) x 92+
0.8/0
(height)
0.8/0
(height)
• Mounting position: Up to 30 degrees above the hori­zontal. No downward titling allowed.
• Wiring: M3 screw terminal with square washer (signal wiring and power)
GS 05P01D31-01EN
Jun.11, 2010-00
<<Contents>> <<Index>>
nModelandSufxCode
Model Sufxcode
UT35A
Type 1: Basic control
Type 2: Functions
Type 3: Open networks
Display language (*1)
Case color
Fixed code -00 Always "-00"
Optional sufx codes
-0
-1
-2 0 None 1 2 additional DIs, 2 additional DOs 2 5 additional DIs, 5 additional DOs
0 None 1 RS-485 communication (Max.38.4 kbps, 2-wire/4-wire) 2 Ethernet communication (with serial gateway function) 3 CC-Link communication 4 PROFIBUS-DP communication
-1 English
-2 German
-3 French
-4 Spanish 0 White (Light gray) 1 Black (Light charcoal gray)
Optional
sufx
code
/LP 24 V DC loop power supply (*2) /HA Heater break alarm (*3) /DC Power supply 24 V AC/DC /CT Coating (*4)
Digital Indicating Controller (provided with retransmission output or 15 V DC loop power supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC) Standard type Position proportional type Heating/cooling type
*1: English, German, French, and Spanish can be displayed as the guide display.
*2: The /LP option can be specied in the combination of Type 2 code (any of "0" or "1") and Type 3 code (any of "0" or "1".) *3: The /HA option can be specied when the Type 1 code is "-0" or "-2." *4: When the /CT option is specied, the UT35A does not conform to the safety standards (UL and CSA) and CE marking.
Model Sufxcode
UT32A
Type 1: Basic control
Type 2: Functions
Type 3: Open networks
Display language (*1)
Case color
Fixed code -00 Always "-00"
Optional sufx codes
-0
-1
-2 0 None 1 RS-485 communication (Max. 38.4 kbps, 2-wire/4-wire) (*2) 2 2 additional DIs and 2 additional DOs
0 None
-1 English
-2 German
-3 French
-4 Spanish 0 White (Light gray) 1 Black (Light charcoal gray)
Optional
sufx
code
/LP 24 V DC loop power supply (*2) /HA Heater break alarm (*3) /DC Power supply 24 V AC/DC /CT Coating (*4)
Digital Indicating Controller (provided with retransmission output or 15 V DC loop power supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC) Standard type Position proportional type Heating/cooling type
*1: English, German, French, and Spanish can be displayed as the guide display. *2: The /LP option can be specied in the combination of Type 1 code (any of "-0" or "-1") and Type 2 code (any of "0" or "1.") Ad-
ditionally, when the Type 2 code is "1", the RS-485 communication is 2-wire system.
*3: The /HA option can be specied when the Type 1 code is "-0" or "-2." *4: When the /CT option is specied, the UT32A does not conform to the safety standards (UL and CSA) and CE marking.
Description
Description
12
nItemstobespeciedwhenordering
Model and sufx codes, whether User’s Manual and
QIC required.
nStandardaccessories
Brackets (mounting hardware), Unit label, Operation Guide
nAccessory
Name
Terminalcover
User’sManual
(CD-ROM)
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation Subject to change without notice.
UTAP001 For UT35A
UTAP002 For UT32A
UTAP003
Model Description
nSpecialOrderItems
Modelcode
LL50A
Sufxcode Description
-00 Parameter Setting Software
GS 05P01D31-01EN
Jun.11, 2010-00