The UT35A/UT32A digital indicating controllers employ
an easy-to-read, 14-segment large color LCD display,
along with navigation keys, thus greatly increasing
the monitoring and operating capabilities. A ladder
sequence function is included as standard. The short
depth of the controller helps save instrument panel
space. The UT35A/UT32A also support open networks
such as Ethernet communication.
nFeatures
• A 14-segment, active (PV display color changing
function) color LCD display is employed.
Two ve-digit, high-resolution displays are possible.
Alphabet letters can be displayed in an easy-to-read
manner. The guide display shows parameter names.
• Easy to operate
Navigation keys (SET/ENTER and Up/Down/Left/
Right arrow keys) are employed to facilitate making
settings.
• 65 mm depth
The small depth enables the mounting in a thin and
small instrumented panel.
• Ladder sequence function is included as standard.
This function allows for creating a simple sequence
control. Dedicated LL50A Parameter Setting Software
(sold separatly) allows for performing programming
using a ladder language.
• Various built-in open network functions such as Ethernet are available.
Easy connection with various vendors’ PLCs is possible.
• Quick setting function
Setting only the minimum necessary parameters for
operation is possible.
• Equipped with a multitude of functions
Universal I/O are included as standard. PID control,
heating/cooling control, etc. are available.
[Style:S2]
UT35A UT32A
TableofNumberofInputsandOutputs
Modeland
sufxcode
(Seethe
modelcode)
UT35A
UT32A
*1: Excluding control output
*2: In the case of cooling control output is analog output, it
*3: Excluding control output relays
Number
ofanalog
input
points
-×0×
-×1×1145
-×2×11 (*2)78
-×0×1123
-×1×1123
-×2×11 (*2)45
can not be used for transmission output.
1123
Number
ofanalog
output
points(*1)
Number
ofcontact
input
points
Numberof
points(*3)
contact
output
nFunctionalSpecications
ControlSpecications
(1)ControlMode
Single-loop control
(
2)Controlperiod
200 ms
nControlComputationFunction
(1)Typesofcontrol
• PID control
• ON/OFF control (*4)
• Two-position two-level control (*5)
• Heating and cooling control (*5)
*4: Not selectable for Position proportional type
*5: Selectable for heating and cooling control
Yokogawa Electric Corporation
2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan
Tel.: 81-422-52-7179 Fax.: 81-422-52-6619
(a) Target setting point and the number of PID param-
eter groups
Respectively, four sets of target setpoints, alarm
setpoints, and PID parameters can be set.
(b) Selecting the PID parameter group
The following PID parameter groups can be selected.
• Target setpoint number (SPNO) (The PID number
can be set arbitrarily.)
• Measured input zone PID
• Target setpoint zone PID
• Reached target setpoint zone PID
(c) Auto-tuning
• Tuning results can be selected from two options,
Normal or Stable.
• Tuning output limit can be set. (It cannot be used in
heating/cooling control.)
(d) “Super” function: Overshoot-suppressing function
(e) “Super 2” function: Hunting-suppressing function
(f) STOP preset output function
(g) Input ERROR preset output function
(h) MANUAL preset output function
(3)OperationModeSwitching
Operationmode
switching
AUTO/MANUAL and RUN/STOP switching
REMOTE/LOCAL switching (only model
with communication option)
(4)ControlParameterSettingRange
Proportional
band
Integraltime1 to 6000 sec. or OFF (using manual reset)
Derivativetime 1 to 6000 sec. or OFF
ON/OFFcontrol
hysteresis(one
ortwohysteresis
points)
Presetoutput
value
High/lowoutput
limiter
Tightshut
function
Rate-of-change
limiterofoutput
Output
deadband
0.1 to 999.9%
0.0 to 100.0% of measured input range
width
-5.0 to 105.0% (however, 0 mA or less
cannot be output)
-5.0 to 105.0%
Low limit setpoint < high limit setpoint
When manual control is carried out with
4 to 20 mA output, control output can be
reduced to about 0 mA.
0.1 to 100.0%/sec., OFF
For heating and cooling control: -100.0 to
50.0%
For position proportional control: 1.0 to
10.0%
(5)Laddercomputationperiod
Ladder computation period is the same as control
period.
AlarmFunctions
• Types of Alarm
Measuredvalue
alarm
Deviationalarm
Rate-of-change
alarm
Setpointalarm
Outputalarm
Otheralarms
PV (measured value) high/low limit alarm
Deviation high/low limit alarm
Deviation high and low limits alarm
Deviation within high and low limits alarm
Analog input PV high/low limit alarm
This function allows for allocating the input error
condition, operation condition, alarm condition or other
conditions to the contact input and contact output.
AUTO/MANUAL switching
REMOTE/LOCAL switching (only model
with communication option)
STOP/START switching
Switching to AUTO
Switching to MANUAL
Switching to REMOTE (only model with
Contactinput
Contactoutput
communication option)
Switching to LOCAL (only model with
communication option)
AUTO-TUNING START/STOP switching
LCD backlight ON/OFF switching
Message interrupt displays 1 through 4
SP number specication
PID number specication
Manual preset output number specication
Alarms 1 through 4
Status output
LadderSequenceFunction
(1) NumberofI/OPoints
UT35AUT32A
NumberofdigitalinputpointsUp to 7Up to 4
NumberofdigitaloutputpointsUp to 8Up to 5
This is limited by the number of contact I/O signal
points. (See the model code.)
Jun.11, 2010-00
<<Contents>> <<Index>>
3
(2) Types of Command
Number of
commands
Number of basic
command types
Number of application command
types
13
73
Remark
Load, AND, OR, Timer,
Counter, etc.
Comparison, reverse,
addition/subtraction/
multiplication/division, logic
operation, high/low limiter,
etc.
(3) Sequence Device
Types of deviceNumber of points
Digital I/O
Internal device
Special device Special relay (bit data)12
Input relay7 (max)
Output relay8 (max)
M relay (bit data)256
DAT register (data)28
P register (parameter)10
K register (constant)
30
Process data and process relay can be used besides
the above-mentioned.
(4) Program capacity
Max Program capacity: 300 steps *
*: Available number of steps differs according to the
parameters and using command.
Communication Function
FunctionMethodInterfaceTargetsMax connection
Modbus/TCP
Modbus
(RTU/ASCII)
PROFIBUS-DP
CC-Link
Peer to peer
Coordinated
Communication
PC link
Ladder
*1: UT digital indicating controller, Signal conditioner JUXTA, Power monitor POWERCERT can be connected.
*2: UT digital indication controllers can be connected.
A standard industry protocol
allowing communications
between the controller and
devices such as PCs, PLCs,
and DCSs.
Used for communication
between PLCs and
remote I/O, enabling highspeed data transmission.
A protocol allowing multiple
controllers to send and
receive data between
one another. The Ladder
Program is used.
A protocol to coordinate the
operation of two or more
instruments controlling the
same process.
The proprietary Yokogawa
protocol allowing
communications to PCs,
PLCs and touch panels.
A protocol to communicate
to PLCs.
ServerEthernetPLC and others2 connections
Gateway
SlaveRS-485
SlaveRS-485PLC and others
Modbus master
function
SlaveRS-485PLC and others
Modbus master
function
Multi-drop
Master/SlaveRS-485
SlaveRS-485
Ethernet
+RS-485
RS-485
RS-485
RS-485
(2 wire
only)
RS-485:
UT55A/UT52A
UT35A/UT32A (*1)
PLC and others,
UT55A/UT52A
UT35A/UT32A (*2)
UT55A/UT52A
UT35A/UT32A
UT55A/UT52A/
UT35A/UT32A
UT55A/UT52A
UT35A/UT32A
UT55A/UT52A
UT35A/UT32A (*2)
PC and others,
UT55A/UT52A
UT35A/UT32A (*2)
Number of nodes:
(Main Controller
is included.)
Number of nodes:
42 (Remote device)
(Main Controller
is included.)
Read/Write: 4
Read only : 28
Master : 1 unit
Slave : 31 units
31 units
31 units
126
31 Units
31 Units
units
units
31units
Physical interface
Ethernet Standard : IEEE802.3 (10BASE-T, 100BASE-TX)
Max segment length : 100m
• PV display
5-digit, 14-segment active color LCD (white/red)
Character height: 21.5 mm for UT35A and 13.0 mm
for UT32A
• Data display
5-digit, 11-segment color LCD (orange)
• Bar graph display
12-segment color LCD (orange)
UniversalInputSpecications
• Number of input points: 1
• Types of input, instrument range, and measurement
accuracy (see the table below)
Typesofinput
-270.0 to 1370.0°C -450.0 to 2500.0°F ±0.1% of instrument
K
-270.0 to 1000.0°C -450.0 to 2300.0°F
-200.0 to 500.0°C-200.0 to 1000.0°F
J-200.0 to 1200.0°C -300.0 to 2300.0°F
-270.0 to 400.0°C-450.0 to 750.0°F
T
0.0 to 400.0°C-200.0 to 750.0°F
B0.0 to 1800.0°C32 to 3300°F
S0.0 to 1700.0°C32 to 3100°FR0.0 to 1700.0°C32 to 3100°F
N-200.0 to 1300.0°C -300.0 to 2400.0°F
E-270.0 to 1000.0°C -450.0 to 1800.0°F ±0.1% of instrument
Thermocouple
L-200.0 to 900.0°C-300.0 to 1600.0°F
-200.0 to 400.0°C-300.0 to 750.0°F
U
0.0 to 400.0°C-200.0 to 1000.0°F
W(*2) 0.0 to 2300.0°C32 to 4200°F
Platinel
0.0 to 1390.0°C32.0 to 2500.0°F
2
PR20-40 0.0 to 1900.0°C32 to 3400°F
W97
Re3-W75
0.0 to 2000.0°C32 to 3600°F
Re25
-200.0 to 500.0°C-300.0 to 1000.0°F
JPt100
-150.00 to 150.00°C -200.0 to 300.0°F
-200.0 to 850.0°C-300.0 to 1560.0°F
(RTD)3-wire
Resistance-temperature
detector
Standard
signal
DCvoltage
DCcurrent 0.00 to 20.00 mA-
-200.0 to 500.0°C-300.0 to 1000.0°F
Pt100
-150.00 to 150.00°C -200.0 to 300.0°F
0.400 to 2.0000 V-
1.000 to 5.000 V-
4.00 to 20.00 mA-
0.000 to 2.000 V-
0.00 to 10.00 V-
-10.00 to 20.00 mV -
Instrumentrange
°C°F
Accuracy
range ±1 digit for 0°C
or more
±0.2% of instrument
range ±1 digit for less
than 0°C
However, ±2% of
instrument range
±1 digit for less than
-200°C of thermocouple
K ±1% of instrument
range ±1 digit for less
than -200°C of thermocouple T
±0.15% of instrument
range ±1 digit for 400°C
or more
±5% of instrument
range ±1 digit for less
than 400°C
±0.15% of instrument
range ±1 digit
±0.1% of instrument
range ±1 digit
±0.25% of instrument
range ±1 digit for less
than 0°C
range ±1 digit for 0°C
or more
±0.2% of instrument
range ±1 digit for less
than 0°C
However, ±1.5% of
instrument range ±1 digit
for less than -200.0°C of
thermocouple E
±0.2% of instrument
range ±1 digit
±0.1% of instrument
range ±1 digit
±0.5% of instrument
range ±1 digit for 800°C
or more
Accuracy not guaranteed for less than 800°C
±0.2% of instrument
range ±1 digit
±0.1%
of instrument
range ±1 digit
±0.1% of instrument
range ±1 digit
±0.1%
range ±1 digit
±0.1% of instrument
range ±1 digit
±0.1% of instrument
range ±1 digit
(*1)
of instrument
(*1)
The accuracy is that in the standard operating conditions: 23 ±2°C, 55 ±10%RH, and power frequency at
50/60 Hz.
*1:
±0.3°C and ±1 digit in the range between 0 and 100°C
±0.5°C ±1 digit in the range between -100 and 200°C
*2:
W-5% Re/W-26% Re (Hoskins Mfg.Co.), ASTM E988 ASTM E988ASTM E988
•
Applicable standards: JIS, IEC and DIN (ITS-90) for thermocouples and resistance-temperature detectors (RTD)
• Input sampling period: Synchronized to control period
• Burnout detection
Upscale and downscale of function, and OFF can
be specied for the standard signal of thermocouple and resistance-temperature detector (RTD).
For integrated signal input, 0.1 V or 0.4 mA or less
is judged as a burnout.
• Input bias current: 0.05 μA (for thermocouple and
resistance-temperature detector (RTD))
• Resistance-temperature detector (RTD) measured
current: About 0.16 mA
• Input resistance
1 MΩ or more for thermocouple/mV input
About 1 MΩ for voltage input
About 250 Ω for current input (with built-in shunt
resistance)
• Allowable signal source resistance
250 Ω or less for thermocouple/mV input
Effect of signal source resistance: 0.1 μV/Ω or less
2 kΩ or less for DC voltage input
Effect of signal source resistance: about
0.01%/100 Ω
• Allowable wiring resistance
Up to 150 Ω per line for resistance-temperature
detector (RTD) input (conductor resistance
between the three lines shall be equal)
Effect of wiring resistance: ±0.1°C/10 Ω
• Allowable input voltage/current
±10 V DC for thermocouple/mV/mA or resistance temperature detector (RTD) input
±20 V DC for V input
±40 mA DC for mA input
• Noise reduction ratio
40 dB or more (at 50/60 Hz) in normal mode
120 dB or more (at 50/60 Hz) in common mode
• Reference junction compensation error
±1.0°C (15 to 35°C)
±1.5°C (-10 to 5°C and 35 to 50°C)
Jun.11, 2010-00
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.