Yokogawa UT35A, UT32A Specifications

<<Contents>> <<Index>>
General
Specications
UT35A/UT32A Digital Indicating Controllers
n Overview
The UT35A/UT32A digital indicating controllers employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The UT35A/UT32A also support open networks such as Ethernet communication.
nFeatures
• A 14-segment, active (PV display color changing function) color LCD display is employed.
Two ve-digit, high-resolution displays are possible. Alphabet letters can be displayed in an easy-to-read
manner. The guide display shows parameter names.
• Easy to operate Navigation keys (SET/ENTER and Up/Down/Left/ Right arrow keys) are employed to facilitate making settings.
• 65 mm depth
The small depth enables the mounting in a thin and
small instrumented panel.
• Ladder sequence function is included as standard. This function allows for creating a simple sequence control. Dedicated LL50A Parameter Setting Software (sold separatly) allows for performing programming using a ladder language.
• Various built-in open network functions such as Eth­ernet are available. Easy connection with various vendors’ PLCs is possible.
• Quick setting function Setting only the minimum necessary parameters for operation is possible.
• Equipped with a multitude of functions Universal I/O are included as standard. PID control,
heating/cooling control, etc. are available.
[Style:S2]
UT35A UT32A
TableofNumberofInputsandOutputs
Modeland
sufxcode
(Seethe
modelcode)
UT35A
UT32A
*1: Excluding control output *2: In the case of cooling control output is analog output, it
*3: Excluding control output relays
Number
ofanalog
input
points
-×0×
-×1× 1 1 4 5
-×2× 1 1 (*2) 7 8
-×0× 1 1 2 3
-×1× 1 1 2 3
-×2× 1 1 (*2) 4 5
can not be used for transmission output.
1 1 2 3
Number
ofanalog
output
points(*1)
Number
ofcontact
input
points
Numberof
points(*3)
contact
output
nFunctionalSpecications
ControlSpecications
(1)ControlMode
Single-loop control
(
2)Controlperiod
200 ms
nControlComputationFunction
(1)Typesofcontrol
• PID control
• ON/OFF control (*4)
• Two-position two-level control (*5)
• Heating and cooling control (*5)
*4: Not selectable for Position proportional type *5: Selectable for heating and cooling control
Yokogawa Electric Corporation 2-9-32, Nakacho, Musashino-shi, Tokyo, 180-8750 Japan Tel.: 81-422-52-7179 Fax.: 81-422-52-6619
GS 05P01D31-01EN
1st Edition Nov.30, 2009 (KP)
2nd Edition Jun.11, 2010 (KP)
2
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 05P01D31-01EN
(2)ControlComputationFunction
(a) Target setting point and the number of PID param-
eter groups
Respectively, four sets of target setpoints, alarm
setpoints, and PID parameters can be set.
(b) Selecting the PID parameter group
The following PID parameter groups can be selected.
• Target setpoint number (SPNO) (The PID number can be set arbitrarily.)
• Measured input zone PID
• Target setpoint zone PID
• Reached target setpoint zone PID
(c) Auto-tuning
• Tuning results can be selected from two options, Normal or Stable.
• Tuning output limit can be set. (It cannot be used in
heating/cooling control.)
(d) “Super” function: Overshoot-suppressing function (e) “Super 2” function: Hunting-suppressing function (f) STOP preset output function (g) Input ERROR preset output function (h) MANUAL preset output function
(3)OperationModeSwitching
Operationmode
switching
AUTO/MANUAL and RUN/STOP switching REMOTE/LOCAL switching (only model with communication option)
(4)ControlParameterSettingRange
Proportional
band
Integraltime 1 to 6000 sec. or OFF (using manual reset)
Derivativetime 1 to 6000 sec. or OFF
ON/OFFcontrol hysteresis(one
ortwohysteresis
points)
Presetoutput
value
High/lowoutput
limiter
Tightshut
function
Rate-of-change
limiterofoutput
Output
deadband
0.1 to 999.9%
0.0 to 100.0% of measured input range width
-5.0 to 105.0% (however, 0 mA or less
cannot be output)
-5.0 to 105.0% Low limit setpoint < high limit setpoint
When manual control is carried out with
4 to 20 mA output, control output can be reduced to about 0 mA.
0.1 to 100.0%/sec., OFF
For heating and cooling control: -100.0 to
50.0% For position proportional control: 1.0 to
10.0%
(5)Laddercomputationperiod
Ladder computation period is the same as control period.
AlarmFunctions
• Types of Alarm
Measuredvalue
alarm Deviationalarm Rate-of-change
alarm
Setpointalarm
Outputalarm
Otheralarms
PV (measured value) high/low limit alarm Deviation high/low limit alarm Deviation high and low limits alarm Deviation within high and low limits alarm Analog input PV high/low limit alarm
Feedback input high/low limit alarm
PV rate-of-change alarm SP (setpoint) high/low limit alarm
Target SP high/low limit alarm Target SP deviation high/low limit alarm Target SP deviation high and low limits alarm Target SP deviation within high and low limits alarm
Control output high/low limit alarm Cooling control output high/low limit alarm
Heater disconnection alarm (for /HA option) Self-diagnosis alarm FAIL
• Alarm Functions
Alarmoutput
action
Numberofalarm
settings
Numberofalarm
outputpoints
Alarm stand-by action
Alarm latch (forced reset) function Alarm hysteresis Alarm ON/OFF delay timer
4
Up to 8 (differs by model code)
ContactI/OFunction
This function allows for allocating the input error condition, operation condition, alarm condition or other conditions to the contact input and contact output.
AUTO/MANUAL switching REMOTE/LOCAL switching (only model
with communication option) STOP/START switching Switching to AUTO Switching to MANUAL Switching to REMOTE (only model with
Contactinput
Contactoutput
communication option) Switching to LOCAL (only model with
communication option) AUTO-TUNING START/STOP switching
LCD backlight ON/OFF switching
Message interrupt displays 1 through 4
SP number specication PID number specication Manual preset output number specication
Alarms 1 through 4 Status output
LadderSequenceFunction
(1) NumberofI/OPoints
UT35A UT32A
Numberofdigitalinputpoints Up to 7 Up to 4
Numberofdigitaloutputpoints Up to 8 Up to 5
This is limited by the number of contact I/O signal
points. (See the model code.)
Jun.11, 2010-00
<<Contents>> <<Index>>
3
(2) Types of Command
Number of
commands
Number of basic command types
Number of appli­cation command types
13
73
Remark
Load, AND, OR, Timer, Counter, etc.
Comparison, reverse, addition/subtraction/ multiplication/division, logic operation, high/low limiter, etc.
(3) Sequence Device
Types of device Number of points
Digital I/O
Internal device
Special device Special relay (bit data) 12
Input relay 7 (max) Output relay 8 (max) M relay (bit data) 256 DAT register (data) 28 P register (parameter) 10 K register (constant)
30
Process data and process relay can be used besides the above-mentioned.
(4) Program capacity
Max Program capacity: 300 steps *
*: Available number of steps differs according to the
parameters and using command.
Communication Function
Function Method Interface Targets Max connection
Modbus/TCP
Modbus (RTU/ASCII)
PROFIBUS-DP
CC-Link
Peer to peer
Coordinated Communication
PC link
Ladder
*1: UT digital indicating controller, Signal conditioner JUXTA, Power monitor POWERCERT can be connected. *2: UT digital indication controllers can be connected.
A standard industry protocol allowing communications between the controller and devices such as PCs, PLCs, and DCSs.
Used for communication between PLCs and remote I/O, enabling high­speed data transmission.
A protocol allowing multiple controllers to send and receive data between one another. The Ladder Program is used. A protocol to coordinate the operation of two or more instruments controlling the same process. The proprietary Yokogawa protocol allowing communications to PCs, PLCs and touch panels. A protocol to communicate to PLCs.
Server Ethernet PLC and others 2 connections
Gateway
Slave RS-485
Slave RS-485 PLC and others
Modbus master
function
Slave RS-485 PLC and others
Modbus master
function
Multi-drop
Master/Slave RS-485
Slave RS-485
Ethernet
+RS-485
RS-485
RS-485
RS-485
(2 wire
only)
RS-485:
UT55A/UT52A
UT35A/UT32A (*1)
PLC and others,
UT55A/UT52A
UT35A/UT32A (*2)
UT55A/UT52A UT35A/UT32A
UT55A/UT52A/
UT35A/UT32A
UT55A/UT52A UT35A/UT32A
UT55A/UT52A
UT35A/UT32A (*2)
PC and others, UT55A/UT52A
UT35A/UT32A (*2)
Number of nodes:
(Main Controller
is included.)
Number of nodes:
42 (Remote device)
(Main Controller
is included.)
Read/Write: 4
Read only : 28
Master : 1 unit
Slave : 31 units
31 units
31 units
126
31 Units
31 Units
units
units
31units
Physical interface
Ethernet Standard : IEEE802.3 (10BASE-T, 100BASE-TX) Max segment length : 100m
Max.ConnectingCongguration:CascadeMax.4level(10BASE-T),Max.2level(100BASE-TX)
RS-485 Standard : EIA RS-485 Communication method : Two-wire harf-duplex or four-wire harf-duplex, start-stop synchoronization, and non-procedural
Baud rate : 600,1200,2400,4800,9600,19200 or 38400bps Peer to peer communication is only 19200bps
Maximum communication distance : 1200m
Terminatingresistor:220Ω(External)
PROFIBUS-DP Standard : Field bus (IEC61158) Corresponding version : DP V0 Baud rate : 9.6k, 19.2k, 45.45k, 93.75k, 187.5k, 0.5M, 1.5M, 3M, 6M, 12M
, AUTO (*3)
Communication distance : 1200m (9.6k to 93.75k) 1000m (187.5k)
400m (0.5M) 200m (1.5M)
100m (3M to 12M)
*3: AUTO automatically sets the baud rate to that of the host controller (PROFIBUS-DP master).
CC-Link Supported on version : Remote device (Ver.1.10, Ver.2.00) Baud rate : 156k, 625k, 2.5M, 5M, 10M bps Transmission distance : 1.2km (156k bps), 600m (625k bps), 200m (2.5M bps), 150m (5M bps),
100m (10M bps)
When used optical repeater : 7.6 km (156k) to 4.3 km (10M)
Communication
Data
PV, SP, OUT,
ALM etc
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
GS 05P01D31-01EN
Jun.11, 2010-00
4
All Rights Reserved. Copyright © 2009, Yokogawa Electric Corporation
<<Contents>> <<Index>>
GS 05P01D31-01EN
nHardwareSpecications
DisplaySpecications
• PV display 5-digit, 14-segment active color LCD (white/red)
Character height: 21.5 mm for UT35A and 13.0 mm for UT32A
• Data display 5-digit, 11-segment color LCD (orange)
• Bar graph display 12-segment color LCD (orange)
UniversalInputSpecications
• Number of input points: 1
• Types of input, instrument range, and measurement
accuracy (see the table below)
Typesofinput
-270.0 to 1370.0°C -450.0 to 2500.0°F ±0.1% of instrument
K
-270.0 to 1000.0°C -450.0 to 2300.0°F
-200.0 to 500.0°C -200.0 to 1000.0°F
J -200.0 to 1200.0°C -300.0 to 2300.0°F
-270.0 to 400.0°C -450.0 to 750.0°F
T
0.0 to 400.0°C -200.0 to 750.0°F
B 0.0 to 1800.0°C 32 to 3300°F
S 0.0 to 1700.0°C 32 to 3100°F R 0.0 to 1700.0°C 32 to 3100°F
N -200.0 to 1300.0°C -300.0 to 2400.0°F
E -270.0 to 1000.0°C -450.0 to 1800.0°F ±0.1% of instrument
Thermocouple
L -200.0 to 900.0°C -300.0 to 1600.0°F
-200.0 to 400.0°C -300.0 to 750.0°F
U
0.0 to 400.0°C -200.0 to 1000.0°F
W(*2) 0.0 to 2300.0°C 32 to 4200°F
Platinel
0.0 to 1390.0°C 32.0 to 2500.0°F
2
PR20-40 0.0 to 1900.0°C 32 to 3400°F
W97
Re3-W75
0.0 to 2000.0°C 32 to 3600°F
Re25
-200.0 to 500.0°C -300.0 to 1000.0°F
JPt100
-150.00 to 150.00°C -200.0 to 300.0°F
-200.0 to 850.0°C -300.0 to 1560.0°F
(RTD)3-wire
Resistance-temperature
detector
Standard
signal
DCvoltage
DCcurrent 0.00 to 20.00 mA -
-200.0 to 500.0°C -300.0 to 1000.0°F
Pt100
-150.00 to 150.00°C -200.0 to 300.0°F
0.400 to 2.0000 V -
1.000 to 5.000 V -
4.00 to 20.00 mA -
0.000 to 2.000 V -
0.00 to 10.00 V -
-10.00 to 20.00 mV -
Instrumentrange
°C °F
Accuracy
range ±1 digit for 0°C or more ±0.2% of instrument range ±1 digit for less than 0°C However, ±2% of instrument range ±1 digit for less than
-200°C of thermocouple K ±1% of instrument range ±1 digit for less than -200°C of thermo­couple T ±0.15% of instrument range ±1 digit for 400°C or more ±5% of instrument range ±1 digit for less than 400°C ±0.15% of instrument range ±1 digit ±0.1% of instrument range ±1 digit ±0.25% of instrument range ±1 digit for less than 0°C
range ±1 digit for 0°C or more ±0.2% of instrument range ±1 digit for less than 0°C However, ±1.5% of instrument range ±1 digit for less than -200.0°C of thermocouple E ±0.2% of instrument range ±1 digit ±0.1% of instrument range ±1 digit ±0.5% of instrument range ±1 digit for 800°C or more Accuracy not guaran­teed for less than 800°C
±0.2% of instrument range ±1 digit
±0.1%
of instrument range ±1 digit ±0.1% of instrument range ±1 digit ±0.1% range ±1 digit
±0.1% of instrument range ±1 digit
±0.1% of instrument range ±1 digit
(*1)
of instrument
(*1)
The accuracy is that in the standard operating condi­tions: 23 ±2°C, 55 ±10%RH, and power frequency at 50/60 Hz.
*1:
±0.3°C and ±1 digit in the range between 0 and 100°C ±0.5°C ±1 digit in the range between -100 and 200°C
*2:
W-5% Re/W-26% Re (Hoskins Mfg.Co.), ASTM E988 ASTM E988ASTM E988
Applicable standards: JIS, IEC and DIN (ITS-90) for ther­mocouples and resistance-temperature detectors (RTD)
• Input sampling period: Synchronized to control period
• Burnout detection Upscale and downscale of function, and OFF can be specied for the standard signal of thermocou­ple and resistance-temperature detector (RTD). For integrated signal input, 0.1 V or 0.4 mA or less
is judged as a burnout.
• Input bias current: 0.05 μA (for thermocouple and
resistance-temperature detector (RTD))
• Resistance-temperature detector (RTD) measured
current: About 0.16 mA
• Input resistance
1 MΩ or more for thermocouple/mV input About 1 MΩ for voltage input
About 250 Ω for current input (with built-in shunt
resistance)
• Allowable signal source resistance
250 Ω or less for thermocouple/mV input
Effect of signal source resistance: 0.1 μV/Ω or less 2 kΩ or less for DC voltage input Effect of signal source resistance: about
0.01%/100 Ω
• Allowable wiring resistance Up to 150 Ω per line for resistance-temperature
detector (RTD) input (conductor resistance
between the three lines shall be equal)
Effect of wiring resistance: ±0.1°C/10 Ω
• Allowable input voltage/current
±10 V DC for thermocouple/mV/mA or resistance­ temperature detector (RTD) input ±20 V DC for V input ±40 mA DC for mA input
• Noise reduction ratio 40 dB or more (at 50/60 Hz) in normal mode 120 dB or more (at 50/60 Hz) in common mode
• Reference junction compensation error ±1.0°C (15 to 35°C) ±1.5°C (-10 to 5°C and 35 to 50°C)
Jun.11, 2010-00