Model PR300
Power and Energy Meter
Communication Interface
(RS-485 and Ethernet Communications)
IM 77C01E01-10E
IM 77C01E01-10E
4th Edition
<Toc> <Ind> <Rev>
Introduction
This user's manual describes the communication functions of the PR300 power and energy
meter and contains information on how to create communication programs.
Hereafter, the PR300 power and energy meter is simply referred to as the PR300.
Read the manual carefully to understand the communication functions of the PR300 .
The PR300 has the following communication protocols.
●PC link communication protocol
●Modbus /RTU and Modbus/ASCII communication protocols
●Modbus/TCP communication protocol (for the PR300 with Ethernet communication
function)
●PR201 original communication protocol
You are required to have background knowledge of the communication specifications of
higher-level devices, their communication hardware, language used for creating communication programs, and so on.
i
■ Intended Readers
This manual is intended for people familiar with the functions of the PR300, control engineers and personnel in charge of maintaining instrumentation and control equipment.
■ Related Documents
The following user's manuals all relate to the communication functions of the PR300. Read
them as necessary.
● Model PR300 Power and Energy Meter User's Manual (electronic manual)
Document number: IM 77C01E01-01E
● Model PR300 Power and Energy Meter Startup Manual <Installation>
Document number: IM 77C01E01-02E
● Model PR300 Power and Energy Meter Startup Manual <Initial Setup Operations>
Document number: IM 77C01E01-03E
These manuals provide information about the procedure of installation, wiring and operation.
■ Trademark
(1)All the brands or names of Yokogawa Electric's products used in this manual are
either trademarks or registerd trademarks of Yokogawa Electric Corporation.
(2)Ethernet is a registered trademark of XEROX Corporation in the United States.
(3)Company and product names that appear in this manual are trademarks or registered
Draws attention to information that is essential for understanding the operation and/or
features of the product.
TIP
Gives additional information to complement the present topic.
See Also
ii
Gives reference locations for further information on the topic.
● Symbols Used in Figures and Tables
[NOTE]
Draws attention to information that is essential for understanding the features of the
product.
[TIP]
Gives additional information to complement the present topic.
[See Also]
Gives reference locations for further information on the topic.
■ Description of Displays
(1)Some of the representations of product displays shown in this manual may be exag-
gerated, simplified, or partially omitted for reasons of convenience when explaining
them.
(2)Figures and illustrations representing the PR300's displays may differ from the real
displays in regard to the position and/or indicated characters (upper-case or lowercase, for example), the extent of difference does not impair a correct understanding of
the functions and the proper operations and monitoring of the system.
IM 77C01E01-10E
<Toc> <Ind> <Rev>
Notices
■ Regarding This User's Manual
(1)This manual should be passed on to the end user. Keep the manual in a safe place.
(2)Read this manual carefully to gain a thorough understanding of how to operate this
product before you start using it.
(3)This manual is intended to describe the functions of this product. Yokogawa Electric
Corporation (hereinafter simply referred to as Yokogawa) does not guarantee that
these functions are suited to the particular purpose of the user.
(4)Under absolutely no circumstance may the contents of this manual, in part or in whole,
be transcribed or copied without permission.
(5)The contents of this manual are subject to change without prior notice.
(6)Every effort has been made to ensure accuracy in the preparation of this manual.
Should any errors or omissions come to your attention however, please contact your
nearest Yokogawa representative or our sales office.
(7)The document concerning TCP/IP software has been created by Yokogawa based on
the BSD Networking Software, Release 1 that has been licensed from the University
of California.
iii
■ Regarding Protection, Safety, and Prohibition Against Unauthorized
Modification
(1)In order to protect the product and the system controlled by it against damage and
ensure its safe use, be certain to strictly adhere to all of the instructions and precautions relating to safety contained in this document. Yokogawa does not guarantee
safety if products are not handled according to these instructions.
(2)The following safety symbols are used on the product and/or in this manual.
● Symbols Used on the Product and in This Manual
This symbol on the product indicates that the operator must refer to an explanation in
the user's manual in order to avoid the risk of injury or death of personnel or damage
to the instrument. The manual describes how the operator should exercise special
care to avoid electric shock or other dangers that may result in injury or loss of life.
Protective Grounding Terminal
This symbol indicates that the terminal must be connected to ground prior to operating
the equipment.
IM 77C01E01-10E
<Toc> <Ind> <Rev>
■ Force Majeure
(1)Yokogawa does not make any warranties regarding the product except those men-
tioned in the WARRANTY that is provided separately.
(2)Yokogawa assumes no liability to any party for any loss or damage, direct or indirect,
caused by the use or any unpredictable defect of the product.
(3)Be sure to use the spare parts approved by Yokogawa when replacing parts or
consumables.
(4)Modification of the product is strictly prohibited.
(5)Reverse engineering such as the disassembly or decompilation of software is strictly
prohibited.
(6)No portion of the software supplied by Yokogawa may be transferred, exchanged,
leased, or sublet for use by any third party without the prior permission of Yokogawa.
iv
IM 77C01E01-10E
<Int> <Ind> <Rev>
Model PR300 Power and Energy Meter
Communication Interface
Toc-1
(RS-485 and Ethernet Communications)
IM 77C01E01-10E 4th Edition
CONTENTS
Introduction........................................................................................................... i
This chapter describes how to set up the PR300, which is equipped with RS-485
communication as a standard feature.
When using an Ethernet-equipped model, either RS-485 or Ethernet can be selected
by parameter setting for communications.
For details of use of RS-485 communication, see subsection 2.1.1 “Procedure for
RS-485 Communication.”
For details of use of the Ethernet communication, see subsection 2.1.2 “Procedure
for Ethernet Communication.”
For details of use of the Ethernet-serial gateway function, see subsection 2.1.3
“Procedure for Ethernet-Serial Gateway Function.”
2.1Setup Procedure
Set up the communication functions on the PR300 as follows:
2-1
WARNING
To avoid an electric shock, be sure to turn off the power supply source to the equipment
involved before you start wiring.
Note: Create communication programs referring to the user’s manual for communications of each higher-level device.
Higher-level devices : PCs, PLCs (sequencers), and others.
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
2.1.1Procedure for RS-485 Communication
(Example)
Higher-level device
Maximum communication distance: 1200 m
Maximum number of slave stations to be connected: 31
2-2
Station number 01
(arbitrary)
Communication parameters setting for PR300
1
Set up the communication function using
the front panel keys.
Connect a higher-level device with PR300
2
Create communication programs for the
3
higher-level device to perform
communication
Station number 02
(arbitrary)
Subsection 2.2.1 “Conditions for RS-485
Communication”
Subsection 2.3.1
“Wiring for RS-485 Communication”
Chapter 3
“Procedures for Setting PR300 Functions”
For communication protocol, see
Chapter 4
“PC Link Communication Protocol”
Chapter 5
Modbus/RTU and ASCII Communication Protocols
“
Chapter 8
“PR201 Original Communication Protocol”
For data storage location, see
Chapter 7
“Functions and Usage of D Registers”
See
See
See
Station number 10
(arbitrary)
Station number 20
(arbitrary)
”
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
2.1.2Procedure for Ethernet Communication
(Example)
2-3
Higher-level device
IP address [192.168.1.1]
HUB
LAN
connection
Station number 01 (fixed)
IP address [192.168.1.2]
(arbitrary)
Communication parameters setting for PR300
1
Set up the communication function using
(arbitrary)
Ethernet
Station number 01 (fixed)
IP address [192.168.1.3]
(arbitrary)
the front panel keys.
See
Subsection 2.2.2 “Conditions for Ethernet
Communication”
Connect a higher-level device with PR300
2
See
Subsection 2.3.2
“Wiring for Ethernet Communication”
Maximum distance between hub and module: 100 m
Maximum number of hubs connectable in cascade configuration:
4 levels for 10BASE-T
2 levels for 100BASE-TX
Station number 01 (fixed)
IP address [192.168.1.4]
(arbitrary)
Station number 01 (fixed)
IP address [192.168.1.5]
(arbitrary)
Create communication programs for the
3
higher-level device to perform
communication
See
Chapter 3
“Procedures for Setting PR300 Functions”
For communication protocol, see
Chapter 6
“Modbus/TCP Communication Protocol”
For data storage location, see
Chapter 7
“Functions and Usage of D Registers”
Note: It is recommended to use the Ethernet network as a dedicated one for the
PR300.
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
2.1.3Procedure for Ethernet-Serial Gateway Function
(Example)
Higher-level device
IP address [192.168.1.1] (arbitrary)
Ethernet
2-4
PR300
communication function)
(with Ethernet
Communication parameters setting for PR300
1
Set up the communication function using
the front panel keys.
Connect a higher-level device with PR300
2
RS-485
Station number 02
(arbitrary)
Subsection 2.2.2
“Conditions for Ethernet Communication”
Subsection 2.2.3
“
Subsection 2.3.2
“Wiring for Ethernet Communication”
Station number 01 (fixed)
IP address [192.168.1.2] (arbitrary)
Station number 03
(arbitrary)
See
Conditions for Ethernet-Serial Gateway Function
See
Station number 20
(arbitrary)
”
Connect a lower-level device with PR300
3
See
Subsection 2.3.3
“Wiring for RS-485 Communication for
Ethernet-Serial Gateway Function”
Create communication programs for the
4
higher-level device to perform
communication
Note: It is recommended to use the Ethernet network as a dedicated one for the PR300.
See
Chapter 3
“Procedures for Setting PR300 Functions”
For communication protocol, see
Chapter 6
“Modbus/TCP Communication Protocol”
For data storage location, see
Chapter 7
“Functions and Usage of D Registers”
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
●
VJET Ethernet/RS-485 converter as an Ethernet-serial gateway function
(Example)
Higher-level device
IP address [192.168.1.1] (arbitrary)
Ethernet
2-5
Ethernet/RS-485 converter
VJET*
RS-485
Station number 02 (arbitrary)Station number 03 (arbitrary)
* The VJET is Yokogawa’s converter. For details of use of the VJET, refer to its user’s manual.
Note: It is recommended to use the Ethernet network as a dedicated one for the PR300.
The communication conditions of any slave PR300 must conform to those of the VJET at
a higher level.
Station number 01 (fixed)
IP address [192.168.1.2] (arbitrary)
Station number 20 (arbitrary)
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
2.2Setting Communication Conditions
This section describes the setting parameters for using the communication functions, and the setting ranges. For details of setting method, refer to the PR300
Power and Energy Meter User’s Manual (electronic manual).
2.2.1Conditions for RS-485 Communication
This subsection describes the setting parameters for using the RS-485 communication
function, and the setting ranges.
Table 2.1 Parameters to be Set for Communication Functions
Parameter Name
Menu
Parameter Symbol
Setting Range
2-6
Initial
Value
Station number
Protocol
Baud rate
3
Parity*
Stop bit*
3
(RS-485
communication)
(ST-NO)
(COMM)
(B-RT)
(PRI)
(STP)
01 to 99 (01 to 31 recommended)
PC link without checksum
PC link with checksum
Modbus/ASCII
Modbus/RTU
Modbus/TCP*
PR201 original
1
(PCLK1)
(PCLK2)
(M ASC)
(M RTU)
(M TCP)
(PR201)
2400 bps
9600 bps
19200 bps
None
Even
Odd
(NONE)
(EVEN)
(ODD)
1
2
01
PCLK2
9600
NONE
1
Data length*2 *
*1:Modbus/TCP can be selected for the PR300 with Ethernet communication function only.
*2:When Modbus /RTU is selected for the protocol, select 8 for the data length. If 7 is selected for the data length,
communication is not possible.
*3:When PR201 original is selected for the protocol, select NONE for the parity, 1 for the stop bit and 8 for the data length.
3
(DLN)
7
8
8
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
● Protocol (COMM)
Set the communication protocol identical to that of the higher-level device to be connected.
● Station number (ST-NO)
Set the station number of the PR300 itself. A station number of 01 to 99 may be assigned
in any order. However, the maximum number of PR300 to be connected to a single communication port is 31.
When connecting two or more PR300 to a single communication port, set a different station
number to each.
Example of connecting a higher-level device with four PR300 having station numbers 01,
05, 10, and 20
(Example)
Higher-level device
2-7
Maximum communication distance: 1200 m
Maximum number of slave sations to be connected: 31
Station number 01
(arbitrary)
Station number 05
(arbitrary)
Station number 10
(arbitrary)
Station number 20
(arbitrary)
● Baud rate (B-RT)
Set the baud rate identical to that of the higher-level device to be connected. (Otherwise,
proper communication cannot be achieved.)
● Parity (PRI)
Set the handling of parity to be carried out when data is sent or received. Set the parity bit
state identical to that of the higher-level device to be connected.
* When PR201 original is selected for the protocol, select NONE for the parity.
● Stop bit (STP)
Set the stop bit identical to that of the higher-level device to be connected.
* When PR201 original is selected for the protocol, select 1 for the stop bit.
● Data length (DLN)
Set the same data length as for the upper device that is to be connected.
* When Modbus/RTU is selected for the protocol, select 8 for the data length.
* When PR201 original is selected for the protocol, select 8 for the data length.
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
2.2.2Conditions for Ethernet Communication
This subsection describes the setting parameters for using the Ethernet communication
function, and the setting ranges.
Table 2.2 Parameters to be Set for Communication Functions
Parameter Name
Menu
Parameter Symbol
Setting Range
2-8
Initial
Value
Protocol
IP address-1
IP address-2
IP address-3
IP address-4
Subnet mask-1
Subnet mask-2
(RS-485
Communication)
(COMM)
(IP-1)
(IP-2)
(IP-3)
(IP-4)
(SM-1)
(SM-2)
PC link without checksum
PC link with checksum
Modbus/ASCII
Modbus/RTU
Modbus/TCP*
1
PR201 original
0 to 255
0 to 255
0 to 255
0 to 255
0 to 255
0 to 255
(PCLK1)
(PCLK2)
(M ASC)
(M RTU)
(M TCP)
(PR201)
PCLK2
192
168
1
1
255
255
Subnet mask-3
(SM-3)
(Ethernet
Subnet mask-4
Communication)
2
*
(SM-4)
Default gateway-1
(DG-1)
Default gateway-2
(DG-2)
Default gateway-3
(DG-3)
Default gateway-4
(DG-4)
Port number
(PORT)
Ethernet setting switch
(E-SW)
*1:Modbus/TCP can be selected for the PR300 with Ethernet communication function only.
*2:Ethernet communication menu is displayed when Modbus/TCP is selected for the protocol.
0 to 255
0 to 255
0 to 255
0 to 255
0 to 255
0 to 255
502, 1024 to 65535
OFF, ON
255
0
0
0
0
0
502
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
● Protocol (COMM)
Set the protocol to Modbus/TCP.
● IP address-1 to 4 (IP-n) [n: integers from 1 to 4]
Set the IP address for the PR300 by the following format.
2-9
0 to 255
IP addressIP-1
0 to 255
IP-2
0 to 255
IP-3
0 to 255
IP-4
● Subnet mask-1 to 4 (SM-n) [n: integers from 1 to 4]
Set the subnet mask for the PR300 by the following format.
0 to 255
Subnet MaskSM-1
0 to 255
SM-2
0 to 255
SM-3
0 to 255
SM-4
● Default gateway-1 to 4 (DG-n) [n: integers from 1 to 4]
Set the default gateway for the PR300 by the following format.
0 to 255
Default GatewayDG-1
0 to 255
DG-2
0 to 255
DG-3
0 to 255
DG-4
NOTE
Before performing setup of IP address, subnet mask, and default gateway, consult the
administrator for the network to which the PR300 is to be connected.
● Port number (PORT)
Set the port number for the PR300.
NOTE
To activate the settings of IP address, subnet mask, default gateway, and port number, set
the Ethernet setting switch to ‘ON’ after setting them.
● Ethernet setting swtich (E-SW)
This switch activates the Ethernet communication parameters settings. Setting this parameter to ON activates the settings of IP address, subnet mask, default gateway, and port
number.
This parameter automatically reverts to OFF in about 20 seconds after being set to ON.
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
2.2.3Conditions for Ethernet-Serial Gateway Function
The Ethernet-serial gateway function is a function that reads/writes data from/to other
devices equipped with RS-485 serial communication function using the Modbus/TCP
protocol via the PR300.
With this function, the higher-level device can access the devices connected to the RS-485
serial communication line in the same way as to access the devices connected to Ethernet.
(Example)
Higher-level device
2-10
PR300
communication function)
Device with RS-485 serial
communication function
Power Monitor of POWERCERT series
Digital indicating controller of
GREEN series
Signal conditioner of JUXTA series
(with Ethernet
Ethernet
RS-485
Station number 02
(arbitrary)
10BASE-T, 100BASE-TX
Station number 01 (fixed)
Station number 03
(arbitrary)
Station number 04
(arbitrary)
The PR300 operates as a gateway that changes the Modbus/TCP protocol received via
network to the Modbus/RTU protocol for the serial devices connected to the RS-485
communication interface. Therefore, the devices supporting the Modbus/RTU protocol are
required for the devices to be connected.
NOTE
• If the Ethernet-serial gateway function is used, set a station number other than 01 for
the RS-485 communication devices which are slaves of the PR300 connected to
Ethernet.
• If the Ethernet communication function is used, the RS-485 communication interface
is used specifically for the Ethernet-serial gateway function. Therefore, it is not possible for a higher-level device such as a PC to access the PR300 via the RS-485
communication interface.
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
● Setting for PR300 to perform the Ethernet-serial gateway function
To use the Ethernet-serial gateway function, set the parameters of subsection 2.2.2, “Conditions for Ethernet Communication” and set a parity (PRI) in Table 2.3.
When the protocol is set to Modbus/TCP, the parameters of RS-485 other than the parity
are fixed and unchangeable.
Table 2.3 Parameters of PR300 to Perform the Ethernet-Serial Gateway Function
Parameter Name
MenuSetting Range
Parameter Symbol
2-11
Initial
Value
Station number
Baud rate
Parity
Stop bit
Data length
(RS-485
communication)
(ST-NO)
(B-RT)
(PRI)
(STP)
(DLN)
01 (fixed)
9600 bps (fixed)
None
Even
Odd
1 (fixed)
8 (fixed)
NONE
EVEN
ODD
● Slave PR300
The station number of any slave PR300 (device for RS-485 communication) must be a
different number other than 01.
The communication conditions for any slave PR300 (device for RS-485 communication)
other than the station number must conform to those in Table 2.3.
Table 2.4 Parameters of Slave PR300
Parameter Name
Station number
Baud rate
Parity
Stop bit
MenuSetting Range
(RS-485
communication)
Parameter Symbol
(ST-NO)
(B-RT)
(PRI)
(STP)
02 to 99
2400 bps
9600 bps
19200 bps
None
Even
Odd
1
2
NONE
EVEN
ODD
01
9600
NONE
1
8
Initial
Value
01
9600
NONE
1
Data length
(DLN)
8
8
When using the VJET Ethernet/RS-485 converter as an Ethernet-serial gateway function,
the communication conditions of any slave PR300 must conform to those of the VJET at a
higher level. The initial value of the VJET parity is EVEN.
IM 77C01E01-10E
7
<Toc> <Ind><2. Setup>
2.3Wiring for Communication
Connect a higher-level device with the PR300 for using the communication functions. The wiring procedures and precautionary notes are as follows.
2.3.1Wiring for RS-485 Communication
For a common PC, the RS-485 interface is not directly connectable. Use a ML2 RS232C/
RS485 converter for wiring.
WARNING
To avoid an electric shock, be sure to turn off the power supply source to the equipment
involved before you start wiring.
Use crimp-on terminals at cable ends.
Before you start wiring, read the user’s manual of each device.
PR300
(with RS-485
communication function)
17
Aⴚ
18
Bⴙ
19
PC
(RS232C/RS485 converter)
Terminator
120Ω 1/4W
3
4
Aⴚ
Bⴙ
PR300
(with RS-485
communication function)
18
19
2-12
Terminator (built-in)
120Ω 1/4W
Wthen terminating on
wiring, short-circuit
terminals 17 and 18 .
SG
RS-232C
straight cable
SG
5
6
JIS Class D (3) grounding
(grounding resistance
of 100Ω or less)
20
Communication cableCommunication cable
JIS Class D (3) grounding
(grounding resistance
of 100Ω or less)
Note: Use UL Listed RS-232C/RS-485 converter if the converter has AC/DC power supply input; this is
optional for converters supplied by a Limited Power Source with input voltages less than 30 V AC or
60 V DC and which are separated from mains by double or reinforced insulation.
Communication cable: Shielded twisted pair cable (AWG24-eqivalent size)
Recommended terminals: See the PR300 Power and Energy Meter User’s Manual (electronic manual).
20
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
2.3.2Wiring for Ethernet Communication
To use the Ethernet communication function, connect a higher-level device with the PR300
with Ethernet communication function using 10BASE-T/100BASE-TX. 10BASE-T/
100BASE-TX are Ethernet connection methods using twisted pair cables. The transmission
rates are 10 Mbps/100 Mbps. In 10BASE-T/100BASE-TX networks, higher-level devices
such as a PC are connected in a star pattern through a hub.
WARNING
To avoid an electric shock, be sure to turn off the power supply source to the equipment
involved before you start wiring.
Use hubs and twisted pair cables that conforms to the Ethernet specifications. The maximum number of hubs connectable in cascade configuration is 4 for 10ABSE-T and 2 for
100BASE-TX. The maximum allowable length of twisted pair cables is 100 meters.
Read the user’s manual of each device carefully before wiring.
* Devices that can be connected to Ethernet
PC
2-13
PR300 with
Ethernet
communication
function
HUB
Data transmission
and reception
Ethernet
Ethernet Port of PR300
The PR300 can detect 10BASE-T or
100BASE-TX automatically. The LEDs of
Ethernet port show its status.
Link LED (upper side)
Color
Off
Amber
Green
Activity LED (lower side)
Color
Off
Amber
Green
Meaning
No Link
10 Mbps
100 Mbps
Meaning
No Activity
Half-duplex
Full-duplex
IM 77C01E01-10E
<Toc> <Ind><2. Setup>
2.3.3Wiring for RS-485 Communication for Ethernet-Serial
Gateway Function
To use the Ethernet-serial gateway function, connect other RS-485 serial communication
device to the RS-485 communication terminals .
WARNING
To avoid an electric shock, be sure to turn off the power supply source to the equipment
involved before you start wiring.
The figure below shows the example of wiring connection for the PR300 with Ethernet
communication function. If other devices are used for connection, the names of communication terminals and others may be different from those mentioned in the figure.
Read the user’s manual of each device carefully before wiring.
PC
2-14
(with Ethernet
communication function)
Terminator (built-in)
120Ω 1/4W
Wthen terminating on
wiring, short-circuit
terminals 17 and 18 .
Ethernet
PR300
PR300
(with RS-485
1717
Aⴚ
18
Bⴙ
19
SG
Communication
cable
communication function)
18
19
2020
JIS Class D (3) grounding
(grounding resistance
of 100Ω or less)
Communication
cable
PR300
(with RS-485
communication function)
Aⴚ
Bⴙ
SG
Terminator (built-in)
18
19
20
120Ω 1/4W
Wthen terminating on
wiring, short-circuit
terminals 17 and 18 .
IM 77C01E01-10E
<Toc> <Ind><3. Procedures for Setting PR300 Functions>
3-1
3.Procedures for Setting PR300 Functions
To set the functions of the PR300, use the protocols described in Chapter 4, “PC
Link Communication Protocol,” Chapter 5, “Modobus/RTU and ASCII Communication Protocols,” or Chapter 6, “Modbus/TCP Communication Protocol” according to
the instructions in this chapter.
For details of each function, refer to the PR300 Power and Energy Meter User’s
Manual (electronic manual).
For how to read the tables in this chapter, refer to Chapter 7, “Functions and Usage
of D Registers.”
The PR300 offers registers for floating-point data. To perform settings via communication from higher-level device, floating-point data is displayed by IEEE754 (single
precision).
NOTE
•The PR300 has data (D register) the unit of which is two words. When 2-word data
need to be written or read, writing or reading operations must be performed for the 2word data at the same time.
•Even if data written to the D register is out of the effective range, a normal response is
returned. The part of the written data within the effective range becomes effective on
the PR300 when the equivalent setting change status is written for that data.
IM 77C01E01-10E
<Toc> <Ind><3. Procedures for Setting PR300 Functions>
3.1Basic Setting
3.1.1Setting of VT Ratio
[Procedure]
(1)Write a VT ratio to the two D registers in the table below. The data type is 4-byte
floating point.
(2)After writing that value, write 1 to the setup change status register, D0207.
3-2
D Register
D0201
D0202
D0207
Initial value of VT ratio: 1 (4-byte floating-point data: 3F800000)
Reference No.
40201
40202
40207
H No.
00C8
00C9
00CE
VT ratio (float, lower 2 bytes)
VT ratio (float, upper 2 bytes)
Setup change status
(D0201 to D0206 are validated)
Description
Effective Range
1 to 6000
If other than 1: Invalid
If 1: Writing is executed
[Example]
To set the VT ratio to 10:
For station number 01, use PC link communication (without checksum) and the random
write command as shown below:
If 10 is converted into a 4-byte floating-point value, the value is 4120 0000.
•When changing the VT ratio, the integrated values of active energy, reactive energy,
apparent energy, optional active energy, and regenerative energy will return to “0.”
The values of the demand alarm point and the scaling of analog output will also be
initialized.
•Set the VT and CT ratios so that [secondary rated power] × [VT ratio] × [CT ratio] is
smaller than 10 GW. When this value is 10 GW or greater, writing to D registers will be
invalid (no error is output).
IM 77C01E01-10E
<Toc> <Ind><3. Procedures for Setting PR300 Functions>
3.1.2Setting of CT Ratio
[Procedure]
(1)Write a CT ratio to the two D registers in the table below. The data type is 4-byte
floating point.
(2)After writing that value, write 1 to the setup change status register, D0207.
3-3
D Register
D0203
D0204
D0207
Initial value of CT ratio: 1 (4-byte floating-point data: 3F800000)
Reference No.
40203
40204
40207
H No.
00CA
00CB
00CE
CT ratio (float, lower 2 bytes)
CT ratio (float, upper 2 bytes)
Setup change status
(D0201 to D0206 are validated)
Description
Effective Range
0.05 to 32000
If other than 1: Invalid
If 1: Writing is executed
[Example]
To set the CT ratio to 10.0:
For station number 01, use PC link communication (without checksum) and the random
write command as shown below:
If 10.0 is converted into a 4-byte floating-point value, the value is 4120 0000.
•When changing the CT ratio, the integrated values of active energy, reactive energy,
apparent energy, optional active energy, and regenerative energy will return to “0.”
The values of the demand alarm point and the scaling of analog output will also be
initialized.
•Set the VT and CT ratios so that [secondary rated power] × [VT ratio] × [CT ratio] is
smaller than 10 GW. When this value is 10 GW or greater, writing to D registers will be
invalid (no error is output).
IM 77C01E01-10E
<Toc> <Ind><3. Procedures for Setting PR300 Functions>
3.1.3Setting of Integrated Low-cut Power
[Procedure]
(1)Write an integrated low-cut power value to the two D registers in the table below. The
data type is 4-byte floating point.
(2)After writing that value, write 1 to the setup change status register, D0207.
3-4
D Register
D0205
D0206
D0207
Initial value of integrated low-cut power: 0.05% (4-byte floating-point data: 3D4CCCCD)
Reference No.
40205
40206
40207
H No.
00CC
00CD
00CE
Description
Integrated low-cut power
(float, lower 2 bytes)
Integrated low-cut power
(float, upper 2 bytes)
Setup change status
(D0201 to D0206 are validated)
Effective Range
0.05 to 20.00
Unit: %
If other than 1: Invalid
If 1: Writing is executed
[Example]
To set the integrated low-cut power value to 10.0%:
For station number 01, use PC link communication (without checksum) and the random
write command as shown below:
If 10.0 is converted into a 4-byte floating-point value, the value is 4120 0000.
<Toc> <Ind><3. Procedures for Setting PR300 Functions>
3.2Setting Pulse Output
3.2.1Selection of Measurement Item for Pulse Output
[Procedure]
(1)Write a measurement item for pulse output value to the D register in the table below.
The data type is integer.
(2)After writing that value, write 1 to the pulse output writing status register, D0211.
3-5
D Register
D0208
D0211
Initial value of measurement item for pulse output: 0 (active energy)
Reference No.
40208
40211
H No.
00CF
00D2
Description
Measurement item for
pulse output
Pulse output writing status
(D0208, D0209, and D0210
are validated)
Effective Range
0: Active energy
1: Regenerative energy
2: LEAD reactive energy
3: LAG reactive energy
4: Apparent energy
If other than 1: Invalid
If 1: Writing is executed
[Example]
To set the measurement item for pulse output to 1 (LEAD reactive energy):
For station number 01, use PC link communication (without checksum) and the random
•A measurement item for pulse output value can be set for the PR300 with pulse
output.
•When the PR300 is the three-phase four-wire system (2.5 element), the following
measurement items can be measured only when the current is in a state of equilibrium:
“2: LEAD reactive energy”, “3: LAG reactive energy” and “4: Apparent energy.”
IM 77C01E01-10E
<Toc> <Ind><3. Procedures for Setting PR300 Functions>
3.2.2Pulse Unit
[Procedure]
(1)Write a pulse unit value to the D register in the table below. The data type is integer.
(2)After writing that value, write 1 to the pulse output writing status register, D0211.
3-6
D Register
D0209
D0211
Initial value of pulse unit: 10 (1000 Wh/pulse)
Reference No.
40209
40211
H No.
00D0
00D2
Description
Pulse unit
Pulse output writing status
(D0208, D0209, and D0210
are validated)
Effective Range
1 to 50,000
Unit: 100 Wh/pulse
If other than 1: Invalid
If 1: Writing is executed
[Example]
To set the pulse unit to 100 Wh/pulse, write “0001.”
For station number 01, use PC link communication (without checksum) and the random