YOKOGAWA PR201 User Manual

Page 1
User’ s Manual
IM 77C01C01-01E
Model PR201 Power Monitor
IM 77C01C01-01E
1st Edition
Page 2
Blank Page
Page 3
1
IM 77C01C01-01E 1st Edition : March 5.2001-00
How to Install
NOTE
(1) To install the product, select a location where:
• no one may accidentally touch the terminals,
• mechanical vibrations are minimal,
• corrosive gas is minimal,
• Ambient temperature: 0 to 50°C; Ambient humidity: 50 to 90%RH And the fluctuation is minimal,
• no direct radiant heat is present,
• no magnetic disturbances are caused,
• no wind blows against the terminal board (reference junction compensation ele­ment),
• no water is splashed,
• no flammable materials are around,
(2) Make sure to connect the grounding. (3) Turn off the product before installation and wiring. (4) Use the power supply within specifications. (5) Observe the following instructions for correct installation:
Recommended panel thickness is 1 to 10mm. Install the product horizontally . Install the product using attached fixture from the backside of the product. Turn the screw only up to 180° after the screw touches the mounting panel to prevent the case deformation by tightening the screw excessively .
(6) Observe the following instructions for correct wiring:
M3 screw terminal connection (output, communication, optional integrated control signal) M4 screw terminal connection (input, power supply) Applicable wire size for input signal and power supply is 1.25mm
2
or more of cross
sectional area.
Page 4
2
IM 77C01C01-01E 1st Edition : March 5.2001-00
Model and Suffix Codes
PR201-䊐䊐䊐䊐䊐-20
Model Phase & Wire Type
1: 1-phase 2-wire system 2: 1-phase 3-wire system (Note 1) 3: 3-phase 3-wire system 4: 3-phase 4-wire system
Output Function
0: None 1: Analog output 2: Integrated pulse output
Communication Output Function
0: None 1: RS-485 Communication Output 2: LON Communication Output
Optional Function
0: None 1: Power Factor Measuring Function 2: Current 2 Measuring Function (Note 5)
Power Supply
2: 85 to 264V AC
Rated Input Voltage / Current
1: 110V/1A (Note 2) A: 64V (110V/√3) /1A (Note 4) 2: 110V/5A (Note 2) B: 64V (110V/√3) /5A (Note 4) 3: 220V/1A (Note 1) C: 127V (220V/√3) /1A (Note 4) 4: 220V/5A (Note 1) D: 127V (220V/√3) /5A (Note 4) 5: 440V/1A (Note 3) E: 277V (480V/√3) /1A (Note 4) 6: 440V/5A (Note 3) F: 277V (480V/√3) /5A (Note 4)
(Note 1) Input specs. of 1-phase 3-wire system can only select rated input 3 and 4. Input voltage is 200VAC (100V+100V). (Note 2) Rated input 1, 2 (110V) can also be used at 120V input. (Note 3) Rated input 5, 6 (440V) is the specs. only for 1-phase 2-wire system and 3-phase 3-wire system. (Note 4) Rated input A to F is the specs. for only 3-phase 4-wire system. Rated input voltage indicates phase voltage.
A, B: 64V , C, D: 127V, E,F: 227V indicate 110V/3, 220V/3, 480V/3 respectively. In case of 440V/3 input, it can be used at E, F: 227V of rated input.
(Note 5) Specify this option when the previous style UZ005(S2.0) with option “Current 2 measuring Function” is required.
Current measuring object of current 2 measuring function:
1-phase 3-wire system : I2current r.m.s. value 3-phase 3-wire and 3-phase 4-wire system : I3 current r.m.s. value
NOTE
Before using the product, check that its model and suffix codes as you ordered.
LIST OF COMBINATION OF PR201 RATED INPUT
: Available :Not available *200V AC (100V+100V)
Phase & Wire System
1-phase 2-wire
Rated InputCode
1-phase 3-wire
3-phase 3-wire
3-phase 4-wire
110V/1A 110V/5A 220V/1A 220V/5A 440V/1A 440V/5A
64V/1A
64V/5A 127V/1A 127V/5A 277V/1A 277V/5A
1 2 3 4 5 6 A B C D E F
**
Page 5
3
IM 77C01C01-01E 1st Edition : March 5.2001-00
External Dimensions and Panel Cutout Dimensions
External Dimensions
R S T
kWh Wh W
V A
×10
6
×10
3
COMM
COS
φ
SET/ENT
110
110
0.5
15
15
66
82.4 96
45
Panel Thickness 1 to 10
2-Bolt M5
45
45
45
9-Screw M3
10-Screw M4
4-Screw M4
Short Bar (When short-ciruit,
end terminal ON)
Unit: mm
Panel Cut Dimension
Minimum130
45±0.3 45±0.3
45±0.345±0.3
Minimum 117
φ101 Hole
2-φ6 Hole
Page 6
4
IM 77C01C01-01E 1st Edition : March 5 2001-00
Mounting the Product
CAUTION
Turn off the power to the product before installing it on the panel because there is a possi­bility of electric shock.
After opening the mounting hole on the panel, follow the procedures below to install the product:
1. Insert the product into the opening from the front of the panel so that the terminal board on the rear is at the far side.
2. Set the brackets in place on the top and bottom of the product as shown in the figure below, then tighten the screws of the brackets. T ake care not to overtighten them.
Insert the product into the opening at the front of the panel
Directionm to insert the product
T erminal Arrangement
10
8
6
4
2
9
7
5
3
1
23
22
21
20
19
18
17
16
15
12
11
14
13
F05.EPS
T14.EPS
1-phase
2-wire
TML
No.
1 2 3 4 5 6 7 8
9 10 11 12 13 14 15 16 17 18 19 20 21 22 23
1S
1L
P1 P2
1-phase
3-wire
1S 1L 2S 2L
P1 P0 P2
+
A B C
+
L N
GND
3-phase
3-wire
Signal
Input
Output
Communication
Communication
Terminating
Power Supply
Optional Integrated
Control Signal
1S 1L 3S 3L
P1 P2 P3
3-phase
4-wire
1S 1L 2S 2L 3S 3L P1 P0 P2 P3
Page 7
5
IM 77C01C01-01E 1st Edition : March 5.2001-00
Wiring Diagrams
Voltage
or
Contact
2
Power Side
Load Side
K
1S 1L
P1 P2
PT
CT
L
L
N
GND
Power Supply
A B C
+
+
-
-
1
1 3 5 7 9
2 4
6 8
10
20
19
18
17
16
15
14
13
12
11
21 22 23
+ Receiver
-
Device
Communication Shield
Short Terminating
(R)
(S)
N
K
1S
1L
P1
2S
2L
P2
PT
CT
L
K
CT
L
L
N
GND
A B C
12
1 3 5 7 9
2 4
6 8
10
19
18
17
16
15
14
13
12
11
20 21
22 23
Voltage
or
Contact
Power Side
Load Side
Power Supply
+
-
+
-
+ Receiver
-
Device
Communication Shield
Short Terminating
(R) (S) (T)
1 phase 2 wire system 1 phase 3 wire system
2
K
1S 1L
P1
3S 3L
P3
P2
PT
CT
L
K
CT
L
L N
GND
A B C
13
1 3 5 7 9
2 4
6 8
10
19
18
17
16
15
14
13
12
11
20 21
22 23
Voltage
or
Contact
Power Side
Load Side
Power Supply
+
-
+
-
Communication Shield
Short Terminating
(R) (S) (T)
+ Receiver
- Device
A B C
L
N
GND
N3
2
PT
CT
K
L
K L
CT
1
K L
CT
1 3 5 7 9
2 4
6 8
10
19
18
17
16
15
14
13
12
11
20 21
22 23
Voltage
or
Contact
Power Side
Load Side
Power Supply
+
-
+
-
Communication Shield
Short Terminating
(R)
(S) (T)
+ Receiver
-
Device
3 phase 3 wire system 3 phase 4 wire system
CAUTION
The following caution for safety should be taken for handling of product. We are not respon­sible for damage incurred by use contrary to caution.
The following items should be checked before turning power on. Use of product ignoring specifications may cause over heating or burning. (a) V oltage of power supply and input value applied to the product should meet with
required specifications.
(b) External wiring to terminals should be connected correctly .
(See precding Article 4)
When take off wiring from the product, check to see primary side of CT , PT and power supply is in OFF status. If CT secondary side is in OPEN status during operation, be careful for danger of high voltage.
Do not use the product in such dangerous places where exist inflammable and explo­sive gas or steam.
Page 8
6
IM 77C01C01-01E 1st Edition : March 5.2001-00
Outline of Each Section
Panel switch
Status indicator (LED-RED)
Data display (7seg LED)
SET/ENT
11
13
12
1
3
14
2
4
6
7
5
9
8
10
1 kWh (Integration)
Light on when data on Display Section is inte­grated power [kWh].
2 Wh (Optional Integration)
Light on when data on Display Section is optional integrated power [Wh].
3 W (Power)
Light on when data on Display Section is power momentary value [W].
4 V (V oltage)
Light on when data on Display Section is voltage momentary value [V].
5 A (Current)
Light on when data on Display Section is current momentary value [A].
6 cos φ
Light on when data on Display Section is power factor momentary value [cos φ].
7X 10
3
Light on when data value on Display Section is kilo unit. And light on when integrated power value is mega unit.
8X 10
6
Light on when data value on Display Section is mega unit.
9 COMM
Light on during communication (RS-485 commu­nication) is made.
10 Display Section
Display measured value data, preset parameter symbol, set value data, adjustment parameter symbol, adjustment data and the like.
(1) Measurement items: integrated power, op-
tional integrated power, power momentary value voltage momentary value, current mo­mentary value, power factor momentary value
(2) Setting items: RS-485 station number, data
transmission rate, lower limit of input range, upper limit of input range, PT ratio, CT ratio, in­tegrating low cut power, integrating pulse unit (fixed point part, exponent), integrating pulse ON pulse duration
(3) Adjustment items: power momentary value in-
put zero, power momentary value input span,voltage momentary value input zero, volt­age momentary input span, current momen­tary value input zero, current momentary value input span, power momentary value input zero, power momentary value input span
11
SET/ENT
SET/ENT Switch
This switch is used for changing over displays of screens and items. It is also used for registration of set values and adjusted values. Pressing the switch for 3 seconds or more changes over the dis­plays for measured value, parameter setting, or input/output adjusting.
12 Range Switch
This switch is used for changing over display of phases. It is also used for shifting digit position and decimal position of set values on parameter setting display .
13 Figure UP switch
This switch is used for the followings:
1. Increase the set value on parameter setting display .
2. Display the maximum value of voltage or cur­rent.
3. Increase the adjusted value at input/output ad­justment. I
14 Figure DOWN switch
This switch is used for the followings:
1. Parameter decrement at parameter setting.
2. Display the minimum value of voltage or current
3. Decrease the adjusted value at input/output adjust­ment
Page 9
7
IM 77C01C01-01E 1st Edition : March 5.2001-00
Schematic Diagram of Change-over Display Screen
Integrated power
Measured Value Display Screen
Optional integrated
power
Instantaneous power
value
Voltage r.m.s. value
Current r.m.s. value
Instantaneous power
factor value
[kWh] display
[Wh] display
[W] display
[V] display
[A] display
[cosf] display
Input/Output Adjust Screen
Instantaneous power input
zero level adjust
Instantaneous power input
span level adjust
Instantaneous voltage input
zero level adjust
Instantaneous voltage input
span level adjust
Instantaneous current input
zero level adjust
Instantaneous current input
span level adjust
Optional instantaneous input
zero level adjust
Optional instantaneous input
span level adjust
Analog output zero level adjust
Analog output span level adjust
Parameter Setting Screen
PT ratio setting
CT ratio setting
Integrated low-cut power setting
Turn-off mode ON/OFF setting
Turn-off mode time setting
Input scaling “L” level setting for analog output *4
Input scaling “H” level setting for analog output *4
Integrated pulse unit mantissa setting *4
Integrated pulse unit characteristic setting *4
Integrated pulse ON width setting *4
RS-485 communication protocol setting *4
RS-485 station number setting *4
RS-485 data baud rate setting *4
LON communication node number setting *4
LON communication integrated power data
transmission period setting (minute) *4
LON communication integrated power data
transmission period setting (second) *4
LON communication power data transmission
period setting (minute) *4
LON communication power data transmission
period setting (second) *4
LON communication max/min.
Data transmission period setting (minute) *4
LON communication max/min.
Data transmission period setting (second) *4
*2 *3
*1
SET/ENT
Screen Development Sequence Key used
SET/ENT
Screen Development Sequence Key used
SET/ENT
Screen Development Sequence Key used
*1: Press SET/ENT key till the PT Ratio Setting Screen is displayed.
*2: Press SET/ENT key till the Instantaneous Power Input Zero Level Adjust Setting Screen is displayed.
*3: Press SET/ENT key till the last MEASURED VALUE DISPLAY SCREEN is displayed.
*4: By-passed if option is none.
*: If no key operation continues during five minutes when INPUT/OUTPUT ADJUST DISPLAY SCREEN
or PARAMETER SETUP DISPLAY SCREEN are displayed, the display screen changes to
VALUE DISPLAY SCREEN and displays the last measured value.
Page 10
8
IM 77C01C01-01E 1st Edition : March 5.2001-00
Example of Parameter Setting Screen (PT Ratio Setting)
SET/ENT
SET/ENT
SET/ENT
1, 3, 6
2, 4
5
7
SET/ENT
SET/ENT
1
Display Setting Screen at pressing key within three seconds
2
Change decimal point position at pressing key
3
Fixing decimal point position at pressing key
4
Change numeral column at pressing key
5
Change numeral column at pressing and key
6
Fixing numeral value at pressing key
7
Light on and off of setting value.
8
If the setting is complete correctly, press key.
If required correcting, press any of key, key, and key, then repeat from step
1
.
Example of Communication Connection
RS232-C Converter
RS232-C Cable
Short-circuit terminating
13 14 15
13 14 15
16 17
A –
A –
B +
B +
SG
Shield
13 14 15
Power monitor # 1
Power monitor # 2
Power monitor # N (N31)
PR201
A –
B +
Shield
A –
B +
Shield
Page 11
9
IM 77C01C01-01E 1st Edition : March 5.2001-00
Specifications
When outer set of PT, CT, check to see the primary side input
power is less than 10000 MW and the value calculated by the formula below is within above input measuring range list.
Input range (W) =
Primary side input power (W)
(PT ratio) x (CT ratio) Rated power factor: LEAD 0.5 to 1 to LAG 0.5 <Optional integrated control signal> Input point: 1 point Input signal: contact or voltage
Contact signal
ON signal OFF signal
below 200 over 100k
Voltage signal
–1V DC, below 200
4.5 to 25V DC
ON signal: Optional integration start (reset, integration start) OFF signal: Optional integration stop
(Note) Control of optional integration can also be made
through communication. Control by communication is once made, only control by communication is once made, only control by communication is made thereafter.
Integratad lowcut power: Integrated lowcut power below
lowcut power is not made by integrated power, optional integrated power and integrated pulse output. Set integrated lowcut power for input to this instrument .
Parameter setting
screen item
Setting
range
Integrated lowcut power
Fixed decimal point
0.5W when shipment0.1 to 99.9W
Output Specs.
Output point: 1 point (commonly used for analog and
integrated pulse outputs) <Analog Output> Function: Conversion of output instantanous power into DC
current. Output signal (instantanous power) : 4 to 20mA DC Permissible load resistance: 0 to 750 Input scaling: Indicates instantanous power range to be
converted. Input scaling can be set by “H” and
“L” levls of analog output on parameter setting
screen. Set “L” and “H” levels within measur-
ing range of this instrument. Also set span
(difference between “L” level and “H” level) so
as it would be more than 50% of rated power. If
not specified when ordering, it would be shipped
“L” level at OW, and “H” level at rated power
(W). <Integrated pulse output> Function: Outputs pulse in proportion to integrated power Output signal: Open collector Output capacity: 200mA, 30V DC Integrated pulse unit: Indicates actual kWh corresponding 1
pulse input to this instrument. It can be set
through integrated pulse unit characteristic and
mantissa sections on parameter setting screen.
Input & Output Specifications
Input Specs.
Phase & wire system: 1-phase 2-wire system, 1-phase 3-wire
system, 3-phase 3-wire system, 3-phase 4-wire
system Input frequency: 45 to 65Hz Rated input voltage: 110V AC, 220V AC, 440V AC,
3-phase 4-wire system: 64V AC, 127V AC,
277V AC Permissible Input voltage: 1.2 times of rated voltage
(continuous) , 1.5 times (10 seconds) Rated input current: 1A AC, 5A AC Permissible Input current: 1.2 times of rated current
(coninuous) , 2 times (10 seconds),
10 times (3 seconds) Input (power) measuring range (secondary side of PT, CT
when CT, PT are set)
1-phase 2-wire system
Input (AC) Input range
App. Consumed VA Voltage Current
0.2VA
0.4VA 0.2VA
0.8VA
RP
110V/1A 110V/5A 220V/1A 220V/5A 440V/1A 440V/5A
100W 500W 200W
1000W
400W
2000W
-120 to +120W
-600 to +600W
-240 to +240W
-1200 to +1200W
-480 to +480W
-2400 to +2400W
1-phase 3-wire system
Input (AC) Input range
App. Consumed VA
Voltage Current
0.2VA/ phase
0.2VA/ phase
RP
200V/1A 200V/5A
200W
1000W
-240 to +240W
-1200 to +1200W
3-phase 3-wire system
Input (AC) Input range
App. Consumed VA
Voltage Current
0.2VA/ phase
0.4VA/ phase
0.2VA/ phase
0.8VA/ phase
RP
110V/1A 110V/5A 220V/1A 220V/5A 440V/1A 440V/5A
200W
1000W
400W
2000W
800W
4000W
-240 to +240W
-1200 to +1200W
-480 to +480W
-2400 to +2400W
-960 to +960W
-4800 to +4800W
3-phase 4-wire system
Input (AC) Input range
App. Consumed VA
Voltage Current
0.2VA/ phase
RP=Rated Power
0.4VA/ phase
0.1VA/ phase
0.2VA/ phase
0.2VA/ phase
0.5VA/ phase
RP
110V/1A 110V/5A 220V/1A 220V/5A
64V/1A
64V/5A 127V/1A 127V/5A 277V/1A 277V/5A
300W
1500W
600W
3000W
200W
1000W
400W
2000W
800W
4000W
-360 to +360W
-1800 to +1800W
-720 to +720W
-3600 to +3600W
-240 to +240W
-1200 to +1200W
-480 to +480W
-2400 to +2400W
-960 to +960W
-4800 to +4800W
Page 12
10
IM 77C01C01-01E 1st Edition : March 5.2001-00
Setting range
Rated power
100W 200W 300W 400W 500W 600W
800W 1000W 1500W 2000W 3000W 4000W
5.556 × 10
-6
to 1.000 × 10-1kWh/pulse
6.667 × 10
-6
to 1.000 × 10-1kWh/pulse
1.000 × 10
-5
to 1.000 × 10-1kWh/pulse
1.334 × 10
-5
to 1.000 × 10-1kWh/pulse
2.000 × 10
-5
to 1.000 × 10-1kWh/pulse
2.667 × 10
-5
to 1.000 × 10-1kWh/pulse
(Note) When power OFF , integrated power on display is
maintained. As for integrated pulse output, error of less than 1 pulse of integrated power arises.
Integrated pulse ON pulse width: Indicates ON time of pulse to
output. It can be set on parameter setting screen. Set it so as not to exceed maximum ON pulse widthe obtained by the formula below:
Maximum On pulse width (ms)
= pulse unit [kWh/pulse] x 3600 x 1000
2
-10
rated power [W] x 1.2
Setting range Remarks
10 to 1270ms Set at 10ms unit
Initial value if not specified
50ms
Communication Output specs.
Output point:1 point (Commonly use for RS-485 and LON
communications)
Function:Refer “Communication Output”
Standard Performance
Accuracy rating: Instantanous power, voltage r.m.s. value,
current r.m.s. value ±0.5% of rated value (at 23°C±2°C) (Equivalent JIS C 1102 0.5 grade) Integrated power energy ±(Power measuring accuracy+0.5% of rdg) (at 23°C±2°C) Power factor ±2% of rated value (at 23°C±2°C) Analog output ±0.5% of span (at 23°C±2°C) (Equivalent JIS C 1111 0.5 grade) However, ±1% of span in case span is 50 to 80% of rated power.
Optional integrationg function: This function integrates power
energy during the time optional integration starts to operate and display it by digital. There are 2 methods to control optional integration, one is made through optional integrating control signal and the other is made through communication. When optional integration control is made through commuication, optional integrationg control signal thereafter becomes invalid. Therefore, make control through either one of the above 2 methods. When optional integration changes over from stop to start, integration starts after optional integrated power is reset.
Backup when power off (power meter): Integrated power holds
last integrated value when power off. Optional integration has not this function.
Response speed of instantanous power (analog output): Within
1 second (until enter into ±1% of last value)
Up date of transmit data: Power, voltage, current, power factor
within 500ms
Insulation resistance: 100M (500V DC) between any two
points of voltage input, current input, optional integrated control signal, output, communication output, power supply and ground
Withstand voltage: 2000V AC/minute between any two points
of voltage input, current input, output, power supply and ground 2000V AC/minute between communication output and (input, power supply) 1000V AC/minute between communication output and (output, ground). 500V AC/minute between optional integrated control signal and (input, output, communication output, power supply and ground)
Impulse withstand voltage: 5kV (1.2/50µs) between input and
output, input and ground, power supply and ground
Temperature range: -10 to 55°C Humidity range: 5 to 90% RH (no condensation) Effect of power supply voltage fluctuation: ±0.3% of RV
(instantanous value)/85 to 264V AC ±1.0% of RV (power factor)/85 to 264V AC
Effect of temperature change: ±0.5% of RV (instantanous
value)10°C ±2.0% of RV (power factor)/10°C
Effect of input frequency: ±0.3% of RV (instantanous value)/45
to 65Hz ±1.0% of RV (power factor)/45 to 65Hz
(RV=Rated Value) Power voltatge: 85 to 264V AC, 45 to 65Hz Power dissipation: 6VA (at 100V AC)
8VA (at 200V AC)
Display Operation
PT ratio CT ratio:
Setting of PT and CT ratio makes display
converting input of this instrument into primary
side input value of PT and CT.
Setting can be done on parameter setting screen.
PT ratio setting range CT ratio setting range
1 to 32000 0.05 to 32000
Integrated power:
䊐䊐䊐䊐䊐[kWh] or 䊐䊐䊐䊐䊐[MWh]
(w/o symbol, partially fixed decimal point integer
5 digits)
Input power rating
x PT ratio x CT ratio
30W to 99999kW 100kW to 999.99kW 1MW to 9.9999MW 10MW over
Display, decimal point
0 to 99999kWh
0.00 to 999.99MWh (kWh+10
3
)
0.0 to 9999.9MWh (kWh+10
3
)
0 to 99999kWh (kWh+10
3
)
Inregrated power data is reset to zero when the data exceed
maximunm display value.
Page 13
11
IM 77C01C01-01E 1st Edition : March 5.2001-00
Optional integrated power:
䊐䊐䊐䊐䊐[Wh] (w/o symbol, integer 5 digits)
Instantanous power:
±䊐䊐䊐.[W] to ±䊐䊐䊐䊐[MW] (w/symbol. floating decimal point 4 digits, minimum resolution:0.1W)
Voltage r.m.s. value:
䊐䊐䊐.[V] to 䊐䊐䊐䊐[kV] (w/o symbol, floating decimal point 4 digits, minimum resolution:0.1V)
Current r.m.s. value:
.䊐䊐䊐[A] to .䊐䊐䊐[kA] (w/o symbol, floating decimal point 4 digits, minimum resolution:0.001A)
Voltage maximum value:
䊐䊐䊐.[V] to —䊐䊐䊐䊐[kV] (w/o symbol, floating decimal point 4 digits, minimum resolution:0.1V)
Voltage minimum value:
䊐䊐䊐䊐[V] to —䊐䊐䊐䊐[kV] (w/o symbol, floating decimal point 4 digits, minimum resolution:0.1V)
Current maximum value:
.䊐䊐䊐[A] to —䊐.䊐䊐䊐[kA] (w/o symbol, floating decimal point 4 digits, minimum resolution:0.001A)
Instantanous power factor:
d.䊐䊐䊐 to 1.000 to G.䊐䊐䊐[COSφ] (w/o symbol, fixed decimal point 4 digits, minimum resolution:0.001COSφ, d:Lead, G:Lag)
kWh LED: Light on during display of integrated power
[kWh].
Wh LED: Light on during display of optional integrated
power [Wh].
W LED: Light on during display of instantanous power [w]. V LED: Light on during display of voltage r.m.s. value
[V].
A LED: Light on during display of current r.m.s. value [A]. COSφ LED: Light on during instantanous power factor [COSφ] X10
3
LED: Light on when displaying instantanous value is
kilo unit. Or lighton when integrated power [kWh] is Mega unit.
X10
6
LED: Light on when displaying instantanous value is
mega unit.
COMM LED: Green light on when RS-485 or LON communi-
cation. As for LON communication, red light on and off when network parameter is under construction, and red light on when communica­tion trouble or service.
SET/ENT Switch: This switch changes-over display of
integrated power, optional integrated power, instantanous power, voltage r.m.s. value, current r.m.s. value and instantanous power factor. Also, it selects parameter setting item and input/output adjust item.
R, S, T (phase indicator) Light on phase that the data is displayed in data display. Current display: R, S, T Voltage display: R-S, S-T, T-R
R, S, T (3-phase 4-wire system)
(Range switch)
This switch is used for display line change-over, and for movement column position of setting data and decimal point position.
(Numeric up switch)
This switch is used for increment of setting parameter and input/output adjustment data.
(Numeric down switch)
This switch is used for decrement of setting parameter and input/output adjustment data.
Note 1: Instantanous power value is displayed with symbol in
case only negative.
Note 2: When display of maximum value, —’ is displayed at
the top with light on and off.
Note 3: When display of minimum value, —’ is displayed at
the top with light on and off.
Note 4: Instantanous power factor is displayed only when
measuring option is designated.
Communication Output
RS-485 or LON communication outputs can optionally be
selected <Communication data> Following measuring value can be read out by converting input
into PT•CT primary side input.
• Integrated power
• Optional integrated power (present value)
• Optional integrated power (last value)
• Instantanous power
• Voltage r.m.s. value
• Current r.m.s. value
• Instantanous power factor or Current 2 r.m.s. value
• Voltage maximum value
• Valtage minimum value
• Current maximum value
• Current 2 maximum value Also, start•stop of optional integrated power and reset of
maximum and minimum values of voltage r.m.s.
value and maximum value of current r.m.s. value
can be done through communication.
<RS-485 Communication> Function: Various measuring values can be read out through
personal computer by command/ response mode.
Readout of measuring value would be made
individually or in block. Also, control of optional integration and initialization of
maxium and mimimum values can be done
through persomal computer.
System Configuration:
Application Software
RS-232C Port
RS-232C/485 Conveter
RS-485
Personal Computer
Power Monitor
Power Monitor
Power Monitor
Power Monitor
Power Monitor
Terminating
Note: RS-232C/485 Converter is recommended to use our
ML1 in AUTO mode.
Communication specs.: RS-485 Interface Transmit distance: Maximum about 1.2km
(When use of 24AWG twist pair cable)
Page 14
12
IM 77C01C01-01E 1st Edition : March 5.2001-00
Connectiong mode:
(1) RS-485 standard Multi-drop connection Maximum 32 stations (including upper personal computer) (2) Terminating resistor: 120 (ON by terminal short) (3) Not insulated with inner circuit
Connecting Terminal: 3 terminals back face
A: Balanced type twist pair cable – B: Balanced type twist pair cable +
C: Shield Transmit mode: Half duplex communication Synchronizing mode: Start-stop synchronization Transmit speed: Can be set through parameter setting screen
Setting Range
9600 / 4800 / 2100 / 1200
Data format: Start bit 1 bit
Data bit 8 bits
Parity None
Stop bit 1 bit Error detect: SUM CHECK (simply adding 2 bytes) Xon/Xoff Control: None Terminating character designation: Yes (CR) Station number setting: Can be set through parameter setting
screen
Setting range
1 to 31
Communication error disposal: If data received is other than
command, reading is ignored and no disposal be
made. (noise or erroneous data would be
ingnored).
Make time-out disposal through upper computer.
Set time-out time more than 1 second.
<LON Communication> Function: Measuring data can be simply read out on personal
computer through LON communication adapter
and DDE: server without consciousness of
communication. Also, control of optional
integration and initaialization of maximum and
minimum values can be done through personal
computer. Please contact us as to connection with
other instruments.
System Configuration:
Application Softwaer
DDE Server
Data Base
LON Communication
Adapter
LON
Personal Computer
Power Monitor
Power Monitor
Power Monitor
Power Monitor
Power Monitor
Shape & Mounting
External dimension: 110 x 110 x111mm (HxWxD) Mounting method: Panel mouting
(Refer panel cut dimension) Material: Case: uninflammable ABS plastic (black) Terminal board: uninflammable ABS plastic (black) Weight: Abt 500g Connecting method: M3 screw terminal connection (output,
communication, optional integrated control signal)
M4 screw terminal connection (input, power
supply)
Accessories:
Label...2, Nut M5...2, Washer M5...2 Spring
washer M5...2 Short bar...1