YOKOGAWA PH402G User's Manual

YOKOGAWA
Instruction Manual
Model PH402G pH Converter
IM 12B6B3-E-E
8th Edition
TABLE OF CONTENTS
PREFACE
1. INTRODUCTION AND GENERAL DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-1
-1. Instrument check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-1
1
1-2. Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1-2
2. PH402 SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
-1. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-1
2
2-2. Operating specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
2-3. Model and suffix codes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2-2
3. INSTALLATION AND WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
3-1. Installation and dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
3-1-1. Installation site . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
3-1-2. Mounting methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-1
3-2. Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-3
3-3. Wiring the power supply . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
3-3-1. General precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
3-3-2. Access to terminal and cable entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-4
3-3-3. AC power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-5
3-3-4. DC power . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-5
3-3-5. Grounding the housing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-5
3-3-6. Switching on the instrument . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-5
3-4. Wiring the contact signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-6
3-4-1. General precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-6
3-4-2. Contact outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-6
3-5. Wiring the analog output signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-6
3-5-1. General precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-6
3-5-2. Analog output signals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-6
3-6. Wiring the sensor system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-7
3-6-1. Impedance measurement jumper settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-7
3-7. Sensor wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-10
3-7-1. Connection cable . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-11
3-7-2. Sensor cable connection with special grommet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-12
3-13
3-7-3. Sensor cable connections using junction box (BA10) and extension cable (WF10)
. . . .
3-8. Tag plate mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3-15
4.
OPERA
TION; DISPLA
Y FUNCTIONS AND SETTING
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-1
4-1. Operator interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-1
4-2. Explanation of operating keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-2
4-3. Setting passcodes
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4-3
4-3-1. Passcode protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-3
4-4. Display examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-3
4-5. Display functions
4-5-1. Display functions pH (default) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-4
4-4
4-5-2. Display functions pH (ORP) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-5
4-5-3. Display functions pH (rH) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4-6
5. PARAMETER SETTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-1
5-1. Maintenance mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-2
5-1-1. Manual temperatur
e selection and adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-3
5-1-2. Process temperature measuring in ORP mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-4
5-1-3. Manual activation of HOLD . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-4
5-1-4. Manual wash start/stop . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-5
IM 12B6B3-E-E
5-1-5. Setpoint adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-6
5-1-6. Manual impedance check . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-7
5-2. Commissioning mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-8
-2-1. Setpoints . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-9
5
5-2-2. Range . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-11
5-2-3. Hold . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-13
5-2-4. Wash . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-15
-2-5. Service . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-16
5
-3. Notes for guidance in the use of service coded settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-17
5
5-3-1. Parameter specific functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-18
5-3-2. Temperature compensation and measuring functions . . . . . . . . . . . . . . . . . . . . . . . . . .5-20
5-3-3. Calibration functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-22
5-3-4. mA Output functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-24
5-3-5. Contact outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-26
5-3-6. User interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-30
5-3-7. Communication setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-32
5-3-8. General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-32
5-3-9. Test and setup mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5-34
6. CALIBRATION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-1
6-1. Automatic calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-1
6-2. Manual calibration
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-1
6-3. Sample calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-1
6-4. Data entry . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-1
6-5. Calibration procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-2
6-5-1. Automatic calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-2
6-5-2. Automatic calibration with HOLD active . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-3
6-5-3. Manual calibration (2nd parameter calibration) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-4
6-5-4. Sample calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6-6
7. MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-1
7-1. Periodic maintenance for the EXA PH402 converter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-1
7-2. Periodic maintenance for the sensor system . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7-1
8. TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-1
8-1. Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-2
8-1-1. Off-line calibration checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-2
8-1-2. On-line impedance checks . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8-2
9. SPARE PARTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9-1
10. APPENDIX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-1
10-1. User setting table . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-1
10-2. Configuration checklist for PH402G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-3
10-3. Setup for sensor compatibility . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-4
10-3-1. General
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-4
10-3-2. Selection of measurement and reference electrode . . . . . . . . . . . . . . . . . . . . . . . . . . .10-4
10-3-3. Selecting a temperature sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-4
10-4. Setup for other functions
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10-5
10-5. Set up for Pfaudler Type 18 sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-6
10-5-1. General set up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10-6
10-5-2. Calibration set up
10-6. Softwar
GLOSSAR
e histor
Y
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
y
10-6
10-7
ERROR CODES QUALITY INSPECTION STANDARD & CERTIFICATE
IM 12B6B3-E-E
CAUTION
PREFACE
WARNING
Electric discharge
The EXA analyzer contains devices that can be damaged by electrostatic discharge. When servicing this equipment, please observe proper procedures to prevent such damage. Replacement components should be shipped in conductive packaging. Repair work should be done at grounded workstations using
rounded soldering irons and wrist straps to avoid electrostatic discharge.
g
Installation and wiring
The EXA analyzer should only be used with equipment that meets the relevant IEC, American or Canadian standards. Yokogawa accepts no responsibility for the misuse of this unit.
The Instr
ument is packed carefully with shock absorbing materials, nevertheless, the instrument may be
damaged or broken if subjected to strong shock, such as if the instrument is dropped. Handle with care.
Although the instr
ument has a weatherproof construction, the transmitter can be harmed if it becomes
submerged in water or becomes excessively wet.
Do not use an abrasive or solvent in cleaning the instrument.
Notice
Contents of this manual are subject to change without notice. Yokogawa is not responsible for damage to the instrument, poor performance of the instrument or losses resulting from such, if the problems are caused by:
l Improper operation by the user. l Use of the instrument in improper applications l Use of the instrument in an improper environment or improper utility program l Repair or modification of the related instrument by an engineer not authorized by Yokogawa.
Warranty and service
Yokogawa products and parts are guaranteed free from defects in workmanship and material under normal use and service for a period of (typically) 12 months fr
om the date of shipment from the manufactur
er.
Individual sales organisations can deviate from the typical warranty period, and the conditions of sale
elating to the original purchase order should be consulted. Damage caused by wear and tear, inadequate
r maintenance, cor
osion, or by the ef
r
fects of chemical pr
ocesses ar
e excluded fr
om this war
ranty coverage.
In the event of warranty claim, the defective goods should be sent (freight paid) to the service department of
elevant sales or
the r
ganisation for r
epair or r
eplacement (at Y
okogawa discr
etion). The following information
must be included in the letter accompanying the returned goods:
l Part number l Original pur l Length of time in service and a description of the process l Description of the fault, and the cir
ocess/envir
l Pr l A statement whether warranty or non-warranty service is requested l Complete shipping and billing instructions for return of material, plus the name and phone number of a
contact person who can be r
ned goods that have been in contact with process fluids must be decontaminated/disinfected before
Retur shipment. Goods should car
, model code and serial number
chase or
der and date
cumstances of failur
onmental conditions that may be r
eached for further information.
tificate to this ef
y a cer
r
e
elated to the installation failur
e of the device
fect, for the health and safety of our employees. Material safety data sheets should also be included for all components of the processes to which the equipment has been exposed.
IM 12B6B3-E-E
Introduction 1-1
MODEL SERIAL NO. SUPPLY
PH402G-E-1-E FD 020 034 110-120 VAC, 50/60 Hz, 10 VA
N200
1. INTRODUCTION AND GENERAL DESCRIPTION
The Yokogawa EXA 402 is a 4-wire transmitter designed for industrial process monitoring, measurement and control applications. This instruction manual contains the information needed to install, set up, operate and maintain the unit correctly. This manual also includes a basic troubleshooting guide to answer typical user questions.
Yokogawa can not be responsible for the performance of the EXA analyzer if these instructions are not followed.
1-1. Instrument Check
Upon delivery, unpack the instrument carefully and inspect it to ensure that it was not damaged during shipment. If damage is found, retain the original packing materials (including the outer box) and then immediately notify the carrier and the relevant Yokogawa sales office.
Make sure the model number on the nameplate affixed to the top of the display board of the instrument agrees with your order.
NOTE: The nameplate will also contain the serial number and power supply selection. Be sure to apply correct power to the unit.
Figure 1-1. Nameplate
Check that all the parts are present, including mounting hardware, as specified in the option codes at the end of the model number. For a description of the model codes, refer to Chapter 2 of this manual under General Specifications.
Basic Parts List: Converter EXA 402
Instruction Manual (See model code for language) Packet with special cable gr
ommet and blanking pieces Packet with 4 screws for mounting on a panel (M6x8mm) Optional mounting hardware when specified (See model code)
IM 12B6B3-E-E
1-2 Introduction
1-2. Application
he EXA converter is intended to be used for continuous on-line measurement in industrial installations. The
T unit combines simple operation and microprocessor-based performance with advanced self-diagnostics and enhanced communications capability to meet the most advanced requirements. The measurement can be used as part of an automated process control system. It can also be used to indicate dangerous limits of a process, to monitor product quality, or to function as a simple controller for a dosing/neutralisation system.
Yokogawa designed the EXA analyzer to withstand harsh environments. The converter may be installed either indoors or outside because the IP65 (NEMA4X) housing and cabling glands ensure the unit is adequately protected. The flexible polycarbonate window on the front door of the EXA allows pushbutton access to the keypad, thus preserving the water and dust protection of the unit even during routine maintenance operations. A variety of EXA hardware is optionally available to allow wall, pipe, or panel mounting. Selecting a proper installation site will permit ease of operation. Sensors should normally be mounted close to the converter in order to ensure easy calibration and peak performance. If the unit must be mounted remotely from the sensors, WF10 extension cable can be used up to a maximum of 50 metres (150 feet) with a BA10 junction box. Except installations with dual high impedance sensors, where the maximum cable length is 20 metres using integral cable only (no junction box).
The EXA is delivered with a general purpose default setting for programmable items. (Default settings are listed in Chapter 5 and again in Chapter 10). While this initial configuration allows easy start-up, the configuration should be adjusted to suit each par
ticular application. An example of an adjustable item is the type of temperature sensor used. The EXA can be adjusted for any one of five different types of temperature sensors.
To record such configuration adjustments, write changes in the space provided in Chapter 10 of this manual. Because the EXA is suitable for use as a monitor, a controller or an alarm instrument, program configuration possibilities are numerous.
Details provided in this instruction manual are sufficient to operate the EXA with all Yokogawa sensor systems and a wide range of third-party commercially available probes. For best results, read this manual in conjunction with the corresponding sensor instruction manual.
Yokogawa designed and built the EXA to meet the CE regulatory standards. The unit meets or exceeds stringent requirements of EN 55082-2, EN55022 Class A and low voltage safety directive IEC1010 without
mance in even the most demanding industrial
omise, to assur
compr
e the user of continued accurate per
for
installations.
IM 12B6B3-E-E
Specification 2-1
2. PH402 SPECIFICATIONS
-1. General
2 A. Input specifications
: Dual high impedance inputs
(2 x 1013Ω) with provision for liquid earth connection.
uitable for inputs from glass
S or enamel pH & reference sensors and ORP metal electrodes.
B. Input ranges
- pH : -2 to 16 pH
- ORP : -1500 to 1500 mV
- rH : 0 to 55 rH
- Temperature : -30 to 140 ºC (-20 -to 300 ºF) (for 8k55 sensor -10 to 120 ºC (10 to 250 ºF);
for 10kPTC sensor -20 to
140 ºC (0 to 300 ºF))
C. Span
- pH : min 1 max 20 pH
- ORP : min 100 max 2000 mV
- rH : min 2 max 55 rH
- Temperature : min 25 ºC max 200 0C min 50 ºF max 400 0F (for 8k55 sensor max 100 ºC (250 ºF))
D. Transmission Signals
: Two isolated outputs of 0/4-
20 mA DC with common negative. Maximum load 600 Ω. Auxiliary output can be chosen from pH, temperature, ORP or rH (with suitable sensor), P.I. control. burn up (22 mA) or burn down (0/3.5 mA) to signal failure.
E. Temperature compensation
- Range : Automatic or manual compensation to Nernst equation. Process compensation by configurable temperature coefficient. Adjustable ITP (Isothermal point of intersection).
F. Calibration : Semi-automatic using
preconfigured NIST buffer tables 4, 7 & 9, or with user
defined buffer tables, with automatic stability check.
anual adjustment to grab
M sample. Slope and Asymmetry Potential setting. Zero point can be selected for
alibration and display instead
c of As. Pot. (IEC746-2)
G. Serial Communication
: Bi-directional according to the
EIA-485 standard using HART protocol and PC402 software.
H. Logbook : Software record of important
events and diagnostic data. Available through RS485, with key diagnostic information available in the display.
I. Display : Custom liquid crystal display,
1
2
with a main display of 3
/ digits 12.5 mm high. Message display of 6 alphanumeric characters, 7 mm high. Warning flags and units (pH and mV) as appropriate.
J. Contact outputs
- General : Four (4) SPDT relay contacts with LED indicators. For S1, S2, and S3, the LED is on when relay is powered. NOTE: For S4 (FAIL) LED
lights when power is
removed (Fail safe). Contact outputs configurable for hysteresis and delay time.
- Switch capacity : Maximum values 100 VA, 250 VAC, 5 Amps. Maximum values 50 Watts, 250 VDC, 5 Amps.
- Status : High/Low process alarms, selected from pH, ORP, rH and temperature. Contact output is also available to signal “Hold Active”
- Control function : On / Off
PI pulsed Proportional duty cycle
control with integral term.
PI frequency Proportional frequency control
with integral term. In addition wash cleaning control signal on S3, and FAIL alarm for system and diagnostic errors on S4
IM 12B6B3-E-E
2-2 Specifications
K. Contact input : Remote wash cycle start.
L. Power supply : 230 VAC ±15%, 50/60 Hz.
Max. consumption 10 VA. 115 VAC ±15%, 50/60 Hz. Max. consumption 10 VA.
00 VAC ± 15% 50/60 Hz.
1 Max. consumption 10 VA. 24 VDC -20% / +30% Max. consumption 10 Watts.
M. Input isolation : 1000 VDC
N. Shipping details: Package size w x h x d
290 x 225 x 170 mm.
11.5 x 8.9 x 6.7 in. Packed weight approx.
2.5 kg (5lb).
2-2. Operating specifications
A. Performance : pH
- Linearity : ≤0.01 pH ± 0.02 mA
- Repeatability : ≤0.01 pH ± 0.02 mA
- Accuracy : ≤0.01 pH ± 0.02 mA
Performance : ORP
- Linearity : ≤1 mV ± 0.02 mA
- Repeatability : ≤1 mV ± 0.02 mA
- Accuracy : ≤1 mV ± 0.02 mA
Performance : Temperature with Pt1000
, 3 kBalco, 5 k1and 10k PTC
- Linearity : ≤0.2 oC ± 0.02 mA
- Repeatability : ≤0.1 oC ± 0.02 mA
- Accuracy : ≤0.3 oC ± 0.02mA
Performance : Temperature with Pt100
& 8k55
- Linearity : ≤0.3 oC ± 0.02 mA
- Repeatability : ≤0.1 oC ± 0.02 mA
- Accuracy
: ≤0.4
± 0.02 mA
C
o
B. Ambient operating temperature
-30 to +70
:
o
C (-20 to 160 ºF)
for mA output.
-10 to +70 oC (10 to 160 ºF) for LCD
C. Storage temperature
: -30 to +70 oC (-20 to 160 ºF)
D. Humidity : 10 to 90% RH non-
condensing
E. Housing
Case : Cast aluminium with
chemically resistant coating
Cover : flexible polycarbonate window.
ase color : off-white and
C Cover color : moss green. Cable entry : via six 1/2” polyamide glands. Cable terminals : are provided for up to 2.5
mm2finished wires.
rotection : weather resistant to IP65 and
P
NEMA 4X standards.
Mounting : Pipe wall or panel, using
optional hardware.
F. Data protection : EEPROM for configuration and
logbook, and lithium battery for clock.
G. Watchdog timer: Checks microprocessor
H. Automatic safeguard
: Return to measuring mode
when no keystroke is made for 10 min.
I. Power interruption
: Less than 50 milliseconds no
effect. More than 50 milliseconds reset to measurement.
J. Operation protection
: 3-digit programmable
password.
K. Regulatory compliance
- EMC : meets council directive 89/336/EEC
- Emmission : meets EN 55022 Class A
- Immunity
: meets EN 50082-2
- Low voltage : meets council directive 73/23/EEC
- Installation
: Designed for installation
conforming to IEC 1010-1. Category II.
2-3. Model and suffix codes
Model Suffix Option Description
PH402G .................................... pH/ORP transmitter
Supply -1 ........................... 115 Volts 50/60 Hz
voltage
Instr
Options /U......... Pipe and wall mounting
* For other languages contact local sales of
-E ................................ Always E
...........................
-2
-4........................... 24 Volts DC
-5
uction manual -E
........................... 100 Volts 50/60 Hz
code
olts 50/60 Hz
230 V
.................... English language *
e
dwar
/PM...... Panel mounting hardware
/Q /SCT
har
........ Quality certificate
Stainless steel tag
....
fice
IM 12B6B3-E-E
Installation and wiring 3-1
min.185 (7.25)
min.195 (7.75)
1
3
8 (5.
43)
138
M6
M6
M5
cut - out = 138 x 138 (5.43 x 5.43)
3. INSTALLATION AND WIRING
3-1. Installation and dimensions
-1-1. Installation site
3
The EXA converter is weatherproof and can be installed inside or outside. It should, however, be installed as
lose as possible to the sensor to avoid long cable runs between sensor and converter. In any case, the
c cable length should not exceed 50 meters (162 feet). Select an installation site where:
l Mechanical vibrations and shocks are negligible l No relay/power switches are in the direct environment l Access is possible to the cable glands (see figure 3-1) l The transmitter is not mounted in direct sunlight or severe weather conditions l Maintenance procedures are possible (avoiding corrosive environments)
The ambient temperature and humidity of the installation environment must be within the limits of the instrument specifications. (See chapter 2).
3-1-2. Mounting methods
Refer to figures 3-2 and 3-3. Note that the EXA converter has universal mounting capabilities:
l Panel mounting using optional brackets l Surface mounting on a plate (using bolts from the back) l Wall mounting on a bracket (for example, on a solid wall) l Pipe mounting using a bracket on a horizontal or vertical pipe (maximum pipe diameter 50 mm)
144(5.67)
24(1)
16.5
(0.65)
115.5(4.55)
Figure 3-1. Housing dimensions and layout of
glands
144(5.67)
Figure 3-2. Panel mounting diagram
IM 12B6B3-E-E
3-2 Installation and wiring
wall mounting pipe mounting
80
(3.15)
2x ø6.5
(0.26)
200
(7.87)
70
(2.75)
4x ø10 (0.4)
145
(5.70)
Figure 3-3. Wall and pipe mounting diagram
pipe mounting (vertical)
(horizontal)
2” ND. pipe
OPTION/U: Universal pipe/wall mounting kit
e 3-4. Internal view of EXA wiring compartment
Figur
IM 12B6B3-E-E
Installation and wiring 3-3
12D7C3-04
GLANDS TO BE
USED FOR CABLING
3-2. Preparation
efer to figure 3-4. The relay contact terminals and power supply connections are under the screening
R (shielding) plate. These should be connected first. Connect the sensor, outputs and data communication connections last.
To open the EXA 402 for wiring:
. Loosen the four frontplate screws and remove the cover.
1
2. Use the rubber knob in the lower righthand corner and swing open the display board to the left.
3. The upper terminal strip is now visible.
4. Remove the screen (shield) plate covering the lower terminal strip.
5. Connect the power supply and contact outputs. Use the three glands at the back for these cables.
6. Replace the screen (shield) plate over the lower terminals.
WARNING
Always replace the screen plate over the power and contact outputs for safety and avoid interference.
7. Connect the analog output(s), the sensor input, and, if necessary, the RS485 serial bus.
8. Use the front three glands for analog output, sensor input, contact input and communication cabling (see figur
e 3-5).
9. Close the display board and switch on the power. Commission the instrument as required or use the default settings. Replace the cover and secure frontplate with the four screws.
10.
High voltage section
Contact
(S3,S4,FAIL)
output cables
Sensor
cables
Contact
(S1,S2)
output cables
Analog output cables
Power
cable
Communi-
cation,
contact
input
Suitable for cables with an outside diameter between 7 - 12 mm (9/32-15/32in.)
Figure 3-5. Glands to be used for cabling
IM 12B6B3-E-E
3-4 Installation and wiring
S1
S2
S4/FAIL
S3/WASH
SYSTEM CONFIGURATION
1
SYSTEM CONFIGURATION
FRONT GLANDS
0/4-20 mA
0/4-20 mA
Figure 3-6. System configuration
Sensor
Output signals
RS485
Contact input
REAR GLANDS
Power
Contact output
ontact
C output
3-3. Wiring the power supply
3-3-1. General pr
ecautions
Make sure the power supply is switched off. Also, make sure that the power supply is correct for the specifications of the EXA and that the supply agrees with the voltage specified on the nameplate. Remove the front cover by unscrewing the four screws to check this nameplate on the top of the display board.
Local health and safety r protected internally by a fuse. The fuse rating is dependent on the supply to the instrument. The 250 VAC fuses should be of the “time-lag” type, conforming to IEC127.
Fuse ratings are 230 VAC - 50 mA; 100 VAC - 100 mA; 115 VAC - 100 mA; 24 VDC - 1.0 A.
The inter
nal fuse is located next to the power ter
3-3-2. Access to terminal and cable entry
Terminals 1, 2 and 3 on the bottom terminal strip are used for the power supply. Guide the power cables through the gland closest to the power supply terminals. The terminals will accept wires of 2.5 mm2(14 AWG). Use cable finishings if possible.
Connect the wires as indicated in the wiring diagram (refer to figure 3-6).
egulations may r
e an external circuit breaker to be installed. The instrument is
equir
minals (in the lower righthand corner).
IM 12B6B3-E-E
Installation and wiring 3-5
1
41317
1
1
1
2 22 21 63 66 65 62 61 95 94 93 9291
SCREEN
mA2
mA1
SCREEN
TL TL
161
5
7
1
S4
S3
S2
S1
C NC N
O
7
2 73 51 52 53 41 43 31 334232
250V AC
5A
100V A
2
50VDC
5A
50W
F
USE
1
00
115
2
30
24
250VAC; T
3
12
C NC NO C NC NO C NC NO
V
AC
VAC
V
AC
VDC
100 mA
100 mA
50 mA
1 A
S
ensor Inputs
Contact Input
m
A Outputs
Digital Communications
Relay Contacts
P
ower Supply
p
H/ORP
ref.
l
iquid
earth
t
emp.
sens.
High voltage compartment
S
ENSOR(S) CONT mA OUTPUT RS485
Figure 3-7. Input and output connections
3-3-3. AC power
Connect terminal 1 to the phase line of the AC power and terminal 2 to the zero line. Terminal 3 is for the power ground. This is separated from input ground by a galvanic isolation.
3-3-4. DC power
Connect terminal 1 to the positive outlet and terminal 2 to the negative outlet. Terminal 3 is for the power ground. This is separated from input ground by a galvanic isolation. A 2-core screened cable should be used with the screen connected to terminal 3. The size of conductors should be at least 1.25 mm2. The overall cable diameter should be between 7 & 12 mm.
3-3-5. Grounding the housing
ea
otect the instrument against inter
o pr
T
ence, the housing should be connected to gr
fer
ound by a lar
ge ar
conductor. This cable can be fixed to the rear of the housing using a braided wire cable. See figure 3-8.
3-3-6. Switching on the instrument
After all connections ar
e made and checked, the power can be switched on from the power supply. Make sure the LCD display comes on. All segments will illuminate, then the instr
ument will momentarily display its unique serial number. After a brief interval, the display will change to the measured value. If
e displayed or a valid measured value is not
ors ar
r
er shown, consult the troubleshooting section (Chapter
8) before calling Yokogawa.
Figure 3-8. Grounding the housing
IM 12B6B3-E-E
3-6 Installation and wiring
3-4. Wiring the contact signals
3-4-1. General precautions
The contact output signals consist of voltage-free relay contacts for switching electrical appliances (SPDT). They can also be used as digital outputs to signal processing equipment (such as a controller or PLC). It is possible to use multi-core cables for the contact in and output signals and shielded multi-core cable for the
nalog signals.
a
3-4-2. Contact outputs
The EXA unit’s four contact outputs can be wired to suit your own custom requirements (Figure 3-6).
In the Non-Alarm or Power Off states, contacts S1, S2 and S3 are OFF, Common (C) and Normally Closed (NC) are in contact.
In the “Fail” or Power Off states, contact S4 is ON, Common (C) and Normally Closed (NC) are in contact.
You can either use them to switch AC power, or switch a DC Voltage for digital interfacing. Default settings
l The contact S1 is pre-programmed for high alarm function. l The contact S2 is pre-programmed for a low alarm function. l The contact S3 is not activated as an alarm (off). l The contact S4 is pre-programmed for FAIL.
The three control contacts (S1 to S3) can be used for simple process control by programming their function (Chapter 5). The FAIL contact is programmed to signal a fault in the measuring loop. Always connect the FAIL contact to an alarm device such as a warning light, sound annunciator, or alarm panel to make full use of the fault detection possibilities (self diagnostics) of the EXA converter.
3-5. Wiring the analog output signals
3-5-1. General precautions
The analog output signals of the EXA transmit low power standard industry signals to peripherals like control systems or strip-chart recorders (Figure 3-6).
3-5-2. Analog output signals
The output signals consist of active current signals of either 0-20 mA or 4-20 mA. The maximum load can be 600 ohms on each.
It is necessary to use screening/shielding on the output signal cables. Terminal 63 is used to connect the shielding.
IM 12B6B3-E-E
Installation and wiring 3-7
3-6. Wiring the sensor system
3-6-1. Impedance measurement jumper settings
NOTE: It is important to decide first which application and which settings are appropriate for the installation. This decision is best done before the jumpers are installed, because the cables will rest on top of the jumpers in their installed positions.
able 3-1. Impedance measuring jumpers
T
Figure no. Jumper Settings Jumper Settings Application & Sensor Connections
Input #1 Input #2
1 High Impedance Low Impedance Normal pH sensors
Glass sensor on Input #1
Reference sensor on Input #2
2 High Impedance High Impedance Special electrodes using
2 glass sensors
(e.g. Pfaudler 18)
3 Low Impedance High Impedance ORP (pH compensated) and/or rH
metal sensor on Input #1
pH glass (as reference) on Input #2
4 Low Impedance Low Impedance ORP (Redox measurement)
metal sensor on Input #1
Normal reference on Input #2
The following four jumper figure illustrations (figure 3-9) show the jumper positions related to the figure numbers in the above table.
IM 12B6B3-E-E
3-8 Installation wiring
2
1
1
2D8B2-02
J
UMPERS 1&2
Default jumper connections for :
- Input 1, High impedance
- Input 2, Low impedance Service code 03 = 1.1.1
- Input 1, High impedance, Temp. comp., Check on Service code 04 = 0.0.1
- Input 2, Low impedance, Temp. comp. off, Check on
Jumper connections for :
- Input 1, High impedance
- Input 2, High impedance Service code 03 = 1.0.1
- Input 1, High impedance, Temp. comp. off, Check on vice code 04 = 1.0.1
Figure 3-9a. Impedance measurement jumper setting
IM 12B6B3-E-E
Ser
- Input 2, Low impedance, T
emp. comp. of
f, Check on
Installation and wiring 3-9
4
3
Jumper connections for :
- Input 1, Low impedance
- Input 2, High impedance Service code 03 = 0.0.1
- Input 1, Low impedance, Temp. comp. off, Check on Service code 04 = 1.1.1
- Input 2, High impedance, Temp. comp. on, Check on
Jumper connections for :
- Input 1, Low impedance
- Input 2, Low impedance vice code 03 = 0.0.1
Ser
- Input 1, Low impedance, Temp. comp. off, Check on
Figure 3-9b. Impedance measurement jumper setting
Service code 04 = 0.0.1
- Input 2, Low impedance, T
emp. comp. of
f, Check on
IM 12B6B3-E-E
3-10 Installation and wiring
71
S4
S3
S2
S1
C NC NO
72 73 51 52 53 41 43 31 334232
250V AC
5A
100V A
250VDC
5A
50W
100
115
230
24
250VAC; T
312
C NC NO C NC NO C NC NO
VAC
VAC
VAC
V
DC
100 mA
100 mA
50 mA
1 A
SCREEN
mA2
mA1 TL
RS485
15 16 17 13
1
4
12
11 22 21 63 66 65
6
2
61
9
5
94 93 92 91
SCREEN
TL
INPUT 1 L
OW IMP
INPUT 2 L
OW IMP
I
NPUT 2 H
IGH IMP
INPUT 1 H
IGH IMP
Sensor inputs
Sensor(s)
Contact input
Cont
mA outputs
mA output
Relay contacts Power supply
e 3-10. Terminal identification labels
Figur
3-7. Sensor wiring
Refer to figure 3-11, which includes drawings that outline sensor wiring.
Digital communications
Fuse
The EXA PH402 can be used with a wide range of commercially available sensor types, both from Yokogawa and other manufacturers. The sensor systems from Yokogawa fall into two categories; the ones that use a fixed cable and the ones with separate cables.
To connect sensors with fixed cables, simply match the terminal numbers in the instrument with the identification numbers in the instrument on the cable ends.
The separate sensors and cables are not numbered, but instead use a color-coding system. The electrodes have a colored band incorporated in the label on the connection cap:
l Red for measuring electrodes (both pH and ORP) l Yellow for reference electrodes l Blue for combined sensors with both measuring and reference elements in the same body l Green for temperature sensors
The recommended procedure is to color-code each end of the cables to match the sensors with the color strips provided with each cable. This provides a quick way to identify the ends of the cables belonging to a particular sensor when they are installed. (The procedure for fixing the identification labels is described in detail in the instruction sheet provided with the cable.)
IM 12B6B3-E-E
Installation and wiring 3-11
*
*
*
*
1
2B6B3-03/1
12B6B3-03/3
*
*
*
12B6B3-03/2
3-7-1. Connection cable
here are two types of connection cable, one for single sensors and one for combined sensors. The former
T is a coaxial cable and has only two connections.
l Red to measuring element l Blue to screen (shield)
he latter is a triaxial cable with three connections, (it has an extra white wire termination) these wires are
T connected:
l Red to measuring element l Blue to reference l White to screen (shield)
To connect the other sensor systems, follow the general pattern of the terminal connections as listed below: 11 & 12 Temperature compensation resistor input (Pt100, Pt1000, 3k, 5k1, 8k55 and 10k PTC ) 13 Input no. 2 (normally the reference element) 17 Screen (shield) for input no. 2 14 Liquid earth (solution ground) connection 15 Input no. 1 (normally the measuring element) 16
Screen (shield) for input no. 1
Green
Yellow
Red
Red
Blue
Red
Black
Red Blue Blue
Cable markers
pH transmitter
11 Temperature 12 Temperature 13 Reference 14 Solution ground 15 Glass (measure) 16 Shield 17 Shield
FU20/FU25 4-in one sensor
11 Temperature 12 Temperature 13 Reference 14 Solution ground 15 Glass (measure) 16 Shield 17
Note: Connect cables to similarly marked
terminals: 11 to 11, 12 to 12, etc.
een
Gr
Blue
Red
Blue Blue Black
Red
White
11 Temperature 12 T 13 Reference 14 Solution gr 15 Glass (measure) 16 Shield 17 Shield
emperature
ound
11 Temperature 12 Temperature
ence
13 Refer 14 Solution ground 15 Glass (measur 16 Shield 17 Shield
e)
Cable markers
Combined pH/r
ef sensors
Figure 3-11a. Sensor wiring
Retractable sensor assembly PR20
(Also PD20, PF20 & PS20)
NOTE: Connect cables to similarly marked ter to 11, 12 to 12, etc.
minals: 11
IM 12B6B3-E-E
3-12 Installation and wiring
11 TEMPERATURE
1
2 TEMPERATURE
13 REFERENCE
14 SOLUTION GROUND (ORP)
15 pH
16 SHIELD
17
"All in one" pH & ORP (or rH)
Service code 01 set to pH Service code 02 set to ORP (or rH)
S
eparate sensors ORP
Temp. sensors optional for indication o
nly, not for compensation
Service code 01 set to ORP
*
Cable Markers
R
ED
BLUE
RED
B
LACK
RED
BLUE
BLUE
Red
*
Yellow
*
Green
*
11 TEMPERATURE
1
2 TEMPERATURE
1
3 REFERENCE
1
4 SOLUTION GROUND
15 GLASS (MEASURE)
16 SHIELD
17 SHIELD
11 TEMPERATURE
1
2 TEMPERATURE
13 REFERENCE
1
4 SOLUTION GROUND
15 GLASS (MEASURE)
1
6 SHIELD
17 SHIELD
Separate sensors ORP/ref sensor
Temp. sensors optional for indication only, not for compensation Service code 01 set to ORP
*
C
able Markers
R
ED
BLUE
BLUE
B
LACK
R
ED
W
HITE
Blue
*
G
reen
*
Separate sensors pH & ORP (or rH)
Temp. sensors optional for indication only, not for compensation Service code 01 set to pH Service code 02 set to ORP (or rH)
*
Cable Markers
RED
BLUE
R
ED
BLACK
R
ED
B
LUE
B
LUE
R
ed
*
Yellow
*
Green
*
1
1 TEMPERATURE
1
2 TEMPERATURE
1
3 REFERENCE
14 METAL ORP SENSOR
15 GLASS (MEASURE)
16 SHIELD
17 SHIELD
1
1 TEMPERATURE
12 TEMPERATURE
13 REFERENCE
14 SOLUTION GROUND
1
5 GLASS (MEASURE)
16 SHIELD
17 SHIELD
Combined pH/ORP sensor
Temp. sensors optional for indication only, not for compensation Service code 01 set to ORP
*
Cable Markers
R
ED
BLUE
BLUE
BLACK
RED
WHITE
B
lue
*
Green
*
"All in one" ORP
Service code 01 set to ORP Service code 03 set to off Service code 04 set to off
11 TEMPERATURE
1
2 TEMPERATURE
13 REFERENCE
14 SOLUTION GROUND (ORP)
15 pH
16 SHIELD
17
11
12
1
3
14
16
15
>
Connections normal pH
A-15 B-13 C­D-14 E-11 F-12 S-3 or 63
pH
ref
LE
temp
>
Conn ecti ons differen tial pH
A-15 B-14 C-13 D-17 E-11 F-12 S-3 or 63
pH
pH ref
LE
temp
Figure 3-11b. Sensor wiring
IM 12B6B3-E-E
17 Overall Screen
11
12
12
13
14
14
16
15
13
14141615
17
11
17
11 Red
12 Blue
15 Core 16 Screen White Co-axial cable
13 Core 14 Screen Brown Co-axial Cable
14 (screen)
17 (overall screen)
12 (blue)
11 (red)
13 (core)
16 (screen)
15 (core)
Co-axial cable
(white)
Co-axial cable
(brown)
WF10 Cable
EXA pH TRANSMITTER / CONVERTER
11
12
13
14
15
16
17
11
12
13
17
15
16
14
Note that cables 14 & 17 connect to terminals 17 & 14 respectively.
Installation and wiring 3-13
3-7-2. Sensor cable connection with special grommet
In order to seal multiple sensor cables into EXA PH402, a special grommet is provided that is designed to accommodate one, two or three sensor cables (5 mm dia.) plus a liquid earth cable (2.5 mm dia.). In the
ack with the grommet are blanking pieces to close any unused holes. When correctly assembled, the
p grommet maintains the IP65 (NEMA 4X) rating of the EXA PH402 housing.
Refer to figure 3-12 to assemble the grommet connections:
1. First remove the nut and standard rubber seal from the selected gland . Discard the seal. This will be replaced later by the special grommet
2
3. Thread the cables through the nut and the gland
4. Connect the cables to their designated terminals
5. Arrange the cables to avoid tangles and insert the grommet between the gland and the nut
6. The grommet is split to permit the cables to be mounted after connection.
(This also ensures even length adjustment.)
7. Ensure that any unused holes are filled with the blanking pieces
8. Tighten the nut to form a firm seal. (Hand-tight is sufficient.)
Note: The special gland is intended to be used to seal the multiple cables from the Yokogawa flow fittings
such as FF20 and FP20. The designated cables are WU20 sensor cables, which are approximately 5 mm (0.2 “) in diameter, and 82895002 liquid earth cables, which are approximately 2.5 mm (0.1 “) in diameter.
For sensor systems using a single cable, like the FU20 (FU25) and the PR20, PD20, PF20 and PS20, the standard gland will accommodate the cable adequately. Single cables between approximately 7 mm and 12 mm (0.28 “ and 0.47 “) can be sealed properly with these glands.
3-7-3. Sensor cable connections using junction box (BA10) and extension cable (WF10)
Where a convenient installation is not possible using the standard cables between sensors and converter, a junction box and extension cable may be used. The Yokogawa BA10 junction box and the WF10 extension cable should be used. These items are manufactured to a very high standard and are necessary to ensure that the specifications of the system can be met. The total cable length should not exceed 50 metres (e.g. 5 m fixed cable and 45 m extension cable). In the case of systems using dual high impedance sensors (e.g. Pfaudler 18), then the cable length is restricted to 20 metres (fixed cable only, no extension with F10).
Fig. 3-12. Connection of WF10 extension cable and BA10/BP10 junction box
IM 12B6B3-E-E
3 cm
heat shrink
9
cm
remove insulation
3 cm
cotton threads
11 12
17
15
16 13
14
3-14 Installation and wiring
Extension cable may be purchased in bulk quantities or in pre-finished lengths. In the case of bulk quantities
ut to length, then it is necessary to terminate the cable as shown below.
c
Termination procedure for WF10 cable.
1. Slide 3 cm of heat shrink tube (9 x 1.5) over the cable end to be terminated.
2. Strip 9 cm of the outer (black) insulating material, taking care not to cut or damage internal cores.
Fig. 3-13a.
3. Remove loose copper screening, and cut off the cotton packing threads as short as possible.
4. Strip insulation from the last 3 cm of the brown, and the white coaxial cores.
Fig. 3-13b.
5. Extract the coaxial cores from the braid, and trim off the black (low-noise) screening material as short as possible.
6. Insulate the overall screen and the 2 coaxial screens with suitable plastic tubing.
7. Strip and terminate all ends with suitable (crimp) terminals and identify with numbers as shown.
Fig. 3-13.c
8. Finally shrink the overall heat shrink tube into position.
IM 12B6B3-E-E
Installation and wiring 3-15
Figure 3-14. Sensor cable connections with special grommet
3-8. Tag plate mounting
When option /SCT is specified, a stainless steel tagplate is supplied with the designated Tag No. stamped or engraved. It is mounted as shown in figure 3-14 using one of the cable glands.
IM 12B6B3-E-E
IM 12B6B3-E-E
Operation 4-1
4. OPERATION; DISPLAY FUNCTIONS AND SETTING
4-1. Operator interface
This section provides an overview of the operation of the EXA operator interface. The basic procedures for obtaining access to the three levels of operation are described briefly. For a step-by-step guide to data entry, refer to the relevant section of this instruction manual. Figure 4-1 shows the EXA operator interface.
LEVEL 1: Maintenance
These functions are accessible by pushbutton through a flexible front cover window. The functions make up the normal day-to-day operations that an operator may be required to complete. Adjustment of the display and routine calibration are among the features accessible in this way. (See table 4-1).
LEVEL 2: Commissioning
A second menu is exposed when the EXA front cover is removed and the display board is revealed. Users gain access to this menu by pressing the button marked *in the lower right of the display board. This menu is used to set such values as the output ranges and hold and wash features. It also gives access to the service menu. (See table 4-1).
LEVEL 3: Service
For more advanced configuration selections, press the button marked *, then press “NO” repeatedly until you reach SERVICE. Now push the “YES” button. Selecting and entering “Service Code” numbers in the commissioning menu provide access to the more advanced functions. An explanation of the Service Codes is listed in chapter 5 and an overview table is shown in chapter 10.
Table 4-1. Operations overview
Routine Function Chapter
Maintenance AUT CAL Calibration with programmed buffer solutions 6
MAN CAL Calibration with other buffer solutions 6
SAMPLE Grab sample calibration 6
DISPLAY Read auxiliary data or set message display 4
SETPOINTS Adjust alarm setpoints (when activated) 5
WASH Manual wash start (when activated) 5
MAN.IMP Manual start of impedance check 5
TEMPERATURE Select automatic or manual compensation 5
HOLD Switch hold on/off (when activated) 5
Commissioning SETPOINTS Adjust alarm setpoints 5
RANGE Adjust the output range 5
SET HOLD Activate the hold function 5
WASH Activate and configure the wash timer 5
Service SERVICE Fine tune the specialized functions of the 5
(Access to coded entries converter
from the commissioning
level)
NOTE: All three levels may be separately protected by a password. See Service Code 52 in chapter 5 Service Code table for details on setting passwords.
IM 12B6B3-E-E
4-2 Operation
HOLD FAIL
YES NO
ENT
SETPOINTS RANGE SET HOLD
SERVIC
E
*
MEASURE
MAN.CAL DISPLAY
HOLD
NO MODEYES
ENT
YOKOGAWA
M
ODE
TEMPERATURE
AUT.CAL
WASH
TEMP.MAN.
pH
mV
C
ONTACTS
S
1
S2
WASH/S3
FAIL/S4
Output hold flag
Units
Main display
Message display
Key prompt flags
Selection keys YES : Accept setting NO : Change setting
Adjustment keys > : Choose digit to
adjust ^ : Adjust digit ENT : Confirm change
Manual temperature compensation flag
Figure 4-1. PH402 operator interface
Fail flag
Broken line indicates area that can be seen through front cover
Menu pointer flags
ommissioning
C function menu
Commissioning
ode access key
m
Relay contact status indicators
Measure/Maintenance mode key
4-2. Explanation of operating keys MODE key
This key toggles between the measuring and maintenance modes. Press once to obtain access to the maintenance function menu.
Press again to return to the measuring mode (press twice when hold is activated).
YES/NO keys These ar
YES is used to accept a menu selection. NO is used to reject a selection, or to move ahead to the next option.
DA
T
A ENTRY keys ( )
is used as a “cursor” key. Each press on this key moves the cursor or flashing digit one place to the right. This is used to select the digit to be changed when entering numerical data. is used to change the value of a selected digit. Each pr value by one unit.The value can not be decr incr
key This is the commissioning mode key
*
IM 12B6B3-E-E
When the r data entr the ENT key is pressed.
menu. This can only be done with the cover r been used to initiate the commissioning menu, follow the pr as described above.
AUTO CAL MAN CAL DISPLAY SETPOINT WASH MAN.IMP TEMPERA
TURE
HOLD
e used to select choices fr
ease past nine to zer
o, then incr
equired value has been set using the > & ^ keys, press ENT to confirm the
. Please note that the EXA 402 does not r
y
om the menu.
ess on this key increases the
eased, so in order to obtain a lower value,
ease to the r
equir
ed number
.
egister any change of data until
. It is used to obtain access to the commissioning
emoved or opened. Once this button has
ompts and use the other keys
Operation 4-3
4-3. Setting passcodes
4-3-1. Passcode protection
In Service Code 52, EXA users can set passcode protection for each one of the three operating levels, or for any one or two of the three levels. This procedure should be completed after the initial commissioning (setup) of the instrument. The passcodes should then be recorded safely for future reference.
When passcodes have been set, the following additional steps are introduced to the configuration and programming operations:
Maintenance
Press MODE key. The display shows 000 and *PASS* Enter a 3-digit passcode as set in Service Code 52 to obtain access to the Maintenance Mode
Commissioning
Press *key. The display shows 000 and *PASS* Enter a 3-digit passcode as set in Service Code 52 to obtain access to the Commissioning Mode.
Service
From the commissioning menu, select *Service by pressing YES key. The display shows 000 and *PASS* Enter a 3-digit passcode as set in Service Code 52 to obtain access to the Service Mode.
NOTE: See Service Code 52 for the setting of passcodes.
4-4. Display examples
The following pages show the sequence of button presses and screens displayed when working in some standard configurations.
More or less options will be made available by the configuration of some service codes. For instance the impedance measurement screens do not appear when impedance checking is switched off in service codes 03 and 04.
IM 12B6B3-E-E
NO
Y
ES
pH
p
H
pH
YES
pH
YES
NO
pH
pH
pH
YES
(See Temp menu Chapter 5)
Y
ES NO
TEMP.
M
ODE
N
O
YES
YES
NO
NO
NO
(See Auto calibration Chapter 6)
(See Manual calibration Chapter 6)
Y
ES
N
O
YES NO
Y
ES NO
MEASURE
MAN.CAL DISPLAY
HOLD
TEMP.
AUT.CAL
MAN.CAL
DISPLAY
AUT.CAL
MAN.CAL
(See Sample calibration Chapter 6)
SETPOINTS RANGE SET HOLD
SERVICE
*
WASH
HOLD FAIL
YES NO
ENT
MEASURE
MAN.CAL DISPLAY
HOLD
NO MODEYES
ENT
YOKOGAWA
MODE
TEMPERATURE
AUT.CAL
TEMP.MAN.
pH
mV
CONTACTS
S1
S2
WASH/S3
FAIL/S4
pH
pH
pH
pH
pH
pH
pH
pH
NO
NO
NO
NO
NO
NO
NO
NO
Display Access
Impedance of input 1
Impedance of input 2
Process temperature
Current output 1
Current output 2
Software release number
Offset (as. pot. or zero point)
Efficiency
(slope)
Press YES to fix
the selected second
line of display
YES
YES
NO
Y
ES
N
O
YES
NO
Y
ES
N
O
Y
ES
NO
Y
ES
NO
YES
NO
YES
NO
DISPLAY
DISPLAY
DISPLAY
DISPLAY
DISPLAY
DISPLAY
DISPLAY
DISPLAY
12B6B3-21
D
isplay Functions pH (Default)
NO
YES
(See Manual Impedance check Chapter 5)
NO
4-4 Operation
4-5. Display functions
4-5-1. Display functions pH (default)
IM 12B6B3-E-E
pH
pH
1
2B6B3-19
p
H
pH
T
EMP.
See Setpoint Menu chapter 5.5
See Wash Menu chapter 5.4
pH
NO
NO
NO
YES
YES
pH
pH
YES
NO
YES
NO
TEMP.
HOLD
HOLD
YES
NO
YES
NO
NO
DATE
pH
pH
pH
TIME
CAL -1
VALUE
Display Fuctions pH (ORP)
Service Code 01 Set for pH. Service Code 02 Set for ORP on parameter 2.
DISPLAY
D
ISPLAY
D
ISPLAY
D
ISPLAY
D
ISPLAY
"Logbook Scrolling"
The display can give information
about calibrations performed
with date and time.
The example below shows
A
symmetry Potential.
S
crolling of Data is also
available on Slope.
As Pot ORP Impedance Input 1 Impedance Input 2
When these functions are enabled in Service
Codes.
Measuring Mode
As Pot
Display 2
Back to the Top
p
H
Y
ES
NO
D
ISPLAY
DISPLAY
DISPLAY
DISPLAY
DISPLAY
DISPLAY
DISPLAY
D
ISPLAY
DISPLAY
D
ISPLAY
YES
NO
NO
NO
NO
NO
NO
NO
NO
N
O
p
H
NO
MODE
NO
NO
Y
ES
YES
YES
YES
YES
YES
YES
YES
NO
NO
NO
NO
pH
p
H
pH
pH
Y
ES
NO
Y
ES
NO
YES
NO
YES
NO
Y
ES
NO
YES
NO
YES
NO
pH
p
H
pH
pH
pH
pH
pH
pH
pH
MAN.CAL
MEASURE
M
AN.CAL
D
ISPLAY
HOLD
T
EMP.
A
UT.CAL
A
UT.CAL
D
ISPLAY
YES
NO
YES
NO
YES
N
O
YES
NO
YES
NO
YES
NO
YES NO
ENT
YES NO
ENT
Y
ES NO
E
NT
Y
ES NO
ENT
YES NO
ENT
NO
NO
YES
p
H
NO
YES
YES
See Temp Menu chapter 5
See Hold Menu chapter 5
YES
See Man. Imp. Check chapter 5
4-5-2. Display functions pH (ORP)
Operation 4-5
IM 12B6B3-E-E
Loading...
+ 67 hidden pages