Yokogawa FVX110 User Manual

User’s Manual
FVX110 Fieldbus Segment Indicator
IM 01S01C01-01EN
IM 01S01C01-01EN
2nd Edition
FVX110 Fieldbus Segment Indicator
IM 01S01C01-01EN 2nd Edition

Contents

1. Introduction ............................................................................................... 1-1
Regarding This Manual ................................................................................................1-1
1.1 Safe Use of This Product .................................................................................1-1
1.2 Warranty .............................................................................................................1-2
1.3 ATEX Documentation .......................................................................................1-3
2. Handling Cautions .................................................................................... 2-1
2.1 Model and Specications Check .....................................................................2-1
2.2 Unpacking ..........................................................................................................2-1
2.3 Storage ...............................................................................................................2-1
2.4 Selecting the Installation Location ................................................................2-1
2.5 Waterproong of Cable Conduit Connections ..............................................2-2
2.6 Restrictions on Use of Radio Transceivers ...................................................2-2
2.7 Insulation Resistance and Dielectric Strength Test ......................................2-2
2.8 Installation of an Explosion-Protected Instrument .......................................2-3
2.8.1 FM approval .......................................................................................2-3
2.8.2 CSA Certication ................................................................................2-7
2.8.3 CENELEC ATEX Certication ..........................................................2-10
2.8.4 IECEx Certication ...........................................................................2-13
i
3. Component Names .................................................................................. 3-1
4. About Fieldbus ......................................................................................... 4-1
4.1 Outline ................................................................................................................4-1
4.2 Internal Structure of FVX110 ............................................................................4-1
4.2.1 System/network Management VFD ..................................................4-1
4.2.2 Function Block VFD ...........................................................................4-1
4.3 Logical Structure of Each Block .....................................................................4-2
4.4 Wiring System Conguration ..........................................................................4-2
5. Installation ................................................................................................. 5-1
5.1 Precautions .......................................................................................................5-1
5.2 Mounting ...........................................................................................................5-1
5.3 Wiring .................................................................................................................5-2
5.3.1 Wiring Precautions .............................................................................5-2
5.3.2 Wiring Installation ...............................................................................5-2
5.4 Grounding ..........................................................................................................5-3
2nd Edition: July 2011(YK) All Rights Reserved, Copyright © 2010, Yokogawa Electric Corporation
5.5 Connection of Devices .....................................................................................5-3
5.6 Host Setting .......................................................................................................5-4
5.7 Bus Power ON ...................................................................................................5-5
5.8 Integration of DD ...............................................................................................5-6
5.9 Set the Parameters Using DTM .......................................................................5-6
5.10 Continuous Record of Values ..........................................................................5-6
5.11 Generation of Alarm ..........................................................................................5-6
6. Conguration ............................................................................................ 6-1
6.1 Network Design .................................................................................................6-1
6.2 Network Denition ............................................................................................6-2
6.3 Denition of Combining Function Blocks ......................................................6-3
6.4 Setting of Tags and Addresses .......................................................................6-4
6.5 Communication Setting ...................................................................................6-4
6.5.1 VCR Setting .......................................................................................6-4
6.5.2 Function Block Execution Control ......................................................6-6
6.6 Block Setting ..................................................................................................... 6-6
6.6.1 Link Object .........................................................................................6-6
6.6.2 Trend Object ......................................................................................6-7
6.6.3 View Object ........................................................................................6-7
6.6.4 Function Block Parameters..............................................................6-10
ii
7. Explanation of Basic Items...................................................................... 7-1
7.1 Outline ................................................................................................................ 7-1
7.2 Setting and Changing Parameters for the Whole Process ..........................7-1
7.3 LCD Transducer Block ....................................................................................7-1
7.3.1 Function Outline .................................................................................7-1
7.3.2 Operating mode .................................................................................7-1
7.3.3 Indicator names and functions ...........................................................7-1
7.3.4 Communication status indication .......................................................7-2
7.3.5 Indicator settings ................................................................................7-4
7.3.6 Other display settings ........................................................................7-7
7.3.7 Flow chart of indicator settings ..........................................................7-8
7.3.8 Units the auto link function allows you to display on the LCD ...........7-9
8. Explanation of Basic Items (switching displays) .................................. 8-1
8.1 Single Scroll Mode ............................................................................................8-1
8.2 Continuous Scroll Mode (scan mode) ............................................................ 8-2
8.3 Direction of Display Switching ........................................................................8-2
9. In-Process Operation ............................................................................... 9-1
9.1 Mode Transition ................................................................................................9-1
9.2 Generation of Alarm ..........................................................................................9-1
9.2.1 Indication of Alarm..............................................................................9-1
9.2.2 Alarms and Events .............................................................................9-1
9.2.3 Standard categories for NAMUR NE-107 instrument diagnostics
alarms ................................................................................................9-2
9.3 Device Diagnostic Simulation Function .........................................................9-4
9.4 Write lock (Write-protect) function ..................................................................9-5
10. Maintenance ............................................................................................10-1
10.1 Overview ..........................................................................................................10-1
10.2 Disassembly and Reassembly ......................................................................10-1
10.2.1 Replacing the display .......................................................................10-1
10.2.2 Replacing the CPU Board Assembly ...............................................10-2
11. Device Information ................................................................................. 11-1
11.1 DEVICE STATUS ..............................................................................................11-1
11.2 Status of Each Parameter in Failure Mode ................................................... 11-3
12. Parameter Lists....................................................................................... 12-1
12.1 Resource Block ...............................................................................................12-1
12.2 LCD Transducer Block ...................................................................................12-4
13. General Specications .......................................................................... 13-1
13.1 Functional Specications ..............................................................................13-1
13.2 Physical Specications ..................................................................................13-2
13.3 Model and Sufx Codes .................................................................................13-2
13.4 Optional Specications (For Explosion Protected type) ............................13-3
13.5 Optional Specications ..................................................................................13-4
13.6 Dimensions ......................................................................................................13-5
iii
Appendix 1. Signal Characterizer (SC) Block .............................................A1-1
A1.1 Schematic Diagram of Signal Characterizer Block .................................... A1-1
A1.2 Input Section .................................................................................................. A1-2
A1.2.1 Determining the Mode .....................................................................A1-2
A1.2.2 Judging BLOCK_ERR .....................................................................A1-2
A1.3 Line-segment Factor Determination Section .............................................. A1-3
A1.3.1 Conditions for Conguring Valid Coefcients
(CURVE_X, CURVE_Y) ..................................................................A1-3
A1.4 List of Signal Characterizer Block Parameters .......................................... A1-5
A1.5 Application Example ..................................................................................... A1-6
A1.5.1 Input Compensation .........................................................................A1-6
A1.5.2 Calorie Flow Compensation ............................................................A1-6
A1.5.3 Backward Control ............................................................................A1-7
Appendix 2. Integrator (IT) Block .................................................................A2-1
A2.1 Schematic Diagram of Integrator Block ..................................................... A2-1
A2.2 Input Process Section ................................................................................... A2-2
A2.2.1 Determining Input Value Statuses ...................................................A2-2
A2.2.2 Converting the Rate .........................................................................A2-2
A2.2.3 Converting Accumulation .................................................................A2-3
A2.2.4 Determining the Input Flow Direction...............................................A2-3
A2.3 Adder ............................................................................................................... A2-3
A2.3.1 Status of Value after Addition ...........................................................A2-3
A2.3.2 Addition ............................................................................................A2-4
A2.4 Integrator ........................................................................................................ A2-4
A2.5 Output Process .............................................................................................. A2-5
A2.5.1 Status Determination .......................................................................A2-5
A2.5.2 Determining the Output Value ..........................................................A2-6
A2.5.3 Mode Handling ................................................................................A2-7
A2.6 Reset ................................................................................................................ A2-7
A2.6.1 Reset Trigger....................................................................................A2-7
A2.6.2 Reset Timing ....................................................................................A2-8
A2.6.3 Reset Process ..................................................................................A2-8
A2.7 List of Integrator Block Parameters ............................................................. A2-9
Appendix 3. Input Selector (IS) Block ..........................................................A3-1
A3.1 Input Selector Function Block Schematic .................................................. A3-1
A3.2 Input Section .................................................................................................. A3-3
A3.2.1 Mode Handling ................................................................................A3-3
A3.2.2 MIN_GOOD Handling .....................................................................A3-4
A3.3 Selection ........................................................................................................ A3-5
A3.3.1 OP_SELECT Handling ...................................................................A3-5
A3.3.2 SELECTION Handling ....................................................................A3-6
A3.4 Output Processing ...................................................................................... A3-12
A3.4.1 Handling of SELECTED ................................................................A3-12
A3.4.2 OUT Processing ............................................................................A3-13
A3.4.3 STATUS_OPTS ............................................................................A3-14
A3.5 List of Input Selector Block Parameters ................................................... A3-14
A3.6 Application Example ................................................................................... A3-16
iv
Appendix 4. Arithmetic (AR) Block .............................................................A4-1
A4.1 Arithmetic Function Block Schematic ........................................................ A4-1
A4.2 Input Section .................................................................................................. A4-2
A4.2.1 Main Inputs ......................................................................................A4-2
A4.2.2 Auxiliary Inputs ................................................................................A4-2
A4.2.3 INPUT_OPTS .................................................................................A4-3
A4.2.4 Relationship between the Main Inputs and PV ...............................A4-3
A4.3 Computation Section .................................................................................... A4-4
A4.3.1 Computing Equations .....................................................................A4-4
A4.3.2 Compensated Values ......................................................................A4-4
A4.3.3 Average Calculation ........................................................................A4-4
A4.4 Output Section .............................................................................................. A4-4
A4.4.1 Mode Handling ................................................................................A4-5
A4.4.2 Status Handling ...............................................................................A4-5
A4.5 List of the Arithmetic Block Parameters ..................................................... A4-6
Appendix 5. PID Block ...................................................................................A5-1
A5.1 Function Diagram .......................................................................................... A5-1
A5.2 Functions of PID Block .................................................................................. A5-1
A5.3 Parameters of PID Block ............................................................................... A5-2
A5.4 PID Computation Details ............................................................................... A5-5
A5.4.1 PV-proportional and -derivative Type PID (I-PD) Control Algorithm
.........................................................................................................A5-5
A5.4.2 PID Control Parameters ...................................................................A5-5
A5.5 Control Output ................................................................................................ A5-5
A5.5.1 Velocity Type Output Action .............................................................A5-5
A5.6 Direction of Control Action ........................................................................... A5-5
A5.7 Control Action Bypass .................................................................................. A5-6
A5.8 Feed-forward .................................................................................................. A5-6
A5.9 Block Modes ................................................................................................... A5-6
A5.9.1 Mode Transitions ..............................................................................A5-6
A5.10 Bumpless Transfer ......................................................................................... A5-7
A5.11 Setpoint Limiters ............................................................................................ A5-7
A5.11.1 When PID Block Is in Auto Mode .....................................................A5-7
A5.11.2 When PID Block Is in Cas or RCas Mode .......................................A5-7
A5.12 External-output Tracking .............................................................................. A5-8
A5.13 Measured-value Tracking .............................................................................. A5-8
A5.14 Initialization and Manual Fallback (IMan) .................................................... A5-8
A5.15 Manual Fallback ............................................................................................. A5-9
A5.16 Auto Fallback .................................................................................................. A5-9
A5.17 Mode Shedding upon Computer Failure ..................................................... A5-9
A5.17.1 SHED_OPT......................................................................................A5-9
A5.18 Alarms ........................................................................................................... A5-10
A5.18.1 Block Alarm (BLOCK_ALM) ...........................................................A5-10
A5.18.2 Process Alarms ..............................................................................A5-10
A5.19 Example of Block Connections .................................................................. A5-10
A5.20 View Object for PID Function Block ............................................................A5-11
v
Appendix 6. Multiple Analog Output (MAO) Block ....................................A6-1
A6.1 Function Block Diagram ............................................................................... A6-1
A6.2 Block Mode ..................................................................................................... A6-2
A6.3 Fault State ....................................................................................................... A6-3
A6.3.1 Transition to Fault State ...................................................................A6-3
A6.3.2 Clearing a Fault State ......................................................................A6-3
A6.3.3 Fault State Operation .......................................................................A6-3
A6.4 Status Transitions .......................................................................................... A6-4
A6.5 Parameter list display .................................................................................... A6-4
Appendix 7. Link Master Functions .............................................................A7-1
A7.1 Link Active Scheduler.................................................................................... A7-1
A7.2 Link Master ..................................................................................................... A7-1
A7.3 Transfer of LAS .............................................................................................. A7-2
A7.4 LM Functions .................................................................................................. A7-3
A7.5 LM Parameters ............................................................................................... A7-4
A7.5.1 LM Parameter List ............................................................................A7-4
A7.5.2 Descriptions for LM Parameters ......................................................A7-6
A7.6 FAQs ................................................................................................................ A7-8
Appendix 8. Software Download ..................................................................A8-1
A8.1 Benets of Software Download .................................................................... A8-1
A8.2 Specications ................................................................................................. A8-1
A8.3 Preparations for Software Downloading ..................................................... A8-1
A8.4 Software Download Sequence ..................................................................... A8-2
A8.5 Download Files ............................................................................................... A8-2
A8.6 Steps after Activating a Field Device ........................................................... A8-3
A8.7 Troubleshooting ............................................................................................. A8-3
A8.8 Resource Block’s Parameters Relating to Software Download ............... A8-4
A8.9 System/Network Management VFD Parameters Relating to Software
Download ........................................................................................................ A8-5
A8.10 Comments on System/Network Management VFD Parameters Relating to
Software Download ....................................................................................... A8-6
vi
Revision Information ...............................................................................................i
<1. Introduction>

1. Introduction

1-1
Thank you for purchasing the FVX110 Fieldbus Segment Indicator.
Your FVX110 Fieldbus Segment Indicator was precisely calibrated at the factory before shipment. To ensure both safety and efciency, please read this manual carefully before you operate the instrument.
Model Style code
FVX110 S1

Regarding This Manual

• This manual should be provided to the end user.
• The contents of this manual are subject to change without prior notice.
• All rights reserved. No part of this manual may be reproduced in any form without Yokogawa’s written permission.
• Yokogawa makes no warranty of any kind with regard to this manual, including, but not limited to, implied warranty of merchantability and tness for a particular purpose.
• If any question arises or errors are found, or if any information is missing from this manual, please inform the nearest Yokogawa sales ofce.
• If the customer or any third party is harmed by the use of this product, Yokogawa assumes no responsibility for any such harm owing to any defects in the product which were not predictable, or for any indirect damages.
• The following safety symbols are used in this manual:
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death or serious injury.
CAUTION
Indicates a potentially hazardous situation which, if not avoided, may result in minor or moderate injury. It may also be used to alert against unsafe practices.
IMPORTANT
Indicates that operating the hardware or software in this manner may damage it or lead to system failure.
• The specications covered by this manual are limited to those for the standard type under the specied model number break-down and do not cover custom-made instruments.
• Please note that changes in the specications, construction, or component parts of the instrument may not immediately be reected in this manual at the time of change, provided that postponement of revisions will not cause difculty to the user from a functional or performance standpoint.
• Yokogawa assumes no responsibility for this product except as stated in the warranty.
NOTE
Draws attention to information essential for understanding the operation and features.
Direct current

1.1 Safe Use of This Product

For the safety of the operator and to protect the instrument and the system, please be sure to follow this manual’s safety instructions when handling this instrument. If these instructions are not heeded, the protection provided by this instrument may be impaired. In this case, Yokogawa cannot guarantee that the instrument can be safely operated. Please pay special attention to the following points:
<1. Introduction>
1-2
(a) Installation
• This instrument may only be installed by an engineer or technician who has an expert knowledge of this device. Operators are not allowed to carry out installation unless they meet this condition.
• All installation shall comply with local installation requirements and the local electrical code.
(b) Wiring
• The instrument must be installed by an engineer or technician who has an expert knowledge of this instrument. Operators are not permitted to carry out wiring unless they meet this condition.
• Before connecting the power cables, please conrm that there is no current owing through the cables and that the power supply to the instrument is switched off.
(c) Operation
• Wait 5 min. after the power is turned off, before opening the covers.
(d) Maintenance
• Please carry out only the maintenance procedures described in this manual. If you require further assistance, please contact the nearest Yokogawa ofce.
• Care should be taken to prevent the build up of dust or other materials on the display glass and the name plate. To clean these surfaces, use a soft, dry cloth.
(e) Explosion Protected Type Instrument
• Users of explosion proof instruments should refer rst to section 2.8 (Installation of an Explosion Protected Instrument) of this manual.
• The use of this instrument is restricted to those who have received appropriate training in the device.
• Take care not to create sparks when accessing the instrument or peripheral devices in a hazardous location.
(f) Modication

1.2 Warranty

• The warranty shall cover the period noted on the quotation presented to the purchaser at the time of purchase. Problems occurring during the warranty period shall basically be repaired free of charge.
• If any problems are experienced with this instrument, the customer should contact the Yokogawa representative from which this instrument was purchased or the nearest Yokogawa ofce.
• If a problem arises with this instrument, please inform us of the nature of the problem and the circumstances under which it developed, including the model specication and serial number. Any diagrams, data and other information you can include in your communication will also be helpful.
• The party responsible for the cost of xing the problem shall be determined by Yokogawa following an investigation conducted by Yokogawa.
• The purchaser shall bear the responsibility for repair costs, even during the warranty period, if the malfunction is due to:
- Improper and/or inadequate maintenance by
the purchaser.
- Malfunction or damage due to a failure
to handle, use, or store the instrument in accordance with the design specications.
- Use of the product in question in a location
not conforming to the standards specied by Yokogawa, or due to improper maintenance of the installation location.
- Failure or damage due to modication or
repair by any party except Yokogawa or an approved representative of Yokogawa.
- Malfunction or damage from improper
relocation of the product in question after delivery.
- Reason of force majeure such as res,
earthquakes, storms/oods, thunder/ lightening, or other natural disasters, or disturbances, riots, warfare, or radioactive contamination.
• Yokogawa will not be liable for malfunctions or damage resulting from any modication made to this instrument by the customer.
<1. Introduction>

1.3 ATEX Documentation

This is only applicable to the countries in European Union.
1-3
GB
DK
E
NL
SK
CZ
I
LT
LV
EST
PL
SF
P
F
D
S
SLO
H
BG
RO
M
GR
<2. Handling Cautions>

2. Handling Cautions

2-1
This chapter provides important information on how to handle the indicator. Read this carefully before using the indicator.
FVX110 Fieldbus Segment Indicator thoroughly tested at the factory before shipment. When taking delivery of an instrument, visually check them to make sure that no damage occurred during shipment.
Also check that all indicator mounting hardware shown in gure 2.1 is included. If the indicator is ordered without the mounting bracket the indicator mounting hardware will not be included. After checking the indicator, carefully repack it in its box and keep it there until you are ready to install it.
U-bolt nut (L)
Mounting bracket
U-bolt nut (S)
U-bolt (S)
U-bolt (L)
F0201.ai
Figure 2.1 Indicator Mounting Hardware
2.1 Model and Specications Check
The model name and specications are written on the name plate attached to the case.
MODEL
SUFFIX
SUPPLY OUTPUT
Figure 2.2 Name Plate
STYLE
NO.
F0202.ai

2.2 Unpacking

Keep the indicator in its original packaging to prevent it from being damaged during shipment. Do not unpack the indicator until it reaches the installation site.

2.3 Storage

The following precautions must be observed when storing the instrument, especially for a long period.
(a) Select a storage area which meets the following
conditions:
• It is not exposed to rain or subject to water seepage/leaks.
• Vibration and shock are kept to a minimum.
• It has an ambient temperature and relative humidity within the following ranges.
Storage ambient temperature: –30 to 80°C Relative humidity: 0% to 100% R.H. Preferred temperature and humidity: approx. 25°C and 65% R.H.
(b) When storing the indicator, repack it carefully
in the packaging that it was originally shipped with.

2.4 Selecting the Installation Location

The indicator is designed to withstand severe environmental conditions. However, to ensure that it will provide years of stable and accurate performance, take the following precautions when selecting the installation location.
(a) Ambient Temperature
Avoid locations subject to wide temperature variations or a signicant temperature gradient. If the location is exposed to radiant heat from plant equipment, provide adequate thermal insulation and/or ventilation.
(b) Ambient Atmosphere
Do not install the indicator in a corrosive atmosphere. If this cannot be avoided, there must be adequate ventilation as well as measures to prevent the leaking of rain water and the presence of standing water in the conduits.
<2. Handling Cautions>
2-2
(c) Shock and Vibration
Although the indicator is designed to be relatively resistant to shock and vibration, an installation site should be selected where this is kept to a minimum.
(d) Installation of Explosion-protected Indicators
An explosion-protected indicators is certied for installation in a hazardous area containing specic gas types. See subsection 2.8 “Installation of an Explosion-Protected Indicators.”
2.5 Waterproong of Cable Conduit Connections
Apply a non-hardening sealant to the threads to waterproof the indicator cable conduit connections. (See gure 5.2, 5.3 and 5.4.)

2.6 Restrictions on Use of Radio Transceivers

IMPORTANT
Although the indicator has been designed to resist high frequency electrical noise, if a radio transceiver is used near the indicator or its external wiring, the indicator may be affected by high frequency noise pickup. To test this, start out from a distance of several meters and slowly approach the indicator with the transceiver while observing the measurement loop for noise effects. Thereafter use the transceiver outside the range where the noise effects were rst observed.

2.7 Insulation Resistance and Dielectric Strength Test

Since the indicator has undergone insulation resistance and dielectric strength tests at the factory before shipment, normally these tests are not required. If the need arises to conduct these tests, heed the following:
(a) Do not perform such tests more frequently than
is absolutely necessary. Even test voltages that do not cause visible damage to the insulation may degrade the insulation and reduce safety margins.
(b) Never apply a voltage exceeding 500 V DC
(100 V DC with an internal lightning protector) for the insulation resistance test, nor a voltage exceeding 500 V AC (100 V AC with an internal lightning protector) for the dielectric strength test.
(c) Before conducting these tests, disconnect all
signal lines from the indicator terminals. The procedure for conducting these tests is as follows:
• Insulation Resistance Test
1) Short-circuit the + and – SUPPLY terminals in the terminal box.
2) Turn OFF the insulation tester. Then connect the insulation tester plus (+) lead wire to the shorted SUPPLY terminals and the minus (–) leadwire to the grounding terminal.
3) Turn ON the insulation tester power and measure the insulation resistance. The voltage should be applied as briey as possible to verify that the insulation resistance is at least 20 MΩ.
4) After completing the test and being very careful not to touch exposed conductors disconnect the insulation tester and connect a 100 kΩ resistor between the grounding terminal and the short­circuiting SUPPLY terminals. Leave this resistor connected at least one second to discharge any static potential. Do not touch the terminals while it is discharging.
• Dielectric Strength Test
1) Short-circuit the + and – SUPPLY terminals in the terminal box.
2) Turn OFF the dielectric strength tester. Then connect the tester between the shorted SUPPLY terminals and the grounding terminal. Be sure to connect the grounding lead of the dielectric strength tester to the ground terminal.
3) Set the current limit on the dielectric strength tester to 10 mA, then turn ON the power and gradually increase the test voltage from ‘0’ to the specied voltage.
4) When the specied voltage is reached, hold it for one minute.
5) After completing this test, slowly decrease the voltage to avoid any voltage surges.
<2. Handling Cautions>
2-3
2.8 Installation of an Explosion­Protected Instrument
If a customer makes a repair or modication to an intrinsically safe or explosionproof instrument and the instrument is not restored to its original condition, its intrinsically safe or explosionproof construction may be compromised and the instrument may be hazardous to operate. Please contact Yokogawa before making any repair or modication to an instrument.
CAUTION
This instrument has been tested and certied as being intrinsically safe or explosionproof. Please note that severe restrictions apply to this instrument’s construction, installation, external wiring, maintenance and repair. A failure to abide by these restrictions could make the instrument a hazard to operate.
WARNING
Maintaining the safety of explosionproof equipment requires great care during mounting, wiring, and piping. Safety requirements also place restrictions on maintenance and repair. Please read the following sections very carefully.

2.8.1 FM approval

a. FM Explosionproof Type
Caution for FM Explosionproof type
Note 1. FVX110 Fieldbus Segment Indicator with
optional code /FF1 is applicable for use in hazardous locations:
• Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250
• Explosionproof for Class I, Division 1, Groups B, C and D.
• Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G.
• Enclosure rating: NEMA 4X.
• Temperature Class: T6
• Ambient Temperature: –40* to 60ºC
* –15ºC when O-ring material is Fluoro-rubber.
• Supply Voltage: 32V dc max.
• Current Draw: 15 mA
Note 2. Wiring
• All wiring shall comply with National Electrical Code ANSI/NFPA70 and Local Electrical Codes.
• When installed in Division 1, “FACTORY SEALED, CONDUIT SEAL NOT REQUIRED.”
Note 3. Operation
• Keep the “WARNING” nameplate attached to the indicator.
WARNING: OPEN CIRCUIT BEFORE
REMOVING COVER. FACTORY SEALED, CONDUIT SEAL NOT REQUIRED. INSTALL IN ACCORDANCE WITH THE USERS MANUAL IM 01S01C01.
• Take care not to generate mechanical sparking when accessing the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void Factory Mutual Explosionproof Approval.
<2. Handling Cautions>
2-4
b. FM Intrinsically safe and Nonincendive
Type
FVX110 Fieldbus Segment Indicator with optional code /FS15.
Applicable standard: FM3600, FM3610,
• FM3611, FM3810, ANSI/NEMA250, ISA60079-27
• FM Intrinsically Safe Approval
[Entity Model] Class I, II & III, Division 1, Groups A, B, C, D,
E, F & G, Temperature Class T4 Ta=60ºC, Type 4X and Class I, Zone 0, AEx ia IIC, Temperature Class T4 Ta=60ºC, Type 4X
[FISCO Model] Class I, II & III, Division 1, Groups A, B, C, D,
E, F & G, Temperature Class T4 Ta=60ºC, Type 4X and Class I, Zone 0, AEx ia IIC, Temperature Class T4 Ta=60ºC, Type 4X
• Nonincendive Approval
Class I, Division 2, Groups A, B, C & D
Temperature Class T4 Ta=60ºC, Type 4X and Class II, Division 2, Groups F & G Temperature Class T4 Ta=60ºC, Type 4X and Class I, Zone 2, Group IIC, Temperature Class T4 Ta=60ºC, Type 4X and Class III, Division 1, Temperature Class T4 Ta=60ºC, Type 4X
• Electrical Connection: 1/2 NPT female, M20 female
• Caution for FM Intrinsically safe type. (Following contents refer to “DOC. No. IFM040-A11 p.1 to p.6.”)
■ IFM040-A11
Installation Diagram for Intrinsically safe (Division 1 Installation)
Terminator
+
Indicator
+
Field Instruments
+
Field Instruments
Hazardous Location
Terminator
+
Safety Barrier
+
Non-Hazardous Location
F0203.ai
Note 1. Barrier must be installed in an enclosure
that meets the requirements of ANSI/ISA 61010-1.
Note 2. Control equipment connected to the Associ
ated Apparatus must not use or generate more than 250 Vrms or Vdc.
Note 3. Installation should be in accordance
with ANSI/ISA 12.06.01 “Installation of Intrinsi cally Safe Systems for Hazardous (Classied) Locations” and the National Electrical Code (ANSI/NFPA 70) Sections 504 and 505.
Note 4. The conguration of Associated Apparatus
must be Factory Mutual Research Approved under FISCO Concept.
Note 5. Associated Apparatus manufacturer’s
installa tion drawing must be followed when installing this equipment.
Note 6. No revision to drawing without prior
Factory Mutual Research Approval.
Note 7. Terminator must be FM Approved.
Note 8. Note a warning label worded “SUBSTITU
TION OF COMPONENTS MAY IMPAIR INTRINSIC SAFETY”, and “INSTALL IN ACCORDANCE DOC.NO.IFM040-A11 P.1 to P.6.”
Electrical Data:
• Rating 1 (Entity) For Groups A, B, C, D, E, F, and G or Group IIC
Maximum Input Voltage Vmax: 24 V Maximum Input Current Imax: 250 mA Maximum Input Power Pmax: 1.2 W Maximum Internal Capacitance Ci: 1.76 nF Maximum Internal Inductance Li: 0 mH or
• Rating 2 (FISCO) For Groups A, B, C, D, E, F, and G or Group IIC
Maximum Input Voltage Vmax: 17.5 V Maximum Input Current Imax: 500 mA Maximum Input Power Pmax: 5.5 W Maximum Internal Capacitance Ci: 1.76 nF Maximum Internal Inductance Li: 0 mH or
• Rating 3 (FISCO)
For Groups C, D, E, F, and G or Group IIB Maximum Input Voltage Vmax: 17.5 V Maximum Input Current Imax: 500 mA Maximum Input Power Pmax: 5.5 W Maximum Internal Capacitance Ci: 1.76 nF Maximum Internal Inductance Li: 0 mH
<2. Handling Cautions>
2-5
Note: In the rating 1, the output current of the barrier must
be limited by a resistor “Ra” such that Io=Uo/Ra. In the rating 2 or 3, the output characteristics of the barrier must be the type of trapezoid which are certied as the FISCO model (See “FISCO Rules”). The safety barrier may include a terminator. More than one eld instruments may be connected to the power supply line.
FISCO Rules
The FISCO Concept allows the interconnection of intrinsincally safe apparatus to associated apparatus not specically examined in such combination. The criterion for such interconnection is that the voltage (Ui), the current (Ii) and the power (Pi) which intrinsically safe apparatus can receive and remain intrinsically safe, considering faults, must be equal or greater than the voltage (Uo, Voc, Vt), the current (Io, Isc, It) and the power (Po) which can be provided by the associated apparatus (supply unit).
Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii
In addition, the maximum unprotected residual capacitance (Ci) and inductance (Li) of each apparatus (other than the terminators) connected to the eldbus must be less than or equal to 5 nF and 10 µH respectively.
Ci ≤ 5nF, Li ≤ 10µH
In each I.S. eldbus segment only one active source, normally the associated apparatus, is allowed to provide the necessary power for the eldbus system. The allowed voltage(Uo, Voc,Vt) of the associated apparatus used to supply the bus cable must be limited to the range of 14 V dc to 17.5 V dc. All other equipment connected to the bus cable has to be passive, meaning that the apparatus is not allowed to provide energy to the system, except to a leakage current of 50 µA for each connected device.
Supply unit
Trapezoidal or rectangular output characteristic only
Uo = 14...17.5 V (I.S. maximum value)
Io according to spark test result or other
assessment. No specication of Lo and Co is required on the certicate or label.
Cable
The cable used to interconnect the devices needs to comply with the following parameters:
Loop resistance R': 15...150 Ω/km Inductance per unit length L': 0.4...1 mH/km Capacitance per unit length C': 45...200 nF/km. C'=C' line/line + 0.5 C' line/screen, if both lines are oating or C'=C' line/line + C' line/screen, if the screen is connected to one line. Length of spur cable: max. 60 m Length of trunk cable: max. 1 km (Group IIC) or 5 km (Group IIB) Length of splice: max.1m
Terminators
At each end of the trunk cable an FM approved line terminator with the following parameters is suitable:
R = 90...100 Ω C = 0...2.2 mF
System evaluations
The number of passive device like transmitters, actuators, hand held terminals connected to a single bus segment is not limited due to I.S. reasons. Furthermore, if the above rules are respected, the inductance and capacitance of the cable need not to be considered and will not impair the intrinsic safety of the installation.
SAFE AREAHAZARDOUS AREA
Terminator (FISCO Model)
Ex i
Hand-
held-
Terminal
Field Instruments
(Passive)
I.S. eldbus system complying with FISCO model
Supply Unit and Safety Barrier (FISCO Model)
U
I
Terminator
Data
F0204.ai
U
<2. Handling Cautions>
2-6
Installation Diagram for Nonincendive (Division 2 Installation)
Terminator
+
Indicator
+
Field Instruments
+
Field Instruments
Hazardous Location
Non-Hazardous Location
Terminator
FM Approved
+
General Purpose
Equipment
+
Associated Nonincendive Field Wiring Apparatus Vt or Voc It or Isc Ca La
F0205.ai
Note 1. Installation should be in accordance with
the National Electrical Code ® (ANSI/NFPA
70) Article 500.
Note 2. The conguration of Associated
Nonincendive Field Wiring Apparatus must be FM Approved.
Note 3. Approved under FNICO Concept.
Note 4. Dust-tight conduit seal must be used
when installed in Class II and Class III environments.
Note 5. Associated Apparatus manufacturer’s
installation drawing must be followed when installing this apparatus.
Note 6. No revision to drawing without prior FM
Approvals.
Note 7. Terminator must be FM Approved.
Note 8. The nonincendive eld wiring circuit
concept allows interconection of nonincendive eld wiring apparatus with associated nonincendive eld wiring apparatus, using any of the wiring methods permitted for unclassied locations.
Note 9. Installation requirements;
Vmax ≥ Voc or Vt Imax = see note 10. Ca ≥ Ci + Ccable La ≥ Li + Lcable
Note 10. For this current controlled circuit, the
parameter (Imax) is not required and need not be aligned with parameter (Isc) of the barrier or associated nonincendive eld wiring apparatus.
Note 11. If ordinary location wiring methods are
used, indicator and eld instruments shall be connected to FM Approved associated nonincendive eld wiring apparatus.
Electrical data:
Vmax: 32 V Ci: 1.76 nF Li: 0 µH
FNICO Rules
The FNICO Concept allows the interconnection of nonincendive eld wiring apparatus to associated nonincendive eld wiring apparatus not specically examined in such combination. The criterion for such interconnection is that the voltage (Vmax), the current (Imax) and the power (Pmax) which nonincendive eld wiring apparatus can receive and remain nonincendive, considering faults, must be equal or greater than the voltage (Uo, Voc or Vt), the current (Io, Isc or It) and the power (Po) which can be provided by the associated nonincendive eld wiring apparatus (supply unit). In addition the maximum unprotected residual capacitance (Ci) and inductance (Li) of each apparatus (other than terminators) connected to the Fieldbus must be less than or equal to 5nF and 20uH respectively.
In each N.I. Fieldbus segment only one active source, normally the associated nonincendive eld wiring apparatus, is allowed to provide the necessary power for the Fieldbus system. The allowed voltage (Uo, Voc or Vt) of the associated nonincendive eld wiring apparatus used to supply the bus cable must be limited to the range 14Vdc to 17.5Vdc. All other equipment connected to the bus cable has to be passive, meaning that the apparatus is not allowed to provide energy to the system, except a leakage current of 50 µA for each connected device. Separately powered equipment needs galvanic isolation to ensure the nonincendive eld wiring Fieldbus circuit remains passive.
<2. Handling Cautions>
2-7
Cable
The cable used to interconnect the devices needs to comply with the following parameters:
Loop resistance R': 15...150 Ω/km Inductance per unit length L': 0.4...1 mH/km
Capacitance per unit length C': 45....200 nF/km
C' =C' line/line+0.5 C' line/screen, if both lines are oating or C' = C' line/line + C' line/screen, if the screen is connected to one line. Length of spur cable: max. 60 m Length of trunk cable: max. 1 km (Group IIC) or 5 km (Group IIB) Length of splice: max = 1 m
Terminators
At the end of each trunk cable an FM Approved line terminator with the following parameters is suitable:
R= 90...100 Ω
C = 0 ....2.2 mF
2.8.2 CSA Certication
a. CSA Explosionproof Type
Caution for CSA explosionproof type.
Note 1. FVX110 Fieldbus Segment Indicator with
optional code /CF1 is applicable for use in hazardous locations:
Certicate: 2325751
• Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30, C22.2 No.94, C22.2 No.213, C22.2 No.61010-01-04, C22.2 No.60079-0, C22.2 No.60079-1
[For CSA C22.2]
• Explosion-proof for Class I, Groups B, C and D.
• Dustignition-proof for Class II/III, Groups E, F and G.
• Enclosure: TYPE 4X
• Temperature Code: T6
[For CSA E60079]
• Flameproof for Zone 1, Ex d IIC T6
• Enclosure: IP66 and IP67
• Ambient Temperature: –50* to 75ºC (T6)
* –15ºC when O-ring material is Fluoro-rubber.
• Supply Voltage: 32 V dc max.
• Output Signal: 15 mA
Note 2. Wiring
• All wiring shall comply with Canadian Electrical Code Part I and Local Electrical Codes.
• In hazardous location, wiring shall be in conduit as shown in the gure.
• WARNING:
A SEAL SHALL BE INSTALLED WITHIN
50cm OF THE ENCLOSURE.
UN SCELLEMENT DOIT ÊTRE INSTALLÉÀ
MOINS DE 50cm DU BOîTIER.
• WARNING:
WHEN INSTALLED IN CL.I, DIV 2, SEAL
NOT REQUIRED.
UNE FOIS INSTALLÉ DANS CL I, DIV 2,
AUCUN JOINT N'EST REQUIS.
Note 3. Operation
• WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
APRÉS POWER-OFF, ATTENDRE 5
MINUTES AVANT D'OUVRIR.
• WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65ºC,
USE THE HEAT-RESISTING CABLES ≥ 90ºC.
QUAND LA TEMPÉRATURE AMBIANTE
≥ 65ºC, UTILISEZ DES CÂBLES RÉSISTANTES Á LA CHALEUR ≥ 90ºC.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation and Yokogawa Corporation of America is prohibited and will void Canadian Standards Explosionproof Certication.
<2. Handling Cautions>
2-8
Non-Hazardous
Hazardous Locations Division 1
Locations
Non-hazardous Location Equipment
32 V DC Max. 15 mA DC Signal
Non-Hazardous
Sealing Fitting
Hazardous Locations Division 2
50 cm Max.
Conduit
Segment Indicator
PULSE
PULSE
SUPPLY
SUPPLY
CHECK
CHECK
ALARM
ALARM
Locations
Non-hazardous Location Equipment
PULSE
PULSE
SUPPLY
SUPPLY
CHECK
CHECK
ALARM
32 V DC Max. 15 mA DC Signal
Sealing Fitting
Segment Indicator
ALARM
F0206.ai
b. CSA Intrinsically safe and Nonincendive
Type
FVX110 Fieldbus Segment Indicator with optional code /CS15.
• Certicate: 2346277
• Applicable standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.157, C22.2 No.213, C22.2 No.61010-1-04, C22.2
CAN/CSA E60079-0, CAN/CSA E60079-11, CAN/CSA E60079-15, IEC 60529
• CSA Intrinsically Safe Approval
Class I, Division 1, Groups A, B, C, & D;
Class II, Division 1, Groups E, F & G; Class III Division 1; Ex ia IIC T4
Ambient Temperature: –40* to 60°C (–40* to
140°F) Encl. Type 4X, IP66 and IP67
* –15ºC when O-ring material is Fluoro-rubber.
• CSA Nonincendive Approval
Class I, Division 2, Groups A, B, C, & D;
Class II, Division 2, Groups F & G; Class III Division 1; Ex nL IIC T4
Ambient Temperature: –40* to 60°C (–40* to
140°F) Encl. Type 4X, IP66 and IP67
* –15ºC when O-ring material is Fluoro-rubber.
Caution for CSA Intrinsically safe type. (Following contents refer to “DOC. No. ICS018”)
Installation Diagram for Intrinsically safe
(Division 1 Installation)
Terminator
+
Indicator
+
Field Instruments
+
Field Instruments
Hazardous Location
Non-Hazardous Location
Terminator
+
Safety Barrier
+
F0207.ai
Note 1. The safety barrier must be CSA certied.
Note 2. Input voltage of the safety barrier must be
less than 250Vrms/Vdc.
Note 3. Installation should be in accordance with
Canadian Electrical Code Part I and local Electrical Code.
Note 4. Do not alter drawing without authorization
from CSA.
<2. Handling Cautions>
2-9
Electrical Data:
• Rating 1 (Entity) For Groups A, B, C, D, E, F, and G or Group
IIC Ui (vmax) = 24 V dc Ii (Imax) = 250 mA Pi (Pmax) = 1.2 W Ci = 1.76 nF Li = 0 mH or
• Rating 2 (FISCO) For Groups A, B, C, D, E, F, and G or Group
IIC Ui (vmax) = 17.5 V dc Ii (Imax) = 500 mA Pi (Pmax) = 5.5 W Ci = 1.76 nF Li = 0 mH or
• Rating 3 (FISCO) For Groups C, D, E, F, and G or Group IIB Ui (vmax) = 17.5 V dc Ii (Imax) = 500 mA Pi (Pmax) = 5.5 W Ci = 1.76 nF Li = 0 mH Installation requirements; Po ≤ Pi Uo ≤ Ui Io ≤ Ii, Co ≥ Ci + Ccable Lo ≥ Li + Lcable Vmax ≥ Voc Imax ≥ Isc Ca ≥ Ci + Ccable La ≥ Li + Lcable Uo, Io, Po, Co, Lo,Voc, Isc, Ca and La are parameters of barrier.
Caution for CSA Non-incendive type. (Following contents refer to “DOC. No. ICS018”)
Installation Diagram for Non-incendive
or Type of protection "n" (Division 2 Installation)
Terminator
+
Indicator
+
Field Instruments
+
Field Instruments
Hazardous Location
Non-Hazardous Location
Terminator
+
CSA Certified
Equipment [nL]
+
F0208.ai
Note 1. Installation should be in accordance with
Canadian Electrical Code Part I and local Electrical Code.
Note 2. Dust-tight conduit seal must be used when
installed in class II and III environments.
Note 3. Do not alter drawing without authorization
from CSA.
Electrical Data:
• Rating (including FNICO) Ui or Vmax = 32 V Ci = 1.76 nF Li = 0 mH
<2. Handling Cautions>
2-10
2.8.3 CENELEC ATEX Certication
(1) Technical Data
a. CENELEC ATEX (DEKRA) Intrinsically Safe
Type
Caution for CENELEC ATEX (DEKRA) Intrinsically safe type.
Note 1. FVX110 Fieldbus Segment Indicator
with optional code /KS25 for potentially explosive atmospheres:
• No. DEKRA 11ATEX0022 X
• Applicable Standard: EN 60079-0:2009, EN 60079-11:2007, EN 60079-26:2007, EN 60079-27:2008, EN 61241-11:2006
Note 2. Ratings
Type of Protection and Marking Code: II1G Ex ia IIB/IIC T4 Ga II1D Ex ia IIIC T80ºC Da IP6X Group: II Category: 1G 1D Ambient Temperature: –40* to 60ºC
* –15ºC when O-ring material is Fluoro-rubber.
Maximum Surface Temperature for dust-proof. T80ºC (Tamb.: –40* to 60ºC)
* –15ºC when O-ring material is Fluoro-rubber.
Degree of Protection of the Enclosure: IP66 and IP67 Electrical Data
• When combined with Trapezoidal output characteristic FISCO model IIC or IIB barrier
[Supply/Output circuit (terminals + and –)] Ui = 17.5 V, Ii = 500 mA, Pi = 5.5 W,
Ci = 3.52 nF, Li = 0 µH
• When combined with Linear characteristic barrier
[Supply/Output circuit (terminals + and –)] Ui = 24.0 V, Ii = 250 mA, Pi = 1.2 W,
Ci = 3.52 nF, Li = 0 µH
Note 3. Installation
• All wiring shall comply with local installation requirements. (Refer to the installation diagram)
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void DEKRA Intrinsically safe Certication.
Note 5. Special Conditions for Safe Use
• In the case where the enclosure of the segment indicator is made of aluminium, if it is mounted in an area where the use of category 1 G apparatus is required, it must be installed such, that even in the event of rare incidents, ignition sources due to impact and friction sparks are excluded.
Note 6. Installation instructions
• The test voltage for the isolation between the intrincically safe supply/output circuit and the frame of the apparatas for segment indicator that are provided with surge protection is limited to 90 V, due to the presence of the surge protection device only.
When used in a potentially explosive
atmosphere, requiring the use of apparatus of equipment category 1D or 2D, certied cable entry devices shall be used that are suitable for the application and correctly installed.
FISCO Model
Non-Hazardous
Locations
Supply Unit and Safety Barrier (FISCO Model)
U
U
I
Terminator
Data
I.S. eldbus system complying with FISCO
Hazardous Locations
Terminator (FISCO Model)
Ex i
Hand-
held-
Terminal
Field Instruments
(Passive)
F0209.ai
<2. Handling Cautions>
2-11
The criterion for such interconnection is that the voltage (Ui), the current (Ii) and the power (Pi), which intrinsically safe apparatus can receive, must be equal or greater than the voltage (Uo), the current (Io) and the power (Po) which can be provided by the associated apparatus (supply unit).
Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii
In addition, the maximum unprotected residual capacitance (Ci) and inductance (Li) of each apparatus (other than the terminators) connected to the eldbus line must be equal or less than 5 nF and 10 µH respectively.
Ci ≤ 5 nF, Li ≤ 10 µH
Supply unit
The supply unit must be certied by a Notied body as FISCO model and following trapezoidal or rectangular output characteristic is used.
Uo = 14...17.5 V (I.S. maximum value) Io based on spark test result or other assessment, No specication of Lo and Co is required on the certicate or label.
Cable
The cable used to interconnect the devices needs to comply with the following parameters:
Entity Model
Non-Hazardous
Locations
Supply Unit and Safety Barrier
U
U
I
Terminator
Data
I.S. eldbus system complying with Entity model
Hazardous Locations
Ex i
Hand-
held-
Terminal
Field Instruments
(Passive)
Terminator
F0210.ai
I.S. values Power supply-eld device:
Po ≤ Pi, Uo ≤ Ui, Io ≤ Ii
Calculation of max. allowed cable length:
Ccable ≤ Co – ∑Ci – ∑Ci (Terminator) Lcable ≤ Lo – ∑Li
Number of Devices
The number of devices (max. 32) possible on a eldbus link depends on factors such as the power consumption of each device, the type of cable used, use of repeaters, etc.
Loop resistance Rc: 15...150 Ω/km
Inductance per unit length Lc: 0.4...1 mH/km
Capacitance per unit length Cc: 45...200 nF/km
Length of spur cable: max. 60 m (IIC and IIB)
Length of trunk cable: max. 1 km (IIC) or 5 km
(IIB)
Terminators
The terminator must be certied by a Notied body as FISCO model and at each end of the trunk cable an approved line terminator with the following parameters is suitable:
R = 90 . . . 102 Ω
C = 0 . . . 2.2 µF. (0.8...1.2 µF is required in
operation)
The resistor must be infallible according to IEC 60079-11.
Number of Devices
The number of devices (max. 32) possible on a eldbus link depends on factors such as the power consumption of each device, the type of cable used, use of repeaters, etc.
b. CENELEC ATEX (KEMA) Flameproof Type
Caution for CENELEC ATEX (KEMA) ameproof type
Note 1. FVX110 Fieldbus Segment Indicator
with optional code /KF25 for potentially explosive atmospheres:
• No. KEMA 10ATEX0157
• Applicable Standard: EN 60079-0:2006, EN 60079-1:2004, EN 61241-0:2006, EN 61241-1:2004
• Type of Protection and Marking Code: Ex d IIC T6, Ex tD A21 IP6x T80
• Group: II
• Category: 2G, 2D
• Temperature Class: T6
• Enclosure: IP66 and IP67
• Ambient Temperature for gas-proof: –50* to 75ºC (T6)
* –15ºC when O-ring material is Fluoro-rubber.
• Maximum Surface Temperature for dust­proof:
T80ºC (Tamb.: –40* to 75ºC)
* –15ºC when O-ring material is Fluoro-rubber.
<2. Handling Cautions>
2-12
Note 2. Electrical Data
• Supply voltage: 32 V dc max. Output current: 15 mA dc
Note 3. Installation
• All wiring shall comply with local installation requirements.
• The cable entry devices shall be of a certied ameproof type, suitable for the conditions of use.
Note 4. Operation
• Keep the “WARNING” label attached to the indicator.
WARNING: AFTER DE-ENERGIZING,
DELAY 5 MINUTES BEFORE OPENING. WHEN THE AMBIENT TEMP.≥65ºC, USE HEAT-RESISTING CABLES≥90ºC.
• Take care not to generate mechanical sparking when accessing the instrument and peripheral devices in hazardous location.
Note 5. Maintenance and Repair
• The instrument modication or part replacement by other than an authorized representative of Yokogawa Electric Corporation is prohibited and will void KEMA Flameproof Certication.
(2) Electrical Connection
A mark indicating the electrical connection type is stamped near the electrical connection port. These marks are as follows.
(3) Installation
WARNING
• All wiring shall comply with local installation requirements and the local electrical code.
• There is no need for a conduit seal in Division 1 and Division 2 hazardous locations because this product is sealed at the factory.
The grounding terminals are located on the inside and outside of the terminal area. Connect the cable to grounding terminal in accordance with wiring procedure 1) or 2).
1) External grounding terminal
Wiring Procedure for Grounding Terminals
2) Internal grounding terminal
F0212.ai
(4) Operation
WARNING
ISO M20×1.5 female
ANSI 1/2 NPT female
MarkingScrew Size
M
A or W
Location of the mark
F0211.ai
• OPEN CIRCUIT BEFORE REMOVING COVER. INSTALL IN ACCORDANCE WITH THIS USER’S MANUAL
• Take care not to generate mechanical sparking when accessing the instrument and peripheral devices in a hazardous location.
(5) Maintenance and Repair
WARNING
The instrument modication or part replacement by other than an authorized Representative of Yokogawa Electric Corporation is prohibited and will void the certication.
<2. Handling Cautions>
2-13
(6) Name Plate
● Name plate
MODEL
SUFFIX
SUPPLY OUTPUT
STYLE
NO.
● Tag plate for flameproof type
No. KEMA 10ATEX0157 Ex d IIC T6, Ex tD A21, IP6X T80ºC Enlcosure: IP66, IP67 Tamb.(GAS) -50(-15) to 75 ºC Tamb.(Dust) -40(-15) to 75 ºC
AFTER DE-ENERGIZING, DELAY 5 MINUTES BEFORE OPENING. WHEN THE AMBIENT TEMP. ≥ 65ºC, USE THE HEAT-RESISTING CABLES ≥ 90ºC
● Tag plate for intrinsically safe type
No. DEKRA 11ATEX0022 X Ex ia IIB/IIC T4 Ga Ex ia IIIC T80ºC Da IP6X Tamb: -40 to 60ºC ENCLOSURE: IP66/IP67 FISCO Field device Entity Parameters Ui=24V, Ii=250mA, Pi=1.2W, Ci=3.52nF, Li=0µH
F0213.ai
MODEL: Specied model code. STYLE: Style code. SUFFIX: Specied sufx code. SUPPLY: Supply voltage. OUTPUT: Output signal. NO.: Serial number and year of production*1. TOKYO 180-8750 JAPAN: The manufacturer name and the address*2.
*1: The rst digit in the nal three numbers of the serial
number appearing after “NO.” on the name plate indicates the year of production. The following is an example of a serial number for a product that was produced in 2010:
91K819857 032
The year 2010
*2: “180-8750” is the Zip code for the following address.
2-9-32 Nakacho, Musashino-shi, Tokyo Japan
2.8.4 IECEx Certication
a. IECEx Flameproof Type
Caution for IECEx ameproof type.
Note 1. FVX110 Fieldbus Segment Indicator with
optional code /SF25 are applicable for use in hazardous locations:
• No. IECEx KEM10.0071
• Applicable Standard: IEC60079-0(:2004), IEC60079-1(:2003)
• Type of Protection and Marking Code:
Ex d IIC T6
• Temperature Class: T6
• Enclosure: IP66 and IP67
• Ambient Temperature for gas-proof:
–50* to 75ºC (T6)
* –15ºC when O-ring material is Fluoro-rubber.
Note 2. Wiring
• In hazardous locations, the cable entry devices shall be of a certied ameproof type, suitable for the conditions of use and correctly installed.
• Unused apertures shall be closed with suitable ameproof certied blanking elements.
Note 3. Operation
• WARNING:
AFTER DE-ENERGIZING, DELAY 5
MINUTES BEFORE OPENING.
• WARNING:
WHEN AMBIENT TEMPERATURE ≥ 65ºC,
USE THE HEAT-RESISTING CABLES ≥ 90ºC.
• Take care not to generate mechanical sparking when accessing to the instrument and peripheral devices in a hazardous location.
Note 4. Maintenance and Repair
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation is prohibited and will void IECEx Certication.
<2. Handling Cautions>
2-14
b. IECEx Intrinsically Safe Type
Caution for IECEx Intrinsically safe type.
Note 1. FVX110 Fieldbus Segment Indicator with
optional code /SS25 are applicable for use in hazardous locations:
• No. IECEx DEK 11.0004 X
• Applicable Standard: IEC60079-0:2007, IEC60079-11:2006,
IEC60079-26:2006, IEC60079-27:2008
Note 2. Ratings
[Ex ia IIB/IIC T4 Ga]
• Type of Protection: II1G Ex ia IIB/IIC T4 Ga
• Ambient Temperature: –40* to 60ºC
* –15ºC when O-ring material is Fluoro-rubber.
• Degree of Protection of the Enclosure: IP66 and IP67
• When combined with Trapezoidal output characteristic FISCO model
IIC or IIB barrier [Supply/Output circuit (terminals + and –)] Ui = 17.5 V, Ii = 500 mA, Pi = 5.5 W,
Ci = 3.52 nF, Li = 0
• When combined with Linear characteristic barrier
[Supply/Output circuit (terminals + and –)] Ui = 24.0 V, Ii = 250 mA, Pi = 1.2 W,
Ci = 3.52 nF, Li = 0
[Ex ic IIC T4 Gc]
• Type of Protection: II3G Ex ic IIC T4 Gc
• Ambient Temperature: –40* to 60ºC
* –15ºC when O-ring material is Fluoro-rubber.
• Degree of Protection of the Enclosure: IP66 and IP67
[Supply/Output circuit (terminals + and –)] Ui = 32.0 V, Ci = 3.52 nF, Li = 0
Note 3. Installation
• In any safety barrier used output current must be limited by a resistor 'R' such that Io=Uo/R.
• The safety barrier must be IECEx certied.
• Input voltage of the safety barrier must be less than 250 Vrms/Vdc.
• The instrument modication or parts replacement by other than authorized representative of Yokogawa Electric Corporation and will void IECEx Intrinsically safe certication.
[Intrinsically safe apparatus level of protection “ia”]
Terminator
+
Indicator
+
Field Instruments
+
Field Instruments
Hazardous Location
Terminator
+
Safety Barrier
+
[Intrinsically safe apparatus level of protection “ic”]
Terminator
Terminator
+
General Porpose
Equipment
+
Non-Hazardous Location
+
Indicator
+
Field Instruments
+
Field Instruments
Hazardous Location
Non-Hazardous Location
F0214.ai
F0215.ai
<3. Component Names>

3. Component Names

3-1
Display assembly
Mounting screw
Display cover
CPU assembly
1
2
Conduit connection
Slide switch
O
SIM.ENABLE switch
N O
WRITE LOCK switch
N
(Note 1)
Terminal box cover
Conduit connection
Scroll Knob
SIM.ENABLE Switch
SIM.ENABLE
Switch position
(Note 2)
SIM.ENABLE
(Note 1) See Subsection 13.3 “Model and Sufx codes” for details. (Note 2) Set the switches as shown in the gure above to set the SIM.ENABLE and WRITE LOCK. The SIM.ENABLE and WRITE LOCK switch is set to OFF for delivery. (For function detail, please refer to Subsection 9.3 and
9.4.)
1
2
OFF
(Simulation disenable)ON(Simulation enable)
O
1
N
O
2
N
O N
O N
WRITE LOCK
Switch position
(Note 2)
WRITE LOCK
WRITE LOCK Switch
1
2
OFF
(WRITE LOCK OFF)ON(WRITE LOCK ON)
O
1
N
O
2
N
O N
O N
F0301.ai
Figure 3.1 Component Names
<4. About Fieldbus>

4. About Fieldbus

4-1

4.1 Outline

Fieldbus is a widely used bi-directional digital communication protocol for eld devices that enable the simultaneous output to many types of data to the process control system.
FVX110 Fieldbus Segment Indicatior employs the specication standardized by The Fieldbus Foundation, and provides interoperability between Yokogawa devices and those produced by other manufacturers.
For information on other features, engineering, design, construction work, startup and maintenance of Fieldbus, refer to “Fieldbus Technical Information” (TI 38K03A01-01E).

4.2 Internal Structure of FVX110

The FVX110 contains two virtual eld devices (VFD) that share the following functions.

4.2.1 System/network Management VFD

• Sets node addresses and Physical Device tags (PD Tag) necessary for communication.
• Controls the execution of function blocks.
• Manages operation parameters and communication resources (Virtual Communication Relationship: VCR).

4.2.2 Function Block VFD

(1) Resource block
• Manages the status of FVX110 hardware.
• Automatically informs the host of any detected faults or other problems.
(2) LCD Transducer block
• Controls the display of the integral indicator.
(3) MAO function block
• Transfers 8 analog variables of the IO subsystem to transducer block using 8 input parameters (IN_1 to IN_8).
(4) PID function block
• Performs the PID control computation based on the deviation of the measured value from the setpoint.
(5) SC function block
• Uses the line-segment function to convert input signal values.
(6) IT function block
• Integrates input signal values.
(7) IS function block
• Same as MAO function block, this block transfer 8 analog variables (IN_1 to IN_8) to transducer block.
• Provides a function for automatic selection of one signal from multiple input signals using a specied method of selection.
(8) AR function block
• Applies gain multiplication and bias addition to the calculated result through use of multiple computing equations to perform limitation processing for output.
<4. About Fieldbus>
4-2

4.3 Logical Structure of Each Block

FVX110
System/network management VFD
PD Tag
Node address
Function block VFD
PID Function
block (x2)
AR F unct ion
bloc k (x 2)
IT Function
block
SC Function
block
MAO or IS
Function block
Block tag
Parameters
IN_1 IN_2
IN_8
MAO or IS
Function block
Link Master
Communication
parameters
VCR
Function block
execution schedule
LCD Transducer
block
Block tag
Parameters
4.4 Wiring System Conguration
The number of devices that can be connected to a single bus and the cable length vary depending on system design. When constructing systems, both the basic and overall design must be carefully considered to achieve optimal performance.
LCD
External input
Block tag
(Max. 16 input)
Parameters
IN_1 IN_2
IN_8
Block tag
Parameters
Resource block
F0401.ai
Figure 4.1 Logical Structure of Each Block
Setting of various parameters, node addresses, and PD Tags shown in Figure 3.1 is required before starting operation.
<5. Installation>

5. Installation

5-1

5.1 Precautions

Before installing the indicator, read the cautionary notes in section 2.4, “Selecting the Installation Location.” For additional information on the ambient conditions allowed at the installation location, refer to section 13.1 “Functional Specications.”
IMPORTANT
• When welding piping during construction, take care not to allow welding currents to ow through the indicator.
• Do not step on this instrument after installation.

5.2 Mounting

■ The Indicator can be mounted on a nominal 50 mm (2-inch) pipe using the mounting bracket supplied, as shown in Figure 5.1.
Vertical pipe mounting
U-bolt nut (L)
U-bolt nut (S)
Mounting bracket
U-bolt (S)
Horizontal pipe mounting
50 mm (2-inch) pipe
U-bolt (L)
U-bolt nut (L)
Mounting bracket
50 mm (2-inch) pipe
U-bolt nut (S)
U-bolt (S)
U-bolt (L)
Figure 5.1 Indicator Mounting
F0501.ai
<5. Installation>
5-2

5.3 Wiring

5.3.1 Wiring Precautions

IMPORTANT
• Lay wiring as far as possible from electrical noise sources such as large capacity transformers, motors, and power supplies.
• Remove the electrical connection dust cap before wiring.
• All threaded parts must be treated with waterproong sealant. (A non-hardening silicone group sealant is recommended.)
• To prevent noise pickup, do not pass signal and power cables through the same ducts.
• Explosion-protected instruments must be wired in accordance with specic requirements (and, in certain countries, legal regulations) in order to preserve the effectiveness of their explosion-protected features.
• The terminal box cover is locked by an Allen head bolt (a shrouding bolt) on ATEX ameproof type indicators. When the shrouding bolt is driven clockwise using an Allen wrench, it goes in. The cover lock can then be released and the cover can be opened by hand. See subsection 10.2 “Disassembly and Reassembly” for details.
• Plug and seal an unused conduit connection.

5.3.2 Wiring Installation

(1) General-use Type and Intrinsically Safe
Type
With the cable wiring, use a metallic conduit or waterproof glands.
• Apply a non-hardening sealant to the terminal box connection port and to the threads on the exible metal conduit for waterproong.
Flameproof packing adapter
Flexible metal conduit
Wiring metal conduit
Tee
Apply a non-hardening sealant to the threads for waterproofing.
Figure 5.2 Typical Wiring Using Flexible Metal
Conduit
(2) Flameproof Type
Wire cables through a ameproof packing adapter, or use a ameproof metal conduit.
■ Wiring cable through ameproof packing adapter.
• Apply a non-hardening sealant to the terminal box connection port and to the threads on the ameproof packing adapter for waterproong.
Drain plug
F0502.ai
Flameproof packing adapter
Flexible metal conduit
Wiring metal conduit
Tee
Apply a non-hardening sealant to the threads for waterproofing.
Figure 5.3 Typical Cable Wiring Using Flameproof
Packing Adapter
Drain plug
F0503.ai
<5. Installation>
5-3
■ Flameproof metal conduit wiring
• A seal tting must be installed near the terminal box connection port for a sealed construction.
• Apply a non-hardening sealant to the threads of the terminal box connection port, exible metal conduit and seal tting for waterproong.
Flameproof flexible metal conduit
Gas sealing device
Apply a non-hardening sealant to the threads of these fittings for waterproofing
Seal fitting After wiring, impregnate the fitting with a compound to seal tubing.
Figure 5.4 Typical Wiring Using Flameproof Metal
Conduit
Non-hazardous area
Hazardous area
Flameproof heavy-gauge steel conduit
Tee
Drain plug
F0504.ai

5.4 Grounding

Grounding is always required for the proper operation of indicator. Follow the domestic electrical requirements as regulated in each country. For a indicator with a built-in lightning protector, grounding should satisfy ground resistance of 10Ω or less.
Ground terminals are located on the inside and outside of the terminal box. Either of these terminals may be used.
Terminal box
PULSE
SUPPLY
CHECK
Ground terminal (inside)
ALARM

5.5 Connection of Devices

The following are required for use with Fieldbus devices:
• Power supply:
Fieldbus requires a dedicated power supply. It is recommended that current capacity be well over the total value of the maximum current consumed by all devices (including the host). Conventional DC current cannot be used as is.
• Terminator:
Fieldbus requires two terminators. Refer to the supplier for details of terminators that are attached to the host.
• Field devices:
Connect Fieldbus communication type eld devices. Two or more EJX, YTA, AXF or other devices can be connected.
• Host:
Used for accessing eld devices. A dedicated host (such as DCS) is used for an instrumentation line while dedicated communication tools are used for experimental purposes. For operation of the host, refer to the instruction manual for each host. No other details on the host are given in this manual.
• Cable:
Used for connecting devices. Refer to “Fieldbus Technical Information” (TI 38K03A01-01E) for details of instrumentation cabling. For laboratory or other experimental use, a twisted pair cable two to three meters in length with a cross section of 0.9 mm2 or more and a cycle period of within 5 cm (2 inches) may be used. Termination processing depends on the type of device being deployed. For FVX110, use an M4 screw terminal claw. Some hosts require a connector.
Ground terminal (outside)
Figure 5.5 Ground Terminals
F0505.ai
Refer to Yokogawa when making arrangements to purchase the recommended equipment.
Connect the devices as shown in Figure 5.6. Connect the terminators at both ends of the trunk, with a minimum length of the spur laid for connection.
The polarity of signal and power must be maintained.
<5. Installation>
5-4
Fieldbus power supply
Terminator
Figure 5.6 Cabling
Communication terminals connection hook
SUPPLY +
SUPPLY –
SUPPLY
Figure 5.7 Wiring Diagram
+
Power supply and output terminal
Ground terminal
Field device
FVX110
HOST
Terminator
F0506.ai
F0507.ai
NOTE
No CHECK terminal is used for FVX110. Do not connect anything on CHECK terminal.
Before using a Fieldbus conguration tool other than the existing host, conrm it does not affect the loop functionality in which all devices are already installed in operation. Disconnect the relevant control loop from the bus if necessary.
IMPORTANT
Connecting a Fieldbus conguration tool to a loop with its existing host may cause communication data scrambling resulting in a functional disorder or a system failure.

5.6 Host Setting

To activate Fieldbus, the following settings are required for the host.
IMPORTANT
Do not turn off the power immediately after setting. When the parameters are saved to the EEPROM, the redundant processing is executed for an improvement of reliability. If the power is turned off within 60 seconds after setting is made, the modied parameters are not saved and the settings may return to the original values.
Table 5.1 Operation Parameters
Symbol Parameter Description and Settings
V (ST) Slot-Time Indicates the time
V (MID) Minimum-Inter-
PDU-Delay
V (MRD) Maximum-
Reply-Delay
V (FUN) First-Unpolled-
Node
V (NUN) Number-of-
consecutive­Unpolled-Node
necessary for immediate reply of the device. Unit of time is in octets (256 μs). Set maximum specication for all devices. For FVX110, set a value of 4 or greater.
Minimum value of communication data intervals. Unit of time is in octets (256 μs). Set the maximum specication for all devices. For FVX110, set a value of 4 or greater.
The worst case time elapsed until a reply is recorded. The unit is Slot-time; set the value so that V (MRD) × V (ST) is the maximum value of the specication for all devices. For FVX110, the setting must be a value of 12 or greater.
Indicate the address next to the address range used by the host. Set 0 × 15 or greater.
Unused address range.
<5. Installation>
0x00
Not used
0x0F
V(FUN)
V(FUN)+V(NUN)
0x10
0x13 0x14
0xF7 0xF8
Bridge device
LM device
Unused V(NUN)
BASIC device
Device ID : 5945430010XXXXXXXX PD Tag : UT1001 Device Revision : 3 Node Address : 0xf3 Serial No. : XXXXXXXXXXXXXXXXX Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld (English) or
http://www.yokogawa.co.jp/Sensor/fieldbus/fieldbus.htm (Japanese)
DEVICE INFORMATION
Default address
0xFB
0xFC
Portable device address
0xFF
Note 1: Bridge device: A linking device which brings data
from one or more H1 networks.
Note 2: LM device: with bus control function (Link Master
function).
Note 3: BASIC device: without bus control function.
F0508.ai
Device ID : 5945430010XXXXXXXX PD Tag : UT1001 Device Revision : 3 Node Address : 0xf3 Serial No. : XXXXXXXXXXXXXXXXX Physical Location :
Note:
Our Device Description Files and Capabilities Files available at
http://www.yokogawa.com/fld (English) or
http://www.yokogawa.co.jp/Sensor/fieldbus/fieldbus.htm (Japanese)
DEVICE INFORMATION
Figure 5.8 Available Address Range
5-5

5.7 Bus Power ON

Turn on the power of the host and the bus. After displaying the startup screen shown in Figure 5.9, the regular screen display appears. If the indicator is not lit, check the polarity of the power supply.
F0509.ai
Figure 5.9
Using the host device display function, check that the FVX110 is in operation on the bus.
The device information, including PD tag, Node address, and Device ID, is described on the sheet attached to the FVX110. The device information is given in duplicate on this sheet.
F0510.ai
Figure 5.10 Device Information Sheet Attached to
FVX110
If no FVX110 is detected, check the available address range and the polarity of the power supply. If the node address and PD tag are not specied when ordering, default value is factory set. If two or more FVX110s are connected at a time with default value, only one FVX110 will be detected from the host as FVX110 have the same initial address. Separately connect each FVX110 and set a different address for each.
<5. Installation>
5-6

5.8 Integration of DD

If the host supports DD (Device Description), the DD of the FVX110 needs to be installed. Check if host has the following directory under its default DD directory.
594543\0010
(594543 is the manufacturer number of Yokogawa Electric Corporation, and 0010 is the
FVX110 device number, respectively.) If this directory is not found, the DD of the FVX110 has not been included. Create the above directory and copy the DD le (0m0n.ffo, 0m0n.sym) (m, n is a numeral) into the directory. ‘0m’ in the le name shows the device revision, and ‘0n’ shows the DD revision. If you do not have the DD or capabilities les, you can download them from our web site:
http://www.yokogawa.com/d
Once the DD is installed in the directory, the name and attribute of all parameters of the FVX110 are displayed.

5.10 Continuous Record of Values

If the host has a function that continuously records the indications, use this function to list the indications (values). Depending on the host being used, it may be necessary to set the schedule of Publish (the function that transmits the indication on a periodic basis).

5.11 Generation of Alarm

Generation of an alarm can be attempted from FVX110. Block alarm, Output limit alarm, and Update alarm are informed to the host. When generating alarm, a Link Object and a VCR Static Entry need to be set. For details of Link Object and VCR Static Entry, refer to section 6.6.1 Link object and section 6.5.1 VCR Setting.
Off-line conguration is possible by using capabilities les.

5.9 Set the Parameters Using DTM

Following Device DTM on YOKOGAWA FieldMate can be used to congure the parameters for FVX110 Fieldbus Segment Indicator
Table 5.2 YOKOGAWA device DTM for FVX110
Fieldbus Segment Indicator
Device
DTM
Name
FVX FF
DTM
FVX110 Fieldbus Segment Indicator
Model
Name
FVX110
Device
Type
FVX
(0x0010)
Device
Revision
1
NOTE
For more information on FieldMate, refer to the User’s Manual IM 01R01A01-1E “Versatile Device Management Wizard”.
<6. Conguration>
6. Conguration
6-1
This chapter describes how to adapt the function and performance of the FVX110 to suit specic applications. Because multiple devices are connected to Fieldbus, it is important to carefully consider the device requirements and settings when conguring the system. The following steps must be taken.
(1) Network design
Determines the devices to be connected to Fieldbus and checks the capacity of the power supply.
(2) Network denition
Determines the tag and node addresses for all devices.
(3) Denition of combining function blocks
Determines how function blocks are combined.
(4) Setting tags and addresses
Sets the PD Tag and node addresses for each device.
(5) Communication setting
Sets the link between communication parameters and function blocks.
(6) Block setting
Sets the parameters for function blocks.
The following section describes in sequence each step of this procedure. The use of a dedicated conguration tool signicantly simplies this procedure. Refer to Appendix 7 when the FVX110 is used as Link Master.

6.1 Network Design

Select the devices to be connected to the Fieldbus network. The following are essential for the operation of Fieldbus.
• Power supply
Fieldbus requires a dedicated power supply. It is recommended that current capacity be well over the total value of the maximum current consumed by all devices (including the host). Conventional DC current cannot be used as this.
• Terminator
Fieldbus requires two terminators. Refer to the supplier for details of terminators that are attached to the host.
• Field devices
Connect the eld devices necessary for instrumentation. The FVX110 has passed the interoperability test conducted by The Fieldbus Foundation. In order to properly start Fieldbus, it is recommended that the devices used satisfy the requirements of the above test.
• Host
Used for accessing eld devices. A minimum of one device with the bus control function is needed.
• Cable
Used for connecting devices. Refer to “Fieldbus Technical Information” for details of instrumentation cabling. Provide a cable sufciently long to connect all devices. For eld branch cabling, use terminal boards or a connection box as required.
First, check the capacity of the power supply. The power supply capacity must be greater than the sum of the maximum current consumed by all devices to be connected to Fieldbus. The maximum current consumed (power supply voltage 9 V to 32 V) for the FVX110 is 15 mA (24 mA in Software download operation). The cable used for the spur must be of the minimum possible length.
<6. Conguration>
6-2
6.2 Network Denition
Before connection of devices with Fieldbus, dene the Fieldbus network. Allocate PD Tag and node addresses to all devices (excluding such passive devices as terminators).
The PD Tag is the same as the conventional one used for the device. Up to 32 alphanumeric characters may be used for denition. Use a hyphen as a delimiter as required.
The node address is used to specify devices for communication purposes. Because this data is too long for a PD Tag, the host uses the node address in place of the PD Tag for communication. A range of 20 to 247 (or hexadecimal 14 to F7) can be set. The device (LM device) with bus control function (Link Master function) is allocated from a smaller address number (20) side, and other devices (BASIC device) without bus control function allocated from a larger address number (247) side respectively. Place the FVX110 in the range of the BASIC device. When the FVX110 is used as Link Master, place the FVX110 in the range of the LM device. Set the range of addresses to be used to the LM device. Set the following parameters.
Table 6.1 Parameters for Setting Address Range
Symbol Parameters Description
V (FUN) First-Unpolled-
Node
V (NUN) Number-of-
consecutive­Unpolled-Node
The devices within the address range written as “Unused” in Figure 6.1 cannot be used on a Fieldbus. For other address ranges, the range is periodically checked to identify when a new device is mounted. Care must be taken to keep the unused device range as narrow as possible so as to lessen the load on the Fieldbus.
Indicates the address next to the address range used for the host or other LM device.
Unused address range
0x00
Not used
0x0F 0x10
0x13 0x14
V(FUN)
V(FUN)+V(NUN)
0xF7 0xF8
0xFB
0xFC
0xFF
Figure 6.1 Available Range of Node Addresses
Bridge device
LM device
Unused V(NUN)
BASIC device
Default address
Portable device address
F0601.ai
To ensure stable operation of Fieldbus, determine the operation parameters and set them to the LM devices. While the parameters in Table 6.2 are to be set, the worst-case value of all the devices to be connected to the same Fieldbus must be used. Refer to the specication of each device for details. Table 6.2 lists FVX110 specication values.
Table 6.2 Operation Parameter Values of the
FVX110 to be Set to LM Devices
Symbol Parameters
V (ST) Slot-Time Indicates the time
V (MID) Minimum-Inter-
PDU-Delay
V (MRD) Maximum-
Reply-Delay
Description and
Settings
necessary for immediate reply of the device. Unit of time is in octets (256 μs). Set maximum specication for all devices. For FVX110, set a value of 4 or greater.
Minimum value of communication data intervals. Unit of time is in octets (256 μs). Set the maximum specication for all devices. For FVX110, set a value of 4 or greater.
The worst case time elapsed until a reply is recorded. The unit is Slottime; set the value so that V (MRD) × V (ST) is the maximum value of the specication for all devices. For FVX110, the setting must be a value of 12 or, greater and V (MID) < V (MRD) × V (ST).
<6. Conguration>
6.3 Denition of Combining Function Blocks
The input/output parameters for function blocks are combined. As required, they can be combined with the input of the control block. The setting is written to the FVX110 link object. See “Block setting” in Section 6.6 for the details. It is also possible to read values from the host at proper intervals instead of connecting the FVX110 block output to other blocks.
EJX
#1
LI100
LIC100
FVX
110
FIC100
6-3
UI100
The combined blocks need to be executed synchronously with other blocks on the communications schedule. In this case, change the FVX110 schedule according to the following table. The values in the table are factory-settings.
Table 6.3 Execution Schedule of the FVX110
Function Blocks
Index Parameters
269
MACROCYCLE_
(SM)
DURATION
Setting (Enclosed is
factory-setting)
Cycle (MACROCYCLE) period of control or measurement. Unit is 1/32 ms. (32000 =
1.0 s)
276
FB_START_ENTRY.1 Excution block startup
(SM)
time. Elapsed time from the start of MACROCYCLE specied in 1/32 ms. (0 = 0 s)
277
FB_START_ENTRY.2
to
to
291
FB_START_ENTRY.16
(SM)
Excution block startup time. Elapsed time from the start of MACROCYCLE specied in 1/32 ms. (0 = 0 s)
A maximum of 30 ms is taken for execution of MAO function block and IS function block. For scheduling of communications for combination with the next function block, the execution is so arranged as to start after a lapse of longer than 30 ms. In no case should function blocks of the FVX110 be executed at the same time (execution time is overlapped).
Figure 6.3 shows an example of schedule based on the loop shown in Figure 6.2.
EJX
#2
FI100
FC100
F0602.ai
Figure 6.2 Example of Loop Connecting Function
Block of FVX110 and Two EJX with Other Instruments
Macrocycle (Control Period)
LI100 OUT
Commu-
nication
Schedule
OUT
LIC100
BKCAL_IN
FI100
IN
OUT
CAS_IN
BKCAL_OUT
FIC100
IN
OUT
BKCAL_IN
Unscheduled Communication
Scheduled Communication
FC100
BKCAL_OUT
IN_1
UI 100
IN_2
F0603.ai
Figure 6.3 Function Block Schedule and
Communication Schedule
When the control period (macrocycle) is set to more than 4 seconds, set the following intervals to be more than 1% of the control period.
- Interval between “end of block execution” and “start of sending CD from LAS”
- Interval between “end of block execution” and “start of the next block execution”
<6. Conguration>
6-4

6.4 Setting of Tags and Addresses

This section describes the steps in the procedure to set PD Tags and node addresses in the FVX110. There are three states of Fieldbus devices as shown in Figure 6.4, and if the state is other than the lowest SM_OPERATIONAL state, no function block is executed. FVX110 must be transferred to this state when an FVX110 tag or address is changed.
UNINITIALIZED
(No tag nor address is set)
Tag clear Tag setting
INITIALIZED
(Only tag is set)
Address clear
SM_OPERATIONAL
(Tag and address are retained, and
the function block can be executed.)
Figure 6.4 Status Transition by Setting PD Tag and
Node Address
FVX110 has a PD Tag (UT1001) and node address (245, or hexadecimal F5) that are set upon shipment from the factory unless otherwise specied. To change only the node address, clear the address once and then set a new node address. To set the PD Tag, rst clear the node address and clear the PD Tag, then set the PD Tag and node address again.
Devices whose node addresses have been cleared will have the default address (randomly chosen from a range of 248 to 251, or from hexadecimal F8 to FB). At the same time, it is necessary to specify the device ID in order to correctly specify the device. The device ID of the FVX110 is 5945430010xxxxxxxx. (The xxxxxxxx at the end of the above device ID is a total of 8 alphanumeric characters.)
Address setting
F0604.ai

6.5 Communication Setting

To set the communication function, it is necessary to change the database residing in SM-VFD.

6.5.1 VCR Setting

Set VCR (Virtual Communication Relationship), which species the called party for communication and resources. FVX110 has 35 VCRs whose application can be changed, except for the rst VCR, which is used for management.
FVX110 has VCRs of four types:
Server(QUB) VCR
A Server responds to requests from a host. This communication needs data exchange. This type of communication is called QUB (Queued User-triggered Bidirectional) VCR.
Source (QUU) VCR
A Source multicasts alarms or trends to other devices. This type of communication is called QUU (Queued User-triggered Unidirectional) VCR.
Publisher (BNU) VCR
A Publisher multicasts AI block output of eld device to another function block(s). This type of communication is called BNU (Buffered Network-triggered Unidirectional) VCR.
Subscriber (BNU) VCR
A Subscriber receives output of another function block(s) by MAO block or PID block.
A Server VCR is capable to responding to requests from a Client (QUB) VCR after the Client successfully initiates connection to the Server. A Source VCR transmits data without established connection. A Sink (QUU) VCR on another device can receive it if the Sink is congured so. A Publisher VCR transmits data when LAS requests so. An explicit connection is established from Subscriber (BNU) VCR(s) so that a Subscriber knows the format of published data.
Each VCR has the parameters listed in Table 6.4. Parameters must be changed together for each VCR because modication of individual parameters may cause inconsistent operation.
<6. Conguration>
Table 6.4 VCR Static Entry
Sub-
index
Parameter Description
1 FasArTypeAndRole Indicates the type and
role of communication (VCR). The following 4 types are used for FVX110. 0x32: Server
(Responds to requests from host.)
0x44: Source
(Transmits alarm or trend.)
0x66: Publisher (Sends
AI block output of eld device to other blocks.)
0x76: Subscriber
(Receives output of other blocks by MAO block or PID block.)
2 FasDllLocalAddr Sets the local address
to specify VCR in FVX110. A range of 20 to F7 in hexadecimal.
3 FasDllCongured
RemoteAddr
Sets the node address of the called party for communication and
Sub-
index
Parameter Description
7 FasDllMaxDlsduSize Species maximum DL
Service Data unit Size (DLSDU). Set 256 for Server and Trend VCR, and 64 for other VCRs.
8 FasDllResidual
ActivitySupported
Species whether connection is monitored. Set TRUE (0xff) for Server. This parameter is not used for other communication.
9 FasDllTimelinessClass Not used for FVX110.
10 FasDllPublisherTime
Not used for FVX110.
WindowSize
11 FasDllPublisher
Not used for FVX110.
SynchronizaingDlcep
12 FasDllSubsriberTime
Not used for FVX110.
WindowSize
13 FasDllSubscriber
Not used for FVX110.
SynchronizationDlcep
14 FmsVfdId Sets VFD for FVX110
to be used.
0x1: System/network
0x1234: Function block
the address (DLSAP or DLCEP) used to specify VCR in that address. For DLSAP or DLCEP, a range of 20 to F7 in hexadecimal is used. Addresses in Subindex 2 and 3 need to be set to the same contents of the VCR as the called party (local and remote are reversed).
4 FasDllSDAP Species the quality
of communication.
15 FmsMaxOutstanding
ServiceCalling
16 FmsMaxOutstanding
ServiceCalled
17 FmsFeatures
Supported
Set 0 to Server. It is not used for other applications.
Set 1 to Server. It is not used for other applications.
Indicates the type of services in the application layer. In the FVX110, it is automatically set according to specic applications.
Usually, one of the following types is set.
35 VCRs are factory-set as shown in the Table 6.5.
0x2B: Server 0x01: Source (Alert) 0x03: Source (Trend) 0x91: Publisher/
Subscriber
5 FasDllMaxConrm
DelayOnConnect
To establish connection for communication, a maximum wait time for the called party's response is set in ms. Typical value is 60 secounds (60000).
6 FasDllMaxConrm
DelayOnData
For request of data, a maximum wait time for the called party's response is set in ms. Typical value is 60 secounds (60000).
6-5
management VFD
VFD
<6. Conguration>
6-6
Table 6.5 VCR List
Index
(SM)
303 1 For system management (Fixed) 304 2 Server (LocalAddr = 0xF3) 305 3 Server (LocalAddr = 0xF4) 306 4 Server (LocalAddr = 0xF7) 307 5 Trend Source (LocalAddr = 0x07,
308 6 Publisher for PID1 (LocalAddr =
309 7 Alert Source (LocalAddr = 0x07,
310 8 Server (LocalAddr = 0xF9) 311 9 Publisher for PID2 (LocalAddr =
312 to
337
VCR
Number
Remote Address=0x111)
0x20)
Remote Address=0x110)
0x21)
10 to 35 Not used.
Factory Setting

6.5.2 Function Block Execution Control

According to the instructions given in Section 6.3, set the execution cycle of the function blocks and schedule of execution.

6.6 Block Setting

Table 6.6 Link Object Parameters
Sub-
index
1 LocalIndex Sets the index of function
2 VcrNumber Sets the index of VCR to be
3 RemoteIndex Not used in FVX110. Set
4 ServiceOperation Set one of the following.
5 StaleCountLimit Set the maximum number
Parameter Description
block parameters to be combined; set “0” for Trend and Alert.
combined. If set to “0”, this link object is not used.
to “0”.
Set only one each for link object for Alert or Trend.
0: Undened 2: Publisher 3: Subscriber 6: Alert 7: Trend
of consecutive stale input values which may be received before the input status is set to BAD. To avoid the unnecessary mode transition caused when the data is not correctly received by subscriber, set this parameter to “2” or more.
Set the parameter for function block VFD.

6.6.1 Link Object

A link object combines the data voluntarily sent by the function block with the VCR. The FVX110 has 40 link objects. A single link object species one combination. Each link object has the parameters listed in Table 6.6. Parameters must be changed together for each VCR because the modications made to each parameter may cause inconsistent operation.
<6. Conguration>
6-7

6.6.2 Trend Object

It is possible to set the parameter so that the function block automatically transmits Trend. FVX110 has seven Trend objects, six of which are used for Trend in analog mode parameters and one is used for Trend in discrete mode parameter. A single Trend object species the trend of one parameter.
Each Trend object has the parameters listed in Table 6.8. The rst four parameters are the items to be set. Before writing to a Trend object, it is necessary to release the WRITE_LOCK parameter.
Table 6.7 Parameters for Trend Objects
Sub-
index
1 Block Index Sets the leading index
2 Parameter Relative
3 Sample Type Species how trends are
4 Sample Interval Species sampling
5 Last Update The last sampling time.
6 to 21List of Status Status part of a sampled
21 to 37List of Samples Data part of a sampled
Parameter Description
of the function block that takes a trend.
Index
Sets the index of parameters taking a trend by a value relative to the beginning of the function block.
taken. Choose one of the following 2 types:
1: Sampled upon
execution of a function block.
2: The average value is
sampled.
intervals in units of 1/32 ms. Set the integer multiple of the function block execution cycle.
parameter.
parameter.

6.6.3 View Object

This object forms a group of parameters in a block. One advantage brought by forming groups of parameters is the reduction of load for data transactions. View Object has the parameters listed in Table 6.10 and 6.11. Purpose of View Objects is shown in Table 6.9.
Table 6.9 Purpose of Each View Object
Description
VIEW_1 Set of dynamic parameters required by
operator for plant operation. (PV, SP, OUT, Mode etc.)
VIEW_2 Set of static parameters which need to be
shown to plant operator at once. (Range etc.)
VIEW_3 Set of all the dynamic parameters. VIEW_4 Set of static parameters for conguration or
maintenance.
Seven trend objects are factory-set as shown Table
6.8.
Table 6.8 Trend Object are Factory-Set
Index Parameters Factory Settings
32000 to
32005 32006 TREND_DIS.1 Not used.
TREND_FLT.1 to TREND_FLT.5
Not used.
<6. Conguration>
Table 6.10 View Object for Resource Block
Relative
Index
1 ST_REV 2 2 2 2 2 2 TAG_DESC 3 STRATEGY 2 4 ALERT_KEY 1 5 MODE_BLK 4 4 6 BLOCK_ERR 2 2 7 RS_STATE 1 1 8 TEST_RW
9 DD_RESOURCE 10 MANUFAC_ID 4 11 DEV_TYPE 2 12 DEV_REV 1 13 DD_REV 1 14 GRANT_DENY 2 15 HARD_TYPES 2 16 RESTART 17 FEATURES 2 18 FEATURE_SEL 2 19 CYCLE_TYPE 2 20 CYCLE_SEL 2 21 MIN_CYCLE_T 4 22 MEMORY_SIZE 2 23 NV_CYCLE_T 4 24 FREE_SPACE 4 25 FREE_TIME 4 4 26 SHED_RCAS 4 27 SHED_ROUT 4 28 FAULT_STATE 1 1 29 SET_FSTATE 30 CLR_FSTATE 31 MAX_NOTIFY 1 32 LIM_NOTIFY 1 33 CONFIRM_TIME 4 34 WRITE_LOCK 1 35 UPDATE_EVT 36 BLOCK_ALM 37 ALARM_SUM 8 8 38 ACK_OPTION 2 39 WRITE_PRI 1 40 WRITE_ALM 41 ITK_VER 2 42 SOFT_REV 43 SOFT_DESC 44 SIM_ENABLE_MSG 45 DEVICE_STATUS_1 4 46 DEVICE_STATUS_2 4 47 DEVICE_STATUS_3 4 48 DEVICE_STATUS_4 4 49 DEVICE_STATUS_5 4 50 DEVICE_STATUS_6 4 51 DEVICE_STATUS_7 4 52 DEVICE_STATUS_8 4 53 SOFTDWN_PROTECT 1 54 SOFTDWN_FORMAT 1 55 SOFTDWN_COUNT 2 56 SOFTDWN_ACT_AREA 1 57 SOFTDWN_MOD_REV 16 58 SOFTDWN_ERROR 2 59 SOFTDWN_HISTORY 60 SOFTDWN_HIST_INDEX 61 COMPATIBILITY_REV 1 62 CAPABILITY_LEV 1 63 CAPABILITY_CONFIG 2 64 WRITE_LOCK_LEVEL 1 65 SI_CONTROL_CODES 1 66 FD_VER 2
Parameter Mnemonic
1 2
View
3_1 3_2 4_1 4_2
Relative
Index
67 FD_FAIL_ACTIVE 4 4 68 FD_OFFSPEC_ACTIVE 4 4 69 FD_MAINT_ACTIVE 4 4 70 FD_CHECK_ACTIVE 4 4 71 FD_FAIL_MAP 4 72 FD_OFFSPEC_MAP 4 73 FD_MAINT_MAP 4 74 FD_CHECK_MAP 4 75 FD_FAIL_MASK 4 76 FD_OFFSPEC_MASK 4 77 FD_MAINT_MASK 4 78 FD_CHECK_MASK 4 79 FD_FAIL_ALM 80 FD_OFFSPEC_ALM 81 FD_MAINT_ALM 82 FD_CHECK_ALM 83 FD_FAIL_PRI 1 84 FD_OFFSPEC_PRI 1 85 FD_MAINT_PRI 1 86 FD_CHECK_PRI 1 87 FD_SIMULATE 9 88 FD_RECOMMEN_ACT 2 2 89 FD_EXTENDED_ACTIVE_1 4 90 FD_EXTENDED_ACTIVE_2 4 91 FD_EXTENDED_ACTIVE_3 4 92 FD_EXTENDED_ACTIVE_4 4 93 FD_EXTENDED_ACTIVE_5 4 94 FD_EXTENDED_ACTIVE_6 4 95 FD_EXTENDED_ACTIVE_7 4 96 FD_EXTENDED_ACTIVE_8 4 97 FD_EXTENDED_MAP_1 4 98 FD_EXTENDED_MAP_2 4
99 FD_EXTENDED_MAP_3 4 100 FD_EXTENDED_MAP_4 4 101 FD_EXTENDED_MAP_5 4 102 FD_EXTENDED_MAP_6 4 103 FD_EXTENDED_MAP_7 4 104 FD_EXTENDED_MAP_8 4 105 PRIVATE_1 106 PRIVATE_2 107 PRIVATE_3 108 PRIVATE_4 109 110 PRIVATE_6 111 PRIVATE_7 112 PRIVATE_8 113 PRIVATE_9 114 PRIVATE_10 115 PRIVATE_11
Parameter Mnemonic
PRIVATE_5
Total (# bytes) 40 32 77 61 73 32
1 2
6-8
View
3_1 3_2 4_1 4_2
<6. Conguration>
6-9
Table 6.11 View Object for LCD Transducer Block
Relative
Index
1 2 3 4 5 6 7 8 9
10
11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 38 39 40 41 42 43 44 45 46 47 48 49 50 51 52 53 54 55 56 57 58 59 60 61 62 63 64 65 66
Parameter Mnemonic
ST_REV TAG_DESC STRATEGY ALERT_KEY MODE_BLK BLOCK_ERR UPDATE_EVT BLOCK_ALM TRANSDUCER_DIRECTORY TRANSDUCER_TYPE XD_ERROR COLLECTION_DIRECTORY NOW_DISPLAYING DISP_TARGET_FORCE NO_OF_VALID_CON VALID_CON_SUMMARY MAO_CON_SUMMARY ISEL_CON_SUMMARY SIM_CON_SUMMARY BAR_GRAPH_SELECT EACH_BAR_GRAPH MAIN_TAG_SCROLL V_SCROLL_BAR SCROLL_DIRECTION DISP_PAGE_INFO DISP_QUIET_MODE DISP_FORMAT_TYPE DISPLAY_CYCLE DISPLAY_TEST DISPLAY_CONTRAST SQUAWK AMBIENT_TEMPERATURE MAIN_CONNECT_TYPE IN01_CONNECTION IN02_CONNECTION IN03_CONNECTION IN04_CONNECTION IN05_CONNECTION IN06_CONNECTION IN07_CONNECTION IN08_CONNECTION IN09_CONNECTION IN10_CONNECTION IN11_CONNECTION IN12_CONNECTION IN13_CONNECTION IN14_CONNECTION IN15_CONNECTION IN16_CONNECTION IN_01 IN_02 IN_03 IN_04 IN_05 IN_06 IN_07 IN_08 IN_09 IN_10 IN_11 IN_12 IN_13 IN_14 IN_15 IN_16 IN01_MAIN_TAG
View
1 2 3 4
2 2 2 2
4 4 2 2
2 2 2 2 1 1
1 1 1 1 1 1
2 2 2 2 2 2
2
1
4 4
1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1 1
1 1 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5 5
Relative
Index
67 68
2 1
2
1
1 1 1 1
1 1
1
1
69 70 71 72 73 74 75 76 77 78 79 80 81 82 83 84 85 86 87 88 89 90 91 92 93 94 95 96 97 98
99 100 101 102 103 104 105 106 107 108 109 110 111 112 113 114 115 116 117 118 119 120 121 122 123 124 125
Parameter Mnemonic
IN01_SUB_TAG IN01_SCALE IN02_MAIN_TAG IN02_SUB_TAG IN02_SCALE IN03_MAIN_TAG IN03_SUB_TAG IN03_SCALE IN04_MAIN_TAG IN04_SUB_TAG IN04_SCALE IN05_MAIN_TAG IN05_SUB_TAG IN05_SCALE IN06_MAIN_TAG IN06_SUB_TAG IN06_SCALE IN07_MAIN_TAG IN07_SUB_TAG IN07_SCALE IN08_MAIN_TAG IN08_SUB_TAG IN08_SCALE IN09_MAIN_TAG IN09_SUB_TAG IN09_SCALE IN10_MAIN_TAG IN10_SUB_TAG IN10_SCALE IN11_MAIN_TAG IN11_SUB_TAG IN11_SCALE IN12_MAIN_TAG IN12_SUB_TAG IN12_SCALE IN13_MAIN_TAG IN13_SUB_TAG IN13_SCALE IN14_MAIN_TAG IN14_SUB_TAG IN14_SCALE IN15_MAIN_TAG IN15_SUB_TAG IN15_SCALE IN16_MAIN_TAG IN16_SUB_TAG IN16_SCALE MS_CODE SERIAL_NO MANUFAC_DATE TEST_KEY1 TEST_KEY2 TEST_KEY3 TEST_1 TEST_2 TEST_3 TEST_4 TEST_5 TEST_6 Total (# bytes)
104 23 104 34
View
1 2 3 4
<6. Conguration>
Table 6.12 Indexes of View for Each Block
VIEW1VIEW2VIEW3VIEW
4
Resourse Block 40100 40101 40102 40103 LCD Transducer Block PID1 Function Block 40800 40801 40802 40803 PID2 Function Block 40810 40811 40812 40813 MAO1 Function Block 41000 41001 41002 41003 MAO2 Function Block 41010 41011 41012 41013 SC Function Block 41450 41451 41452 41453 IT Function Block 41600 41601 41602 41603 IS1 Function Block 41700 41701 41702 41703 IS2 Function Block 41710 41711 41712 41713 AR1 Function Block 41750 41751 41752 41753 AR2 Function Block 41760 41761 41762 41763
40250 40251 40252 40253

6.6.4 Function Block Parameters

Function block parameters can be read from the host or can be set. For a list of the parameters of blocks refer to “12. Parameter Lists”. For the function blocks, LM function and software download function, refer to Appendix 1 to 8.
6-10
<7. Explanation of Basic Items>

7. Explanation of Basic Items

7-1

7.1 Outline

This chapter provides an outline of the LCD transducer block and describes basic parameter setup procedures. For information on function blocks as well as the LM function and software download functions, refer to Appendix 1 to 8.

7.2 Setting and Changing Parameters for the Whole Process

IMPORTANT
Do not turn off the power immediately after making a setting. When data is saved to the EEPROM, redundant processing is performed to enhance reliability. If the power is turned off within 60 seconds after making a setting, the modied parameters are not saved and may return to their original values.
Operating mode
Many parameters require a change of operating mode of the function block to O/S (Out of Service) to rewrite parameter data. To change the operating mode of the function block, its MODE_BLK needs to be changed. The MODE_BLK is comprised of the four sub-parameters below: (1) Target (target mode): Parameter to set the operating mode of the
block. (2) Actual (Actual mode): Parameter to indicate the current operating
mode of the block. (3) Permit (Permitted mode): Parameter to indicate operating mode that the
block is allowed to take. (4) Normal (Normal mode): Parameter to indicate the operating mode the
block will usually take.

7.3 LCD Transducer Block

7.3.1 Function Outline

The LCD transducer block controls the indications displayed on the LCD. FVX110 displays process variables from eld instruments which have received in MAO or IS function block and also simulation input.

7.3.2 Operating mode

The operating conditions permitted for the LCD transducer block are Automatic (AUTO) and Out of Service (O/S) mode. Settings can normally be changed in the O/S mode, but can also be performed in the Auto mode except for changes of the block tag parameter of the block header in the LCD transducer block.

7.3.3 Indicator names and functions

The LCD consists of three elds: the top, center and bottom elds. The top eld shows the Main Tag which identies the instrument whose values are indicated (for example PD_Tag), and other freely settable information. It also shows the page information (number of displayed page)/(total number of display pages). The middle eld shows process value and measuring unit. The lower eld shows the Sub Tag, a eld indicating data required for identifying instruments whose values are displayed, communication status, bar graph and other information. At the center right edge, there is a scroll bar enabling visual conrmation of page numbers. The lower right corner displays an icon indicating the scroll knob turning direction and the center left edge provides an icon indicating communication status.
The communication signal
Main Tag
Page information display
Scroll bar
Sub tag, communication status bar graph (selected display)
Figure 7.1 Display design
Scroll knob turning direction
F0701.ai
<7. Explanation of Basic Items>
Table 7.1 Indicated values
Component
name
Top eld Shows the Main Tag and page number
Center eld Indicates process value and measuring
Lower eld Displays the Sub Tag (a settable
Additional displays
information. Maximum of 32 characters can be set for Main Tag. But 14 characters (8 characters in case page information indicates) is limit of displaying on LCD. Main Tag scroll enables to conrm more than 14 characters.
unit from eld instruments including +/­sign. “Squawk” indicate incase squawk function enabled.
descriptor), communication status and bar graphs. The scaling range of the bar graph must be set elsewhere.
▲ ▼ Shows scroll knob turning
Description
direction. (Single scroll mode)
7-2
Shows scroll knob turning direction (continuous scan mode)
Flashes when communication status is normal.

7.3.4 Communication status indication

The lower eld of the LCD shows communication status (Quality + SubStatus + Limit). Table 7.2 shows characters for each status displayed on the LCD.
<7. Explanation of Basic Items>
Table 7.2 Communication status indications
Quality Sub-status
Bad Non-specic
Conguration Error
Not Connected
Device Failure
Sensor Failure
No Comm, with LastUsableValue
No Comm, no LUV (NoComm_withNoUsableValue)
Out of Service
Uncertain Non-specic
Last Usable Value
Substitute/Manual Entry (SubstitudeValue)
Initial Value
Sensor Conversion not Accurate
Engineering Unit Range Violation
Sub-normal
Good(NC) Non-specic
Active Block Alarm
Active Advisory Alarm
Active Critical Alarm
Unack Block Alarm
Unack Advisory Alarm
Unack Critical Alarm
Good(C) Non-specic
Initialization Acknowledge
Initialization Request
Not Invited
Not Selected
Local Override
Fault State Active
Initial Fault State
“Invalid status” will be indicated in case of code not listed in chart above
limit (Upper line: LCD indication, Lower line: Status Code)
Not limited Low limited High limited Constant
Bad NonSpc 0x00
Bad ConfErr 0x04
Bad NotCnnct 0x08
Bad DevFail 0x0C
Bad SnsrFail 0x10
Bad NC LUV 0x14
Bad NCnoLUV 0x18
Bad OOS 0x1C
Unc NonSpc 0x40
Unc LUV 0x44
Unc S/M_Entr 0x48
Unc InitVal 0x4C
Unc SnCnv_nA 0x50
Unc EURangeV 0x54
Unc SubNrml 0x58
G(NC) NonSpc 0x80
G(NC) A_Blk 0x84
G(NC) A_Adv 0x88
G(NC) A_Crit 0x8C
G(NC) U_Blk 0x90
G(NC) U_Adv 0x94
G(NC) U_Crit 0x98
G(C) NonSpc 0xC0
G(C) InitAck 0xC4
G(C) InitReq 0xC8
G(C) NotInv 0xCC
G(C) NotSel 0xD0
G(C) LocOvr 0xD8
G(C) FSActiv 0xDC
G(C) InitFS 0xE0
Bad NonSpc L 0x01
Bad ConfErr L 0x05
Bad NotCnnct L 0x09
Bad DevFail L 0x0D
Bad SnsrFail L 0x11
Bad NC LUV L 0x15
Bad NCnoLUV L 0x19
Bad OOS L 0x1D
Unc NonSpc L 0x41
Unc LUV L 0x45
Unc S/M_Entr L 0x49
Unc InitVal L 0x4D
Unc SnCnv_nA L 0x51
Unc EURangeV L 0x55
Unc SubNrml L 0x59
G(NC) NonSpc L 0x81
G(NC) A_Blk L 0x85
G(NC) A_Adv L 0x89
G(NC) A_Crit L 0x8D
G(NC) U_Blk L 0x91
G(NC) U_Adv L 0x95
G(NC) U_Crit L 0x99
G(C) NonSpc L 0xC1
G(C) InitAck L 0xC5
G(C) InitReq L 0xC9
G(C) NotInv L 0xCD
G(C) NotSel L 0xD1
G(C) LocOvr L 0xD9
G(C) FSActiv L 0xDD
G(C) InitFS L 0xE1
Bad NonSpc H 0x02
Bad ConfErr H 0x06
Bad NotCnnct H 0x0A
Bad DevFail H 0x0E
Bad SnsrFail H 0x12
Bad NC LUV H 0x16
Bad NCnoLUV H 0x1A
Bad OOS H 0x1E
Unc NonSpc H 0x42
Unc LUV H 0x46
Unc S/M_Entr H 0x4A
Unc InitVal H 0x4E
Unc SnCnv_nA H 0x52
Unc EURangeV H 0x56
Unc SubNrml H 0x5A
G(NC) NonSpc H 0x82
G(NC) A_Blk H 0x86
G(NC) A_Adv H 0x8A
G(NC) A_Crit H 0x8E
G(NC) U_Blk H 0x92
G(NC) U_Adv H 0x96
G(NC) U_Crit H 0x9A
G(C) NonSpc H 0xC2
G(C) InitAck H 0xC6
G(C) InitReq H 0xCA
G(C) NotInv H 0xCE
G(C) NotSel H 0xD2
G(C) LocOvr H 0xDA
G(C) FSActiv H 0xDE
G(C) InitFS H 0xE2
7-3
Bad NonSpc C 0x03
Bad ConfErr C 0x07
Bad NotCnnct C 0x0B
Bad DevFail C 0x0F
Bad SnsrFail C 0x13
Bad NC LUV C 0x17
Bad NCnoLUV C 0x1B
Bad OOS C 0x1F
Unc NonSpc C 0x43
Unc LUV C 0x47
Unc S/M_Entr C 0x4B
Unc InitVal C 0x4F
Unc SnCnv_nA C 0x53
Unc EURangeV C 0x57
Unc SubNrml C 0x5B
G(NC) NonSpc C 0x83
G(NC) A_Blk C 0x87
G(NC) A_Adv C 0x8B
G(NC) A_Crit C 0x8F
G(NC) U_Blk C 0x93
G(NC) U_Adv C 0x97
G(NC) U_Crit C 0x9B
G(C) NonSpc C 0xC3
G(C) InitAck C 0xC7
G(C) InitReq C 0xCB
G(C) NotInv C 0xCF
G(C) NotSel C 0xD3
G(C) LocOvr C 0xDB
G(C) FSActiv C 0xDF
G(C) InitFS C 0xE3
<7. Explanation of Basic Items>
7-4

7.3.5 Indicator settings

To use the FVX110 as a eld indicator, information (Main Tag and Sub Tag) identifying eld instruments, units, bar graph scaling and other parameters must be set to enable display on the FVX110.
Selection of function block to receive output signals from eld instruments (MAIN_CONNECT_YTPE, INxx_CONNECTION)
Select function block to receive output signals from eld instruments from MAO or IS function block. Batch settings should start from the MAIN_ CONNECT_TYPE parameter in the LCD transducer block. To use the MAO function block to receive all 16 inputs, select 1: All connects to MAO-FB, to use the IS function block, select 2: All connects to ISEL-FB and to use a simulation instruction for all inputs, select 3: All are in simulate. To set a separate input source, start from the INxx_ CONNECTION parameter in the LCD transducer block. To use the MAO function block to receive inputs IN_01 to IN_08, set 1:from MAO-FB_1_INxx (xx: 01~08). To use the IS function block to receive the same inputs, set 2:from ISEL-FB_1_INxx (xx: 01~08). To use the MAO function block to receive inputs from IN_09 to IN_16, set 1:from MAO-FB_ 2_INxx (xx : 09~16). To use the IS function block to receive the same inputs, set 2:from ISEL_FB_2_ INxx (xx : 09~16). Select 0:In simulate for all inputs to perform a simulation instruction.
NOTE
Selecting 0: All are in simulate or 0: In simulate will display directly input test input values for IN_xx on the display.
Main Tag settings (INxx_MAIN_TAG)
The Main Tag is a memo eld for making settings used for entering the most important information to identify the indicating eld instrument (for example, a PD_TAG of eld instrument). Setting can be done in INxx_MAIN_TAG (xx: 01 to 16). Maximum of 32 characters can be set, but 14 characters are limit of indication on LCD. Scroll to view the digits beyond the rst 14 digits. Use MAIN_TAG_SCROLL to set the scroll Main Tag.
F0702.ai
Figure 7.2 Main Tag settings
NOTE
8 characters are allowed if page information have set to enable. To set MAIN_TAG_ SCROLL=1:Active, it is possible to view information exceeding the allowed number of characters through scrolling.
Indicator setting (INxx_SCALE)
Use INxx_SCALE(xx:01 to 16) to set measuring units, bar graph scaling and the number of decimal point digits of display values. Scaling is normally set to the same value as the eld instrument measurement range. Set the upper limit and lower limit values in EU at 100% and EU at 0%. Scaling is not a mandatory setting, but is required to enable display of bar graphs.
Valid input values (VALID_CON_SUMMARY)
Select valid IN_xx (xx: 01~16) to indicate in LCD at VALID_CON_SUMMARY. IN_xx which is not chosen at VALID_CON_SUMMARY will not indicated in LCD. This setting is reected to the MAO_CON_ SUMMARY, ISEL_CON_SUMMARY and the SIM_CON_SUMMARY.
F0703.ai
Figure 7.3 Indicator value settings
You can set the range of decimal places that are displayed after the decimal point from 0 to 4 digits. The number of decimal places is automatically adjusted so that 5 digits are displayed. Any measuring unit in the table of section 7.3.8 can be selected. Here, (N) indicates “Normal” (normal state) and (S) indicates “Standard” (standard state) for standard mass ow rate.
<7. Explanation of Basic Items>
Scroll bar display setting (V_SCROLL_BAR)
NOTE
• When 5 digits are displayed, the values beyond the decimal point are rounded off.
• When the sum of displayed digits and decimal places is 5 or more digits, the number of displayed digits and decimal place digits is automatically adjusted to 5 digits
Use V_SCROLL_BAR to set the scroll bar display setting. Set V_SCROLL_BAR = 0: Inactive to turn off the scroll bar display and set it to V_SCROLL_ BAR = 1 Active to have it on at all times. Selecting V_SCROLL_BAR = 2: Knob link will turn on the scroll bar display only during display switching and turns off the display within a few seconds.
regardless of decimal place setting.
Sub Tag settings (INxx_MAIN_TAG)
The Sub Tag is a memo eld for making settings used for entering information (for example, AI1.OUT or AI1 PV1 and other I/O block information) that is to be displayed to identify a eld instrument in addition to the information displayed by the Main Tag. Use
Figure 7.5 Scroll bar settings
F0705.ai
INxx_SUB_TAG ( xx: 01 to 16) for setting Sub Tags. A total of 32 characters can be displayed 14 of which appear on the screen.
Changing scroll direction (SCROLL_ DIRECTION)
The user can change the direction of display changes made using the scroll knob. Selecting 0: Turn page clockwise for SCROLL_DIRECTION increases page numbers (For example: 1/16 à 2/16 à à 16/16 à 1/16à … when the scroll knob is turned clockwise). Selecting 1:Turn page
F0704.ai
Figure 7.4 Sub Tag settings
counter-clockwise increase page numbers when the scroll knob is turned counter-clockwise. 0:Turn page clockwise is the factory default setting.
7-5
Bar graph setting example (BAR_GRAPH_SELECT, EACH_BAR_GRAPH)
The bar graph in the lower eld on the LCD allows the user to select either (BAR_GRAPH_SELECT) to display all IN_xx (xx:01 to 16) or to display an individual selection of inputs (EACH_BAR_ GRAPH). Bar graphs display upper and lower limit values according to values scaled using INxx_ SCALE (xx: 01 to 16). In a batch bar graph setting, setting BAR_GRAPH_ SELECT=0: All are set to inactive will turn off all bar graph displays and setting 2: All are set to active will display bar graphs on all screens. When bar graphs are enabled, the lower display eld will alternately display Sub Tag, communication status and bar graphs in stated order according to the interval set by DISPLAY_CYCLE.
Page number information settings (DISP_ PAGE_INFO)
Page number information for process values indicated by the FVX110 can be displayed in a minute format. The denominator indicating the total number of pages is the total number of IN_xx (xx:01 to 16) specied using VALID_CON_SUMMARY above.
F0706.ai
Figure 7.6 Setting page number information
<7. Explanation of Basic Items>
7-6
NOTE
DISP_PAGE_INFO does not display numbers of function blocks whose inputs are valid. It only displays the numbers of total inputs that are valid, which do not necessarily correspond to input signal numbers and page numbers displayed by the minute of function blocks. Example: When IN_01, IN_03, IN_04 inputs
are valid for the function block of the VALID_CON_SUMMARY, page number information is displayed as 1/3, 2/3 and 3/3.
When DISP_PAGE_INFO is 0: Knob link, page information is displayed only when switching screens and disappears after a few seconds. Page information is displayed at all times when DISP_PAGE_INFO is set to 1: Active and displays information for highlighted pages when DISP_ PAGE_INFO is set to 2: Active (Reverse).
Setting screen displaying cycle (DISPLAY_ CYCLE)
Select from AUTO, 0.5 sec, 1.0 sec, 2.0 sec, or
4.0 sec for screen displaying cycle. This cycle determines the displaying cycle in scan mode, displaying cycle of indication in the lower display eld, scroll bar movement cycle and cycle of communication icon ashing. When set to AUTO, displaying cycle listed above are automatically set according to ambient temperature where FVX110 installed (-10 °C is the border of temperature) Displaying cycle is listed in Table 7.3.
NOTE
When the ambient temperature where FVX110 installed is very low, Please set the DISPLAY_ CYCLE to AUTO or more than 2.0 sec.
NOTE
Please don’t charge DISPLAY_CYCLE setting during squawk. It will be cause of stopping squawk indication.
Table 7.3 Screen displaying cycle
Seting of DISPLAY_CYCLE
0:
Auto
Ambient
Temperature
>
-10 ˚C≤-10 ˚C
Object Parameter Setting Time
Scan mode - 0.5 sec 5 sec 0.5 sec 1 sec 2 sec 4 sec Flashi ng cyc le of comm. Signal Display cycle of lower eld - 1 sec 5 sec 0.5 sec 1 sec 2 sec 4 sec
Main Tag Scrolling speed ()is scroll starting time
Scroll bar moving speed (Display out time for 2:Knob link)
Display cycle of Squawk Display action after backlight off Display out time of Page number information
MAIN_TAG_SCROLL
V_SCROLL_BAR
SQUAWK 1:Squawk 0.5 sec 5 sec 0.5 sec 1 sec 2 sec 4 sec
DISP_QUIET_MODE
DISP_PAGE_INFO 0:Knob link 4 sec 5 sec 4 sec 4 sec 4 sec 4 sec
- 1 sec 10 sec 1 sec 2 sec 4 sec 8 sec
0.25
1:Active
(2 sec)
1:Active 0.5 sec 5 sec 0.5 sec 1 sec 2 sec 4 sec
2:Knob link 4 sec 5 sec 4 sec 4 sec 4 sec 4 sec
1:Turn page cyclic 1 sec 5 sec 0.5 sec 1 sec 2 sec 4 sec
sec
5 sec
(10 sec)
1:
0.5sec
0.5sec
(1 sec)
2:
1.0sec
1 sec
(2 sec)
3:
2.0sec
2 sec
(4 sec)
4:
4.0sec
4 sec
(8 sec)
<7. Explanation of Basic Items>

7.3.6 Other display settings

Setting display mode after backlight off (DISP_ QUIET_MODE)
This setting allows the user to set the display mode after backlight off. DISP_QUIET_MODE: 0 = Stay at last target (the display remains in the state it had before backlight off), 1: Turn page cyclic (engages scan mode after backlight off), 2: Display off (the screen is turned off after backlight off).
Squawk (SQUAWK)
This function displays a notice that identies the communicating FVX110. Executing this function alternates the screen shown in Figure 7.7. The squawk display is automatically cancelled after about a minute, but can also be cancelled by turning the scroll knob.
7-7
F0707.ai
Figure 7.7 Screen displayed during squawk
operation
<7. Explanation of Basic Items>

7.3.7 Flow chart of indicator settings

Setting block that is the source of
input indicator value
7-8
Individual settings
(INxx_CONNECTION (xx:01 to 16)
Making input values valid
(VALID_CON_SUMMARY)
Main Tag setting
(INxx_MAIN_TAG (xx: 01 to 16))
Main Tag scroll setting
(MAIN_TAG_SCROLL)
Indicator value setting
(INxx_SCALE (xx: 01 to 16))
Bar graph scaling (upper limit value)
(EU_at_100%)
Bar graph scaling (Lower limit value
(EU_at_0%)
Unit selection (Units_Index)
Batch settings
(MAIN_CONNECT_TYPE)
A value up to 32 characters long can be set
)
Select unit displayed in the table
Set the number of decimal places
to be displayed (Decimal_Point)
Sub Tag display data setting
(INxx_SUB_TAG (xx: 01 to 16))
Bar graph setting example
Bar graph setting example
(BAR_GRAPH_SELECT)
(V_SCROLL_BAR)
Scroll knob turning direction setting
(SCROLL_DIRECTION)
Page information display setting
(DISP_PAGE_INFO)
Display cycle setting
(DISPLAY_CYCLE)
A value up to 32 characters long can be set. However, the indicator displays only 14 characters.
Example of individual
bar graph setting
(EACH_BAR_GRAPH)
Scroll bar setting
Select from AUTO, 0.5 s, 1.0 s, 2.0 s and 4.0 s
Figure 7.8 Flow chart of indicator settings
F0708.ai
<7. Explanation of Basic Items>

7.3.8 Units the auto link function allows you to display on the LCD

7-9
Index Unit Display on the LCD
1000 K
1001 °C
1002 °F
1003 °R
1004 rad
1005 °
1006 min
1007 sec
1008 gon
1009 rev
1010 m
1011 km
1012 cm
1013 mm
1014 μm
1015 nm
1016 pm
1017 Å
1018 ft
1019 in
1020 yd
1021 mile
1022 nautical mile
1023 m2
1024 km2
1025 cm2
1026 dm2
1027 mm2
1028 a
1029 ha
1030
in2
1031 ft2
1032 yd2
1033 mile2
1034 m3
K
° C
° F
° R
r a d °
'
''
g o n
r e v
m
k m
c m
m m
u m
n m
p m ˚ A
f t
i n
y d
m i l e n a u t i m i l e
2
m
2
k m
2
c m
2
d m
2
m m
a
h a
2
i n
2
f t
2
y d
m i l e
3
m
Index Unit Display on the LCD
1035 dm3
1036 cm3
1037 mm3
1038 L
1039 cl
1040 ml
1041 hl
1042 in3
1043 ft3
1044 yd3
1045 mile2
1046 pint
1047 quart
1048 gal
1049 Imp Gal
1050 bushel
1051 bbl
1052 bbl (liquid)
1053 SCF
1054 sec
1055 ksec
1056 msec
1057 μsec
1058 min
1059 h
1060 d
1061 m/s
1062 mm/s
1063 m/h
1064 km/h
1065 knot
1066 in/s
1067 ft/s
2
1068 yd/s
1069 in/min
3
d m
3
c m
3
m m
L
c l
m l
h l
3
i n
3
f t
3
y d
m i l e
p i n t
q u a r t
g a l I m p
G a l
b u s h
e l
b b l b b l ( l i q )
S C F
s
k s
m s
u s
m i n
h
d
m / s
m m / s
m / h
k m / h
k n o t
i n / s
f t / s
y d / s i n / m i n
3
<7. Explanation of Basic Items>
7-10
Index Unit Display on the LCD
1070 ft/min
1071 yd/min
1072 in/h
1073 ft/h
1074 yd/h
1075 MPH
1076 m/s2
1077 Hz
1078 THz
1079 GHz
1080 MHz
1081 kHz
1082 1/s
1083 1/min
1084 rev/s
1085 RPM
1086 rad/s
1087 1/s2
1088 kg
1089 g
1090 mg
1091 Mg
1092 t
1093 oz
1094 lb
1095 STon
1096 Lton
1097 kg/m2
1098 Mg/m2
1099 kg/m2
1100 g/cm3
1101 g/m3
1102 t/m3
1103 kg/L
1104 g/ml
1105 g/L
f t / m i n y d / m i n
i n / h
f t / h
y d / h
M P H
m / s
H z
T H z
G H z
M H z
k H z
1 / s 1 /
m i n
r e v
/ s
R P M r a d
/ s
1 / s
k g
g
m g
M g
t
o z
l
b
S T o n
L T o n k g
/ m
M g
/ m k g / d m g / c m
g / m
t / m
k g / L
g / m l
g / L
Index Unit Display on the LCD
1106 lb/in3
1107 lb/ft3
1108 lb/gal
1109 STon/yd3
1110 deg Twad
1111 Deg Baum hv
2
1112 dg Baum lt
1113 dep API
1114 SGU
1115 kg/m
1116 mg/m
1117 tex
1118 kg•m2
1119 kg•m/s
1120 N
1121 MN
1122 kN
2
1123 mN
1124 μN
1125 kg•m2/s
1126 N•m
1127 MN•m
1128 kN•m
1129 mN•m
1130 Pa
1131 Gpa
1132 Mpa
3
3
3
3
3
3
1133 kPa
1134 mPa
1135 μPa
1136 hPa
1137 bar
1138 mbar
1139 torr
1140 atm
1141 psi
l b / i n l b / f t
3
3
l b / g a l S T o n / y d
3
d e g T w a d d e g B a u m h v d e g B a u m l t d e g
A P I
S G U
k g / m
m g / m
t e x k g
m
2
k g • m
/ s
N
M N
k N
m N
u N k g •
2
m
/ s
N • m
M N • m
k N • m
m N • m
P a
G P a
M P a
k P a
m P a
u P a
h P a
b a r
m b a r
t o r r
a t m
p s i
<7. Explanation of Basic Items>
7-11
Index Unit Display on the LCD
1142 psia
1143 psig
1144 g/cm2
1145 k/cm2
1146 inH2O
1147 inH2O (4°C)
1148 inH2O (68°F)
1149 mmH2O
1150 mmH2O (4°C)
1151 mmH2O (68°F)
1152 ftH2O
1153 ftH2O (4°C)
1154 ftH2O (68°F)
1155 inHg
1156 inHg (0°C)
1157 mmHg
1158 mmHg (0°C)
1159 Pa•s
1160 m2/s
1161 P
1162 cP
1163 St
1164 cSt
1165 N/m
1166 mN/m
1167 J
1168 EJ
1169 PJ
1170 TJ
1171 GJ
1172 MJ
1173 kJ
1174 mJ
1175 W•h
1176 TW•h
1177 GW•h
p s i a
p s i g g / c m k g / c m
i n H 2 O i n H 2 O ( 4 C ) i n H 2 O ( 6 8 F )
m m H 2 O m m H 2 O ( 4 C ) m m H 2 O ( 6 8 F )
f t H 2 O f t H 2 O ( 4 C ) f t H 2 O ( 6 8 F )
i n H g i n H g ( 0
C )
m m H g m m H g ( 0 C )
P a s
2
m
/ s
P
c P
S t
c S t
N / m
m N / m
J
E J
P J
T J
G J
M J
k J
m J
W • h
T W • h
G W • h
Index Unit Display on the LCD
1178 MW•h
1179 kW•h
2
2
1180 cal
1181 kcal
1182 Mcal
1183 Btu
1184 decatherm
1185 ft-lb
1186 W
1187 TW
1188 GW
1189 MW
1190 kW
1191 mW
1192 μW
1193 nW
1194 pW
1195 Mcal/h
1196 MJ/h
1197 Btu/h
1198 hp
1199 W/(m•K)
1200 W/(m2•K)
1201 m2•K/W
1202 J/K
1203 kJ/K
1204 J/(kg•K)
1205 kJ/(kg•K)
1206 J/kg
1207 MJ/kg
1208 KJ/kg
1209 A
1210 kA
1211 mA
1212 μA
1213 nA
M W • h
k W • h
c a l
k c a l
M c a l
B t u d e c a t h e r m f t
- l b
W
T W
G W
M W
k W
m W
u W
n W
p W M c a l
/ h
M J / h B t u
/ h
h p W / ( m • K ) W / (
2
m
K )
2
m
K / W
J / K
k J / K J / ( k g • K ) k J / ( k g • K )
J / k g M J
/ k g
k J
/ k g
A
k A
m A
u A
n A
<7. Explanation of Basic Items>
7-12
Index Unit Display on the LCD
1214 pA
1215 C
1216 MC
1217 kC
1218 μC
1219 nC
1220 pC
1221 A•h
1222 C/m3
1223 C/mm3
1224 C/cm3
1225 kC/m3
1226 mC/m3
1227 μC/m3
1228 C/m2
1229 C/mm2
1230 C/cm2
1231 kC/m2
1232 mC/m2
1233 μC/m2
1234 V/m
1235 MV/m
1236 kV/m
1237 V/cm
1238 mV/m
1239 μV/m
1240 V
1241 MV
1242 kV
1243 mV
1244 μV
1245 F
1246 mF
1247 μF
1248 nF
1249 pF
p A
C
M C
k C
u C
n C
p C
A • h
C / m C /
m m C /
c m k C
/ m m C
/ m u C
/ m
C / m C /
m m C /
c m k C
/ m m C
/ m u C
/ m
V / m
M V / m
k V / m
V / c m
m V / m
u V / m
V
M V
k V
m V
u V
F
m F
u F
n F
p F
Index Unit Display on the LCD
1250 F/m
1251 μF/m
1252 nF/m
1253 pF/m
1254 C•m
1255 A/m2
1256 MA/cm2
1257 A/cm2
3
3
3
3
3
3
2
2
2
2
2
2
1258 KA/m2
1259 A/m
1260 kA/m
1261 A/cm
1262 T
1263 mT
1264 μT
1265 nT
1266 Wb
1267 mWb
1268 Wb/m
1269 kWb/m
1270 H
1271 mH
1272 μH
1273 nH
1274 picoH
1275 H/m
1276 μH/m
1277 nH/m
1278 A•m2
1279 N•m2/A
1280 Wb•m
1281 Ω
1282
1283
1284 kΩ
1285
F / m
u F / m
n F / m
p F / m
C • m
/ m
c m
/ m
2
2
2
2
A / m M A
A /
k A
A / m
k A / m
A / c m
T
m T
u T
n T
W b
m W b
W b / m k W b
/ m
H
m H
u H
n H
p i c o H
H / m
u H / m
n H / m
A • m N • m
2
2
/ A
W b • m
o h m
G o h m
M o h m
k o h m
m o h m
<7. Explanation of Basic Items>
7-13
Index Unit Display on the LCD
1286 μΩ
1287 S
1288 kS
1289 mS
1290 μS
1291 Ω•m
1292 GΩ•m
1293 MΩ•m
1294 kΩ•m
1295 Ω•cm
1296 mΩ•m
1297 μΩ•m
1298 nΩ•m
1299 S/m
1300 MS/m
1301 kS/m
1302 mS/cm
1303 μS/mm
1304 1/H
1305 sr
1306 W/sr
1307
W/(sr•m2)
1308 W/m2
1309 lm
1310 lm•s
1311 lm•sh
1312 lm/m2
1313 lm/W
1314 lx
1315 lx•s
1316 cd
1317 cd/m2
1318 g/s
1319 g/min
1320 g/h
1321 g/d
u o h m
S
k S
m S
u S o h m
m
G o h m
m
M o h m
m
k o h m
m
o h m
c m
m o h m
m
u o h m
m
n o h m
m
S / m
M S / m
k S / m m S
/ c m
u S
/ m m
1 / H
s r
W / s r W / ( s r
m
W / m
l m
l m • s
l m • h l m
/ m
l m / W
l x
l x s
c d c d
/ m
g / s g / m i n
g / h
g / d
Index Unit Display on the LCD
1322 kg/s
1323 kg/min
1324 kg/h
1325 kg/d
1326 t/s
1327 t/min
1328 t/h
1329 t/d
1330 lb/s
1331 lb/min
1332 lb/h
1333 lb/d
1334 STon/s
1335 STon/min
1336 STon/h
1337 STon/d
1338 LTon/s
1339 LTon/min
1340 LTon/h
1341 LTon/d
1342 %
2
)
2
1343 %sol/wt
1344 %sol/vol
1345 % stmqual
1346 m3/min
1347 m3/s
2
1348 m3/min
1349 m3/h
1350 m3/d
1351 L/s
1352 L/min
2
1353 L/h
1354 L/d
1355 ML/d
1356 CFS
1357 CFM
k g / s k g / m i n
k g / h
k g / d
t / s t / m i n
t / h
t / d
l b / s l b / m i n
l b / h
l b / d S T o n
/ s S T o n / m i n S T o n
/ h S T o n
/ d L T o n
/ s L T o n / m i n L T o
n
/ h L T o n
/ d
% % s o l
/ w t % s o l / v o l % s t m q u a l % p l a t o
3
m
/ s
3
m / m i n
3
m
/ h
3
m
/ d
L / s L / m i n
L / h
L / d
M L / d
C F S
C F M
<7. Explanation of Basic Items>
7-14
Index Unit Display on the LCD
1358 CFH
1359 ft3/d
1360 CFM (0°C, 1atm)
1361 CFH (0°C, 1atm)
1362 gal/s
1363 GPM
1364 gal/h
1365 gal/d
1366 Mgal/d
1367 IGal/s
1368 IGal/min
1369 IGal/h
1370 IGal/d
1371 bbl/s
1372 bb/min
1373 bbl/h
1374 bbl/d
1375 kW/m2
1376 mW/m2
1377 μW/m2
1378 pW/m2
1379 Pa•s/m3
1380 N•s/m
1381 Pa•s/m
1382 B
1383 dB
1384 mol
1385
kmol
1386 mmol
1387 μmol
1388 kgmol
1389 g/mol
1390 m3/mol
1391 d3/mol
1392 cm3/mol
1393 L/mol
C F H
3
f t
/ d
C F M
( S )
C F H
( S )
g a l
/ s
G P M g a l
/ h
g a l
/ d
M g a l
/ d
I G a l
/ s I G a l / m i n I G a l
/ h I G a l
/ d b b l
/ s b b l / m i n b b l
/ h b b l
/ d k W
/
m m W
/ m
u W
/ m
p W
/ m
P a s
/ m
N • s
/ m P a s
/ m
B
d B
m o l
k m o l
m m o l
u m o l k g / m o l g / m o l
3
m / m o l
3
d m / m o l
3
c m / m o l L / m o l
Index Unit Display on the LCD
1394 J/mol
1395 kJ/mol
1396 J/mol k
1397 mol/m3
1398 mol/dm3
1399 mol/L
1400 mol/kg
1401 mmol/kg
1402 Bq
1403 MBq
1404 kBq
1405 Bq/kg
1406 kBq/kg
1407 MBq/kg
1408 Gy
1409 mGy
1410 rad
2
2
2
2
3
1411 Sv
1412 mSv
1413 rem
1414 C/kg
1415 mC/kg
1416 R
1417 1/J•m3
1418 e/V•m3
1419 m3/C
1420 V/k
1421 mV/K
1422 pH
1423 ppm
1424 ppb
1425 ppt
1426 degBrix
1427 degBall
1428 proof/vol
1429 proof/mass
J / m o l k J / m o l J / m o l K m o l
m o l / d m
/ m
3
3
m o l
/ L
m o l
/ k g
m m o l
/ k g
B q
M B q
k B q B q
/ k g
k B q
/ k g
M B q
/ k g
G y
m G y
r a d
S v
m S v
r e m
C / k g m C
/ k g
R 1 / J
e / V
m
m
m
3
3
3
/ C
V / K
m V / K
p H
p p m
p p b
p p t d e g B r i x d e g B a l l p r o o f / v o l p r o o f / m a s s
<7. Explanation of Basic Items>
7-15
Index Unit Display on the LCD
1430 lb/Igal
1431 kcal/s
1432 kcal/min
1433 kcal/h
1434 kcal/d
1435 Mcal/s
1436 Mcal/min
1437 Mcal/d
1438 kJ/s
1439 kJ/min
1440 kJ/h
1441 kJ/d
1442 MJ/s
1443 MJ/min
1444 MJ/d
1445 Btu/s
1446 Btu/min
1447 Btu/d
1448 μgal/s
1449 mgal/s
1450 kgal/s
1451 Mgal/s
1452 μgal/min
1453 mgal/min
1454 kgal/min
1455 Mgal/min
1456 μgal/h
1457 mgal/h
1458 kgal/h
1459 Mgal/h
1460 μgal/d
1461 mgl/d
1462 kgal/d
1463 μImpGal/s
1464 mImpGal/s
1465 kImpGal/s
l b / I G a l k c a l
/ s k c a l / m i n k c a l
/ h k c a l
/ d M c a l
/ s M c a l / m i n M c a l
/ d
k J / s k J / m i n
k J / h
k J / d
M J / s M J / m i n
M J / d B t u
/ s B t u / m i n B t u
/ d u g a l
/ s m g a l
/ s k g a l
/ s M g a l
/ s u g a l / m i n m g a l / m i n k g a l / m i n M g a l / m i n u g a l
/ h m g a l
/ h k g a l
/ h M g a l
/ h u g a l
/ d m g a l
/ d k g a l
/ u I m p G a l / s m I m p G a l / s k I m p G a l / s
Index Unit Display on the LCD
1466 MImpGal/s
1467 μIGal/min
1468 mIGal/min
1469 kIGal/min
1470 MIGal/min
1471 μImpGal/h
1472 mImpGal/h
1473 kImpGal/h
1474 MImpGal/d
1475 μImpGal/d
1476 mImpGal/d
1477 kImpGal/d
1478 MImpGal/d
1479
μbbl/s
1480 mbbl/s
1481 kbbl/s
1482 Mbbl/s
1483
μbbl/min
1484 mbbl/min
1485 kbbl/min
1486 Mbbl/min
1487 μbbl/h
1488 mbbl/h
1489
kbbl/h
1490 Mbbl/h
1491 μbbl/d
1492 mbbl/d
1493 kbbl/d
1494 Mbbl/d
1495 μm3/s
1496 mm3/s
1497 km3/s
d
1498 M3/s
1499 μm3/min
1500
mm3/min
1501 km3/min
M I m p G a l / s u I G a l / m i n m I G a l / m i n k I G a l / m i n M I G a l / m i n u I m p G a l / h m I m p G a l / h k I m p G a l / h M I m p G a l / h u I m p G a l / d m I m p G a l / d k I m p G a l / M I m p G a l / d u b b l
/ s
m b b l
/ s
k b b l
/ s
M b b l
/ s u b b l / m i n m b b l / m i n k b b l / m i n M b b l / m i n u b b l
/ h m b b l
/ h k b b l
/ h M b b l
/ h u b b l
/ d m b b l
/ d k b b l
/ d M b b l
/ d
3
u m
/ s
3
m m
/ s
3
k m
/ s
3
M m
/ s
3
u m / m i n
3
m m / m i n
3
k m / m i n
d
<7. Explanation of Basic Items>
7-16
Index Unit Display on the LCD
3
1502 Mm3/min
1503 μm3/h
1504 mm3/h
1505 km3/h
1506 Mm3/h
1507 μm3/d
1508 mm3/d
1509 km3/d
1510 Mm3/d
1511 cm3/s
1512 cm3/min
1513 cm3/h
1514 cm3/d
1515 kcal/kg
1516 Btu/lb
1517 kL
1518 kL/min
1519 kL/h
1520
kL/d
1521 m3 (0°C, 1atm)
1522 m3/s (0°C, 1atm)
1523 m3/min (0°C, 1atm)
1524 m3/h (0°C, 1atm)
1525 m3/d (0°C, 1atm)
1526 m3 (20°C, 1atm)
1527 m3/s (20°C, 1atm)
1528 m3/mine(20°C, 1atm)
1529 m3/h(20°C, 1atm)
1530 m3/d (20°C, 1atm)
1531 L (0°C, 1atm)
1532 L/s (0°C, 1atm)
1533 L/min (0°C, 1atm)
1534 L/h (0°C, 1atm)
1535 L/d (0°C, 1atm)
1536 L (20°C, 1atm)
1537 L/s (20°C, 1atm)
M m / m i n
3
u m
/ h
3
m m
/ h
3
k m
/ h
3
M m
/ h
3
u m
/ d
3
m m
/ d
3
k m
/ d
3
M m
/ d
3
c m
/ s
3
c m / m i n
3
c m
/ h
3
c m
/ d
k c a l
/ k g
B t u
/ l b
k L k L / m i n
k L / h
k L / d
3
m
( N )
3
m
( N )
/ s
3
m
( N )
/ m i n
3
m
( N )
/ h
3
m
( N )
/ d
3
m
( S )
3
m
( S )
/ s
3
m
( S )
/ m i n
3
m
( S )
/ h
3
m
( S )
/ d
L ( N ) L ( N ) / s L ( N ) / m i n L ( N ) / h L ( N ) /
d
L ( S ) L ( S ) / s
Index Unit Display on the LCD
1538 L/min (20°C, 1atm)
1539 L/h (20°C, 1atm)
1540 L/d (20°C, 1atm)
1541 Paa
1542 Pag
1543 Gpaa
1544 Gpag
1545 Mpaa
1546 Mpag
1547 kPaa
1548 kPag
1549 mPaa
1550 mPag
1551
μPaa
1552 μPag
1553 hPaa
1554 hPag
1555 g/cm3a
1556 g/cm2a
1557 kg/cm2a
1558 kg/cm2g
1559 inH2Oa
1560 inH2Og
1561 inH2Oa (4°C)
1562 inH2Og (4°C)
1563 inH2Oa (68°F)
1564 inH2Og (68°F)
1565 mmH2Oa
1566 mmH2Og
1567 mmH2Oa (4°C)
1568 mmH2Og (4°C)
1569 mmH2Oa (68°F)
1570 mmH2Og (68°F)
1571 ftH2Oa
1572 ftH2Og
1573 ftH2Oa (4°C)
L ( S ) / m i n L ( S ) / h L ( S ) / d
P a a
P a g
G P a a
G P a g
M P a a
M P a g
k P a a
k P a g
m P a a
m P a g
u P a a
u P a g
h P a a
h P a g g /
2
c m g /
2
c m k g /
2
c m k g /
2
c m i n H 2 O
i n H 2 O
i n H 2 O a ( 4 C ) i n H 2 O g ( 4 C ) i n H 2 O a ( 6 8 F i n H 2 O g ( 6 8 F m m H 2 O
m m H 2 O
m m H 2 O a ( 4 C ) m m H 2 O g ( 4 C ) m m H 2 O a ( 6 8 F m m H 2 O g ( 6 8 F f t H 2 O
f t H 2 O
f t H 2 O a ( 4 C )
a
g
a
g
a
g
a
g
a
g
<7. Explanation of Basic Items>
7-17
Index Unit Display on the LCD
1574 ftH2Og (4°C)
1575 ftH2Oa (68°F)
1576 ftH2Og (68°F)
1577 inHga
1578 inHgg
1579 inHga (0°C)
1580 inHgg (0°C)
1581 mmHga
1582 mmHgg
1583 mmHga (0°C)
1584 mmHgg (0°C)
1585 mV/pH
1586 μS/cm
1587 MΩ•cm
f t H 2 O g ( 4 C ) f t H 2 O a ( 6 8 F f t H 2 O g ( 6 8 F i n H g
i n H g
i n H g a ( 0 C ) i n H g g ( 0 C ) m m H g
m m H g
m m H g a ( 0 C ) m m H g g ( 0 C ) m V
/ p H
u S
/ c m
M o h m
c m
1588 no units
1589 ml/min
1590 Garg
1591 mGarg
1592 ft/s2
1593 G's
1594 microns
1595 mils
1596 lb/in
1597 Bara
1598 MSCFD
1599 MMSCFD
1600 MLB/H
1601 nA/ppm
1602 mS/m
1603 μS/m
1604 kΩ•cm
1605 %/°C
1606 pH/°C
1607 /cm
1608 mg/L
1609 Mmcells/mL
m l / m i n
B a r g m B a r
f t
/ s
G ' s m i c r o
m i l s l b
/ i n
B a r a
M S C F D M M S C F
M L B
/ H n A / p p m
m S / m
u S / m k o h m
c m
% / ° C p H /
° C
/ c m
m g / L M M c e l l s / m L
a
g
a
g
g
2
n s
Index Unit Display on the LCD
1610 AU
1611 cnt/g
1612 EBC
1613 FTU
1614 OD
1615 Unitless
1616 J/g
1617 Ml/h
1618 Ml/min
1619 kL/s
1620 kft3/d
1621 kCFH
1622 kCFM
1623 kCFS
1624 mft3/d
1625 mCFH
1626 mCFM
1627 mCFS
1628 kbbl(US Beer)/d
1629 kbbl (US Beer)/h
1630 kbbl (US Beer)/min
1631 bbl(US Beer)/d
1632 bbl (US Beer)/h
1633 bbl (US Beer)/min
1634 bbl (US Beer)/s
D
1635 mbbl(US Beer)/d
1636 mbbl (US Beer)/h
1637 mbbl (US Beer)/min
1638 mbbl (US Beer)/s
1639 μbbl (US Beer)/min
1640 μbbl (US Beer)/s
1641 klb (US)/d
1642 klb (US)/h
1643 klb (US)/min
1644 klb (US)/s
1645 Ml
A U c n t
/ s
E B C
F T U
O D U n i t l e s s
J / g
M l / h M l / m i n
k L / s k f t
3
/ d
k C F H
k C F M
k C F S m f t
3
/ d
m C F H
m C F M
m C F S k b b l ( U B ) / d k b b l ( U B ) / h k b b l U B / m i n b b l ( U B r ) / d b b l ( U B r ) / h b b l U B / m i n b b l ( U B r ) / s m b b l ( U B ) / d m b b l ( U B ) / h m b b l U B / m i n m b b l ( U B ) / s u b b l U B / m i n u b b l ( U B )
/ s k l b ( U S ) / d k l b ( U S ) / h k l b U S / m i n k l b ( U S ) / s
M l
<7. Explanation of Basic Items>
7-18
Index Unit Display on the LCD
1646 mBara
1647 1/32 mec
1648 kgal
1649 kImpGal
1650 WT-%
1651 Vol-%
1652 lbf/in
1653 Mft3/d
1654 Mm3/d
1655 ac-in/s
1656 ac-in/m
1657 ac-in/h
1658 ac-in/d
1659 ac-ft/s
1660 ac-ft/m
1661 ac-ft/h
1662 ac-ft/d
1663 Mft3
1664 Mbbl
1665 ac-in
1666 ac-ft
1667 Mgal
1668 Mm3/d
1669 Vol%
1670 %LEL
1671 L/m3
1672 mg/m3
1673 mL/L
1674 mL/m3
1675 μbar
1676 μg/L
1677 μg/m3
1678 μL/L
1679 μL/m3
1680 S/cm
1681 rH
m B a r
1 / 3 2
m s
k g a l k I m p
G a l
W T - % V o l
- %
l b f
/ i n
M f t
/ d
3
M m
/ d a c ­i n / s a c ­i n / m a c ­i n / h a c ­i n / d a c ­f t / s a c ­f t / m a c ­f t / h a c ­f t / d
M f t
M b b l a c
- i n
a c
- f t
M g a l
3
M m
V o l %
% L E L
L / m m g
/ m
m L / L m L
/ m
u b a r
u g / L u g
/ m
u L / L u L
/ m
S / c m
r H
Index Unit Display on the LCD
a
1682 mils/yr
1683 mm/yr
3
3
3
3
3
3
3
m i l s
/ y r
m m
/ y r
<8. Explanation of Basic Items (switching displays)>

8. Explanation of Basic Items (switching displays)

8-1
Turn the scroll knob on the outside of the case to switch displays. Display switching on the FVX110 is of two modes depending on the speed of turning the scroll knob. Single scroll mode, when one display is switched to another, or continuous scroll mode (scan mode) when displays are switched continuously during a set cycle. By changing the turning direction of the scroll knob, you can scroll forward or backward through the displays.
Scroll knob
F0801.ai
Figure 8.1 Scroll knob for switching displays

8.1 Single Scroll Mode

To scroll only one display, turn the scroll knob about 90° (Single scroll mode). An arrow icon (▲ or ▼) indicating the direction the scroll knob is turned will appear in the lower right corner of the display.
F0802.ai
Figure 8.2 Screen display during single display
switching
NOTE
Turning the scroll knob 90° is only rough description. Thus even if a 90° turn of the scroll knob fails to switch the displays, this is not a malfunction.
NOTE
Long continuous use during high or low temperatures may reduce visibility. Should this happen, replace the indicator at the earliest opportunity.
NOTE
Notes for scroll knob operation
• Do not use a spanner, wrench or other tools for turning the scroll knob as it could damage the knob. Turn the scroll knob only by hand.
<8. Explanation of Basic Items (switching displays)>
8-2

8.2 Continuous Scroll Mode (scan mode)

To scroll display continuosly (scan mode), turn the scroll knob about 180° or more in less than a second. Scan mode operation is automatically cancelled about 1 minute after start of operation. To stop during operation, turn the scroll knob in the opposite direction used to start continuous scroll mode. During continuos scroll mode, an arrow icon (
or
) indicating the direction the scroll knob is turned will appear in the lower right corner of the display. Automatically scrolling cycle will be the setting of DISPLAY_CYCLE in LCD transducer block. (Please refer to Table 7.3)

8.3 Direction of Display Switching

The direction of display switching by turning the scroll knob can be changed by SCROLL_ DIRECTION setting of the LCD transducer block. In the factory default setting, turning the scroll knob clockwise increases the page numbers. For details, refer to the instructions provided in the Section 7.3.
F0803.ai
Figure 8.3 Screen display during continuous
display switching
NOTE
Turning the scroll knob 180° is only rough description. Thus even if a 180° turn of the scroll knob fails to switch the displays, this is not a malfunction. If a 180° turn of the scroll knob fails to engage scan mode, try turning the knob faster.
<9. In-Process Operation>

9. In-Process Operation

This chapter describes the procedure performed when changing the operation of the function block of the FVX110 in process.

9.1 Mode Transition

9-1
When the function block mode is changed to Out_Of_Service, the function block pauses and a block alarm is issued.

9.2 Generation of Alarm

9.2.1 Indication of Alarm

The self-diagnostics function of the FVX110 uses the display to notify the user of the following three faults.
• The Resource block is in O/S mode
• The MAO1 block is in O/S mode
• The MAO2 block is in O/S mode The display will then indicate FVX RB OOS, FVX MAO1 OOS, or FVX MAO2 OOS.
F0901.ai
Figure 9.1 Error identication on indicator (when
MAO1 block is in O/S mode)
When process value have transferred correctly from eld instruments, the ● icon at the center part of the display ashes. When they are not correctly transferred, the ● icon is off and the process value will be highlighted.
F0903.ai
Figure 9.3 Example showing when process value
have not correctly transferred
The ● icon is not displayed during simulation.

9.2.2 Alarms and Events

The following alarms or events can be reported by the FVX110 if Link object and VCR static entry are set.
Analog Alerts (Generated when a process value
exceeds threshold) By PID Block Hi-Hi Alarm, Hi Alarm, Low
Alarm, Low-Low Alarm. Deviation - Hi Alarm, Deviation -Low Alarm.
Discret Alerts (Generated when an abnormal
condition is detected) By Resource Block Block Alarm, Write Alarm By Transducer Block Block Alarm By MAO, SC, IT, IS, AR and PID Blocks
Block Alarm
Update Alerts (Generated when an important
(restorable) parameter is updated) By Resource Block Update Event By Transducer Block Update Event By MAO, SC, IT, IS, AR and PID Blocks
Update Event
Field Diagnostic Alerts (Generated when an
abnormal condition in eld device is detected) By Resource Block Check Alarm, Failure
Alarm, Maintenance Alarm, and off specication Alarm.
F0902.ai
Figure 9.2 Example showing when process value
have correctly transferred
<9. In-Process Operation>
9-2
An alert has following structure:
Table 9.1 Alert Object
Subindex
Parameter
Name
Analog
Alert
Discrete
Alert
Update
Alert
Field
Diagnostic Alert
1 1 1 1 Block
2 2 2 2 Alert Key Alert Key copied
3 3 3 3 Standard
4 4 4 4 Mfr Type Alert Name identied
5 5 5 5 Message
6 6 6 6 Priority Priority of the alarm 7 7 7 7 Time
8 8 8 Subcode Enumerated cause
9 9 9 Value Value of referenced
10 10 10 Relative
8 Static
11 11 9 Unit Index Unit code of
Index
Type
Type
Stamp
Index
Revision
11 Source
Block Index
Explanation
Index of block from which alert is generated
from the block Type of the alert
by manufacturer specic DD
Reason of alert notication
Time when this alert is rst detected
of this alert
data Relative index of
referenced data Value of static
revision (ST_REV) of the block
referenced data Relative index of the
block that triggered the alert
9.2.3 Standard categories for NAMUR NE­107 instrument diagnostics alarms
The following standard categories of instrument diagnostics are dened for the NAMUR NE-107.
F (Failed):
An alarm category that indicates a failure has
occurred in the instrument or in its peripheral devices.
C (Check Function):
An alarm category that indicates that a detected
failure is a temporary event.
S (Off Specication):
An alarm category that indicates that the
detected failure was caused by the instrument being used outside of its range or because a discrepancy has occurred between the set value and measured value. The alarm was caused either by the instrument or process state.
M (Maintenance):
An alarm category for a detected failure that
has a low level of urgency but is a failure that could develop into a problem causing restrictions in instrument functionality in some environments.
Alarms displayed by DEVICE_STATUS_1 to DEVICE_STATUS_3 resource block parameters in their default setting are categorized as described in “NAMUR NE-107 Alarm Categories” in the DEVICE_STATUS table in section 11.1. When an alarm occurs, a character string that corresponds to an alarm category is assigned to FD_*_ACTIVE (index 1067 to 1070) [* indicates FAIL, OFF SPEC, MAINT or CHECK]. (For example, an F category alarm is assigned to FD_FAIL_ACTIVE) Similarly, procedures for processing alarms are assigned to FD_RECOMMEN_ACT. For details on alarm displays and how to deal with them, refer to Table
9.2.
<9. In-Process Operation>
Table 9.2 Field Diagnostic Alert
Indication of FD_*_ACTIVE Indication of FD_RECOMMEN_ACT Solution
Electronics failure Repair electronics Replace electrical parts e.g. amplier.
Sensor/Actuator failure Repair Sensor/Actuator Replace mechanics e.g. sensor or
Potential failure Investigate failure Perform reconguration, cleaning,
Backup function in operation Repair primary side Repair primary sensor before backup
Firmware update error Retry updating rmware Retry rmware update. Check cause of
Communication conguration error Congure communication correctly Correct conguration of
Non-operating-state Wait for a while Wait for a while. Check cause of the
Calibration warning Check calibration Investigate cause of failure and
Device conguration error Congure device correctly Correct conguration relating to sensor
Function restricted Conrm the state Check if this is right state. Simulation mode Conrm the state Check if this is right state. Manual mode Conrm the state Check if this is right state. Function Block notice Check Function Block status Check conditions of function
Sensor/Actuator out of range Check specication Check specication of sensor and
Out of operating limit Check environment Check environment specication
Temporal decrease of value quality Check process or peripherals Check process and peripherals
Deterioration estimated by Time Based Maintenance
Deterioration estimated by Condition Based Maintenance
Optional function conguration error Check optional conguration Check conguration of optional
Alarm related information Conrm information Check the alarm related information. Process alarm Check process Check process conditions.
Check deterioration Check if maintenance is required.
Check deterioration Check if maintenance is required.
Or contact sales ofce or service center.
actuator. Or contact sales ofce or service center.
wiring/connector or electrical board check. If alarm still persists, contact sales ofce or service center.
sensor fails.
the failure if alarm persists.
communication.
failure if alarm persists.
recalibrate device.
or actuator.
blocks. In order to avoid alarm from unused function blocks, congure RESOURCE2.FD_EXTENDC_MAP_n (n: 1 to 3) parameter.
actuator. Or process conditions may be temporarily non-conforming.
of sensor and actuator. Or process environment may be temporarily non­conforming.
conditions.
functions.
9-3
<9. In-Process Operation>
9-4

9.3 Device Diagnostic Simulation Function

It is possible to conduct testing for the downstream function blocks or alarm processes.
A SIMULATE_ENABLE switch is mounted in the FVX110 amplier. This is to prevent the accidental operation of this function. When this is switched on, simulation is enabled. (See Figure 9.4.) To initiate the same action from a remote terminal, if REMOTE LOOP TEST SWITCH is written to the SIM_ENABLE_MSG parameter (index 1044) of the resource block, the resulting action is the same as is taken when the above switch is on. In simulation enabled status, an alarm is generated from the resource block, and other device alarms will be masked; for this reason the simulation must be disabled immediately after using this function.
The FD_SIMULATE parameter located in the Resource Block consists of the elements shown in Table 9.3.
Table 9.3 FD_SIMALATION parameters
Subindex Parameters Description
1 Diagnostic
Simulate Value
2 Diagnostic Value This parameter displays
3 Enable It controls the simulator
Sets alarm bits that perform simulation. When Sub-index3: Enable becomes disabled, Sub-index2: Diagnostic Value is displayed here.
actual instrument diagnostics states at all times not simulation diagnostics alarms.
function. 1: Simulation inhibited (default setting) 2: Simulation start
Turn on the simulator function either by the SIMULATE_ENABLE switch or by setting SIM_ ENABLE_MSG in the Resource Block to ON when “2” is set in Enable for the Sub-index parameter in Table 9.3 to generate the alarm bits set in the Sub-index parameter Diagnostic Simulate Value. Use this function to check whether or not the eld instrument can correctly generate diagnostics alarms.
Amplifier Assembly
SIM. ENABLE
1
2
Figure 9.4 SIMULATE_ENABLE Switch
O N
O N
"OFF" during operation
F0904.ai
<9. In-Process Operation>
9-5

9.4 Write lock (Write-protect) function

The FVX110 is provided with a write lock (write­protect) function to restrict write operations to blocks and prevent inadvertent writing of parameter data. To enable this function, use the write lock switch (Hard W Lock) or the WRITE_LOCK (index
1034) (Soft W Lock).
The CPU assembly of the FVX110 is provided with a write lock switch (switch 2 in Figure 9.5). Setting switch 2 to On activates the write lock function, to prevent changes to block parameters of WRITE_ LOCK_LEVEL (index 1064). Table 9.4 shows how WRITE_LOCK_LEVEL relates to the block targeted by write lock. In the factory default setting, WRITE_ LOCK_LEVEL is “2” (preventing writing to the LCD transducer block, resource block and function block). To enable the switch lock function, set "Hard W Lock” (bit 4) of FEATURE_SEL (index 1018) to “1” (On). (The factory default for “Hard W Lock” (bit
4) is “0” (Off).
Table 9.4 Relationship between WRITE_LOCK_
LEVEL and block targeted by write lock
WRITE_LOCK_
LEVEL
0
1
2
(Factory default)
3
Block targeted by
All parameters for the LCD transducer block and FEATURE_ SEL and WRITE_LOCK_ LEVEL parameter settings for FEATURE_SEL
All parameters for the LCD transducer block and resource block
All function block parameters in addition to WRITE_LOCK_ LEVEL “1”
MIB and VCR in addition to WRITE_LOCK_LEVEL “2”
Write lock
When the write lock switch is disabled, set 2 (enabled) for WRITE_LOCK (index 1034) of the resource block to enable the write lock function. To enable the write lock function using the WRITE_ LOCK setting, FEATURE_SEL (index 1018) of the resource block must be returned to its factory default. (In the factory default setting, “Hard W Lock” (bit 4) is “0” (Off and “Soft W Lock” (bit 3) is “1” (On).
Table 9.5 FEATURE_SEL, write lock switch and
WRITE_LOCK parameter relationship
FEATURE_SEL
Hard
W Lock (bit4)
0 (OFF)
Soft
W Lock (bit3)
0 (OFF)
1 (ON)
Write
lock
switch
Disabled
WRITE_LOCK
Unavailable (“1” (Write lock disabled)
1 (Write lock disabled) (Factory default)
2 (Write lock enabled) Unavailable
(depends on write lock
1 (ON)
0 (OFF)
Enabled
switch)
* When “Hard W Lock” and “Soft W Lock” are both 1 (On), the
“Hard W Lock” setting takes precedence and “Soft W Lock” is automatically set to 0 (Off).
Amplifier Assembly
1
2
WRITE LOCK
Figure 9.5 WRITE_LOCK Switch
O N
O N
"OFF" during operation
F0905.ai
<10. Maintenance>

10. Maintenance

10.1 Overview

Maintenance of the indicator is easy due to its modular construction. This chapter describes the procedures for the disassembly and reassembly procedures required for component replacement.
Indicators are precision instruments. Please carefully and thoroughly read the following sections for information on how to properly handle them while performing maintenance.
IMPORTANT
• As a rule, maintenance of this indicator should be done in a shop that has all the necessary tools.
• The CPU assembly contains sensitive parts that can be damaged by static electricity. Take precautions such as using a grounded wrist strap when handling electronic parts or touching the board circuit patterns. Also be sure to place the removed CPU assembly into a bag with an antistatic coating.
Precautions for ATEX Flameproof Type Indicators
CAUTION
• Flameproof type indicators must be, as a rule, removed to a non-hazardous area for maintenance and be disassembled and reassembled to the original state.
• On the ameproof type indicators the two covers are locked, each by an Allen head bolt (shrouding bolt). When a shrouding bolt is driven clockwise by an Allen wrench, it is going in and cover lock is released, and then the cover can be opened.
When a cover is closed it should be locked
by a shrouding bolt without fail. Tighten the shrouding bolt to a torque of 0.7 N·m.
10-1

10.2 Disassembly and Reassembly

This section describes procedures for disassembly and reassembly for maintenance and component replacement.
Always turn OFF power and shut off and release pressures before disassembly. Use proper tools for all operations. Table 10.1 shows the tools required.
Table 10.1 Tools for Disassembly and Reassembly
Tool Quantity Remarks
Phillips screwdriver
Slotted screwdriver
Allen wrenches 3 JIS B4648
Socket driver 1 Width across ats, 5.5 mm Tweezers 1
1 JIS B4633, No. 2
1
One each, nominal 3, 4 and
2.5 mm Allen wrenches
Shrouding Bolt
F1001.ai
Figure 10.1 Shrouding Bolts

10.2.1 Replacing the display

CAUTION
Cautions for Flameproof Type Indicators
Users are prohibited by law from modifying the construction of a ameproof type indicator. This would invalidate the agency approval for the use of the indicator in a rated area. It follows that the user is prohibited from using a ameproof type indicator with its display removed, or from adding an display to a indicator. If such modication is absolutely required, contact Yokogawa.
This subsection describes the procedure for replacing an display. (See gure 10.2)
<10. Maintenance>
10-2
NOTE
Long continuous use during high or low temperatures may reduce visibility. Should this happen, replace the indicator at the earliest opportunity.
NOTE
If two display actions below showed up, it may be failure of Display
• Display repeat turning on and off
• Abnormal indication such as blackout If these two actions occurred, please replace display with procedure written in this user’s manual or contact Yokogawa.
■ Removing the Display assembly
1) Remove the Display cover.
2) While supporting the Display assembly with one hand, loosen its two Mounting screws.
3) Dismount the Display assembly from the CPU assembly.
When doing this, carefully pull the Display
assembly straight forward so as not to damage the connector pins between it and the CPU assembly.
■ Attaching the Display assembly
1) Align both the Display assembly and CPU assembly connectors and engage them.
2) Insert and tighten the two Mounting screws.
3) Replace the Display cover.

10.2.2 Replacing the CPU Board Assembly

This subsection describes the procedure for replacing the CPU assembly. (See gure 10.2)
■ Removing the CPU Assembly
1) Remove the Display cover.
2) Turn the Scroll knob screw to the position
(where the screw head slot is horizontal) as shown in gure 10.2.
3) Disconnect the Output terminal cable (cable
with brown connector at the end). When doing this, lightly press the side of the CPU assembly connector and pull the cable connector to disengage.
4) Use a socket driver (width across ats, 5.5mm)
to loosen the two bosses.
5) Carefully pull the CPU assembly straight
forward to remove it.
NOTE
Be careful not to apply excessive force to the CPU assembly when removing it.
■ Mounting the CPU Assembly
1) Connect the output terminal cable (with brown
connector).
NOTE
Make certain that the cables do not get pinched between the case and the edge of the CPU assembly.
CPU
assembly Display assembly
Mounting screw
Display Cover
Figure 10.2 Removing and Display Assembly and
Boss
Output terminal cable
CPU Assembly
Slide switch
Bracket
(for scroll
knob screw
scroll knob
pin)
scroll knob screw pin
F1002.ai
2) Align and engage the scroll knob screw pin with the groove on the bracket on the CPU assembly. Then insert the CPU board assembly straight onto the post in the case.
3) Tighten the two bosses.
NOTE
Conrm that the scroll knob screw pin is placed properly in the groove on the bracket prior to tightening the two bosses. If it is not, the display scroll mechanism will be damaged.
4) Replace the Display cover.
<11. Device Information>
11-1

11. Device Information

11.1 DEVICE STATUS

Device status for the FVX110 are indicated by using parameter DEVICE_STATUS_1 to DEVICE_STATUS_3 (index 1045 to 1047) in Resource Block.
Table 11.1 Contents of DEVICE_STATUS_1 (index 1045)
Hexadecimal Diplay through DD Description
0x10000000 Write Locked Write lock is ON ­0x08000000 Hard Write Lock SW ON Hardware write lock switch is ON ­0x04000000 Abnormal Boot Process Abnormal boot processing was detected at the starting F 0x02000000 SoftDL Failure Software download has failed C 0x01000000 SoftDL Incomplete Software download is incomplete C 0x00800000 Simulation Switch ON Software or hardware simulation switch is ON ­0x00400000 RB in O/S Mode Resource Block is in O/S mode C 0x00080000 Amp EEPROM Failure Amplier EEPROM failed F 0x00008000 Link Obj. 1/17/33 Not Open Link object 1, 17 or 33 is not open C 0x00004000 Link Obj. 2/18/34 Not Open Link object 2, 18 or 34 is not open C 0x00002000 Link Obj. 3/19/35 Not Open Link object 3, 19 or 35 is not open C 0x00001000 Link Obj. 4/20/36 Not Open Link object 4, 20 or 36 is not open C 0x00000800 Link Obj. 5/21/37 Not Open Link object 5, 21 or 37 is not open C 0x00000400 Link Obj. 6/22/38 Not Open Link object 6, 22 or 38 is not open C 0x00000200 Link Obj. 7/23/39 Not Open Link object 7, 23 or 39 is not open C 0x00000100 Link Obj. 8/24/40 Not Open Link object 8, 24 or 40 is not open C 0x00000080 Link Obj. 9/25 Not Open Link object 9 or 25 is not open C 0x00000040 Link Obj. 10/26 Not Open Link object 10 or 26 is not open C 0x00000020 Link Obj. 11/27 Not Open Link object 11 or 27 is not open C 0x00000010 Link Obj. 12/28 Not Open Link object 12 or 28 is not open C 0x00000008 Link Obj. 13/29 Not Open Link object 13 or 29 is not open C 0x00000004 Link Obj. 14/30 Not Open Link object 14 or 30 is not open C 0x00000002 Link Obj. 15/31 Not Open Link object 15 or 31 is not open C 0x00000001 Link Obj. 16/32 Not Open Link object 16 or 32 is not open C
NAMUR
NE-107 category
<11. Device Information>
Table 11.2 Contents of DEVICE_STATUS_2 (index 1046)
Hexadecimal Diplay through DD Description
0x80000000 LTB in O/S Mode LCD Transducer Block is in O/S mode C 0x40000000 LCD Failure LCD has been failing F 0x20000000 Amp Temp Out of Range Amplier temperature is out specication range S 0x00008000 MAO1 in O/S Mode MAO1 Block is in O/S mode C 0x00004000 MAO1 in Man Mode MAO1 Block is in Man mode C 0x00002000 MAO1 Not Scheduled MAO1 Block is not scheduled C 0x00000800 MAO2 in O/S Mode MAO2 Block is in O/S mode C 0x00000400 MAO2 in Man Mode MAO2 Block is in Man mode C 0x00000200 MAO2 Not Scheduled MAO2 Block is not scheduled C 0x00000080 IS1 in O/S Mode IS1 Block is in O/S mode C 0x00000040 IS1 in Man Mode IS1 Block is in Man mode C 0x00000020 IS1 Not Scheduled IS1 Block is not scheduled C 0x00000008 IS2 in O/S Mode IS2 Block is in O/S mode C 0x00000004 IS2 in Man Mode IS2 Block is in Man mode C 0x00000002 IS2 Not Scheduled IS2 Block is not scheduled C
NAMUR
NE-107 category
Table 11.3 Contents of DEVICE_STATUS_3 (index 1047)
Hexadecimal Diplay through DD Description
0x80000000 PID1 in O/S Mode PID1 Block is in O/S mode C 0x40000000 PID1 in Man Mode PID1 Block is in Man mode C 0x20000000 PID1 Not Scheduled PID1 Block is not scheduled C 0x10000000 PID1 in Bypass Mode PID1 Block is in Bypass mode C 0x08000000 PID2 in O/S Mode PID2 Block is in O/S mode C 0x04000000 PID2 in Man Mode PID2 Block is in Man mode C 0x02000000 PID2 Not Scheduled PID2 Block is not scheduled C 0x01000000 PID2 in Bypass Mode PID2 Block is in Bypass mode C 0x00080000 SC in O/S Mode SC Block is in O/S mode C 0x00040000 SC in Man Mode SC Block is in Man mode C 0x00020000 SC Not Scheduled SC Block is not scheduled C 0x00008000 IT in O/S Mode IT Block is in O/S mode C 0x00004000 IT in Man Mode IT Block is in Man mode C 0x00002000 IT Not Scheduled IT Block is not scheduled C
0x00001000 IT Total Backup Err
0x00000800 IT Conf. Err
0x00000080 AR1 in O/S Mode AR1 Block is in O/S mode C 0x00000040 AR1 in Man Mode AR1 Block is in Man mode C 0x00000020 AR1 Not Scheduled AR1 Block is not scheduled C
0x00000010 AR1 Range Conf. Err
0x00000008 AR2 in O/S Mode AR2 Block is in O/S mode C 0x00000004 AR2 in Man Mode AR2 Block is in Man mode C 0x00000002 AR2 Not Scheduled AR2 Block is not scheduled C
0x00000001 AR2 Range Conf. Err
IT Total Backup has failed. Last IT Output.Value(IT.LAST. VALUE) is not saved IT Clock Period(IT.CLOCK_PER) is smaller than IT Period of Execution(EXECUTION_PERIOD)
AR1 Range High(AR1.RANGE_HI) is smaller than AR1 Range Lo(AR1.RANGE_LO)
AR2 Range High(AR2.RANGE_HI) is smaller than AR2 Range Lo(AR2.RANGE_LO)
NAMUR
NE-107 category
11-2
F
C
C
C
<11. Device Information>

11.2 Status of Each Parameter in Failure Mode

Following tables summarize the value of FVX110 parameters when LCD display indicates an Alarm.
Table 11.4 Action of each parameters in failure mode
Alarm Display Cause of Alarm Object Block BLOCK_ERR
FVX RB OOS RESOURCE block is in O/S mode RB Out-of-Service FVX MAO1 OOS MAO1 block is in O/S mode MAO1 Out-of-Service FVX MAO2 OOS MAO2 block is in O/S mode MAO2 Out-of-Service
11-3
<12. Parameter Lists>

12. Parameter Lists

Note: The Write Mode column contains the modes in which each parameter is write enabled. O/S: Write enabled in O/S mode. MAN: Write enabled in Man mode and O/S mode. AUTO: Write enabled in Auto mode, Man mode, and O/S mode.

12.1 Resource Block

12-1
Relative
Index
0 1000 Block Header TAG:“RS” Block
1 1001 ST_REV The revision level of the static data associated with the
2 1002 TAG_DESC Null AUTO The user description of the intended application of the block. 3 1003 STRATEGY 0 AUTO The strategy eld can be used to identify grouping of blocks.
4 1004 ALERT_KEY 0 AUTO The identication number of the plant unit. This information
5 1005 MODE_BLK AUTO AUTO The actual, target, permitted, and normal modes of the block. 6 1006 BLOCK_ERR This parameter reects the error status associated with the
7 1007 RS_STATE State of the resource block state machine. 8 1008 TEST_RW Null AUTO Read/write test parameter-used only for conformance testing
9 1009 DD_RESOURCE Null String identifying the tag of the resource which contains the
10 1010 MANUFAC_ID 0x00594543 Manufacturer identication number-used by an interface device
11 1011 DEV_TYPE 16 Manufacturer’s model number associated with the
12 1012 DEV_REV 1 Manufacturer revision number associated with the
13 1013 DD_REV 1 Revision of the DD associated with the resource-used by an
14 1014 GRANT_DENY 0 AUTO Options for controlling access of host computer and local
15 1015 HARD_TYPES Scalar input The types of hardware available as channel numbers.
16 1016 RESTART Allows a manual restart to be initiated. Several degrees of
17 1017 FEATURES Reports
18 1018 FEATURE_SEL Report
19 1019 CYCLE_TYPE Scheduled Identies the block execution methods available for this
Index Parameter Name Factory Default
Fault state Soft W Lock Hard W Lock Multi_bit Alarm support
Fault state Soft W Lock
Write Mode
Tag =O/S
Used to show supported resource block options.
AUTO Used to select resource block options dened in FEATURES.
Information on this block such as Block Tag, DD Revision, Execution Time etc.
resource block. The revision value is incremented each time a static parameter value in this block is changed.
This data is not checked or processed by the block.
may be used in the host for sorting alarms, etc.
hardware or software components associated with a block. It is a bit string, so that multiple errors may be shown.
and simulation.
Device Description for this resource.
to locate the DD le for the resource.
resourceused by interface devices to locate the DD le for the resource.
resourceused by an interface device to locate the DD le for the resource.
interface device to locate the DD le for the resource.
control panels to operating, tuning and alarm parameters of the block.
bit0: Scalar input bit1: Scalar output bit2: Discrete input bit3: Discrete output
restart are possible. They are 1: Run, 2: Restart resource, 3: Restart with initial value specied in FF functional spec. (*1), and 4: Restart processor.
*1: FF-891 FoundationTM Specication Function Block
Application Process Part 2.
bit0: Scheduled bit1: Event driven bit2: Manufacturer specied
resource.
Explanation
<12. Parameter Lists>
12-2
Relative
Index
20 1020 CYCLE_SEL Scheduled AUTO Used to select the block execution method for this resource. 21 1021 MIN_CYCLE_T 3200 (100ms) Time duration of the shortest cycle interval of which the
22 1022 MEMORY_SIZE 0 Available conguration memory in the empty resource. To be
23 1023 NV_CYCLE_T 0 Interval between writing copies of nonvolatile parameters to
24 1024 FREE_SPACE 0 Percent of memory available for further conguration. FVX110
25 1025 FREE_TIME 0 Percent of the block processing time that is free to process
26 1026 SHED_RCAS 640000 (20S) AUTO Time duration at which to give up on computer writes to
27 1027 SHED_ROUT 640000 (20S) AUTO Time duration at which to give up on computer writes to
28 1028 FAULT_STATE 1 Condition set by loss of communication to an output block,
29 1029 SET_FSTATE 1 AUTO Allows the fail-safe condition to be manually initiated by
30 1030 CLR_FSTATE 1 AUTO Writing a Clear to this parameter will clear the device fail-safe
31 1031 MAX_NOTIFY 4 Maximum number of unconrmed notify messages possible. 32 1032 LIM_NOTIFY 4 AUTO Maximum number of alarm information which FVX110 can
33 1033 CONFIRM_TIM 64000 (20S) AUTO The minimum time between retries of alert reports. 34 1034 WRITE_LOCK Not locked AUTO If set, no writes from anywhere are allowed, except to clear
35 1035 UPDATE_EVT This alert is generated by any change to the static data. 36 1036 BLOCK_ALM The block alarm is used for all conguration, hardware,
37 1037 ALARM_SUM Enable The current alert status, unacknowledged states, unreported
38 1038 ACK_OPTION 0xFFFF AUTO Selection of whether alarms associated with the block will be
39 1039 WRITE_PRI 0 AUTO Priority of the alarm generated by clearing the write lock. 40 1040 WRITE_ALM This alert is generated if the write lock parameter is cleared. 41 1041 ITK_VER 5 Version number of interoperability test by Fieldbus Foundation
42 1042 SOFT_REV FVX110 software revision number. 43 1043 SOFT_DESC Yokogawa internal use. 44 1044 SIM_ENABLE_MSG Null AUTO Software switch for simulation function. 45 1045 DEVICE_STATUS_1 0 Device status For details, refer to Table 11.1 46 1046 DEVICE_STATUS_2 0 Device status For details, refer to Table 11.2 47 1047 DEVICE_STATUS_3 0 Device status For details, refer to Table 11.3 48 1048 DEVICE_STATUS_4 reserve FVX110 does not support this. 49 1049 DEVICE_STATUS_5 reserve FVX110 does not support this. 50 1050 DEVICE_STATUS_6 reserve FVX110 does not support this. 51 1051 DEVICE_STATUS_7 reserve FVX110 does not support this. 52 1052 DEVICE_STATUS_8 reserve FVX110 does not support this. 53 1053 SOFTDWN_
Index Parameter Name Factory Default
0x01 AUTO Denes whether to accept software downloads.
PROTECT
Write Mode
resource is capable.
checked before attempting a download.
non-volatile memory. Zero means never.
has zero which means a precongured resource.
additional blocks. FVX110 does not support this.
function block RCas locations. Supported only with PID function.
function block ROut locations. Supported only with PID function.
failure promoted to an output block or a physical contact. When fail-safe condition is set, then output function blocks will perform their FSAFE actions.
selecting Set.
state if the eld condition, if any, has cleared.
transfer at the same time. Setting of this parameter restrict number of alarm transfer to the HOST and prevent HOST from overow.
WRITE_LOCK. Block inputs will continue to be updated
connection failure or system problems in the block. The cause of the alert is entered in the subcode eld. The rst alert to become active will set the Active status in the Status attribute. As soon as the Unreported status is cleared by the alert reporting task, another block alert may be reported without clearing the Active status, if the subcode has changed.
states, and disabled states of the alarms associated with the function block.
automatically acknowledged.
applied to FVX110.
0x01: Unprotected 0x02: Protected
Explanation
<12. Parameter Lists>
12-3
Relative
Index
54 1054 SOFTDWN_FORMAT 0x01 AUTO Selects the software download method.
55 1055 SOFTDWN_COUNT 0 Indicates the number of times the internal FlashROM was
56 1056 SOFTDWN_ACT_
57 1057 SOFTDWN_MOD_
58 1058 SOFTDWN_ERROR 0 Indicates the error during a software download.
59 1059 60 1060 61 1061
62 1062 CAPABILITY_LEV 0x00 Indicates the capability level of instrument interior. 63 1063
64 1064 65 1065
66 1066 FD_VER 0 Indicates value of major version of instrument diagnostics
67 1067 FD_FAIL_ACTIVE 0 A parameter that corresponds to ”Failed” in the NAMUR NE-
68 1068
69 1069 FD_MAINT_ACTIVE 0 A parameter that corresponds to ”Maintenance” in the NAMUR
70 1070 FD_CHECK_ACTIVE 0 A parameter that corresponds to ”Check Function” in the
71 1071 FD_FAIL_MAP 0xFC000000 AUTO Species the bit assigned to FD_FAIL_ACTIVE, a parameter
72 1072 FD_OFFSPEC_MAP 0x00003800 AUTO Species the bit assigned to FD_OFFSPEC_ACTIVE, a
73 1073 FD_MAINT_MAP 0x000003E0 AUTO Species the bit assigned to FD_MAINT_ACTIVE, a parameter
74 1074 FD_CHECK_MAP 0x01FF8008 AUTO Species the bit assigned to FD_CHECK_ACTIVE, a
75 1075 FD_FAIL_MASK 0xFFFFFFFF AUTO Species the bit that noties the host of 32-bit ”Failed” alarms
76 1076
77 1077 FD_MAINT_MASK 0xFFFFFFFF AUTO A parameter that species the bit that noties the host of
78 1078 FD_CHECK_MASK 0xFFFFFFFF AUTO Species the bit that noties the host of 32-bit ”Check Function”
79 1079 FD_FAIL_ALM AUTO Indicates alarm information for alarms categorized under
80 1080 FD_OFFSPEC_ALM AUTO Indicates alarm information for alarms categorized under ”Off
81 1081 FD_MAINT_ALM AUTO Indicates alarm information for alarms categorized under
82 1082 FD_CHECK_ALM AUTO Indicates alarm information for alarms categorized under
83 1083 FD_FAIL_PRI 0 AUTO Indicates the FD_FAIL_ALM priority for an alarm. 84 1084 FD_OFFSPEC_PRI 0 AUTO Indicates the FD_OFFSPEC_ALM priority for an alarm. 85 1085 FD_MAINT_PRI 0 AUTO Indicates theFD_MAINT_ALM priority for an alarm.
Index Parameter Name Factory Default
AREA
REV
SOFTDWN_HISTORY SOFTDWN_HIST_INDEX COMPATIBILITY_REV
CAPABILITY_CONFIG
WRITE_LOCK_LEVEL SI_CONTROL_CODES
FD_OFFSPEC_ACTIVE
FD_OFFSPEC_MASK
0 Indicates the ROM number of the currently working FlashROM.
1, 0, 0, 0, 0, 0, 0, 0, 0
0 AUTO Not used by the FVX110. 1 Indicates the smallest Rev value compatible with device
0x0000 A parameter corresponding to AP_CONF or DEV_OPTIONS
2 AUTO Species blocks that activates Write Lock. 1 A parameter for switching to make the instrument compatible
0 A parameter that corresponds to ”Off Specication” in the
0xFFFFFFFF AUTO Species the bit that noties the host of 32-bit ”Off
Write Mode
0x01: Standard 0x02: YOKOGAWA Standard
erased.
0: FlashROM #0 working 1: FlashROM #1 working
Indicates the software module revision.
Refer Table A8.4.
Not used by the FVX110.
DevRev.
before the addition of parameter CAPABILITY_LEV.
with SI units.
specications (FF-912).
107 category.
NAMUR NE-107 category.
NE-107 category.
NAMUR NE-107 category.
for indicating ”Failed,” a 32-bit alarm listed in FD_SIMULATE. DiagnosticValue.
parameter for indicating ”Off Specication,” a 32-bit alarm listed in FD_SIMULATE. DiagnosticValue.
for indicating ”Maintenance,” a 32-bit alarm listed in FD_ SIMULATE. DiagnosticValue.
parameter for indicating ”Check Function,” a 32-bit alarm listed in FD_SIMULATE. DiagnosticValue.
listed in FD_FAIL_ACTIVE.
Specication” alarms listed in FD_OFFSPEC_ACTIVE.
32-bit ”Maintenance” alarms listed in FD_MAINT_ACTIVE. A parameter set by the user.
alarms listed in FD_CHECK_ACTIVE.
”Failed.”
Specication.”
”Maintenance”.
”Check Function”.
Explanation
<12. Parameter Lists>
12-4
Relative
Index
86 1086 FD_CHECK_PRI 0 AUTO Indicates the FD_CHECK_ALM priority for an alarm. 87 1087 FD_SIMULATE AUTO A parameter for simulating an alarm. 88 1088 89 1089
90 1090
91 1091
92 1092 93 1093 94 1094 95 1095 96 1096 97 1097
98 1098
99 1099
100 1100 101 1101
102 1102 103 1103 104 1104 105 1105 PRIVATE_1 Not used by the FVX110. 106 1106 PRIVATE_2 Not used by the FVX110. 107 1107 108 1108 PRIVATE_4 Not used by the FVX110. 109 1109 PRIVATE_5 Not used by the FVX110. 110 1110 PRIVATE_6 Not used by the FVX110. 111 1111 PRIVATE_7 Not used by the FVX110. 112 1112 PRIVATE_8 Not used by the FVX110. 113 1113 PRIVATE_9 Not used by the FVX110. 114 1114 PRIVATE_10 Not used by the FVX110. 115 1115 PRIVATE_11 Not used by the FVX110.
Index Parameter Name Factory Default
FD_RECOMMEN_ACT FD_EXTENDED_ACTIVE_1
FD_EXTENDED_ACTIVE_2
FD_EXTENDED_ACTIVE_3
FD_EXTENDED_ACTIVE_4 FD_EXTENDED_ACTIVE_5 FD_EXTENDED_ACTIVE_6 FD_EXTENDED_ACTIVE_7 FD_EXTENDED_ACTIVE_8 FD_EXTENDED_MAP_1
FD_EXTENDED_MAP_2
FD_EXTENDED_MAP_3
FD_EXTENDED_MAP_4 FD_EXTENDED_MAP_5
FD_EXTENDED_MAP_6 FD_EXTENDED_MAP_7 FD_EXTENDED_MAP_8
PRIVATE_3 Not used by the FVX110.
0 Indicates procedures for handling essential alarms. 0 A parameter serving as a starting point for alarms handled by
0 A parameter serving as a starting point for alarms handled by
0 A parameter serving as a starting point for alarms handled by
0 Not used by the FVX110. 0 Not used by the FVX110. 0 Not used by the FVX110. 0 Not used by the FVX110. 0 Not used by the FVX110. 0x0748FFFF AUTO A parameter set by the user as a mask from DEVICE_
0xE000EEEE AUTO A parameter set by the user as a mask from DEVICE_
0xFF0EF8FF AUTO A parameter set by the user as a mask from DEVICE_
Write Mode
FF-912.
FF-912.
FF-912.
STATUS_1 to FD_EXTENDED_ACTIVE_1.
STATUS_2 to FD_EXTENDED_ACTIVE_2.
STATUS_3 to FD_EXTENDED_ACTIVE_3.
AUTO Not used by the FVX110. AUTO Not used by the FVX110.
AUTO Not used by the FVX110. AUTO Not used by the FVX110. AUTO Not used by the FVX110.
Explanation

12.2 LCD Transducer Block

Relative
Index
0 2000 Block Header TAG : "LTB" "Block
1 2001 ST_REV - AUTO Describes the revision level of parameters for setting the
2 2002 TAG_DESC Null AUTO A universal parameter intended for storing comments describ-
3 2003 STRATEGY 1 AUTO A universal parameter used by the high-level system to iden-
4 2004 ALERT_KEY 1 AUTO Key information used to identify the location at which an alert
Index Parameter Name Factory Default
Write Mode
Tag =O/S"
Explanation
Information on this block such as Block Tag, DD Revision, Execution Time, etc.
transducer block. The revision is updated when set values are changed. This parameter is used to check for parameter changes.
ing tag data.
tify function blocks.
occurred. Generally, this parameter is used by a high-level system to identify specic areas in a plant that are under the control of specic operators to distinguish necessary alarms only. This is a universal parameter.
<12. Parameter Lists>
12-5
Relative
Index
5 2005 MODE_BLK AUTO AUTO A universal parameter that represents block operating condi-
6 2006 BLOCK_ERR - AUTO Indicates error status of the PID block. The FVX110 trans-
7 2007 UPDATE_EVT - AUTO Indicates event information if an event update occurs. 8 2008 BLOCK_ALM - AUTO Indicates error information if an error occurs in a block. 9 2009 10 2010
11 2011 XD_ERROR 0 AUTO Stores the most serious errors that occur in the transducer
12 2012
13 2013 NOW_DISPLAYING 0 AUTO Indicates the number that the input currently displayed on the
14 2014
15 2015 NO_OF_VALID_CON 0 AUTO Indicates how many of the 16 inputs are valid. (Corresponds
16 2016 17 2017 18 2018 19 2019 20 2020
21 2021 EACH_BAR_GRAPH 0x0000 AUTO Use to specify whether bar graphs should be displayed in the
22 2022 MAIN_TAG_SCROLL 1 AUTO Use to set the character scroll function for MAIN_TAG infor-
23 2023 V_SCROLL_BAR 2 AUTO Use to turn the vertical scroll bar on and off.
24 2024
Index Parameter Name Factory Default
TRANSDUCER_DIRECTORY TRANSDUCER_TYPE
COLLECTION_DIRECTORY
DISP_TARGET_FORCE
VALID_CON_SUMMARY MAO_CON_SUMMARY ISEL_CON_SUMMARY SIM_CON_SUMMARY BAR_GRAPH_SELECT
SCROLL_DIRECTION
- AUTO Parameter for storing indexes of FVX110 transducers. 65535 AUTO Indicates FVX110 types.
0 AUTO A parameter for identifying information of valid inputs that you
0xFFFF AUTO Sets which of the 16 inputs are valid inputs. 0x0000 AUTO Indicates which of the 16 inputs gets MAO block values. 0x0000 AUTO Indicates which of the 16 inputs gets IS block values. 0xFFFF AUTO Indicates which of the 16 inputs gets Simulation state values. 0 AUTO Use to specify whether bar graphs should be displayed in the
0 AUTO A parameter for changing scroll knob turning direction, page
Write Mode
tion. It comprises the Actual, Target, Permit and Normal modes.
ducer block handles the following factors. Bit 0 = An XD_ERROR has occurred Bit 15 = Target mode is O/S
Indicates 65535 (other) for the FVX110.
block. 0 = No error 50 = Reset performed 100 = LCD error
AUTO Stores the DD item ID for the rst index of important param-
eters in the LCD transducer block.
LCD occupies among valid inputs of information.
want to view
0: Scroll knob is active 1: No.01 in valid connection 2: No.02 in valid connection 3: No.03 in valid connection 4: No.04 in valid connection 5: No.05 in valid connection 6: No.06 in valid connection 7: No.07 in valid connection 8: No.08 in valid connection
9: No.09 in valid connection 10: No.10 in valid connection 11: No.11 in valid connection 12: No.12 in valid connection 13: No.13 in valid connection 14: No.14 in valid connection 15: No.15 in valid connection 16: No.16 in valid connection
to the denominator when DISP_PAGE_INFO is displayed.)
lower eld of the LCD. (16 input batch setting)
lower eld of the LCD. (Each input batch setting)
mation. 0 = scroll function Off 1 = scroll function On
0 = Scroll bar display function Off 1 = Scroll bar display function On 2 = On only during display switch
number turning direction and turning direction of the vertical scroll bar. 0 = Clockwise turn of scroll knob à Increases page numbers 0 = Counterclockwise turn of scroll knob à Increases page numbers
Explanation
<12. Parameter Lists>
12-6
Relative
Index
25 2025 DISP_PAGE_INFO 2 AUTO Parameter for turning on or off current page numbers dis-
26 2026 DISP_QUIET_MODE 0 AUTO Use to specify LCD operation after switching screens.
27 2027 28 2028 DISPLAY_CYCLE 0 AUTO Use to set interval when screens are switched.
29 2029 DISPLAY_TEST 0 AUTO Parameter to turn LCD test mode on and off. 30 2030
31 2031 SQUAWK 0 AUTO Turns Squawk on and off. 32 2032 33 2033
34 2034 IN01_CONNECTION 0 AUTO Use to specify what values of IN01 are connected to.
35 2035 IN02_CONNECTION 0 AUTO Use to specify what values of IN02 are connected to.
36 2036 IN03_CONNECTION 0 AUTO Use to specify what values of IN03 are connected to.
37 2037 IN04_CONNECTION 0 AUTO Use to specify what values of IN04 are connected to.
38 2038 IN05_CONNECTION 0 AUTO Use to specify what values of IN05 are connected to.
39 2039 IN06_CONNECTION 0 AUTO
40 2040 IN07_CONNECTION 0 AUTO Use to specify what values of IN07 are connected to.
41 2041 IN08_CONNECTION 0 AUTO Use to specify what values of IN08 are connected to.
Index Parameter Name Factory Default
DISP_FORMAT_TYPE
DISPLAY_CONTRAST
AMBIENT_TEMPERATURE MAIN_CONNECT_TYPE
0 AUTO Not currently used.
32 (0x20) AUTO Parameter for setting relative brightness (contrast) between
0 - Indicates amplier temperature. 0 AUTO Use to set the connection (MAO or ISEL function block) for 16
Write Mode
Explanation
played as an xx/yy fraction in the top right corner of the LCD screen. 0 = On during highlighting when display screens are switched 1 = Always On 2 = Always On during highlighting
0 = Displays last output screen 1 = Switches screens at specied intervals to display all screens 2 = LCD display Off
0 = Auto (automatically set depending on ambient tempera­ture) 1 = 0.5 sec 2 = 1.0 sec 3 = 2.0 sec 4 = 4.0 sec
the LCD when it is on and when it is off.
inputs at one time. 0 = All 16 inputs are input to simulation 1 = All 16 inputs are connected to MAO-FB 2 = All 16 inputs are connected to ISEL-FB
0 = Simulation dISELplay 1 = Connected to MAO-FB_1 IN01 2 = Connected to ISEL-FB_1 IN01
0 = Simulation dISELplay 1 = Connected to MAO-FB_1 IN02 2 = Connected to ISEL-FB_1 IN02
0 = Simulation dISELplay 1 = Connected to MAO-FB_1 IN03 2 = Connected to ISEL-FB_1 IN03
0 = Simulation dISELplay 1 = Connected to MAO-FB_1 IN04 2 = Connected to ISEL-FB_1 IN04
0 = Simulation dISELplay 1 = Connected to MAO-FB_1 IN05 2 = Connected to ISEL-FB_1 IN05
Use to specify what values of IN06 are connected to. 0 = Simulation dISELplay 1 = Connected to MAO-FB_1 IN06 2 = Connected to ISEL-FB_1 IN06
0 = Simulation dISELplay 1 = Connected to MAO-FB_1 IN07 2 = Connected to ISEL-FB_1 IN07
0 = Simulation dISELplay 1 = Connected to MAO-FB_1 IN08 2 = Connected to ISEL-FB_1 IN08
<12. Parameter Lists>
12-7
Relative
Index
42 2042 IN09_CONNECTION 0 AUTO Use to specify what values of IN09 are connected to.
43 2043 IN10_CONNECTION 0 AUTO Use to specify what values of IN10 are connected to.
44 2044 IN11_CONNECTION 0 AUTO Use to specify what values of IN11 are connected to.
45 2045 IN12_CONNECTION 0 AUTO Use to specify what values of IN12 are connected to.
46 2046 IN13_CONNECTION 0 AUTO Use to specify what values of IN13 are connected to.
47 2047 IN14_CONNECTION 0 AUTO Use to specify what values of IN14 are connected to.
48 2048 IN15_CONNECTION 0 AUTO Use to specify what values of IN15 are connected to.
49 2049 IN16_CONNECTION 0 AUTO Use to specify what values of IN16 are connected to.
50 2050 IN_01 Status: 0xC0
51 2051 IN_02 Status: 0xC0
52 2052 IN_03 Status: 0xC0
53 2053 IN_04 Status: 0xC0
54 2054 IN_05 Status: 0xC0
55 2055 IN_06 Status: 0xC0
56 2056 IN_07 Status: 0xC0
57 2057 IN_08 Status: 0xC0
58 2058 IN_09 Status: 0xC0
59 2059 IN_10 Status: 0xC0
60 2060 IN_11 Status: 0xC0
61 2061 IN_12 Status: 0xC0
62 2062 IN_13 Status: 0xC0
63 2063 IN_14 Status: 0xC0
64 2064 IN_15 Status: 0xC0
Index Parameter Name Factory Default
Value: 0.0
Value: 99999.0
Value: 0.0
Value: 99999.0
Value: 0.0
Value: 99999.0
Value: 0.0
Value: 99999.0
Value: 0.0
Value: 99999.0
Value: 0.0
Value: 99999.0
Value: 0.0
Value: 99999.0
Value: 0.0
Write Mode
0 = Simulation dISELplay 1 = Connected to MAO-FB_2 IN01 2 = Connected to ISEL-FB_2 IN01
0 = Simulation dISELplay 1 = Connected to MAO-FB_2 IN02 2 = Connected to ISEL-FB_2 IN02
0 = Simulation dISELplay 1 = Connected to MAO-FB_2 IN03 2 = Connected to ISEL-FB_2 IN03
0 = Simulation dISELplay 1 = Connected to MAO-FB_2 IN04 2 = Connected to ISEL-FB_2 IN04
0 = Simulation dISELplay 1 = Connected to MAO-FB_2 IN05 2 = Connected to ISEL-FB_2 IN05
0 = Simulation dISELplay 1 = Connected to MAO-FB_2 IN06 2 = Connected to ISEL-FB_2 IN06
0 = Simulation dISELplay 1 = Connected to MAO-FB_2 IN07 2 = Connected to ISEL-FB_2 IN07
0 = Simulation dISELplay 1 = Connected to MAO-FB_2 IN08 2 = Connected to ISEL-FB_2 IN08
AUTO Indicates process information for input 1.
AUTO Indicates process information for input 2.
AUTO Indicates process information for input 3.
AUTO Indicates process information for input 4.
AUTO Indicates process information for input 5.
AUTO Indicates process information for input 6.
AUTO Indicates process information for input 7.
AUTO Indicates process information for input 8.
AUTO Indicates process information for input 9.
AUTO Indicates process information for input 10.
AUTO Indicates process information for input 11.
AUTO Indicates process information for input 12.
AUTO Indicates process information for input 13.
AUTO Indicates process information for input 14.
AUTO Indicates process information for input 15.
Explanation
<12. Parameter Lists>
12-8
Relative
Index
65 2065 IN_16 Status: 0xC0
66 2066 IN01_MAIN_TAG PD_Tag01 AUTO Use to set the Main Tag for input 1. Use as a memo eld and
67 2067 IN01_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 1. Use as a memo eld and set the
68 2068 IN01_SCALE 100.0
69 2069 IN02_MAIN_TAG ABCDEFGHIJKL
70 2070 IN02_SUB_TAG abcdefghijiklmno
71 2071 IN02_SCALE 100.0
72 2072 IN03_MAIN_TAG PD_Tag03 AUTO Use to set the Main Tag for input 3. Use as a memo eld and
73 2073 IN03_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 3. Use as a memo eld and set the
74 2074 IN03_SCALE 100.0
75 2075 IN04_MAIN_TAG PD_Tag04 AUTO Use to set the Main Tag for input 4. Use as a memo eld and
76 2076 IN04_SUB_TAG BLK01.OUT AUTO
77 2077 IN04_SCALE 100.0
78 2078 IN05_MAIN_TAG PD_Tag05 AUTO Use to set the Main Tag for input 5. Use as a memo eld and
79 2079 IN05_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 5. Use as a memo eld and set the
80 2080 IN05_SCALE 100.0
Index Parameter Name Factory Default
Value: 99999.0
0.0 1000 2
MNOPQRSTUV WXYZabcdef
pqrstuvwxyzABC DEF
0.0 1000 2
0.0 1000 2
0.0 1000 2
0.0 1000 2
Write Mode
AUTO Indicates process information for input 16.
set the information you most want to display in order to inden­tify instruments. See PD_TAG connected devices and other information for setup examples.
information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 1.
AUTO Use to set the Main Tag for input 2. Use as a memo eld and
set the information you most want to display in order to inden­tify instruments. See PD_TAG connected devices and other information for setup examples.
AUTO Use the Sub Tag for input 2. Use as a memo eld and set the
information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 2.
set the information you most want to display in order to inden­tify instruments. See PD_TAG connected devices and other information for setup examples.
information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 3.
set the information you most want to display in order to inden­tify instruments. See PD_TAG connected devices and other information for setup examples.
Use the Sub Tag for input 4. Use as a memo eld and set the information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 4.
set the information you most want to display in order to inden­tify instruments. See PD_TAG connected devices and other information for setup examples.
information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 5.
Explanation
<12. Parameter Lists>
12-9
Relative
Index
81 2081 IN06_MAIN_TAG PD_Tag06 AUTO Use to set the Main Tag for input 6. Use as a memo eld and
82 2082 IN06_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 6. Use as a memo eld and set the
83 2083 IN06_SCALE 100.0
84 2084 IN07_MAIN_TAG PD_Tag07 AUTO Use to set the Main Tag for input 7. Use as a memo eld and
85 2085 IN07_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 7. Use as a memo eld and set the
86 2086 IN07_SCALE 100.0
87 2087 IN08_MAIN_TAG PD_Tag08 AUTO Use to set the Main Tag for input 8. Use as a memo eld and
88 2088 IN08_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 8. Use as a memo eld and set the
89 2089 IN08_SCALE 100.0
90 2090 IN09_MAIN_TAG PD_Tag09 AUTO Use to set the Main Tag for input 9. Use as a memo eld and
91 2091 IN09_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 9. Use as a memo eld and set the
92 2092 IN09_SCALE 100.0
93 2093 IN10_MAIN_TAG PD_Tag10 AUTO Use to set the Main Tag for input 10. Use as a memo eld
94 2094 IN10_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 10. Use as a memo eld and set
95 2095 IN10_SCALE 100.0
96 2096 IN11_MAIN_TAG PD_Tag11 AUTO Use to set the Main Tag for input 11. Use as a memo eld and
Index Parameter Name Factory Default
0.0 1000 2
0.0 1000 2
0.0 1000 2
0.0 1000 2
0.0 1000 2
Write Mode
set the information you most want to display in order to inden­tify instruments. See PD_TAG connected devices and other information for setup examples.
information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 6.
set the information you most want to display in order to inden­tify instruments. See PD_TAG connected devices and other information for setup examples.
information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 7.
set the information you most want to display in order to inden­tify instruments. See PD_TAG connected devices and other information for setup examples.
information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 8.
set the information you most want to display in order to inden­tify instruments. See PD_TAG connected devices and other information for setup examples.
information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 9.
and set the information you most want to display in order to indentify instruments. See PD_TAG connected devices and other information for setup examples.
the information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 10 .
set the information you most want to display in order to inden­tify instruments. See PD_TAG connected devices and other information for setup examples.
Explanation
<12. Parameter Lists>
12-10
Relative
Index
97 2097 IN11_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 11. Use as a memo eld and set the
98 2098 IN11_SCALE 100.0
99 2099 IN12_MAIN_TAG PD_Tag12 AUTO Use to set the Main Tag for input 12. Use as a memo eld
100 2100 IN12_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 12. Use as a memo eld and set
101 2101 IN12_SCALE 100.0
102 2102 IN13_MAIN_TAG PD_Tag13 AUTO Use to set the Main Tag for input 13. Use as a memo eld
103 2103 IN13_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 13. Use as a memo eld and set
104 2104 IN13_SCALE 100.0
105 2105 IN14_MAIN_TAG PD_Tag14 AUTO Use to set the Main Tag for input 14. Use as a memo eld
106 2106 IN14_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 14. Use as a memo eld and set
107 2107 IN14_SCALE 100.0
108 2108 IN15_MAIN_TAG PD_Tag15 AUTO Use to set the Main Tag for input 15. Use as a memo eld
109 2109 IN15_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 15. Use as a memo eld and set
110 2110 IN15_SCALE 100.0
111 2111 IN16_MAIN_TAG PD_Tag16 AUTO Use to set the Main Tag for input 16. Use as a memo eld
Index Parameter Name Factory Default
0.0 1000 2
0.0 1000 2
0.0 1000 2
0.0 1000 2
0.0 1000 2
Write Mode
information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 11.
and set the information you most want to display in order to indentify instruments. See PD_TAG connected devices and other information for setup examples.
the information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 12.
and set the information you most want to display in order to indentify instruments. See PD_TAG connected devices and other information for setup examples.
the information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 13.
and set the information you most want to display in order to indentify instruments. See PD_TAG connected devices and other information for setup examples.
the information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 14.
and set the information you most want to display in order to indentify instruments. See PD_TAG connected devices and other information for setup examples.
the information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 15.
and set the information you most want to display in order to indentify instruments. See PD_TAG connected devices and other information for setup examples.
Explanation
<12. Parameter Lists>
12-11
Relative
Index
112 2112 IN16_SUB_TAG BLK01.OUT AUTO Use the Sub Tag for input 16. Use as a memo eld and set
113 2113 IN16_SCALE 100.0
114 2114 MS_CODE Null AUTO Records and displays instrument MS codes. 115 2115 SERIAL_NO Null AUTO Records and displays instrument serial numbers. 116 2116 MANUFAC_DATE Null AUTO Records and displays manufacture dates for instruments. 117 2117 TEST_KEY1 0, 0 AUTO Not used by the FVX110. 118 2118 TEST_KEY2 0.0, 0.0, 0.0, 0.0 AUTO Not used by the FVX110. 119 2119 TEST_KEY3 AUTO Not used by the FVX110. 120 2120 TEST_1 Not used by the FVX110. 121 2121 TEST_2 Not used by the FVX110. 122 2122 TEST_3 Not used by the FVX110. 123 2123 TEST_4 Not used by the FVX110. 124 2124 TEST_5 Not used by the FVX110. 125 2125 TEST_6 Not used by the FVX110.
Index Parameter Name Factory Default
0.0 1000 2
Write Mode
the information to be displayed after MAIN_TAG information in order to indentify instruments. See block names, parameter names and other information for setup examples.
AUTO Sets scaling, units and number of decimal places for display-
ing bar graphs of input 16.
Explanation
<13. General Specications>
13. General Specications
13-1
13.1 Functional Specications
Functional specications for Fieldbus communication conform to the standard specications (H1) of FOUNDATION eldbus.
Supply Voltage
9 to 32 V DC for general use, ame proof type,
Type n, or nonincendive. 9 to 24 V DC for intrinsically safe type Entity model 9 to 17.5 V DC for intrinsically safe type FISCO
model
Communication Requirements
Supply Voltage: 9 to 32 V DC Current consumption: Steady condition: 15 mA (max)
Software download condition: 24 mA (max)
Ambient Temperature Limits
-20 to 70°C (-4 to 158°F)
Ambient Humidity Limits
0 to 100 %RH
LCD Display
84 column x 32 lines full-dot matrix with LED
backlight.
3 lines indication as
• Top line 14 alphanumerics indication of main description
(Main Tag) such as PD TAG of eld device.
Scroll up to maximum 32 alphanumerics
• Middle line 5 digits process value including +/- sign and unit
of 5digits x 2 lines
• Bottom line 14 alphanumerics of communication status and
indicate description (Sub Tag) such as block information.
Bar graph, Scroll bar, Page information, Scroll
direction information, Squawk
Top line
Unit (Middle line)
Bottom line
Process value
(Middle line)
14 characters
5 digits
14 characters
5 digits 5 digits
Display Scroll Functions
Single scroll and cyclic scroll (Scan mode) Display up to 16 variables
EMC Conformity Standard:
EN61326-1 Class A, Table 2 (For use in industrial location)
Link Master Function:
Link Master function is supported.
Function Block:
Block name Number Execution time Note
MAO
IS
AR
PID
SC
IT
2 30 ms Output eight analog signals from eld deveces 2 30 ms Input Selector block provides selection of up to eight inputsand generate
an output based on the congured action
2 30 ms Arithmetic block permits simple use of popular measurement math func-
tion
2 45 ms Works as a eld controller in conjunction with another function block. 1 30 ms An output of Signal Characterizer block is a nonlinear function of the
respective input. The function is determined by a table
1 30 ms Integrator block integrates a variable as a function of the time or accumu-
lates the counts
F1301.ai
<13. General Specications>
13.2 Physical Specications
Enclosure
Material
Housing: Low copper cast aluminum alloy with
polyurethane, mint-green paint (Munsell 5.6BG
3.3/2.9 or its equivalent) or ASTM CF-8M
stainless steel. Body: 316L SST Scroll Knob: 316L SST Cover O-rings: Buna-N Name plate and tag: 304 SST, 316 SST (for
optional code /HC)
Degrees of Protection
IP67, NEMA4X
Weight
1.2 kg (2.6 lb) * *: Without mounting bracket. Add 1.5 kg (3.3 lb) for Amplier housing code 2.
13-2
Electrical Connections
Refer to 13.3 Model and Sufx Codes.
13.3 Model and Sufx Codes
Model Sufx code Description
FVX110 . . . . . . . . . . . . . . . . . . . . Fieldbus segment indicator
Output signal
Amplier housing
Electrical connection
Mounting bracket L
Optional Codes
-F
. . . . . . . . . . . . . . . . . .
1
. . . . . . . . . . . . . . . .
2 . . . . . . . . . . . . . . . .
0 . . . . . . . . . . . . .
2
. . . . . . . . . . . . .
4
. . . . . . . . . . . . .
5
. . . . . . . . . . . . .
7
. . . . . . . . . . . . .
9
. . . . . . . . . . . . .
A
. . . . . . . . . . . .
D
. . . . . . . . . . . .
C
. . . . . . . . . . . .
. . . . . . . . . .
N
. . . . . . . . . .
/
Digital communication (FOUNDATION Fieldbus protocol)
Cast aluminum alloy ASTM CF-8M stainless steel
G 1/2 female, one electrical connection without blind plug 1/2 NPT female, two electrical connections without blind plugs M20 female, two electrical connections without blind plugs G 1/2 female, two electrical connections and a blind plug 1/2 NPT female, two electrical connections and a blind plug M20 female, two electrical connections and a blind plug G 1/2 female, two electrical connections and a 316 SST blind plug 1/2 NPT female, two electrical connections and a 316 SST blind plug M20 female, two electrical connections and a 316 SST blind plug 316 SST 2-inch pipe mounting None Optional Specication
*1
*1: Not applicable for electrical connection code 0, 5, 7 or 9
<13. General Specications>
13.4 Optional Specications (For Explosion Protected type)
13-3
Item Description Code
1
1
1
1
1
Factory Mutual (FM)
CENELEC ATEX
Canadian Standards Association (CSA)
FM Explosionproof Approval *
Applicable Standard: FM3600, FM3615, FM3810, ANSI/NEMA 250 Explosionproof for Class I, Division 1, Groups B, C and D, Dust-ignitionproof for Class II/III, Division 1, Groups E, F and G, Enclosure Rating: NEMA Type 4X Temperature class: T6, Amb. Temp.: –40 to 60°C (–40 to 140°F)
FM Intrinsically Safe and Nonincendive Approval *
Applicable Standard: FM3600, FM3610, FM3611, FM3810, ANSI/NEMA 250, ISA60079-27 Intrinsically Safe for Class I,II, & III, Division 1, Groups A,B,C,D,E,F & G, Entity, FISCO. /Class I, Zone 0, AEx ia IIC, Enclosure: "NEMA 4X", Temp. Class: T4, Amb. Temp.: –40 to 60°C (–40 to 140°F). Intrinsically Apparatus Parameters : [FISCO (IIC)] Ui=17.5 V, Ii=500 mA, Pi=5.5 W, Ci=1.76 nF, Li=0 µH [FISCO (IIB)] Ui=17.5 V, Ii=500 mA, Pi=5.5 W, Ci=1.76 nF, Li=0 µH [Entity] Ui=24 V, Ii=250 mA, Pi=1.2 W, Ci=1.76 nF, Li=0 µH Nonincendive for Class I, Division 2, Groups A, B, C and D, NIFW, FNICO Class I, Zone 2, Group IIC, NIFW, FNICO Class II, Division 2, Groups F&G, and Class III, Division 1 Enclosure: "NEMA 4X", Temp. Class: T4, Amb. Temp.: –40 to 60°C (–40 to 140°F) Nonincendive Apparatus Parameters : Vmax.=32 V, Ci=1.76 nF, Li=0 µH
CENELEC ATEX (KEMA) Flameproof Approval *
Applicable Standard: EN 60079-0, EN 60079-1, EN 61241-0, EN 61241-1 Certicate: KEMA 10ATEX0157 II 2G, 2D Ex d IIC T6 Ex tD A21 IP6X T80 Degree of protection : IP66 and IP67 Amb. Temp. (Tamb) for gas-proof : T6; –50 to 75°C (–58 to 167°F) Max. surface Temp. for dust-proof : T80°C (Tamb: –40 to 167°F)
CENELEC ATEX (DEKRA) Intrinsically safe Approval *
Certicate: DEKRA 11ATEX0022 X Applicable standards: EN 60079-0, EN 60079-11, EN 60079-26, EN 60079-27, EN 61241-11 II 1G Ex ia IIB/IIC T4 Ga, II 1D Ex ia IIIC T80°C Da IP6X Amb. Temp.: –40 to 60°C (–40 to 140°F) Max. Surface Temp. for dust-proof: T80°C (Tamb.: –40 to 140°F) Enclosure: IP66 and IP67 [FISCO (IIC)] Ui=17.5 V, Ii=500 mA, Pi=5.5 W, Ci=3.52 nF, Li=0 µH [FISCO (IIB)] Ui=17.5 V, Ii=500 mA, Pi=5.5 W, Ci=3.52 nF, Li=0 µH [Entity] Ui=24 V, Ii=250 mA, Pi=1.2 W, Ci=3.52 nF, Li=0 µH
CSA Explosionproof Approval *
Certicate: 2325751 Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.0.5, C22.2 No.25, C22.2 No.30, C22.2 No.94, C22.2 No.213, C22.2 No.60079-0, C22.2 No.60079-1, C22.2 No.61010-1-04 Explosion-proof for Class I, Groups B, C and D. Dustignition-proof for Class II/III, Groups E, F and G. When installed in Division 2, "SEAL NOT REQUIRED" Enclosure: TYPE 4X, Temp. Class: T6 Ex d IIC T6 Enclosure: IP66 and IP67 Amb.Temp.: –50 to 75°C (–58 to 167°F)
CSA Intrinsically safe Approval *1
Certicate: 2346277 Applicable Standard: C22.2 No.0, C22.2 No.0.4, C22.2 No.25, C22.2 No.94, C22.2 No.157, C22.2 No.213, C22.2 No.61010-1-04 CAN/CSA E60079-0, CAN/CSA E60079-11, CAN/CSA E60079-15, IEC 60529 Intrinsically Safe for Class I, Division 1, Groups A, B, C & D, Class II, Division 1, Groups E, F & G, Class III Division 4; Ex ia IIC T4 Amb. Temp.: –40 to 60°C (–40 to 140°F) Encl. Type 4X, IP66 and IP67 Entity Parameters for Intrinsically Safe: Ui (Vmax)=24 V, Ii (Imax)=250 mA, Pi (Pmax)=1.2 W, Ci=1.76 nF, Li=0 µH or Ui (Vmax)=17.5 V, Ii (Imax)=500 mA, Pi (Pmax)=5.5 W, Ci=1.76 nF, Li=0 µH Nonincendive for Class I, Division 2, Groups A, B, C & D, Class II, Division 2, Groups F & G, Class III Division 1; Ex nL IIC T4 Amb. Temp.: –40 to 60°C (–40 to 140°F) Encl. Type 4X, IP66 and IP67 Entity Parameters for Nonincendive: Ui=32 V, Ci=1.76 nF, Li=0 µH
FF1
FS15
KF25
KS25
CF1
CS15
<13. General Specications>
13-4
Item Description Code
IECEx Flameproof Approval *
Applicable Standard: IEC 60079-0, IEC60079-1 Certicate: IECEx KEM 10.0071 Flameproof for Zone 1, Ex d IIC T6 Enclosure: IP66 and IP67 Amb.Temp.: –50 to 75°C (–58 to 167°F)
IECEx Intrinsically safe and type n Approval *1
IECEx Scheme
*1: Applicable for Electrical connection code 2, 4, 7, 9, C and D.
No. IECEx DEK 11.0004 X Applicable Standard: IEC 60079-0, IEC 60079-11, IEC 60079-26, IEC 60079-27, Ex ia IIB/IIC T4, Ga Ex ic IIC T4 GC Ambient Temperature: –40 to 60°C Enclosure: IP66 and IP67 Intrinsically safe ratings (Ex ia IIB/IIC T4) [Entity] Ui=24 V, Ii=250 mA, Pi=1.2 W, Ci=3.52 nF, Li=0 µH [FISCO IIC] Ui=17.5 V, Ii=500 mA, Pi=5.5 W, Ci=3.52 nF, Li=0 µH [FISCO IIB] Ui=17.5 V, Ii=500 mA, Pi=5.5 W, Ci=3.52 nF, Li=0 µH Intrinsically safe ratings (Ex ic IIC T4): Ui=32 V, Ci=3.52 nF, Li=0 µH
1
13.5 Optional Specications
Item Description Optional code
Painting Color change Amplier cover only
Amplier cover and terminal cover, Munsell 7.5 R4/14
Coating change Anti-corrosion coating 316 SST exterior parts 316 SST name plate, tag plate and screw Lightning protector Power supply voltage: 10.5 to 32 V DC (10.5 to 30 V DC for intrinsically safe
type, 9 to 32 V DC for Fieldbus communication type) Allowable current: Max. 6000A (1x40μs), Repeating 1000A (1x40μs) 100times
Wired tag plate 304 SST tag plate wired onto indicator (316 SST when /HC is specied)
*1: Not applicable for amplier housing code 2 *2: Not applicable with color change option *3: 316 SST or 316L SST. The specication is included in amplier housing code 2.
*1
*1*2
*3
SF25
SS25
P
PR
X2
HC
A
N4
<13. General Specications>

13.6 Dimensions

13-5
Conduit connection
Mounting bracket
(optional)
(2.36)
126 (4.96)
95 (3.74)
60
50
(1.97)
12
(0.47)
Scroll knob
Conduit connection
139 (5.47)
159 (6.26)
(O.D. 60.5 mm)
54
(2.13)
6
(0.24)
Ø78 (3.07)
Ground
terminal
Body
2-inch pipe
110 (4.33)
12
(0.47)
Unit: mm (approx.inch)
188 (7.40)
39
(1.54)
Ø70 (2.76)
110 (4.33)
129 (5.08)
Electrical connection for code 5, 9, A and D
● Terminal Conguration ● Terminal Wiring
Communication terminals connection hook
SUPPLY +
SUPPLY –
SUPPLY
<Factory Setting>
Tag Number
Software Tag
Node Address '0xF5' unless otherwise specied in
+ –
(Tag plate)
(PD_TAG)
Operation
Functional
Class
Power supply and output terminal
Ground terminal
'UI1001' unless otherwise both Tag Number and software Tag specied in order
order BASIC or as specied
F1302.ai
F1303.ai
As specied in order
<Appendix 1. Signal Characterizer (SC) Block>
Appendix 1. Signal Characterizer (SC)
Block
A1-1
The Signal Characterizer (SC) block is used to convert the values of input signals according to a line-segment function. The line-segment function is created using 21 points of the X/Y coordinates specied by the user. This function block can also be used as a transmission line for control signals and supports backward control.
Application
The Signal Characterizer block is primarily used if you wish for one of the following reasons to correct signals using the coordinates rather than a computational expression:
• The computational expression for correction in relation to input signals is complex
• The relationship between input signals and the signals after correction is only empirically known
A1.1 Schematic Diagram of
Signal Characterizer Block
The following shows the schematic diagram of the Signal Characterizer block.
IN_1
IN_2
Figure A1.1 Signal Characterizer Block
y
OFF OFF
ON
x
Inverse function
SWAP_2
ON
x
y
OUT_1
OUT_2
FA0101.ai
Input/Output Parameters
Input IN_1 Inputs a signal desired to be corrected using a line-segment function.
IN_2 Inputs a signal desired to be corrected using a line-segment function.
Output OUT_1 Outputs the result of the IN_1 input that has been corrected using the line-segment function.
OUT_2 Outputs the result of the IN_2 input that has been corrected using the line-segment function.
Others CURVE_X The points of the curve determining inputs and outputs.
CURVE_Y The points of the curve determining inputs and outputs.
SWAP_2 Selector switch used to specify if an inverse function is used for the line-segment
(It is substituted for X of the line-segment function.)
(If SWAP_2 = off, it is substituted for X of the line-segment function.) (If SWAP_2 = on, it is substituted for Y of the line-segment function.)
(The function block outputs the value of Y corresponding to IN_1.)
The output can also be approximated using the inverse function of the specied line-segment function. (This is used for backward control.) (If SWAP_2 = off, the value of Y corresponding to X of IN_1 is output.) (If SWAP_2 = on, the value of X corresponding to Y of IN_1 is output.)
The x points of the curve are dened by an array of 1 to 21 points with a monotone increase. "+INFINITY" is congured for unused point(s).
The y points of the curve are dened by an array of 1 to 21 points. If SWAP_2 = on, the elements of the curve are dened with a monotone increase or decrease. "+INFINITY" is congured for unused point(s).
approximation of IN_2 to OUT_2. The setting of SWAP_2 = on (which uses the inverse function) is used for backward control.
<Appendix 1. Signal Characterizer (SC) Block>
Line-segment factor
determination section
Determining
the gradient
and intercept
Output section
OUT
processing
Determining the
status and
computing OUT
OUT_1
OUT_2
IN_1
IN_2
Input section
Determining
the mode
BLOCK_ERR
A1-2
Y
or
X
X or Y
CURVE_X CURVE_Y
Figure A1.2 Overview of the Signal Characterizer Block
SWAP_2
The following describes the Signal Characterizer block, dividing its functions into three sections:
• Input section: Determines the mode and judges BLOCK_ERR.
• Line-segment factor determination section: Determines the gradient and intercept for OUT_1 and
OUT_2 based on CURVE_X, CURVE_Y, and
SWAP_2 at shift .
• Output section: Multiplies the input values in IN_1 and IN_2 by the gradient and adds the intercept to them before outputting the results. Alternatively, it outputs a limit value.

A1.2 Input Section

The input section determines the mode and judges BLOCK_ERR.

A1.2.1 Determining the Mode

MODE = AUTO MODE = MAN or O/S
FA0102.ai

A1.2.2 Judging BLOCK_ERR

BLOCK_ERR indicates the cause of an error in the function block. If the cause of an error indicated by BLOCK_ERR occurs, the following conguration error is generated.
Name Description
Block Conguration Error
1) “–INFINITY” has been congured for CURVE_X and CURVE_Y.
2)
“+INFINITY” has been congured for
X1 of CURVE_X.
3)
“+INFINITY” has been congured for
Y1 of CURVE_Y.
4)
A value of the array of CURVE_X
does not increase in a monotone manner.
5)
A conguration error when SWAP_2
is on"
• A value of the array of CURVE_Y does not increase or decrease in a monotone manner.
6)
The value of SWAP_2 is any value
other than 1 or 2.
The following describes operations of the Signal Characterizer block.
Supported Mode Rules
O/S (Out of Service)
Man
Auto
• System-stopped status
• Conguration change If you do not want to output the
value and the status from IN, you can manually transmit the value to OUT.
Automatic system operation status
The mode changes to O/S if a block conguration error occurs.
<Appendix 1. Signal Characterizer (SC) Block>
A1-3

A1.3 Line-segment Factor Determination Section

When the mode is AUTO and no bit in BLOCK_ERR is set, the "gradient" and "intercept" of a line passing through two points that are considered line-segment approximation values are determined.
A1.3.1 Conditions for Conguring Valid Coefcients (CURVE_X, CURVE_Y)
No write error is generated with respect to the settings in CURVE_X and CURVE_Y. However, a conguration error occurs in the following cases:
1. "+INFINITY" has been congured for X1 or Y1.
2. "–INFINITY" has been congured for each X or Y.
3. The values of CURVE_X are not increasing in a monotone manner (X1 < X2 < ... < X20 < X21). (If SWAP_2 is off, it is acceptable if the values of CURVE_Y do not increase or decrease in a monotone manner.)
4. The values of CURVE_Y are not increasing or decreasing in a monotone manner when SWAP_2 is on.
If a conguration error occurs, the Block Conguration Error bit in BLOCK_ERR is set, causing the mode to change to O/S.
Example of the case where SWAP_2 is off:
Y
Output
Y6
(High limit)
Y1
(Low limit)
X1 X2 X3 X4 X5 X6 X7 =INFINITY X
Input
FA0103.ai
Figure A1.3 Example of Curve (SWAP_2 = off)
The range of CURVE_X: X1 to X6 (X7 and above are invalid because "+INFINITY" has been congured for X7*1.)
The X1 to X6 values always increase in a monotone manner (X1 < X2 < X3 < X4 < X5 < X6).
If an input value is smaller than X1, it is set to Y1.
If an input value is larger than X6, it is set to Y6.
The range of CURVE_Y: Y1 to Y6
It is acceptable if the Y1 to Y6 values do not increase in a monotone manner.
However, if the setting of SWAP_2 is changed from off to on, the values of CURVE_Y must increase or decrease in a monotone manner. Thus, if a value of CURVE_Y does not increase or decrease in a monotone manner in this setting, the mode changes to O/S, causing the Block Conguration Error bit in BLOCK_ERR to be set.
*1: For any points of the curve that are not used, congure "+INFINITY" for all of them.
<Appendix 1. Signal Characterizer (SC) Block>
A1-4
Example of the case where SWAP_2 is on (monotone increase):
The input range of IN_1 is always in CURVE_X. The following shows the input/output graph of the IN_1 values.
Y
Output
Y6
(High limit)
Y1
(Low limit)
X1 X2 X3 X4 X5 X6 X7 =INFINITY X
Input
FA0104.ai
Figure A1.4 Example of Curve for IN_1 (SWAP_2 = on)
The input range of IN_2 is always in CURVE_Y. The following shows the input/output graph of the IN_2 values.
Output
X
X6
X5
X4
X3
X2
X1
Y Input
Y1
(Low limit)
Figure A1.5 Example of Curve for IN_2 (SWAP_2 = on)
Y2 Y3 Y4 Y5 Y6 Y7 =INFINITY
(High limit)
FA0105.ai
When SWAP_2 is on, the array elements of CURVE_Y must be congured for a monotone increase or decrease. (Y1 < Y2 < Y3 < Y4 < Y5 < Y6 or Y6 < Y5 < Y4 < Y3 < Y2 < Y1)
<Appendix 1. Signal Characterizer (SC) Block>

A1.4 List of Signal Characterizer Block Parameters

A1-5
Relative
Index
0 BLOCK_
1 ST_REV - - - - - 2 2 2 2 The revision level of the set parameters associated
2 TAG_DESC Null Stores comments describing tag information. 3 STRATEGY 1 2 The strategy eld can be used by the high-level
4 ALERT_KEY 1-255 1 1 Key information used to identify the location at which
5 MODE_BLK 4 4 Mode of the Signal Characterizer block. O/S, Man,
6 BLOCK_ERR 2 2 Indicates the error status of the Signal Characterizer
7 OUT_1 MAN 5 5 Outputs the result of the value of IN_1 corrected
8 OUT_2 MAN 5 5 Outputs the result of the value of IN_2 corrected
9 X_RANGE 100
10 Y_RANGE 100
11 GRANT_DENY 2 The parameter used to check if various operations
12 IN_1 5 5 Input a signal to be corrected using a line-segment
13 IN_2 5 5 Input a signal to be corrected using a line-segment
14 SWAP_2 0:Initialized
15 CURVE_X Curve input points that determine inputs and
16 CURVE_Y Curve input points that determine inputs and
17 UPDATE_EVT Indicates event information if an update event
18 BLOCK_ALM Indicates alarm information if a block alarm occurs.
Parameter
HEADER
Write
Mode
Block Tag=O/S
Valid Range
0 1342 1
0 1342 1
1:No swap 2:Swap
Initial
Value
TAG: "SC" Information relating to this function block, such as
View
1 2 3 4
block tag, DD revision, and execution time
with the Signal Characterizer block
system to identify function blocks.
an alert has occurred
and Auto are supported.
block in bit strings.
using a line-segment function.
using a line-segment function. It is also possible to approximate the result using the inverse function of the specied line-segment function. (This is used for backward control.)
11 The engineering unit of variables corresponding to
the X-axis for display
11 The engineering unit of variables corresponding to
the Y-axis for display
have been executed. The bits in the GRANT parameter corresponding to various operations are set before being executed. After the operations are complete, the DENY parameter is checked for the setting of any bit relating to the corresponding operation. If no bit is set, it is evident that the operations have been executed successfully.
function.
function.
1 Selector switch used to apply the inverse function to
line-segment approximation of IN_2 to OUT_2
outputs. The "x" points of the curve are dened by an array of 1 to 21 points with a monotone increase.
outputs. The "y" points of the curve are dened by an array of 1 to 21 points. If SWAP_2 is on, the elements of the curve must be dened with a monotone increase or decrease.
occurs.
Description / Remarks
<Appendix 1. Signal Characterizer (SC) Block>
A1-6

A1.5 Application Example

A1.5.1 Input Compensation

The following is an application example of pH compensation made by performing feedback control.
The pH is a value representing the degree of acidity or alkalinity and ranges from 0 to 14. pH 7 indicates neutral, a value smaller than 7 represents acidity, and a value larger than 7 denotes alkalinity. It is very difcult to control pH with a quickly changing reaction rate at a point near 7.
14 13 12 11 10
9 8
pH
7 6 5 4 3 2 1
0 0.2 0.4 0.6 0.8 1.0 1.2 1.4 1.6 1.8 2.0
Ratio of Reagent to Influent Flow
Figure A1.6 pH and Reagent Flow
Small increases in reagent
flow cause large pH shifts
FA0106.ai
The following shows the approximation-value graph of GX Output that is approximation-value output and GX Input that is pH input. pH with a quickly changing reaction rate can be controlled at a point near neutral 7 according to the following graph.
100
90 80 70 60 50
CURVE_Y
40 30 20 10
0 10 20 30 40 50 60 70 80 90 100
0 to 100% = 0 to 14 pH
CURVE_X
FA0108.ai
Figure A1.8 Approximation Curve

A1.5.2 Calorie Flow Compensation

AI_1: Inlet temperature, AI_2: Outlet temperature, AI_3: Flow rate SC: Corrects the inlet and outlet temperatures. AR: Calculates a calorie ow rate on the basis of the difference between the corrected inlet and outlet temperatures.
To control this pH, the input is regulated using line-segment approximation, gain, and input compensation.
Characterizer
GX
X Gain
DM
Figure A1.7 Input Compensation
pH Input
PID
Control
Control
Output
Input Compensation
FA0107.ai
SWAP_2=OFF
IN_1
IN_2
SC
AI3
OUT_1
OUT_2
OUT
AR
IN_1
IN_2 OUT
IN
FA0109.ai
AI1
OUT
AI2
OUT
Figure A1.9 Calorie Flow Rate Compensation
(SWAP_2 = Off)
<Appendix 1. Signal Characterizer (SC) Block>
A1-7

A1.5.3 Backward Control

SC: The controlled variable output from PID is converted into an information quantity that can be interpreted by AO, and backward information from AO is converted into an information quantity that can be interpreted by PID before being transmitted to the PID.
AI
OUT
PID
OUTIN
BKCAL_IN
SC
OUT_1IN_1
OUT_2
SWAP_2=ON
IN_2
Figure A1.10 Backward Control (SWAP_2 = On)
To enable backward control (which inverts the X and Y axes), the line-segment function must be set so that the elements of the curve increase in a monotone manner.(As shown in Figure A1.11) If they do not increase in a monotone manner, the mode changes to O/S, disabling calculation.
AO
CAS_IN
BKCAL_OUT
FA0110.ai
Line-segment function
100
90
80
70
60
50
CURVE_Y
40
30
20
10
0 10 20 30 40 50 60 70 80 90 100
CURVE_X
X_RANGE = 100, 0, %, 0x00 Y_RANGE = 100, 0, %, 0x00
Figure A1.11 Setting Example of a Line-segment
Function
FA0111.ai
No. CURVE_X CURVE_Y
1 5 5 2 10 10 3 15 11 4 20 20 5 25 25 6 30 26 7 35 30 8 40 40 9 45 45
10 50 50
11 51 51 12 52 54 13 53 59 14 54 66 15 55 75 16 65 80 17 75 81 18 80 85 19 85 86 20 90 90 21 95 95
<Appendix 2. Integrator (IT) Block>
A2-1

Appendix 2. Integrator (IT) Block

The Integrator (IT) block adds two main inputs and integrates them for output. The block compares the integrated or accumulated value to TOTAL_SP and PRE_TRIP and generates discrete output signals OUT_ TRIP or OUT_PTRIP when the limits are reached.
The output is as represented by the following equation (for counting upward and rate conversion).
OUT.Value = Integration start value + Total Total = Total + Current Integral Current Integral = (x + y) × Δt x: IN_1 value whose unit has been converted y: IN_2 value whose unit has been converted Δt: block execution period

A2.1 Schematic Diagram of Integrator Block

The following shows the schematic diagram of the Integrator block.
INTEG_OPTS (INPUT TYPE)
–1
INTEG_OPTS (INPUT TYPE)
–1
Forward
Reverse
Forward
Reverse
INTEG_OPTS (FROW TYPE)
Add
UNIT_CONV
INTEG_TYPE
INTEG_OPTS (QUALITY)
GOOD_LIM
UNCERT_LIM
CLOCK_PER
Integrate
TOTAL / RTOTAL
INTEG_OPTS
(CARRY)
OP_CMD_INT
(RESET)
N_RESET
PRE_TRIP
Compare
TOTAL_SP
Compare
MAN
OUT
MAN
OUT_PTRIP
MAN
OUT_TRIP
IN_1
REV_FLOW1
IN_2
REV_FLOW2
RESET_IN
TIME_UNIT1
Convert Rate
Convert Accum
PULSE_VAL1
TIME_UNIT2
Convert Rate
Convert Accum
PULSE_VAL2
RESET_CONFIRM
IN_1: Block input 1 (value and status) IN_2: Block input 2 (value and status) REV_FLOW1: Indicates whether the sign of IN_1 is reversed. It is a discrete signal. REV_FLOW2: Indicates whether the sign of IN_2 is reversed. It is a discrete signal. RESET_IN: Resets the integrated values. It is a discrete signal. RESET_CONFIRM: Reset conrmation input. It is a discrete signal. OUT: Block output (value and status) OUT_PTRIP: Set if the target value exceeds PRE_TRIP. It is a discrete signal. OUT_TRIP: Set if the target value exceeds TOTAL_SP (or 0). It is a discrete signal. The Integrator block is classied into the following ve sections for each function:
• Input process section: Determines the input value status, converts the rate and accumulation, and determines the input ow direction.
• Adder: Adds the two inputs.
• Integrator: Integrates the result of the adder into the integrated value.
• Output process section: Determines the status and value of each output parameter.
• Reset process section: Resets the integrated values.
Figure A2.1 Integrator Block
FA0201.ai
<Appendix 2. Integrator (IT) Block>
A2-2

A2.2 Input Process Section

When executed, the Integrator block rst performs input processing in the order of:
"Determining input status" → "Converting Rate or Accum" → "Determining the input ow direction"
Switching between Convert Rate and Convert Accum is made using bit 0 (for IN_1) or bit 1 (for IN_2) of INTEG_OPTS. INTEG_OPTS is one of the system parameters and should be set by the user. The values of IN_1 and IN_2 are not retained if the power is turned OFF.

A2.2.1 Determining Input Value Statuses

The following shows the correlation between the statuses of input parameters (IN_1, IN_2) and the statuses of input values used in the Integrator block.
Statuses of Input
Parameters (IN_1, IN_2)
Bit 4 of INTEG_OPTS
(Use Uncertain)
Bit 5* of INTEG_OPTS
(Use Bad)
Status of Input Values
Handled in IT Block
Good Irrelevant Irrelevant Good
Bad Irrelevant H (=1) Good
Bad Irrelevant L (=0) Bad Uncertain H (=1) Irrelevant Good Uncertain L (=0) Irrelevant Bad
For addition (see A2.3), if the status of an input value is "Bad," the "Good" value just before the status changed to "Bad" is used.
* Even if the Use Bad option is used, changing the internal status to "Good," the value of "Good" just before
the status changed to "Bad" is used.

A2.2.2 Converting the Rate

The following describes an example of rate conversion.
In rate conversion, rstly convert the unit of two inputs to that based on seconds. Next, convert the unit of the inputs to the same unit to be added together. The unit of IN_2 is standardized to that of IN_1. Then, calculates a weight, volume, or energy by multiplying each input value and block execution time. Because unit information is not input to the Integrator block as an input value, the user must input in advance tuned values to the TIME_UNIT1/2 and UNIT_CONV parameters.
Converts the unit into that based on seconds
TIME_UNIT1
input1
kg/hour
input2 lb/min
lb: pounds
sec:÷1
min:÷60
hour:÷3600
day:÷86400
Converts the unit into that based on seconds
TIME_UNIT2
sec:÷1
min:÷60
hour:÷3600
day:÷86400
Standardizes the unit of IN_2 to that of IN_1. Because "lb/s" is converted into "kg/s" in this example, the input 2 value is multiplied by 0.453. (1 lb = 0.453 kg)
UNIT_CONV
lb/s kg/s kg
x [conversion factor]
(Conversion factor:
0.453 in this example)
Figure A2.2 Increment Calculation with Rate Input
kg/s kg
× block execution time
× block execution time
increment1
increment2
FA0202.ai
<Appendix 2. Integrator (IT) Block>
A2-3

A2.2.3 Converting Accumulation

This following describes an example of accumulation conversion.
In accumulation conversion, the difference between the value executed previously and the value executed this time is integrated or accumulated. This conversion applies when the output of a function block used as a counter is input to the input process of the Integrator block.
In order to convert the rate of change of an input to a value with an engineering unit, the user must congure the factor of conversion to the appropriate engineering unit in the PULSE_VAL1 and PULSE_VAL2 parameters.
Moreover, the unit of IN_2 is standardized to that of IN_1 in the same way as rate conversion. Thus, the user must also set an appropriate value to UNIT_CONV.
input1
counts number of pulse kg
input2
counts number of pulse lb kg
Figure A2.3 Increment Calculation with Counter Input
[Current read value] – [Previous read value]
[Current read value] – [Previous read value]
PULSE_VAL1(#19)
× [pulse value1]
kg/pulse
PULSE_VAL2(#20)
× [pulse value2]
lb/pulse
UNIT_CONV(#18)
× [conversion factor]
increment1
increment2
FA0203.ai

A2.2.4 Determining the Input Flow Direction

The Integrator block also considers the input ow direction. Information about the input ow direction is contained in REV_FLOW1 and REV_FLOW2 (0: FORWARD, 1: REVERSE).
In input processing, the sign of the value after rate and accumulation conversion is reversed if the REV_ FLOW1 and REV_FLOW2 parameters are set to REVERSE. When determination of the ow direction of two input values is complete, these two inputs are passed to the adder. The settings in REV_FLOW will be retained even if the power is turned OFF.

A2.3 Adder

When input processing is complete, two arguments that have been rate and accumulate converted will be passed to the adder. The adder adds these two values according to the option.

A2.3.1 Status of Value after Addition

If one of the statuses of two arguments is "Bad" or if two of them are both "Bad," the status of the value after addition becomes "Bad." In this case, the value of "Good" just before the status changed to "Bad" is used as the addition value (see A2.1).
When the statuses of two arguments are both "Good," the status of the value after addition becomes "Good." In this case, the status of the value after addition will be used for the status applied to integration.
<Appendix 2. Integrator (IT) Block>

A2.3.2 Addition

The following three options are available for addition:
• TOTAL: Adds two argument values as is.
• FORWARD: Adds two argument values, regarding a negative value as "0."
• REVERSE: Adds two argument values, regarding a positive value as "0."
You can choose these options using bit 2 and bit 3 of INTEG_OPTS as follows:
A2-4
Bit 2 of INTEG_OPTS
(Flow Forward)
H H TOTAL
L L TOTAL
H L FORWARD
L H REVERSE
Bit 3 of INTEG_OPTS
(Flow Reverse)
Adder Options
The result of the adder is passed to the integrator. If only one of the inputs is connected, the value of a non­connected input will be ignored.
When bit 7 of INTEG_OPTS (Add zero if bad) has been set, if the status of a value after addition is "Bad," the value after addition (increment) becomes "0."

A2.4 Integrator

When addition is complete, its result will be passed to the integrator.
Integration consists of combinations of a reset method and counting up/down. There are the following seven integration types, which can be set using INTEG_TYPE.
1. UP_AUTO: Counts up with automatic reset when TOTAL_SP is reached
2. UP_DEM: Counts up with demand reset
3. DN_AUTO: Counts down with automatic reset when zero is reached
4. DN_DEM: Counts down with demand reset
5. PERIODIC: Counts up and is reset periodically according to CLOCK_PER
6. DEMAND: Counts up and is reset on demand
7. PER&DEM: Counts up and is reset periodically or on demand
Each type of integration is independently run as a function.
There are the following four types of integrated values:
1. Total: Integrates the result of the adder as is.
2. ATotal: Integrates the absolute value of the result of the adder.
3. RTotal: Integrates the absolute value of the result of the adder only if the status of the result is "Bad." This value is used for the RTOTAL value.
4. AccTotal: An extension function. The result of the adder is integrated as is and will not be reset.
The value is used for the ACCUM_TOTAL (expanded parameter) value.
The table A2.1 shows the details of INTEG_TYPE.
Loading...