Yellow Jacket 8002, 68004, 68006, 68008, 68010 Operating Manual

...
®
1
68010 68011 68016 68024
68104 68108
68132 68136 68143 68147
68064 68068 68164 68168
Instruction Manual
Leak Monitors
Refrigerant Models: 68002 68004 68006 68008
Ammonia Models: 68032 68036 68043 68047
Hydrocarbon Models:
YELLOW JACKET
The instructions contained in this manual must be adhered to or the
correct operation of this product may be impaired resulting in danger
from unobserved gas leaks.
Ritchie Engineering Co., Inc.
YELLOW JACKET Products Division
10950 Hampshire Avenue South
Bloomington, MN 55438-2623
Telephone: 800-769-8370
Fax: 800-322-8684
E-mail: custerv@yellowjacket.com
Web: www.yellowjacket.com
CERTIFIED REFRIGERANT TEST GAS MIXTURES
Some municipalities require the use of a certified test gas to validate the installation
prior to approving the Building Inspection. YELLOW JACKET does not offer certified
test gases but has identified the following source which can ship the gas via UPS. They are small high pressure cylinders which require a special regulator. The test
shipped via UPS ground. MSA Mine Safety Appliances
121 Gamma Drive
Pittsburgh, PA 15238-2919, US
1-800-672-2222
http://www.msanet.com
Part No. Description Cyl. Size
459948 0.25 L/min Regulator
803500 R134a, 100 PPM Test Gas 100 L
710874 R134a, 990 PPM Test Gas 100 L
494450 Hydrocarbon, 100 PPM Test Gas 100 L
711078 Ammonia, 25 PPM NH3 Test Gas 34 L To ensure the certified gas remains at the correct PPM (parts per million) concentra-
tion, tape a small box with a hole in it, over the senor to retain the gas. Insert the flexi-
ble hose into the hole and fill the box with the test gas for 60 seconds. Close the cylin-
der and hold the hose in the hole. The system under test should respond to the test gas within three to four minutes time.
This product is fully warranted against defective materials and/or workmanship for
a period of one year after purchase, provided it was not improperly used. For your
protection, please use this product as soon as possible. If returned, it must be securely
WARRANTY
wrapped, sent prepaid and insured to Ritchie Engineering Co., Inc.
12
Printed in U.S.A. P/N 395098_B
11
TIP: A YELLOW JACKET quick coupler gasket (#19020) inserted in the end
of the syringe will help make a seal at the cylinder port. Open the cylinder
valve until a light hiss can be heard. This will purge air from the cylinder port.
Press the syringe against the cylinder port and watch the plunger move as the
syringe fills. Close the cylinder valve when the syringe is full.
1 gallon plastic jug (clean) and screw cap (with seal)
10 to 15cc syringe
Cylinder of virgin refrigerant
MAKING AND USING A REFRIGERANT TEST GAS MIXTURE
Materials:
Procedure: NOTE: Perform these steps in an area away from the refrigerant monitor. 1. Clean the plastic jug by blowing it out with compressed air. Start with the syringe
plunger fully engaged (0cc). Carefully fill the syringe with vapor refrigerant from
the virgin cylinder. This should be done in an area away from the plastic jug.
to obtain the desired volume (4cc for a ~1000ppm mixture, 2cc for a ~500ppm
2. Immediately turn the syringe so the opening is upward. Slowly move the plunger
mixture). If the plunger moves below the desired volume, go back to step 2.
opening of the syringe to contain the measured gas. Place the opening of the
3. Once the proper volume is achieved in the syringe, place your finger over the
syringe into the opening of the plastic jug, remove your finger, and slowly release
the refrigerant sample down into the jug by pressing on the plunger.
4. When the syringe plunger is fully engaged, remove the syringe from the jug, place
the screw cap on the jug, and tighten the screw cap so it seals. Allow the jug to sit
in an upright position for a few minutes. Then turn the jug upside down and allow it
to sit for a few more minutes in this position. This will allow the refrigerant to blend
with the air in the jug.
A NOTE ON TESTING
To test refrigerant monitors, open the jug screw cap and place the opening of the jug
over the sensor, holding it so it seals against the sensor housing. This will minimize the
dissipation of the sample. Once the test is completed, immediately replace the screw
cap. Avoid rapid movement of the jug when it is open, as this will create air currents
that will dissipate the sample. Mix a fresh sample as required.
SYSTEM TECHNICAL DATA
Controller: Steel Mounting: Wall or Bulkheads Audio Alarm: 1/2 Sensors internal 80 dB/12 V DC Horn
4/6 Sensors external 110 dB/12 V DC Horn Outputs: Dry Contacts rated for 10 A @ 120/230 VAC
Uncommitted 12 v DC @ 100mA (4/6 Sensor Models)
Mechanical obstructions to inhibit air flow
Plenums for return air
Heat domes created by large boilers or equipment.
Product which limits gas movement
Where is the system vulnerable to breakage
Dangerous to Life if Leak Occurs
INSTALLATION INSTRUCTIONS
The controller and its sensors should be positioned carefully to avoid mechanical
damage, i.e. moving product, machinery, doors, etc.. They should also be kept away
from heat sources and should not be placed in strong drafts or in high moisture areas. DO NOT route sensor cables on building exteriors or between buildings via overhead
cables. Also, sensor wiring should be kept a minimum of 1.5 feet (500mm) from
electrical and telephone cables. (See section on sensor location). The controller and sensor must be installed in accordance with these instructions to
protect this equipment and ensure its correct performance.
QUANTITY AND LOCATION OF SENSORS
Sensor cable length must not exceed recommendations for the type of monitor if the
unit is to operate correctly. For one and two sensor models the wires to the sensors
cannot exceed 200 feet (60 meters). For four and six sensor models the sensor wires
cannot exceed 500 feet (160 meters). It is sometimes difficult to determine the number of sensors needed and the best
location of the sensors, as there is no hard and fast rule. However, there are a number
of simple guidelines which help to make the decision easier. Most standards normally
recommend some degree of ‘overkill’ to ensure adequate coverage. The two methods of locating sensors are “Point”, where sensors are located near the
most likely sources of leakage, and “Perimeter”, where sensors completely surround
the hazardous area. The size and nature of the site will help to decide which of these
methods is the most appropriate to use, consider the following:
YELLOW JACKET sensors can be calibrated for a maximum sensitivity to either group
“A” or group “C” refrigerant gases. If not specified ,the default is to Group A gases. Important: Do not try to economize by using the minimum number of sensors
possible. A few extra sensors could make all the difference when a gas leak occurs!
POSITIONING SENSORS
When detecting a refrigerant gas with vapor density greater than 1 (i.e. heavier than
air) the sensors should be located near ground level, approximately 16 –20” (40-50cm)
from the floor. Examples of such gases would be butane, LP Gas, xylene and very cold
ammonia in a deeply refrigerated cold storage. For any lighter than air gases, such as ammonia, methane or hydrogen, the sensor
2
needs to be located higher, 8-12” (20-30cm) from top of wall.
Loading...
+ 4 hidden pages