To properly use the product, read this manual thoroughly
and retain for easy reference, inspection, and maintenance.
Ensure the end user receives this manual.
200 V Class, Three-Phase Input: 0.1 to 5.5 kW
200 V Class, Single-Phase Input: 0.1 to 2.2 kW
400 V Class, Three-Phase Input: 0.2 to 5.5 kW
All rights reserved. No part of this publication
system, or transmitted, in any form or by any means, mechanical, electronic,
photocopying, recording, or otherwise, without the prior written permission of
Yaskawa. No patent liability is assumed with respect to the use of the information
contained herein. Moreover, because Yaskawa is constantly striving to improve its
high-quality products, the information contained in this manual is subject to change
without notice. Every precaution has been taken in the preparation of this manual.
Yaskawa assumes no responsibility for errors or omissions. Neither is any liability
assumed for damages resulting from the use of the information contained in this
publication.
may be reproduced, stored in a retrieval
2
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Table of Contents
i.PREFACE & GENERAL SAFETY ........................9
C.3 UL Standards..................................................................236
UL Standards Compliance .................................................. 236
Drive Motor Overload Protection .......................................... 238
8
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Preface & General
Safety
This section provides safety messages pertinent to this product
that, if not heeded, may result in fatality,
equipment damage. Yaskawa is not responsible for the
consequences of ignoring these instructions.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation
& Start-Up Manual
9
TERMSTERMS
i.1 Preface
i.1Preface
Yaskawa manufactures products used as components in a wide variety of industrial systems
and equipment. The selection and application of Yaskawa
of the equipment manufacturer or end user. Yaskawa accepts no responsibility for the way its
products are incorporated into the final system design. Under no circumstances should any
Yaskawa product be incorporated into any product or design as the exclusive or sole safety
control. Without exception, all controls should be designed to detect faults dynamically and
fail safely under all circumstances. All systems or equipment designed to incorporate a product
manufactured by Yaskawa must be supplied to the end user with appropriate warnings and
instructions as to the safe use and operation of that part. Any warnings provided by Yaskawa
must be promptly provided to the end user. Yaskawa offers an express warranty only as to the
quality of its products in conforming to standards and specifications published in the Yaskawa
manual. NO OTHER WARRANTY, EXPRESSED OR IMPLIED, IS OFFERED. Yaskawa
assumes no liability for any personal injury, property damage, losses, or claims arising from
misapplication of its products.
This manual is designed to ensure correct and suitable application of Variable J1000-Series
Inverters. Read this manual before attempting to install, operate, maintain, or inspect an
Inverter and keep it in a safe, convenient location for future reference. Be sure you understand
all precautions and safety information before attempting application.
u
Applicable Documentation
The following manuals are available for J1000 series drives:
J1000 Series Compact V/f Control Drive Installation and Start-Up Manual
Read this manual first. This guide is packaged together with the product. It
contains basic information required to install and wire the drive. This guide
provides basic programming and simple setup and adjustment. Refer to the
J1000 Technical Manual for complete descriptions of drive features and
functions.
J1000 Series Compact V/f Control Drive Technical Manual
This manual describes installation, wiring, operation procedures, functions,
troubleshooting, maintenance, and inspections to perform before operation.
products remain the responsibility
u
Symbols
Note: Indicates a supplement or precaution that does not cause drive damage.
Indicates a term or definition used in this manual.
10
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
u
Terms and Abbreviations
• Drive: Yaskawa J1000 Series Drive
i.1 Preface
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
11
i.2 General Safety
i.2General Safety
u
Supplemental Safety Information
General Precautions
• The diagrams in this manual may be indicated without covers or safety shields to show details. Restore
covers or shields before operating the drive
in this manual.
• Any illustrations, photographs, or examples used in this manual are provided as examples only and
may not apply to all products to which this manual is applicable.
• The products and specifications described in this manual or the content and presentation of the manual
may be changed without notice to improve the product and/or the manual.
• When ordering a new copy of the manual due to damage or loss, contact your Yaskawa representative
or the nearest Yaskawa sales office and provide the manual number shown on the front cover.
• If nameplate becomes worn or damaged, order a replacement from your Yaskawa representative or
the nearest Yaskawa sales office.
Read and understand this manual before installing, operating or servicing this drive. The
drive must be installed according to this manual and local codes.
The following conventions are used to indicate safety messages in this manual. Failure to
heed these messages could result in serious or possibly even fatal injury or damage to the
products or to related equipment and systems.
and run the drive according to the instructions described
WARNING
DANGER
Indicates a hazardous situation, which, if not avoided, will result in death or serious
injury.
WARNING
Indicates a hazardous situation, which, if not avoided, could result in death or serious
injury.
WARNING! will also be indicated by a bold key word embedded in the text followed by an italicized safety
message.
12
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
i.2 General Safety
CAUTION
Indicates a hazardous situation, which, if not avoided, could result in minor or
moderate injury.
CAUTION! will also be indicated by a bold key word embedded in the text followed by an italicized safety
message.
NOTICE
Indicates a property damage message.
NOTICE: will also be indicated by a bold key word embedded in the text followed by an italicized safety
message.
u
Safety Messages
DANGER
Heed the safety messages in this manual.
Failure to comply will result in death or serious injury.
The operating company is responsible for any injuries
failure to heed the warnings in this manual.
or equipment damage resulting from
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
Before servicing, disconnect all power to the equipment. The internal capacitor remains
charged even after the power supply is turned off. The charge indicator LED will extinguish
when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at least one minute
after all indicators are OFF and measure the DC bus voltage level to confirm safe level.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
13
i.2 General Safety
WARNING
Sudden Movement Hazard
System may start unexpectedly upon application of power,
injury.
Clear all personnel from the drive, motor and machine area before applying power. Secure
covers, couplings, shaft keys and machine loads before applying power to the drive.
resulting in death or serious
Electrical Shock Hazard
Do not attempt to modify or alter the drive in any way not explained in this manual.
Failure to comply could result in death or serious injury.
Yaskawa is not responsible for any modification of the product made by the user. This
product must not be modified.
Do not allow unqualified personnel to use equipment.
Failure to comply could result in death or serious injury.
Maintenance, inspection, and replacement of parts must be performed only by authorized
personnel familiar with installation, adjustment and maintenance of AC drives.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Fire Hazard
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply
before applying power.
CAUTION
Crush Hazard
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive
falling.
14
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
i.2 General Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and
circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting
voltage.
Improper equipment sequencing could result in damage to the drive.
Do not perform a withstand voltage test on any part of the drive.
Failure to comply could result in damage to the sensitive devices within the drive.
Do not operate damaged equipment.
Failure to comply could result in further damage to the equipment.
Do not connect or operate any equipment with visible damage or missing parts.
Install adequate branch circuit short circuit protection per applicable codes.
Failure to comply could result in damage to the drive.
The drive is suitable for circuits capable of delivering not more than 30,000 RMS
symmetrical Amperes, 240 Vac maximum (200 V Class) and 480 Vac maximum (400 V
Class).
Do not expose the drive to halogen group disinfectants.
Failure to comply may cause damage to the electrical components in the drive.
Do not pack the drive in wooden materials that have been fumigated or sterilized.
Do not sterilize the entire package after the product is packed.
u
Drive Label Warnings
Always heed the warning information listed in Figure i.1 in the position shown in Figure i.
2.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
15
i.2 General Safety
WARNING
Risk of electric shock.
Read manual before installing.
Wait 1 minute for capacitor discharge after
disconnecting power suppl
y.
To conform to requirements, make sure
to ground the supply neutral for 400V class.
Figure i.1 Warning Information
Warning
Label
Figure i.2 Warning Information Position
u
Warranty Information
Warranty Period
n
This drive is warranted for 12 months from
from the date of shipment from the Yaskawa factory, whichever comes first.
16
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
the date of delivery to the customer or 18 months
i.2 General Safety
Scope of Warranty
n
Inspections
Customers are responsible for periodic inspections of the drive. Upon request, a Yaskawa
representative
be defective due to Yaskawa workmanship or materials and the defect occurs during the
warranty period, this inspection fee will be waived and the problem remedied free of charge.
Repairs
If a Yaskawa product is found to be defective due to Yaskawa workmanship or materials and
the defect occurs during the warranty period, Yaskawa will provide a replacement, repair the
defective product, and provide shipping to and from the site free of charge.
However, if the Yaskawa Authorized Service Center determines that the problem with the
drive is not due to defective workmanship or materials, the customer will be responsible for
the cost of any necessary repairs. Some problems that are outside the scope of this warranty
are:
Problems due to improper maintenance or handling, carelessness, or other reasons where the
customer is determined to be responsible.
Problems due to additions or modifications made to a Yaskawa product without Yaskawa's
understanding.
Problems due to the use of a Yaskawa product under conditions that do not meet the
recommended specifications.
Problems caused by natural disaster or fire.
After the free warranty period elapses.
Replenishment or replacement of consumables or expendables.
Defective products due to packaging or fumigation.
Other problems not due to defects in Yaskawa workmanship or materials.
Warranty service is only applicable within Japan. However, after-sales service is available for
customers outside of Japan for a reasonable fee.
Contact your local Yaskawa representative for more information.
Exceptions
Any inconvenience to the customer or damage to non-Yaskawa products due to Yaskawa’s
defective products whether within or outside of the warranty period are NOT covered by
warranty.
will
inspect
the
drive
for a fee.
If the Yaskawa representative finds the drive to
Restrictions
n
The J1000 was not designed or manufactured for use in devices or systems that may directly
affect or threaten human lives or health.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
17
i.2 General Safety
Customers who intend to use the product described in this manual for devices or systems
relating to transportation, health care, space aviation, atomic power, electric power, or in
underwater applications must first contact their Yaskawa representatives or the nearest
Yaskawa sales office.
This product has been manufactured under strict quality-control guidelines. However, if this
product is to be installed in any location
where failure of this product could involve or result
in a life-and-death situation or loss of human life or in a facility where failure may cause a
serious accident or physical injury, safety devices must be installed to minimize the likelihood
of any accident.
u
Quick Reference
When using this drive for variable torque loads such as fans and pumps, a motor one frame size larger can be used.
The functions listed below affect the safe operation of the drive. Ensure that the settings fit the application requirements
prior to operation.
Safe operations. Run by power on. Parameter setting b1-17.
LOCAL/REMOTE key effective during stop in drive mode. Parameter o2-01.
LED operator stop key priority selection. Parameter o2-02.
Enter press required after changing the keypad frequency reference. Parameter o2-05.
Operation interlock when program mode is selected. Parameter b1-08.
The maintenance period of fans and capacitors can be checked with drive monitors.
Refer to Fault Displays, Causes, and Possible Solutions on page
Solutions on page 134.
Run a Motor of One-Frame Larger Capacity
Know the Details of Safety Measures
Check the Maintenance Period Using Drive Monitors
Drive or Motor Faults are Displayed on a Digital Operator
126 and Refer to Alarm Codes, Causes, and Possible
Standards Compliance
Refer to European Standards on page 229 and Refer to UL Standards on
236.
18
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
page
U
R
C
LISTED
US
L
1
Receiving
This chapter describes the proper inspections to perform after
receiving the drive and illustrates the different enclosure
and components.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation
& Start-Up Manual
19
1.1 Section Safety
1.1Section Safety
CAUTION
Do not carry the drive by the front cover.
Failure to comply may cause the main body
injury.
Observe proper electrostatic discharge procedures (ESD) when handling the drive and
circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
A motor connected to a PWM drive may
fed motor and the operating speed range may reduce motor cooling capacity.
Ensure that the motor is suitable for inverter duty and/or the motor service factor is adequate
to accommodate the additional heating with the intended operating conditions.
of the drive to fall, resulting in minor or moderate
NOTICE
operate at a higher temperature than a utility-
20
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
1.2 Model Number and Nameplate Check
1.2Model Number and Nameplate Check
Please perform the following tasks after receiving the drive:
• Inspect the drive for damage.
If the drive appears damaged upon receipt, contact the shipper immediately.
• Verify receipt of the correct model by checking the information on the nameplate.
• If you have received the
supplier.
u
Nameplate
wrong model or the drive does not function properly, contact your
Receiving
1
Drive model
Input
specifications
Output
specifications
Lot number
Serial number
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
CIMR-JA2A0004BAA
:
MODEL
MAX APPLI. MOTOR : 0.75kW / 0.4kW REV : A
: AC3PH 200-240V 50 / 60Hz 2.7A / 1.4A
INPUT
: AC3PH 0-240V 0-400Hz 1.2A / 0.8A
OUTPUT
: 0.9 kg
MASS
:
O / N
:
S / N
: E131457 IP20
FILE NO
YASKAWA ELECTRIC CORPORATION
Figure 1.1 Nameplate Information
PRG : 1010
PASS
MADE IN JAPAN
U
CUS
L
LISTED
IND.CONT.EQ.
7J48 B
Software version
21
1.2 Model Number and Nameplate Check
CIMR- J A 2A
Drive
Single-Phase 200 V
n
J1000
Series
Region
No.
Code
AJapan
TAsia
No.Voltage Class
B
2
4
Customized
No.
Specifications
A Standard model
1-phase, 200-240 Vac
3-phase, 200-240 Vac
3-phase, 380-480 Vac
0001B
No.
B
No.
A
M
N
S
AA
Enclosure
Type
IP20
Environmental
Specification <1>
Standard
Humidity- and
dust-resistant
Oil-resistant
Vibration-resistant
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation
& Start-Up Manual
29
2.1 Section Safety
2.1Section Safety
WARNING
Fire Hazard
Provide sufficient cooling when installing the drive inside
Failure to comply could result in overheating and fire.
When multiple drives are placed inside the same enclosure panel, install proper cooling to
ensure air entering the enclosure does not exceed 40 °C.
CAUTION
Crush Hazard
Do not carry the drive by the front cover.
Failure to comply may result in minor or moderate injury from the main body of the drive
falling.
an enclosed panel or cabinet.
30
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
2.1 Section Safety
NOTICE
Observe proper electrostatic discharge (ESD) procedures when handling the drive.
Failure to comply could result in ESD damage to the drive circuitry.
It may be difficult to perform maintenance on the cooling fans of drives installed in a
vertical row inside an enclosure.
Ensure adequate spacing at the top of the drive to perform cooling fan replacement when
required.
Operating the motor in the low-speed range diminishes the cooling effects, increases
motor temperature, and may lead to motor damage by overheating.
Reduce the motor torque in the low-speed range whenever using a standard blower cooled
motor. If 100% torque is required continuously at
or vector motor. Select a motor that is compatible with the required load torque and operating
speed range.
Do not operate motors above the maximum rated RPM.
Failure to comply may lead to bearing or other mechanical motor failures.
The speed range for continuous operation differs according to the lubrication method
and motor manufacturer.
If the motor is to be operated at a speed higher than the rated speed, consult with the
manufacturer.
Continuously operating an oil-lubricated motor in the low-speed range may result in burning.
low speed, consider using a special drive
Mechanical Installation
2
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
31
2.1 Section Safety
NOTICE
When the input voltage is 440 V or higher or the wiring distance is greater than 100
meters, pay special attention to the motor insulation
Failure to comply could lead to motor winding failure.
Motor vibration may increase when operating a machine in variable-speed mode, if
that machine previously operated at a constant speed.
Install vibration-proof rubber on the motor base or use the frequency jump function to skip
a frequency resonating the machine.
The motor may require more acceleration torque with drive operation than with a
commercial power supply.
Set a proper V/f pattern by checking the load torque characteristics of the machine to be
used with the motor.
The rated input current of submersible motors is higher than the rated input current
of standard motors.
Select an appropriate drive according to its rated output current. When the distance between
the motor and drive is long, use a cable thick enough to connect the motor to the drive to
prevent motor torque reduction.
When using an explosion-proof motor, it must be subject to an explosion-proof test in
conjunction with the drive.
This is also applicable when an existing explosion-proof motor is to be operated with the
drive. Since the drive itself is not explosion-proof, always install it in a safe place.
Do not use a drive for a single-phase motor.
Replace the motor with a three-phase motor.
If an oil-lubricated gearbox or speed reducer is used in the power transmission
mechanism, oil lubrication will be affected when the motor operates only in the low
speed range.
The power transmission mechanism will make noise and experience problems with service
life and durability if the motor is operated at a speed higher than the rated speed.
voltage or use a drive-rated motor.
32
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
2.2 Mechanical Installation
2.2Mechanical Installation
This section outlines specifications, procedures, and environment for proper mechanical
installation of the drive.
u
Installation Environment
To help prolong the optimum performance life of the drive, install the drive in the proper
environment. The table below provides a description of the appropriate environment for the
drive.
Table 2.1 Installation Environment
EnvironmentConditions
Installation AreaIndoors
Ambient
Temperature
Humidity95% RH or less and free of condensation
Storage Temperature -20 °C to +60 °C
Surrounding Area
Altitude1000 m or lower
Vibration
OrientationInstall the drive vertically to maintain maximum cooling effects.
NOTICE: Prevent foreign matter such as metal shavings or wire clippings from falling into the drive during
installation and project construction. Failure to comply could
cover over the top of the drive during installation. Remove the temporary cover before startup, as the cover
will reduce ventilation and cause the drive to overheat.
-10 °C to +50 °C (IP20/Open-Chassis)
Drive reliability improves in environments without wide temperature fluctuations.
When using an enclosure panel, install a cooling
the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the drive.
Install the drive in an area free from:
• oil mist and dust
• metal shavings, oil, water or other foreign materials
• radioactive materials
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
•
direct sunlight
10 to 20 Hz at 9.8 m/s
20 to 55 Hz at 5.9 m/s
2
2
fan or air conditioner in the area to ensure that
result in damage to the drive. Place a temporary
Mechanical Installation
2
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
33
2.2 Mechanical Installation
u
Installation Orientation and Spacing
Install the drive upright as illustrated in Figure 2.1 to maintain proper cooling.
A
A – CorrectB – Incorrect
Figure 2.1 Correct Installation Orientation
Single Drive Installation
n
B
B
Figure 2.2 explains the required installation spacing to maintain sufficient space for airflow
and wiring. Install the heatsink against a closed
surface to avoid diverting cooling air around
the heatsink.
Side Clearance
A
A
Top/Bottom Clearance
C
B
A – 30 mm minimum
B – Airflow direction
34
C
C – 100 mm minimum
Figure 2.2 Correct Installation Spacing
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
2.2 Mechanical Installation
Multiple Drive Installation
n
When
installing
Figure 2.2. When mounting drives with a minimum side-by-side clearance of 2 mm according
to Figure 2.3, derating must be considered and parameter L8-35 must be set. Refer to
Parameter List on page 197.
multiple
drives
into
the
same
enclosure
panel, mount the drives according to
A
B
2 mm
B
C
D
C
A – Line up the tops of the drives.
B – 30 mm minimum
Figure 2.3 Space Between Drives (Side-by-Side Mounting)
Note: When installing drives of different sizes into the same enclosure panel, the tops of the drives should line
up. Leave space between the top and bottom
this method, it is possible to replace the cooling fans later.
u
Removing and Attaching the Protective Covers
Refer to Electrical Installation on page 39, for information regarding the removal and
reattachment of protective covers.
u
Exterior and Mounting Dimensions
The following table matches each drive model with its appropriate drawing.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
C – 100 mm minimum
D – Airflow direction
of stacked drives for cooling fan replacement if required. Using
Mechanical Installation
2
35
2.2 Mechanical Installation
Table 2.2 Drive Models
Protective Design
IP20/Open-Chassis
Note: Refer to Specifications on page 187 for information on the amount of heat generated by the drive and
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation
& Start-Up Manual
39
3.1 Section Safety
3.1Section Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may show drives without covers or safety shields to show
details. Be sure to reinstall covers or shields before operating the drives and run the drives
according to the instructions described in this manual.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the
motor case.
Do not perform work on the drive while
protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye
protection before beginning work on the drive.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed only by authorized
personnel familiar with installation, adjustment, and maintenance of AC drives.
wearing loose clothing, jewelry or without eye
40
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3.1 Section Safety
WARNING
Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The internal capacitor
remains charged even after the power supply is turned off. The charge indicator LED will
extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at
least one minute after all indicators are off
safe level.
and measure the DC bus voltage level to confirm
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or serious injury by fire due to overheating
of electrical connections.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply
before applying power.
Electrical Installation
3
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
41
3.1 Section Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and
circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting
voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded, twisted-pair wires and ground the shield to the ground terminal of the drive.
Check all the wiring to ensure that all
and connecting any other devices.
Failure to comply could result in damage to the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This
product must not be modified.
connections are correct after installing the drive
42
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3.2 Standard Connection Diagram
3.2Standard Connection Diagram
Connect the drive and peripheral devices as shown
via the digital operator without connecting digital I/O wiring. This section does not discuss
drive operation; Refer to Start-Up Programming & Operation on page 69 for instructions
on operating the drive.
NOTICE: Inadequate branch short circuit protection could result in damage to the drive. Install adequate
branch circuit short circuit protection per applicable codes. The drive is suitable for circuits capable of
delivering not more than 30,000 RMS symmetrical amperes, 240 Vac maximum (200 V Class) and 480 Vac
maximum (400 V Class).
NOTICE: When the input voltage is 440 V or higher or the wiring distance is greater than 100 meters, pay
special attention to the motor insulation voltage or use an inverter duty motor. Failure to comply could lead
to motor insulation breakdown.
NOTICE: Do not connect the AC control circuit ground to the drive enclosure. Improper drive grounding can
cause the control circuit to malfunction.
NOTICE: The minimum load for the multi-function relay output MA-MB-MC is 10 mA.
in Figure 3.1. It is possible to run the drive
Electrical Installation
3
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
43
3.2 Standard Connection Diagram
Terminals +1, +2, , B1, and B2
are for connecting options.
Never connect power supply
lines to these terminals.
For single phase 200 V
power supply, use
R/L1 and S/L2.
R/L1
Three phase
power supply
S/L2
200 to 240 V
T/L3
THRX
2 MCCB
OFF
Thermal relay for
motor cooling fan
MC
MC MA
Main speed
frequency
reference.
Multi-function
programmable
1 MCCB
MC
ON
SA
MC
THRX
SA
TRX
SA
TRX
Fault relay
_
2 MCCB
MC
Forward run/stop
Reverse run/stop
External fault
Fault reset
Multi-step
speed 1
main/aux switch
Digital inputs
(default setting)
2 k
<4>
<3>
r1
s1
t1
DC reactor
(option)
<1>
Jumper
R/L1
Main circuit
S/L2
T/L3
Control circuit
S1
S2
S3
S4
S5
<5>
DIP
switch S3
SC
Shield ground
terminal
Setting power supply
+V
+10.5 max. 20 mA
A1
0 to +10 V (20 k )
(0)4 to 20 mA (250 )
AC
shielded line
main circuit terminal
Thermal relay
(option)
-
J1000
+
24V 8mA
Sink
Source
twisted-pair shielded line
control terminal
<2>
B1+1+2B2
Option unit
connector
DIP switch S1
IV
24 V
Braking resistor
(option)
U/T1
V/T2
W/T3
Ground
10
100
Fault
MA
MB
MC
AM
AC
Motor
Cooling fan
FU
r1
FV
s1
M
FW
t1
U
V
M
W
or less (400 V class)
or less (200 V class)
Digital output
250 Vac, 10 mA to 1 A
30 Vdc, 10 mA to 1 A
(default setting)
<6>
Analog monitor
output
+
AM
0 to +10 Vdc
(2 mA)
-
<7>
Monitor
output
Figure 3.1 Drive Standard Connection Diagram (200 V Class Example)
<1>Remove the jumper when installing an optional DC reactor.
<2>The MC on the input side of the main circuit should open when the thermal relay is
triggered.
<3>Self-cooled motors do not require separate cooling fan motor wiring.
<4>Connected using sequence input
signal (S1 to S5) from NPN transistor; Default: sink
mode (0 V com).
<5>Use only a +24 V internal power supply in sinking mode; the source mode requires
an external power supply Refer to I/O Connections on page 60.
<6>Minimum load: 5 Vdc, 10 mA (reference value).
44
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3.2 Standard Connection Diagram
<7>Monitor outputs work with devices such as analog frequency meters, ammeters,
voltmeters and wattmeters; they are not intended for
use as a feedback-type of signal.
WARNING! Sudden Movement Hazard. Do not close the wiring
input terminal parameter is properly set (S5 for 3-Wire; H1-05 = “0”). Improper sequencing of run/stop circuitry
could result in death or serious injury from moving equipment.
WARNING! Sudden Movement Hazard. Ensure start/stop and safety circuits are wired properly and in the
correct state before energizing the drive. Failure to comply could result in death or serious injury from moving
equipment. When programmed for 3-Wire control, a momentary closure on terminal S1 may cause the drive
to start.
WARNING! When 3-Wire sequence is used, set the drive to 3-Wire sequence before wiring the control
terminals and ensure parameter b1-17 is set to 0 (drive does not accept a run command at power up (default).
If the drive is wired for 3-Wire sequence but set up for 2-Wire sequence (default) and if parameter b1-17 is
set to 1 (drive accepts a Run command at power up), the motor will rotate in reverse direction at power up of
the drive and may cause injury.
for the control circuit unless the multifunction
Figure 3.2 illustrates an example of a 3-Wire sequence.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
45
3.3 Main Circuit Connection Diagram
3.3Main Circuit Connection Diagram
Refer to diagrams in this section for the Main Circuit wiring connections. Connections may
vary based on drive capacity. The main circuit DC power supply powers the control circuit.
NOTICE: Do not use the negative DC bus terminal “-” as a ground terminal. This terminal is at high voltage
DC potential. Improper wiring connections could result in damage to the drive.
u
Single-Phase 200 V Class (CIMR-JoBA0001 ~ 0010)
DC reactor
Jumper
Single-phase
200 Vac
(option)
+2
R/L1
S/L2
–
+1
Figure 3.3 Connecting Single-Phase Main Circuit Terminals
NOTICE: Do not connect T/L3 terminal when using single-phase power supply input. Incorrect wiring may
damage the drive.
u
Three-Phase 200 V Class (CIMR-Jo2A0001 ~ 0020);
Three-Phase 400 V Class (CIMR-Jo4A0001 ~ 0011)
DC reactor
Jumper
(option)
B1 B2
Drive
Braking Resistor
Unit (option)
U/T1
V/T2
W/T3
Braking
Resistor Unit
(option)
Motor
+1
Three phase 200 Vac
(400 Vac)
+2
R/L1
S/L2
T/L3
—
Drive
B1 B2
U/T1
V/T2
W/T3
Motor
Figure 3.4 Connecting Three-Phase Main Circuit Terminals
46
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3.4 Terminal Block Configuration
3.4Terminal Block Configuration
The figures in this section provide illustrations of the main circuit terminal block
configurations of the different drive sizes.
Figure 3.5 Main Circuit Terminal Block Configurations
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
47
3.5 Protective Covers
3.5Protective Covers
Follow the procedure below to remove the protective covers before wiring the drive and to
reattach the covers after wiring is complete.
u
IP20/Open-Chassis Cover Removal and Installation
Removing the Protective Covers
n
1.
Loosen the screw that locks the front cover in place to remove.
Figure 3.6 Remove the Front Cover on an IP20/Open-Chassis Drive
2.
pressure to the tabs on each side
Apply
away from the drive while pushing in on the tabs to pull the cover free.
of the terminal cover. Pull the terminal cover
Figure 3.7 Remove the Terminal Cover on an IP20/Open-Chassis Drive
48
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3.5 Protective Covers
Reattaching the Protective Covers
n
Properly
all protective covers when wiring is complete. Apply only a small amount of pressure to lock
the cover back into place.
all
connect
Figure 3.8 Reattach the Protective Covers on an IP20/Open-Chassis Drive
wiring
and
route
power
away from control signal wiring. Reattach
wiring
Electrical Installation
3
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
49
3.6 Main Circuit Wiring
3.6Main Circuit Wiring
This section describes the functions, specifications, and procedures required to safely and
properly wire the main circuit of the drive.
NOTICE: Do not solder the ends of wire connections to the drive. Soldered wiring connections can loosen
over time. Improper wiring practices could result in drive malfunction due to loose terminal connections.
u
Main Circuit Terminal Functions
Table 3.1 Main Circuit Terminal Functions
TerminalTypeFunctionReference
R/L1
T/L3
U/T1
W/T3
B1
B2
+1
+2
+1
–
(2 terminals)
Main circuit power
supply input
Drive outputConnects to the motor.52V/T2
Braking resistor
DC reactor
connection
DC power supply
input
Ground
Connects line power to the drive.
Drives with single-phase 200 V input power use
S/L2 only (T/L3 must not be used).
Available for connecting a braking resistor or the braking resistor
unit option.
These terminals are shorted at shipment. Remove the shorting bar
between +1 and +2 when connecting to this terminal.
For connecting a DC power supply.–
Grounding Terminal
For 200 V class: 100 Ω or less
For 400 V class: 10 Ω or less
terminals R/L1 and
46S/L2
65
173
52
u
Wire Gauges and Tightening Torque
Select the appropriate wires and crimp terminals from Table 3.2 through Table 3.4.
Note: 1. Wire gauge recommendations based on drive continuous current ratings using 75 °C 600 Vac vinyl-
sheathed wire assuming ambient temperature within 30 °C and wiring distance less than 100 m.
2. Terminals +1, +2, –, B1 and B2 are for connecting optional devices such as a DC reactor or braking
resistor. Do not connect other non-specified devices to these terminals.
• Consider the amount of voltage drop when selecting wire gauges. Increase the wire gauge
when the voltage drop is greater than 2% of motor rated voltage. Ensure the wire gauge is
suitable for the terminal block. Use the following formula to calculate the amount of voltage
drop:
• Line drop voltage (V) = 3 x wire resistance (Ω/km) x wire length (m) x current (A) x
-3
10
• Refer to instruction manual TOBPC72060000 for braking unit
or braking resistor unit wire
gauges.
• Refer to UL Standards Compliance on page 236 for information on UL compliance.
50
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Main Circuit Terminal Power Supply and Motor Wiring
Terminal
Screw
This section outlines the various steps, precautions, and
Size
M4
M4
Tightening
Torque
N•m (lb.in.)
1.2 to 1.5
(10.6 to 13.3)
1.2 to 1.5
(10.6 to 13.3)
checkpoints for wiring the main circuit
Applicable
Gauge
mm2 (AWG)
2.0 to 5.5
(14 to 10)
2.0 to 5.5
(14 to 10)
Recommended
Gauge
mm2 (AWG)
2
(14)
3.5
(12)
terminals and motor terminals.
NOTICE: When connecting the motor to the drive output terminals U/T1, V/T2, and W/T3, the phase order
for the drive and motor should match. Failure to comply with proper wiring practices may cause the motor to
run in reverse if the phase order is backward.
NOTICE: Do not connect phase-advancing capacitors or LC/RC noise filters to the output circuits. Improper
application of noise filters could result in damage to the drive.
NOTICE: Do not connect the AC power line to the output motor terminals of the drive. Failure to comply could
result in death or serious injury by fire as a result of drive damage from line voltage application to output
terminals.
Cable Length Between Drive and Motor
n
When the cable length between the drive and the motor is too long (especially at low frequency
output), note that the cable voltage drop may cause reduced motor torque. Drive output current
will increase as the leakage current from the cable increases. An increase in leakage current
may trigger an overcurrent situation and weaken the accuracy of the current detection.
Adjust the drive carrier frequency according to the following table. If the motor wiring distance
exceeds 100 m because of the system configuration, reduce the ground currents.
Refer to Table 3.5 to set the carrier frequency to an appropriate level.
Table 3.5 Cable Length Between Drive and Motor
Cable Length50 m or less100 m or lessGreater than 100 m
Carrier Frequency15 kHz or less5 kHz or less2 kHz or less
Note: When setting carrier frequency, calculate the cable length as the total distance of wiring to all connected
motors when running multiple motors from a single drive.
Ground Wiring
n
Follow the precautions to wire the ground for one drive or a series of drives.
WARNING! Electrical Shock Hazard. Always use a ground wire that complies with technical standards on
electrical equipment and minimize the length of the ground wire. Improper equipment grounding may cause
dangerous electrical potentials on equipment chassis, which could result in death or serious injury.
WARNING! Electrical Shock Hazard. Be sure to ground the drive ground terminal. (200 V Class: Ground to
100 Ω or less, 400 V Class: Ground to
serious injury by contacting ungrounded electrical equipment.
52
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
10 Ω or less). Improper equipment grounding could result in death or
3.6 Main Circuit Wiring
NOTICE: Do not share the ground wire with other
equipment. Improper equipment grounding could result in drive or equipment malfunction due to electrical
interference.
NOTICE: When using more than one drive, ground multiple drives according to instructions. Improper
equipment grounding could result in abnormal operation of drive or equipment.
devices such as welding machines or large-current electrical
Refer to Figure 3.9 when using multiple drives. Do not loop the ground wire.
A
A – CorrectB – Incorrect
Figure 3.9 Multiple Drive Wiring
Wiring the Main Circuit Terminal
n
WARNING! Electrical Shock Hazard. Shut off the power supply to the drive before wiring the main circuit
terminals. Failure to comply may result in death or serious injury.
Note: A cover placed over the DC Bus and braking circuit terminals prior to shipment helps prevent miswiring.
Cut away covers as needed for terminals with a needle-nose pliers.
B
A
A –Protective Cover to Prevent Miswiring
Electrical Installation
3
Main Circuit Connection Diagram
Refer to section 3.3 Main Circuit Connection Diagram on page 46 for drive main power
circuit connections.
WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect braking
resistors to any other terminals. Improper wiring connections could cause the braking resistor to overheat
and cause death or serious injury by fire. Failure to comply may result in damage to the braking circuit or
drive.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
53
3.7 Control Circuit Wiring
3.7Control Circuit Wiring
NOTICE: Do not solder the ends of wire connections
time. Improper wiring practices could result in drive malfunction due to loose terminal connections.
to the drive. Soldered wire connections can loosen over
Main speed
frequency
reference.
Multi-function
programmable
Forward run/stop
Reverse run/stop
External fault
Fault reset
Multi-step
speed 1
main/aux switch
Digital inputs
(default setting)
2 k
<1>
S1
S2
S3
S4
S5
<2>
DIP
switch S3
SC
Shield ground
terminal
Setting power supply
+V
+10.5 max. 20 mA
A1
0 to +10 V (20 k )
(0)4 to 20 mA (250 )
AC
shielded line
main circuit terminal
J1000
Control circuit
+
24V 8mA
Sink
Source
twisted-pair shielded line
control terminal
Option unit
connector
DIP switch S1
IV
MA
MB
MC
24 V
AM
AC
Digital output
250 Vac, 10 mA to 1 A
30 Vdc, 10 mA to 1 A
(default setting)
<3>
Analog monitor
output
+
AM
0 to +10 Vdc
(2 mA)
-
Monitor
output
Figure 3.10 Control Circuit Connection Diagram
<1> Connected using sequence input signal (S1 to S5) from NPN transistor; Default: sink
mode (0 V com)
Use only the +24 V internal power
<2>
supply in sinking mode; the source mode requires an
external power supply. Refer to I/O Connections on page 60.
<3> Minimum load: 5 Vdc, 10 mA (reference value).
54
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3.7 Control Circuit Wiring
u
Control Circuit Terminal Block Functions
Drive parameters determine which functions apply to the multi-function digital inputs (S1 to
S5), and multi-function digital outputs (MA, MB). The default is called out next to each
terminal in Figure 3.10.
WARNING! Sudden Movement Hazard. Always check the operation and wiring of control circuits after being
wired. Operating a drive with untested control circuits could result in death or serious injury.
WARNING! Confirm the drive I/O signals and external sequence before starting test run. Failure to comply
may result in death or serious injury.
NOTICE: Do not switch an input contactor more often than once every 30 minutes. Improper equipment
sequencing could shorten useful life of the drive electrolytic capacitors and circuit relays. Normally the drive
I/O should be used to stop and start the motor.
Input Terminals
n
Table 3.6 Control Circuit Input Terminals
TypeNo.Terminal Name (Function)Function (Signal Level) Default Setting
+V Analog input power supply+10.5 Vdc (max allowable current 20 mA)
AC Frequency reference common0 Vdc
24 Vdc, 8 mA
Note: Drive preset to sinking mode. When using
source mode, set DIP switch S3 to allow
(±10%) external power supply. Refer to Sinking/
Sourcing Mode Switch on page 60.
Sequence common
Input voltage or input current (Selected by DIP switch
S1 and H3-01) 0 to +10 Vdc (20 kΩ),
Resolution: 1/1000
4 to 20 mA (250 Ω) or 0 to 20 mA (250 Ω),
Resolution: 1/500
for a 24 Vdc
Electrical Installation
3
Output Terminals
n
Table 3.7 Control Circuit Output Terminals
TypeNo.Terminal Name (Function)Function (Signal Level) Default Setting
Multi-Function
Digital Output
Monitor Output
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
MA N.O. (fault)
MB N.C. output (fault)
MC Digital output common
AM Analog monitor output0 to 10 Vdc (2 mA or less) Resolution: 1/256
AC Monitor common0 V
Digital output
30 Vdc, 10 mA to 1 A; 250 Vac, 10 mA to 1 A
Minimum load: 5 Vdc, 10 mA (reference value)
55
3.7 Control Circuit Wiring
u
Terminal Configuration
MCMBMA
Figure 3.11 Control Circuit Terminal
Wire Size and Torque Specifications
n
S1 S2 S3 S4 S5 SC A1 +V AC AM AC
Select appropriate wire type and size from Table 3.8. For simpler and more reliable wiring,
crimp ferrules to the wire ends. Refer to Table 3.9 for ferrule terminal types and sizes.
Table 3.8 Wire Size and Torque Specifications (Same for All Models)
Scre
Terminal
MA, MB,
MC
S1-S5, SC,
+V, A1, AC,AMM2 0.22 to 0.25 1.9 to 2.2
Tightening
w
Torque
Size
M30.5 to 0.64.4 to 5.3
N•m
Tightening
Torque
(in-lbs)
Bare Wire TerminalFerrule-Type Terminal
Applicable
wire size
mm2 (AWG)
Stranded: 0.25
to 1.5
(24 to 16)
Single: 0.25 to
1.5
(24 to 16)
Stranded: 0.25
to 1.0
(24 to 18)
Single: 0.25 to
1.5
(24 to 16)
Recomm.
(AWG)
0.75 (18)
0.75 (18)
mm
2
Applicable
wire size
2
mm
(AWG)
0.25 to 1.0
(24 to 18)
0.25 to 0.5
(24 to 20)
Recomm.
mm
(AWG)
0.5 (20)
0.5 (20)
2
Wire
Type
Shielded
line, etc.
56
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3.7 Control Circuit Wiring
Ferrule-Type Wire Terminations
n
Crimp a ferrule
to
signal
wiring
to
improve
wiring simplicity and reliability. Use CRIMPFOX
ZA-3, a crimping tool manufactured by PHOENIX CONTACT.
fd1
6 mm
L
fd2
Figure 3.12 Ferrule Dimensions
Table 3.9 Ferrule Terminal Types and Sizes
Size mm2 (AWG)
0.25 (24)AI 0.25-6YE10.50.82.0
0.34 (22)AI 0.34-6TQ10.50.82.0
0.5 (20)AI 0.5-6WH121.12.5
0.75 (18)AI 0.75-6GY121.32.8
1.0AI 1-6RD121.53.0
u
Wiring Procedure
section
This
WARNING! Electrical Shock Hazard. Do not remove covers or touch the circuit boards while the power is on.
Failure to comply could result in death or serious injury.
NOTICE: Separate control circuit wiring from main circuit wiring (terminals R/L1, S/L2, T/L3, B1, B2, U/T1,
V/T2, W/T3, -, +1, +2) and other high-power lines. Improper wiring practices could result in drive malfunction
due to electrical interference.
NOTICE: Separate wiring for digital output terminals MA, MB and MC from wiring to other control circuit lines.
Improper wiring practices could result in drive or equipment malfunction or nuisance trips.
NOTICE: Use a class 2 power supply (UL standard) when connecting to the control terminals. Improper
application of peripheral devices could result in drive performance degradation due to improper power supply.
NOTICE: Insulate shields with tape or shrink tubing to prevent contact with other signal lines and equipment.
Improper wiring practices could result in drive or equipment malfunction due to short circuit.
NOTICE: Connect the shield of shielded cable to the appropriate ground terminal. Improper equipment
grounding could result in drive or equipment malfunction or nuisance trips.
describes
TypeL (mm)d1 (mm)d2 (mm)Manufacturer
PHOENIX CONTACT
the
proper
procedures
preparations
and
for wiring the control terminals.
Wire the control terminals using Figure 3.13 as a guide. Prepare the ends of the control circuit
wiring as shown in Figure 3.14. Refer to Wire Size and Torque Specifications on page 56.
Electrical Installation
3
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
57
3.7 Control Circuit Wiring
NOTICE: Do not tighten screws beyond the specified tightening torque. Failure to comply may damage the
terminal.
NOTICE: Use shielded twisted-pair cables as indicated to prevent
could result in drive or equipment malfunction due to electrical interference.
operating faults. Improper wiring practices
Connect control wires as shown in the following figure:
D
A
S1 S2 S3 S4 S5 SC A1 +V AC AM AC
C
A – Control terminal block
B – Avoid fraying wire strands when
stripping insulation from wire. Strip
length 5.5 mm.
C – Single wire or stranded wire
Figure 3.13 Terminal Board Wiring Guide
A
B
A – Drive side
B – Connect shield to ground terminal of
drive.
C – Insulation
Figure 3.14 Preparing the Ends of Shielded Cables
Preparing wire
E
terminal ends
B
D – Loosen screw to insert wire.
E – Blade depth of 0.4 mm or less
Blade width of 2.5 mm or less
F
C
E
D – Control device side
E – Shield sheath (Insulate with tape)
F – Shield
D
58
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3.7 Control Circuit Wiring
When setting the frequency by analog reference from an external potentiometer, use shielded
twisted-pair wires and ground the shield of twisted-pair wires to the ground terminal of the
drive.
NOTICE: The analog signal lines between the drive and
not exceed 50 meters when using an analog signal from a remote source to supply the frequency reference.
Failure to comply could result in poor system performance.
the operator station or peripheral equipment should
A
B
+V
A1
AC
A – Drive
B – Ground terminal (shield connection)
Figure 3.15 Wiring the Frequency Reference to the Control Circuit Terminals (External
Reference)
C
D
C – (+V) Frequency setting power source
+10.5 Vdc maximum 20 mA
D – (A1) Main speed frequency reference 0
to +10 Vdc (20 kΩ)
or
4 to 20 mA (250 Ω)/
0 to 20 mA (250 Ω)
Electrical Installation
3
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
59
3.8 I/O Connections
3.8I/O Connections
u
Sinking/Sourcing Mode Switch
Set the DIP switch S3 on the front of the drive to switch the digital input terminal logic between
sinking mode and sourcing mode; the drive is preset to sinking mode.
Table 3.10 Sinking/Sourcing Mode Setting
Set ValueDetails
SINKSinking Mode (0 V common): default setting
SOURCESourcing Mode (+24 V common)
DIP Switch S3
SOURCE
Figure 3.16 DIP Switch S3
60
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
SINK
3.8 I/O Connections
Transistor Input Signal Using 0 V Common/Sink Mode
n
When controlling the digital inputs by NPN transistors (0 V common/sinking mode), set the
DIP switch S3 to SINK and use the internal 24 V power supply.
Shielded Cable
SOURCE
SINK
Figure 3.17 Sinking Mode: Sequence from NPN Transistor (0 V Common)
FWD Run/Stop
REV Run/Stop
External Fault N.O.
Fault Reset
Multi-step Speed 1
Multi-funciton input
S1
S2
S3
S4
S5
SC
S3
SINK
SOURCE
+24 V
Electrical Installation
3
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
61
3.8 I/O Connections
Transistor Input Signal Using +24 V Common/Source Mode
n
When controlling digital inputs by PNP transistors (+24 V common/sourcing mode), set the
DIP switch S3 to SOURCE and use an external 24 V power supply.
Shielded cable
SOURCE
SINK
External
power supply
+24V
FWD Run/Stop
REV Run/Stop
External Fault N.O.
Fault reset
Multi-step speed 1
S1
S2
S3
S4
S5
SC
SINK
S3
SOURCE
Figure 3.18 Source Mode: Sequence from PNP Transistor (+24 V Common)
+24V
62
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3.9 Main Frequency Reference
3.9Main Frequency Reference
u
DIP Switch S1 Analog Input Signal Selection
The main frequency reference can either be a voltage or current signal input.
To use current input at terminal A1, set the DIP switch S1 to "I" (default setting) and set
parameter H3-01 = “2” or “3” (4-20 mA or 0-20 mA).
When using as a voltage input, set DIP switch S1 to “V” (right position) and program
parameter H3-01 to “0” (0 to +10 Vdc with lower limit) or “1” (0 to +10 Vdc without lower
limit).
Table 3.11 Frequency Reference Configurations
Voltage InputCurrent Input
Drive
+10.5 V
+V
20 mA current
Main speed
A1
frequency reference
(current input)
AC
Frequency
reference
common
0 to 10 V
Drive
+10.5 V
+V
20 mA current
Main speed frequency
A1
reference (voltage input)
Frequency reference
AC
common
4 to 20 mA input
or
0 to 20 mA input
Electrical Installation
DIP Switch S1
IV
Figure 3.19 DIP Switch S1
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3
63
3.9 Main Frequency Reference
Table 3.12 DIP Switch S1 Settings
Setting ValueDescription
V (right position)Voltage input (0 to 10 V): default setting
I (left position)Current input (4 to 20 mA or 0 to 20 mA)
Table 3.13 Parameter H3-01 Details
No.Parameter NameDescription
Selects the signal level for terminal A1.
Frequency ref.
(voltage/current)
H3-01
terminal A1 signal
level selection
0: 0 to +10 V, unipolar input (negative
frequency reference values are zeroed)
1: 0 to +10 V, bipolar input (negative
frequency reference changes the direction)
2: 4 to 20 mA
3: 0 to 20 mA
Setting
Range
0 to 30410H
Default
Setting
MEMOBUS
Register
64
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3.10 Braking Resistor
3.10Braking Resistor
Dynamic braking (DB) helps bring the motor to
high inertia loads. As the drive lowers the frequency of a motor with high inertia connected,
regeneration occurs. This can cause an overvoltage situation when the regenerative energy
flows back into the DC bus capacitors. A braking resistor prevents these overvoltage faults.
NOTICE: Do not allow unqualified personnel to use the product. Failure to comply could result in damage to
the drive or braking circuit. Carefully review the braking resistor instruction manual when connecting a braking
option to the drive.
Note: The braking circuit must be sized properly in order to dissipate the power required to decelerate the load in
the desired time. Ensure that the braking circuit can dissipate the energy for the set deceleration time prior
to running the drive.
NOTICE: Use a thermal overload relay or an over-temperature contact to interrupt input power to the drive
in the event the braking resistor overheats. In the event of a possible thermal overload, the relay will trigger
the input contactor and prevent the braking resistor from burning up.
u
Installation
WARNING! Fire Hazard. The braking resistor connection terminals are B1 and B2. Do not connect a braking
resistor directly to any other terminals. Improper wiring connections could result in death or serious injury by
fire. Failure to comply may result in damage to the braking circuit or drive.
NOTICE: Connect braking resistors to the drive as shown in the I/O wiring examples. Improperly wiring braking
circuits could result in damage to the drive or equipment.
a smooth and rapid stop when working with
Installation Procedure
n
1.
Disconnect all electrical power to the drive and wait at least one minute before
servicing the drive and any connected components.
2.
Remove drive front cover.
3.
Use a voltmeter to verify that voltage is disconnected from incoming power terminals
and that the DC bus no longer holds a charge.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Electrical Installation
3
65
3.10 Braking Resistor
Power
supply
Thermal relay switch for
external braking resistor
MC
4.
Follow manufacturer instructions to connect the resistor unit to the drive using proper
wire gauge according to local electrical codes.
Power leads for the remote mount resistors generate high levels of electrical noise;
group these signal leads separately.
5.
Mount the resistor unit on a noncombustible surface. Maintain minimum side and top
clearances according to resistor manufacturer instructions.
WARNING! Fire Hazard. Do not use improper combustible materials. Failure to comply could
result in death or serious injury by fire. Attach the drive or braking resistors to metal or other
noncombustible material.
6.
Reinstall drive covers and resistor covers, if provided.
7.
Set parameter L3-04 = “0” to disable stall prevention during deceleration.
Set parameter L8-01 to “1” to enable overheat protection when using Yaskawa
heatsink-mounted braking resistor.
Set L8-01 = “0” for other braking resistor types.
L3-04: Stall Prevention During Deceleration0: Stall prevention disabled.
8.
Operate the system and verify the required deceleration rate is obtained during
dynamic braking or stopping.
Thermal
OFFTHRX
MA MC
MCCB
MCON
SA
MC
THRX
SA
TRX
SA
TRX
Fault contact
relay
MC
B1B2
R/L1
S/L2
T/L3
Drive
Braking resistor
U/T1
V/T2
W/T3
Figure 3.20 Connecting a Braking Resistor
Table 3.14 Braking Resistor Settings
ParameterSettings
0: Disabled. The drive will not provide overheat
protection. Supply separate means of overheat
protection.
1: Enabled. Braking Resistor is protected from
overheat.
Motor
66
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
3.11 Interlocking with Connected Machinery
3.11Interlocking with Connected Machinery
For safety reasons, applications that may be affected
be set up so that operation can only occur when the drive is ready to operate. A "Drive ready"
and "Fault" signal should be assigned to the multi-function outputs to guarantee interlock with
application.
u
Drive Ready Signal
The "Drive ready" signal is output to one of the multi-function terminals after the drive has
booted up and there is no fault present. It indicates that the drive is ready for operation.
• The power is off.
• A fault situation is present.
• There is a problem with the drive internal power supply.
• Parameter settings restrict a Run command from being entered.
• An overvoltage or undervoltage situation is present so that when the Run command is given
a fault is immediately triggered.
• The drive is in the programming mode and parameter settings restrict a Run command from
being entered in the programming mode.
by the operation status of the drive should
Electrical Installation
3
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
67
3.11 Interlocking with Connected Machinery
This Page Intentionally Blank
68
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
4
Start-Up
Programming &
Operation
This chapter explains the functions of the LED operator and how
to program the drive for initial operation.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation
& Start-Up Manual
69
4.1 Section Safety
4.1Section Safety
DANGER
Electrical Shock Hazard
Do not connect or disconnect wiring while the power is on.
Failure to comply will result in death or serious injury.
WARNING
Electrical Shock Hazard
Do not operate equipment with covers removed.
Failure to comply could result in death or serious injury.
The diagrams in this section may include drives
details. Be sure to reinstall covers or shields before operating the drives and run the drives
according to the instructions described in this manual.
Always ground the motor-side grounding terminal.
Improper equipment grounding could result in death or serious injury by contacting the
motor case.
Do not touch any terminals before the capacitors have fully discharged.
Failure to comply could result in death or serious injury.
Before wiring terminals, disconnect all power to the equipment. The internal capacitor
remains charged even after the power supply is turned off. The charge indicator LED will
extinguish when the DC bus voltage is below 50 Vdc. To prevent electric shock, wait at
least one minute after all indicators are off and measure the DC bus voltage level to confirm
safe level.
Do not allow unqualified personnel to perform work on the drive.
Failure to comply could result in death or serious injury.
Installation, maintenance, inspection, and servicing must be performed only by authorized
personnel familiar with installation, adjustment and maintenance of AC drives.
without covers or safety shields to illustrate
70
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
4.1 Section Safety
WARNING
Do not perform work on the drive while wearing loose clothing, jewelry or without eye
protection.
Failure to comply could result in death or serious injury.
Remove all metal objects such as watches and rings, secure loose clothing, and wear eye
protection before beginning work on the drive.
Do not remove covers or touch circuit boards while the power is on.
Failure to comply could result in death or serious injury.
Fire Hazard
Tighten all terminal screws to the specified tightening torque.
Loose electrical connections could result in death or
of electrical connections.
Do not use an improper voltage source.
Failure to comply could result in death or serious injury by fire.
Verify that the rated voltage of the drive matches the voltage of the incoming power supply
before applying power.
Do not use improper combustible materials.
Failure to comply could result in death or serious injury by fire.
Attach the drive to metal or other noncombustible material.
serious injury by fire due to overheating
Start-Up Programming
& Operation
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
4
71
4.1 Section Safety
NOTICE
Observe proper electrostatic discharge procedures (ESD) when handling the drive and
circuit boards.
Failure to comply may result in ESD damage to the drive circuitry.
Never connect or disconnect the motor from the drive while the drive is outputting
voltage.
Improper equipment sequencing could result in damage to the drive.
Do not use unshielded cable for control wiring.
Failure to comply may cause electrical interference resulting in poor system performance.
Use shielded twisted-pair wires and ground the shield to the ground terminal of the drive.
Do not allow unqualified personnel to use the product.
Failure to comply could result in damage to the drive or braking circuit.
Carefully review instruction manual TOBPC72060000 when connecting a braking option
to the drive.
Do not modify the drive circuitry.
Failure to comply could result in damage to the drive and will void warranty.
Yaskawa is not responsible for any modification of the product made by the user. This
product must not be modified.
Check all the wiring to ensure that all
and connecting any other devices.
Failure to comply could result in damage to the drive.
connections are correct after installing the drive
72
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
4.2 Using the Digital LED Operator
4.2Using the Digital LED Operator
Use the LED operator to enter run and
as display fault and alarm information.
u
Keys, Displays, and LEDs
stop commands, display data, edit parameters, as well
1
2
3
J1000
:
6
1
:
7
2
据据据
据据据据据
8
3
:
据据据据据
据据据据据据
9
4
:
据据据据据据
据据据据据
5
:
据据据据据据据
据据据据
据据据据
WARNING
Risk of electric shock.
Read manual before installing.
Wait 5 minutes for capacitor discharge after
disconnecting power supply.
To conform to requirements, make sure
to ground the supply neutral for 400V class.
据据据据据据据据据据据据据据据
据据据
据据据据据据据据据据据据据据据据据据据据据据据据
据据据据据据据据据据据
据据据据据据据据据据据据
5
据据据据据据据
据据据据据据据据据据据据据据据据据据据据
400V
据据据据据据据据据据据据据据据据据据据据据
11
12
5
13
10
15
4
P
STOP
9
6
STOP
:
:
:
:
8
14
7
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
73
4.2 Using the Digital LED Operator
Table 4.1 Keys and Displays on the LED Operator
No.DisplayNameFunction
1Data Display AreaDisplays the frequency reference, parameter number, etc.
2ESC KeyReturns to the previous menu.
3RESET Key
4RUN KeyStarts the drive.
5Up Arrow KeyScrolls up to select parameter numbers, setting values, etc.
6Down Arrow KeyScrolls down to select parameter numbers, setting values, etc.
7
8ENTER Key
9LO/RE Selection Key
10RUN LightLit while the drive is operating the motor.
11LO/RE LightLit while the operator (LOCAL) is selected to run the drive.
12ALM LED Light
13REV LED Light
14DRV LED Light
15FOUT LED Light
STOP
STOP Key
Moves the cursor to the right.
Resets the drive to clear a fault situation.
Stops the drive.
Note: Stop priority circuit. A fast-stop is available by pressing the
STOP key when the drive detects a danger even if the drive is
running by a signal from the multi-function contact input terminal
(REMOTE is set). To avoid stoppage by using the STOP key, set
o2-02 (STOP Key Function Selection) to 0 (Disabled).
Selects all modes, parameters, settings, etc.
Selects a menu item to move from one display screen to the next.
Switches drive control between the operator (LOCAL) and the
control circuit terminals (REMOTE).
Note: LOCAL/REMOTE key effective during stop in drive
Refer to LED Screen Displays on page 75.
mode.
u
Digital Text Display
Text appears on the LED Operator as shown
as it appears on the display screen.
LitFlashing
74
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
below. This section explains the meaning of text
4.2 Using the Digital LED Operator
TextLEDTextLEDTextLEDTextLED
09IR
1AJS
2BKT
3CLU
4DM
<1>
V
5ENW
6FOXnone
7GPY
8HQZnone
<1>Displayed in two digits.
u
LED Screen Displays
DisplayLitFlashingOff
As illustrated
in this manual
u
LEDLitFlashing
When the drive detects an alarm or
error
Motor is rotating in reverse—Motor is rotating forward
Drive Mode—Programming Mode
Displays output frequency (Hz)——
• When an alarm occurs
• oPE detected
Normal state (no fault or alarm)
LO/RE LED and RUN LED Indications
<1>
Run command is selected
from device other than LED
operator (REMOTE)
During stop
When run command is
selected from LED
operator (LOCAL)
During run
——
• During deceleration to
stop
• When a run command
is input and frequency
reference is 0
Flashing Quickly
• During deceleration
at a fast-stop.
• During stop by
interlock operation.
Off
<1>
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
75
4.2 Using the Digital LED Operator
LEDLitFlashing
As shown
<1>Refer to Figure 4.1 for the difference between “flashing” and “flashing quickly”.
1 s
Flashing
Flashing
quickly
Drive output frequency
/
Frequency setting
RUN LED
ON
ONON
Figure 4.1 RUN LED Status and Meaning
during stop
0 Hz
OFF
Figure 4.2 RUN LED and Drive Operation
RUN
6 Hz
Flashing Quickly
ONON
ON
<1>
ON
STOP
Flashing
OFF
Off
RUN
STOP
OFF
76
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
4.2 Using the Digital LED Operator
u
Menu Structure for Digital LED Operator
Turn the power on
Forward Selection
Output Frequency
Output Current
DRIVE MODE
Output Voltage
Monitor Display
Note: “XX” characters are shown in this manual.
The drive will display the actual setting values.
<1>
Reverse Selection
Description of Key Operations
:
:
:
:
XX
XX
Verify Menu
Set Up Mode
Parameter Setting Mode
XX
XX
XXXX
XX
XX
XX
XX
XX
XX
XX
XX
XX
XX
PROGRAMMING MODE
Figure 4.3 Digital LED Operator Screen Structure
<1> Reverse can only be selected when LOCAL is set.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Start-Up Programming
& Operation
4
77
4.3 The Drive and Programming Modes
4.3The Drive and Programming Modes
The drive functions are divided into two main
Drive Mode: The Drive mode allows motor operation and parameter monitoring. Parameter
settings cannot be changed when accessing functions in the Drive Mode (Table 4.3).
Programming Mode: The Programming Mode allows access to setup/adjust, verify
parameters. The drive prohibits changes in motor operation such as start/stop when the Digital
LED Operator is accessing a function in the Programming Mode.
Table 4.3 illustrates the different functions visible as the “Up arrow” is scrolled immediately
after powering up the drive.
Note: When b1-08 (Run Command Selection while in Programming Mode) is set to 1 (enabled), the drive can run
even if the mode is switched to the programming mode. When setting b1-08 to 0 (disabled), the mode cannot
be switched to the programming mode while the drive is running.
Table 4.3 Summary of Modes
Mode GroupDescriptionKey Press LED Digital Operator Display
Frequency Reference Display
(Initial power-up state)
Forward/Reverse
groups accessible via the Digital LED Operator:
Drive Mode Functions
(Motor operation and
monitoring)
Programming Mode Functions
(Changing parameters)
u
Navigating the Drive and Programming Modes
The drive is set to operate in Drive
screens by using the
78
Output Frequency Display
Output Current Display
Output Voltage Reference
Monitor Display
Verify Function
Setup Group Parameters
All Parameters
Mode when it is first powered up. Switch between display
and keys.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Power Up
Drive Mode
Frequency Reference
STOP
Default Setting
Forward/Reverse
Output Frequency Display
Output Current Display
4.3 The Drive and Programming Modes
This display screen allows the user to monitor and set the frequency
reference while the drive is running. Refer to The Drive and
Programming Modes on page 78.
Note: The user can select items to display when the drive is first
powered up by setting parameter o1-02.
: Motor rotates forward.
: Motor rotates in reverse.
Note: For applications that should not run in reverse (fans, pumps,
etc.), set parameter b1-04 = “1” to prohibit the motor from rotating in
reverse. This sequence also puts the drive in LOCAL mode.
Switching to reverse:
The LED is lit when
LOCAL is selected
Monitors the frequency output by the drive.
Monitors the output current of the drive.
Start-Up Programming
& Operation
Output Voltage Reference
Drive Mode
Monitor Display
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Monitors the output voltage of the drive.
Monitor parameters (U parameters) are displayed.
4
79
4.3 The Drive and Programming Modes
Programming
Mode
Parameter Setting
Drive Mode
Drive Mode Details
n
Frequency Reference
Verify Function
Setup
Lists all parameters that have been edited or changed from default
settings.Refer to Verifying Parameter Changes: Verify Menu on
.
page 83
A select list of parameters necessary to get the drive operational
quickly.Refer to The Setup Group within the Programming
Mode on page 81.
Allows the user to access and edit all parameter settings.Refer
to Parameter List on page 197.
Returns to the frequency reference display screen.
The following actions are possible in the Drive Mode:
• Run and stop the drive.
• Monitor the operation status of the drive (frequency reference, output frequency, output
current, output voltage, etc.).
• View information on an alarm.
Note: Select "Drive Mode" when running. The mode can be switched to any mode (program mode, etc.) other
than drive mode while the
the mode to "Drive Mode" after completing periodic inspection.
drive is stopped. However, the drive cannot be operated in other modes. Return
Figure 4.4 illustrates changing the default frequency reference of F 0.00 (0 Hz) to F 6.00 (6
Hz) while in Drive Mode. This example assumes the drive is set to LOCAL.
80
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Frequency reference
display at power up
4.3 The Drive and Programming Modes
STOP
Press to select LOCAL
Press until the frequency
reference becomes 6 Hz
Figure 4.4 Setting the Frequency Reference while in Drive Mode
Note: The drive will not accept a frequency reference set value unless the ENTER key is pressed after the frequency
reference is entered. This feature prevents accidental setting of the frequency reference. By setting o2-05
(Frequency Reference Setting Method Selection) to 1 (Enabled), the drive will accept the frequency
reference while it is being adjusted on the digital operator.
Programming Mode Details
n
Press to select the
digit to the right
The following actions are possible in the programming mode:
• Verify Function: Verify parameter setting changes from original default values.
• Setup Group: Access a list of commonly used parameters to simplify setup.
• Parameter Setting Mode: Access and edit all parameter settings.
The Setup Group within the Programming Mode
In Setup Group, the user can access the minimum group of parameters required to operate the
application.
Note: Setup Group parameters are listed in Table 4.4.
Figure 4.5 illustrates the keys to press to enter the Setup Group.
In this example, the source of the frequency reference is changed from the control circuit
terminals to the LED Operator (i.e., b1-01 is changed from 1 to 0).
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
81
4.3 The Drive and Programming Modes
Frequency reference
appears when powered up
STOP
Press until
appears
<1>
Parameter Display
Control Circuit
Terminal
Select digit
to edit
<2>
Parameter Display
<1> Move to the right to change parameter settings. Scroll
down to view and check settings in the Setup Mode.
<2> To return to the Top Menu, press .
other parameters, press and .
Figure 4.5 Setup Group Example
u
Changing Parameter Settings or Values
This example explains changing C1-01 (Acceleration Time 1)
20.0 seconds.
StepDisplay/Result
1. Turn on the power to the drive. The initial display appears.
LED Operator
(2x)
To view or edit
from 10.0 seconds (default) to
2.
Press the key until the Setup Mode Screen appears.
3.
Press the key to view the parameter setting display.
82
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
4.3 The Drive and Programming Modes
StepDisplay/Result
4.
Scroll through parameters by pressing the key until C1-01
appears.
5.
Press to view the current setting value (10.0). (Number
farthest to the left flashes)
6.
Press until the desired number is selected. (“1” flashes)
7.
Press the key and enter 0020.0.
8.
Press and the drive will confirm the change.
9. The display automatically returns to the screen shown in Step 4.
10.
Press the key until back at the initial display.
u
Verifying Parameter Changes: Verify Menu
The Verify Menu lists edited parameters from the Programming Mode. The Verify Menu
helps determine which settings have been changed, and
a drive. If no settings have been changed the Verify Menu will read
is particularly useful when replacing
. The Verify menu
also allows users to access and re-edit edited parameters.
Note: The Verify Menu will not display parameters from
from default settings.
the A1 group even if those parameters have been changed
The following example is a continuation of the steps beginning on page 82. Here, parameter
C1-01 is accessed using the Verify Menu and is changed again to 20.0 s.
To check the list of edited parameters:
StepDisplay/Result
1. Turn on the power to the drive. The initial display appears.
Start-Up Programming
& Operation
4
2.
Press until the display shows the “Verify” representation.
Press to enter the list of parameters that have been edited
3.
from their original default settings.
Scroll through the list by pressing the key.
4.
Press the key until C1-01 appears.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
83
4.3 The Drive and Programming Modes
StepDisplay/Result
5.
Press the key to access the setting value. (number farthest to
the left flashes)
u
Switching Between LOCAL and REMOTE
Entering the run command using the LED operator is referred to as LOCAL, while entering
the run command from an external device via
the control circuit terminals or network option
unit is referred to as REMOTE.
WARNING! Sudden Movement Hazard. The drive may start unexpectedly if the Run command is already
applied when switching from LOCAL mode to REMOTE mode when b1-07 = 1, resulting in death or serious
injury. Be sure all personnel are clear of rotating machinery and electrical connections prior to switching
between LOCAL mode and REMOTE mode.
There are two ways to switch between LOCAL and REMOTE.
Note: 1. After selecting LOCAL, the LO/RE light will remain lit.
2. The drive will not allow the user to switch between LOCAL and REMOTE during run.
Using the LO/RE Key on the LED Operator
n
StepDisplay/Result
1. Turn on the power to the drive. The initial display appears.
Press . The LO/RE light will light up. The drive is now in
2.
Local.
To set the drive for REMOTE operation, press
the
key again.
STOP
Using Input Terminals S1 through S5 to Switch between LO/RE
n
Switch between LOCAL and REMOTE using one of the digital input terminals S1 through
S5 (set the corresponding parameter H1-01 through H1-05 to “1”).
Follow the example below to set the digital input terminals.
Note: 1. For a list of digital input selections, Refer to Parameter List on page 197.
2. Setting a multi-function input terminal to a value of 1 disables the LO/RE key on the LED operator.
84
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
4.3 The Drive and Programming Modes
u
Parameters Available in the Setup Group
Setup Mode (STUP)
n
Parameters used for this drive are classified into A to U. To simplify the drive setup, frequently
used parameters are selected and input into Setup Mode.
1.
To set a parameter, the Setup Mode must be displayed first. Press the Up/Down key
until is displayed.
2.
Select the parameter and change the setting. Table 4.4 lists
the Setup group. If the desired parameter cannot be set in the Setup mode, use the
Parameter Setting mode.
Note: This manual also explains other parameters not visible in the Setup Group (A1-06 = 0). Use the “Par” menu
in the Programming mode to access parameters not listed in the Setup Group.
b1-03Stop Method Selection
C1-01Acceleration Time 1
C1-02Deceleration Time 1
C6-01Duty Selection
C6-02Carrier Frequency Selection
d1-01Frequency Reference 1
d1-02Frequency Reference 2
d1-03Frequency Reference 3
d1-04Frequency Reference 4
ParameterName
d1-17Jog Frequency Reference
E1-01Input Voltage Reference
E1-04Maximum Output Frequency
E1-05Maximum Voltage
E1-06Base Frequency
E1-09Minimum Output Frequency
E2-01Motor Rated Current
H4-02Terminal FM Gain Setting
L1-01Motor Protection Function Selection
L3-04
Stall Prevention Selection during
Deceleration
parameters available in
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
85
4.4 Start-up Flowcharts
4.4Start-up Flowcharts
This section summarizes the basic steps required to
quick reference to help familiarize the user with start-up procedures.
u
Flowchart: Basic Start-up and Motor Tuning
Figure 4.6 describes basic start-up sequence for the drive and motor system. This sequence
varies slightly depending on application. Use drive default parameter settings in simple
applications that do not require high precision.
Install and wire the drive as explained in Chapters 1, 2 and 3
Adhere to safety messages concerning application of power.
Apply main power on to the drive.
start the drive. The chart is intended as a
START
* b1-01/02 for frequency reference and run command source selection
* h1-oo, H2-01, H3-oo, H4-oo, H5-oo for I/O terminal setting
* d1-oo for multi-speed references if used
* C1-oo and C2-oo for accel./decel. and S-curve time settings
* C6-01 for heavy/normal duty mode selection
* L3-04 if braking options are used
Run the motor without load; check the rotation direction and operation.
Verify external signal commands to the drive work as desired.
Couple the load or machine to the motor. Run the machine and check for desired operation.
Fine tune parameters. Adjust application settings if necessary.
Check the machine operation and verify parameter settings.
Figure 4.6 Basic Start-Up and Motor Tuning
86
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Set the basic parameters:
Drive is ready to run the application.
4.5 Basic Operation
4.5Basic Operation
This section explains the basic settings required for initial drive operation. Checking these
basic parameter settings during start-up will help to ensure a successful drive start-up.
If more information is required for parameters not
List on page 197 as required for a complete listing of drive parameters.
u
Initialize Parameter Values: A1-03
Parameter A1-03 (Initialize Parameters) resets all parameters to the original default values.
Note: Record all the changed settings before initializing parameters.
Different Methods of Drive initialization
n
2220: 2-Wire Initialization
Returns all parameters to factory default values for 2-wire control.
3330: 3-Wire Initialization
Returns all parameters to factory default values for 3-wire control.
u
Frequency Reference Source: b1-01
This section explains how to assign the frequency reference. Parameters b1-01 and b1-02 can
be used to select the source of the run command and the frequency reference independently
(e.g., set the reference from the operator and set the run command from the terminals).
Frequency Reference from the LED Operator: b1-01 = 0
n
When b1-01 = 0 the frequency reference will be provided by the LED operator. Refer to The
Drive and Programming Modes on page 78 for information on how to set the frequency
reference.
listed in this section, Refer to Parameter
Start-Up Programming
& Operation
4
Frequency Reference from the Analog Input Terminal: b1-01 = 1
n
When b1-01 = 1, analog input A1 provides the frequency reference.
Note: Set H3-01 (Terminal A1 Function Selection) to “0” to configure Terminal A1 for the main analog frequency
reference.
Voltage Input
When entering the frequency reference with a voltage signal, set parameter H3-01 to “0” for
0 to 10 Vdc with lower reference limit. Set H3-01 to “1” if 0 to 10 Vdc input without lower
limit is required. Set DIP Switch S1 for voltage input (position “V”).
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
87
4.5 Basic Operation
DIP switch S1
IV
Drive
0 to 10 V
Main frequency
A1
(voltage or current input)
Analog common
AC
Figure 4.7 Voltage Input for the Frequency Reference
Current Input
When entering the frequency reference using an analog input signal, set parameter H3-01 to
“2” if 4 to 20 mA input is used. When using 0 to 20 mA input, set H3-01 to “3”. Set DIP
Switch S1 for current input (position “I”).
DIP switch S1
IV
0 or 4 to 20 mA input
Figure 4.8 Current Input for the Frequency Reference
Drive
V (+10.5 V, 20 mA power supply)
Main Frequency
A1
(current input)
Analog common
AC
88
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
4.5 Basic Operation
u
Run Command Input Selection: b1-02
This section explains how to assign the run command input.
Parameters b1-01 and b1-02 can be used to select the source of the run command and the
frequency reference independently, e.g. set the reference from the operator and set the run
command from the terminals.
WARNING! Sudden Movement Hazard. When the run command is given by turning on the power to the drive,
the motor will begin rotating as soon as the drive is powered up. Be sure to take proper precautions if using
this setting. Ensure the area around the motor is safe. Failure to comply could result in death or serious injury.
Run the Drive at 6 Hz using the LED Operator: b1-02 = 0
n
To assign the run command to the operator panel, set parameter b1-02 to “0”. This will set up
the drive to acknowledge the run command through the LED operator. Initialize the run
command using the Run and Stop keys. Upon power up, the drive uses parameter b1-02 to
determine the run command location.
The following procedure indicates how to start and stop the drive through the LED operator
after parameter b1-02 has been set to 0.
Note:
When b1-02 (Run Command Selection) is not set to 0 (operator), press
StepDisplay/Result
1. Turn on the power to the drive. The initial display appears.
Set the frequency reference to F6.00 (6 Hz).
2.
Note:Refer to Drive Mode Details on page 80
to set the frequency reference.
3.
Press the key to start the motor.
for instructions on how
to set LOCAL.
Start-Up Programming
& Operation
4
4. The motor should accelerate up to 6 Hz while the RUN light is on.
5.
Press the
until the motor comes to a complete stop.
Run the Drive using Digital Input Terminals: b1-02 = 1
n
STOP
key to stop the motor. The RUN light will flash
offon
flashing
STOP
off
This setting uses the digital input terminals to enter the run command. The factory setting is
a 2-wire sequence.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
89
4.5 Basic Operation
Using a 2-Wire Sequence
Digital Input TerminalsONOFF
S1Forward RunStop
S2Reverse RunStop
Drive
Forward Run
S1
Reverse Run
S2
SC
Digital Input Common
Figure 4.9 Example Wiring Diagram for 2-Wire Sequence
Using a 3-Wire Sequence
When H1-05 (Multi-Function Digital Input Terminal S5 Function
Selection) = 0, the functions
of terminals S1 and S2 are set to 3-wire sequence, and the multi-function input terminal
becomes forward/reverse run command terminal.
Stop Button
(N.C.)
Figure 4.10 Example Wiring Diagram for 3-Wire Sequence Using Terminal S5
Run Button
(N.O.)
S1
Run Command
Runs when S1 and S2 are closed
(Run button pushed)
S2
Stop Command
Stops when S1 and S2 are open
(Stop button pushed)
S5
FWD/REV Command
SC
Drive
<1>
Digital Input Common
<1> When terminal S5 is open, the motor rotates forward. When closed, the motor rotates in
reverse.
90
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
4.5 Basic Operation
WARNING! When 3-Wire sequence is used, set the drive to 3-Wire sequence before wiring the control
terminals and ensure parameter b1-17 is set to
If the drive is wired for 3-Wire sequence but set up for 2-Wire sequence (default) and if parameter b1-17 is
set to 1 (drive accepts a Run command at power up), the motor will rotate in reverse direction at power up of
the drive and may cause injury.
Note: Refer to Parameter List on page 197 for a list of digital input functions. After performing a 3-wire
initialization (A1-03 = “3”), the drive will automatically assign the forward/reverse command to terminal
S5.
Note: Run by Turning on/off the Power Supply. For safety reasons, the drive is initially set up not to accept a run
command at power up (b1-17 = "0"). If a run command is issued at power up, the RUN indicator LED will
flash quickly. To change this and have the run command issued by the drive, change parameter b1-17 to 1.
u
Stopping Method Selection: b1-03
0 (drive does not accept a run command at power up (default)).
When a Stop command is issued, the drive stops the motor using one of two possible methods.
Ramp to Stop: b1-03 = 0
n
When b1-03 = 0, the motor will decelerate to a stop when a stop command is entered. The
deceleration time is set by C1-02 (Deceleration Time 1). Refer to Acceleration/Deceleration:
C1-01 to C1-04 on page 92.
When the output frequency falls below E1-09 (Minimum Output Frequency) during
deceleration, the DC Injection braking current (b2-02) will be activated for the specified DC
Injection time at stop (b2-04).
Run Command
ONOFF
Output Frequency
Decelerates according to the
specified deceleration time
DC Injection Braking
Figure 4.11 Ramp to Stop
Coast to Stop: b1-03 = 1
n
When the run command is removed, the drive
Decel Time
(C1-02, etc.)
will shut off its output and the motor will coast
DC Braking
Minimum Output Freq.
(E1-09)
DC Injection
Current (b2-02)
Time at Stop (b2-04)
(uncontrolled deceleration). The motor will coast to a stop at the rate determined by the load
inertia.
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Start-Up Programming
& Operation
4
91
4.5 Basic Operation
Run Command
ON
OFF
Output Voltage
Drive output voltage interrupted
Motor Rotations
Figure 4.12 Coast to Stop
Note: 1. After entering a stop command, the drive will not accept another run command until the time set passes.
2. Do not enter another run command until the motor comes to a complete stop. If a run command must
be entered before the motor has fully stopped, use DC Injection to slow the motor or catch the motor
before restarting.
u
Acceleration/Deceleration: C1-01 to C1-04
C1-01 (Acceleration Time 1) sets the time to accelerate from 0 to the maximum output
frequency (E1-04). C1-02 (Deceleration Time 1) sets the time to decelerate from maximum
output frequency to 0.
No.Parameter NameDescription
<1>
C1-01
C1-02
<1>The parameter can be changed during run.
WARNING! Sudden Movement Hazard. Rapid deceleration may cause the drive to fault on an overvoltage
condition, resulting in death or serious injury due to an uncontrolled motor state. Set an acceptable
deceleration time in parameter C1-09 when using the Fast-stop feature.
Acceleration Time 1
<1>
Deceleration Time 1
Sets the time to accelerate from 0 to 100% (maximum
output frequency).
Sets the time to decelerate from 100% (maximum output
frequency) to 0%.
Setting
Range
0.0 to
6000.0
Default
10.0 s
Switching Accel/Decel Times with Digital Input Terminals
n
Two acceleration / deceleration times can be selected
using one of the digital input terminals
S1 through S5.
Program one of the parameters H1-01 through H1-05 to “07” (Accel/Decel Time). Opening
or closing the digital input changes the accel/decel times as shown below:
Accel/Decel Time
H1-oo = 7
Open (not selected)C1-01C1-02
92
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Acceleration TimeDeceleration Time
4.5 Basic Operation
Accel/Decel Time
H1-oo = 7
ClosedC1-03C1-04
Using S-Curve Characteristics during Acceleration/Deceleration
n
Using S-curve characteristics to smooth acceleration and deceleration
Acceleration TimeDeceleration Time
minimizes abrupt shock
to the load. Set S-curve characteristic time during acceleration/deceleration at start and
acceleration/deceleration at stop.
Note: Setting S-curve characteristics will lengthen accel/decel times as follows:
Accel Time = Selected Accel Time + (C2-01 + C2-02)/2
Decel Time = Selected Decel Time + (C2-03 + C2-04)/2
Setting Example
Figure 4.13 illustrates S-curve characteristics switching between forward and reverse.
Forward Run
Command
Reverse Run
Command
C2-03
C2-04
C2-01
C2-02
C2-04
C2-03
C2-02
Output
Frequency
u
Drive Duty Mode and Carrier Frequency Selection: C6-01 and
C2-01
Figure 4.13 S-Curve Characteristics
C6-02
Start-Up Programming
& Operation
4
Drive Duty Mode Selection: C6-01
n
The drive has two different duty modes from
which to select based on the load characteristics.
The drive rated current, overload capacity, carrier frequency, and maximum output frequency
will change depending upon the duty mode selection. Use parameter C6-01 (Duty Cycle) to
select Heavy Duty (HD) or Normal Duty (ND) for the application. The default setting is ND.
Refer to Specifications on page 187 for details about the rated current.
HD and ND Mode Selections
ModeHD RatingND Duty Rating
C6-0101
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
93
4.5 Basic Operation
ModeHD RatingND Duty Rating
150 %
100 %
Characteristics
Overload
Rated Load
120 %
100 %
Overload
Rated Load
0
Use ND Rating for applications in which the
torque requirements drop along with the speed.
Examples include fans or pumps where a high
overload tolerance is not required.
100% continuous, 120% of drive rated current
for 60 s
1 : 2.0 kHz
2 : 5.0 kHz
3 : 8.0 kHz
4 : 10.0 kHz
5 : 12.5 kHz
6 : 15.0 kHz
7: Swing PWM
F : User defined (C3-03 to C3-05)
Motor Speed
Application
Overload capability
(oL2)
C6-02
L3-02 Stall
Prevention during
Acceleration
L3-06 Stall
Prevention during
Run
0Motor Speed
Use HD Rating is designed applications
requiring a high overload tolerance with
constant load torque, like conveyors.
100% continuous, 150% of drive rated current
for 60 s
1 : 2.0 kHz
2 : 5.0 kHz
3 : 8.0 kHz
4 : 10.0 kHz
5 : 12.5 kHz
6 : 15.0 kHz
7: Swing PWM
F : User defined (C3-03 to C3-05)
100 %
150%120%
150%120%
Note: By selecting HD/ND, motor parameter E2 is changed to the value for the maximum applicable motor.
Note: Swing PWM uses 2.0 kHz carrier frequency as a base. The application of special PWM patterns keeps the
audible noise of the motor low.
Carrier Frequency Selection: C6-02
n
Fixed Carrier Frequencies
The carrier frequency can be set using parameter C6-02 as shown in table below.
100 %
94
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
4.5 Basic Operation
ParameterNameDescriptionSetting RangeDefault
C6-02
Note: Settings 7 through A for parameter C6-02 use a Swing PWM equivalent to a 2 kHz audible noise. This
Note: The upper limit for the carrier frequency is determined by drive capacity.
Carrier
frequency
function turns the motor noise into a less obtrusive white noise.
1 : 2.0 kHz
2 : 5.0 kHz
3 : 8.0 kHz
4 : 10.0 kHz
5 : 12.5 kHz
6 : 15.0 kHz
7: Swing PWM
F : User defined (C3-03 to C3-05)
1 to F
Depends on
drive size
Precautions when setting parameter C6-02:
Speed and torque are unstable at low speeds.
Noise from the drive is affecting peripheral devices.
Excessive leakage current from the drive.
Wiring between the drive and motor is too long.
Motor acoustic noise is too loud.Increase the carrier frequency or use Swing PWM.
<1>The carrier frequency may need to be lowered if the motor cable is too long. Refer to the table below.
Wiring DistanceUp to 50 mUp to 100 mGreater than 100 m
C6-02 (Carrier Frequency Selection) 1 to F (15 kHz)1 to 2 (5 kHz), 71 (2 kHz), 7
Carrier Frequency Setting Error (oPE11)
SymptomPossible Solution
Lower the carrier frequency.
<1>
A carrier frequency setup error (oPE11) will occur when carrier frequency gain (C6-05) is
greater than 6 and C6-03 < C6-04.
Note: Refer to Troubleshooting without Fault Display on page 143 for information on operator errors (oPE).
Carrier Frequency and Drive Overload Current Level
n
With C6-01 set to 1, the carrier frequency setting defines drive output current level.
Table 4.5 Current Derating by Carrier Frequency Setting
Single-Phase 200 VThree-Phase 200 VThree-Phase 400 V
Model
(Capacity)
BA0001
0.2 kW/
0.1 kW
BA0002
0.4 kW/
0.2 kW
Carrier
Frequency
(kHz)
Output
Current
21.2
150.6150.6
21.9
101.6101.681.2
151.3151.3150.7
(A)
Model
(Capacity)
2A0001
0.2 kW/
0.1 kW
2A0002
0.4 kW/
0.2 kW
Carrier
Frequency
(kHz)
21.2
21.9
Output
Current
(A)
Model
(Capacity)
———100.8100.8
4A0001
0.4 kW/
0.2 kW
Carrier
Frequency
(kHz)
21.2
Output
Current
(A)
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
95
4.5 Basic Operation
Single-Phase 200 VThree-Phase 200 VThree-Phase 400 V
Model
(Capacity)
BA0003
0.75 kW/
0.4 kW
BA0006
1.1 kW/
0.75 kW
———
———
BA0010
2.2 kW/
1.5W
———
———
———
Carrier
Frequency
(kHz)
103.0103.081.8
152.4152.4151.1
105.083.4
154.0152.0
156.4156.4152.9
Output
Current
23.3
26.0
29.6
88.088.084.8
(A)
Model
(Capacity)
2A0004
0.75 kW/
0.4 kW
2A0006
1.1 kW/
0.75W
2A0008
1.5 kW/
1.1 kW
2A0010
2.2 kW/
1.5W
2A0012
3.0 kW/
2.2 kW
2A0018
3.7 kW/
3.0W
2A0020
5.5 kW/
4.0 kW
Carrier
Frequency
(kHz)
———
Output
Current
23.3
26.0
154.0
28.0
155.5
29.6
212.0
811.085.5
158.8153.3
217.5
814.087.2
1511.2154.3
219.6
817.589.2
1514.0155.5
(A)
Model
(Capacity)
4A0002
0.75 kW/
0.4 kW
4A0004
1.5 kW/
0.75 kW
———105.0
———86.9
4A0005
2.2 kW/
1.5W
4A0007
3.0 kW/
2.2 kW
4A0009
3.7 kW/
3.0 kW
4A0011
5.5 kW/
4.0 kW
Carrier
Frequency
(kHz)
22.1
24.1
25.4
26.9
28.8
211.1
Output
Current
(A)
u
Multi-Step Speed Operation (4-Step Speed)
Select up to 9 preset references (including Jog reference) using two multi-function inputs S4
and S5. Two multi-step references can be selected using two multi-function inputs as
illustrated in Figure 4.14.
Multi-Step Speed Operation Parameters
n
No.NameDescription
d1-01 Frequency Reference 1Frequency reference. o1-03 determines the units, with Hz as the default.
d1-02 Frequency Reference 2
d1-03 Frequency Reference 3
96
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
Frequency reference when multi-function input “Multi-Step Speed Reference
1" (H1-oo = 3) is on. Setting unit: set by o1-03.
Frequency reference when multi-function input “Multi-Step Speed Reference
2” (H1-oo = 4) is on. Setting unit: set by o1-03.
Frequency reference when multi-function input “Multi-Step Speed Reference 1,
2" (H1-oo = 3 and 4) are both on. Setting unit: set by o1-03.
Set up external switches SW1 and SW2.
Three-Phase, 200 Vac
(400 Vac)
SW1
SW2
Figure 4.14 Control Terminals for 4 Multi-Step Speeds
R/L1
S/L2
T/L3
S4
S5
SC
Drive
U/T1
V/T2
W/T3
M
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
97
4.5 Basic Operation
Frequency
Reference
Freq Ref 4
Freq Ref 3
Freq Ref 2
Freq Ref 1
Forward/Reverse Run/Stop
Multi-Step Speed 1
Multi-Step Speed 2
Figure 4.15 4-Step Speed Time Chart
Setting Procedure
n
StepDisplay/Result
1. Turn on the power to the drive. The initial display appears.
Set the frequencies listed below to the specified parameters:
1. d1-01 = 5 Hz: Step 1
2.
2. d1-02 = 20 Hz: Step 2
3. d1-03 = 50 Hz: Step 3
4. d1-04 = 60 Hz: Step 4
3.
Press the key until the initial display appears.
4. turns on.
5.
Press to select LOCAL. The LO/RE light will turn on.
<1>
OFF
OFF
ON
ON
ON
ON
STOP
98
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
4.5 Basic Operation
StepDisplay/Result
6.
Press to run the motor at 5 Hz. The RUN light will turn on.
STOP
OffOn
With SW1 closed, the drive runs the motor at Multi-Step Speed 2
7.
(20 Hz).
With SW1 open and SW2 closed, the drive runs the motor at Multi-Step
8.
3 (50 Hz).
With both SW1 and SW2 closed, the drive runs the motor at Multi-Step
9.
4 (60 Hz).
10.
STOP
Press
motor comes to a complete stop.
to stop the drive. The RUN light will flash until the
FlashingOff
<1>When the frequency reference is assigned to the LED operator (b1-01=0), the first step in a multi-step speed
sequence comes from d1-01.
Note: When a run command is input from the control circuit terminal, the frequency reference value is selected
as follows:
When b1-01 = 0 and the run command is given, the drive uses the frequency set to d1-01.
When b1-01 = 1 and the run command is given, the drive uses the frequency reference value input to analog
control terminal A1.
u
Drive Input Voltage Setting: E1-01
Set E1-01 according to the power supply voltage.
This setting serves as a base value for certain
STOP
drive protective functions.
NOTICE: Set drive input voltage (not motor voltage) in parameter E1-01 for proper function of the protective
features of the drive. Failure to comply could result in improper drive operation. Set parameter E1-01 to match
the input voltage of the drive.
Parameter NameDescriptionSetting RangeDefault
E1-01
Set to the nominal voltage of the incoming line. Sets
Input
the maximum and base voltage, and adjusts the levels
Voltage
of drive protective features (e.g., overvoltage, braking
Setting
resistor level, stall prevention, etc.).
200 V Class: 155 to 255
400 V Class: 310 to 510
200 V
Start-Up Programming
& Operation
4
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
99
4.5 Basic Operation
Input Voltage Setting Value: E1-01
n
The
input
voltage
level
determines
overvoltage
the
detection
level and the operation level of
the braking transistor as shown in the table below.
Voltage
200 V ClassAll settings410 V394 V
400 V Class
Note: This data is for an internal dynamic braking resistor of 0.1 to 18.5 kW. For larger units, see “Dynamic
u
V/f Pattern Settings: E1-04 to E1-10
Setting Value of
E1-01
Setting ≥ 400V820 V788 V380 V
Setting < 400V740 V708 V350 V
Braking Resistor Unit for VARISPEED-600 Series, TOBPC72060000.”
ov Detection
Level
(Approximate Values)
Braking Transistor
Operation Level
Uv Detection Level
190 V
(single-phase=160 V)
Depending on the application, it may be necessary to adjust the V/f pattern. Figure 4.16
illustrates parameters that need to be set up to adjust the V/f pattern characteristics.
Instructions for Setting a V/f Pattern
n
1.
Set the input voltage for the drive. Refer to Drive Input Voltage Setting: E1-01 on
page 99.
2.
Set the V/f pattern:
Output Vol (V)
E1-05
No.Parameter Name
E1-04Maximum Output Frequency
E1-05Maximum Voltage
E1-06Base Frequency
E1-07Mid Output Frequency
100
YASKAWA ELECTRIC TOEP C710606 25B YASKAWA AC Drive J1000 Installation & Start-Up Manual
E1-08
E1-10
E1-09E1-07 E1-06E1-04
Frequency (Hz)
Figure 4.16 V/f Pattern
No.Parameter Name
E1-08Mid Output Frequency Voltage
E1-09Minimum Output Frequency
E1-10Minimum Output Frequency Voltage
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.