YASKAWA GPD515C Technical Manual

GPD 515/G5 Drive
Technical Manual
Models: GPD515C- and CIMR-G5M Document Number: TM 4515
Section 1. RECEIVING AND INSTALLATION
1.1 G ENERA L
The GPD 515/G5, hereafter referred to as the drive, is a general purpose sine-coded pulse width modulated AC motor drive which generates an adjustable voltage/frequency three phase output for complete speed control of most conventional squirrel cage induction motors. Automatic stall prevention and voltage boost prevents nuisance tripping during load or line side transient conditions. The drive will not induce any voltage line notching distortion back to the utility line and maintains a displacement power factor of not less than 0.98 throughout its speed range.
When properly installed, operated and maintained, the drive will provide a lifetime of service. It is mandatory that the person who operates, inspects, or maintains this equipment thoroughly read and understand this manual before proceeding.
This manual primarily describes the GPD 515/G5, but contains basic information for the operator control station as well. This manual is equally applicable to drives labelled GPD 515 or G5.
1.2 R ECEIV ING
The drive is thoroughly tested at the factory. After unpacking, verify the part numbers with the purchase order (invoice). Any damages or shortages evident when the equipment is received must be reported immediately to the commercial carrier who transported the equipment. Assistance, if required, is available from your sales representative.
If the drive will be stored after receiving, keep it in its original packaging and store according to storage temperature specifications in Appendix 2.
1.3 P H Y S ICAL INS TALL ATI ON
Location of the drive is important to achieve proper performance and normal operating life. The unit should be installed in an area where it will be protected from:
• Direct sunlight, rain or moisture.
• Corrosive gases or liquids.
• Vibration, airborne dust or metallic particles.
When preparing to mount the drive, lift it by its base, effective cooling as well as proper maintenance, the drive must be installed on a flat, non­flammable vertical surface (wall or panel) using four mounting screws. There MUST be a MINIMUM 4.7 in. clearance above and below the drive to allow air flow over the heat sink fins. A minimum 1.2 in. clearance is required on each side on the drive.
A GPD 515/G5 in a free-standing floor-mount cabinet must be positioned with enough clear-ance for opening the door of the cabinet; this will ensure sufficient air space for
cooling. Make sure air entering the drive is below 113°F (45°C) (for protected chassis drives), or below 104°F (40°C) (for NEMA 1 drives), by adding a fan or other cooling device, if needed. See environmental specifications in Appendix 2.
ne v e r by the front cover. For
1-1
1.4 ELECT RICA L I NSTA LLAT ION
All basic interconnections (using the Digital Operator) are shown in Figures 1-3 and 1-4.
1 . 4 . 1 Ma i n C i r c u i t In p u t / O u t p u t
Complete wire interconnections according to Table 1-2, Figure 1-3 and Figure 1-4. Be sure to observe the following:
• Use 600V vinyl-sheathed wire or equivalent. Wire size and type should be determined by local electrical codes.
• Avoid routing power wiring near equipment sensitive to electrical noise.
• Avoid running input and output wiring in the same conduit.
• NEVER connect AC main power to output terminals T1(U), T2(V), and T3(W).
• NEVER allow wire leads to contact metal surfaces. Short-circuit may result.
• NEVER connect power factor correction capacitors to the drive output. Consult Yaskawa when connecting noise filters to the drive output.
• WIRE SIZING MUST BE SUITABLE FOR CLASS I CIRCUITS.
• When connecting motor to drive’s output terminals, include a separate ground wire. Attach ground wire solidly to motor frame and to drive’s ground terminal.
• When using armored or shielded cable for connection between drive and motor, solidly connect armor or shield to motor frame, and to drive’s ground terminal.
• Motor lead length should NOT EXCEED 164 feet (50 meters), and motor wiring should be run in a separate conduit from other power wiring. If lead length must exceed this distance, reduce carrier frequency (see paragraph 5.8) and consult factory for proper installation procedures.
• Use UL listed closed loop connectors or CSA certified ring connectors sized for the selected wire gauge. Install connectors using the correct crimp tool recommended by the connector
manufacturer.
WIRE SIZE
AWG mm
20 0.5 M3.5 1.25 - 3.5 7.8 0.9 7.0 0.8 18 0.75 M4 1.25 - 4 13.0 1.5 10.4 1.2 16 1.25 M4 1.25 - 4 13.0 1.5 10.4 1.2
14 2
12 3.5
10 5.5
8 8
6 14 M6 14 - 6 40.9 34.8 4.8 4.1 4 22 M8 22 - 8 100.0 82.6 11.7 10.7
2 38
1/0 60 M10 60 - 10 182.6 156.5 21.4 18.4 3/0 80 M10 80 - 10 182.6 156.5 21.4 18.4
4/0 100
MCM300 150 M12 150 - 12 313.0 191.3 36.7 23.1 MCM400 200 M12 200 - 12 313.0 191.3 36.7 23.1
MCM650 325
2 SCREW CONNECTOR
TERMINAL CLOSED-LOOP
M4 2 - 4 13.0 1.5 10.4 1.2 M5 2 - 5 26.1 20.9 3.1 2.4 M4 3.5 - 4 13.0 1.5 10.4 1.2 M5 3.5 - 5 26.1 20.9 3.1 2.4 M4 5.5 - 4 13.0 1.5 10.4 1.2 M5 5.5 - 5 26.1 20.9 3.1 2.4 M5 8 - 5 26.1 20.9 3.1 2.4 M6 8 - 6 40.9 34.8 4.8 4.1
M8 38 - 8 100.0 82.6 11.7 10.7
M10 38 - 10 182.6 156.5 21.4 18.4
M10 100 - 10 182.6 156.5 21.4 18.4 M12 100 - 12 313.0 191.3 36.7 23.1
M12 325 - 12 313.0 191.3 36.7 23.1 M16 325 - 16 313.0 191.3 36.7 23.1
CLAMPING TORQUE
STEEL COPPER
lb-in N-m lb-in N-m
1-2
Table 1-1. Typical Wire Sizing For Main Circuit*
SECTION A. 230V
NEW DRIVE OLD DRIVE
HP TERMINAL WIRE SIZE
MODEL NO. MODEL NO.
RATING TERMINAL SYMBOL SCREW AWG MM2
CIMR-G5M GPD515C–
TERMINAL SYMBOL
TERMINAL
SCREW
20P41F A003, L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, M4 14 - 10 2 - 5.5 20P71F A006 T1 (U), T2 (V),T3 (W),
21P51F A008 L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M4 14 - 10 2 - 5.5
T2 (V), T3 (W)
M4 12 - 10 3.5 - 5.5
22P21F A011 L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M4 12 - 10 3.5 - 5.5
T2 (V), T3 (W),
23P71F A017 L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M4 10 5.5
T2 (V), T3 (W),
25P51F A025, L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M5 8 8 27P51F A033 T2 (V), T3 (W)
M5 10 - 8 5.5 - 8
20111F A049 L1 (R), L2 (S), L3 (T), , 1, 2, 3, T1 (U), M6 4 22
T2 (V), T3 (W)
M6 8 8
20151F A064 L1 (R), L2 (S), L3 (T), , 1, 2, 3, T1 (U), M8 3 30
T2 (V), T3 (W)
M6 8 8
20181F A080, L1 (R), L2 (S), L3 (T), , 1, 2, 3, T1 (U), M8 3 30 20221F A096 T2 (V), T3 (W)
M8 6 14
l
1 (r), l2 (s) M4 20 - 10 0.5 - 5.5
20300F A130 L1 (R), L2 (S), L3 (T), T1 (U), T2 (V), T3 (W) M10 4/0 100
, 3, M8 4 22
l
1 (r), l2 (s) M4 20 - 10 0.5 - 5.5
20370F A160 L1 (R), L2 (S), L3 (T), T1 (U), T2 (V), T3 (W) M10 1/0 x 2P 60 x 2P
, 3, M8 4 22
l
1 (r), l2 (s) M4 20 - 10 0.5 - 5.5
20550F A224 L1 (R), L2 (S), L3 (T), T1 (U), T2 (V), T3 (W) M10 1/0 x 2P 60 x 2P
, 3, M8 3 30
l
1 (r), l2 (s) M4 20 - 10 0.5 - 5.5
20750F A300 L1 (R), L2 (S), L3 (T), T1 (U), T2 (V), T3 (W) M12 4/0 x 2P 100 x 2P
, 3, M8 1 50
l
1 (r), l2 (s) M4 20 - 10 0.5 - 5.5
WIRE SIZE
AWG mm
2
* Consult local electrical codes for wire sizing requirements.
1-3
Table 1-1. Typical Wire Sizing For Main Circuit - Continued*
Section B. 460V
DRIVE TERMINAL WIRE SIZE
NEW DRIVE OLD DRIVE MODEL NO. MODEL NO.
MODEL NO. TERMINAL SYMBOL SCREW AWG mm
CIMR-G5M GPD515C–
TERMINAL SYMBOL
TERMINAL
SCREW
40P41F B001 L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M4 14 - 10 2 - 5.5
T2 (V), T3 (W), 40P71F B003, L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2,T1 (U), M4 14 - 10 2 - 5.5 41P51F B004, T2 (V), T3 (W) 43P71F B008 M4 12 - 10 3.5 - 5.5 44P01F B011, L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M4 12 - 10 3.5 - 5.5 45P51F B014 T2 (V), T3 (W), 47P51F B021 L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M4 8 - 6 8 - 14
T2 (V), T3 (W), 40111F B027, L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M5 8 - 6 8 - 14 40151F B034 T2 (V),T3 (W)
M6 8 8
40181F B041 L1 (R), L2 (S), L3 (T), , 1, 2, 3, T1 (U), M6 6 14
T2 (V), T3 (W)
M8 8 8
l
1 (r), l2 (s) M4 20 - 10 0.5 - 5.5
40221F B052 L1 (R), L2 (S), L3 (T), , 1, 2, 3, T1 (U), M6 4 22
T2 (V), T3 (W)
M8 8 8
l
1 (r), l2 (s) M4 20 - 10 0.5 - 5.5
40301F B065 L1 (R), L2 (S), L3 (T), , 1, 2, 3, T1 (U), M8 4 22
T2 (V), T3 (W)
M8 8 8
l
1 (r), l2 (s) M4 20 - 10 0.5 - 5.5
40371F B080 L1 (R), L2 (S), L3 (T), , 1, 2, 3, T1 (U), M8 3 30
T2 (V), T3 (W)
M8 6 14
l
1 (r), l2 (s) M4 20 - 10 0.5 - 5.5
40451F B096 L1 (R), L2 (S), L3 (T), , 1, 2, 3, T1 (U), M8 1 50
T2 (V), T3 (W)
M8 6 14
l
1 (r), l2 (s) M4 20 - 10 0.5 - 5.5
40551F B128 L1 (R), L2 (S), L3 (T), T1 (U), T2 (V), T3 (W) M10 4/0 100
, 3, M8 4 22
l
1 (r), l2 200 (s200), l2 400 (s400) M4 20 - 10 0.5 - 5.5
40750F B165 L1 (R), L2 (S), L3 (T), T1 (U), T2 (V), T3 (W) M10 1/0 x 2P 60 x 2P
, 3, M8 4 22
l
1 (r), l2 200 (s200), l2 400 (s400) M4 20 - 10 0.5 - 5.5
41100F B224 L1 (R), L2 (S), L3 (T), T1 (U), T2 (V), T3 (W) M10 1/0 x 2P 60 x 2P
, 3, M8 3 30
l
1 (r), l2 200 (s200), l2 400 (s400) M4 20 - 10 0.5 - 5.5
41600F B302 L1 (R), L2 (S), L3 (T), T1 (U), T2 (V), T3 (W) M12 4/0 x 2P 100 x 2P
, 3, M8 1 50
l
1 (r), l2 200 (s200), l2 400 (s400) M4 20 - 10 0.5 - 5.5
41850F B340, L1 (R), L2 (S), L3 (T), , 1, 3, T1 (U), T2 (V), M16
MCM650 x 2P 42200F B450, T3 (W) 43000F B605 M8 1/0 60
l
1 (r), l2 200 (s200), l2 400 (s400) M4 20 - 10 0.5 - 5.5
* Consult local electrical codes for wire sizing requirements.
WIRE SIZE
AWG mm
2
2
325 x 2P
1-4
Table 1-1. Typical Wire Sizing For Main Circuit - Continued*
DRIVE TERMINAL WIRE SIZE
NEW DRIVE OLD DRIVE
MODEL NO.TERMINAL SYMBOL SCREW AWG mm
MODEL NO. MODEL NO.
CIMR-G5M GPD515C–
TERMINAL SYMBOL
Section C. 600V
TERMINAL
SCREW
WIRE SIZE
AWG mm
51P51F C003, L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M4 14-10 2 - 5.5 52P21F C004 T2 (V),T3 (W)
53P71F C006 L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M4 14-10 2 - 5.5
T2 (V), T3 (W)
12-10 3.5-5.5
55P51F C010 L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M4 12-10 3.5-5.5
T2 (V), T3 (W)
57P51F C012 L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M4 10 5.5
T2 (V), T3 (W)
12-10 3.5-5.5
50111F C017 L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M5 10-6 5.5-14
T2 (V), T3 (W)
M6
50151F C022 L1 (R), L2 (S), L3 (T), , 1, 2, B1, B2, T1 (U), M5 8-6 8-14
T2 (V), T3 (W)
M6 10-6 5.5-14
50181F C027 L1 (R), L2 (S), L3 (T),
,
1, B1, B2, T1 (U), M6 8-6 8-14
50221F C032 T2 (V), T3 (W)
10-6 5.5-14
l
1 (r), l2(s) M4 14 - 10 2 - 5.5
50301F C041 L1 (R), L2 (S), L3 (T), ,⊕1, T1 (U), T2 (V), T3 (W) M8 6-1/0 14-50
8-2 8-30
l
1 (r), l2(s) M4 14 - 10 2 - 5.5
50371F C052 L1 (R), L2 (S), L3 (T), ,⊕1, T1 (U), T2 (V), T3 (W) M8 4-1/0 22-50
8-2 8-30
l
1 (r), l2(s) M4 14 - 10 2 - 5.5
50451F C062 L1 (R), L2 (S), L3 (T), ,⊕1, T1 (U), T2 (V), T3 (W) M8 3-1/0 30-50
8-2 8-30
l
1 (r), l2(s) M4 14 - 10 2 - 5.5
50551F C077 L1 (R), L2 (S), L3 (T), ,⊕1, T1 (U), T2 (V), T3 (W) M8 2-1/0 30-50
6-2 22-30
l
1 (r), l2(s) M4 14 - 10 2 - 5.5
50751F C099 L1 (R), L2 (S), L3 (T), ,⊕1, T1 (U), T2 (V), T3 (W) M8 2/0-1/0 50-60
4-2 22-30
l
1 (r), l2(s) M4 14 - 10 2 - 5.5
50900F C130 L1 (R), L2 (S), L3 (T), ,⊕1, T1 (U), T2 (V), T3 (W) M10 3/0-300 80-150
4-2/0 22-60
l
1 (r), l2(s) M4 14 - 10 2 - 5.5
51100F C172 L1 (R), L2 (S), L3 (T), ,⊕1, T1 (U), T2 (V), T3 (W) M12 300-400 150-200
4-2/0 22-60
l
1 (r), l2(s) M4 14 - 10 2 - 5.5
51600F C200 L1 (R), L2 (S), L3 (T), ,⊕1, T1 (U), T2 (V), T3 (W) M12 350-400 180-200
3-2/0 30-60
l
1 (r), l2(s) M4 14 - 10 2 - 5.5
2
2
* Consult local electrical codes for wire sizing requirements.
Indicates terminal uses a pressure lug.
1-5
Table 1-2. Terminal Functions and Voltages of Main Circuit
SECTION A. 230V
FUNCTION
New Model No. 20P41F -
TERMINAL CIMR-G5M 27P51F 20221F
TERMINAL FUNCTION
Old Model No.
L1 (R) L2 (S) L3 (T)
T1 (U) T2 (V) T3 (W)
B1 B2
1 HP 3 TO 40 HP GPD515C- A096
DB Resistor terminals (B1 & B2) – – – – – –
A003 - A033 A049 - A064
Three phase Main circuit input power supply 200 / 208 / 220V at 50 Hz; 200 / 208 / 220 / 230V at 60 Hz
Three phase AC output to motor 0V to max. input voltage level
SECTION A. 230V
20111F - 20151F
20181F
A080, -
20300F - 20750F
A130 - A300
1 DC Reactor terminals (1 & 2) 2 DC Bus terminals (1 & )
– – – – – –
⊕ 3 – – – – – – DB Unit terminals (⊕3 & )
l
1 (r) Power for heat sink fan:
l
2 (
s
)
– – – – – –
l
1 to l2 : 230 VAC
Ground terminal (100 ohms or less)
SECTION B. 460V
SECTION B. 460V
New Model No.
TERMINAL
TERMINAL FUNCTION 1 TO 60 HP
CIMR-G5M
Old Model No.
GPD515C-
L1 (R) L2 (S) L3 (T)
T1 (U) T2 (V) T3 (W)
B1 B2
DB Resistor terminals (B1 & B2) – – – – – –
40P41F -
B001 - B034 B041 - B096 B128 - B605
Three phase Main circuit input power supply 380 / 400 / 415 / 460V at 50/60 Hz
Three phase AC output to motor 0V to max. input voltage level
40151F 40181F - 40451F 40551F - 43000F
1 DC Reactor terminals (1 & 2) 2 DC Bus terminals (1 & )
FUNCTION
– – – – – –
⊕ 3 – – – – – – DB Unit terminals (⊕3 & )
l
1 (r) Power for heat sink fan: Power for heat sink fan:
l
2 (
s
l
2 200 (
l
2 400 (
)
s
200) – – – – – –
s
400)
l
1 to l2 : 230 VAC
– – – – – –
l
1 to l2 200: 230 Vac
l
1 to l2 400: 460 Vac
Ground terminal
– – – – – indicates that terminals are not present.
1-6
TERMINAL
Table 1-2. Terminal Functions and Voltages of Main Circuit
SECTION C. 600V
FUNCTION
New Model No.
CIMR-G5M
Old Model No.
GPD515C-
51P51F - 50151F 50181F - 50221F 50301F - 51600F
C003 - C022 C027 - C032 C041 - C200
L1 (R) L2 (S) L3 (T)
T1 (U) T2 (V) T3 (W)
B1 B2
12
l
1 (r) Power for heat sink fan:
l
2 (
s
)
DC Reactor terminals (1 & 2) DC Bus terminals (1 & )
Three phase Main circuit input power supply 500 / 575 / 600V at 50 Hz / 60HZ
Three phase AC output to motor 0V to max. input voltage level
DB Resistor terminals (B1 & B2)
DB Units terminals (1 & ) (C041 to C200 only) DC Bus terminals (1 & )
l
1 to l2 : 600 VAC
Ground terminal (100 ohms or less)
1-7
Main Circu i t Config u ration B l ock Diag r ams 230V
+
1
+
2
_
L1 (R)
L2 (S)
L3 (T)
+
Power Supply
Control Circuit
Cooling Fan
(A011 to A033 only)
(RCC)
U (T1)
V (T2)
W (T3)
B1
B2
(DCL Option)
CIMR-G5M20P41F to 27P51F
GPD515C-A003 to -A033
(DCL Option)
+ 1
+ 2
L1 (R)
L2 (S)
L3 (T)
_
+ 3
U (T1)
Power Supply
(RCC)
Cooling Fan
+
Control Circuit
V (T2)
W (T3)
CIMR-G5M20181F, 20221F
GPD515C-A080, -A096
When using DC input as main circuit power, connect 230Vac to control power transformer terminals l (r) and l (s).
CIMR-G5M20111F to 20151F
GPD515C-A049 to -A064
+ 1
+ 2
L1 (R)
L2 (S)
L3 (T)
_
Cooling Fan
Power Supply
(RCC)
Internal Cooling Fan
+ 3
+
Control Circuit
U (T1)
V (T2)
W (T3)
L1 (R)
L2 (S)
L3 (T)
_
Cooling Fan
Power Supply
(RCC)
Internal Cooling Fan
+ 3
+
Control Circuit
U (T1)
V (T2)
W (T3)
CIMR-G5M20300F to 20750F
GPD515C-A130 to -A300
When using DC input as main circuit power, connect 230Vac to control power transformer terminals l (r) and l (s).
1-8
Main Circu i t Config u ration B l ock Diag r ams 460V
+
1
+
2
_
L1 (R)
L2 (S)
L3 (T)
+
Power Supply
Control Circuit
Cooling Fan
(B008 to B034 only)
(RCC)
U (T1)
V (T2)
W (T3)
B1
B2
(DCL Option)
CIMR-G5M40P41F to 40151F
GPD515C- B001 to - B034
(RCC)
Internal Cooling Fan
+ 3
+
+ 1
+ 2
L1 (R)
L2 (S)
L3 (T)
_
Cooling Fan
Power Supply
CIMR-G5M40551F to 41600F
GPD515C- B128 to - B302
When using DC input as main circuit power, connect 460Vac to control power transformer terminals l
l
400 (s400).
2
Control Circuit
(r) and
1
U (T1)
V (T2)
W (T3)
CIMR-G5M40181F to 40451F
GPD515C- B041 to - B096
When using DC input as main circuit power, connect 460Vac to control power transformer terminals l1(r) and l2(s).
L1 (R)
L2 (S)
L3 (T)
_
Power Supply
(RCC)
Internal
Cooling Fan
Cooling Fan
+ 3
+
Control Circuit
U (T1)
V (T2)
W (T3)
+ 1
L1 (R)
L2 (S)
L3 (T)
_
Cooling Fan
Power Supply
(RCC)
+ 3
+
Control Circuit
U (T1)
V (T2)
W (T3)
CIMR-G5M41850F to 43000F
GPD515C- B340 to - B605
When using DC input as main circuit power, connect 460Vac to control power transformer terminals l
(r) and l2400 (s400).
1
1-9
Main Circu i t Config u ration B l ock Diag r ams 600V
+
1
+
2
_
L1 (R)
L2 (S)
L3 (T)
+
Power Supply
Control Circuit
Cooling Fan
(RCC)
U (T1)
V (T2)
W (T3)
B1
B2
(DCL Option)
CIMR-G5M51P51F to 50151F
GPD515C- C003 to - C022
When using DC input as main circuit power, connect 600Vac to control power transformer terminals r and s.
+ 1
L1 (R)
L2 (S)
L3 (T)
_
B2B1
U (T1)
Cooling Fan
Power Supply
+
(RCC)
Control Circuit
V (T2)
W (T3)
CIMR-G5M50301F to 51600F
GPD515C-C041 to -C200
When using DC input as main circuit power, connect 600Vac to control power transformer terminals r and s.
CIMR-G5M50181F to 50221F
GPD515C-C027 to -C032
When using DC input as main circuit power, connect 600Vac to control power transformer terminals r and s.
+ 1
L1 (R)
L2 (S)
L3 (T)
_
Power Supply
(RCC)
Cooling Fan
U (T1)
+
Control Circuit
V (T2)
W (T3)
1-10
1.4 . 2 G r o u n d i n g
The drive must be solidly grounded using the main circuit ground terminal.
If Drive is installed in a cabinet with other equipment, ground leads for all equipment should be
connected to a common low-impedance ground point within the cabinet.
The supply neutral should be connected to the ground point within the cabinet.
Select appropriate ground wire size from Table 1-1.
Make all ground wires as short as practical.
NEVER ground the drive in common with welding machines or other high power electrical
equipment.
Where several drives are used, ground each directly to the ground point (see Figure 1-1). DO NOT FORM A LOOP WITH THE GROUND LEADS.
When connecting a motor to the drives output terminals, include a separate ground wire. Attach ground wire solidly to motor frame and to drives ground terminal.
When using armored or shielded cable for connection between drive and motor, solidly connect armor or shield to motor frame, and to the drives ground terminal.
PREFERRED NOT RECOMMENDED NOT
ACCEPTABLE
A. Grounding of Three Drives
CORRECT NOT RECOMMENDED
B. Grounding of Drive & Vector Control Motor (VCM)
Figure 1-1. Grounding
1.4.3 A u x i l iary Input and Output Power O p tion Devices
A disconnect device (circuit breaker, contactor, disconnect switch, etc.) should NOT be used as a means of starting and stopping the drive or motor.
A disconnect device can be installed for emergency stop purposes, but when that disconnect device is opened, there may be loss of electrical braking.
1-11
Figure 1-2 is a factory guideline for proper wiring practices and relative locations within the electrical path from the line to the load. It does not imply what devices are needed for a particular application, nor does it show what devices were shipped with a particular order. Therefore, disregard those items in the diagram which are not being used in your installation. However, it
is
recommended that an input or DC reactor be used with models GPD515C-A003 thru -A064 (CIMR-G5M20P41F thru 20151F), -B001 thru -B034 (40P41F thru 40151F) , and -C003 thru -C062 (51P51F thru 51451F) when wired to a source of 600 kVA or greater. Mount all optional power devices close to the drive, and keep electrical connections as short as possible.
CUSTOMER'S
3Ø A.C. LINE
POWER
SUPPLY
NOTES
1. Connect drive ground terminal or panel to earth ground. Always use low impedance paths and connections.
2. Mount input and output RFI filters as close to the drive as possible (on the same panel, if possible). Filters should have a solid connection from filter ground terminal to the cabinet ground point. If multiple input or output RFI filters are used, they must be wired in parallel.
3. Shield individual conductors with metallic conduit, or use armored or shielded cable.
4. Connect output conduit armored cable or shielded cable in a manner that allows it to act as an unbroken shield from the drive panel to the motor casing.
5. RF noise filter (different from RFI filter) part no. 05P00325-0023 is a delta wye capacitor network which is wired in parallel with the drive input terminals. On the smaller drives with die cast chassis, it must be mounted externally. On the larger drives with sheet metal chassis, it may be mounted inside the area where the input power wiring enters the drive. On units equipped with bypass, it may be wired to the primary side of the circuit breaker and mounted to the bypass panel or sidewall.
6. Connection points:
L3
L2
L1
physically
Drive Terminals
Input
Power L1, L2, L3
ISOLATION
TRANSFORMER
H3
H2
H1
X3
X2
X1
RFI FILTER
C1(L3)
B1(L2)
A1(L1)
RF NOISE
FILTER
PANEL GROUND
SEE NOTE 2
PANEL GROUND
SEE NOTE 1
INPUT
(L3)C2
L
L
O
I
(L2)B2
A
N
D
E
(L1)A2
(G)
PANEL GROUND
SEE NOTE 5
OUTPUT
RFI FILTER
OUTPUT
REACTOR
SEE NOTE 2
SEE NOTE 6
OUTPUT
INPUT
REACTOR
C1
B1
A1
L3L2L1
INPUT
Drive
T2T1
1 2 3
IN
OUT
4 5 6
C2
B2
A2
SEE NOTE 3
DC
REACTOR
+ 1
+ 2
SEE NOTES 3, 4
PANEL GROUND SEE NOTE 2
SEE NOTES 3, 4
C1B1A1
C2B2A2
T3T2T1
Output Power
T1, T2, T3
Figure 1-2. Customer Connection Diagram For Isolation Transformers, Input
Reactors, Input RFI Filters, DC Reactors, Output Reactors and Output RFI FIlters
A.C. MOTOR
1-12
1.4.3a C onforman c e to European EMC D irective
In order to conform to EMC standards, the following methods are required for line filter application, cable shielding and drive installation. The following explains the outline of the methods.
The line filter and the drive must be mounted on the same metal plate. The filter should be mounted as close to the drive as practical. The cable must be kept as short as possible and the metal plate should be securely grounded. The ground of the line filter and the drive must be bonded to the metal plate with as much bare-metal contact as possible.
For main circuit input cables, a screened cable is recommended within the panel, and is also suggested for external connections. The screen of the cable should be connected to a solid ground. For the motor cables, a screened cable (max. 20 m) must be used and the screen of the motor cable should be connected to ground at both ends by a short connection, again using as much bare-metal contact as possible.
For more detailed explanation, refer to document EZZ006543, “Installation Guidelines For EMC Directive using Yaskawa AC Drive Products.”
Table 1-2.1 and Figure 1-2A show the line filter list for EMC standards and the installation/wiring of the drive and line filter.
Table 1 - 2 . 1 . L i n e Filters f o r Drive
New Drive Model Old Drive Model
Number Number Part Number Rated Mass Dimensions in mm
CIMR-G5M GPD 515C- 05P00325- Current (A) (kg) L x W x D
40P41F, B001, 40P71F B003 41P51F, B004, 43P71F, B008, 0103 20 1.8 320 x 143 x 46 44P01F B011 45P51F, B014, 47P51F B021 40111F, B027,
40151F B034
40181F, B041,
40221F B052 40301F B065 0108 100 13.8 420 x 200 x 130 40371F B080 0109 150 13.8 480 x 200 x 160 40451F B096 0110 160 25 480 x 200 x 160 40551F B128 0111 180 25 480 x 200 x 160
40750F, B165,
41100F B224 41600F B302 0113 400 45 588 x 250 x 200 41850F B340 0119 500 42200F B450 0120 600 43000F B605 0121 900
(1)
1mm = 0.0394 inches
(2)
D is the distance the filter will extend outward from the surface of the metal plate.
0106 8 1.8 320 x 143 x 46
0104 30 3.0 350 x 213 x 51
0105 60 5.3 435 x 268 x 56
0107 80 7.5 350 x 180 x 90
0112 300 25 480 x 200 x 160
Line Filter
Consult Factory
(1)
(2)
1-13
L2 PEL1 L3
LINE
FILTER
Ground Bonds (remove any paint)
GPD
515/G5
Cable Length
max. 40cm
Metal Plate
LOAD
T2 PET1 T3L1 L3PE L2
Motor Cable
max. 20m
Ground Bonds (remove any paint)
IM
Figure 1-2A. Installation of Line Filter and GPD 515/G5
3~
1-14
1 . 4 . 4 C o nt r o l C i r c u i t
TO GPD 515 SIGNAL TERMINALS
TO SHIELD SHEATH TERMINAL (TERM. 12)
WRAP BOTH ENDS OF SHEATH WITH
INSULATING TAPE
CRIMP CONNECTION
SHIELD SHEATH
OUTER JACKET
DO NOT CONNECT
TO EXTERNAL CIRCUIT
All basic control circuit (signal) interconnections are shown in the appropriate diagram:
Interconnections for external two-wire control in combination with the Digital Operator are shown in Figure 1-3.
Interconnections for external three-wire control in combination with the Digital Operator
are shown in Figure 1-4.
Make wire connections according to Figures 1-3, 1-4 and Table 1-3; observe the following:
Signal Leads: Terminals 1-8 & 11; 12-17 & 33; and 21-27.
Control Leads: Terminals 9 & 10 and 18-20.
Use twisted shielded or twisted-pair shielded wire (20-16 AWG [0.5 1.25mm2]) for
control and signal circuit leads. The shield sheath MUST be connected at the drive end ONLY (terminal 12). The other end should be dressed neatly and left unconnected
(floating). See Figure 1-2B.
Signal leads and feedback leads (PG) must be separated from control leads
main circuit leads and any other power cables to prevent erroneous operation caused
by electrical noise.
Lead length should NOT EXCEED 164 feet (50 meters). Wire sizes should be determined
considering the voltage drop.
All AC relays, contactors and solenoids should have RC surge supressors installed across their coils.
All DC relays, contactors and solenoids should have diodes installed across their coils.
Figure 1-2B. Shielded Sheath Termination
1-15
1-16
Table 1-3. Terminal Functions and Signals of Control Circuit
TERMINAL FUNCTIONS DESCRIPTION / SIGNAL LEVELS
TERMINAL FUNCTIONS LEVELS
1 2-WIRE CONTROL: Forward Run / Stop signal Run at closed, stop at open (See NOTE 2)
(See NOTE 1)
3-WIRE CONTROL: Run signal Run at closed (See NOTE 2)
2 2-WIRE CONTROL: Reverse Run / Stop signal Run at closed, stop at open (See NOTE 2)
(See NOTE 1)
3-WIRE CONTROL: Stop signal Stop at open (See NOTE 2)
3 External fault input Fault at closed (see NOTES 2 & 3). When the
External Fault input is applied, the drives Fault relay trips (shutdown) and the motor coasts to a stop. The Digital Operator displays EF3 failure.
4 Fault Reset input (external) Fault Reset at closed (see NOTES 2 & 3). The
Fault Reset input will reset the Fault relay, if the drive is in stopped condition. Both Forward Run/Stop signal and Reverse Run/Stop signal must be OPEN.
5 Multi-step Speed Reference 1 Effective when closed (See NOTES 2 & 3)
6 Multi-step Speed Reference 2 Effective when closed (See NOTES 2 & 3)
7 Jog Reference Run at preset jog frequency when closed
8 External baseblock Drive output stops when closed
9, 10 Multi-function contact output (N.O.). Contact capacity:
One of 18 functions are available, by setting 250 Vac at 1A or less of parameter H2-01 . 30 Vdc at 1A or less
11 Sequence control input common Sequence control input 0 V
for terminals 1-8.
12 Connection for shield sheath of signal leads – – – –
13 Frequency reference analog input (voltage); 0 to +10V (20K ohms)
auto input – can be changed to manual by –10 to +10V (20K ohms) setting of parameter H3-01 .
14 Frequency reference analog input (current); 4-20mA (250 ohms)
can be changed to voltage input by setting of parameter H3-08 and cutting jumper J1.
15 Frequency reference power supply +15V (Control power supply for frequency setting:
max 20 mA)
17 Frequency reference analog input common 0 V
18 Multi-function contact output Closed at fault
(N.O./N.C.). Contact capacity:
19 Open at fault 250 Vac at 1A or less
30 Vdc at 1A or less
20 Common
1-17
Table 1-3. Terminal Functions and Signals of Control Circuit - Continued
TERMINAL FUNCTIONS LEVELS
TERMINAL FUNCTIONS DESCRIPTION / SIGNAL LEVELS
21 Multi-function analog monitor 1 (+) Output current Type of analog signal (operation parameter) to be
22 Multi-function analog monitor (–)
23 Multi-function analog monitor 2 (+) selectable Monitor output: 0 to +11V; 2 mA maximum
25 Multi-function open collector One of 18 functions Photocoupler insulation output: +48V, 50 mA
output 1 available, by setting maximum
26 Multi-function open collector
output 2
27 Multi-function open collector output common 0V
33 Frequency reference power supply –15V Control power supply for frequency setting:
NOTES:
1 . When Fo rward Run and Rever se Run inputs are bot h closed for more tha n 500 ms, the Digital
Operato r display s a blinkin g EF alarm code an d the motor (if rotating) is decelerated by the dr ive to a sto p. This stop cond ition is n ot s tored by t he d rive (on Digital Operat or, red LED at
S T OP k ey does not l ight); IF ON E OF THE I NPU TS IS OPE N ED, THE M OTO R WIL L I MMEDIA T E L Y S T A R T U P A G AIN.
or output output is selected by setting of parameters H4-01 frequency is and H4-04 .
of parameters H2-02 and H2-03 .
max 20 mA
2 . Te rminals 1-8 sou rce +24 Vdc (8mA max.) and operat e in a Low = True (ON) confi guration when
co nn ected to ter mi nal 11 .
When us ing r elays for input to t erminals 1-8, use relays with high ly re li ab le co ntacts (for very sm al l current) wi th a ca pa ci ty of 3 0 Vdc o r more an d rated c ur re nt of 1 00 mA or h ig he r. W he n us in g transistor (open collect or ) input, us e transistors w it h rated v ol ta ge of 3 5 Vdc or more and rated curre nt of 100 mA or mor e.
3 . Th ese terminals are mul ti-func tion i nputs. The indicated fun ctions are their sett ings, based on a
2-Wir e r es et. F or 3-Wir e res et defin it ions, an d o th er setti ngs, see desc ripti on s f or Mult i­Fu nction In pu t Terminals , parameters H 1 - 0 1 t h ru H 1 - 0 6 , in paragraph 5.32.
1-18
1-19
1.4.5 I n t e r c o n n e c t i o n – 2 - W i r e C o n t r o l O p e r a t i o n - F i g u r e 1 - 3 .
Notes referred to in figure 1-3.
✱ – Indicates components not supplied.
✱✱– Bra nc h cir cu it pr ot ec tion (c ir cuit br eaker o r i np ut fuse s) m ust be supplied by custom er.
– Indicates cus tomer connectio n term inal. Wir e on ly to term in als shown. No te t ha t no t al l term inals
sh own are available in all rating s – see Tables 1-1 and 1-2.
( ) – Indicate s alte rnate terminal markin g, i.e ., (R) and L1.
– Function labels shown for t he se ter mi na ls are determi ne d by factory settings of pa ra meters
H 1 - 0 1 th rough H 1 - 0 6 . See paragraph 5. 32.
– Fu nc tion l ab els sh ow n for these terminals are d etermined by f ac to ry set ti ngs of parameter s
H 2 - 0 1 th rough H 2 - 0 3 . See paragraph 5. 33.
– F unction labels s ho wn for these terminals are determined by fa ctory se tt ings o f parame te rs
H 3 - 0 1, - 0 4, - 0 5, - 0 8, & - 0 9 . See paragraphs 5.19 & 5.30.
– Functi on l abels and signal levels sho wn f or the se t erminals are determ ined by factory setti ngs
of pa ra meters H 4 - 0 1 & H 4 - 0 4 . See paragraph 5.31.
1 . If only a remote M anual Speed pot (1RH) is used, 3SS is not neede d; in that case, a jumper must be
ad ded between termina ls 5 and 11. This jumper will overr ide both t he A uto and Di gital Operato r fr eq ue nc y references, r eg ar dl es s of th e programming o f parameter b 1 - 0 1 . If y ou a re usi ng a rem ote speed command or the Digital Operator, DO NOT in st al l this jumper. See paragraph 5.19.
2 . Th e Driv e Elec tronic Thermal Overlo ad fun ct ion (parameters L 1 - 0 1 , L 1 - 0 2 ) meets standar ds set by
UL a nd c UL for motor thermal overl oad prote ction. If local code r equires separate mec hanical o verload pr otection, an over lo ad r elay should be installe d, i nterlocke d wi th the dri ve a s show n. It shoul d be the ma nu al res et type to pr event au tomatic re start fo ll owing a motor fault and s ub sequent co ntact re closure a ft er cool d ow n.
3 . Insu la te d twiste d shielded wire i s requir ed .
2-condu ctor #18 GA. (B elden #87 60 or equival ent). 3-c onductor #18 GA. (Belden #8770 of equivale nt).
Connect shield ONLY AT DRIVE END. Stub and isolate other end.
4 . Digi tal Op erator is st andard on ev ery dr ive. Remote opera tors, as sho wn, ma y not be required.
5 . Cust om er t o connec t termin al to earth ground (100 or les s, 2 30V ; 1 0 o r l ess , 460V and 600V).
6 . Wi re only o ne of the i nputs a s an Auto Refere nce. If H 3 - 0 9 is s et to 1F , t ermin als 13 and 14 are
ad de d for the i nternal fr equency re ference.
7 . If the Dynamic Braki ng (DB ) opti on is used, wire per Appendix 6 instruct io ns.
8 . An optional DC reactor may be added for harmonic atte nuati on, if need ed; see separate i nstruction she et
for w i ring .
9 . If applica ti on doe s not allow reverse operatio n, b 1 - 0 4 , Revers e Run Prohib it , s ho ul d b e set to 1
(Reverse Run Disabled), and the Reverse Run/Stop inp ut ca n be eliminated.
1 0 . I f supplying t he drive wi th DC v ol ta ge instead of 3ø A C, remove j um pe rs from t erminals
and connect a separa te 1ø AC sup ply to l1 and l2 inste ad.
l1 and l2
1 1 . Use
l1 (R) and l2 ( S) f or singl e- ph as e in pu t. Not e that for drives up through GPD515C-A064, -B034, and
-C 032 (CI MR -G 5M 20 15 1F, 4 01 51 F, and 50221F) m us t be derated b y 50%. Co nsult f ac to ry for derating of lar ger dri ves .
1-20
MAN SPEED 1RH
SEE NOTE 1
ISOLATED AUTO REFERENCE SEE NOTE 6
1R
4-20mA
0-10V
FOR OPTIONAL DC REACTOR
SEE NOTE 8
FOR WIRING DYNAMIC BRAKING OPTION
SEE NOTE 7
1ø POWER SUPPLY (SEE NOTE 11)
3ø POWER SUPPLY (SEE NAMEPLATE DATA)
L1 L2 L3
+15Vdc
15
(20mA MAX)
MAN REF. IN
16
(0 TO ±10Vdc)
COM
17
SHIELD
12
4-20mA
14
(250
0 TO ±10Vdc
13
(20K
+ 1
+ 2
B2
NOTE 4
L1 L2 L3
(R) (S) (T) (r)
GPD 515/G5
DRIVE FWD REV REMOTE
SEE
DIGITAL OPERATOR JVOP-130
LOCAL
REMOTE
JOG
FWD REV
RUN STOP
MENU ESC
B1
OR
+ 3
(GPD515C-B041 thru -B096)
FACTORY SET FOR 460V
400/
380V
415V 440V 460V
Voltage Selector
–15Vdc
33
(20mA MAX)
(E)
G
(U) (V) (W)
T1 T2 T3
SEQ REF
DATA
ENTER
RESET
1CB ✱✱
1 2
COOLING
FAN
POWER
FAULT RESET
MULTI-STEP
FREQ SELECT
COAST STOP (BASE BLOCK)
RUN CONTACT
FAULT CONTACTS
ANALOG OUTPUT
ANALOG OUTPUT
OPEN
COLLECTOR
CIRCUIT
OPEN
COLLECTOR
CIRCUIT
(GPD515C-A080 [CIMR-G5M20151F] AND ABOVE; GPD515C-B041 [CIMR-G5M40151F] AND ABOVE; GPD515C-C027 [CIMR-G5M50221F] AND ABOVE)
FWD
REV
SEE NOTE 10
1
2
EXT. FAULT
3
4
TO
AUTO/MAN
TERM. 12
5
6
SEE
JOG SPEED
NOTE 1
7
8
11
0 VOLTS
RY1
RY2
RY2
9
10
18
19
20
21
22
23
25
26
27
TERMINALS 1-8: IF INPUT FROM RELAY CONTACTS: RATED 30Vdc OR MORE, 100mA OR MORE IF OPEN COLLECTOR INPUT: RATED 35Vdc OR MORE, 100mA OR MORE
RY CONTACTS CAPACITY: 1A AT 250Vac 1A AT 30Vdc
MULTI­FUNCTION OPEN COLLECTOR OUTPUTS CAPACITY: 50mA AT 48Vdc MAX.
(U) (V) (W)
T1 T2 T3
FWD
RUN/STOP
1SS
REV
RUN/STOP
EXT. FAULT
EXT. FAULT RESET
+
+
SEE NOTE 9
2SS
1PB
SEE NOTE 3
3SS
MULTI-FUNCTION MONITOR OUTPUT 0 to +10V or –10 to +10V, 2mA MAX.
AUTO
MAN
1OL
SEE NOTE 2
EARTH
GROUND
SEE NOTE 5
BASIC INTERCONNECT DIAGRAM FOR 2-WIRE CONTROL
Figure 1-3. 230, 460 or 600V Interconnections - 2-Wire Control
(with parameters b1-01 = 1, b1-02 = 1, H1-01 = 24, H1-02 = 14, H1-03 = 3,
H1-04 = 4, H1-05 = 6, and H1-06 = 8 )
See Figure 1-5 for Closed-loop PG connections
(T2)
(T1) (T3)
1-21
ALTERNATE MOTOR CONNECTION
AC MOTOR
(T2)
(T1) (T3)
1OL
SEE NOTE 2
AC MOTOR
1.4.6 I n t e r c o n n e c t i o n – 3 - W i r e C o n t r o l O peration F i g u r e 1 - 4 .
Notes referred to in figure 1-4.
✱ – Indicates components not supplied.
✱✱– B ra nch c ir cuit pr ot ection (circuit breaker or i np ut fu se s) m ust be supplied by cus tomer.
– Indicates cus tomer connectio n term inal. Wir e on ly to term in als shown. No te t ha t no t al l term inals
sh own are available in all rating s – see Tables 1-1 and 1-2.
( ) – Indicate s alte rnate terminal markin g, i.e ., (R) and L1.
– Function labels shown for t he se ter mi na ls are determi ne d by factory settings of pa ra meters H 1 - 0 1
th rough H 1 - 0 6 : H 1 - 0 1 = 2 4 , H 1 - 0 2 = 1 4, H 1 - 0 3 = 0 , H 1 - 0 4 = 3 , H 1 - 0 5 = 4 , H 1 - 0 6 = 6 . See paragraph 5. 32.
– Fu nc tion l ab els sh ow n for these terminals are d etermined by f ac to ry set ti ngs of parameter s
H 2 - 0 1 th rough H 2 - 0 3 . See paragraph 5. 33.
– F unction labels s ho wn for these terminals are determined by fa ctory se tt ings o f parame te rs
H 3 - 0 1, - 0 4, - 0 5, - 0 8, & - 0 9 . See paragraphs 5.19 & 5.30.
– Functi on l abels and signal levels sho wn f or the se t erminals are determ ined by factory setti ngs
of pa ra meters H 4 - 0 1 & H 4 - 0 4 . See paragraph 5.31.
1 . If only a remote M anual Speed pot (1RH) is used, 2SS is not neede d; in that case, a jumper must be
ad ded between termina ls 6 and 11. This jumper will overr ide both t he A uto and Di gital Operato r fr eq ue nc y references, r eg ar dl es s of th e programming o f parameter b 1 - 0 1 . If you are usin g a remote spe ed command or the Digital Operator, D O NOT install th is jumper. S ee parag ra ph 5.19.
2 . Th e Driv e Elec tronic Thermal Overlo ad fun ct ion (parameters L 1 - 0 1 , L 1 - 0 2 ) mee ts sta nd ards s et
by U L an d cUL for motor the rmal overlo ad protec tion. If local code re quires sepa rate mech anical ov er load p ro te ction, a n over lo ad relay should be installed, interlocked with the dr iv e as shown. It sh ould be the manual reset type to preven t au tomatic restart fol lowing a motor fault and subseq uent co nt ac t reclosure a ft er cool d ow n.
3 . Insu la te d twiste d shielded wire i s requir ed .
2-conductor #18 GA. (B elden #8760 or eq uivalent). 3-conducto r #18 GA. (Belden # 8770 of equivalent).
Connect shield ONLY AT DRIVE END. Stub and isolate other end.
4 . Digi tal Op erator is st andard on ev ery dr ive. Remote opera tors, as sho wn, ma y not be required.
5 . Cust om er t o connec t termin al to earth ground (100 or les s, 2 30V ; 1 0 o r l ess , 460V and 600V).
6 . Wi re only o ne of the i nputs a s an Auto Refere nce. If H 3 - 0 9 is s et to 1F , t ermin als 13 and 14 are
ad de d for the i nternal fr equency re ference.
7 . If the Dynamic Braki ng (DB ) opti on is used, wire per Appendix 6 instruct io ns.
8 . An optional DC reactor may be added for harmonic atte nuati on, if need ed; see separate i nstruction she et
for w i ring .
9 . If applica ti on doe s not allow reverse operatio n, b 1 - 0 4 , Revers e Run Prohib it , s ho ul d b e set to 1
(Reverse Run Disabled), and the Forward/Reverse input can be eliminated.
1 0 . I f supplying t he drive wi th DC v ol ta ge instead of 3ø A C, remove j um pe rs from t erminals
and connect a separa te 1ø AC sup ply to l1 and l2 inste ad.
1 1 . Use l1 (R) and l2 (S) for single-phase input . No te t ha t fo r dr iv es u p th ro ug h GP D5 15 C- A064, -B034, and
-C 032 (CIMR-G 5M 20 15 1F , 40151F, and 50221F ) must be derated by 50%. C on su lt factory fo r deratin g of lar ger dri ves .
l1 and l2
CAUTION
Before running, parameter A1-03 must be set to " 0 ". Resetting drive constant A1-03 to " 2220 " may cause the motor to run in the reverse direction WITHOUT A RUN COMMAND, and possibly result in damage to the equipment or personal injury.
1-22
MAN SPEED 1RH
2K / 2.5K
SEE NOTE 1
ISOLATED AUTO REFERENCE SEE NOTE 6
1R
4-20mA
0-10V
FOR OPTIONAL DC REACTOR
SEE NOTE 8
FOR WIRING DYNAMIC BRAKING OPTION
SEE NOTE 7
3ø POWER SUPPLY (SEE NAMEPLATE DATA)
L1 L2 L3
1CB ✱✱
2K
+15Vdc
15
(20mA MAX)
MAN REF. IN
16
(0 TO ±10Vdc)
L1 L2 L3
(R) (S) (T)
1 2
COOLING
FAN
POWER
GPD 515/G5
COM
17
SHIELD
12
4-20mA
14
(250
SEE
NOTE 4
0 TO ±10Vdc
13
(20K
+ 1
+ 2
B2
B1
OR
+ 3
(GPD515C-B041 thru -B096)
FACTORY SET FOR 460V
400/
380V
415V 440V 460V
Voltage Selector
–15Vdc
33
(20mA MAX)
(E)
G
DRIVE FWD REV REMOTE
DIGITAL OPERATOR JVOP-130
LOCAL
REMOTE
JOG
FWD REV
SEQ REF
MENU ESC
RUN STOP
(U) (V) (W)
T1 T2 T3
DATA
ENTER
RESET
FAULT RESET
FREQ SELECT
FAULT CONTACTS
ANALOG OUTPUT
ANALOG OUTPUT
OPEN
COLLECTOR
CIRCUIT
OPEN
COLLECTOR
CIRCUIT
(GPD515C-A080 [CIMR-G5M20151F] AND ABOVE;
GPD515C-B041 [CIMR-G5M40151F] AND ABOVE; GPD515C-C027 [CIMR-G5M50221F] AND ABOVE)
RUN
STOP
SEE NOTE 10
1
2
EXT. FAULT
3
4
TO
FWD/REV
TERM. 12
5
AUTO/MAN
MULTI-STEP
0 VOLTS
RUN CONTACT
JOG SPEED
RY1
RY2
RY2
6
7
SEE NOTE 1
8
11
9
10
18
19
20
21
22
23
25
26
27
TERMINALS 1-8: IF INPUT FROM RELAY CONTACTS: RATED 30Vdc OR MORE, 100mA OR MORE IF OPEN COLLECTOR INPUT: RATED 35Vdc OR MORE, 100mA OR MORE
RY CONTACTS CAPACITY: 1A AT 250Vac 1A AT 30Vdc
MULTI­FUNCTION OPEN COLLECTOR OUTPUTS CAPACITY: 50mA AT 48Vdc MAX.
(U) (V) (W)
RUN
1PB
STOP
2PB
EXT. FAULT
EXT. FAULT RESET
3PB
SEE NOTE 3
1SS
SEE NOTE 9
2SS
MULTI-FUNCTION
+
MONITOR OUTPUT 0 to +10V or
10 to +10V,
2mA MAX.
+
1OL
FWD
REV
AUTO
MAN
SEE NOTE 2
T1 T2 T3
EARTH
GROUND
SEE NOTE 5
BASIC INTERCONNECT DIAGRAM FOR 3-WIRE CONTROL
Figure 1-4. 230, 460 or 600V Interconnections - 3-Wire Control
(with parameters b1-01 = 1, b1-02 = 1, H1-01 = 24, H1-02 = 14, H1-03 = 0,
H1-04 = 3, H1-05 = 4, and H1-06 = 6 )
See Figure 1-5 for Closed-loop PG connections
(T2)
(T1) (T3)
AC MOTOR
1-23
ALTERNATE MOTOR CONNECTION
(T2)
(T1) (T3)
1OL
SEE NOTE 2
AC MOTOR
1.4.7 E n c o d e r F e e d b a c k
If either the Flux Vector (A1-02 = 3) or Volts Per Hertz with Encoder (A1-02 = 1) control method is desired, an encoder feedback board for the drive is required.
The drive can accept many types of encoder feedback. Table 1-4 shows which option board is needed for each type of encoder.
Table 1-4. E n coder f e edback option b oard t y pes.
Option
Boar d
PG-X 2
PG-W2*
Contr o l
M e t h o d ( s )
ALL
ALL
Elec t rical I n put
Schem e
Quadrature,
Line D r iver
Dual Input,
Quadrature, Line
Req uir ed Si gna ls Fr om Enc ode r
A + , A- , B+ , & B - ( Z + , Z - o p t io n a l )
A+, A-, B+, B-, (Z+, Z- optional)
Driver
PG-B2
PG-D2
PG-A2
ALL
All, Except
Flux Vector
All, Except
Flux Vector
Quadrature,
Single Ended
Line Driver
Single Ended
A, B, & Common
A+ & A-
A & Common
*Accepts inputs from two encoders. Primarily used with custom software.
The most common encoder used with the drive is the Quadrature, Line Driver style encoder. When an encoder of this type is used, a PG-X2 option board must be mounted onto the drive. The encoder then wires to the PG-X2 option board.
Table 1-5 and Figure 1-5 show connections for the PG-X2 and some typical encoders.
Table 1-5. Encoder (PG) Connection
PG-X2 EPC (1) DYNAPAR DYNAPAR LAKESHORE/
FUNCTION TERMINAL MODEL H-20 (2) HS-35 NORTHSTAR
TA1 755A (Pin #) SL-56
+12V (200mA) 1 White D D 6
0V 2 Black F F 1
+5V 3 No Connection No Connection No Connection No Connection
A+ 4 Red A A 3
A– 5 Green H H 8
B+ 6 Brown B B 2
B– 7 Yellow I I 7
SHIELD TA3 Shield E No Connection 10
( 1 )
For PG, EPC Model 755A, Orange and Blue wires are not used.
( 2 )
For PG, Dynapar H-20, pins C, G, and J are not used.
The PG-X2 card also has a connector TA2 which provides processed PG signal output for use by an external pulse monitor. This connection can be made according to Figure 1-5.
1-24
GPD 515/G5 panel or enclosure
Factory wiring TB1 to TA1
GPD 515/G5
PG-X2 Card
PG input per Table 1-9
300 KHz input max.
Pulse Monitor Ouptut
RS422 Compatible 300kHz ouptut max.
(2)
(2)
Line Receiver
TB1
10
(1)
1
2
3
4
5
6
7
8
9
120
120
120
Shield
P
P
P
TA1
P
P
P
P
1
2
3
4
5
6
7
8
9
10
TA3
Isolated Power Supply
+12V
0V
+5V
A+
A-
B+
B-
(3)
Z+
(3)
Z-
0V
Optical
Isolation
TA2
1
2
3
4
5
6
7
A+
A-
B+
B-
Z+
Z-
N/C
Line Driver
Pulse A
Pulse B
Pulse Z
E
NOTE: Wiring distance from GPD 515/G5 to pulse monitor: 100m or less.
(1)
Customer supplied.
(2)
Refer to Section 2.2b or 2.2d (PG-X2) to calculate frequency.
(3)
Z pulses not requred for most applications.
Figure 1-5. PG-X2 Card Input/Output Connections
Factory Connection
(to control terminal 12)
1-25
Loading...