Models: GPD515C- and CIMR-G5M Document Number: TM 4515
Section 1. RECEIVING AND INSTALLATION
1.1 G ENERA L
The GPD 515/G5, hereafter referred to as the drive, is a general purpose sine-coded pulse
width modulated AC motor drive which generates an adjustable voltage/frequency three
phase output for complete speed control of most conventional squirrel cage induction
motors. Automatic stall prevention and voltage boost prevents nuisance tripping during load
or line side transient conditions. The drive will not induce any voltage line notching distortion
back to the utility line and maintains a displacement power factor of not less than 0.98
throughout its speed range.
When properly installed, operated and maintained, the drive will provide a lifetime of
service. It is mandatory that the person who operates, inspects, or maintains this
equipment thoroughly read and understand this manual before proceeding.
This manual primarily describes the GPD 515/G5, but contains basic information for the
operator control station as well. This manual is equally applicable to drives labelled
GPD 515 or G5.
1.2 R ECEIV ING
The drive is thoroughly tested at the factory. After unpacking, verify the part numbers
with the purchase order (invoice). Any damages or shortages evident when the equipment
is received must be reported immediately to the commercial carrier who transported the
equipment. Assistance, if required, is available from your sales representative.
If the drive will be stored after receiving, keep it in its original packaging and store
according to storage temperature specifications in Appendix 2.
1.3 P H Y S ICAL INS TALL ATI ON
Location of the drive is important to achieve proper performance and normal operating life.
The unit should be installed in an area where it will be protected from:
• Direct sunlight, rain or moisture.
• Corrosive gases or liquids.
• Vibration, airborne dust or metallic particles.
When preparing to mount the drive, lift it by its base,
effective cooling as well as proper maintenance, the drive must be installed on a flat, nonflammable vertical surface (wall or panel) using four mounting screws. There MUST be a
MINIMUM 4.7 in. clearance above and below the drive to allow air flow over the heat sink
fins. A minimum 1.2 in. clearance is required on each side on the drive.
A GPD 515/G5 in a free-standing floor-mount cabinet must be positioned with enough
clear-ance for opening the door of the cabinet; this will ensure sufficient air space for
cooling. Make sure air entering the drive is below 113°F (45°C) (for protected chassis
drives), or below 104°F (40°C) (for NEMA 1 drives), by adding a fan or other cooling
device, if needed. See environmental specifications in Appendix 2.
ne v e r by the front cover. For
1-1
1.4 ELECT RICA L I NSTA LLAT ION
All basic interconnections (using the Digital Operator) are shown in Figures 1-3 and 1-4.
1 . 4 . 1 Ma i n C i r c u i t In p u t / O u t p u t
Complete wire interconnections according to Table 1-2, Figure 1-3 and Figure 1-4. Be sure to
observe the following:
• Use 600V vinyl-sheathed wire or equivalent. Wire size and type should be determined by local
electrical codes.
• Avoid routing power wiring near equipment sensitive to electrical noise.
• Avoid running input and output wiring in the same conduit.
• NEVER connect AC main power to output terminals T1(U), T2(V), and T3(W).
• NEVER allow wire leads to contact metal surfaces. Short-circuit may result.
• NEVER connect power factor correction capacitors to the drive output. Consult
Yaskawa when connecting noise filters to the drive output.
• WIRE SIZING MUST BE SUITABLE FOR CLASS I CIRCUITS.
• When connecting motor to drive’s output terminals, include a separate ground wire. Attach ground
wire solidly to motor frame and to drive’s ground terminal.
• When using armored or shielded cable for connection between drive and motor, solidly connect
armor or shield to motor frame, and to drive’s ground terminal.
• Motor lead length should NOT EXCEED 164 feet (50 meters), and motor wiring should be run in
a separate conduit from other power wiring. If lead length must exceed this distance, reduce
carrier frequency (see paragraph 5.8) and consult factory for proper installation procedures.
• Use UL listed closed loop connectors or CSA certified ring connectors sized for the selected wire
gauge. Install connectors using the correct crimp tool recommended by the connector
1 (r) Power for heat sink fan:Power for heat sink fan:
l
2 (
s
l
2 200 (
l
2 400 (
)
s
200) – – – – – –
s
400)
l
1 to l2 : 230 VAC
– – – – – –
l
1 to l2 200: 230 Vac
l
1 to l2 400: 460 Vac
Ground terminal
– – – – – indicates that terminals are not present.
1-6
TERMINAL
Table 1-2. Terminal Functions and Voltages of Main Circuit
SECTION C. 600V
FUNCTION
New Model No.
CIMR-G5M
Old Model No.
GPD515C-
51P51F - 50151F50181F - 50221F50301F - 51600F
C003 - C022C027 - C032C041 - C200
L1 (R)
L2 (S)
L3 (T)
T1 (U)
T2 (V)
T3 (W)
B1
B2
⊕ 1
⊕ 2
l
1 (r) Power for heat sink fan:
l
2 (
s
)
DC Reactor terminals (⊕1 & ⊕2)
DC Bus terminals (⊕1 & )
Three phase Main circuit input power supply
500 / 575 / 600V at 50 Hz / 60HZ
Three phase AC output to motor
0V to max. input voltage level
DB Resistor terminals (B1 & B2)
DB Units terminals (⊕1 & ) (C041 to C200 only)
DC Bus terminals (⊕1 & )
l
1 to l2 : 600 VAC
Ground terminal (100 ohms or less)
1-7
Main Circu i t Config u ration B l ock Diag r ams 230V
+
1
+
2
_
L1 (R)
L2 (S)
L3 (T)
+
Power
Supply
Control
Circuit
Cooling Fan
(A011 to A033 only)
(RCC)
U (T1)
V (T2)
W (T3)
B1
B2
(DCL
Option)
CIMR-G5M20P41F to 27P51F
GPD515C-A003 to -A033
(DCL
Option)
+ 1
+ 2
L1 (R)
L2 (S)
L3 (T)
_
+ 3
U (T1)
Power
Supply
(RCC)
Cooling Fan
+
Control
Circuit
V (T2)
W (T3)
CIMR-G5M20181F, 20221F
GPD515C-A080, -A096
When using DC input as main circuit
power, connect 230Vac to control power
transformer terminals l (r) and l (s).
CIMR-G5M20111F to 20151F
GPD515C-A049 to -A064
+ 1
+ 2
L1 (R)
L2 (S)
L3 (T)
_
Cooling Fan
Power
Supply
(RCC)
Internal
Cooling Fan
+ 3
+
Control
Circuit
U (T1)
V (T2)
W (T3)
L1 (R)
L2 (S)
L3 (T)
_
Cooling Fan
Power
Supply
(RCC)
Internal
Cooling Fan
+ 3
+
Control
Circuit
U (T1)
V (T2)
W (T3)
CIMR-G5M20300F to 20750F
GPD515C-A130 to -A300
When using DC input as main circuit
power, connect 230Vac to control power
transformer terminals l (r) and l (s).
1-8
Main Circu i t Config u ration B l ock Diag r ams 460V
+
1
+
2
_
L1 (R)
L2 (S)
L3 (T)
+
Power
Supply
Control
Circuit
Cooling Fan
(B008 to B034 only)
(RCC)
U (T1)
V (T2)
W (T3)
B1
B2
(DCL
Option)
CIMR-G5M40P41F to 40151F
GPD515C- B001 to - B034
(RCC)
Internal
Cooling Fan
+ 3
+
+ 1
+ 2
L1 (R)
L2 (S)
L3 (T)
_
Cooling Fan
Power
Supply
CIMR-G5M40551F to 41600F
GPD515C- B128 to - B302
When using DC input as main circuit
power, connect 460Vac to control
power transformer terminals l
l
400 (s400).
2
Control
Circuit
(r) and
1
U (T1)
V (T2)
W (T3)
CIMR-G5M40181F to 40451F
GPD515C- B041 to - B096
When using DC input as main circuit
power, connect 460Vac to control power
transformer terminals l1(r) and l2(s).
L1 (R)
L2 (S)
L3 (T)
_
Power
Supply
(RCC)
Internal
Cooling Fan
Cooling Fan
+ 3
+
Control
Circuit
U (T1)
V (T2)
W (T3)
+ 1
L1 (R)
L2 (S)
L3 (T)
_
Cooling Fan
Power
Supply
(RCC)
+ 3
+
Control
Circuit
U (T1)
V (T2)
W (T3)
CIMR-G5M41850F to 43000F
GPD515C- B340 to - B605
When using DC input as main
circuit power, connect 460Vac to
control power transformer
terminals l
(r) and l2400 (s400).
1
1-9
Main Circu i t Config u ration B l ock Diag r ams 600V
+
1
+
2
_
L1 (R)
L2 (S)
L3 (T)
+
Power
Supply
Control
Circuit
Cooling Fan
(RCC)
U (T1)
V (T2)
W (T3)
B1
B2
(DCL
Option)
CIMR-G5M51P51F to 50151F
GPD515C- C003 to - C022
When using DC input as main circuit
power, connect 600Vac to control
power transformer terminals r and s.
+ 1
L1 (R)
L2 (S)
L3 (T)
_
B2B1
U (T1)
Cooling Fan
Power
Supply
+
(RCC)
Control
Circuit
V (T2)
W (T3)
CIMR-G5M50301F to 51600F
GPD515C-C041 to -C200
When using DC input as main
circuit power, connect 600Vac to
control power transformer
terminals r and s.
CIMR-G5M50181F to 50221F
GPD515C-C027 to -C032
When using DC input as main circuit
power, connect 600Vac to control
power transformer terminals r and s.
+ 1
L1 (R)
L2 (S)
L3 (T)
_
Power
Supply
(RCC)
Cooling Fan
U (T1)
+
Control
Circuit
V (T2)
W (T3)
1-10
1.4 . 2 G r o u n d i n g
• The drive must be solidly grounded using the main circuit ground terminal.
• If Drive is installed in a cabinet with other equipment, ground leads for all equipment should be
connected to a common low-impedance ground point within the cabinet.
• The supply neutral should be connected to the ground point within the cabinet.
• Select appropriate ground wire size from Table 1-1.
• Make all ground wires as short as practical.
• NEVER ground the drive in common with welding machines or other high power electrical
equipment.
• Where several drives are used, ground each directly to the ground point (see Figure 1-1). DO
NOT FORM A LOOP WITH THE GROUND LEADS.
• When connecting a motor to the drive’s output terminals, include a separate ground wire. Attach
ground wire solidly to motor frame and to drive’s ground terminal.
• When using armored or shielded cable for connection between drive and motor, solidly connect
armor or shield to motor frame, and to the drive’s ground terminal.
PREFERREDNOT RECOMMENDEDNOT
ACCEPTABLE
A. Grounding of Three Drives
CORRECTNOT RECOMMENDED
B. Grounding of Drive & Vector Control Motor (VCM)
Figure 1-1. Grounding
1.4.3 A u x i l iary Input and Output Power O p tion Devices
A disconnect device (circuit breaker, contactor, disconnect switch, etc.) should NOT be used as a
means of starting and stopping the drive or motor.
A disconnect device can be installed for emergency stop purposes, but when that disconnect
device is opened, there may be loss of electrical braking.
1-11
Figure 1-2 is a factory guideline for proper wiring practices and relative locations within the electrical
path from the line to the load. It does not imply what devices are needed for a particular
application, nor does it show what devices were shipped with a particular order. Therefore,
disregard those items in the diagram which are not being used in your installation. However, it
is
recommended that an input or DC reactor be used with models GPD515C-A003 thru -A064
(CIMR-G5M20P41F thru 20151F), -B001 thru -B034 (40P41F thru 40151F) , and -C003 thru -C062
(51P51F thru 51451F) when wired to a source of 600 kVA or greater. Mount all optional power
devices close to the drive, and keep electrical connections as short as possible.
CUSTOMER'S
3Ø A.C. LINE
POWER
SUPPLY
NOTES
1. Connect drive ground terminal or panel to
earth ground. Always use low impedance
paths and connections.
2. Mount input and output RFI filters
as close to the drive as possible (on the same
panel, if possible). Filters should have a solid
connection from filter ground terminal to the
cabinet ground point. If multiple input or
output RFI filters are used, they must be
wired in parallel.
3. Shield individual conductors with metallic
conduit, or use armored or shielded cable.
4. Connect output conduit armored cable or
shielded cable in a manner that allows it to
act as an unbroken shield from the drive
panel to the motor casing.
5. RF noise filter (different from RFI filter) part
no. 05P00325-0023 is a delta wye capacitor
network which is wired in parallel with the
drive input terminals. On the smaller drives
with die cast chassis, it must be mounted
externally. On the larger drives with sheet
metal chassis, it may be mounted inside the
area where the input power wiring enters the
drive. On units equipped with bypass, it may
be wired to the primary side of the circuit
breaker and mounted to the bypass panel or
sidewall.
6. Connection points:
L3
L2
L1
physically
Drive Terminals
Input
Power L1, L2, L3
ISOLATION
TRANSFORMER
H3
H2
H1
X3
X2
X1
RFI FILTER
C1(L3)
B1(L2)
A1(L1)
RF NOISE
FILTER
PANEL GROUND
SEE NOTE 2
PANEL GROUND
SEE NOTE 1
INPUT
(L3)C2
L
L
O
I
(L2)B2
A
N
D
E
(L1)A2
(G)
PANEL GROUND
SEE NOTE 5
OUTPUT
RFI FILTER
OUTPUT
REACTOR
SEE NOTE 2
SEE NOTE 6
OUTPUT
INPUT
REACTOR
C1
B1
A1
L3L2L1
INPUT
Drive
T2T1
123
IN
OUT
456
C2
B2
A2
SEE NOTE 3
DC
REACTOR
+ 1
+ 2
SEE NOTES 3, 4
PANEL
GROUND
SEE NOTE 2
SEE NOTES 3, 4
C1B1A1
C2B2A2
T3T2T1
Output Power
T1, T2, T3
Figure 1-2. Customer Connection Diagram For Isolation Transformers, Input
Reactors, Input RFI Filters, DC Reactors, Output Reactors and Output RFI FIlters
A.C. MOTOR
1-12
1.4.3a C onforman c e to European EMC D irective
In order to conform to EMC standards, the following methods are required for line filter
application, cable shielding and drive installation. The following explains the outline of the
methods.
The line filter and the drive must be mounted on the same metal plate. The filter should
be mounted as close to the drive as practical. The cable must be kept as short as possible
and the metal plate should be securely grounded. The ground of the line filter and the
drive must be bonded to the metal plate with as much bare-metal contact as possible.
For main circuit input cables, a screened cable is recommended within the panel, and is
also suggested for external connections. The screen of the cable should be connected to
a solid ground. For the motor cables, a screened cable (max. 20 m) must be used and the
screen of the motor cable should be connected to ground at both ends by a short
connection, again using as much bare-metal contact as possible.
For more detailed explanation, refer to document EZZ006543, “Installation Guidelines For EMC
Directive using Yaskawa AC Drive Products.”
Table 1-2.1 and Figure 1-2A show the line filter list for EMC standards and the
installation/wiring of the drive and line filter.
Table 1 - 2 . 1 . L i n e Filters f o r Drive
New Drive ModelOld Drive Model
NumberNumberPart Number RatedMassDimensions in mm
CIMR-G5MGPD 515C-05P00325-Current (A)(kg)L x W x D
40P41F,B001,
40P71FB003
41P51F,B004,
43P71F,B008,0103201.8320 x 143 x 46
44P01FB011
45P51F,B014,
47P51FB021
40111F,B027,
40151FB034
40181F,B041,
40221FB052
40301FB065010810013.8420 x 200 x 130
40371FB080010915013.8480 x 200 x 160
40451FB096011016025480 x 200 x 160
40551FB128011118025480 x 200 x 160
40750F,B165,
41100FB224
41600FB302011340045588 x 250 x 200
41850FB3400119500
42200FB4500120600
43000FB6050121900
(1)
1mm = 0.0394 inches
(2)
D is the distance the filter will extend outward from the surface of the metal plate.
010681.8320 x 143 x 46
0104303.0350 x 213 x 51
0105605.3435 x 268 x 56
0107807.5350 x 180 x 90
011230025480 x 200 x 160
Line Filter
Consult Factory
(1)
(2)
1-13
L2PEL1L3
LINE
FILTER
Ground Bonds (remove any paint)
GPD
515/G5
Cable Length
max. 40cm
Metal Plate
LOAD
T2PET1T3L1L3PEL2
Motor Cable
max. 20m
Ground Bonds (remove any paint)
IM
Figure 1-2A. Installation of Line Filter and GPD 515/G5
3~
1-14
1 . 4 . 4 C o nt r o l C i r c u i t
TO GPD 515
SIGNAL
TERMINALS
TO SHIELD
SHEATH
TERMINAL
(TERM. 12)
WRAP BOTH ENDS
OF SHEATH WITH
INSULATING TAPE
CRIMP
CONNECTION
SHIELD SHEATH
OUTER JACKET
DO NOT
CONNECT
TO
EXTERNAL
CIRCUIT
All basic control circuit (signal) interconnections are shown in the appropriate diagram:
• Interconnections for external two-wire control in combination with the Digital Operator are
shown in Figure 1-3.
• Interconnections for external three-wire control in combination with the Digital Operator
are shown in Figure 1-4.
Make wire connections according to Figures 1-3, 1-4 and Table 1-3; observe the following:
• Signal Leads: Terminals 1-8 & 11; 12-17 & 33; and 21-27.
• Control Leads: Terminals 9 & 10 and 18-20.
• Use twisted shielded or twisted-pair shielded wire (20-16 AWG [0.5 – 1.25mm2]) for
control and signal circuit leads. The shield sheath MUST be connected at the drive end
ONLY (terminal 12). The other end should be dressed neatly and left unconnected
(floating). See Figure 1-2B.
• Signal leads and feedback leads (PG) must be separated from control leads
main circuit leads and any other power cables to prevent erroneous operation caused
by electrical noise.
• Lead length should NOT EXCEED 164 feet (50 meters). Wire sizes should be determined
considering the voltage drop.
• All AC relays, contactors and solenoids should have RC surge supressors installed across
their coils.
• All DC relays, contactors and solenoids should have diodes installed across their coils.
Figure 1-2B. Shielded Sheath Termination
1-15
1-16
Table 1-3. Terminal Functions and Signals of Control Circuit
TERMINALFUNCTIONSDESCRIPTION / SIGNAL LEVELS
TERMINALFUNCTIONSLEVELS
12-WIRE CONTROL: Forward Run / Stop signalRun at closed, stop at open (See NOTE 2)
(See NOTE 1)
3-WIRE CONTROL: Run signalRun at closed (See NOTE 2)
22-WIRE CONTROL: Reverse Run / Stop signalRun at closed, stop at open (See NOTE 2)
(See NOTE 1)
3-WIRE CONTROL: Stop signalStop at open (See NOTE 2)
3External fault inputFault at closed (see NOTES 2 & 3). When the
External Fault input is applied, the drive’s Fault
relay trips (shutdown) and the motor coasts to a
stop. The Digital Operator displays “EF3 ” failure.
4Fault Reset input (external)Fault Reset at closed (see NOTES 2 & 3). The
Fault Reset input will reset the Fault relay, if the
drive is in “stopped” condition. Both Forward
Run/Stop signal and Reverse Run/Stop signal
must be OPEN.
5Multi-step Speed Reference 1Effective when closed (See NOTES 2 & 3)
6Multi-step Speed Reference 2Effective when closed (See NOTES 2 & 3)
7Jog ReferenceRun at preset jog frequency when closed
One of 18 functions are available, by setting 250 Vac at 1A or less
of parameter H2-01 . 30 Vdc at 1A or less
11Sequence control input common Sequence control input 0 V
for terminals 1-8.
12Connection for shield sheath of signal leads– – – –
13Frequency reference analog input (voltage); 0 to +10V (20K ohms)
auto input – can be changed to manual by –10 to +10V (20K ohms)
setting of parameter H3-01 .
14Frequency reference analog input (current); 4-20mA (250 ohms)
can be changed to voltage input by setting of
parameter H3-08 and cutting jumper J1.
15Frequency reference power supply+15V (Control power supply for frequency setting:
max 20 mA)
17Frequency reference analog input common0 V
18Multi-function contact outputClosed at fault
(N.O./N.C.).Contact capacity:
19Open at fault250 Vac at 1A or less
30 Vdc at 1A or less
20Common
1-17
Table 1-3. Terminal Functions and Signals of Control Circuit - Continued
TERMINALFUNCTIONSLEVELS
TERMINALFUNCTIONSDESCRIPTION / SIGNAL LEVELS
21Multi-function analog monitor 1 (+) Output currentType of analog signal (operation parameter) to be
22Multi-function analog monitor (–)
23Multi-function analog monitor 2 (+) selectableMonitor output: 0 to +11V; 2 mA maximum
25Multi-function open collector One of 18 functions Photocoupler insulation output: +48V, 50 mA
output 1available, by settingmaximum
26Multi-function open collector
output 2
27Multi-function open collector output common0V
33Frequency reference power supply–15V Control power supply for frequency setting:
NOTES:
1 .When Fo rward Run and Rever se Run inputs are bot h closed for more tha n 500 ms, the Digital
Operato r display s a blinkin g “EF ” alarm code an d the motor (if rotating) is decelerated by the
dr ive to a sto p. This stop cond ition is n ot s tored by t he d rive (on Digital Operat or, red LED at
S T OP k ey does not l ight); IF ON E OF THE I NPU TS IS OPE N ED, THE M OTO R WIL L
I MMEDIA T E L Y S T A R T U P A G AIN.
or output output is selected by setting of parameters H4-01
frequency is and H4-04 .
of parameters H2-02
and H2-03 .
max 20 mA
2 .Te rminals 1-8 sou rce +24 Vdc (8mA max.) and operat e in a Low = True (ON) confi guration when
co nn ected to ter mi nal 11 .
When us ing r elays for input to t erminals 1-8, use relays with high ly re li ab le co ntacts (for very
sm al l current) wi th a ca pa ci ty of 3 0 Vdc o r more an d rated c ur re nt of 1 00 mA or h ig he r. W he n
us in g transistor (open collect or ) input, us e transistors w it h rated v ol ta ge of 3 5 Vdc or more and
rated curre nt of 100 mA or mor e.
3 .Th ese terminals are mul ti-func tion i nputs. The indicated fun ctions are their sett ings, based on a
2-Wir e r es et. F or 3-Wir e res et defin it ions, an d o th er setti ngs, see desc ripti on s f or “Mult iFu nction In pu t Terminals ”, parameters H 1 - 0 1 t h ru H 1 - 0 6 , in paragraph 5.32.
1-18
1-19
1.4.5 I n t e r c o n n e c t i o n – 2 - W i r e C o n t r o l O p e r a t i o n - F i g u r e 1 - 3 .
Notes referred to in figure 1-3.
✱ – Indicates components not supplied.
✱✱– Bra nc h cir cu it pr ot ec tion (c ir cuit br eaker o r i np ut fuse s) m ust be supplied by custom er.
– Indicates cus tomer connectio n term inal. Wir e on ly to term in als shown. No te t ha t no t al l term inals
sh own are available in all rating s – see Tables 1-1 and 1-2.
( ) – Indicate s alte rnate terminal markin g, i.e ., (R) and L1.
▲ – Function labels shown for t he se ter mi na ls are determi ne d by factory settings of pa ra meters
H 1 - 0 1 th rough H 1 - 0 6 . See paragraph 5. 32.
● – Fu nc tion l ab els sh ow n for these terminals are d etermined by f ac to ry set ti ngs of parameter s
H 2 - 0 1 th rough H 2 - 0 3 . See paragraph 5. 33.
♦ – F unction labels s ho wn for these terminals are determined by fa ctory se tt ings o f parame te rs
■ – Functi on l abels and signal levels sho wn f or the se t erminals are determ ined by factory setti ngs
of pa ra meters H 4 - 0 1 & H 4 - 0 4 . See paragraph 5.31.
1 . If only a remote M anual Speed pot (1RH) is used, 3SS is not neede d; in that case, a jumper must be
ad ded between termina ls 5 and 11. This jumper will overr ide both t he A uto and Di gital Operato r
fr eq ue nc y references, r eg ar dl es s of th e programming o f parameter b 1 - 0 1 . If y ou a re usi ng a rem ote
speed command or the Digital Operator, DO NOT in st al l this jumper. See paragraph 5.19.
2 . Th e Driv e Elec tronic Thermal Overlo ad fun ct ion (parameters L 1 - 0 1 , L 1 - 0 2 ) meets standar ds set by
UL a nd c UL for motor thermal overl oad prote ction. If local code r equires separate mec hanical o verload
pr otection, an over lo ad r elay should be installe d, i nterlocke d wi th the dri ve a s show n. It shoul d be the
ma nu al res et type to pr event au tomatic re start fo ll owing a motor fault and s ub sequent co ntact
re closure a ft er cool d ow n.
3 . Insu la te d twiste d shielded wire i s requir ed .
2-condu ctor #18 GA. (B elden #87 60 or equival ent). 3-c onductor #18 GA. (Belden #8770 of equivale nt).
Connect shield ONLY AT DRIVE END. Stub and isolate other end.
4 . Digi tal Op erator is st andard on ev ery dr ive. Remote opera tors, as sho wn, ma y not be required.
5 . Cust om er t o connec t termin al to earth ground (100 Ω or les s, 2 30V ; 1 0 Ω o r l ess , 460V and 600V).
6 . Wi re only o ne of the i nputs a s an Auto Refere nce. If H 3 - 0 9 is s et to “ 1F “, t ermin als 13 and 14 are
ad de d for the i nternal fr equency re ference.
7 . If the Dynamic Braki ng (DB ) opti on is used, wire per Appendix 6 instruct io ns.
8 . An optional DC reactor may be added for harmonic atte nuati on, if need ed; see separate i nstruction she et
for w i ring .
9 . If applica ti on doe s not allow reverse operatio n, b 1 - 0 4 , Revers e Run Prohib it , s ho ul d b e set to “ 1 ”
(Reverse Run Disabled), and the Reverse Run/Stop inp ut ca n be eliminated.
1 0 . I f supplying t he drive wi th DC v ol ta ge instead of 3ø A C, remove j um pe rs from t erminals
and connect a separa te 1ø AC sup ply to l1 and l2 inste ad.
l1 and l2
1 1 . Use
l1 (R) and l2 ( S) f or singl e- ph as e in pu t. Not e that for drives up through GPD515C-A064, -B034, and
-C 032 (CI MR -G 5M 20 15 1F, 4 01 51 F, and 50221F) m us t be derated b y 50%. Co nsult f ac to ry for derating
of lar ger dri ves .
1-20
MAN SPEED
1RH ✱
SEE NOTE 1
ISOLATED
AUTO
REFERENCE ✱
SEE NOTE 6
1R ✱
4-20mA
0-10V
FOR OPTIONAL
DC REACTOR
SEE NOTE 8
FOR WIRING
DYNAMIC
BRAKING
OPTION
SEE NOTE 7
1ø POWER SUPPLY (SEE NOTE 11)
3ø POWER SUPPLY (SEE NAMEPLATE DATA)
L1 L2 L3
+15Vdc
15
(20mA MAX)
♦
MAN REF. IN
16
(0 TO ±10Vdc)
COM
17
SHIELD
12
♦
4-20mA
14
(250
♦
0 TO ±10Vdc
13
(20K
+ 1
+ 2
B2
NOTE 4
L1 L2 L3
(R) (S) (T)(r)
GPD 515/G5
DRIVE FWD REV REMOTE
SEE
DIGITAL OPERATOR
JVOP-130
LOCAL
REMOTE
JOG
FWD
REV
RUNSTOP
MENUESC
B1
OR
+ 3
–
(GPD515C-B041 thru -B096)
FACTORY SET FOR 460V
400/
380V
415V 440V 460V
Voltage Selector
–15Vdc
33
(20mA MAX)
(E)
G
(U) (V) (W)
T1 T2 T3
SEQ REF
DATA
ENTER
RESET
1CB ✱✱
12
COOLING
FAN
POWER
FAULT RESET
MULTI-STEP
FREQ SELECT
COAST STOP
(BASE BLOCK)
RUN CONTACT
FAULT CONTACTS
ANALOG
OUTPUT
ANALOG
OUTPUT
OPEN
COLLECTOR
CIRCUIT
OPEN
COLLECTOR
CIRCUIT
(GPD515C-A080 [CIMR-G5M20151F] AND ABOVE;
GPD515C-B041 [CIMR-G5M40151F] AND ABOVE;
GPD515C-C027 [CIMR-G5M50221F] AND ABOVE)
FWD
REV
SEE NOTE 10
1
2
▲
EXT. FAULT
3
▲
4
TO
▲
AUTO/MAN
TERM. 12
5
▲
6
SEE
▲
JOG
SPEED
NOTE 1
7
▲
8
11
0 VOLTS
RY1
RY2
RY2
●
9
10
18
19
20
■
21
■
22
■
23
●
25
●
26
27
TERMINALS 1-8:
IF INPUT FROM RELAY CONTACTS:
RATED 30Vdc OR MORE,
100mA OR MORE
IF OPEN COLLECTOR INPUT:
RATED 35Vdc OR MORE,
100mA OR MORE
RY CONTACTS
CAPACITY:
1A AT 250Vac
1A AT 30Vdc
MULTIFUNCTION
OPEN
COLLECTOR
OUTPUTS
CAPACITY:
50mA AT 48Vdc MAX.
(U) (V) (W)
T1 T2 T3
FWD
RUN/STOP
1SS ✱
REV
RUN/STOP
EXT. FAULT ✱
EXT. FAULT RESET
+
–
+
SEE
NOTE 9
2SS ✱
1PB ✱
SEE
NOTE 3
3SS ✱
MULTI-FUNCTION
MONITOR OUTPUT
0 to +10V or
–10 to +10V,
2mA MAX.
AUTO
MAN
1OL ✱
SEE
NOTE
2
EARTH
GROUND
SEE NOTE 5
BASIC INTERCONNECT DIAGRAM FOR 2-WIRE CONTROL
Figure 1-3. 230, 460 or 600V Interconnections - 2-Wire Control
■ – Functi on l abels and signal levels sho wn f or the se t erminals are determ ined by factory setti ngs
of pa ra meters H 4 - 0 1 & H 4 - 0 4 . See paragraph 5.31.
1 . If only a remote M anual Speed pot (1RH) is used, 2SS is not neede d; in that case, a jumper must be
ad ded between termina ls 6 and 11. This jumper will overr ide both t he A uto and Di gital Operato r
fr eq ue nc y references, r eg ar dl es s of th e programming o f parameter b 1 - 0 1 . If you are usin g a
remote spe ed command or the Digital Operator, D O NOT install th is jumper. S ee parag ra ph 5.19.
2 . Th e Driv e Elec tronic Thermal Overlo ad fun ct ion (parameters L 1 - 0 1 , L 1 - 0 2 ) mee ts sta nd ards s et
by U L an d cUL for motor the rmal overlo ad protec tion. If local code re quires sepa rate mech anical
ov er load p ro te ction, a n over lo ad relay should be installed, interlocked with the dr iv e as shown. It
sh ould be the manual reset type to preven t au tomatic restart fol lowing a motor fault and subseq uent
co nt ac t reclosure a ft er cool d ow n.
3 . Insu la te d twiste d shielded wire i s requir ed .
2-conductor #18 GA. (B elden #8760 or eq uivalent). 3-conducto r #18 GA. (Belden # 8770 of equivalent).
Connect shield ONLY AT DRIVE END. Stub and isolate other end.
4 . Digi tal Op erator is st andard on ev ery dr ive. Remote opera tors, as sho wn, ma y not be required.
5 . Cust om er t o connec t termin al to earth ground (100 Ω or les s, 2 30V ; 1 0 Ω o r l ess , 460V and 600V).
6 . Wi re only o ne of the i nputs a s an Auto Refere nce. If H 3 - 0 9 is s et to “ 1F “, t ermin als 13 and 14 are
ad de d for the i nternal fr equency re ference.
7 . If the Dynamic Braki ng (DB ) opti on is used, wire per Appendix 6 instruct io ns.
8 . An optional DC reactor may be added for harmonic atte nuati on, if need ed; see separate i nstruction she et
for w i ring .
9 . If applica ti on doe s not allow reverse operatio n, b 1 - 0 4 , Revers e Run Prohib it , s ho ul d b e set to “ 1 ”
(Reverse Run Disabled), and the Forward/Reverse input can be eliminated.
1 0 . I f supplying t he drive wi th DC v ol ta ge instead of 3ø A C, remove j um pe rs from t erminals
and connect a separa te 1ø AC sup ply to l1 and l2 inste ad.
1 1 . Use l1 (R) and l2 (S) for single-phase input . No te t ha t fo r dr iv es u p th ro ug h GP D5 15 C- A064, -B034, and
-C 032 (CIMR-G 5M 20 15 1F , 40151F, and 50221F ) must be derated by 50%. C on su lt factory fo r deratin g
of lar ger dri ves .
l1 and l2
CAUTION
Before running, parameter A1-03 must be set to " 0 ". Resetting drive constant A1-03
to " 2220 " may cause the motor to run in the reverse direction WITHOUT A RUN
COMMAND, and possibly result in damage to the equipment or personal injury.
1-22
MAN SPEED
1RH ✱
2K / 2.5K
SEE NOTE 1
ISOLATED
AUTO
REFERENCE ✱
SEE NOTE 6
1R ✱
4-20mA
0-10V
FOR OPTIONAL
DC REACTOR
SEE NOTE 8
FOR WIRING
DYNAMIC
BRAKING
OPTION
SEE NOTE 7
3ø POWER SUPPLY (SEE NAMEPLATE DATA)
L1 L2 L3
1CB ✱✱
2K
+15Vdc
15
(20mA MAX)
♦
MAN REF. IN
16
(0 TO ±10Vdc)
L1 L2 L3
(R) (S) (T)
12
COOLING
FAN
POWER
GPD 515/G5
COM
17
SHIELD
12
♦
4-20mA
14
(250
SEE
NOTE 4
♦
0 TO ±10Vdc
13
(20K
+ 1
+ 2
B2
B1
OR
+ 3
–
(GPD515C-B041 thru -B096)
FACTORY SET FOR 460V
400/
380V
415V 440V 460V
Voltage Selector
–15Vdc
33
(20mA MAX)
(E)
G
DRIVE FWD REV REMOTE
DIGITAL OPERATOR
JVOP-130
LOCAL
REMOTE
JOG
FWD
REV
SEQ REF
MENUESC
RUNSTOP
(U) (V) (W)
T1 T2 T3
DATA
ENTER
RESET
FAULT RESET
FREQ SELECT
FAULT CONTACTS
ANALOG
OUTPUT
ANALOG
OUTPUT
OPEN
COLLECTOR
CIRCUIT
OPEN
COLLECTOR
CIRCUIT
(GPD515C-A080 [CIMR-G5M20151F] AND ABOVE;
GPD515C-B041 [CIMR-G5M40151F] AND ABOVE;
GPD515C-C027 [CIMR-G5M50221F] AND ABOVE)
RUN
STOP
SEE NOTE 10
1
2
▲
EXT. FAULT
3
▲
4
TO
▲
FWD/REV
TERM. 12
5
▲
AUTO/MAN
MULTI-STEP
0 VOLTS
RUN CONTACT
JOG
SPEED
RY1
RY2
RY2
6
▲
7
SEE
NOTE 1
▲
8
11
●
9
10
18
19
20
■
21
■
22
■
23
●
25
●
26
27
TERMINALS 1-8:
IF INPUT FROM RELAY CONTACTS:
RATED 30Vdc OR MORE,
100mA OR MORE
IF OPEN COLLECTOR INPUT:
RATED 35Vdc OR MORE,
100mA OR MORE
RY CONTACTS
CAPACITY:
1A AT 250Vac
1A AT 30Vdc
MULTIFUNCTION
OPEN
COLLECTOR
OUTPUTS
CAPACITY:
50mA AT 48Vdc MAX.
(U) (V) (W)
RUN
1PB ✱
STOP
2PB ✱
EXT. FAULT ✱
EXT. FAULT RESET
3PB ✱
SEE
NOTE 3
1SS ✱
SEE NOTE 9
2SS ✱
MULTI-FUNCTION
+
MONITOR OUTPUT
0 to +10V or
–
–10 to +10V,
2mA MAX.
+
1OL ✱
FWD
REV
AUTO
MAN
SEE
NOTE
2
T1 T2 T3
EARTH
GROUND
SEE NOTE 5
BASIC INTERCONNECT DIAGRAM FOR 3-WIRE CONTROL
Figure 1-4. 230, 460 or 600V Interconnections - 3-Wire Control
If either the Flux Vector (A1-02 = 3) or Volts Per Hertz with Encoder (A1-02 = 1) control method is
desired, an encoder feedback board for the drive is required.
The drive can accept many types of encoder feedback. Table 1-4 shows which option board is
needed for each type of encoder.
Table 1-4. E n coder f e edback option b oard t y pes.
Option
Boar d
PG-X 2
PG-W2*
Contr o l
M e t h o d ( s )
ALL
ALL
Elec t rical I n put
Schem e
Quadrature,
Line D r iver
Dual Input,
Quadrature, Line
Req uir ed Si gna ls Fr om Enc ode r
A + , A- , B+ , & B - ( Z + , Z - o p t io n a l )
A+, A-, B+, B-, (Z+, Z- optional)
Driver
PG-B2
PG-D2
PG-A2
ALL
All, Except
Flux Vector
All, Except
Flux Vector
Quadrature,
Single Ended
Line Driver
Single Ended
A, B, & Common
A+ & A-
A & Common
*Accepts inputs from two encoders. Primarily used with custom software.
The most common encoder used with the drive is the Quadrature, Line Driver style
encoder. When an encoder of this type is used, a PG-X2 option board must be
mounted onto the drive. The encoder then wires to the PG-X2 option board.
Table 1-5 and Figure 1-5 show connections for the PG-X2 and some typical encoders.
Table 1-5. Encoder (PG) Connection
PG-X2 EPC (1)DYNAPARDYNAPARLAKESHORE/
FUNCTIONTERMINAL MODEL H-20 (2)HS-35NORTHSTAR
TA1 755A(Pin #)SL-56
+12V (200mA)1WhiteDD6
0V2BlackFF1
+5V3No Connection No Connection No Connection No Connection
A+4RedAA3
A–5GreenHH8
B+6BrownBB2
B–7YellowII7
SHIELDTA3ShieldENo Connection10
( 1 )
For PG, EPC Model 755A, Orange and Blue wires are not used.
( 2 )
For PG, Dynapar H-20, pins C, G, and J are not used.
The PG-X2 card also has a connector TA2 which provides processed PG signal output for
use by an external pulse monitor. This connection can be made according to Figure 1-5.
1-24
GPD 515/G5
panel or
enclosure
Factory wiring —
TB1 to TA1
GPD 515/G5
PG-X2 Card
PG input
per
Table 1-9
300 KHz
input max.
Pulse
Monitor
Ouptut
RS422
Compatible
300kHz
ouptut max.
(2)
(2)
Line Receiver
TB1
10
(1)
1
2
3
4
5
6
7
8
9
120 ‰
120 ‰
120 ‰
Shield
P
P
P
TA1
P
P
P
P
1
2
3
4
5
6
7
8
9
10
TA3
Isolated Power Supply
+12V
0V
+5V
A+
A-
B+
B-
(3)
Z+
(3)
Z-
0V
Optical
Isolation
TA2
1
2
3
4
5
6
7
A+
A-
B+
B-
Z+
Z-
N/C
Line Driver
Pulse
A
Pulse
B
Pulse
Z
E
NOTE:
Wiring distance from GPD 515/G5
to pulse monitor: 100m or less.
(1)
Customer supplied.
(2)
Refer to Section 2.2b or 2.2d (PG-X2) to calculate frequency.
(3)
Z pulses not requred for most applications.
Figure 1-5. PG-X2 Card Input/Output Connections
Factory Connection
(to control terminal 12)
1-25
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.