Xantrex Technology Inc. is a world-leading supplier of advanced power electronics and controls with products from
50 watt mobile units to 1.5 MW utility-scale systems for wind, solar, batteries, fuel cells, microturbines, and backup
power applications in both grid-connected and stand-alone systems. Xantrex products include inverters, battery
chargers, programmable power supplies, and variable speed drives that convert, supply, control, clean, and distribute
electrical power.
Trademarks
PV225S 225 kW Grid-Tied Photovoltaic Inverter is a trademark of Xantrex International. Xantrex is a registered
trademark of Xantrex International.
Other trademarks, registered trademarks, and product names are the property of their respective owners and are used
herein for identification purposes only.
UNLESS SPECIFICALLY AGREED TO IN WRITING, XANTREX TECHNOLOGY INC. (“XANTREX”)
(a) MAKES NO WARRANTY AS TO THE ACCURACY, SUFFICIENCY OR SUITABILITY OF ANY
TECHNICAL OR OTHER INFORMATION PROVIDED IN ITS MANUALS OR OTHER DOCUMENTATION.
(b) ASSUMES NO RESPONSIBILITY OR LIABILITY FOR LOSS OR DAMAGE, WHETHER DIRECT,
INDIRECT, CONSEQUENTIAL OR INCIDENTAL, WHICH MIGHT ARISE OUT OF THE USE OF SUCH
INFORMATION. THE USE OF ANY SUCH INFORMATION WILL BE ENTIRELY AT THE USER’S RISK.
Date and Revision
April 2005 Revision A
Part Number
152606 Rev A
Contact Information
Telephone:1 800 670 0707 (toll free North America)
1 360 925 5097 (direct)
Fax:1 800 994 7828 (toll free North America)
1 360 925 5143 (direct)
Email:customerservice@xantrex.com
Web:www.xantrex.com
About This Manual
Purpose
The purpose of this Planning and Installation Manual is to provide explanations
and procedures for planning and installing the PV225S 225 kW Grid-Tied
Photovoltaic Inverter.
Scope
The Manual provides safety guidelines, detailed planning and setup information,
and procedures for installing the inverter.
Audience
The Manual is intended for use by anyone who plans to construct or install a
system involving the PV225S 225 kW Grid-Tied Photovoltaic Inverter. Installers
must meet all local and state code requirements for licensing and training for the
installation of Electrical Power Systems with AC and DC voltage to 600 volts.
Organization
This Manual is organized into four chapters:
Chapter 1, “Introduction” provides information about the features and functions
of the PV225S 225 kW Grid-Tied Photovoltaic Inverter.
Chapter 2, “Planning” provides information to help plan the installation of the
PV225S 225 kW Grid-Tied Photovoltaic Inverter.
Chapter 3, “Installation” describes the procedures needed to install the PV225S
225 kW Grid-Tied Photovoltaic Inverter. This section includes unpacking and
moving instructions, mounting instructions, and cabling instructions.
Chapter 4, “Verification” provides a checklist to ensure the installation of the
PV225S is correct and complete.
152606 Rev Aiii
About This Manual
Conventions Used
The following conventions are used in this guide.
WARNING
Warnings identify conditions or practices that could result in personal injury or loss of life.
CAUTION
Cautions identify conditions or practices that could result in damage to the unit or other
equipment.
Important:
serious as a caution or warning.
These notes describe things which are important for you to know, but not as
Abbreviations and Acronyms
ANSIAmerican National Standards Institute
CCU2Converter Control Unit 2
CFMCubic Feet per Minute
CWClockwise
DSPDigital Signal Processor
FPGAField Programmable Gate Array
GUIGraphical User Interface
IEEEInstitute of Electrical and Electronics Engineers
IGBTInsulated Gate Bipolar Transistor
IPMIntelligent Power Module
kcmil1000 circular mils
LANLocal Area Network
LCDLiquid Crystal Display
NFPANational Fire Protection Association
PBXPrivate Branch Exchange
PSLPhase-Shift Loop
POTSPlain Old Telephone Service
PVPhotovoltaic
UFCUUniversal Frontpanel Control Unit
Related Information
You can find more information about Xantrex Technology Inc. as well as its
products and services at www.xantrex.com.
iv152606 Rev A
Important Safety Instructions
SAVE THESE INSTRUCTIONS - DO NOT DISCARD
This manual contains important safety instructions for the PV225S that shall be
followed during installation and maintenance procedures.
WARNING: Shock Hazard
Read and keep this Planning and Installation Manual for future reference. Before
installing the PV225S, read all instructions, cautionary markings, and all other appropriate
sections of this manual. Failure to adhere to these warnings could result in severe shock or
possible death. Exercise extreme caution at all times to prevent accidents.
WARNING: Shock Hazard
The PV225S enclosures contain exposed high-voltage conductors. The enclosure doors
should remain closed with the latches tightened, except during installation, maintenance
or testing. These servicing instructions are for use by qualified personnel who meet all
local and state code requirements for licensing and training for the installation of
Electrical Power Systems with AC and DC voltage to 600 volts. To reduce the risk of
electric shock, do not perform any servicing other than that specified in the installation
instructions unless you are qualified to do so. Do not open the cabinet doors if extreme
moisture is present (rain or heavy dew).
WARNING: Lethal Voltage
In order to remove all sources of voltage from the PV225S, the incoming power must be
de-energized at the source. This may be done at the main utility circuit breaker and by
opening the AC Disconnect and the DC Disconnect Switches on the PV225S. Review the
system configuration to determine all of the possible sources of energy. In addition, allow
5 minutes for the DC bus capacitors, located on the ceiling of the cabinet, to discharge
after removing power.
152606 Rev Av
Safety
General Safety Precautions
1. When installing the PV225S use only components recommended or sold by
Xantrex. Doing otherwise may result in a risk of fire, electric shock, injury to
persons, and will void the warranty.
2. Do not attempt to operate the PV225S if it has been dropped, or received more
than cosmetic damage during transport or shipping. If the PV225S is
damaged, or suspected to be damaged, see the Warranty for this unit in the
PV225S 225 kW Grid-Tied Photovoltaic Inverter Operation and Maintenance
Manual.
3. To reduce the risk of electrical shock, lock-out and tag the PV225S before
attempting any maintenance, service, or cleaning.
Personal Safety
Follow these instructions to ensure your safety while working with the PV225S.
Safety Equipment
Authorized service personnel must be equipped with standard safety equipment
including the following:
•Safety glasses
•Ear protection
•Steel-toed safety boots
•Safety hard hats
•Padlocks and tags
•Appropriate meter to verify that the circuits are de-energized
(600 Vac and DC rated, minimum)
Check local safety regulations for other requirements.
Wiring Requirements
1. All wiring methods and materials shall be in accordance with the National
Electrical Code ANSI/NFPA 70. When sizing conductors and conduits
interfacing to the PV225S, both shall be in accordance with the National
Electric Code ANSI/NFPA 70, as well as all state and local code
requirements.
2. Use copper conductors only with insulation rated for 90 °C.
3. The PV225S has a three-phase output. It is marked with this symbol:
4. The AC power conductor wiring interfacing with the AC terminals in the
Transformer Enclosure are located at T6-X1, T6-X2, and T6-X3. These
terminals should be tightened to a torque value of 420 in-lbs (47.5 Nm).
Conductors terminated to these terminals must use a crimp-on type ring
vi152606 Rev A
Safety
terminal or compression-type lug. The terminals can accommodate up to two
conductors per phase. See Figure 3-14 on page 3–15 for the location of these terminals.
5. The AC power conductor wiring interfacing with the AC terminals in the
Main Inverter Enclosure are located at TB5, TB6, and TB7. These terminals
are to be tightened to a torque value of 375 in-lbs (42.4 Nm). The terminals
will accept a conductor size of 350 kcmil and can accommodate up to six
conductors per phase. See Figure 3-15 on page 3–16 for the location of these
terminals.
6. The AC power conductor wiring interfacing with the AC terminals in the
AC Interface Enclosure are located at S1-2T1, S1-4T2, and S1-6T3. These
terminals should be tightened to a torque value of 310 in-lbs (35.0 Nm). See
Figure 3-16 on page 3–16 for the location of these terminals.
7. The AC neutral conductor from the utility is terminated in the AC Interface
Enclosure at the TB11 terminal. This terminal requires the use of a crimp-on
type ring terminal or compression-type lug and should be tightened to a
torque value of 228 in-lbs (25.7 Nm).See Figure 3-18 on page 3–18 for the
location of these terminals.
8. The DC power conductor wiring interfacing with the DC terminals at S2-6,
K2-6T3, and TB4 are to be tightened to a torque value of 600 in-lbs
(67.8 Nm). These terminals will accept a conductor size of 600 kcmil and can
accommodate up to four conductors per pole at S2-6 and K2-6T3 and up to
two conductors at TB4. Keep these cables together as much as possible and
ensure that all cables pass through the same knockout and conduit fittings,
thus allowing any inductive currents to cancel. See Figure 3-19 on page 3–19
for the location of these terminals.
9. This product is intended to be installed as part of a permanently grounded
electrical system per the National Electric Code ANSI/NFPA 70. A copper
ground rod must be installed within three feet of the PV225S enclosure. This
is the single point earth ground for the inverter system. The single point
ground for the system is to be made at the AC ground bus bar (TB12) in the
AC Interface Enclosure. This terminal requires the use of a crimp-on type ring
terminal or compression-type lug and should be tightened to a torque value of
420 in-lb (47.5 Nm).
10. The equipment grounds on the PV225S are marked with this symbol:
11. AC overcurrent protection for the utility interconnect (Grid-tie) must be
provided by the installers as part of the PV225S installation.
CAUTION: Fire Hazard
In accordance with the National Electrical Code, ANSI/NFPA 70, connect only to a circuit
provided with 400 amperes maximum branch circuit overcurrent protection for the
PV225S-480.
152606 Rev Avii
Safety
Operational Safety Procedures
Never work alone when servicing this equipment. A team of two is required until
the equipment is properly de-energized, locked-out and tagged, and verified deenergized with a meter.
Thoroughly inspect the equipment prior to energizing. Verify that no tools or
equipment have inadvertently been left behind.
Lockout and Tag
Safety requirements mandate that this equipment not be serviced while energized.
Power sources for the PV225S must be locked-out and tagged prior to servicing.
A padlock and tag should be installed on each energy source prior to
servicing.
WARNING: Shock Hazard
Review the system schematic for the installation to verify that all available energy sources
are de-energized. DC bus voltage may also be present. Be sure to wait the full 5 minutes to
allow the capacitors to discharge completely.
The PV225S can be energized from both the AC source and the DC source. To
ensure that the inverter is de-energized prior to servicing, lockout and tag the
PV225S using the following procedure.
1. Open, lockout, and tag the incoming power at the utility main circuit breaker.
2. Open, lockout, and tag the AC Disconnect Switch (S1) on the AC Interface
Enclosure. See Figure 1-4 on page 1–9 for the location of the AC Disconnect
Switch.
3. Open, lockout, and tag the DC Disconnect Switch (S2) on the DC Interface
Enclosure. See Figure 1-4 on page 1–9 for the location of the DC Disconnect
Switch.
4. Using a confirmed, accurate meter, verify all power to the inverter is deenergized. A confirmed, accurate meter must be verified on a known voltage
before use. Ensure that all incoming energy sources are de-energized by
checking the following locations.
a) Inverter Terminals: TB5, TB6, TB7 (Phase A, B, C)
See Figure 3-15 on page 3–16.
b) Utility Terminals: Bottom of S1-2T1, S1-4T2, S1-6T3
See Figure 3-16 on page 3–16.
c) PV Terminals: Bottom of S2-6, K2-6T3, TB4 (PV+, PV-, GND)
See Figure 3-19 on page 3–19.
viii152606 Rev A
De-Energize/Isolation Procedure
The following procedure should be followed to de-energize the PV225S for
maintenance.
WARNING
The terminals of the DC input may be energized if the PV arrays are energized. In
addition, allow 5 minutes for all capacitors within the main enclosure to discharge after
disconnecting the PV225S from AC and DC sources.
To isolate the PV225S:
Safety
1. Turn the O
2. Open the DC Disconnect Switch.
3. Open the AC Disconnect Switch.
4. Open the utility connection circuit breaker.
5. Install lockout devices on the utility connection circuit breaker and DC
Disconnect Switch.
N/OFF switch to the OFF position.
Interconnection Standards Compliance
The PV225S has been tested and listed by Underwriters Laboratories to be in
compliance with UL1741 Static Inverters And Charge Controllers For Use In
Photovoltaic Power Systems, as well as IEEE-929-2000 Recommended Practice
For Utility Interface of Photovoltaic (PV) Systems.
IEEE-929-2000 provides guidance regarding equipment and functions necessary
to ensure compatible operation of photovoltaic systems which are connected in
parallel with the electric utility.
UL1741 is the standard applied by Underwriters Laboratory to the PV225S to
verify it meets the recommendations of IEEE-929-2000.
Refer to both documents for details of these recommendations and test
procedures.
Table 1-1Electrical Specifications 1–4
Table 1-2Over/Under Voltage and Over/Under Frequency Ranges 1–4
Table 1-3Environmental Specifications 1–6
Table 3-1AC Terminal Wire Gauge, Bolt Size, and Torque Values 3–12
Table 3-2DC Terminal Wire Gauge, Bolt Size, and Torque Values 3–12
152606 Rev Axv
xvi
1
Introduction
Chapter 1, “Introduction” provides information about the features and
functions of the PV225S 225 kW Grid-Tied Photovoltaic Inverter.
Introduction
Description of the PV225S
The PV225S 225 kW Grid-Tied Photovoltaic Inverter is a UL 1741 Listed, utility
interactive, three-phase power conversion system for grid-connected photovoltaic
arrays with a power rating of 225 kW. Designed to be easy to install and operate,
the PV225S automates start-up, shutdown, and fault detection scenarios. With
user-definable power tracking that matches the inverter to the array and adjustable
delay periods, users are able to customize start up and shut down sequences.
Multiple PV225S inverters are easily paralleled for larger power installations.
The PV225S power conversion system consists of a pulse-width modulated
(PWM) inverter, switch gear for isolation and protection of the connected AC and
DC power sources, and a custom Wye/Wye isolation transformer. Housed in a
rugged NEMA-3R rated, powder-coated steel enclosure, the PV225S incorporates
sophisticated Intellimod
the main power switching devices. An advanced, field-proven, Maximum Peak
Power Tracker (MPPT) integrated within the PV225S control firmware ensures
the optimum power throughput for harvesting energy from the photovoltaic array.
The advanced design of the PV225S includes an EMI output filter and the main
AC contactor located electrically on the utility side of the isolation transformer.
The location of the main AC contactor, and the ability to de-energize the isolation
transformer during times of non-operation, greatly reduces the night-time tare
losses consumed by an idle isolation transformer. An integrated soft-start circuit
precludes nuisance utility-tie circuit breaker trips as the result of isolation
transformer inrush current.
(IPM) Insulated Gate Bipolar Transistors (IGBTs) as
Additionally, the PV225S integrated controller contains self-protection features
including over and under voltage and frequency safeguards. An integral
anti-island protection scheme prevents the inverter from feeding power to the grid
in the event of a utility outage. The PV225S includes a local user interface
comprised of an O
user-friendly, Graphic User Interface (GUI) provides a remote interface for
operator interrogation of PV225S system status, control, metering/data logging
and protective functions within the PV225S. The status, control, and logging
features are also supported by the data modem (included) and can be accessed
remotely.
The PV225S comes in two modules comprised of six enclosures to house the
electronics described above. The first module includes the Main Inverter
Enclosure, Inductor Enclosure, DC Interface Enclosure, and Communications
Enclosure. The second module includes the Transformer Enclosure and AC
Interface Enclosure. These components are identified in Figure 1-1 on page 1–3.
Figure 1-1 also shows the dimensions and locations of the various enclosures that
comprise the PV225S.
See “Layout Options” on page 2–6 for information on configuration options.
N/OFF switch, keypad, and 4-line, 80 character LCD display. A
1–2152606 Rev A
Front View
AC
Interface
Enclosure
Communications
Enclosure
Transformer
Enclosure
Main
Inverter
Enclosure
Inductor
Enclosure
Description of the PV225S
DC Interface
Enclosure
Back
Figure 1-1
Front
AC Interface
Enclosure
AC Side View
Dimensions (Not to scale)
Communications
Enclosure
Front
DC Interface
Enclosure
Back
Inductor
Enclosure
DC Side View
152606 Rev A1–3
Introduction
System Specifications
The PV225S has been designed for photovoltaic power systems, which operate
within the following specifications.
CAUTION: Equipment Damage
Operation of the PV225S in a manner other than specified in this manual may cause
damage to the PV225S and other system components and will void the terms of the
warranty.
Electrical Specifications
Table 1-1 provides the AC and DC specifications for the PV225S.
Table 1-1
SpecificationPV225S-480
Nominal AC Input Voltage
(+10% to -12% acceptable range)
Maximum AC Output Current271 A
Nominal AC Input Frequency
(+0.5 to -0.7 Hz acceptable range)
Output Power225 kW
Peak Power Tracking Window330 to 600 Vdc
Maximum Open Circuit Voltage600 Vdc
Maximum DC Input Current710 amps
Electrical Specifications
Over Voltage, Under Voltage and Frequency Ranges
Table 1-2 provides the over voltage, under voltage, over-frequency, and
under-frequency detection limits for the PV225S. These detection limits have
been factory tested and deemed to be in compliance with IEEE-292 and UL 1741
requirements for utility interaction.
Table 1-2
Vac Condition
(% of Nominal)
Vac < 50%Vac < 2406 cycles
50% <
88% < Vac <
110% < Vac < 137%528 < Vac < 6572 seconds
137% <
f < rated -0.7f < 59.36 cycles
f > rated +0.5f > 60.56 cycles
Over/Under Voltage and Over/Under Frequency Ranges
Voltage RangeTrip Time
Va c < 88%240 < Vac < 4222 seconds
110%422 < Vac < 528normal operation
Vac657 < Vac2 cycles
480 Vac
(422 to 528 Vac)
rms
60 Hz
(59.3 to 60.5 Hz)
PV225S-480
1–4152606 Rev A
System Ground Requirements
This product is intended to be installed as part of a permanently grounded
electrical system per the National Electric Code ANSI/NFPA 70. A copper ground
rod must be installed within three feet of the PV225S enclosures and connected to
the unit as described in “System Grounding” on page 3–12. The single-point
ground for the system is to be made at the AC ground bus bar (TB12) in the AC
Interface Enclosure.
System Neutral Requirements
The PV225S is designed to be installed as a 4-wire system. As required by the
UL 1741 listing, a neutral conductor from the utility-interconnect must be
terminated at TB11 within the AC Interface Enclosure to ensure that the AC
voltage sensing circuit can perform an individual phase voltage (line-to-neutral)
measurement. The function of the neutral connection is to provide a point of
reference for measurement purposes that is essentially at ground potential. No
power will flow through the neutral conductor.
Utility Side Isolation Transformer Requirements
The PV225S is supplied with a custom, high-efficiency, isolation transformer as
part of the AC Interface/Transformer assembly. The utility side windings of the
isolation transformer are configured Wye and must match the voltage at the utility
inter-tie. The PV225S is a balanced, three-phase, current-sourcing inverter and
only operates with the presence of a stable utility voltage. The transformer is also
supplied with a neutral connection on the utility interconnect. Connection of this
utility-side neutral does not affect the operation of the inverter, however
connection of the neutral on the inverter-side does affect the operation and must
be left floating or disconnected. Single-phase, grounded loads which may be
present between the transformer and utility, will maintain their existing ground
reference at the utility distribution transformer.
System Specifications
CAUTION: Equipment Damage
If the Isolation Transformer (T6-X0) neutral terminal is tied to ground, it will cause
irreparable damage to the PV225S. Check local regulations for their requirements
regarding the connection of the neutral.
WARNING: Lethal Voltage
Grounding the neutral of a Wye-wound transformer may create an “open delta” condition,
depending on the utility configuration. This condition may keep the PV225S from
detecting a loss of phase condition on the utility system, which may allow potentially
lethal voltage to be present on the open-phase wiring.
152606 Rev A1–5
Introduction
Environmental Specifications
The following environmental specifications are the same for both models of the
PV225S 225 kW Grid-Tied Photovoltaic Inverter.
Table 1-3
SpecificationValue
Environmental Specifications
Dimensions
Inverter and DC Interface
88.5 in H x 80 in W x 32 in D
(225 cm H x 203 cm W x 81 cm)
Transformer and AC Interface
49.5 in H x 61.5 in W x 35.5 in D
(126 cm H x 156 cm W x 90 cm D)
Overall System Footprint:
Layout Option A
14 ft W x 5 ft L (approximate)
(4.3 m x 1.5 m)
Layout Option B
10 ft W x 9 ft L (approximate)
(3 m W x 2.7 m L)
Weig ht
Inverter and DC Interface
Transformer and AC Interface
Overall Weight
15 ft (4.5 m)
Inverter Enclosure and AC
Interface/Transformer Enclosure
1–6152606 Rev A
Operator Interface Controls
Operator interface controls are located on the front door of the main inverter
enclosure. These controls include an O
keypad called the Universal Frontpanel Control Unit (UFCU). Additionally there
is an AC and DC Disconnect on the AC Interface Enclosure and the DC Interface
Enclosure Doors.
Communication
Enclosure
Operator Interface Controls
N/OFF Switch, 4-line LCD display and
DC Disconnect
Switch (S2)
AC
Disconnect
Switch (S1)
Figure 1-2
AC Interface Enclosure
(AC Side View)
PV225S Operator Interface Components
LCD
Display
Universal
Frontpanel
Control
(UFCP)
ON/OFF
Switch
(S3)
Main Enclosure Door Interlock Switch
The front door of the PV225Smain enclosure is equipped with an interlock switch
to preclude operation while the front door is open. Opening the door of the main
inverter enclosure will initiate an immediate controlled shutdown of the PV225S
and opens both the main AC and DC contactors. The main AC and DC contactors
cannot be closed unless the door’s interlock is in the engaged position. The
PV225S is prevented from being restarted until the door is again closed and the
switch is in the engaged position.
DC Interface
Enclosure
Main Inverter Enclosure
(Front View)
It is required that the PV225Smain enclosure door must be locked during normal
operation. The door interlock switch does NOT remove all hazardous voltages
from inside the inverter. Before attempting to service the PV225S, follow the
de-energize Lockout and Tag procedure on
152606 Rev A1–7
page viii.
Introduction
On/Off Switch
WARNING: Shock Hazard
Disengaging the main enclosure door interlock switch does NOT remove all hazardous
voltages from inside the inverter. Before attempting to service the PV225S, follow the
de-energize Lockout and Tag procedure on page viii.
The PV225Sincorporates a maintained position ON/OFF switch (S3) located on
the front door of the main enclosure. Under normal conditions, the O
is in the O
N position. Turning the switch to the OFF position will initiate an
N/OFFswitch
immediate controlled shutdown of the PV225Sand opens both the main AC and
DC contactors within the unit. The main AC and DC contactors cannot be closed
unless the switch is in the
restarted until the O
ON position. The PV225Sis prevented from being
N/OFFswitch is turned back to the ONposition.
WARNING: Shock Hazard
Turning the ON/OFF switch to the OFF position does NOT remove all hazardous voltages
from inside the inverter. Before attempting to service the PV225S, follow the de-energize
Lockout and Tag procedure on page viii.
Figure 1-3
ON/OFF Switch
(S3)
On/Off Switch (S3)
1–8152606 Rev A
Loading...
+ 58 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.