Whirlpool WHP43, WHP44, WGHP43, WGHP44, WGHP46 Installation Instructions Manual

...
0 (0)
HEAT PUMP INSTALLATION INSTRUCTIONS
Table of Contents
HEAT PUMP SAFETY PRECAUTIONS.........................................1
Shipping Inspection .....................................................................2
Codes and Regulations................................................................2
Installation Clearances................................................................. 2
Rooftop Installations ....................................................................3
SAFE REFRIGERANT HANDLING ................................................3
REFRIGERANT LINES....................................................................4
Burying Refrigerant Lines.............................................................5
Refrigerant Line Connections ......................................................5
Leak Testing—Nitrogen or Nitrogen-Traced ...............................5
System Evacuation ......................................................................5
HEAT PUMP SAFETY PRECAUTIONS
The following symbols and labels are used throughout this manual to indicate immediate or potential safety hazards. It is the owner’s and installer’s responsibility to read and comply with all safety information and instructions accompanying these symbols. Failure to heed safety information increases the risk of personal injury, property damage, and/or product damage.
ELECTRICAL CONNECTIONS ......................................................6
Over-current Protection ...............................................................6
High Voltage Connections ...........................................................6
Low Voltage Connections ............................................................6
SYSTEM START-UP.......................................................................8
FINAL CHARGE ADJUSTMENT....................................................8
Fixed Orifice .................................................................................9
Expansion Valve System..............................................................9
2-Stage Application......................................................................9
Heat Pump—Heating Cycle.......................................................10
TROUBLESHOOTING INFORMATION .......................................11
ASSISTANCE OR SERVICE.........................................................16
Recognize this symbol as a safety precaution.
WARNING
Hazards or unsafe practices could result in property damage, product damage, severe personal injury or death.
Goodman 1
CAUTION
Hazards or unsafe practices may result in property damage, product damage, personal injury or death.
Goodman 6
Disconnect ALL power before servicing.
Multiple power sources may be present.
Failure to do so may cause property damage, personal injury or death.
WARNING
HIGH VOLTAGE!
WARNING
Installation and repair of this unit should
CAUTION
Goodman 9
Hazards or unsafe practices may result in property or product damage.
be performed ONLY by individuals meeting the requirements of an “Entry Level Technician,” at a minimum, as specified by the Air-Conditioning, Heating and Refrigeration Institute (AHRI). Attempting to install or repair this unit without such background may result in product damage, personal injury or death.
Goodman 7
CAUTION
Scroll equipped units should never be used to evacuate
Placeholder
for Bar
the air conditioning system. Vacuums this low can cause internal electrical arcing resulting in a damaged or failed compressor.
Code
Whirlpool® and Whirlpool Gold® Models WHP43, WHP44, WGHP43, WGHP44, WGHP46, WGHP48
WPIO-259L
Goodman 32
Important Note to the Owner Regarding
Product Warranty
Your warranty certificate is supplied as a separate document with the unit installed by your contractor. Read the limited warranty certificate carefully to determine what is and is not covered. Keep the warranty certificate in a safe place. If you are unable to locate the warranty certificate, please contact your installing contractor, or contact customer service at 1-866-944-7575 to obtain a copy.
To receive the 10-Year Parts Limited Warranty, online registration must be completed within 60 days of installation. Online registration is not required in California or Quebec.
Product limited warranty certificates for models currently in production can be viewed at www.whirlpoolhvac.com. If your model is not currently in production or does not appear on the website, please contact your installing contractor or contact customer service at 1-866-944-7575 to obtain a copy of your warranty certificate.
To register your unit, go to www.whirlpoolhvac.com. Click on the manufacturer’s Comfort Commitment the bottom center of the home page. Next, click on the Click Here to Register Your Product link located at the top center of the page, and complete the forms in the manner indicated.
TM
Warranty link located at
Shipping Inspection
Always keep the unit upright; laying the unit on its side or top may cause equipment damage. Shipping damage and subsequent investigation is the responsibility of the carrier. Verify the model number, specifications, electrical characteristics and accessories are correct prior to installation. The distributor or manufacturer will not accept claims from dealers for transportation damage or installation of incorrectly shipped units.
Installation Clearances
Special consideration must be given to the location of the heat pump(s) in regard to structures, obstructions, other units and any/ all other factors that may interfere with air circulation. Where possible, the top of the unit should be completely unobstructed; however, if vertical conditions require placement beneath an obstruction, there should be a minimum of 60" (152 cm) between the top of the unit and the obstruction(s). The specified dimensions meet requirements for air circulation only. Consult all appropriate regulatory codes prior to determining final clearances.
Another important consideration in selecting a location for the unit(s) is the angle to obstructions. Either side adjacent the valves can be placed toward the structure provided the side away from the structure maintains minimum service clearance.
NOTE: Corner installations are strongly discouraged.
Not Recommended
B
A
C
AA
B B
AA AA
C
AA
B
AA
OK!
OK!
OK!
OK!
OK!
OK!
Codes and Regulations
This product is designed and manufactured to comply with national codes. Installation in accordance with such codes and/ or prevailing local codes/regulations is the responsibility of the installer. The manufacturer assumes no responsibility for equipment installed in violation of any codes or regulations.
The United States Environmental Protection Agency (EPA) has issued various regulations regarding the introduction and disposal of refrigerants. Failure to follow these regulations may harm the environment and can lead to the imposition of substantial fines. Should you have any questions please contact the local office of the EPA.
If replacing a condensing unit or air handler, the system must be manufacturer-approved and Air Conditioning, Heating and Refrigeration Institute (AHRI) matched.
NOTE: Installation of unmatched systems is not allowed. Operating the unit in a structure that is not complete (either as
part of new construction or renovation) will void the warranty.
A
AA
AA
CC
Minimum Airflow Clearance—in. (cm)
Model Type A B C AA Residential 10 (25) 10 (25) 18 (46) 20 (51) Light Commercial 12 (31) 12 (31) 18 (46) 24 (61)
This unit can be located at the ground floor level or on flat roofs. At ground floor level, the unit must be on a solid, level foundation that will not shift or settle. To reduce the possibility of sound transmission, the foundation slab should not be in contact with or be an integral part of the building foundation. Ensure the foundation is sufficient to support the unit. A concrete slab raised above ground level provides a suitable base.
2
Rooftop Installations
If it is necessary to install this unit on a roof structure, ensure the roof structure can support the weight and that proper consideration is given to the weather-tight integrity of the roof. Since the unit can vibrate during operation, sound vibration transmission should be considered when installing the unit. Vibration absorbing pads or springs can be installed between the unit legs or frame and the roof mounting assembly to reduce noise vibration.
NOTE: These units require special location consideration in areas of heavy snow accumulation and/or areas with prolonged continuous subfreezing temperatures. Heat pump unit bases have cutouts under the outdoor coil that permit drainage of frost accumulation.
SAFE REFRIGERANT HANDLING
While these items will not cover every conceivable situation, they should serve as a useful guide.
Situate the unit to permit free unobstructed drainage of the defrost water and ice. In more severe weather locations, it is recommended that the unit be elevated to allow unobstructed drainage and airflow.
The following elevation minimums are recommended:
Design Temperature
+15ºF (-9ºC) and above 2¹⁄₂" (6.4 cm)
-5º (-20.6ºC) to +14º (-10ºC) 8" (20.3 cm) below -5º (-20.6ºC) 12" (30.5 cm)
Suggested Minimum Elevation
WARNING
WARNING
To avoid possible injury, explosion or death, practice safe handling of refrigerants.
Goodman 12
WARNING
Refrigerants are heavier than air. They can “push out” the oxygen in your lungs or in any enclosed space. To avoid possible difficulty in breathing or death:
• Never purge refrigerant into an enclosed room or space. By law, all refrigerants must be reclaimed.
• If an indoor leak is suspected, throughly ventilate the area before beginning work.
• Liquid refrigerant can be very cold. To avoid possible frostbite or blindness, avoid contact and wear gloves and goggles. If liquid refrigerant does contact your skin or eyes, seek medical help immediately.
• Always follow EPA regulations. Never burn refrigerant, as poisonous gas will be produced.
Goodman 13
To avoid possible explosion:
• Never apply flame or steam to a refrigerant cylinder. If you must heat a cylinder for faster charging, partially immerse it in warm water.
• Never fill a cylinder more than 80% full of liquid refrigerant.
• Never add anything other than R-22 to an R-22 cylinder or R-410A to an R-410A cylinder. The service equipment used must be listed or certified for the type of refrigerant used.
• Store cylinders in a cool, dry place. Never use a cylinder as a platform or a roller.
Goodman 14
WARNING
To avoid possible explosion, use only returnable (not disposable) service cylinders when removing refrigerant from a system.
• Ensure the cylinder is free of damage which could lead to a leak or explosion.
• Ensure the hydrostatic test date does not exceed 5 years.
• Ensure the pressure rating meets or exceeds 400 lbs.
When in doubt, do not use cylinder.
Goodman 15
3
REFRIGERANT LINES
CAUTION
The compressor POE oil for R-410A units is extremely susceptible to moisture absorption and could cause compressor failure. Do not leave system open to atmosphere any longer than necessary for installation.
Use only refrigerant-grade (dehydrated and sealed) copper tubing to connect the heat pump with the indoor evaporator. After cutting the tubing, install plugs to keep refrigerant tubing clean and dry prior to and during installation. Tubing should always be cut square, keeping the ends round and free from burrs. Clean the tubing to prevent contamination.
NOTE: Do not let the refrigerant lines come in direct contact with plumbing, ductwork, floor joists, wall studs, floors and walls. When running refrigerant lines through a foundation or wall, openings should allow for sound and vibration absorbing material to be placed or installed between tubing and foundation. Any gap between the foundation or wall and refrigerant lines should be filled with a pliable silicon-based caulk, RTV or a vibration damping material. Avoid suspending refrigerant tubing from joists and studs with rigid wire or straps that would come in contact with the tubing. Use an insulated or suspension-type hanger. Keep both lines separate and always insulate the suction line.
These sizes are recommended for line lengths of 79 ft (24 m) or less to obtain optimum performance. For alternate line sizing options or runs of more than 79 ft (24 m), refer to Remote Cooling Service Manual, TP-107 Long Line Set Application R- 410A or contact your distributor for assistance.
Goodman 16
Mounting the evaporator coil above the heat pump will require an inverted loop in the suction line adjacent or near the connection to the evaporator coil. The top of the loop must be slightly higher than the top of the evaporator coil.
C
A
A. Heat pump B. Suction line
Mounting the heat pump above the evaporator coil will require an oil trap in the suction line. Install one oil trap at the evaporator for a height difference of more than 15 ft (4.5 m) between indoor and outdoor units.
B
D
C. Evaporator coil D. Liquid line
A
Recommended Interconnecting Tubing—ft (m) 0 to 24
(7)
25 to 49 (8 to 15)
50 to 79
(15 to 24)* Conditioner Line Diameter (in. OD) Unit Tons Suction Liquid Suction Liquid Suction Liquid
1¹⁄₂ ⁵⁄₈ ¹⁄₄ ³⁄₄ ³⁄₈ ³⁄₄ ³⁄₈ 2 ⁵⁄₈ ¹⁄₄ ³⁄₄ ³⁄₈ ³⁄₄ ³⁄₈ 2¹⁄₂ ⁵⁄₈ ¹⁄₄ ³⁄₄ ³⁄₈ ⁷⁄₈ ³⁄₈ 3 ³⁄₄ ³⁄₈ ⁷⁄₈ ³⁄₈ 1¹⁄₈ ³⁄₈ 3¹⁄₂ ⁷⁄₈ ³⁄₈ 1¹⁄₈ ³⁄₈ 1¹⁄₈ ³⁄₈ 4 ⁷⁄₈ ³⁄₈ 1¹⁄₈ ³⁄₈ 1¹⁄₈ ³⁄₈ 5 ⁷⁄₈ ³⁄₈ 1¹⁄₈ ³⁄₈ 1¹⁄₈ ³⁄₈
*For lines greater than 79 ft (24 m) in length or vertical elevation
changes more than 50 ft (15 m), refer to the Remote Cooling Service Manual or contact your distributor for assistance.
C
B
A. Heat pump B. Liquid line
Insulation is necessary to avoid condensation from forming and dropping from the suction line. Armaflex (or satisfactory equivalent) with ³⁄₈" (1 cm) minimum wall thickness is recommended. In severe conditions (hot, high humidity areas), ¹⁄₂" (1.3 cm) insulation may be required. Insulation must be installed in a manner which keeps tubing from damage and contamination.
Where possible, drain as much residual compressor oil from existing systems, lines and traps; pay close attention to low areas where oil may collect.
NOTE: If changing refrigerant types, ensure the indoor coil and metering device is compatible with the type of refrigerant being used; otherwise, the indoor coil must be replaced.
C. Suction line D. Evaporator coil
D
4
Burying Refrigerant Lines
If burying refrigerant lines cannot be avoided, use the following checklist.
1. Insulate liquid and suction lines separately.
2. Enclose all underground portions of the refrigerant lines in
waterproof material (conduit or pipe) sealing the ends where tubing enters/exits the enclosure.
3. If the lines must pass under or through a concrete slab,
ensure lines are adequately protected and sealed.
Leak Testing—Nitrogen or Nitrogen-Traced
WARNING
Goodman 17
To avoid the risk of fire or explosion, never use oxygen, high pressure air or flammable gases for leak testing of a refrigeration system.
Refrigerant Line Connections
IMPORTANT: To avoid overheating the service valve, TXV valve or filter dryer while brazing, wrap the component with a wet rag, or use a thermal heat trap compound. Be sure to follow the manufacturer’s instruction when using the heat trap compound.
NOTE: Remove Schrader valves from service valves before brazing tubes to the valves. Use a brazing alloy of 2% minimum silver content. Do not use flux.
Torch heat required to braze tubes of various sizes is proportional to the size of the tube. Tubes of smaller size require less heat to bring the tube to brazing temperature before adding brazing alloy. Applying too much heat to any tube can melt the tube. Service personnel must use the appropriate heat level for the size of the tube being brazed.
NOTE: The use of a heat shield when brazing is recommended to avoid burning the serial plate or the finish on the unit.
1.
The ends of the refrigerant lines must be cut square, deburred, cleaned and be round and free from nicks or dents. Any other condition increases the chance of a refrigerant leak.
2. “Sweep” the refrigerant line with nitrogen or inert gas during
brazing to prevent the formation of copper-oxide inside the refrigerant lines. The POE oils used in R-410A applications will clean any copper-oxide present from the inside of the refrigerant lines and spread it throughout the system. This may cause a blockage or failure of the metering device.
3. After brazing, quench the joints with water or a wet cloth to
prevent overheating of the service valve.
4. Ensure the filter dryer paint finish is intact after brazing. If the
paint of the steel filter dryer has been burned or chipped, repaint or treat with a rust preventive. This is especially important on suction line filter dryers which are continually wet when the unit is operating.
NOTES:
Be careful not to kink or dent refrigerant lines. Kinked or
dented lines will cause poor performance or compressor damage.
Do not make final refrigerant line connection until plugs are
removed from refrigerant tubing.
Before brazing, verify indoor piston size by checking the
piston kit chart packaged with indoor unit.
WARNING
To avoid possible explosion, the line from the nitrogen cylinder must include a pressure regulator and a pressure relief valve. The pressure relief valve must be set to open at no more than 150 psig.
Pressure test the system using dry nitrogen and soapy water to locate leaks. If you wish to use a leak detector, charge the system to 10 psi using the appropriate refrigerant, and then use nitrogen to finish charging the system to working pressure. Apply the detector to suspect areas. If leaks are found, repair them. After repair, repeat the pressure test. If no leaks exist, proceed to system evacuation.
Condensing unit liquid and suction valves are closed to contain the charge within the unit. The unit is shipped with the valve stems closed and caps installed.
NOTE: Do not open valves until the system is evacuated.
Goodman 18
System Evacuation
WARNING
REFRIGERANT UNDER PRESSURE! Failure to follow proper procedures may cause property damage, personal injury or death.
NOTE: Scroll compressors should never be used to evacuate or pump down a heat pump or air conditioning system.
Goodman 19
CAUTION
Prolonged operation at suction pressures less than 20 psig for more than 5 seconds will result in overheating of the scrolls and permanent damage to the scroll tips, drive bearings and internal seal.
1. Connect the vacuum pump with 250 micron capability to the
service valves.
2. Evacuate the system to 250 microns or less using suction
and liquid service valves. Using both valves is necessary as some compressors create a mechanical seal separating the sides of the system.
3. Close pump valve and hold vacuum for 10 minutes. Typically
pressure will rise during this period.
Goodman 20
5
Loading...
+ 11 hidden pages