Whirlpool UXT5230BFS Installation manual

0 (0)

30" (76.2 CM) RANGE HOOD

Installation Instructions and Use & Care Guide

For questions about features, operation/performance, parts, accessories or service, call: 1-800-253-1301 or visit our website at www.whirlpool.com

In Canada, call 1-800-807-6777 or visit our website at www.whirlpool.ca

HOTTE D’ASPIRATION DE 30" (76,2 CM)

Instructions d’installation et Guide d’utilisation et d’entretien

Au Canada, pour assistance, installation ou service, composer le 1-800-807-6777 ou visiter notre site Web à www.whirlpool.ca

Table of Contents/Table des matières......................................

2

Model/Modèle:

UXT5230BF

IMPORTANT: READ AND SAVE THESE INSTRUCTIONS.

FOR RESIDENTIAL USE ONLY.

IMPORTANT : LIRE ET CONSERVER CES INSTRUCTIONS.

POUR UTILISATION RÉSIDENTIELLE UNIQUEMENT.

LIB0117644/W10848282A

TABLE OF CONTENTS

 

RANGE HOOD SAFETY..................................................................

2

INSTALLATION REQUIREMENTS.................................................

4

Tools and Parts.............................................................................

4

Location Requirements.................................................................

4

Venting System.............................................................................

5

Electrical Requirements................................................................

6

INSTALLATION INSTRUCTIONS...................................................

7

RANGE HOOD USE......................................................................

11

Range Hood Controls.................................................................

11

RANGE HOOD CARE....................................................................

11

Cleaning......................................................................................

11

WIRING DIAGRAM........................................................................

12

ASSISTANCE OR SERVICE..........................................................

13

In the U.S.A.................................................................................

13

In Canada....................................................................................

13

WARRANTY...................................................................................

14

TABLE DES MATIÈRES

 

SÉCURITÉ DE LA HOTTE DE CUISINIÈRE................................

15

EXIGENCES D’INSTALLATION....................................................

17

Outillage et pièces......................................................................

17

Exigences d’emplacement.........................................................

17

Circuit d’évacuation....................................................................

18

Spécifications électriques...........................................................

19

INSTRUCTIONS D’INSTALLATION.............................................

20

UTILISATION DE LA HOTTE........................................................

24

Commandes de la hotte de cuisinière........................................

24

ENTRETIEN DE LA HOTTE..........................................................

25

Nettoyage....................................................................................

25

SCHÉMA DE CÂBLAGE...............................................................

26

ASSISTANCE OU SERVICE..........................................................

27

Au Canada..................................................................................

27

GARANTIE.....................................................................................

27

RANGE HOOD SAFETY

Your safety and the safety of others are very important.

many important safety messages in this manual and on your appliance. Always read and obey all safety

safety alert symbol.

alerts you to potential hazards that can kill or hurt you and others.

messages will follow the safety alert symbol and either the word “DANGER” or “WARNING.” mean:

DANGER WARNING

You can be killed or seriously injured if you don't immediately follow instructions.

You can be killed or seriously injured if you don't follow instructions.

All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.

2

Whirlpool UXT5230BFS Installation manual

State of California Proposition 65 Warnings:

WARNING: This product contains one or more chemicals known to the State of California to cause cancer.

WARNING: This product contains one or more chemicals known to the State of California to cause birth defects or other reproductive harm.

IMPORTANT SAFETY INSTRUCTIONS

READ AND SAVE THESE INSTRUCTIONS

3

INSTALLATION REQUIREMENTS

Tools and Parts

Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed here.

Tools needed

Metal snips

Wire stripper

#2 Phillips

Flat-blade

screwdriver

screwdriver

Pencil

 

Caulking gun and weatherproof caulking compound

Jigsaw or keyhole saw

Parts supplied

Remove parts from package. Check that all parts are included.

#8-18 x 1" (4.2 x 25 mm)

flat-head screws

Drywall

Mounting

anchors

brackets

Short Phillips

Torx®† T10 adapter

head screws

 

Parts needed

UL listed/CSA approved

wire connectors

For 7" (17.8 cm) round vented installations

7" (17.8 cm)

7" (17.8 cm)

round

round damper

metal vent

Part Number

system with

W10355451*

wall or roof cap

 

Vent clamps as

7" (17.8 cm)

required

round vent

 

mounting plate

 

Part Number

 

W10388168*

®TORX is a registered trademark of Acument Intellectual Properties, LLC.

For 31/4" x 10" (8.3 x 25.4 cm) rectangular vented installations

3¹⁄" x 10"

Duct tape

(8.3 x 25.4 cm) rectangular

 

metal vent system with

 

wall or roof cap

 

Optional accessories

Charcoal

Power

Stainless steel

filter kit

cord kit

cleaner and

Part Number

Part Number

polish

W10386873*

W10355452*

Part Number

 

 

31462A*

*For information on ordering, see the “Assistance or Service” section.

Location Requirements

IMPORTANT: Observe all governing codes and ordinances.

■■ It is the installer’s responsibility to comply with installation clearances specified on the model/serial/rating plate. The model/serial/rating plate is located inside the range hood on the left wall.

■■ Range hood location should be away from strong draft areas, such as windows, doors, and strong heating vents.

■■ Cabinet opening dimensions that are shown must be used. Given dimensions provide minimum clearance. Consult the cooktop/range manufacturer installation instructions before making any cutouts.

■■ This range hood is recommended for use with cooktops with a maximum total rating of 50,000 BTUs or less.

■■ Grounded electrical outlet is required. See “Electrical Requirements” section.

■■ All openings in ceiling and wall where range hood will be installed must be sealed.

■■ These range hoods are factory set for vented installations. Models that are capable of being installed as non-vented (recirculating) require charcoal filters. See the “Assistance or Service” section for information on ordering charcoal filters.

For Mobile Home Installations

The installation of this range hood must conform to the Manufactured Home Construction Safety Standards, Title 24 CFR, Part 328 (formerly the Federal Standard for Mobile Home Construction and Safety, title 24, HUD, Part 280)

or, when such standard is not applicable, the standard for Manufactured Home Installation 1982 (Manufactured Home Sites, Communities and Setups) ANSI A225.1/NFPA 501A, or latest edition, or with local codes.

Product Dimensions

2" (5.1 cm)

1" (2.5 cm)

1"

(2.5 cm) 9"

(22.9 cm)

4

Installation Clearances

C

A

D

B

E

A.18" (45.7 cm) minimum distance from electric cooking surface 24" (61.0 cm) minimum distance from gas cooking surface 30" (76.2 cm) suggested maximum above the cooking surface

B.18" (45.7 cm) minimum clearance - upper cabinet to countertop

C.30" (76.2 cm) minimum cabinet opening width

D.12" (30.5 cm) cabinet depth

E.36" (91.4 cm) base cabinet height

Venting System

Venting Methods

NOTES:

■■ Flexible vent is not recommended. Flexible vent creates both back pressure and air turbulence that greatly reduce performance.

■■ The vent system is optional for this model.

Vent system can terminate either through the roof or wall. Use 31/4" x 10" (8.3 x 25.4 cm) rectangular with a maximum vent length of 35 ft (10.7 m) or 7" (17.8 cm) or larger round vent with a maximum length of 50 ft (15.2 m) for vent system.

Top Venting

B

A

Wall Venting

A

B

A.7" (17.8 cm) round vent through roof (purchased separately) or 31/4" x 10"

(8.3 x 25.4 cm) rectangular vent through the roof (purchased separately)

B.Roof cap with damper (purchased separately)

A.7" (17.8 cm) round vent through the wall or out the top (purchased separately) or 31/4" x 10" (8.3 x 25.4 cm) rectangular vent through the wall or out the top (purchased separately)

B.Wall cap with damper (purchased separately)

Cold Weather Installations

An additional backdraft damper should be installed to minimize backward cold air flow and a thermal break should be installed to minimize conduction of outside temperatures as part of the vent system. The damper should be on the cold air side of the thermal break.

The break should be as close as possible to where the vent system enters the heated portion of the house.

Makeup Air

Local building codes may require the use of makeup air systems when using ventilation systems greater than

specified CFM of air movement. The specified CFM varies from locale to locale. Consult your HVAC professional

for specific requirements in your area.

Venting Requirements

■■ Vent system must terminate to the outdoors, except for non-vented (recirculating) installations.

■■ Do not terminate the vent system in an attic or other enclosed area.

■■ Do not use a 4" (10.2 cm) laundry-type wall cap.

■■ Use 7" (17.8 cm) round metal vent or 31/4" x 10"

(8.3 x 25.4 cm) rectangular metal vent, depending on your installation requirement. Rigid metal vent is recommended. Plastic or metal foil vent is not recommended.

■■ The length of vent system and number of elbows should be kept to a minimum to provide efficient performance.

For the most efficient and quiet operation:

■■ Use no more than three 90° elbows.

■■ Make sure there is a minimum of 24" (61.0 cm) of straight vent between the elbows if more than 1 elbow is used.

■■ Do not install 2 elbows together.

■■ Use clamps or duct tape to seal all joints in the vent system.

■■ The vent system must have a damper. If roof or wall cap has a damper, do not use damper supplied with the range hood.

■■ Use caulking to seal exterior wall or roof opening around the cap.

5

Calculating Vent System Length

To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.

Vent System

Vent Piece

45° elbow

2.5 ft (0.8 m)

90° elbow

5 ft (1.5 m)

31/4" x 10"

12 ft (3.7 m)

 

 

 

 

(8.3 cm x 25.4 cm)

 

 

 

 

 

 

 

 

 

 

 

 

flat elbow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7" (17.8 cm)

0 ft (0.0 m)

 

 

 

 

 

wall cap

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31/4" x 10"

4.5 ft (1.4 m)

 

 

 

 

(8.3 cm x 25.4 cm)

 

 

 

 

 

 

 

 

 

 

 

 

to 7" (17.8 cm)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31/4" x 10"

5 ft (1.5 m)

 

 

 

 

 

(8.3 cm x 25.4 cm)

 

 

 

 

 

 

 

 

 

 

 

 

to 7" (17.8 cm)

 

 

 

 

 

 

 

 

 

 

 

 

90° elbow

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Example vent system

 

 

 

 

 

90˚ elbow

 

 

 

 

 

 

 

 

 

 

 

Wall cap

 

 

 

 

 

 

 

6 ft (1.8 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 ft (0.6 m)

 

 

 

 

 

 

1 - 90° elbow

 

 

 

 

 

 

 

=

5 ft (1.5 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1 - wall cap

 

 

 

 

 

 

 

=

0 ft (0.0 m)

8 ft (2.4 m) straight

 

 

 

 

 

 

 

=

8 ft (2.4 m)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

System length

 

 

 

 

 

 

 

=

13 ft (3.9 m)

 

 

 

 

 

 

 

 

 

 

 

 

Maximum Recommended Length

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7" (17.8 cm) Round Vent

=

50 ft (15.2 m)

31/4" x 10" (8.3 x 25.4 cm)

=

35 ft (10.7 m)

Rectangular Vent

 

 

 

 

 

 

 

 

 

 

 

 

Electrical Requirements

Observe all governing codes and ordinances.

Ensure that the electrical installation is adequate and in conformance with National Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards C22.1-94, Canadian

Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition), and all local codes and ordinances.

If codes permit and a separate ground wire is used, it is recommended that a qualified electrician determine that the ground path is adequate.

A copy of the above code standards can be obtained from:

National Fire Protection Association

1 Batterymarch Park

Quincy, MA 02169-7471

CSA International

8501 East Pleasant Valley Road

Cleveland, OH 44131-5575

■■ A 120 volt, 60 Hz., AC only, 15-amp, fused electrical circuit is required.

■■ If the house has aluminum wiring, follow the procedure below:

1.Connect a section of solid copper wire to the pigtail leads.

2.Connect the aluminum wiring to the added section of copper wire using special connectors and/or tools

designed and UL listed for joining copper to aluminum.

Follow the electrical connector manufacturer’s recommended procedure. Aluminum/copper connection must conform

with local codes and industry accepted wiring practices.

■■ Wire sizes and connections must conform with the rating of the appliance as specified on the model/serial/rating plate. The model/serial/rating plate is located inside the range hood on the left wall.

■■ Wire sizes must conform to the requirements of the National Electrical Code, ANSI/NFPA 70 (latest edition) or CSA Standards C22. 1-94, Canadian Electrical Code, Part 1

and C22.2 No. 0-M91 (latest edition) and all local codes and ordinances.

6

INSTALLATION INSTRUCTIONS

NOTES:

■■ Depending on your model, determine which venting method to use: roof, wall, or non-vented (recirculating).

■■ It is recommended that the vent system be installed before the range hood is installed. Go to “Venting System” in the “Installation Requirements” section if you need assistance.

■■ Before making cutouts, make sure there is proper clearance within the ceiling or wall for the vent system.

1. Disconnect power

WARNING

Electrical Shock Hazard Disconnect power before servicing.

Replace all parts and panels before operating.

Failure to do so can result in death or electrical shock.

2. Mark Hole Locations

Align the exterior edge of the mounting brackets with the exterior edges of the upper cabinet.

IMPORTANT: The brackets should touch the upper cabinet. With a pencil, mark the upper holes on the brackets.

3. Install Brackets

■■ Using a #2 Phillips screwdriver, install the drywall anchors.

■■ Using #8-18 x 1" (4.2 x 25 mm) flat-head #2 Phillips screws, install the mounting brackets using the upper holes.

NOTE: For installations to a surface other than drywall, it is recommended that a qualified contractor determine the anchoring method.

4. Prepare Range Hood

■■ Set the range hood on its back on a covered surface. ■■ Remove the filter, locking screw, and side panels.

■■ Remove the rectangular damper.

■■ Using a #2 Phillips screwdriver, remove the electrical box cover.

■■ Using a flat-blade screwdriver, remove the appropriate power supply knockout.

7

5. Mark Hole Locations

Lift the range hood into place and insert the mounting bracket tabs through the slots in the back of the range hood.

 

A

 

 

90¡

 

C

C

B

 

 

D

 

D

Hold the range hood firmly in place with one hand and bend each mounting tab (A) upward approximately 90°.

OPTIONAL: Mark the hole in each mounting tab. Mark the hole at the power supply knockout (B).

For a non-vented (recirculating) installation: Go to Step 7.

For a top vented installation: Mark the 4 vent hole locations (C) on the top of the range hood.

For a rear vented installation: Mark the 4 vent hole locations (D) on the rear of the range hood.

Remove the range hood and set it aside.

6. Mark and Cut Vent Opening

31/4" x 10" (8.3 x 25.4 cm) Rectangular Vent System

■■ Using a 1/2" (13 mm) drill bit, drill a hole in each of the dots marked previously on either the wall or upper cabinet. Using the outside edges of the holes, mark the vent opening.

■■ Using a jigsaw or keyhole saw, cut the vent opening.

7" (17.8 cm) Round Vent System

1" (2.5 cm)

A

■■ Using the 7" (17.8 cm) round vent mounting plate, draw the vent opening outline on the underside of the cabinet:

-- Place the vent mounting plate on the bottom of the cabinet. Position the edge of the plate with the widest distance (A) between the hole and edge of the mounting plate against the wall. Position the side edges of the mounting plate between the dots marked previously.

IMPORTANT: The widest edge (A) of the vent mounting plate must be positioned against the wall.

-- Trace the 7" (17.8 cm) vent opening (solid line) on the cabinet bottom.

■■ Using a jigsaw or keyhole saw, cut the vent opening 1" (2.5 cm) larger than the 7" (17.8 cm) hole traced (dashed line).

8

7. Drill Electrical Opening

9. Attach Vent Damper or Transition

 

31/4" x 10" (8.3 x 25.4 cm) Rectangular Vent Damper

Using a 11/4" (3 cm) drill bit, drill the hole in the dot marked previously at the electrical strain relief.

OPTIONAL: Using a 1/8" (3 mm) drill bit, drill pilot holes for the dots marked previously at each mounting tab at an approximate 45° angle in an upward direction.

8.Prepare Range Hood Vents and Mounting Tabs

x2 F

E

C D

B

A

■■ Install Strain Relief

Install a UL listed/CSA approved 1/2" (13 mm) strain relief (A).

■■ Mounting Tabs

Start a #8-18 x 5/8" (4.2 x 16 mm) truss-head screw into the mounting tab (F) on each side of the range hood as shown in the inset. Insert the screws approximately 2 turns into the mounting tab holes.

■■ Non-vented (Recirculating) Installations

Remove the (2) T10 Torx® screws and remove the top, front rectangular vent cover (E). Go to Step 12.

■■ 31/4" x 10" (8.3 x 25.4 cm) Rectangular Vent Installations

For top vent installations, remove the top rectangular vent knockout (C).

OR

For wall vent installations, remove the rear rectangular vent knockout (B).

■■ 7" (17.8 cm) Round Vent Installations

Remove both top knockouts (C and D).

Using (2) short Phillips head screws, install the 31/4" x 10" (8.3 x 25.4 cm) rectangular damper over the top or rear vent knockout removed in Step 8.

NOTE: If the wall cap used has a damper and it interferes with the rectangular damper, remove the rectangular damper flap.

7" (17.8 cm) Round Vent Mounting Plate

A

C

B

■■ Using (2) short Phillips head screws, install the 7" (17.8 cm) round vent mounting plate over the vent knockouts removed in Step 8. Position the wide flange (C) to the front.

NOTE: An optional 7" (17.8 cm) round damper (A), Part Number W10355451, and a 7" (17.8 cm) round vent mounting plate (B), Part Number W10388168, are available as accessories. For information on ordering, see the “Assistance or Service” section.

■■ If installing the optional round damper, position it over the round vent mounting plate.

9