VEGA PULS56 User Manual

Operating Instructions
VEGAPULS 56 Profibus PA
Level and Pressure
Contents
Safety information ........................................................................ 3
Note Ex area ................................................................................ 3
1.1 Function................................................................................. 4
1.2 Application features ............................................................. 6
1.3 Profibus output signal .......................................................... 7
1.4 Adjustment ............................................................................ 8
1.5 Antennas............................................................................. 13
2 Types and versions
2.1 Type survey ........................................................................ 14
2.2 Type code........................................................................... 15
2.3 Bus configuration ............................................................... 16
3 Mounting and installation
3.1 General installation instructions ........................................ 22
3.2 Measurement of liquids ..................................................... 24
3.3 Measurement in standpipe (surge or bypass tube) ...... 25
3.4 False echoes ...................................................................... 32
3.5 Installation mistakes ........................................................... 34
Contents
2 VEGAPULS 56 Profibus PA
Contents
4 Electrical connection
4.1 Connection – Connection cable – Screening ................... 36
4.2 Sensor address ................................................................. 39
4.3 Connection of the sensor .................................................. 40
4.4 Connection of the external indicating
instrument VEGADIS 50 .................................................... 42
5 Setup
5.1 Adjustment media .............................................................. 43
5.2 Adjustment with VVO ......................................................... 44
5.3 Sensor adjustment with the adjustment
module MINICOM ............................................................... 66
6 PA function diagram ............................................................... 72
7 Diagnosis
7.1 Simulation ............................................................................ 76
7.2 Error codes ........................................................................ 76
8 Tec hnical data
8.1 Data ..................................................................................... 77
8.2 Approvals ........................................................................... 84
8.3 Data format of the output signal ........................................ 85
8.4 Dimensions ......................................................................... 86

Safety information

Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and acci­dent prevention rules. For safety and warranty reasons, any internal work on the instruments, apart from that in­volved in normal installation and electrical con­nection, must be carried out only by qualified VEGA personnel.
VEGAPULS 56 Profibus PA 3

Note Ex area

Please note the attached safety instructions containing important information on installation and operation in Ex areas. These safety instructions are part of the oper­ating instructions and come with the Ex ap­proved instruments.

1 Product description

Level measurement of high temperature processes or products with high tempera­tures was previously very difficult or even impossible. If such measurement also had to be done under high pressure, there was practically no measuring system available at all, let alone a non-contact measurement system with good measuring accuracy.
Up to now, levels in distillation and stripper columns (e.g. of sump, plate or head prod­ucts) could usually only be measured by pressure transmitters or differential pressure measurements. The installation required for such pressure measuring systems (pressure cables, pressure transmitters…) is consider­able and expensive, often amounting to sev­eral times the value of the sensor itself. Be­cause of the lack of suitable alternatives, instrumentation departments have not only had to accept this fact, but also the high maintenance costs (cleaning of measuring pipes, errors by condensation, buildup on the diaphragm…) and the often inadequate accuracy (temperature errors, density fluc­tuations, installation faults…).
In the petrochemical industry, the require­ments for a non-contact level sensor are therefore the following:
• independent of pressure and temperature
• process temperature up to 400°C
• process pressure up to 64 bar
• high resistance wetted parts for universal use
• accuracy 0.1 %
• rugged metal housing
• Ex approved (available in EEx d and EEx ia)
• loop-powered as well as usable in digital networks
This initial set of requirements defined the development goals for the VEGAPULS 56 series, a high-temperature radar level meas­uring system. The series represents a com­pletely new development of high-temperature radar sensors for temperatures up to 400°C and pressures up to 64 bar.
Product description
These sensors would not have been possible without the recent new results of materials research and production technology. A specially developed ceramic (with high­frequency properties similar to those of the plastics normally used) is used as coupling material. As opposed to plastic, this ceramic has a very high chemical and thermal resist­ance.
The sensor materials in contact with the proc­ess are all highly resistant. This refers not so much to the flange material of high-alloy stainless steel (1.4571 or superior), as to the specially developed ceramic (Al components connecting it. The ceramic rod receives the radar signals from the high­frequency module and acts with its cone­shaped end as emitter and receiver. The seal between stainless steel flange and ceramic rod is made with a Tantalum seal ring.
) and the
2O3

1.1 Function

Radio detecting and ranging: Radar.
VEGAPULS radar sensors are used for non­contact and continuous distance measure­ment. The measured distance corresponds to a filling height and is outputted as level.
Measuring principle:
emission – reflection – reception
Extremely small 5.8 GHz radar signals are emitted from the antenna of the radar sensor as short pulses. The radar impulses reflected by the sensor environment and the product are received by the antenna as radar ech­oes. The running period of the radar im­pulses from emission to reception is proportional to the distance and hence to the level.
4 VEGAPULS 56 Profibus PA
Product description
Meas. distance
emission - reflection - reception
The radar impulses are emitted by the an­tenna system as impulse packets with a pulse duration of 1 ns and pulse intervals of 278 ns; this corresponds to a pulse package frequency of 3.6 MHz. In the impulse inter­vals, the antenna system operates as re­ceiver. Signal running periods of less than one billionth of a second must be processed and the echo image evaluated in a fraction of a second.
Through this, it is possible for VEGAPULS series 56 radar sensors to process the slow­motion pictures of the sensor environment precisely and in detail in cycles of 0.5 to 1 second without using time-consuming fre­quency analysis (e.g. FMCW, required by other radar techniques).
Virtually all products can be measured
Radar signals display physical properties similar to those of visible light. According to the quantum theory, they propagate through empty space. Hence, they are not depend­ent on a conductive medium (air), and spread out like light at the speed of light. Radar signals react to two basic electrical properties:
- the electrical conductivity of a substance
- the dielectric constant of a substance.
All products which are electrically conductive reflect radar signals very well. Even slightly conductive products ensure a sufficient re­flection for a reliable measurement.
1 ns
278 ns
Pulse sequence
VEGAPULS radar sensors can achieve this through a special time transformation proce­dure which spreads out the more than 3.6 million echo images per second in a slow­motion picture, then freezes and processes them.
All products with a dielectric constant ε more than 2.0 reflect radar impulses suffi­ciently (note: air has a dielectric constant ε
1).
%
50 40 30 20 10
5 %
5
0
2
4 6 8 12 14 16 18
0
25 %
10
40 %
20
of
r
r
ε
r
Reflected radar power dependent on the dielectric constant of the measured product
t
t
Time transformation
VEGAPULS 56 Profibus PA 5
of
Product description
The signal reflection grows stronger with increasing product conductivity or dielectric constant. Hence virtually all products can be measured.
With standard flanges of DN 50 to DN 250, ANSI 2“ to ANSI 10“ the sensor antenna sys­tems can be adapted to various products and measuring environments. The high­quality materials of the sensors can also withstand extreme chemical and physical conditions. The sensors deliver stable, repro­ducible analogue or digital level signals with reliability and precision, and have a long useful life.
Continuous and reliable
Unaffected by temperature, pressure and individual gas atmospheres, VEGAPULS radar sensors are ideal for non-contact, fast and accurate level measurement of various products.
%
0,03 0,02 0,01
0
100 500 1000 1300 ˚C
0
0,018 %
Temperature influence: Temperature error absolutely zero (e.g. at 500°C 0.018 %)
%
10
5
0
10
0
0,8 %
20 30 40 60
50
Pressure influence: Error with pressure increase very low (e.g. at 50 bar 1.44 %)
0,023 %
3 %
70 80 90 110 120 130 140
100
bar

1.2 Application features

Applications
• level measurement of liquids, limited use in solids
• measurement also in vacuum
• all slightly conductive materials and all substances with a dielectric constant
ε
> 2.0 can be measured
r
• measuring ranges 0 … 20 m
Two-wire technology
• power supply and output signal on one two-wire cable
• digital output signal
Rugged and abrasionproof
• non-contact
• high resistance materials
Exact and reliable
• resolution 1 mm
• unaffected by noise, vapours, dusts, gas compositions and inert gas stratification
• unaffected by varying density and tem­perature of the medium
• measurement of pressures up to 64 bar and product temperatures up to 350°C
Communicative
• individual wiring, with 15 sensors on one two-wire cable (digital output signal)
• integrated measured value display
• optional display module up to 25 m sepa­rate from the sensor
• connection to all bus systems: Interbus S, Modbus, Siemens 3964R, Profibus DP, Profibus FMS, ASCII
• adjustment from PLC level
Ex approvals
• CENELEC, FM, ABS, LRS, GL, LR, ATEX, PTB, FCC
VEGAPULS series 56 sensors enable level measurement with radar in systems where it was previously not used due to high costs.
6 VEGAPULS 56 Profibus PA
Product description

1.3 Profibus output signal

PROPRO
PROcess
PROPRO sult of a joint project of thirteen companies and five universities. The companies Bosch, Klöckner-Möller and Siemens played a deci­sive role. The specifications of the bus are described in the protocol layers 1, 2 and 7 of the ISO/OSI reference model and are avail­able from the PNO (Profibus User Organisa­tion). Layers 3 … 5 have not yet been developed as a standard, leaving Profibus with far-reaching perspectives for the future.
Today approx. 600 companies make use of Profibus technology and belong to the PNO, Profibus Specification. Profibus Periphery and Profibus mation.
As a process automation bus, Profibus PA enables power supply over the bus. Up to 32 sensors with power supply and measuring signal can be operated on a shielded two­wire cable that carries both power supply and measuring signal. In Ex areas, up to ten sensors can be connected from the PA level to one two-wire cable (EEx ia).
Bus structure
A Profibus system with DP and PA segments consists of up to 126 Master and Slave par­ticipants. Data are always exchanged from point to point, with the data traffic being ex­clusively controlled and checked by master devices. Communication is carried out ac­cording to the Token-Passing procedure. This means that the master holding the Token can contact the slaves, give instructions, enquire data and cause the slaves to receive and transmit data. After the work is done or after a predetermined time interval, the Token is passed on by the master to the next mas­ter.
FIFI
BUSBUS
FIeld
BUS (PROFIBUS) is the re-
FIFI
BUSBUS
FMSFMS
FMS stands for Fieldbus Messaging
FMSFMS
DPDP
DP for Decentralised
DPDP
PP
AA
P
A for Process Auto-
PP
AA
Master-Class 1
is the actual automation system, i.e. the proc­ess control computer or the PLC that en­quires and processes all measured values.
Master-Class 2
One or several Master-Class 2 can operate in a Profibus network. As a rule, Master-Class 2 devices are engineering, adjustment or visu­alisation stations. The VEGA adjustment soft­ware VVO (VEGA Visual Operating) operates as Master-Class 2 participant on the DP bus and can work on an engineering PC, on an adjustment PC or on the process control computer and can access any VEGA sensor on the PA level.
Instrument master file
A so-called GSD (instrument master file) is provided with the VEGAPULS Profibus sen­sor. This file is necessary to integrate the sensor in the bus system. The GSD contains, beside the sensor name and manufacturer, the sensor-specific communication param­eters which are necessary for a stable inte­gration of the sensor in the bus.
Load the GSD belonging to the sensor into your bus configuration program. If the GSD is not available, it can be downloaded from the VEGA homepage: http://www.vega.com.
Do not mistake the GSD for the EDD (Elec­tronic Device Description), which is neces­sary for the PDM environment and can also be found on the VEGA homepage.
VEGAPULS 56 Profibus PA 7
Product description

1.4 Adjustment

Each measuring situation is unique. For that reason, every radar sensor needs some basic information on the application and the environment, e.g. which level means "empty" and which level "full". Beside this "empty and full adjustment", many other settings and adjustments are possible with VEGAPULS radar sensors. The output of echo curves or the calculation of vessel linearisation curves by means of vessel dimensions are only two examples.
Profibus adjustment structure
In the Profibus environment, there are differ­ent adjustment concepts and adjustment tools which often differ considerably from manufacturer to manufacturer. From the us­er’s point of view, a manufacturer-independ­ent adjustment program which could be operated directly on the Profibus DP, as well as at any system node (e.g. the engineering station or the process control), would be ideal.
In the past, only the program "SIMATIC PDM“, based on the HART ture, could fulfil this wish (though with the limitations common to HART
®
HART
, the availability of an instrument-spe­cific database for a comprehensive adjust­ment with PDM (Process Device Managing) is a requirement. Otherwise, only the basic instrument functions, such as adjustment, are available. In the PDM environment, this instru­ment-specific database is called EDD (Elec­tronic Device Description), in perfect analogy to the HART
®
environment which also re­quires, except for the VEGA HART ments, a DD (Device Description) for each sensor.
®
adjustment struc-
®
). As with
®
instru-
We are aware of the disadvantages of the
®
HART
environment: for each sensor/partici­pant, an individual DD must be loaded, which in addition, must always be the latest and most up-to-date DD. Special adjustment options such as e.g., the output of an echo curve, are available neither with HART
®
nor with PDM. User-friendly adjustment is out of the question. With VEGA’s adjustment pro­gram VVO, those restrictions belong to the past.
The legitimate wish of many Profibus users for a manufacturer-independent adjustment tool without EDD has been realised in the form of PACTware number of process technology companies developed PACTware
TM 1)
. An association of a
TM
: a Process Automa­tion Configuration Tool that can run different manufacturer software tools under a stand­ardized user interface and adjustment struc­ture. Specialists call this technology Field Device Transcription. Just as different Win­dows printer drivers enable operation of completely different printers under a single user interface, PACTware
TM
enables operation of all field instruments under a single user interface. Instrument-specific databases (EDD), like those required for SIMATIC PDM, are not necessary.
As a result of this development, three adjust­ment media are available for VEGA-Profibus sensors:
- adjustment with the PC and the adjustment
program VVO (VEGA Visual Operating) as stand-alone tool, on the segment coupler or directly on the sensor.
- adjustment with the detachable adjustment
module MINICOM in the sensor
- adjustment with the SIMATIC PDM adjust-
ment program (requires EDD instrument databases) from the control room.
- adjustment with the universal adjustment
interface PACTware
TM
on the sensor, from
the control room or on the segment coupler.
8 VEGAPULS 56 Profibus PA
Product description
Adjustment with the adjustment pro­gram VVO - VEGA Visual Operating
The setup and adjustment of the radar sen­sors is generally done on the PC with the adjustment program VEGA Visual Operating (VVO) or with PACTware The programs lead quickly through adjust­ment and parameter setting by means of pictures, graphics and process visualisations.
TM
under Windows®.
Note:
The adjustment program VVO must be avail­able in version 2.70 or higher.
The VEGA adjustment software VVO (VEGA Visual Operating) operates either as a subprogram of the host program PACTware
TM
acc. to the FDT concept (Field Device Tool) or as an independent adjustment program on any PC, engineering station or process con­trol computer.
The adjustment program recognises the sensor type
Visualised input of a vessel linearisation curve in the adjustment program VVO
VEGA’s adjustment program VVO can ac­cess the adjustment options of VEGA sen­sors in their entirety and, if necessary, can update the complete sensor software. To do this, the adjustment program must be in­stalled on a PC which is equipped with a Profibus Master Class 2 interface card or the interface adapter VEGACONNECT 3.
The PC with the Profibus interface card can be connected directly to any point on the DP bus with the standard RS 485 Profibus cable.
In conjunction with the adapter VEGACONNECT, the PC can be connected directly to the sensor. VEGACONNECT com­municates via a small jack directly with the respective sensor.
The adjustment and parameter data can be saved at any time on the PC with the adjust­ment software and can be protected by passwords. If necessary, the adjustments can be transferred quickly to other sensors.
VEGAPULS 56 Profibus PA 9
In practice, the adjustment program VVO is often installed as a tool on an engineering station or operating station. VVO then ac­cesses all VEGA sensors directly over the bus via the Profibus interface card (e.g. from Softing) as Master Class 2, from the DP level to the PA level (via segment coupler) right down to the individual sensor.
Beside the instrument master file (GSD), with which a sensor is logged into the Profibus system, the majority of all Profibus sensors requires for adjustment, beside the specific adjustment software, also a so-called EDD (Electronic Device Description) for each sensor, in order to access and adjust the sensor from the bus levels. This is not the case with VVO. The adjustment software VVO can communicate at any time with all VEGA sensors without the help of a special database. Of course, all other non-Profibus VEGA sensors can be adjusted with the adjustment software as well (4 … 20 mA sensors or VBUS sensors). With VEGA sen­sors, it is not necessary to go looking for the latest EDD. This is the basic prerequisite for a manufacturer-independent adjustment program, like PACTware
TM
, anticipated by
many users, see following pages.
Product description
10 VEGAPULS 56 Profibus PA
Product description
Adr. 21
SPS
Adr. 22
VVO
3
PA-
Adr. 23
Bus
Master-Class 1
Adr. 1
DP-Bus
Adr. 24
Profibus DP interface card as Master-Class 2 (e.g. Softing)
Adr. 10
Adr. 57
Segment coupler
Adr. 25 … 56
2
3
Adr. 58
Adr. 59
(max. 32 participants)
Adr. 60
Adr. 26
Adr. 25
Adr. 27
Adr. 28
Adr. 29
Adjustment of the VEGAPULS radar sensors from process control via a Profibus interface card in the process control computer or in an additional PC. The adjustment software VEGA Visual Operating (VVO) accesses via the interface (interface card) the sensors bidirectionally.
VEGAPULS 56 Profibus PA 11
Product description
Adjustment with adjustment module MINICOM
With the small (3.2 cm x 6.7 cm) 6-key ad­justment module with display, you carry out the adjustment in clear text dialogue. The adjustment module can be plugged into the radar sensor or into the optional, external indicating instrument.
Tank 1
+
-
m (d)
12.345
Detachable adjustment module MINICOM
The adjustment module can be removed easily so that unauthorised people cannot modify the sensor setting.
ESC
+
-
Tank 1 m (d)
12.345
OK
2
PA-Bus
ESC
+
-
Tank 1 m (d)
12.345
OK
4
Adjustment with the SIMATIC PDM adjustment program
For adjustment of all essential functions of the VEGA sensor with the adjustment station SIMATIC PDM from Siemens, a so-called EDD is required. Without this EDD, only the basic functions such as min./max. wet adjust­ment or integration time can be adjusted with the PDM adjustment program. Further impor­tant adjustment functions, such as the input of the "
Meas. environment
storage are not available without EDD. After
ESC
integration of the EDD files in the Simatic PDM
OK
adjustment software, all important adjustment
“ or a false echo
functions are accessible. If it is not at hand, the obligatory GSD (instrument master file) as well as the EDD (Electronic Device De­scription) necessary for PDM can be downloaded from the VEGA-Homepage (http://www.vega.com).
Adjustment with PACTware
The above-mentioned program PACTware is a manufacturer-independent automation/ configuration tool, by which access to instru­ments of different manufacturers (Krohne, Pepperl + Fuchs, VEGA, VIKA- Bürkert…) is possible. The VEGA adjustment software VVO works as a subprogram/menu. PACTware options for the sensor/instrument being accessed.
PACTware constructed in tree structure. Operating instructions for PACTware the PACTwareTM documentation. They are not described in this operating instructions manual.
TM
activates the required menu
TM
looks different than VVO and is
TM
can be found in
TM
TM
max. 25 m
Adjustment with detachable adjustment module. The adjustment module can be plugged into the radar sensor or into the external indicating instrument VEGADIS 50.
12 VEGAPULS 56 Profibus PA
Product description

1.5 Antennas

The antenna is the eye of the radar sensor. An uninitiated observer would probably not realise how carefully the antenna geometry must be adapted to the physical properties of electromagnetic fields. The geometrical form determines focal prop­erties and sensitivity - the same way it deter­mines the sensitivity of a unidirectional microphone.
For different applications and process re­quirements various antenna systems are available.
Horn antenna
Horn antennas focus the radar signals very well. Made of 1.4571 (stainless steel) or Hastelloy C22 they are very rugged, and physically as well as chemically resistant. Horn antennas are used for measurement in closed or open vessels.
Pipe antenna
Only in conjunction with a meas­uring tube, i.e. with a surge or bypass tube (which can also be angled), do horn antennas form a complete antenna system. Pipe antennas are mainly suit­able for very agitated products or for products with very small dielectric constant.
The antenna can be with or with­out horn. The antennas are char­acterised by a very high antenna gain. High reliability can be achieved even with products having poor reflective proper­ties.
For the radar signals, the meas­uring tube acts as a conductor.
DN 50
The running time of the radar signal changes in the tube and depends on the tube diameter.
Therefore, the sensor must be informed about the tube inner diameter so that the change in the running time can be taken into account and precise level signals ensured.
DN 150
DN 80
DN 250
VEGAPULS 56 Profibus PA 13

2 Types and versions

VEGAPULS 56 sensors are a newly devel­oped generation of very compact, high tem­perature radar sensors. They enable for the first time non-contact level measurements under high temperatures and pressures. They offer the advantages of radar level measurement for applications in which the special advantages of radar could not be previously applied due to extreme process conditions.
VEGAPULS 56 radar sensors utilise two-wire technology perfectly. The supply voltage and the output signal are transmitted via one two­wire cable. They provide an analogue 4 … 20 mA output signal as output or meas­uring signal. This operating instructions manual describes the sensors with digital output signal.
Types and versions

2.1 Type surve y

General features
• Level measurement of processes and products under high temperatures and high pressures
• Measuring range 0 … 20 m
• Ex approved in Zone 1 and Zone 10 (IEC) or Zone 0 and Zone 20 (ATEX) classifica­tion mark EEx ia IIC T6 or EEx d ia IIC T6
• Integrated measured value display
• External measured value display which can be mounted at a distance of up to 25 m in Ex area
Survey of features
Signal output
- digital transmission of measuring signals to a VEGAMET signal conditioning instrument or the VEGALOG processing system
VEGAPULS 56 DN 150
VEGAPULS 56 DN 50 pipe antenna
VEGAPULS 56 DN 80 pipe antenna
Power supply – two-wire technology (voltage supply and
digital signal via one two-wire cable)
Process fitting – DN 50; ANSI 2“ – DN 80; ANSI 3“ – DN 100; ANSI 4“ – DN 150; ANSI 6“ – DN 200; ANSI 8“ – DN 250; ANSI 10“
Adjustment –PC – adjustment module in the sensor – adjustment module in external indicating
instrument
Antennas – horn antenna with stainless steel horn and
ceramic tip
– standpipe antenna only with ceramic tip or
with small horn and ceramic tip
14 VEGAPULS 56 Profibus PA
Types and versions

2.2 Type code

56… High temperature radar sensor …K 4 … 20 mA output signal (not described in this operating instruction manual) …P Output signal Profibus PA
VEGAPULS 56 V EXXX X X X X X X X
J - Tube extension for horn antenna X - without
A - Aluminium housing D - Aluminium housing with Exd connection housing
T - Seal of the antenna system of Tantalum
KVX - Process fitting DN 50 PN 16 (for standpipe) LV6 - Process fitting DN 80 PN 16 (for standpipe) EV1 - Process fitting DN 100 PN 16 (for standpipe) FV2 - Process fitting DN 150 PN 16 SVX - Pr ocess fitting ANSI 2“ 150 psi (for standpipe) WV6 - Process fitting ANSI 3“ 150 psi (for standpipe) PV1 - Process fitting ANSI 4“ 150 psi (for standpipe) VV2 - Process fitting ANSI 6“ 150 psi 0V2 - Process fitting ANSI 6“ 300 psi 1V2 - Process fitting ANSI 6“ 600 psi (1.4571) 1M2 - Process fitting ANSI 6“ 600 psi (Hastelloy C22) YYY - Ot her pr ocess connections and materials
X - without display A - with integrated display
X - without adjustment module MINICOM
B - with adjustment module MINICOM (mounted)
B - 20 … 72 V DC; 20 … 250 V AC; 4 … 20 mA; HART D - Two-wire (loop-powered); 4 … 20 mA; HART E - Power supply via signal conditioning instrument G - Profibus PA (power supply from segment coupler) P - 90 … 250 V AC (only in USA) N - 20 … 36 V DC, 24 V AC (only in USA) Z - Power supply via signal conditioning instrument (only in USA)
®
®
.X - FTZ approval (Germany) EX.X - Approved Zone 1 and Zone 10 EX0.X - Ex approved Zone 0
K - Analogue 4 … 20 mA output signal
(two-wire technology)
P - Digital output signal (two-wire technology) Profibus
Instrument series for high temperature application
Measuring technology (PULS for radar)
VEGAPULS 56 Profibus PA 15
Types and versions

2.3 Bus configuration

The type of radar sensor you use depends on your process requirements and mounting conditions, as well as on the requirements of your control, regulative, or process control system.
VEGAPULS 56 Profibus radar sensors are sensors for use in Profibus PA environment. Profile 3 has been implemented in the sen­sors. A measuring system consists of one or several sensors, one or several segment couplers and one DP master computer, such as e.g. a S7 PLC with Profibus interface or a process control system with Profibus DP­Master-Slot. The processing unit, e.g. the PLC, evaluates the level-proportional, digital measuring signals in a number of evaluation routines and puts them to use process-spe­cifically.
On the following four pages you will see schematic illustrations of the bus configura­tion.
The automation system as Master-Class 1 takes over bus control completely. It reads out all signals cyclically and, if necessary, gives instructions to the participants (e.g. sensors). Besides this, additional master systems (e.g. visualisation systems or ad­justment tools) can be connected to the DP bus. These systems operate as so-called Master-Class 2 participants. Like the Master­Class 1 system, they can read out signals, give instructions and operate in the acyclical mode.
A DP bus does not allow power supply via signal cable, whereas the PA bus does. Both, DP and PA, require at a minimum a screened two-wire cable. The DP bus can additionally have up to 8 cores (screened), of which some can be supply cables (see also "Instal­lation Guides PA + DP“ of the Profibus User Organisation (PNO).
Each participant on the bus must have an unambiguous address. The addressing covers both bus levels. A Profibus DP net­work can have max. 126 participants, includ­ing all participants on the PA level. In practice, each Master-Class 1 computer gets address 1 and the Master-Class 2 comput­ers address 10 … 20. As a rule, the slaves or participants get the addresses 21 … 126. On the Profibus PA network segment, max. 32 sensors are possible on one PA segment coupler.
Ex environment
In Ex environment, intrinsically safe (EEx ia) PA sensors are used with Ex segment cou­plers. Generally, the number of PA sensors on a segment coupler (Ex or non Ex) de­pends on the current requirement of the sensors and on the current supplied by the segment coupler. Segment couplers for EEx ia environment provide 90 … 110 mA. The number of sensors results from the sum of:
- the basic current intake of all sensors
- plus 9 mA communication signal
- plus the leakage currents of all sensors
- plus a recommended current reserve (approx. 10 mA)
The min. basic current has been set at 10 mA according to the Profibus specification. VEGA Profibus sensors constantly consume a basic current of 10 mA and operate without leakage current requirement, so that in Ex environment, up to max. ten VEGA sensors can be operated on one segment coupler.
16 VEGAPULS 56 Profibus PA
Types and versions
VEGAPULS 56 Profibus PA 17
Types and versions
1
Master-Class 1
Bus terminator
3...9
Profibus PA (31,25 kBit/s)
Profibus DP
21
Profibus interface card
RS 232
22...54
3
RS 485
10
Master-Class 2
Segment coupler
Bus terminator
2
22
23
24
53
54
VEGACONNECT 3
PA segment on segment coupler: 1 … 32 sensors on one two-wire cable (Ex: 10 sensors)
18 VEGAPULS 56 Profibus PA
Types and versions
Profibus DP segment level 1 … 126 participants including all DP and PA participants. Through segment couplers and PA segments, the trans­mission rate, also on the DP level, is determined by the slowest coupler or participant on the Profibus DP and PA network.
Bus terminator
3...9
M
Segment coupler
3...9
3~M
89
90
55
56...88
Bus terminator
2
Profibus PA
2
Bus terminator
56
57
87
88
PA segment on segment coupler: 1 … 32 sensors on one two-wire cable (Ex: 10 sensors)
VEGAPULS 56 Profibus PA 19
Types and versions
1
Master-Class 1
Bus terminator
VEGALOG
Profibus PA (31,25 kBit)
3~M
3…9
Profibus DP
Profibus interface card
21
3
RS 485
22
10
Master-Class 2
VEGACONNECT 3
4
RS 232
1
2
3
5
11
12
4
1 … 15 PA sensors per two-wire cable
13
15
14
with independent address zone (Ex: 10 sensors)
20 VEGAPULS 56 Profibus PA
Types and versions
Profibus DP segment level 1 … 126 participants including all DP and PA participants. Up to 12 MBit/s transmission rate on DP level. In the PA segments 31.25 kBit/s transmission rate.
VEGACONNECT 3
4 … 20 mA (HART )
2
4
4
4
2
2
2
Profibus PA (31,25 kBit)
3…9
23
M
3…9
24
25
VEGALOG
VBUS
Outputs
2
2
2
2
®
2
2
2
2
2
0/4…20 mA
0…10 V
VBUS
2
Bus termi­nator
Profibus PA: 1 … 15 PA sensors per two-wire cable with independent address zone (Ex: 10 sensors)
VBUS: 1 … 15 sensors per two­wire cable Exd: also 15 Ex ia: 5 sensors
VEGAPULS 56 Profibus PA 21
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;
;;

3 Mounting and installation

3.1 General installation instructions

Measuring range
The reference plane for the measuring range of the sensors is the lower edge of the flange. The measuring range is 0 … 20 m. For meas­urement in surge or bypass tubes (pipe antenna) the max. measuring distance is reduced (see "Technical data - Measuring range“).
Mounting and installation
Keep in mind that in measuring environments where the medium can reach the sensor flange, buildup can form on the antenna which can cause measurement errors. The min. distance of the antenna to the medium should be 5 cm.
Reference plane
min. meas. distance
full
min.
Meas. range
empty
max. meas. distance 20 m
Measuring range (operating range) and max. measuring distance Note: Use of the sensors for applications with solids is limited.
False reflections
Flat obstructions and struts cause large false reflections. They reflect the radar signal with high energy density.
Interfering surfaces with a round profile dif­fuse the reflected radar signals and cause
If flat obstructions in the range of the radar signals cannot be avoided, we recommend the installation of a deflector plate to scatter the reflected signals. Due to this scattering, the interfering signals will be low in amplitude and so diffuse that they can be filtered out by the sensor.
false reflections with lower energy density. Hence, they are less critical than reflections from a flat surface.
Round profiles diffuse radar signals
min. meas. distance
min. meas. distance
full
empty
Profile with smooth interfering surfaces cause large false signals
22 VEGAPULS 56 Profibus PA
A deflector causes signal scattering
Mounting and installation
Emission cone and false reflections
The radar signals are focused by the an­tenna system. The signals leave the antenna in a conical path similar to the beam pattern of a spotlight. This emission cone depends on the antenna used.
Any object in this beam cone causes a reflec­tion of the radar signals. Within the first few meters of the beam cone, tubes, struts or other installations can interfere with the meas­urement. At a distance of 6 m, the false echo of a strut has an amplitude nine times greater than at a distance of 18 m.
At greater distances, the energy of the radar signal distributes itself over a larger area, thus causing weaker echoes from obstruct­ing surfaces. The interfering signals are therefore less critical than those at close range.
If possible, orient the sensor axis perpen­dicularly to the product surface and avoid vessel installations (e.g. pipes and struts) within the 100 % area of the emission cone.
If possible, provide a "clear view“ of the product inside the emission cone and avoid vessel installations in the first third of the emission cone.
Meas. distance
0 m
30˚
10 m
40˚
20 m
6,8 m 6,8 m
0
Emission cone of a DN 100 horn antenna
Meas. distance
0 m
100 %
emitted power
50 %
5,3 m5,3 m
Optimum measuring conditions exist when the emission cone reaches the measured product perpendicularly and when the emis­sion cone is free from obstructions.
10 m
20 m
5,0 m
3,5 m
Emission cone of a DN 150 horn antenna
VEGAPULS 56 Profibus PA 23
20˚
30˚
0
100 %
emitted power
50 %
emitted power
5,0 m
3,5 m
Mounting and installation
Meas. distance
0 m
14˚
100 %
22˚
0
emitted power
50 %
3,8 m
2,4 m
emitted power
10 m
20 m
3,8 m
2,4 m
Emission cone of a DN 250 horn antenna
Heat insulation
In process temperatures of more than 200°C the rear of the flange must be insulated to protect the sensor electronics from radiated heat.
We recommend integrating the sensor insula­tion into the vessel insulation and extending it approx. up to the first tube segment.

3.2 Measurement of liquids

Sensor on DIN socket piece
Most commonly, the mounting of radar sen­sors is done on short DIN socket pieces. The lower side of the instrument flange is the reference plane for the measuring range. The antenna should always protrude out of the flange pipe.
Reference plane
Mounting on DIN socket piece
With a longer DIN socket piece, the horn antenna must protrude at least 10 mm out of the socket.
40°C
60°C
> 10 mm
350°C
100°C
240°C
Mounting on longer DIN socket piece
Vessel insulation
max. 350°C
When mounting on dished vessel tops, the antenna must also protrude at least 10 mm beyond the longer side of the socket).
Heat insulation
24 VEGAPULS 56 Profibus PA
Mounting and installation
> 10 mm
Sensor directly on the vessel top
If the stability of the vessel will allow it (sensor weight), flat mounting directly on the vessel top is a good and economical solution. The top side of the vessel is the reference plane.
Mounting on a dished vessel top
On dished tank ends, please do not mount the instrument in the centre or close to the vessel wall, but approx.
1
/2 vessel radius from
the centre or from the vessel wall.
Dished tank ends can act as paraboloidal reflectors. If the radar sensor is placed in the focal point of the parabolic tank, the radar sensor receives amplified false echoes. The radar sensor should be mounted outside the focal point. Parabolically amplified echoes are thereby avoided.
Reference plane
1
/2 vessel radius
Mounting on dished tank ends
Reference plane
Mounting directly on the flat vessel top

3.3 Measurement in standpipe (surge or bypass tube)

General instructions
Pipe antennas are preferred in vessels which contain many installations, e.g. heating tubes, heat exchangers or fast-running stirrers. Measurement is then possible where the product surface is very turbulent, and vessel installations cannot cause false echoes.
Through focusing of the radar signal within the measuring tube, even products with small dielectric constants (ε reliably measured in surge or bypass tubes. Please note the following instructions.
Surge pipes which are open at the bottom must extend over the full measuring range (i.e. down to 0% level), as a measurement is only possible within the tube.
It is advantageous to install a deflector below the end of the tube. The product can then be reliably detected around the min. level. This is particularly important for products with a dielectric constant of less than 5.
= 1.6 up to 3) can be
r
VEGAPULS 56 Profibus PA 25
;;;
;;;
;
;
;
;
;
Mounting and installation
Surge pipe welded to the tank
Surge pipe in the socket piece
Marking holes in the intermedi­ate flange
max.
Vent hole
Deflector
min.
Pipe antenna systems in the tank
Make sure that the required upper vent hole is on one axis with the marking hole in the intermediate flange (polarisation direction of the radar signals).
Marking hole
100 %
;
;
;
;
;
0 %
Tube flange system as bypass tube
As an alternative to a surge pipe in the ves­sel, a pipe antenna can be mounted outside the vessel as a bypass tube.
When measuring in a surge or bypass tube, the max. measuring range decreases by 5 … 20 % (e.g. DN 50: 16 m instead of 20 m and DN 100 only 19 m instead of 20 m).
Align the sensor such that the marking hole in the intermediate flange is on one axis with the tube holes or tube openings. The polarisation of the radar signal enables a considerably stabler measurement with this alignment.
Extended bypass tube on a vessel with turbulent product movements
26 VEGAPULS 56 Profibus PA
100 %
75 %
0 %
Mounting and installation
Adhesive products
For adhesive products, a surge pipe with a larger inner diameter should be used. For nonadhesive products, the best and most inexpensive solution is a measurement tube with a diameter of 50 mm. For slightly adhe­sive products, use a surge pipe with a nomi­nal diameter of 100 mm to 150 mm to prevent buildup from causing measurement errors.
DN 50
ø 50
DN 80
ø 80
Standpipe measurement of inhomoge­neous products
If you want to measure inhomogeneous prod­ucts or stratified products in a surge pipe, it must have holes, elongated holes or slots. These openings ensure that the liquid is mixed and corresponds to the liquid in the vessel.
ø 100
DN 100
DN 150
ø 150
homogeneous liquids
inhomogeneous liquids
Openings in a surge pipe for mixing of inhomogene-
slightly inhomogeneous liquids
strongly inhomogeneous liquids
ous products
The more inhomogeneous the measured product, the closer together the openings
Pipe antenna with DN 50, DN 80, DN 100 and DN 150
VEGAPULS 56 Profibus PA 27
should be.
Mounting and installation
Polarisation direction
Due to radar polarisation, the holes or slots must be positioned in two rows offset by 180°. The radar sensor must be mounted so that the marking hole of the sensor (located in the intermediate flange) is on one axis with the row of holes in the standpipe.
Marking hole
Rows of holes in one axis with the marking hole
Surge pipe with ball valve
If a ball valve is mounted in the surge pipe, maintenance and servicing can be carried out without opening the vessel (e.g. if it con­tains liquid gas or toxic products).
A prerequisite for trouble-free operation is a ball valve throat that corresponds to the pipe diameter and provides a flush surface with the pipe inner wall.
Make sure there is a ventilation hole in the standpipe.
DN 50
Ball valve
Standpipe ventilation
Correct
Marking hole
The sensor must be directed with the marking hole to the rows of holes or openings.
28 VEGAPULS 56 Profibus PA
Wrong
ø50
Deflector
Tube antenna system with ball valve cutoff in measur­ing tube
Mounting and installation
In products with a small relative dielectric constant, a > 45° deflector plate installed under the end of the standpipe will prevent the vessel bottom from being detected as level instead of the product surface.
Vent hole
Pipe antenna systems must be provided with a vent hole at the upper end of the surge pipe. A missing hole will cause inaccurate measurements.
Correct
Pipe antenna: The surge pipe open to the bottom must have a vent or equalisation hole on top.
Wrong
VEGAPULS 56 Profibus PA 29
Guidelines for standpipe construction
Flange DN 50
100 %
Rz 30
Connection sleeves
Welding neck flanges
150…500
Welding neck flange
2,9…6
Welding of the connect­ing sleeve
5…15
0,0...0,4
Welding of the welding neck flange
2,9
1,5…2
Mounting and installation
Radar sensors for measurement on surge or bypass pipes are routinely mounted in flange sizes DN 50, DN 80, DN 100 and DN 150.
The illustration on the left shows the construc­tional features of a measuring pipe (surge or bypass tube) as exemplified by a sensor with DN 50 flange.
The radar sensor with a DN 50 flange only forms a functioning measuring system in conjunction with a measuring tube.
The measuring pipe must be smooth inside (average roughness Rz < 30). Use stainless steel tubing (drawn or welded lengthwise) for construction of the measuring pipe. Extend the measuring pipe to the required length with welding neck flanges or with connecting sleeves. Make sure that no shoulders or projections are created during welding. Be­fore welding, join pipe and flange with their inner surfaces flush and exactly fitting.
Avoid welding through the pipe wall. The pipe must remain smooth inside. If the welding process inadvertently reaches the inner surface, any resulting roughness or welding beads must be carefully removed and bur­nished, as these cause false echoes and encourage product adhesion.
0,0…0,4
Deburr the holes
Deflector
0 %
ø 51,2
~45˚
Meas. pipe fasten­ing
Min. product level to be measured (0 %)
Vessel bottom
30 VEGAPULS 56 Profibus PA
Mounting and installation
Flange DN 100
100 %
Deburr the holes
ø 96
2
Smooth welding neck flange
Welding of the plain welded flange
5…15
The illustration on the left shows the construc­tional features of a measuring pipe as exem­plified by a sensor with DN 100 flange.
Radar sensors with flanges DN 80, DN 100 and DN 150 are equipped with a horn antenna. With these sensors, a plain welded flange can also be used on the sen­sor end instead of a welding neck flange.
If the vessel contains agitated products, fasten the measuring pipe to the vessel bot­tom. Provide additional fastenings for longer measuring pipes.
A deflector at the bottom end of the measur­ing pipe scatters the radar signals. In nearly empty vessels and products with low dielec­tric value, the deflector ensures that the product surface is detected rather than the vessel bottom. Products with low dielectric constants are partially penetrated, allowing the vessel bottom to produce (when the product level is low) a considerably stronger radar echo than the product surface.
150…500
0,0…0,4
With the deflector, however, only the useful signal is received in a nearly empty vessel ­the 0 % level is reliably detected and the correct measured value transmitted.
Connecting sleeve
Welding neck flanges
Rz 30
Deflector
0 %
ø 100,8
~45˚
VEGAPULS 56 Profibus PA 31
3,6
Welding of the welding neck flange
3,6
1,5…2
0,0…0,4
Meas. pipe fastening
Min. product level to be measured (0 %)
Vessel bottom
Mounting and installation

3.4 False echoes

The installation location of the radar sensor must be selected such that no installations or inflowing material cross the radar impulses. The following examples and instructions show the most frequent measuring problems and how to avoid them.
Vessel protrusions
Vessel forms with flat protrusions can, due to their strong false echoes, greatly affect the measurement. Shields above these flat pro­trusions scatter the false echoes and guaran­tee a reliable measurement.
Correct Wrong
Shield
Vessel protrusions (slope)
Intake pipes, i.e. for the mixing of materials ­with a flat surface directed towards the sen­sor - should be covered with a sloping shield that will scatter false echoes.
Vessel installations
Vessel installations such as, for example ladders, often cause false echoes. Make sure when planning your measuring location that the radar signals have free access to the measured product.
Correct Wrong
Ladder
Vessel installations
Ladder
Struts
Struts, like other vessel installations, can cause strong false echoes that are superim­posed on the useful echoes. Small shields effectively hinder a direct false echo reflec­tion. These false echoes are scattered and diffused in the area and are then filtered out as "echo noise“ by the measuring electronics.
Correct Wrong
Correct Wrong
Shields
Shield
Vessel protrusions (intake pipe)
32 VEGAPULS 56 Profibus PA
Struts
;;
;;
;;;
;;;
;;;
;;;
;;
;;
;;
Mounting and installation
Strong product movements
Strong turbulence in the vessel, e.g. caused by stirrers or intense chemical reactions, can seriously interfere with the measurement. A surge or bypass tube (see illustration) of sufficient size always allows, provided that the product causes no buildup in the tube, a reliable measurement even with strong turbu­lence in the vessel.
Correct Wrong
100 %
75 %
0 %
Strong product movements
Products that cause only light buildup can be measured by using a tube with 100 mm nomi­nal width or more. Light buildup in a tube of this size is no problem.
Buildup
If the sensor is mounted too close to the vessel wall, buildup and deposits from the measured product on the vessel wall cause false echoes. Position the sensor at a suffi­cient distance from the vessel wall. Please also note chapter "4.1 General installation instructions“.
Correct Wrong
Buildup
Inflowing material
Do not mount the instrument in or above the filling stream. Ensure that you detect the product surface and not the inflowing mate­rial.
Correct
Wrong
Inflowing material
VEGAPULS 56 Profibus PA 33
Mounting and installation

3.5 Installation mistakes

Socket piece too long
If the antenna is mounted in a socket exten­sion that is too long, false reflections are caused, and measurement is hindered. Make sure that the horn antenna protrudes at least 10 mm out of the socket piece.
Correct Wrong
10 mm
Horn antenna: correct and wrong socket length
Wrong orientation to the product
A sensor orientation which does not point directly to the product surface causes weak measuring signals. Direct the sensor axis perpendicularly to the product surface to achieve optimum measuring results.
Parabolic effects on dished or arched vessel tops
Round or parabolic tank tops act like a para­bolic mirror on the radar signals. If the radar sensor is placed at the focal point of such a parabolic tank top, the sensor receives am­plified false echoes. The optimum mounting position is generally in the range of half the vessel radius from the centre.
Correct
>10 mm
1
/
~
2
vessel radius
Wrong
Correct Wrong
Wrong
Ladder
Direct sensor perpendicularly to the product surface
34 VEGAPULS 56 Profibus PA
Ladder
Mounting on a vessel with parabolic tank top
Mounting and installation
Standpipe (pipe antenna) without venti­lation hole
Pipe antenna systems must be provided with a ventilation hole on the upper end of the pipe. If this hole is missing, incorrect meas­urements will result.
Correct Wrong
Pipe antenna: The surge pipe open to the bottom must have a ventilation hole on top
Wrong polarisation direction on the standpipe
When measuring in a surge pipe, especially if there are holes or slots for mixing in the tube, it is important that the radar sensor is aligned with the rows of holes.
The two rows of holes (displaced by 180°) of the measuring tube must be in one plane with the polarisation direction of the radar signals. The polarisation direction is always in the same plane as the marking hole. Precise directing is achieved by means of the mark­ing holes in the intermediate flange.
Marking hole
The polarisation direction is in one plane with the marking hole (the sensor must be directed with the marking hole to the rows of holes).
Sensor too close to the vessel wall
If the radar sensor is mounted too close to the vessel wall, strong false echoes can be caused. Buildup, rivets, screws or weld joints superimpose their echoes onto the product or useful echo. Please ensure sufficient dis­tance from the sensor to the vessel wall.
In case of good reflection conditions (liquids, no vessel installations), we recommend se­lecting the sensor distance such that there is no vessel wall within the inner emission cone.
For products with less favourable reflective properties, it is a good idea to also keep the outer emission cone free of interfering instal­lations. Note chapter "4.1 General installation instructions“.
Foam generation
Thick, dense and creamy foam can cause incorrect measurements. Provide a means to prevent foam or measure in a bypass tube. Check, if necessary, the possibility of using a different measuring technology, e.g. capaci­tive electrodes or hydrostatic pressure trans­mitters.
VEGAPULS 56 Profibus PA 35

4 Electrical connection

4.1 Connection – Connection cable – Screening
Safety information – Qualified person­nel
Instruments which are not operated with protective low voltage or DC voltage must be connected only by qualified personnel. This also applies to the configuration of measuring systems planned for Ex environment.
As a rule, do all connecting work in the com­plete absence of line voltage. Always switch off the power supply before you carry out connecting work on the radar sensors. Pro­tect yourself and the instruments.
Connection cables and bus configuration
Note the Profibus specification. The connec­tion cables must be specified for the ex­pected operating temperatures in the plant and must have an outer diameter of 6 … 12 mm, to ensure sealing effect of the cable entry on the sensor.
For power supply and bus communication, a two-wire cable acc. to the Profibus specifica­tion (up to max. 2.5 mm of conductor) is used. The electrical connec­tion on the sensor is made by spring-loaded terminals.
In a laboratory setup, a Profibus system will also work with standard, unshielded two-wire cable. In practice however, an automation network and bus system can only be pro­tected reliably against electromagnetic inter­ference with screened cable. Acc. to the Profibus specification (IEC 1158-2), screened and twisted cables are pre­scribed. All participants are connected in one line
2
cross-section area
Electrical connection
(serially). At the beginning and end of the bus segment, the bus is terminated by an active bus termination. On the DP bus level, most participants already have a bus termi­nation implemented. With more than 32 par­ticipants on the DP level, a so-called repeater must be used to open and combine another DP level with a max. of 32 additional partici­pants. On the PA bus branch of the segment coupler, the PA radar sensors work also with max. 32 participants (Ex max. 10 partici­pants).
A PA sensor can work only in conjunction with a Profibus DP system, to which a Profibus PA subsystem is connected. A PA Profibus par­ticipant must consume min. 10 mA supply current.
Connection cable and cable length
Connection cables must correspond to the Profibus specification and the FISCO model. The sensor cable must be in conformity with the values of the reference cable acc. to IEC 1158-2:
2
0.8 mm Z C
The max. cable length first of all depends on the transmission speed: up to 32 kbit/s: 1900 m Prup to 32 kbit/s: 1900 m Pr
up to 32 kbit/s: 1900 m Pr
up to 32 kbit/s: 1900 m Prup to 32 kbit/s: 1900 m Pr up to 94 kbit/s: 1200 m Profibus DP up to 188 kbit/s: 1000 m Profibus DP up to 500 kbit/s: 500 m Profibus DP up to 1500 kbit/s: 200 m Profibus DP up to 12000 kbit/s: 100 m Profibus DP
The distributed resistance of the cable, in
; R
= 44 Ω/km;
DCmax.
= 80 … 120 ; damping = 3 dB/km;
31.25kHz
= 2 nF/km.
asymmetric
ofibus Pofibus P
ofibus P
ofibus Pofibus P
AA
A
AA
36 VEGAPULS 56 Profibus PA
Electrical connection
conjunction with the output voltage of the segment coupler and the current requirement (VEGAPULS 10 mA) or the voltage require­ment (VEGAPULS 9 V) of the sensors, deter­mines the max. length of the cable.
In a practical application of a PA bus branch, the max. length of the cable is also deter­mined (beside the required supply voltage and max. current consumption of all partici­pants on the PA bus branch) by the bus structure and the type of segment coupler used.
The cable length results from the sum of all cable sections and the length of all stubs. The length of the individual stubs must not exceed the following lengths: 1 … 12 stubs 120 m (Ex: 30 m) 13 … 18 stubs 60 m (Ex: 30 m) 19 … 24 stubs 30 m (Ex: 30 m)
More than 24 stubs are not permitted, whereby each branch longer than 1.2 m is counted as a stub. The total length of the cable must not exceed 1900 m (in Ex version 1000 m).
Ground terminal
The electronics housings of the sensors have a protective insulation. The ground terminal in the electronics is galvanically connected with the metallic process connection. For sensors with a plastic thread as process fitting, the sensor grounding must be made by a ground connection to the outer ground termi­nal.
Screening
"Electromagnetic pollution“ caused by elec­tronic actuators, energy cables and transmit­ting systems has become so pervasive that shielding for normal two-wire bus cable is usually a necessity. According to the Profibus specification, the screen should be grounded on both ends. To avoid potential equalisation currents, a potential equalisation system must be provided in addition to the screen­ing.
According to specification, we recommend the use of twisted and screened two-wire cable, e.g.: SINEC 6XV1 830-5AH10 (Sie­mens), SINEC L26XV1 830-35H10 (Siemens), 3079A (Belden).
Alternatively, when grounding at both ends in non-Ex areas, the cable shielding can be connected on one ground side (in the switch­ing cabinet) via an Y 1500 V) to the ground potential. Make sure
-capacitor (e.g. 10 nF,
C
that the ground connection has the lowest possible resistance (foundation, plate or mains earth).
Profibus PA in Ex environment
When used in Ex area, a PA bus with all con­nected instruments must be carried out in intrinsically safe protection class "i“. Four-wire instruments requiring separate supply must at least have an intrinsically safe PA connec­tion. VEGA sensors for PA-Ex environment are generally "ia” two-wire instruments.
VEGAPULS 56 Profibus PA 37
Electrical connection
In the so-called Fieldbus Intrinsically Safe Concept (FISCO), the general conditions for an Ex safe bus configuration have been laid down. Therein, the participants and the bus cables with their electrical data have been determined, so that the linking of these com­ponents always meets Ex requirements. A more time-consuming Ex calculation is there­fore not necessary. You can build your Ex bus according to the IEC standard 1158-2.
The Ex segment coupler delivers a controlled power supply to the PA bus. It acts as source in the PA branch. All other compo­nents (field instruments and bus terminators) are only consumers. A field instrument must consume at least 10 mA. Ideally, an individual sensor should not consume more than 10 mA, so that the number of instruments can be as large as possible.
VEGA PA sensors, whether Ex or non Ex, consume a constant current of 10 mA. Ac­cording to the Profibus specification, this is the minimum participant current. With VEGA sensors it is therefore possible to connect 10 sensors (also in Ex environment) even with a limited energy supply from the Ex segment couplers.
Watch out for potential losses
Due to potential losses, earthing on both ends without a potential equalisation system is not allowed in Ex applications. If an instru­ment is used in hazardous areas, the re­quired regulations, conformity and type approval certificates for systems in Ex areas must be noted (e.g. DIN 0165). Please also note the approval documents with the safety data sheet attached to the Ex sensors.
Electrical data of the cables
R
DC
No. of A in Z cores mm
2
31.25kHz
C in Damping Screen nF/km
SINEC 6XV1 44 Ω/km 2 0.75 100 Ω < 90 < 3 dB/km Cu braiding 830-5AH10 +/- 20 39 kHz (Siemens)
SINEC L26XV1 44 Ω/km 2 0.75 100 Ω < 90 < 3 dB/km Cu braiding 830-35H10 +/- 20 39 kHz (Siemens)
3079A 105 /km 2 0.32 150 29.5 < 3 dB/km Foil (Belden) 39 kHz
38 VEGAPULS 56 Profibus PA
Electrical connection

4.2 Sensor address

In a Profibus system composed of Profibus DP and Profibus PA subsystem, each partici­pant must have a unique address. Each participant, whether master or slave, is accessed by means of its own address in the bus system. The address of a partici­pant, whether on DP or PA level, should be assigned before connecting to the bus, be­cause an address can be used only once. If an address is used twice, interference in the bus will be caused.
The address of a radar sensor can be set in two ways:
- with the adjustment software VVO (soft­ware addressing) or
- with the DIP switch block in the sensor (hardware addressing).
VEGA Profibus sensors are delivered with the address set at 126 (all DIP switches to "ON“). Remember, in a Profibus system there are max. 126 participants possible. When the DIP switch is set to address 126 (or higher), the address can be adjusted with the adjust­ment software VVO, the adjustment module MINICOM or another configuration tool (e.g. PDM). However, there can be only one sen­sor on the bus with address 126 (delivery status) during address assignment via soft­ware. For that reason, hardware addressing (DIP switch) before connection to the bus is recommended.
Hardware addressing
The DIP switches generate an address number in the binary system. This means that, from right to left (ascending), any switch represents a number twice as high as the previous switch on the right. The corre­sponding number in the decimal system results from the sum of all switches set to "ON“. In the illustration you see the decimal number that corresponds to each individual DIP switch.
DIP switch 8 corresponds to the number 128, switch 1 corresponds to the number 1 and switch 3 corresponds to the decimal number
4.
1
2
8765 4
128
64
32
Example 1
The switches 3, 5 and 7 are set to "ON“. The address is then: DIP switch 3 to "ON“ means 4 DIP switch 5 to "ON“ means 16 DIP switch 7 to "ON“ means 64
The sum is: 4 + 16 + 64 = Address 84
3
1
2
4
8
16
ON
1
2
8765 4
64
64 + 16 + 4 = 84
VEGAPULS 56 Profibus PA 39
3
16
4
Electrical connection
Example 2
You want to set address 27. 16 + 8 + 2 + 1 = 27
You must set the DIP switches 5 = 16 4 = 8 2 = 2 1 = 1 to "ON“.
Example 3
You want to set address 99 64 + 32 + 2 + 1 = 99
You must set the DIP switches 7 = 64 6 = 32 2 = 2 1 = 1 to "ON“.
Software addressing
The DIP switches must be set to an address of 126 … 255, i.e.
- either all DIP switches are set to "ON“, corresponding to address 255 (delivery status)
OFF
1
2
8765 4
Addr.
- or only DIP switch 8 is set to "ON“, corre­sponding to address 128.
3
ON
The adjustment of the address with software VVO is described in chapter "5.2 Adjustment with VVO“ under the heading "Software ad­dressing“ or in chapter "5.3 Sensor adjust­ment with the adjustment module MINICOM“.
1
2
3
1
2
4
8
16
128
64
8765 4
32

4.3 Connection of the sensor

After mounting the sensor at the measure­ment location according to the instructions in chapter "3 Mounting and installation“, loosen the closing screws on top of the sensor. The sensor lid with the optional indication display can then be opened. Unscrew the sleeve nut and slip it over the connection cable (after removing about 10 cm of insulation). The sleeve nut of the cable entry has a self-lock­ing ratchet that prevents it from opening on its own.
Now insert the cable through the cable entry into the sensor. Screw the sleeve nut back onto the cable entry and clamp the stripped wires of the cable into the proper terminal positions.
The terminals hold the wire without a screw (spring-loaded terminals). Press the white opening tabs with a small screwdriver and insert the copper core of the connection cable into the terminal opening. Check the hold of the individual wires in the terminals by lightly pulling on them.
Of course, software addressing is also pos­sible, if the switches 7 … 2 are set to "ON“ (address 126).
40 VEGAPULS 56 Profibus PA
ESC
OK
ESC
OK
Electrical connection
Ex ia version
Power supply and digital measuring signal
+
To the indicating instrument in the
-
sensor lid or to the external indicating instrument VEGADIS 50
M20x1.5 (diameter of the connection cable 6…9 mm)
Spring-loaded terminals (max. 2.5 mm section)
2
wire cross-
12 C 567843
12 C 5 6 7 843
Commu-
VBUS
nication+-4...20mA
-
Spring-loaded terminals (max. 2.5 mm section)
Display
ESC
+
OK
Sockets for connection of VEGACONNECT 2 (communi­cation sockets)
2
wire cross-
Exd version (loop-powered with pressure-tight encapsulated terminal compart­ment)
EEx d connection housing
(opening in Ex area not allowed)
Power supply and digital measuring signal
-+
Locking of the cover
Supply: 20 … 36 V DC, VBUS
Shield
- +
2
1
1
2
Exd terminal compart­ment
1
/2“ NPT EEx d diameter of the connection cable
3.1…8.7 mm (0.12…0.34 inch)
Adjustment module and terminal com­partment of display
(opening in Ex area permitted)
Exd safe connection to the Exd terminal compartment
1
/2“ NPT EEx d diameter of the connection cable to the Exd terminal com­partment
3.1…8.7 mm (0.12…0.34 inch)
12 C 567843
12 C 5 6 7 843
Commu-
VBUS
nication+-4...20mA
-
+
Display
ESC
OK
VEGAPULS 56 Profibus PA 41
ESC
OK
-
+
ESC
OK
Tank 1 m (d)
12.345
Electrical connection
4.4 Connection of the external indi­cating instrument VEGADIS 50
Loosen the four screws of the housing lid on VEGADIS 50. The connection procedure can be facilitated by fixing the housing cover during connection work with one or two screws on the right of the housing (figure).
Input of the sensor
SENSOR
Power supply
+
-
DISPLAY (in the lid of the indicating instrument)
DISPLAY1234 56 78
Terminal strip in VEGADIS 50
M20 x 1.5 (diameter of the connection cable 5…9 mm)
Note:
The four-wire connection cable to VEGADIS 50 should be screened and have a max. length of 25 m. The digital signals to the indi­cating instruments would otherwise be im­paired by the cable capacitance of longer connection cables. Ground the cable screen together with the signal cable screen on the sensor.
VEGADIS 50
Adjustment module
Screws
12 C 567843
12 C 5 6 7 843
Commu-
VBUS
nication+-4...20mA
-
Display
ESC
+
OK
42 VEGAPULS 56 Profibus PA
Setup

5 Setup

5.1 Adjustment media

In chapter "1.4 Adjustment“ the Profibus adjustment structure was briefly explained and the adjustment media for VEGA Profibus sensors were shown. All VEGA Profibus sensors operate in profile 3 and can be ad­justed with:
- the adjustment program VVO on a PC with Profibus card
- the adjustment program PACTware which VVO runs as a subprogram
- the Siemens software PDM in conjunction with an EDD (Electronic-Device-Descrip­tion)
- the adjustment module MINICOM in the sensor.
Adjustment with VVO on the PC
The adjustment program VVO enables user­friendly adjustment of VEGA Profibus PA sensors. All functions and options of sensor adjustment are accessible. The program runs under Windows Profibus-Master-Class 2 inter face card on Profibus DP level as Master-Class 2 tool. The VVO program accesses the VEGA PA sen­sors via the DP bus, the segment coupler and the PA bus.
®
on a PC with a
TM
, under
Adjustment with PACTware
TM
The adjustment with PACTwareTM corre­sponds to VVO adjustment, in this case, VVO runs as a subprogram of PACTware adjustment instructions can be found in the documentation of PACTware
TM
. The
TM
.
Adjustment with PDM
The sensors can be adjusted completely with PDM. However, some convenient functions and many special features, like e.g. display of an echo curve, are not available. In addi­tion to the PDM software, an EDD (upon request available from VEGA) is required for each sensor type. The adjustment instruc­tions for PDM are described in the PDM documentation.
Adjustment with the adjustment module MINICOM
With the adjustment module MINICOM, you adjust the individual sensor directly in the sensor or in the external indicating instrument VEGADIS 50. The adjustment module MINICOM enables (with the 6-key adjustment field with text display) all essential functions of parameter setting and adjustment.
Note:
Keep in mind that for adjustment with VVO, version 2.70 or higher is necessary.
VEGAPULS 56 Profibus PA 43
Setup

5.2 Adjustment with VV O

Before you can adjust the sensors with the adjustment program VVO (VEGA Visual Operating) in version 2.70, they must be integrated into the Profibus system. First of all, address the sensors (chapter "4.2 Sensor address“) and connect them to your PA seg­ment. With the attached GSD file you inte­grate the sensors into your system.
To adjust VEGA sensors with the adjustment software VVO, the PC or the adjustment station on which VVO is installed must be equipped with a Profibus DP interface card (e.g. of Messrs. Softing). The PC or the ad­justment station communicates then as Mas­ter-Class 2 participant on the DP bus with the VEGA sensors on the PA bus segment.
To connect the PC to the DP bus, a standard RS 485-DTE interface cable (Data Terminal Equipment) is required. With the cable you connect the DP interface card to the bus or to the segment coupler.
PCPC
PC
PCPC
Screen 1 1 Screen – – 2 2 M24 RxD/TxD-PRxD/TxD-P
RxD/TxD-P
RxD/TxD-PRxD/TxD-P
33
3
33 – – 4 4 CNTR-P GNDGND
GND
GNDGND
55
5
55 – – 6 6 VP – – 7 7 P24 RxD/TxD-NRxD/TxD-N
RxD/TxD-N
RxD/TxD-NRxD/TxD-N
88
8
88 – – 9 9 CNTR-P
Profibus-DP DP bus (in brackets the interface card PIN number of the P+F
BUSBUS
BUS
BUSBUS
33
RxD/TxD-PRxD/TxD-P
3
RxD/TxD-P (40)
33
RxD/TxD-PRxD/TxD-P
55
GNDGND
5
GND (55)
55
GNDGND
88
RxD/TxD-NRxD/TxD-N
8
RxD/TxD-N (41)
88
RxD/TxD-NRxD/TxD-N
segment couplers)
Segment coupler
DP cable
VVO
VEGA­CONNECT 3
Profibus DP interface card (Messrs. Softing)
Sensor Sensor Sensor Sensor
Profibus PA cable
When the computer is connected to the Profibus DP cable, you can start VVO.
In the following setup and adjustment instruc­tions you will find information on the following topics and adjustment items:
ConfigurationConfiguration
Configuration
ConfigurationConfiguration
- Configuration info
- Software addressing
- Create new measurement loop Parameter adjustment 1Parameter adjustment 1
Parameter adjustment 1
Parameter adjustment 1Parameter adjustment 1
- Meas. loop data
- Adjustment
- Scaling Sensor optimisationSensor optimisation
Sensor optimisation
Sensor optimisationSensor optimisation
- Meas. environment/Operating range
- Meas. environment/Meas. conditions
- Meas. environment/Sonic velocity
- Echo curve
- False echo storage Parameter adjustment 2Parameter adjustment 2
Parameter adjustment 2 (optional)
Parameter adjustment 2Parameter adjustment 2
- Linearisation
- Defining the linearisation curve by incremental filling
- Calculating the linearisation curve
- Calculate cylindrical tank
- Parameter adjustment sensor display
• Display measured value
• Simulation
• Print configuration and adjustments
• Backup
44 VEGAPULS 56 Profibus PA
Setup
Configuration and parameter adjust­ment
During setup of the sensor you will be con­fronted with two terms: "Configuration“ and "Parameter adjustment“. The meas. system is first set up with a configuration and then with a parameter adjustment.
Configuration
The term "Configuration“ means the basic adjustments of the meas. system. You inform the meas. system about the application (level measurement, gauge, distance …), the measurement loop name and the DCS output address of the sensors. The configuration corresponds to an electronic wiring and labelling of your sensor or, in other words, telling the system which sensor for what application and where.
Parameter adjustment
After the configuration, you carry out the parameter adjustment for each individual sensor. This means adjusting the sensors to the respective operating range and to the actual application. You inform the sensor which product distance (which level) is "empty“ and which "full“. This is called adjust­ment. Here you choose in which physical quantity (volume, mass) and unit of measure­ment (m ured value should be outputted. In the submenu "Sensor optimisation“ you inform the sensor electronics about the actual envi­ronment, such as e.g. quick changes of the measured value, foam generation, gas strati­fication, solid or liquid state of the medium.
3
, gal, liters …) the adjusted meas-
Actions, like entering a value or making a choice, are indicated in the following by a large black dot, like this:
• Choose …
• Start …
• Click to …
By this convention, the actions to be carried out are clearly separated from supplemen­tary information in the following adjustment instructions.
Note:
By default, the adjustment software VVO uses address 10 when operating via the PA interface card on the PA bus as Master-Class
2. If on your bus address 10 is already as­signed, enter a free address (description on the next page) before connecting the PC to the bus.
• Now start the adjustment software VVO on your PC.
• Choose with the arrow keys or the mouse the item "Planning“ on the entrance screen and click to "
OKOK
OK
OKOK
“.
You are asked for user identification.
Before starting the setup:
Do not be confused by the many pictures, adjustment steps and menus on the following pages. Just carry out the setup with the PC step by step and you will soon no longer need the following pages.
VEGAPULS 56 Profibus PA 45
• Enter under name "
• Also enter "
VEGAVEGA
VEGA“.
VEGAVEGA
VEGAVEGA
VEGA“ under password.
VEGAVEGA
The adjustment program, called in the follow­ing VVO, gets into contact with the connected sensor …
Setup
… and asks in which mode the adjustment software should be used. After a few sec­onds, the software indicates if and with which system a connection exists.
If the following message is displayed, you have to change the communication setting in VVO.
• Then click to "
gramgram
gram
“ and click to "
gramgram
ConfigurationConfiguration
Configuration
ConfigurationConfiguration
CommunicationCommunication
Communication
CommunicationCommunication
“, point to "
Pro-Pro-
Pro-
Pro-Pro-
“.
• Click to "
The window for the bus communication set­tings opens. 10 is preset as the address for the Master Class 2 interface card. If partici­pant number ten is free on your bus, you can accept the setting. Typical values for bus parameters have been preset. At this point, you should set the communication param­eters that apply to your system.
• Now click to "
The message "
dows
Bus parametersBus parameters
Bus parameters
Bus parametersBus parameters
OKOK
OK
“.
OKOK
®
must be restarted
VVO will shut down and Win-
“.
“ appears.
Note: As a rule, a Windows® restart is not
PrPr
• First click to " Then choose the Profibus card which is installed in your PC.
46 VEGAPULS 56 Profibus PA
ofibus DP (for Pofibus DP (for P
Pr
ofibus DP (for P
PrPr
ofibus DP (for Pofibus DP (for P
A sensorsA sensors
A sensors
A sensorsA sensors
necessary.
“.
• Now start VVO (restart).
Setup
• Click to "
The VVO software asks again for the user identification and then reads in all VEGA Profibus sensors found. You now see the VVO main menu window.
User identification
The preset user identification can be modified at a later time in the menu "
Program/User access
PlanningPlanning
Planning
PlanningPlanning
“ and then to "
“.
OKOK
OK
“.
OKOK
Configuration/
Configuration
Configuration info
• Choose the menu "
ing systeming system
ing system
ing systeming system
You reach the menu window "
measuring system
complete information on the VEGA sensors connected to the Profibus.
Software addressing
If the DIP switch in the sensor is set to ad­dress 126 or higher, the address can be modified in the menu window "
measuring system
the field "
Sensor address
Configuration/MeasurConfiguration/Measur
Configuration/Measur
Configuration/MeasurConfiguration/Measur
“.
Configuration
“. In this window you get
Configuration
“. Enter a free address in
“.
--
-
--
VEGAPULS 56 Profibus PA 47
Setup
The measurement loops are listed in the sequence of sensor addresses with a serial number and any existing name.
If the sensor address has been adjusted with the DIP switch from 1 … 125, the address number in the field " and cannot be changed at this point.
Create new measurement loop
• Choose the menu "C
ment loop/Modify
Sensor address
onfiguration/Measure-
“.
“ is grey
• Choose in the window "
configuration
name for the measurement loop.
“ the application and enter a
Modify meas. loop
Parameter adjustment 1
In the menu "
justment
adjustments.
Instrument data/Parameter ad-
“ you carry out all important sensor
The menu window "
loop - Modify meas. loop configuration
opens.
• Here you choose the sensor to be configured.
48 VEGAPULS 56 Profibus PA
Selection of measurement
• Choose the menu "
eter adjustmenteter adjustment
eter adjustment
eter adjustmenteter adjustment
which you want to carry out the parameter adjustment.
In the opening menu window, you now see the measurement loop names and descrip­tions previously entered under "
measurement loop
configured or connected one sensor, there will naturally be a choice of only one sensor.
Instrument data/Param-Instrument data/Param-
Instrument data/Param-
Instrument data/Param-Instrument data/Param-
“ and then the sensor on
Create new
“. If you have only
Setup
• Click to the sensor or the measurement loop on which you want to carry out the parameter adjustment.
• Then click to "
strument data parameter adjustment
opens.
OKOK
OK
“, the menu window "
OKOK
Adjustment
("adjustment“ in chapter "6 Function dia­gram).
In-
Measurement loop data
• When clicking " important measurement loop data will be displayed.
Meas. loop dataMeas. loop data
Meas. loop data
Meas. loop dataMeas. loop data
“, the most
• Click to "
• Click in the menu window " "
You can carr y out the min./max. adjustment
"with medium“
real level) or the real level into account, i.e. with empty vessel).
Generally, you will carry out the adjustment without medium, so you are completely inde­pendent of the actual vessel filling during the adjustment. If you want to carry out the ad­justment with medium, you have to carry out the min. adjustment with emptied (also partly emptied) vessel and the max. adjustment with filled vessel (also partly filled vessel). It is therefore easier and faster to carry out the adjustment without medium.
AdjustmentAdjustment
Adjustment
AdjustmentAdjustment
Min/Max-AdjustmentMin/Max-Adjustment
Min/Max-Adjustment
Min/Max-AdjustmentMin/Max-Adjustment
(adjustment by means of the
"without medium“
“.
“.
Adjustment
(without taking
“ to
• Click to " menu window "
adjustment
VEGAPULS 56 Profibus PA 49
QuitQuit
Quit
“ and you are again in the
QuitQuit
Instrument data parameter
“.
Setup
no (adjustment without medium)no (adjustment without medium)
• Choose "
In the menu window "Min/Max-Adjustment“ you choose e.g. the level distance corre­sponding to 100 % and 0 %. Of course, you can also enter the distance values e.g. at 20 % and 75 % filling.
If the two points are too close together, e.g. at 45 % and 49 %, a considerable meas. error can result, as the sensor generates by means of the two adjustment points a linear correlation between filling volume (%) and meas. distance.
no (adjustment without medium)
no (adjustment without medium)no (adjustment without medium)
• Confirm the adjustments with "
“.
after a message is displayed, you are again in the menu window "
Note:
The sensor is delivered with the sensor measuring range set to the same value as the operating range. After the sensor has been adjusted, the operating range corre­sponds to the adjustment range. The sensor can only detect levels within the defined oper­ating range. For level detection outside the operating range (if you want to detect e.g. 108 % and -10 %), the operating range must be corrected respectively in the menu "
OKOK
OK
OKOK
Adjustment
sor optimisation/Meas. environment
following chapter "Sensor optimisation“, "Meas. environment/Operating range“).
• Click in the menu window "
QuitQuit
"
Quit
“.
QuitQuit
Adjustment
“ and
“.
Sen-
“ (see the
“ to
• Choose if you want to carry out the adjust­ment in
meters
• Enter a distance for the upper and lower
(m) or in
level and the extent of filling in % corre­sponding to each distance.
In the example, the 0 % filling is at a product distance of 5.850 m and the 100 % filling at a product distance of 1.270 m.
Offset
See also A3-1 in chapter "6 Function dia­gram“ under "Level Offset“.
50 VEGAPULS 56 Profibus PA
feet
(ft).
You are again in the menu window "
ment data parameter adjustment
“.
Instru-
Setup
The sensor electronics has two characteris­tics points (at min. and max.) from which a linear proportionality between product dis­tance and the percentage of filling of the vessel is generated. Of course, the characteristics points must not necessarily be at 0 % and 100 %, however they should be as far apart as possible (e.g. at 20 % and at 80 %). The difference be­tween the characteristics points for the min./ max. adjustment should be at least 20 mm product distance. If the characteristics points are too close together, the possible measur­ing error increases. Ideally, the adjustment would be to carried out, as shown in the example, at 0 % and at 100 %.
In the menu "
justment/Conditioning/Linearisation
enter later, if necessary, a correlation be­tween product distance and % extent of filling other than linear (see later subitem Linearisation).
Scaling
• Click in the menu window "
parameter adjustment
Instrument data/Parameter ad-
“ you can
Instrument data
ConditioningConditioning
“ to "
Conditioning
ConditioningConditioning
“.
“.
ScalingScaling
Scaling
ScalingScaling
Outputs
“.
“ in the menu window
OKOK
OK
“.
OKOK
Conditioning
“.
“.
“ to
Instru-
• Click to "
The displayed message tells you that you will find this function on Profibus sensors under the menu item " "
Instrument data parameter adjustment
• Confirm the message with "
• Click in the menu window "
QuitQuit
"
Quit
QuitQuit
You are again in the menu window "
ment data parameter adjustment
Scaling of the output signal
• Click in the menu window "
parameter adjustment
The menu window "
VEGAPULS 56 Profibus PA 51
Conditioning
“ opens.
Instrument data
OutputsOutputs
“ to "
Outputs
OutputsOutputs
“.
Setup
Profibus outputProfibus output
• Click to "
In the window " determine the options for the Profibus output (acc. to the Profibus PA instrument profile).
VEGA Profibus sensors operate in the so­called profile 3, in which the structure of measured value processing is determined (see also chapter "6 PA Function diagram“). In this software diagram you can see the structure of the measured value processing acc. to profile 3 (schematic presentation). The numberings A1, A2 … E are also stated in the PA function diagram.
PV-Scale
Profibus output
Profibus outputProfibus output
Profibus output
Out-Scale
“.
“ you can
You can choose as a physical quantity
"dimensionless mass, height and distance“
appropriate unit of measurement (e.g. l, hl). The sensor display then shows the meas­ured value in the selected physical quantity and unit.
• Save the adjustments in the menu "
output
The adjustments are now transferred to the sensor and you are again in the menu win­dow "
Outputs
• Click in the menu window "
QuitQuit
"
Quit
QuitQuit
• Click in the menu window "
parameter adjustment
(plain numbers),
OKOK
“ with "
OK
OKOK
“.
“.
A1
A3
volume,
and assign an
Profibus
“.
Outputs
“ to
Instrument data QuitQuit
“ to "
Quit
“.
QuitQuit
A2
B
C
D
E
52 VEGAPULS 56 Profibus PA
Setup
Sensor optimisation
In the menu " pare the sensor for the meas. environment. With this you can carry out special optimising adjustments, and optimise, e.g., the mounting locating of the sensor by means of an echo curve.
Meas. environment/Operating range
• Choose the menu "
eter adjustmenteter adjustment
eter adjustment
eter adjustmenteter adjustment
• Choose in the menu window "
data parameter adjustmentdata parameter adjustment
data parameter adjustment
data parameter adjustmentdata parameter adjustment
""
Sensor optimisationSensor optimisation
"
Sensor optimisation
""
Sensor optimisationSensor optimisation
Sensor optimisation
Instrument data param-Instrument data param-
Instrument data param-
Instrument data param-Instrument data param-
“ and then the sensor.
“ the menu item
““
“.
““
“ you pre-
InstrumentInstrument
Instrument
InstrumentInstrument
The window "
With the menu item " can define a sensor operating range that deviates from the meas. range (depending on the sensor type) and from the "
adjustment
corresponds otherwise to the min./max. ad­justment (span), i.e. the meas. range.
Meas. environment
Operating range
“ opens.
“ you
Min/Max
“. By default, the operating range
Generally, it is better to set the operating range approx. 5 % wider than the adjusted measuring range (span) determined by the min./max. adjustment. In the example:
- Min. adjustment to 1.270 m,
- Max. adjustment to 5.85 m. In the example you would have set the oper­ating range from 1 m to 6 m.
""
• First click to
VEGAPULS 56 Profibus PA 53
Meas. environmentMeas. environment
"
Meas. environment
""
Meas. environmentMeas. environment
““
“.
““
Meas. conditions/Pulse velocity
Setup
• Save the adjustments with " are again in the menu window "
ronment
“.
OKOK
OK
“ and you
OKOK
Meas. envi-
Meas. environment/Meas. conditions
• Click in the menu window "
mentment
ment
mentment
• In the menu window " click on the options corresponding to your application.
• Confirm with
Meas. conditionMeas. condition
“ to "
Meas. condition
Meas. conditionMeas. condition
""
OKOK
"
OK
""
OKOK
““
“.
““
Meas. environ-Meas. environ-
Meas. environ-
Meas. environ-Meas. environ-
“.
Meas. conditions
“ you
In the menu item " are only necessary when measuring in a surge or bypass tube (standpipe). When measuring in a standpipe, a shift of the run­ning time of the radar signal is caused which is dependent on the inner diameter of the standpipe. To take this running time shift into account, it is necessary to inform the sensor in this menu about the diameter (inner) of the standpipe.
Pulse velocity
“, adjustments
After a few seconds, during which the adjust­ments are permanently saved in the sensor, you are again in the window "
ment
“.
54 VEGAPULS 56 Profibus PA
Meas. environ-
• With "
• Click in the window "
sensor.
QuitQuit
"
Quit
“.
QuitQuit
OKOK
OK
“ you save the adjustments in the
OKOK
Meas. environment
“ to
Setup
Echo curve
With the menu item " window "Sensor optimisation“ you can see the course and the strength of the detected radar echo. If, due to vessel installations, you expect strong false echoes, a correction (if possible) of the mounting location and orien­tation (during simultaneous monitoring of the echo curve) can help localise and reduce the size of the false echoes.
Echo curve
“ in the menu
In the next illustration, you see the echo curve after optimum orientation of the sensor to the product surface (sensor axis perpendicular to the product surface). The false echo, e.g. caused by a strut, is now reduced by more than 10 dB and will no longer influence the measurement.
• Quit the menu "
False echo storage
With the menu item " the menu " thorise the sensor to save false echoes. The sensor electronics then saves the false ech-
In the following illustration, you see the echo curve with a false echo nearly as large as the product echo (before correcting the sensor orientation, i.e. pointing the sensor directly at the product surface).
oes in an internal database and assigns them a lower level of importance than the useful echo. Carry out the false echo storage with the vessel emptied.
• Click in the menu window to "
optimisation storagestorage
storage
storagestorage
VEGAPULS 56 Profibus PA 55
Echo curve
False echo storage
Sensor optimisation
“ to the menu item
““
“.
““
QuitQuit
“ with "
Quit
QuitQuit
“ you can au-
Sensor
""
False echoFalse echo
"
False echo
""
False echoFalse echo
“.
“ in
• Click to
""
Show echo curveShow echo curve
"
Show echo curve
""
Show echo curveShow echo curve
Setup
““
“.
““
• Now click in the opening menu window "
False echo storage
oesoes
““
oes
“. A small window opens.
oesoes
““
• Enter here the verified product distance or the distance to the vessel bottom and click
""
Create newCreate new
to
"
Create new
""
Create newCreate new
You hereby authorise the sensor to mark all echoes before the product echo as false echoes. This prevents the sensor from erro­neously detecting a false echo as level echo.
“.“.
“.
“.“.
""
Learn false ech-Learn false ech-
“ to
"
Learn false ech-
""
Learn false ech-Learn false ech-
The false echo marking and the real echo curve (top) are shown.
""
QuitQuit
• Quit the menu with
You are again in the menu window "
optimisation
reset all options of the menu "
optimisation
• Quit the menu window "
optimisation
You are then in the initial menu window "
“. With the menu item "
“ to default.
“ with
strument data parameter adjustment
"
Quit
""
QuitQuit
""
QuitQuit
"
Quit
""
QuitQuit
““
“.
““
Sensor
““
“.
““
Sensor
Reset
Sensor
“.
“ you
In-
56 VEGAPULS 56 Profibus PA
Setup
Parameter adjustment 2
Linearisation
The relation between level and volume is defined with so-called linearisation curves. If there is a correlation in your vessel between level ("
Percentage value
quantity (value of the volume) other than linear, choose the menu window "
ing
“.
“ of the level) and
Condition-
Beside the two programmed linearisation curves "
Cylindrical tank
you can also enter "
curves
“. Linear means that there is a linear
correlation between level and volume.
User programmable linearisation curves
“ and "
Spherical tank
user programmable
• Click to " enter your own vessel geometry or a user programmable filling curve.
• Click to "
• Click in the menu window " the menu item
The menu window " which a linear correlation between percent­age value of the level and the percentage value of the volume is preset.
VEGAPULS 56 Profibus PA 57
""
LinearisationLinearisation
"
Linearisation
""
LinearisationLinearisation
Linearisation
Conditioning
““
“.
““
“ opens, in
“ to
User programmable curveUser programmable curve
User programmable curve
User programmable curveUser programmable curve
EditEdit
Edit
“.
EditEdit
to
The user programmable linearisation curve is generated by index markers. Each index marker consists of a value pair. A value pair is generated from a value " value "
Percentage value
Linearised
“.
“Percentage value”
“ and a
represents the distance as a percentage of the level. "
Linearised
“ represents the per­centage of vessel volume at a certain per­centage value of level.
In the field "
Transfer measured value
“ the current level as a percentage of the adjusted span is displayed. The measuring window has already been adjusted with the min./max. adjustment. In the example, the span is
4.58 m and is between 5.85 m (empty) and
1.27 m (full), see the following illustration.
Setup
5.85 m meas. distance correspond to 0 % level. 1.27 m meas. distance correspond to 100 % level. The span is therefore 4.58 m (5.85 m – 1.27 m = 4.58 m).
A percentage value of 95.79 % then means that 4.387 m of the adjusted span (4.58 m) have been reached:
4.58 • 0.9579 = 4.387 m.
The distance (product distance) outputted by the sensor, if you have chosen "
Distance
is then:
5.85 – (4.58 • 0.9579) = 1.463 m.
If the index markers or value pairs of your vessel are not known, you must gauge the vessel incrementally or calculate it with the vessel calculation program of VVO.
Defining the linearisation curve by incre­mental filling
In the characteristics of the example, you see four index markers or value pairs. There is always a linear interpolation between the index markers. The example vessel consists of three cylindrical segments of different height and diameter. The middle segment has a considerably smaller diameter.
“,
0 m
100 % at 1.27 m
1.463 m (95.79 %)
Span
4.58 m
(100 %)
4.387 m
(95.79 %)
0 % at 5.85 m
58 VEGAPULS 56 Profibus PA
• Click in the check box "
uesues
ues
“, to have the selected unit of measure-
uesues
ment displayed on the y-axis (left bottom part in the menu window).
Show scaled val-Show scaled val-
Show scaled val-
Show scaled val-Show scaled val-
Setup
Index marker 1 is at 0 % filling (
value [%]
), corresponding in the example to
percentage
an actual distance to the product surface of
5.850 m (empty vessel). The volume is 45 liters (fluid remaining in the vessel). Index marker 2 is at a filling level of 30 % (30 % of the meas. distance of
1.270 m … 5.850 m). At a filling level of 30 %, there are 576 liters in the vessel (in our exam­ple). Index marker 3 is at a filling level of 60 %. At this filling level there are 646 liters in the ves­sel. Index marker 4 is at a filling level of 100 % (product distance 1.270 m), where 1200 liters are in the vessel.
Max. 32 index markers can be entered per linearisation curve (value pairs).
Max.
Min.
100 % (1.270 m) correspond to 1200 liters
Span (4.58 m)
0 % (5.850 m) correspond to 45 liters
Calculating the linearisation curve
(use previous tank example)
• Click to "
CalculateCalculate
Calculate
CalculateCalculate
“.
The tank calculation program starts. In the top left corner you choose the vessel type (upright tank, cylindrical tank, spherical tank, individual tank form or matrix). When choos­ing matrix, you can enter a user programma­ble linearisation curve by means of index markers. This corresponds to the entering of value pairs (linearisation points), as previ­ously described. In the following example, the tank calculation program calculates the linearisation curve of a vessel corresponding to the vessel in the previous gauging example.
• Click to "
individual tank form“individual tank form“
individual tank form“
individual tank form“individual tank form“
and choose three round tank segments with the dimen­sions 0.99 m • 0.9 m (height by diameter),
0.68 m • 0.37 m and 0.68 m • 1.02 m (this tank form corresponds to the tank form of the gauging example).
In the menu window "
programmable curve --
Linearisation -- user
“ you can start the vessel calculation program. With the vessel calculation program you can calculate (using dimensions from the technical drawings of the vessel) the correlation of filling height to filling volume. If the curve is defined this way, gauging by incremental filling is not neces­sary - your sensor can then output volume as a function of level.
VEGAPULS 56 Profibus PA 59
Setup
• Click to "
After a few seconds of calculation, the levels as a percentage of span and the corre­sponding volume percentages are shown. The outputted curve shows this correlation in a diagram.
• Quit the linearisation table with "
CalculateCalculate
Calculate
CalculateCalculate
“.
OKOK
OK
“.
OKOK
You are again in the menu window "
calculation
• Click to "
You are again in the menu window "
Linearisation -- user programmable curve --
“. The volume percentages, with the corre­sponding level percentages, are shown. After clicking in the bottom left part of the menu window to " will be displayed according to the adjustment in the menu "
“.
OKOK
OK
“ to save the tank calculation.
OKOK
Show scaled values
Instrument data/Parameter ad-
justment/Conditioning/Scaling
Calculate cylindrical tank
• Click in the menu window "
user programmable curve --
CalculateCalculate
"
Calculate
CalculateCalculate
calculation
tanks.
“ and in the menu window "
“ to the symbol for cylindrical
Tank
“, liters
“.
Linearisation --
“ to
Tank
60 VEGAPULS 56 Profibus PA
Setup
The menu window for the adjustment of the cylindrical tank opens.
• Choose the meas. unit, e.g. mm, that
should apply to the entered vessel dimen­sions.
The following example shows how to enter a cylindrical tank that is inclined by 3° and has a cylinder length of 10000 mm and a diam­eter of 5000 mm. The cylindrical tank has a 1500 mm wide, spherical form at the right end and a dished form at the left.
Above the information
internal dimensions
"All dimensions are
“, you will find two fields with the percentage values 0 % and 100 %. Here you can shift the 100 % line or the 0 % line. In the example, the 100 % filling line was defined at a distance of 650 mm from the upper vessel edge (inside).
• Click to "
CalculateCalculate
Calculate
CalculateCalculate
“.
You will get the calculated linearisation table after a brief processing interval. By means of 32 linearisation points, a function correlating vessel volume to filling height is outputted. The example vessel has a filling of 216561 liters at the 100 % line or of 216.6 m
3
. It is possible to output the volume value in bar­rels, gallons, cubic yards or cubic feet.
Note:
In the bottom left corner in the menu window "
Tank calculation
dimensions are internal dimensions
“ you find the information "
“. Entering
All
a wall thickness is only necessary for the calculation of the dished boiler end because its mathematical calculation is based on the outer dimension.
VEGAPULS 56 Profibus PA 61
There is a linear interpolation between the linearisation points.
OKOK
OK
• Click to " menu window "
• Again click in the menu window "
culation
linearisation menu.
Here the calculated linearisation curve is again outputted. The volume information under " sponds to the calculated volume of the tank calculation program. Why?
In the menu " tioning/Scaling) you entered earlier that at 0 % filling there are 45 liters in the tank and at 100 % filling 1200 liters. The geometry of the calculated cylindrical tank was accordingly scaled down to a size that indeed evaluates to a volume of only 1200 liters. The modified linearisation curve was then applied to the volume data that you entered in the menu "
Scaling
If the true content of the calculated vessel should be outputted, the volume that was determined by the tank calculation program must be entered in the menu "
“ and you are again in the
OKOK
Tank calculation
OKOK
“ to "
OK
“ and you are in the
OKOK
Linearised
“.
“ now no longer corre-
Scaling
“ (Instrument data/Condi-
“.
Tank cal-
Scaling
“.
Setup
The sensor then outputs the actual filling volume calculated from the entered vessel dimensions.
• Quit the menu with "
• Confirm with " linearisation curve is saved in the sensor.
Again in the menu window " can enter with the menu item "
time
“ a measured value integration. This is recommended for agitated product surfaces, to prevent rapid fluctuation of the output signal and the measured value indication. The standard setting is an integration time of 0 seconds.
• Quit the menu with "
the menu window "
eter adjustment
• Quit the menu window with "
OKOK
OK
“.
OKOK
OKOK
OK
“ and your individual
OKOK
Conditioning
Integration
OKOK
OK
“. You are again in
OKOK
Instrument data param-
“.
OKOK
OK
OKOK
“, you
“.
62 VEGAPULS 56 Profibus PA
Setup
Parameter adjustment of sensor dis­play
In the menu item "Outputs“ you choose the scale and the unit in which your level should be displayed.
• Choose in the main menu window "
ment data parameter adjustmentment data parameter adjustment
ment data parameter adjustment
ment data parameter adjustmentment data parameter adjustment
the menu item "
OutputsOutputs
Outputs
OutputsOutputs
“.
Instru-Instru-
Instru-
Instru-Instru-
“ and then
• Click to "
• If the adjustments should remain un­changed, click to "
• Click in the menu window "
QuitQuit
"
Quit
QuitQuit
"
Instrument data parameter adjustment
• Click in the menu window "
parameter adjustment
SaveSave
Save
“ to save the adjustment.
SaveSave
QuitQuit
Quit
“.
QuitQuit
“ and you are in the menu window
Outputs
“ to
Instrument data
“ again to "
QuitQuit
Quit
QuitQuit
“.
“.
Display of measured value
• Click in the main menu window to the menu
Display/Display of measured valueDisplay/Display of measured value
"
Display/Display of measured value
Display/Display of measured valueDisplay/Display of measured value
choose the measurement loop or the sen­sor which you want to have displayed.
“ and
• In the menu window "
Display of measured valueDisplay of measured value
"
Display of measured value
Display of measured valueDisplay of measured value
The menu window " the selection of the " (see also "6 PA function diagram“).
VEGAPULS 56 Profibus PA 63
Outputs
“ click to
“.
Sensor Display
Parameter
“ and the "
“ enables
Unit
• Choose in the line " and the sensor product distance will be displayed. If you choose " measured value will be displayed in liters or volume percent.
Meas. value
“ "
ScaledScaled
Scaled
ScaledScaled
DistanceDistance
Distance
DistanceDistance
“, e.g., the
Simulation
• Click to the menu " and choose the measurement loop.
The menu window " which is similar to the previous window, opens. In this menu window however, you can set the filling of the vessel, i.e. the meas­ured value, and the display to any desired value (simulation of measured value).
Diagnostics/SimulationDiagnostics/Simulation
Diagnostics/Simulation
Diagnostics/SimulationDiagnostics/Simulation
Simulation of outputs
“,
Setup
The grey scroll bar becomes active. With this scroll bar you can change the measured value to any value in the range of
-10 % … 110 % and thereby simulate the filling or emptying of the vessel. In the input box of the turquoise window cutout you can enter any percentage value of filling.
Note:
The simulated measured value is outputted during adjustment with the PC until you stop the simulation mode.
First of all, the actual measured value is dis­played.
StartStart
• Click to " segment.
64 VEGAPULS 56 Profibus PA
Start
in the turquoise window
StartStart
Setup
Print configuration and adjustments
• Click to "
Before printing the complete configuration of all sensors, you can view the individual pages and …
Services/PrintServices/Print
Services/Print
Services/PrintServices/Print
“.
With the menu " justments displayed in detail.
View
“, you can have the ad-
Backup
With the menu items "
conditioning instruments Backup/Sensors
tions and parameter adjustments of any individual sensor.
For further instructions see the manual "VEGA Visual Operating“ (VVO).
… then print all or just certain pages.
VEGAPULS 56 Profibus PA 65
Services/Backup/Signal
“ and "
“, you save the configura-
Services/
Setup
5.3 Sensor adjustment with the ad-
justment module MINICOM
Tank 1 m (d)
12.345
Beside the PC, it is also possible to adjust the sensors with the small, detachable adjust­ment module MINICOM in the sensor.
With the adjustment module MINICOM, only the sensor-relevant adjustments such as e.g. scaling of the sensor display, operating range, meas. conditions, sensor display scaling or false echo storage are possible. Not possible, however, are all adjustment steps relating to configuration, conditioning and signal processing (configuration of the inputs and outputs, linearisation curves, simulation …). This is only possible with the PC.
The adjustment module MINICOM is adjusted with six keys. A small display shows you, apart from the measured value, a short mes­sage on the menu item or the entered value of a menu adjustment.
The volume of information of the small display, however, cannot be compared with that of the adjustment program VVO, but with the help of the menu schematic for MINICOM, you will be able to quickly find your way through the adjustment structure. In time, you might even be able to carry out your adjustments with the small module faster and more efficiently than with the PC.
ESC
+
-
OK
Error codes:
E013 No valid measured value
- Sensor in the warm-up phase
- Loss of the useful echo E017 Adjustment span too small E036 Sensor program not operating
- Sensor must be reprogrammed
(service)
- Fault signal also appears during
programming
E040 Hardware failure, electronics
defective
Adjustment steps
On the following pages you will find the com­plete menu schematic of the adjustment mod­ule MINICOM. Set up the sensor in the numbered se­quence:
1.Address
2. Measurement in a tube (only for measure-
ment in a standpipe)
3. Operating range
4. Adjustment
5. Conditioning
6. Meas. conditions
7. False echo storage (only required when
errors occur during operation).
8. Indication of the useful and noise level
9. Outputs Short explanations to the setup steps 1 … 9 follow.
1. Address
Choose a free bus address with the DIP switch (see chapter "4.2 Sensor address“).
66 VEGAPULS 56 Profibus PA
Setup
2. Measurement in a standpipe
Adjustment is only necessary if the sensor is mounted in a standpipe (surge or bypass tube). When measuring in a standpipe, do a sounding of the distance and correct the display of measured value (which can differ several percent from the sounded value) according to the sounding. From then on, the sensor corrects running time shift of the ra­dar signal and displays the correct value of the level in the standpipe (measuring tube).
3. Operating range
Without special adjustment, the operating range corresponds to the measuring range. Generally, it is useful to choose a slightly wider range (approx. 5 %) for the operating range than for the measuring range.
Example: Min./max. adjustment: 1.270 … 5.850 m; adjust operating range to approx. 1.000 …
6.000 m.
4. Adjustment
Max.
100 % (1.270 m) correspond to 1200 liters
You can carr y out the adjustment with or without medium (dry adjustment). Generally you will carry out the adjustment without me­dium, as you can then adjust without a filling/ emptying cycle.
Adjustment without medium
(adjustment independent of the level)
Key adjustment Display indication
Sensor
m(d)
4.700
Para-
OK
OK
OK
OK
+
The distance indication flashes and you can choose "feet“
meter
Adjust­ment
w.o medium
Ad­just­ment in
m(d)
(min. adjustment)
and "m“.
Span (4.58 m)
Min.
Under the menu item "
0 % (5.850 m) corresponds to 45 liters
Adjustment
“ you inform
the sensor about the measuring range.
OK
+
or
Confirm the adjustment with "
OK
“.
m(d)
0.0%
at
m (d)
XX.XXX
Ad­just­ment in
With "+“ and "–“ you adjust the percentage value for the min. value (example 0.0 %).
The adjusted percentage
OK
value is written in the sensor and the distance for the min. value corresponding to the percentage value flashes.
VEGAPULS 56 Profibus PA 67
Setup
+
or
+
With the "
“ or "–“ key you can assign a level distance (ex­ample 5.85 m) to the previ­ously adjusted percentage
Adjustment with medium
with medium
value. If you do not know the distance, you have to do a sounding.
OK
The adjusted product dis­tance is written in the sensor and the display stops flash­ing.
You thereby adjusted the lower product dis­tance as well as the percentage filling value corresponding to the lower product distance.
Note:
For level detection outside the operating range, the operating range must be corrected accord­ingly in the menu "
ing range
“.
Sensor optimisation/Operat-
100.0%
at
m (d)
XX.XXX
(max. adjustment)
Now you make the max. adjustment (upper product distance) (example: 100 % and
Min.
Max.
adjust
adjust at %
at %
XXX.X
XXX.X
Fill the vessel e.g. to 10 % and enter 10 % in the menu "
Min. adjust
“ with the "+“ and "–“ keys. Then fill the vessel, e.g. to 80 % or 100 % and enter 100 % in the menu "
adjust
“ with the "+“ and "–“ keys.
Max.
5. Conditioning
Signal condit­ioning
Scal­ing
0 %
100 %
Deci-
prop. corres­ponds
XXXX
corres­ponds
XXXX
mal point
888.8
Unit
to
Mass
Kg
1.270 m product distance). First enter the per­centage value and then the product distance corresponding to the percentage value.
Note:
The difference between the adjustment val­ues of the lower product distance and the upper product distance should be as big as possible, preferably at 0 % and 100 %. If the values are very close together, e.g. lower product distance indication at 40 % (3.102 m) and upper product distance adjustment at 45 % (3.331 m), the measurement will be inaccurate. A characteristic curve is gener­ated from the two points. Even the smallest deviations between actual product distance and entered product distance will consider­ably influence the slope of the characteristic curve. If the adjustment points are too close
Under the menu item "
Conditioning
“, you assign a product distance at 0 % and at 100 % filling. Then you enter the parameter and the physical unit as well as the decimal point.
Enter in the menu window "
0 % corresponds
the numerical value of the 0 % filling. In the example of the adjustment with the PC and the adjustment software VVO this would be 45 for 45 liters.
• Confirm with "
OK
“.
With the "—>“ key you change to the 100 % menu. Enter here the numerical value of your parameter corresponding to a 100 % filling. In the example 1200 for 1200 liters.
together, small errors inflate to considerably larger ones when the 0 % or the 100 % value is outputted.
68 VEGAPULS 56 Profibus PA
Setup
• Confirm with "OK“.
If necessary, choose a decimal point. How­ever, note that only max. 4 digits can be displayed. In the menu "
prop. to
“ you choose the physical quantity (mass, volume, dis­tance…) and in the menu " unit (kg, l, ft
3
, gal, m3 …).
Unit
“ the physical
Linearisation:
Adjust­ment
Signal condit­ioning
Scal­ing
Lin. curve
Linear
Integra tion time
0 s
A linear correlation between the percentage value of the product distance and percent­age value of the filling volume is preset. With the menu "Lin. curve“ you can choose be­tween linear, spherical tank and cylindrical tank. The generation of a customized linearisation curve is only possible with the PC and the adjustment program VVO.
6. Meas. conditions
(see menu schematic)
8. Signal-Noise difference
In the menu
you get important information on the signal quality of the product echo. The higher the "S-N“ value, the more reliable the measure­ment (menu plan MINICOM).
Ampl.: means amplitude of the level echo in
S-N: means Signal-Noise, i.e. the useful
The bigger the "S-N“ value (difference be­tween the amplitudes of the useful signal level and the noise level), the better the measure­ment: > 50 dB Measurement excellent 40 … 50 dB Measurement very good 20 … 40 dB Measurement good 10 … 20 dB Measurement satisfactory 5 … 10 dB Measurement sufficient < 5 dB Measurement poor
Example:
Ampl. = 68 dB S-N = 53 dB
68 dB – 53 dB = 15 dB
Ampl.:
XX dB
S-N:
XX
dB
dB (useful level)
level minus the level of the back­ground noise
This means that the noise level is only
7. False echo storage
A false echo storage is always useful when unavoidable false echo sources (e.g. struts) must be minimised. By creating a false echo
68 dB – 53 dB = 15 dB.
A 15 dB noise level with a 53 dB higher signal level would ensure a high degree of meas­urement reliability.
storage, you authorise the sensor electronics to record the false echoes and save them in an internal database. The sensor electronics treats these (false) echoes differently from the useful echoes and filters them out.
9. Outputs
Under the menu "Outputs“ you determine, for example, if the current output should be inverted, or which unit of measurement should be shown on the sensor display.
VEGAPULS 56 Profibus PA 69
Menu schematic for the adjustment module MINICOM
Sensor
m(d)
4.700
Para­meter
Sensor opti­mize
PULS 42
When switching on, the sensor
P
type and the software version are
3.00
displayed for a few seconds.
Confi­gura­tion
1.
Sensor addr.
(•–/ –•)
126
Meas. enviro nment
Sensor Tag
Sensor
Setup
Sensor address:
• Sensor address here from 1 … 126 only adjustable, if the DIP switch in the sensor is set to address greater than/equal to 126.
• For adjustment of the sensor with the DIP switch to address 128, switch 8 must be set to "ON“.
Meas. unit
m (d)
Adjust ment
w.out medium
Opera­ting range
Begin
0.50
4.
m (d)
3.
End
m (d)
6.00
Meas. condit ions
Condit ion
Solid
Condit ion
liquid
6.
Fast change
No
Fast change
No
with medium
High dust level No
Agitat ed sur face No
Large angle repose No
Foam­ing prod. No
Multi ple echo No
Low DK pro­duct No
Signal condit ioning
Sca­ling
Meas­ure in tube No
5.
Lin. curve
Linear
Multi ple echo No
Integr ation time
Measur ing in tube
T ube diamet
mm (d)
Correc tion Now!
0 s
50
OK ?
2.
Correc tion factor
2,50 %
Correc tion Now!
OK?
0.0 %
at
m (d)
XX.XXX
100.0%
at
m (d)
XX.XXX
Min­adjust at %
XXX.X
Max­adjust at %
XXX.X
0 % corres ponds
XXXX
100 % corres ponds
XXXX
Deci­mal point
888.8
Prop. to
Mass
Unit
Kg
Adjust ment in
m(d)
70 VEGAPULS 56 Profibus PA
Setup
With these keys you move in the menu field to the left, right, top and bottom
ESC
7. 8.
9.
act. dist.
m (d)
4.700
Update
Meas. dist.
m (d)
X.XX
Update Now!
Learn­ing!
OK?
False echo memory
Create new
Meas. dist.
m (d)
X.XX
Update Now!
Learn­ing!
Out­puts
OK?
Add’l func­tions
Info
Ampl.:
XX dB
S-N:
XX
dB
Delete
Delete Now!
OK?
Delet­ing!
Simulation:Simulation:
Simulation:
Simulation:Simulation:
Sensor Tag
Sensor
One hour after the last simulation adjustment, the sensor returns automatically to normal operating mode.
Simu­lation
Sensor type
PULS42 P
Reset to de­fault
Reset Now!
OK?
Reset ing!
Serial number
1094 0213
Act. dist. m
X,XX
Lan­guage
Eng­lish
Softw.
Softw.
vers.
date
3.00
15.09. 1999
Act.
max.
dist.
range
m (d)
m (d)
4.700
7.000
Menu items in bolt print provide sensor and measured value information and cannot be modified in this position.
OK
Sensor addr.
(•–/ –•)
Ampl.:
XX dB
S-N:
XX
126
dB
PA output
Prop. to
di­stance
Fail­ure mode
value
Sensor displ.
Prop. to
di­stance
Simu­lation Now!
Simu­lation
XXX.X
OK?
High dust level No
%
Fast change
No
Light grey menu fields are only displayed if required (dependent on the adjustments in other menus).
White menu items can be modified with the "+“ or "–“ key and saved with the "OK“ key.
VEGAPULS 56 Profibus PA 71

6 PA function diagram

PA function diagram
Raw-Distance [Distanz (m)]
Sensor value [sensor unit (m,ft)]
Adjustment
min-max Life-adjustment Dry-adjustment possible
Cal point hi, Cal point lo [sensor unit (%,m,ft ...)] Level hi, Level lo [sensor unit (%,m,ft ...)]
Level
hi
lo
Cal point hi Cal point lo
Cal
Sensor offset (Float) [sensor unit (m,ft )]
Zero adjust
PDM
VVO
FDT
MINICOM
Zero offset
PDM
VVO
FDT
Simulation
Simulate value [level unit] (%,m,ft...)] (manuf. spec. parameter)
Simulation
off
on
Simulate value
F Time (sec) (not available over PA Parameter)
Filter
adjusted Level [level unit] (%,m,ft...)
Level offset [level unit (%,m,ft...)] (*1)
Offset
Offset
A 3-1
PDM
VVO
FDT
72 VEGAPULS 56 Profibus PA
PA function diagram
Simulation distance value (DS_50) [sensor unit (m,ft)] (manuf. spec. parameter)
Simulation
Transducer Block
A 3
Secondary value 2
distance [Not adjusted value (m,ft ...)]
off
Min/Max memory
max
min
A 2
Secondary value 1
[adjusted value (%)]
on
Simulate value
Min/Max sensor value, [Sensor unit (m,ft ...)]
PDM
VVO
FDT
Linearization
[Level-Volume relation] Tab X Y value level unit (%,m,ft ) primary value unit (%,m,ft)
Linearization
PDM
VVO
FDT
MINICOM
Out (VVO…)
Primary value
[linearized value (%)]
PDM
VVO
FDT
MINICOM
A 1
lin % (linearized value, vollume)
A 1
% (adjusted value)
A 2
distance
A 3
VEGAPULS 56 Profibus PA 73
lin % (Primary value; volume)
A 1
% (Secondary value 1)
A 2
distance (Secondary value 1)
A 3
lin %
%
distance
Scaled (PA-Out)
Display source select
Source selector
Integration time
[sec]
Filter
PDM
VVO
FDT
MINICOM
PA function diagram
Sensor display
Sensordisplay
VEGA
Limiting values (Alarms)
Hi hi limit, lo lo limit, hi limit, lo limit, alarm hys [Out scale unit]
Alarm check
Hi hi limit Hi limit
Lo limit Lo lo limit
Alarm hyst
PDM
VVO
FDT
MINICOM
C
PDM
VVO
FDT
Hi hi alarm, lo lo alarm hi alarm, lo alarm, Alarm sum
Out (VVO…)
Simulation
Simulated value:
- primary value (%,m,ft ...)
- secondary value 1 (%,m,ft ...)
Source for scaling
Channel
lin %
%
distance
PDM
VVO
FDT
MINICOM
- secondary value 2 (m,ft ...) (dep. on channel)]
Simulation
off
on
Simulate value
PDM
VVO
FDT
MINICOM
A 1… A 3
74 VEGAPULS 56 Profibus PA
PA function diagram
Fail safe
Fail safe value [out scale unit] Fail safe type eq:
- OFF,
- Last valid Out,
- As calculated
Fail safe
Fail safe value
Target mode
Mode
Auto
Function-Block
Scaled (PA-Out) [output signal see Kap 3.3]
Man
Mode & Status calc.
E
PDM
VVO
FDT
out
Actual mode
D
PDM
VVO
FDT
MINICOM
Device status
Scaling (PV-Scale and Out-Scale)
PV Scale
- primary value (%,m,ft ...)
- secondary value 1 (%,m,ft ...)
- secondary value 2 (m,ft ...) (dep. on channel)
PV Scale
1
0
EU 100%
EU 0%
Out Scale
- primary value (%,m,ft ...)
- secondary value 1 (%,m,ft ...)
- secondary value 2 (m,ft ...) (dep. on channel)
Out Scale
EU 100%
EU 10%
0
PDM
VVO
4
FDT
B
VEGAPULS 56 Profibus PA 75

7 Diagnosis

7.1 Simulation

To simulate a certain filling, you can call up the function "Simulation“ on the adjustment module MINICOM or in the software program VVO.
Diagnosis
Simulation with V VO or PACTware
If you start the simulation mode with the ad­justment program VVO or PACTware
TM
TM
on the PC, the simulated level is outputted until you quit the simulation mode.
With this function, you simulate a real vessel filling level. Please note that connected instru­ments, such as e.g. a PLC, react according to their adjustments and will probably acti-
Simulation with MINICOM
If you start the simulation mode on the adjust­ment module MINICOM, the sensor returns to standard operating mode after one hour.
vate alarms or system functions.

7.2 Error codes

Error codes Corrective measure
E013 No valid measured value Message is displayed during the warm-up
- Sensor in the warm-up phase phase
- Loss of the useful echo If the message remains, a false echo storage
E017 Adjustment span too small Carry out a readjustment.
E036 Sensor software does not run Sensor requires a software update (service).
(with the adjustment software on the PC - see "Echo curve“ under "Sensor optimisation“) must be carried out together with a modification of mounting location and orientation to achieve the lowest possible false echo background.
Make sure that the difference between min. and max. adjustment is at least 10 mm .
Message appears during a software update.
E040 Hardware failure/Electronics defec- Check all connection cables.
tive Contact our service department.
E113 Communication conflict Service or sensor exchange
76 VEGAPULS 56 Profibus PA
Technical data

8 Technical data

8.1 Data

Power supply
Supply voltage 9 … 32 V DC) (output voltage U coupler) see PA specification, e.g.
- non-Ex 22 V DC (nominal voltage of the segment
- Ex 15 V DC nominal voltage of the segment
Current consumption constant 10 mA (no leakage current output) Load dependent on segment coupler, see
Unit and measuring range
Unit distance between product surface and
Standard 0 … 20 m Measuring range Measurement in standpipe
- VEGAPULS 56 on DN 50 0 … 16 m
- VEGAPULS 56 on DN 100 0 … 19 m
of the segment dependent on the segment coupler applied)
O
coupler) max. 32 sensors on one two-wire cable
coupler, max. 10 sensors on one two-wire cable (typical 8 sensors)
technical data of the segment coupler and Profibus specification
1)
process fitting (e.g. lower flange side of the sensor)
Output signal
- digital (Profibus PA) digital output signal in two-wire technology: The digital output signal (meas. signal) is modulated to the power supply and further processed in the PLC or processing system; max. 32 sensors on one two-wire cable l(Ex: max. 10).
Integration time 0 … 999 seconds (adjustable)
Display indication
Indication - optional integrated, scalable, analogue and
digital display of measured values
- optional external display of measured values,
up to 25 m separated and powered by the sensor. The external indication (VEGADIS 50) can be mounted in Ex area.
The four-wire cable to the external indicating instrument VEGADIS 50 must be screened, see "5 Electrical connection“.
VEGAPULS 56 Profibus PA 77
Technical data
Adjustment
- adjustment software VEGA Visual Operating on Master-Class 2 PC
- adjustment module MINICOM in sensor or in external indicating instrument (optional)
- process adjustment interface PACTware
TM
- SIMATIC PDM in conjunction with Electronic Device Description (EDD)
Accuracy (typical values under reference conditions)
2)
Accuracy < 0.1 % (deviation in characteristics including
repeatability and hysteresis acc. to the limit point adjustment relating to the max. measuring
range) Linearity error better than 0.05 % Influence
- of the ambient temperature
- of the process temperature
2)
2)
0.06 %/10 K
negligible (0.004 %/10 K at 5 bar)
(0.003 %/10 K at 40 bar)
- of the process pressure 0.025 %/bar Resolution of the digital output signal 0.005 % (relating to max. measuring range) Adjustment time 1 … 10 s (dependent on default setting) Resolution max. 1 mm
Characteristics
1)
Frequency 6.3 GHz (USA 6.3 GHz) Intervals 0.6 s Min. span between full and empty adjustment 10 mm (recommended 50 mm) Beam angle (at –3 dB)
- with DN 80 38° (only for standpipe measurement)
- with DN 100 30° (only for standpipe measurement)
- with DN 150 20°
- with DN 200 16°
- with DN 250 14° Influence of the process temperature at 0 bar nor measurable;
at 5 bar 0.004 %/10 °K;
at 40 bar 0.03 %/10 °K Influence of the process pressure 0.0265 %/bar Emitted radar power (average) 0.717 µW Received average emitted power
- distance 1 m 0.4 … 3.2 nW per cm2 (0.4 … 3.2 x 10-9 W/cm3)
- distance 5 m 0.02 … 0.13 nW per cm
3)
2
78 VEGAPULS 56 Profibus PA
Technical data
Ambient conditions
Ambient temperature on the housing -20°C … +60°C Flange temperature (process temperature) -40°C … +350°C (pressure-dependent), see
following diagrams
Vessel insulation in process temperatures exceeding 200°C, the
rear of the flange must be covered with a heat insulation, see also chapter "4 Mounting and
installation“. Storage and transport temperature -40°C … +80°C Protection IP 66/IP 67 Protection class
- two-wire sensor II
- four-wire sensor I Overvoltage category III Vessel pressure max. 64 bar (temperature-dependent), see
following diagrams Burst pressure
- at 20°C > 400 bar
- at 350°C > 250 bar
Flange DIN DN 50 Material: 1.4571 Seal surface acc. to DIN 2526 Form B, C, D, E
Flange DIN DN 50 Material: 1.4571 Groove and tongue acc. to DIN 2512 Form F, N
bar
40
25 16
-40 0 50 100 150 200 250 300 350
bar
64
40
25 16
-40 0 50 100 150 200 250 300 350
PN 40
PN 25
PN 16
PN 64
PN 40
PN 25
PN 16
˚C
˚C
VEGAPULS 56 Profibus PA 79
Technical data
Flange DIN DN 80 Material: 1.4571 Seal surface acc. to DIN 2526 Form B, C, D, E
Flange DIN DN 80 Material: 1.4571 Groove and tongue acc. to DIN 2512 Form F, N
Flange DIN DN 100 Material: 1.4571 Seal surface acc. to DIN 2526 Form B, C, D, E
bar
40
25 16
-40 0 50 100 150 200 250 300 350
bar
64
40
25 16
-40 0 50 100 150 200 250 300 350
PN 16
bar
40
25 16
PN 40
PN 25
PN 16
PN 64
PN 40
PN 25
PN 40
PN 25
PN 16
˚C
˚C
-40 0 50 100 150 200 250 300 350
Flange DIN DN 100 Material: 1.4571
bar
64
PN 64
Groove and tongue acc. to DIN 2512 Form F, N
40
25 16
-40 0 50 100 150 200 250 300 350
80 VEGAPULS 56 Profibus PA
PN 40
PN 25
PN 16
˚C
˚C
Technical data
Flange DIN DN 150 Material: 1.4571 Seal surface acc. to DIN 2526 Form B, C, D, E
Flange DIN DN 150 Material: 1.4571 Groove and tongue acc. to DIN 2512 Form F, N
Flange DIN DN 200 Material: 1.4571 Seal surface acc. to DIN 2526 Form B, C, D, E
bar
40
25 16
-40 0 50 100 150 200 250 300 350
bar
64
40
25 16
-40 0 50 100 150 200 250 300 350
bar
40
25 16
PN 40
PN 25
PN 16
PN 64
PN 40
PN 25
PN 16
PN 40
PN 25
PN 16
˚C
˚C
-40 0 50 100 150 200 250 300 350
Flange DIN DN 200 Material: 1.4571 Groove and tongue acc. to DIN 2512 Form F, N
bar
64
40 25
16
-40 0 50 100 150 200 250 300 350
PN 16
PN 64
PN 40
PN 25
˚C
VEGAPULS 56 Profibus PA 81
˚C
Technical data
Flange DIN DN 250 Material: 1.4571 Seal surface acc. to DIN 2526 Form B, C, D, E
Flange DIN DN 250 Material: 1.4571 Groove and tongue acc. to DIN 2512 Form F, N
bar
40
25 16
-40 0 50 100 150 200 250 300 350
bar
64
40
25 16
-40 0 50 100 150 200 250 300 350
PN 16
PN 16
PN 40
PN 25
PN 64
PN 40
PN 25
Flanges acc. to ANSI (ASA) B16.5 seal surface RF, material 1.4571 in sizes 2“ to 10“ can be used along the entire temperature range of -40°C … 350°C with the appropriate nominal pressures from 150 lbs, 300 lbs, 600 lbs and 900 lbs.
Other flanges and appropriate process data on request.
˚C
˚C
Connection cables
Two-wire sensors power supply and signal via one two-wire
cable
Electrical connection
- cable entry for Aluminium and plastic housing: one cable entry (four-wire: two- cable entries) and spring-loaded terminal connection up to max. 2.5 mm
2
wire cross-section.
- plug connection optional for plastic housing: four-pole, polarity reversal-safe screw connection (four-wire: two plug connections)
Cable entry
- ia terminal compartment 1 … 2 x M20 x 1.5 (cable ø 5 … 9 mm)
Ground connection max. 4 mm
82 VEGAPULS 56 Profibus PA
2
Technical data
Ex technical data (note approval documents in the yellow binder)
Classification
- d pressure-tight encapsulation
- ia intrinsically safe in conjunction with a separator or safety barrier)
Version without Exd connection housing VEGAPULS 56V Ex
- classification mark II 2G EEx ia IIC T6
- Ex approved Zone 1 (ATEX) Zone 1 (CENELEC; PTB, IEC)
VEGAPULS 56V Ex0
- classification mark II 1G EEx ia IIC T6
- Ex approved Zone 0, Zone 1 (ATEX) Zone 0, Zone 1 (CENELEC, PTB, IEC)
Version with Exd connection housing VEGAPULS 56V Ex
- classification mark II 2G EEx d ia IIC T6
- Ex approved Zone 1 (ATEX) Zone 1 (CENELEC; PTB, IEC)
VEGAPULS 56V Ex0
- classification mark II 1/2G EEx d ia IIC T6
- Ex approved Zone 0, Zone 1 (ATEX) Zone 0, Zone 1 (CENELEC, PTB, IEC
Permissible ambient temperature on the housing
- T6 -40°C … +55°C
- T5, T4, T3, T2, T1 -40°C … +70°C
- T4, T3, T2, T1 (with Ex d housing) -40°C … +78°C
- T4, T3, T2, T1 (without Ex d housing) -40°C … +85°C
Permissible ambient temperature on the antenna system when used in Ex areas
- T6 -40°C … +85°C
- T5 -40°C … +100°C
- T4 -40°C … +135°C
- T3 -40°C … +200°C
- T2 -40°C … +300°C
- T1 -40°C … +350°C
Materials
Housing Aluminium die-casting (GD-AlSi10Mg) Flange 1.4571 or Hastelloy C22 Antenna ceramic (Al Seal of the ceramic tip Tantalum
), 1.4571 or Hastelloy C22
2O3
Exd connection housing (only EExd version) Aluminium mold casting (GK-Alsi7Mg)
VEGAPULS 56 Profibus PA 83
Technical data
Weights in kg (1 psi = 0.0689 bar)
DIN 16 bar 25 bar 40 bar 64 bar
- DN 50 6.9 -- 7.7 8.5
- DN 80 8.8 -- 10.0 10.9
- DN 100 9.8 -- 11.7 14.1
- DN 150 14.6 -- 18.7 27.5
- DN 200 21.0 -- 26 48
- DN 250 29.6 38.2 38.5 61.4
ANSI 150 psi 300 psi 600 psi 900 psi
- 2“ 6.3 7.6 8.5 15.3
- 3“ 8.1 11.3 13.1 17.2
- 4“ 11.7 16.2 22,6 28.5
- 6“ 15.8 26.7 44.0 56.2
- 8“ 27.0 50.0 85.0 100.0
- 10“ 35.8 60.7 108.0 136.0
CE conformity
VEGAPULS series 56 radar sensors meet the protective regulations of EMC (89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following standards: EMC Emission EN 50 081 - 1: 1992; EN 50 041: 1997
NSR EN 61 010 - 1: 1993
Susceptibility EN 50 082 - 2: 1995; EN 50 020: 1994

8.2 Approvals

When using radar sensors in Ex areas or on ships, the instruments must be suitable and approved for the explosion zones and applications. The suitability is checked by the approval authorities and is certified in approval documents.
Please note the attached approval documents when using a sensor in Ex area.
Test and approval authorities
- PTB
(Physikalisch Technische Bundesanstalt ­Physical Technical Approval Authority)
- FM
(Factory Mutual Research)
- ABS
(American Bureau of Shipping)
- LRS
(Lloyds Register of Shipping)
- GL
(German Lloyd)
- CSA
(Canadian Standards Association)
84 VEGAPULS 56 Profibus PA
Technical data

8.3 Data format of the output signal

Byte4 Byte3 Byte2 Byte1 Byte0
Status Measured value (IEEE-754 Format, see below)
Status byte:
The status byte corresponds to profile 3,0 "Profibus PA Profile for Process Control Devices“ coded. The status "Measured value OK“ is coded as 80 (hex) (Bit7 = 1, Bit 6 … 0 = 0).
Measured value:
The measured value is transmitted as 32 Bit floating point figure in IEEE-754 format.
Byte n Byte n+1
Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit
7654321076543210
VZ 27262524232221202-12-22-32-42-52-62
Sign Exponent Mantissa
Byte n+2 Byte n+3
Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit Bit
7654321076543210
2-82-92
-102-112-122-132-142-152-162-172-182-192-202-212-222-23
-7
Mantissa Mantissa
Formula: Measured value = (-1)VZ • 2
Examples: 41 70 00 00 (hex) = 0100 0001 0111 0000 0000 0000 0000 0000 (bin)
Meas. value = (-1)0 • 2
= 1 • 2
(Exponent - 127)
(130 - 127)
3
• (1 + 0.5 + 0.25 + 0.125)
• (1 + Mantissa)
• (1 + 2-1 + 2-2 + 2-3)
= 1 • 8 • 1.875 = 15.0
VEGAPULS 56 Profibus PA 85

8.4 Dimensions

Aluminium housing
Technical data
Aluminium housing Exd connection housing
(opened)
370
205
320
ø165
213 185
25
116
(opened)
370
205
320
18
23
ø200
ø76
20
75
185
213
ø220
25
116
20
120
ø96
ø18
ø125
DN 50
Pipe antenna
ø18
ø160
DN 80
Pipe antenna
ø18
ø180
DN 100
86 VEGAPULS 56 Profibus PA
Technical data
ø22
ø285
ø146
ø240
DN 150
22
205
ø340
ø197
ø22
ø295
DN 200
24
ø405
296
ø241
ø26
ø355
DN 250
26
380
VEGAPULS 56 Profibus PA 87
External indicating instrument VEGADIS 50
85 38
ø5
48
10
Pg 13,5
Mounting on carrier rail 35 x 7.5 acc. to EN 50 022 or flat screwed
118
108
135
82
Flange dimensions acc. to ANSI
d
2
b
f
d
1
k
D
Technical data
Note:
The cable diameter of the connection cable should be min. 5 mm and max. 9 mm. Otherwise the seal effect of the cable entry
85
would not be ensured.
D = outer flange diameter
b = flange thickness k = diameter of hole circle d
= seal ledge diameter
1
f = seal ledge thickness
1
/16" = approx. 1.6 mm
d
= diameter of holes
2
Size Flange Seal ledge Holes
Db k d1No. d
2
2" 150 psi 152.4 20.7 120.7 91.9 4 19.1 3" 150 psi 190.5 25.5 152.4 127.0 4 19.1 4" 150 psi 228.6 25.5 190.5 157.2 8 19.1 6" 150 psi 279.4 27.0 241.3 215.9 8 22.4
Adjustment module MINICOM
ESC
+
-
Tank 1 m (d)
12.345
67,5
74
32,5
OK
88 VEGAPULS 56 Profibus PA
Adjustment module for insertion into series 50 sensors or into the external indicating instru­ment VEGADIS 50
Notes
VEGAPULS 56 Profibus PA 89
Notes
90 VEGAPULS 56 Profibus PA
Notes
VEGAPULS 56 Profibus PA 91
VEGA Grieshaber KG Am Hohenstein 113 D-77761 Schiltach Phone (07836) 50-0 Fax (07836) 50-201 E-Mail info@de.vega.com
www.vega.com
ISO 9001
All statements concerning scope of delivery, application, practical use and operating conditions of the sensors and processing sys­tems correspond to the latest information at the time of printing.
Technical data subject to alterations
2.26 386 / July 2001
Loading...