VEGA MET307 User Manual

VEGAMET 307 / 308
TIB • Technical Information • Operating Instructions
Signal conditioning instrument
for continuous level measurement
or
• a pressure sensor
VEGA Grieshaber KG
Am Hohenstein 113 Postfach 11 42 D-77757 Schiltach Phone 0 78 36/50-0 Fax 0 78 36/50-201
A
B
0 4
mA
VEGAMET 308
0
20
40
60
80
100
%
Application
These signal conditioning instruments VEGAMET 307 / 308 are used for level proportional output and indication of levels (continuous level measure­ment).
The VEGAMET 308 is additionally equipped with an integral level switch with adjustable switching hysteresis. Therefore level dependent switching functions are possible.
The
VEGAMET 307 consists of:
• plastic housing with pluggable multipoint connec­tor (series 300)
• electronics
• front panel with
- analog indicating meter
- mains control lamp
- potentiometer for empty adjustment
- potentiometer for full adjustment
- change-over switch for current output range
0 … 20 mA or 4 … 20 mA.
The VEGAMET 308 consists of:
• as VEGAMET 307
• however additional adjustment elements for the level switch:
- 2 pressure keys and 2 potentiometers for
adjustment of the switch points
- relay control lamp
- A/B-switch
A measuring system consists of:
• signal conditioning instrument VEGAMET 307 or VEGAMET 308
• capacitive electrode with oscillator
or
• pressure sensor with oscillator
Additional indicators and auxiliary level switches can be connected to the current and voltage outputs.
Level measurement with capacitive electrodes
Electrode, product and vessel wall, or electrode and product form a capacitor. The capacitance increases with increasing level.
In either case the oscillator converts this capaci­tance change into a level proportional measuring signal. This signal is fed to the VEGAMET 307 or 308 for signal conditioning.
Level measurement with pressure sensors
The diaphragm of the pressure sensor converts the hydrostatic pressure of the product into a linear movement. This movement is transmitted to the plunger-type capacitor. The level of the product therefore changes the capacitance.
Configuration
Function
Power supply 20 … 250 V AC; 48 … 62 Hz
20 … 90 V DC
Power consumption at U
N
approx. 3 VA
Measuring signal Connection line 2-wire, unscreened (standard cable) input Resistance per conductor max. 50 Ohms
Linearity error 0,1 % measuring range Temperature error 0,01 % measuring range / 10 K
Adjustment data Empty adjustment range 3,5 … 17 mA
Current difference between empty and full adjustment: > 600
µA
Indication analog indication 0 … 100 %
Current output Range 0 … 20 mA or 4 … 20 mA
(adjustable) Load max. 750 Ohm Resolution 0,05 % Linearity error 0,025 % measuring range Temperature error 0,025 % measuring range / 10 K
Voltage output Range 0 … 10 V, max. 1 mA (short-circuit protected)
Resolution 0,05 % Linearity error 0,025 % measuring range Temperature error 0,025 % measuring range / 10 K
Relay output (only VEGAMET 308) Contact 1 spdt
Function two-point switching Mode A/B Relay data: Contact material AgCdO and Au plated min. turn-on voltage 10 mV
switching current 10 µA
max. turn-on voltage AC 250 V, DC 60 V
switching current AC 2A, DC 1 A
max. breaking power 125 VA, 60 W
Permissible ambient temperature (housing) –25°C … +60°C / –4°F … +140°F Storage and transport temperature –25°C … +70°C / -4°F … +158°F
Housing Type plastic ABS
Protection IP 40 Dimensions w = 96 mm, d = 76 mm, h = 102 mm
Pluggable multipoint connector (cross section area of conductor) max. 2,5 mm
2
Weight approx. 270 g
Technical data