VEGA FLEX60 User Manual

Supple
mentary information
Recurring function
for VEGAFLEX series 60
test
Document ID:
36552
1 Conte
nts
Conten
1 About this document
2 Prerequisites
3 Sequence of the recurring function test
4 Result of the recurring function test
5 Test protocol - Recurring function test
2.1 Authorised personnel . . . . . . . . . . . . . . . . . . . . . . . .
2.2 Required tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2.3 Required comparative data . . . . . . . . . . . . . . . . . . . .
2.4 Required plant situation . . . . . . . . . . . . . . . . . . . . . .
3.1 Restart of the sensor . . . . . . . . . . . . . . . . . . . . . . . .
3.2 Verication of the current output . . . . . . . . . . . . . . . .
3.3 Verication of the instrument parameters . . . . . . . . . .
3.4 Verication of echo data . . . . . . . . . . . . . . . . . . . . . .
3.5 Sensor reaction to a level change . . . . . . . . . . . . . . .
5 5 5 5
7
9 10 11 12
2 Recurring
36552-EN-100225
function test for VEGAFLEX series 60
out this document
1 Ab
Why a function test?
Fault detection rate λ
92 %
1 Abou
t this document
The recurring function test serves to check the safety function and reveal possible undetected, dangerous failures
). The functional
du
capability of the measuring system has to be tested in adequate time intervals. It is the user's responsibility to select an appropriate type of testing. The time intervals are subject to the PFD
-value according to
avg
the specications in the Safety Manual (SIL).
With high demand rate, a recurring function test is not requested in IEC 61508. The functional eciency of the measuring system is
demonstrated by the frequent use of the system. In double channel architectures it is a good idea to verify the eect of the redundancy through recurring function tests at appropriate intervals.
With this supplementary information you can carry out a recurring function test of level sensors VEGAFLEX 61, 62, 63, 65 and 66 without dismounting the instrument or moving the level of the medium to the switching point.
With this procedure, 88 % or 92 % of all dangerous undetected instrument failures
) are detected (DC
du
Proof
).
The described function test fulls the requirements according to SIL.
If you have already created a sensor documentation during setup, you
du
can check the sensor at a detection rate of 92 % of all dangerous undetected failures.
The remaining dangerous undetected failures are 11 FIT.
FIT = Failure In Time (1 FIT = 1 failure/10
9
h)
Fault detection rate λ
88 %
36552-EN-100225
Recurring
function test for VEGAFLEX series 60 3
e sure that also a later sensor documentation is possible. This
Mak sensor documentation of a recurring function test must be at least 6 months old.
If you created no sensor documentation during setup, you can check
du
the sensor only at a detection rate of 88 % of all dangerous undetected failures.
The remaining dangerous undetected failures are in this case 16 FIT.
9
FIT = Failure In Time (1 FIT = 1 failure/10
h)
1 A bou
t this document
ase note the Ex-specic safety information for installation and
Ple operation in Ex areas. These safety instructions are part of the scope of delivery and come with the Ex-approved instruments.
Warning:
The recurring function test inuences connected devices. Take note that downstream devices may be activated during the test.
Informa
tion:
Proceed according to the specied, recommended sequence of these instructions to isolate possible device failures systematically.
Informa
tion:
Document the recurring function test, for example, in the test protocol in the supplement. To facilitate the recording and for further function tests, we recommend to copy the empty test protocol before completing it.
This supplementary information manual can be downloaded from our download section.
Th
e recurring function test cannot replace the prescribed test
according to WHG (Water Resources Act).
4 Recurring
36552-EN-100225
function test for VEGAFLEX series 60
2 Prer
equisites
2 Prere
quisites

2.1 Authorised personnel

All operations described in this operating instructions manual must be carried out only by trained specialist personnel authorised by the plant operator.
During work on and with the device the required personal protective equipment must always be worn.

2.2 Required tools

l This test instruction l PACTware l Actual VEGA DTM Collection l Device-DTM of the corresponding sensor (part of the VEGA DTM
Collection)
l Communication-DTM (part of the VEGA DTM Collection) l Interface adapter VEGACONNECT l mA-meter or PLC resp. DCS (accuracy ≤±0.2 %) l Operating instructions manual of the sensor l Safety Manual

2.3 Required comparative data

The setup data should be used for verication of the settings.
The following setup data are required:
l Sensor documentation of the setup with all parameters or a sensor
documentation created at least 6 months ago
l Documentation of all parameter changes since the setup
36552-EN-100225
Recurring
the sensor documentation of the setup or a sensor documentation
If created at least 6 months ago is not available, then the described recurring function test
92 %) cannot be carried out completely. In
du
this case, only the test at a detection rate of 88 % of all dangerous, undetected failures is possible.

2.4 Required plant situation

Caution:
e sure that there are no considerable process-relating changes in
Mak your plant during the recurring function test. This means also that the level in the vessel should not change signicantly by lling or emptying during the test. Make sure that also temperature changes, stirrers, current reactions in the vessel, etc. can cause level changes.
function test for VEGAFLEX series 60 5
0
0
V
dB
3
1
2
2 P rereq
uisites
tion:
Informa
Document the recurring function test, for example, in the test protocol in the supplement.
The following conditions must be fullled when performing the recurring function test:
Fig. 1: Level 1 Echo curve 2 Logarithmic echo curve 3 Amplitude of the useful echo (logarithmic echo curve)
echo - VEGAFLEX
l The process conditions must be nearly constant (level, process
pressure, process temperature)
l The medium must be the same as during setup or the medium
must at least belong to the same product group.
- Solvents/Liquid gases/Hydrocarbons/Oils (DK value < 3)
- Chemical mixtures (DK value 3 … 10)
- Water/Acids/Bases (DK value > 10 or conductive)
l The level must be either in the following areas:
- Distance to the process tting 200 mm.
- Min. covering of the rod electrode 100 mm/cable electrode
250 mm.
-
- or the following requirement must be fullled:
-
- Reliability at least 20 dB (amplitude of the useful logarithmic
echo above the noise level). The reliability can be veried during the test.
36552-EN-100225
6 Recurring
function test for VEGAFLEX series 60
Loading...
+ 14 hidden pages