Please read this manual carefully, and also take
note of country-specific installation standards
(e.g. the VDE regulations in Germany) as well
as all prevailing safety regulations and accident prevention rules.
For safety and warranty reasons, any internal
work on the instruments, apart from that involved in normal installation and electrical connection, must be carried out only by qualified
VEGA personnel.
2VEGAFLEX 55K
Note Ex area
Please note the attached safety instructions
containing important information on installation
and operation in Ex areas.
These safety instructions are part of the operating instructions and come with the Ex approved instruments.
Contents
Contents
Safety information ........................................................................ 2
Note Ex area ................................................................................ 2
1 Product description
1.1 Function ................................................................................. 4
1.2 Application features ............................................................. 4
1.3 Types and versions ............................................................. 5
1.4 Type code ............................................................................. 7
1.5 Technical data ....................................................................... 8
High frequency microwave impulses are
guided along a steel rod.
The microwave impulses are reflected when
they reach the product surface. The impulse
running time is processed by the integrated
electronics and outputted as level.
The sensors detect levels in all types of liquids. Density, conductivity and dielectric
value of the product do not influence the
measurement. Continuously changing properties of the medium also do not influence the
measured value.
In many applications, VEGAFLEX microwave
sensors are the solution to difficult technical
problems. Even in products with varying or
fluctuating dielectric constant, the level is
reliably detected. In high, narrow vessels,
where non-contact measurement technologies often deliver less than optimal results,
VEGAFLEX carries out problem-free measurements. The sensor part of VEGAFLEX 55
has a coaxial construction. A rod with 8 mm
diameter is positioned in a tube with 21.3 mm
diameter.
• Adjustment without filling or emptying the
vessel.
• 4 … 20 mA two-wire sensors, power supply and measuring signal via one two-wire
cable (loop powered).
• Up to 15 sensors can be connected via
one two-wire cable.
• Measuring range up to 4 m, very small
minimum measuring distance.
• Unaffected by application conditions such
as:
- varying products
• Unaffected by the vessel material, e.g.
metal, concrete, plastic etc.
• As an option, the display with adjustment
functions can be mounted separate from
the sensor.
• Low wiring costs through the use of twowire technology.
1.2 Application features
Applications
• Level measurement of liquids.
• Measurement also in vacuum.
• All slightly conductive substances and all
substances with a dielectric value ε
can be measured.
• Measuring range 0 ... 4 m.
Two-wire technology
• Power supply, signal transmission and
output signal on one two-wire cable.
• 4 … 20 mA output signal or digital output
signal.
• Unaffected by noise, steam, gas compositions and inert gas stratification.
• Unaffected by varying density.
• Measurements under pressure up to
40 bar and with product temperatures up
to 150°C.
Communicative
• Integrated measured value display.
• As an option, display can be mounted
separate from the sensor.
• Adjustment from the PLC level.
Approvals
• Ex Zone 0 EEx ia IIC T 6 acc. to
ATEX II 1/2 G
• Ex Zone 0 EEx d ia IIC T 6 acc. to ATEX II 1/2 G
> 1.5
r
4VEGAFLEX 55K
Product description
Adjustment with PC
The setup and adjustment of VEGAFLEX
sensors is generally done on the PC with the
adjustment program VVO (VEGA Visual
Operating) under Windows®.
The program leads quickly through adjustment and parameter setting by means of
pictures, graphics and process
visualisations.
The PC can be connected at any individual
location in the system or directly to the signal
cable. This is done by connecting the twowire PC interface converter VEGACONNECT 2
or 3 to the sensor or to the signal cable.
The adjustment and parameter data can be
saved with the adjustment software on the
PC and can be protected by passwords. On
request, the adjustments can be quickly
transferred to other sensors.
Adjustment with adjustment module
MINICOM
With the small (3.2 cm x 6.7 cm) 6-key adjustment module MINICOM, the adjustment
can be carried out in clear text dialogue.
The adjustment module can be plugged into
VEGAFLEX or the external indicating instrument VEGADIS 50.
Thus, VEGAFLEX can also be adjusted from
the external indicating instrument VEGADIS
50.
Tank 1
m (d)
12.345
ESC
+
-
OK
Adjustment with HART® handheld
Series 50 sensors with 4 … 20 mA output
signal can also be adjusted with the HART
handheld or via a PC with HART® software
(e.g. Smart version). A special DDD (Data
Device Description) is not necessary. The
sensors can be adjusted with the HART
standard menus of the handheld.
HART Communicator
HART® handheld
®
®
1.3 Types and versions
VEGAFLEX series 50 K
In general, all VEGAFLEX series 50 sensors
can be adjusted with the pluggable adjustment module MINICOM or with any standard
HART® handheld. With the software VEGA
Visual Operating (VVO), it is also possible to
adjust the sensor with a PC.
4 … 20 mA sensors
Two-wire sensors for connection to a power
supply unit or a PLC.
Detachable adjustment module MINICOM
VEGAFLEX 55K5
Configuration
A measuring system with a VEGAFLEX can
be realised in different ways (see following
illustration).
The external indicating instrument VEGADIS
50 can be mounted up to 25 m away from the
sensor.
Two-wire technology
1
4 ... 20 mA sensor, power supply and
measuring signal via one two-wire cable
(loop-powered), indicating instrument
VEGADIS 11 only possible with four-wire
technology.
2
Connection to a PLC (active).
3
Connection to indicating instrument
VEGADIS 371 with up to four relay outputs.
VEGADIS 50
1
Product description
1)
22
4 … 20 mA
4
1)
only with HART
VEGAFLEX
2
2
3
®
1)
2
4 … 20 mA
passive
4 … 20 mA
passive
VEGADIS 11
2
SPS
+
-
VEGADIS 371 Ex
Relay (4 x)
0/4 … 20 mA
6VEGAFLEX 55K
Product description
1.4 Type code
The second figure of the type name, e.g.
VEGAFLEX 5[5]… distinguishes the instruments according to the version of the sensor
component.
The letter, e.g. VEGAFLEX 55[K] characterises the output signal:
K stands for an analogue 4 … 20 mA output
signal (compact instrument)
P stands for a digital signal transmission for
connection to Profibus PA
VEGAFLEX 55 K .CX D
D - Two-wire loop-powered / 4 … 20 mA output, HART
®
G - Profibus PA
CX - Ex Zone 0 EEx ia IIC T 6 acc. to ATEX II 1/2 G
DX - Ex Zone 0 EEx d ia IIC T 6 acc. to ATEX II 1/2 G
P - Profibus PA
K - Analogue 0 … 20 mA output signal (two-wire technology)
Instrument series with 8 mm rod and 21.3 mm tube
Measuring principle (FLEX for guided microwave)
VEGAFLEX 55K7
1.5 Technical data
Power supply
Supply voltage
- two-wire sensor24 V DC (15 … 36 V DC)
Current consumption
- two-wire sensormax. 22.5 mA
Power consumption
- two-wire sensormax. 810 mW
Ω
1000
680
500
250
HART® load
Voltage limit
Ex sensor
Product description
Voltage limit
Non-Ex sensor
0
20222426283032343615 1618
The min. supply voltage depends on the sensor current.
V
36
15
14
0422
Measuring range
VEGAFLEX 550.1 ... 4 m
Output signal
4 … 20 mA current signal, load max. 500 Ω
Adjustment
- PC and adjustment software VEGA Visual Operating
- adjustment module MINICOM
- HART® handheld
V
Supply voltage
Range of the required
terminal voltage on the
sensor
Sensor current
mA
8VEGAFLEX 55K
Product description
Accuracy (under reference conditions acc. to IEC 770 - relating to the max. meas. range)
Linearity error< 0.1 %
Temperature drift0.015 %/10 K
Resolution of the 4 … 20 mA signal0.025 % of range (DA converter)
Resolution1 mm
Characteristics
Min. span between
full and empty adjustment
- analogue output signal10 mm
Ambient conditions
Vessel pressure-1 … 40 bar
Ambient temperature on the housing-40°C … +60°C
Process temperature-40°C … +150°C
Storage and transport temperature-40°C … +80°C
ProtectionIP 66/IP 67 (meets both protection standards)
Protection class
- two-wire sensorII
- four-wire sensorI
Overvoltage categoryIII
Min. dielectric constantε
> 1.5
r
Process fittings
VEGAFLEX 55G 3/4A, 3/4" NPT, G 1A, 1" NPT, G 11/2 A, 11/2" NPT
1.4435 (stst) or Hastelloy C22 plated
flanges
Ex technical data
Ex-Zone 0 acc. to ATEX II 1/2 G
Ex Zone 0 EEx ia IIC T 6 acc. to ATEX II 1/2 G
Ex Zone 0 EEx d ia IIC T 6 acc. to ATEX II 1/2 G
The permissible operating data of the VEGAFLEX sensors for Ex areas are listed in the
certificate.
Materials
HousingPBT (Valox) or
Aluminium (powder-coated)
Coax rod1.4435 (stst: 316L) or Hastelloy C22
VEGAFLEX 55K9
Product description
Connection cables
Two-wire sensor
- power supply and signal via one two-wire cable.
The cable resistance depends on the supply voltage (see diagram).
Conductor cross-sectiongenerally 2.5 mm
Ground connectionmax. 4 mm
2
2
Cable entry2 x M20 x 1.5 (cable diameter 5 … 9 mm)
2 x 1/2" NPT with ExD housing
CE conformity
VEGAFLEX sensors meet the protective regulations of EMC (89/336/EWG) and NSR
(73/23/EWG). Conformity has been judged acc. to the following standards:
EMCEmissionEN 50 081 - 1: 1992
SusceptibilityEN 50 082 - 2: 1995
NSREN 61 010 - 1: 1993
Display
Displayscalable, analogue and digital display of
measured values (option).
An external measured value display, powered by the sensor, can be mounted at a distance
of up to 25 m from the sensor.
Signal output
Signal output
- two-wire technology4 … 20 mA (see diagram)
Resolution of the 20 mA signal0.025 % of range
Load0 … 500 Ω
Two-wire technology:
The analogue 4 … 20 mA output signal (measuring signal) is transmitted together with the
power supply via one two-wire cable.
10VEGAFLEX 55K