VEGA D98 User Manual

Operating instructions
Pressure transmitter D98
p
Contents
Safety information ........................................................................ 2
1 Product description
2 Technical data
2.1 Data ....................................................................................... 4
2.3 Dimensions ........................................................................... 6
3 Mounting
3.1 Mounting instructions ........................................................... 7
3.2 Compensation of the atmospheric pressure ..................... 7
4 Electrical connection
4.1 Connection instructions ....................................................... 8
4.2 Terminal assignment ............................................................ 9
4.3 Connection example ............................................................ 9
Contents
5 Diagnostics............................................................................... 10
6 Instrument modification
6.1 Exchange of hygienic form seal ....................................... 11

Safety information

Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VDE regulations in Ger­many) as well as all prevailing safety regula­tions and accident prevention rules. For safety and warranty reasons, any internal work on the instruments, apart from that involved in normal installation and electrical connection, must be carried out only by qualified VEGA personnel.
2 Pressure transmitter D98
Product description

1 Product description

1.1 Function and configuration

D98 pressure transmitters are efficient modu­lar instruments for pressure and level meas­urement. A dry ceramic-capacitive CERTEC measuring cell is used as the pressure sen­sor element.
®
Pressure transmitter D98 3
Technical data

2 Technical data

2.1 Data

Nominal measuring range Gauge pressure resistanLow pressure resistance
Gauge pressure
0…0.4 bar / 0…40 kPa 30 bar / 3 000 kPa -0.8 bar / -80 kPa 0…1.0 bar / 0…100 kPa 35 bar / 3 500 kPa -1.0 bar / -100 kPa 0…2.5 bar / 0…250 kPa 50 bar / 5 000 kPa -1.0 bar / -100 kPa 0…4.0 bar / 0…400 kPa 65 bar / 6 500 kPa -1.0 bar / -100 kPa 0…10.0 bar / 0…1 000 kPa 90 bar / 9 000 kPa -1.0 bar / -100 kPa 0…16.0 bar / 0…1 600 kPa 130 bar / 13 000 kP a -1.0 bar / -100 k Pa
Power supply and signal circuit
Power supply
- without indication 12 … 36 V DC Residual ripple of the power supply no influence with U Output signal 4 … 20 mA (factory setting) Current limitation approx. 22 mA Fault signal approx. 22 mA Average delay time 20 ms Max. permissible load see load diagram:
load in
900
1 V
SS
600
300
supply voltage
12
18 24 30 36
in V
Measuring accuracy (according to DIN 16 086, DIN V 19 259-1 and IEC 770)
Measuring deviation
Reference conditions acc. to IEC 770, e.g.
- temperature 15°C … 35°C
- rel. humidity 45 % … 75 %
- air pressure 860 mbar … 1060 mbar Determination of characteristics limit point adjustment acc. to DIN 16 086 Characteristics linear Deviation in characteristics Hysteresis (repeatability)
1)
Relating to the nominal range
2)
In compensated temperature range of 0°C … +80°C, reference temperature 20°C
3)
According to IEC 770, Punkt 6.3.2 related to the nominal range
4)
The use of a properly fitting cable seal in the cable connection is necessary for maintaining the housing protection IP 66. If the seal used does not fit the cable, it should be replaced by a suitable one.
5)
FDA approved
4 Pressure transmitter D98
1)
1)
< 0.25 % < 0.02 %
Technical data
Influence of the ambient temperature
Average temperature coefficient of the zero signal
1) 2)
< 0.15 %/10 K
Long-term stability
Long-term stability of the zero signal
1) 3)
< 0.1 %/2 years
Other actuating variables
Vibration resistance mechanical vibration with 4 g and
5 … 100 Hz, tested acc. to the regulations of German Lloyd, GL-characteristics 2
Ambient conditions
Temperatures
Ambient temperature -40°C … +85°C Storage and transport temperature -50°C … +85°C Product temperature -40°C … +100°C (1 h up to +140°C)
Protective measures
Protection class IP 66 (EN 60 529)
Connection cable
Cable entry M20x1.5 (for cable ø 5…9 mm) Screw terminals for conductor cross-sections of up to 2.5 mm
Materials, wetted parts
Process connection stainless steel 1.4435 Diaphragm sapphire-ceramic® (99.9 % Oxide-ceramic) Seal, measuring cell
Materials, non-wetted parts
Housing stainless steel 1.4571 Ground terminal stainless steel 1.4305
4)
5)
EPDM
2
Weight
Weight 1.4 kg … 1.6 kg
CE conformity
The pressure transmitter D98 meets the requirements of EMC (89/336/EC) and NSR (73/23/ EWG). Conformity has been judged according to the following standards: EMC emission EN 50 081 - 1: 1992
susceptibility EN 50 082 - 2: 1995
NSR EN 61 010: 1993
Pressure transmitter D98 5

2.3 Dimensions

D98 DN 25 D98 DN 50
Technical data
188
164
200
176
TA
TB
6 Pressure transmitter D98
Mounting

3 Mounting

3.1 Mounting instructions

Cable entry
The pressure transmitter can be mounted in any position.
Cable entries must point downward to avoid moisture ingress. For this purpose, the hous­ing can be rotated by 330 °. With vertically mounted sensors, the connection cable to the housing must point downward so that rain and condensed water can drip off. This ap­plies especially to outdoor mounting, or mounting in humid rooms (e.g. caused by cleaning processes) or on cooled or heated vessels.
3.2 Compensation of the atmos­pheric pressure
The atmospheric pressure is compensated via a breather facility integrated in the hous­ing (air-permeable and moisture-resistant PTFE insert).
Moisture
Pressure transmitter D98 7

4 Electrical connection

Electrical connection

4.1 Connection instructions

The electronics in the pressure transmitter requires a supply voltage of 12 … 36 V DC. The electronics is designed in two-wire tech­nology i.e. supply voltage (DC) and measur­ing signal are led via the same two-wire connection cable to the terminals. The supply voltage is provided by an external power supply unit.
Please note that the external power supply according to DIN VDE 0106, part 101 must be reliably separated from the mains circuits.
Note the following instructions for electrical connection:
- Connection must be made according to country-specific installation standards (e.g. in Germany acc. to the VDE regulations).
- The terminal voltage should not exceed 36 V to avoid damage to the electronics.
- The electrical connection is provided with polarity reversal.
- The wiring between pressure transmitter and power supply can be carried out with standard two-core cable.
- Screened cable is recommended in case of strong electromagnetic interference. Install the screening on one side of the sensor.
- In case of overvoltage, we recommend using a pressure transmitter with inte­grated overvoltage protection or installing VEGA overvoltage arresters.
- A seal must be used which correctly fits the cable in the cable entry.
Connection cable
Please make sure that the connection cables are specified for the anticipated operating temperatures in your plant. The cable must have an outer diameter of 5 ... 9 mm, other­wise the sealing effect of the cable entry cannot be guaranteed.
8 Pressure transmitter D98
Electrical connection

4.2 Terminal assignment

4-20mA
1 2 3 4 5
-
+
4...20mA
12...36 V DC
+
control unit 4 … 20 mA
-
-
energy supply
+
12 … 36 V DC

4.3 Connection example

The following examples are valid for a direct connection to the terminals of the pressure trans­mitter. When the external connection housing is used, the connections are made to the appro­priate terminals of the housing. The hydrostatic pressure transmitter D98 is adjusted to the indicated measuring range by VEGA and has no adjustment option.
Oscillator is supplied by a power supply unit
The adjustment is made via the indicating instrument.
Ammeter for on-site control
+ – –
1 2 3
connection terminals pressure transmitter
U
K
analogue / digital indicating instrument
U
A
4 … 20 mA
U
H
power supply unit
~
+
Oscillator is supplied by a PLC with active input circuit
Evaluation is carried out via PLC.
Ammeter for on-site check
+ – –
1 2 3
connection terminals pressure transmitter
U
K
4 … 20 mA
memory program­mable control
U
H
+
Notes:
An ammeter for on-site check of the output current can be connected to the terminals 1 and 3. This measurement can be carried out during operation without interruption of the mains sup­ply.
Pressure transmitter D98 9

5 Diagnostics

Diagnostics
Maintenance
When properly used, pressure transmitters D98 are maintenance-free.
Should a dismounting of the pressure trans­mitter be necessary (e.g. vessel cleaning) we recommend the use of a new seal. You should only use VEGA seals.
Troubleshooting
If faults do occur, the following measures
must be taken before dismounting the pressure transmitter:
- check the atmospheric pressure compen­sation (only with gauge measuring ranges)
- check the electrical connections.
Check the atmospheric pressure compen­sation
Open the cover of the housing. The meas­ured value must not change. However, if the displayed value changes, compensation of the atmospheric pressure is not ensured, which can result in distortion of the measured value. Make sure the breather unit is unob­structed. It consists of a black plastic threaded insert with integrated filter element.
Check the electrical connections
Terminals Pressure transmitter
1 2 3
mA
current
voltage
V
current
mA
external energy
– +
~
Check the voltage
- The terminal voltage on the pressure
transmitter must be at least 12 V DC.
Check the current
• Initial current with unimmersed diaphragm of pressure transmitter: approx. 4 mA
• operating measuring current: 4 … 20 mA
• Exceeding or falling short of the specified measuring range: 20.5 mA and 3.8 mA
• Pressure transmitter damaged or short­circuited: current > 22 mA or < 3.6 mA
Note:
The pressure acting on the breather must be the same as the atmospheric pressure in the open vessel.
10 Pressure transmitter D98
Instrument modification

6 Instrument modification

6.1 Exchange of hygienic form seal

In the hygienic connections of pressure transmitter D98, the ceramic measuring cell is gaplessly sealed with a radial, form seal. This form seal (material EPDM-FDA) can be exchanged by the user without a fresh ad­justment being necessary. The criteria and the time intervals for such an exchange of the seal are generally defined by the process and hygienic requirements.
Important:
Use only original replacement seals from VEGA, article no. 2.17 775!
Please note the following exchange proce­dure.
Removal procedure:
1 Pressure transmitter should be
unpressurized (switch off process pres­sure or empty vessel)
2 Loosen the hexagon pressure screw (4)
(width across flats, 46 mm) by turning to the left.
Note!
The process connection (6) (e.g. compres­sion nut) must not be loosened!
Installation procedure: 1 Place the new form seal (5) over the meas-
uring cell (the conical side must mate with the process connection).
2 Turning it lightly clockwise, insert the pres-
sure transmitter carefully into the process connection.
3 Tighten hexagon pressure screw (4) (width
across flats, 46 mm) (45 Nm).
4 Turn the housing (1) of the pressure trans-
mitter to the original position.
The exchange of the form seal is now fin­ished; the removed seal must be properly disposed of.
1
2
3
4
3 Turn the adapter (3) below the pressure
transmitter housing with a spanner (with across flats, 36 mm) slightly to the left (loosen the seal).
5
4 Hold onto the housing (1), pull the entire
pressure transmitter out of the process connection by carefully turning to the left.
5 Slightly lift the form seal (5) and loosen it
from the ceramic measuring cell.
6 If the form seal (5) does not completely
encircle the measuring cell, the remaining part must be carefully removed from the process connection.
Pressure transmitter D98 11
1 Pressure transmitter 2 Headless screw (avoids overwinding and must not be
removed) 3 Adapter 4 Hexagon screw 5 Form seal 6 Process connection
6
VEGA Grieshaber KG Am Hohenstein 113 D-77761 Schiltach Phone (07836) 50-0 Fax (07836) 50-201 E-Mail info@de.vega.com
www.vega.com
ISO 9001
All statements concerning scope of delivery, application, use and operating conditions correspond to the information available at the time of printing.
Technical data subject to alterations
24336 -EN-021030
Loading...