VEGA D96, D97 User Manual

Operating Instructions
Level and Pressure
Hydrostatic pressure transmitters
PROF I
D96/D97 (Profibus PA)
PROCESS FIELD BUS
BUS
p
Safety information, note Ex area

Safety information

Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and acci­dent prevention rules. For safety and warranty reasons, any internal work on the instruments, apart from that in­volved in normal installation and electrical con­nection, must be carried out only by qualified VEGA personnel.
2 Pressure transmitter D96/D97 (Profibus PA)

Note Ex area

Please note the attached safety instructions containing important information on installation and operation in Ex areas. These safety instructions are part of the operating instructions and come with the Ex approved instruments.
Contents
Contents
Safety information ........................................................................ 2
Note Ex area ................................................................................ 2
1 Product description
1.1 Function and configuration .................................................. 4
1.2 Types and versions ............................................................. 5
1.3 Technical data ....................................................................... 6
1.4 Approvals and certificates .................................................. 9
1.5 Dimensions ......................................................................... 10
2 Mounting
2.1 Mounting instructions ......................................................... 12
2.2 Compensation of the atmospheric pressure ................... 12
3 Electrical connection
3.1 Connection instructions ..................................................... 13
3.2 Wiring plan .......................................................................... 14
4 Setup
4.1 Setting the Profibus PA address ...................................... 15
4.2 Setup with module
"Menu-driven adjustment with additional functions" ........ 17
4.3 Setup with adjustment software
VEGA Visual Operating (VVO) ......................................... 23
5 Diagnostics
5.1 Maintenance ....................................................................... 31
5.2 Failure rectification ............................................................. 31
6 Instrument modification
6.1 Exchange of adjustment modules
in the processing unit ........................................................ 32
Pressure transmitter D96/D97 (Profibus PA) 3

1 Product description

0 - 20 bar
Product description

1.1 Function and configuration

D96 and D97 pressure transmitters are effi­cient instruments for hydrostatic level meas­urement. A dry ceramic-capacitive CERTEC measuring cell is used as the pressure sen­sor element for D96. D97 uses a dry metallic­capacitive measuring cell with Duratherm 600 diaphragm. The hydrostatic pressure effects a capacitance change on the diaphragm. This capacitance change is detected by an ASIC (Application Specific Integrated Circuit) and converted into a pressure-proportional signal by the integrated electronic module with microcontroller. Precise, high-resolution digital processing of measurement data ensures excellent technical data.
The electronics module is powered by a Profibus DP - PA segment coupler. The measured pressure is transmitted as a digital signal via the bus cable to the processing system and can be displayed on the indicat­ing module.
To improve reliability, the functionality of im­portant electronic components is continu­ously checked, and internal parameters such as sensor value, temperature and operating voltage are closely monitored.
The pressure transmitters D96 with ceramic CERTEC® measuring cell offer the advantage of continuous self-monitoring: the measuring and reference capacitances of the measuring cell constitute a predefined ratio over the entire measuring range. Any deviation from these data is a reliable indicator of a malfunc­tion of the measuring cell. If errors or mal­functions are detected during these routines, fault signals are triggered according to the Profibus PA specification.
The pressure transmitter consists of two parts, the transmitter and the processing unit. Both parts are connected via a three­wire screened cable (depending on the ver-
®
sion, with or without breather capillaries). The processing unit contains the adjustment elements (address switch, keys and LCD) and the terminals for the Profibus PA cable.
Transmitter
Processing unit
Profibus PA version
The instrument profile of the pressure trans­mitter D96/D97 is according to the profile specification version 3.0. The instrument master file (GSD) is supplied with the pres­sure transmitter D96/D97. In addition, the GSD is available as a download file from the VEGA homepage (www.vega.com).
Adjustment and indication
The following adjustment versions are avail­able:
- menu-driven adjustment (4 keys and DOT­Matrix) in the processing unit
- via PC with the adjustment software VEGA Visual Operating (VVO)
- optional, processing unit equipped with an indicating module.
Profibus PA cable
4 Pressure transmitter D96/D97 (Profibus PA)
Product description

1.2 Types and versions

Housing with terminals
Measuring ranges D96
Nominal meas. range (gauge pressure) Gauge press. resistance Low pressure resistance
00.1 bar / 010 kPa 15 bar / 1 500 kPa -0.2 bar / -20 kPa 00.2 bar / 020 kPa 20 bar / 2 000 kPa -0.4 bar / -40 kPa 00.4 bar / 040 kPa 30 bar / 3 000 kPa -0.8 bar / -80 kPa 01.0 bar / 0100 kPa 35 bar / 3 500 kPa -1.0 bar / -100 kPa 02.5 bar / 0250 kPa 50 bar / 5 000 kPa -1.0 bar / -100 kPa 05.0 bar / 0500 kPa 65 bar / 6 500 kPa -1.0 bar / -100 kPa 010.0 bar / 01 000 kPa 90 bar / 9 000 kPa -1.0 bar / -100 kPa 020.0 bar / 02 000 kPa 130 bar / 13 000 kPa -1.0 bar / -100 kPa
Cable outlet axial
Cable outlet lateral Plug connection
lateral
Measuring ranges D97
Nominal meas. range (gauge pressure) Gauge press. resistance Low pressure resistance
00.1 bar / 010 kPa 2.5 bar / 250 kPa -0.1 bar / -10 kPa 00.2 bar / 020 kPa 5 bar / 500 kP a -0.2 bar / -20 kPa 00.4 bar / 040 kPa 10 bar / 1 000 kPa -0.4 bar / -40 kPa 01.0 bar / 0100 kPa 25 bar / 2 500 kPa -1.0 bar / -100 kPa 02.5 bar / 0250 kPa 25 bar / 2 500 kPa -1.0 bar / -100 kPa 05.0 bar / 0500 kPa 25 bar / 2 500 kPa -1.0 bar / -100 kPa 010.0 bar / 01 000 kPa 25 bar / 2 500 kPa -1.0 bar / -100 kPa 020.0 bar / 02 000 kPa 25 bar / 2 500 kPa -1.0 bar / -100 kPa
Pressure transmitter D96/D97 (Profibus PA) 5
Product description

1.3 Technical data

Mechanical data
Transmitter materials, wetted parts
Pressure transmitter D96
- transmitter stainless steel 1.4571
- diaphragm sapphire-ceramic® (99.9 % Oxide-ceramic)
- suspension cable PE cable bushing CSM
- suspension hose FEP
- connection tube stainless steel 1.4571
- mounting boss stainless steel 1.4571
- transmitter protection PE plastic coating with funnel
- seal measuring cell Viton, Kalrez, EPDM, Hifluor
Pressure transmitter D97
- transmitter stainless steel 1.4571
- diaphragm Duratherm 600
- suspension cable PE cable bushing CSM
- suspension hose FEP
- connection tube stainless steel 1.4571
- mounting boss stainless steel 1.4571
- transmitter protection PE plastic coating with funnel
Transmitter materials, non-wetted parts
Transmitter housing - Alu die casting, powder-coated
Straining clamp galvanized steel Closing screw stainless steel 1.4305
- stainless steel 1.4571
Material of the processing unit
Housing high resistance plastic PBT (Polyester) Ground terminal stainless steel 1.4305 Window of the indication module Lexan
Adjustment and indicating elements (in the processing unit)
Menu-driven adjustment with additional functions
- adjustment elements 4 keys
- indicating elements DOT-matrix display, 3 lines with 7 digits each
Version without adjustment module
- adjustment element 8-pole mini coding switch for adjustment of the
Indication module LC-display with
6 Pressure transmitter D96/D97 (Profibus PA)
bus address
- bar graph (20 segments)
- digital value (4 digits)
- tendency indicators for rising or falling values
Product description
Weight
Basic weight approx. 1.5 kg Suspension cable approx. 0.12 kg/m Closing screw approx. 0.4 kg Straining clamp approx. 0.2 kg Sensor with terminal housing or with direct cable outlet approx. 2.2 kg Processing unit approx. 480 g
Electrical data
Adjustment ranges
Zero adjustable from -20 +95 % of nominal range Span adjustable from 3.3 120 % of nominal range
Supply and signal circuit
Supply voltage 9 … 32 V DC
(delivered by the segment coupler) Current consumption 10 mA ± 1 mA Integration time 0 50 s Rise time 70 ms (ti = 0 sec; 0 – 63 %)
Connection cable, processing unit – Profibus PA
Cable entry M20 x 1.5 (for cable ø 5 9 mm) Screw terminals for conductor cross-sections of up to 2.5 mm Recommended bus cable types - SINEC 6XV 830-5AH10 (Siemens AG)
- SINEC L2 6XV1 830-35H10 (Siemens AG)
- 3079 A (Belden)
2
Connection cable, processing unit – Transmitter
Cable entry M20 x 1.5 (for cable ø 5 9 mm) Screw terminals for conductor cross-sections of up to 2.5 mm
2
Transmitter
- with fixed cable outlet 3-wire screened, with breather capillaries
- with cable connection terminals 3-wire screened
Protective measures
1)
Protection
- transmitter with fixed cable outlet IP 68
- transmitter with terminal housing IP 66/IP 67
- processing unit IP 66/IP 67 Protection class III Overvoltage category III
1)
The use of a properly fitting cable seal in the cable connection is necessary for maintaining the housing protection. If the seal used does not fit the cable, it should be replaced by a suitable one.
Pressure transmitter D96/D97 (Profibus PA) 7
Product description
Accuracy (similar to DIN 16 086, DIN V 19 259 - 1 and IEC 770)
Deviation
Reference conditions (acc. to IEC 770)
- temperature 15°C 35°C
- rel. humidity 45 % 75 %
- air pressure 860 mbar 1060 mbar/86 kPa 106 kPa Determination of characteristics limit point adjustment acc. to DIN 16 086 Characteristics linear Deviation in characteristics
- Turn Down 1 : 1 < 0.25 % with accuracy class 0.25
- Turn Down up to 1 : 5 typ. < 0.3 % with accuracy class 0.25
- Turn Down up to 1 : 10 typ. < 0.4 % with accuracy class 0.25
Hysteresis 1) and repeatability
- D96 (ceramic measuring cell) < 0.02 %
- D97 (metal measuring cell) < 0.05 %
Influence of the ambient temperature
Average temperature coefficient of the zero signal
1) 2)
- Turn Down 1 : 1 < 0.15 %/10 K with accuracy class 0.25
- Turn Down up to 1 : 5 typ. < 0.225 %/10 K with accuracy class 0.25
- Turn Down up to 1 : 10 typ. < 0.3 %/10 K with accuracy class 0.25
1)
< 0.1 % with accuracy class 0.1
typ. < 0.1 % with accuracy class 0.1
1)
typ. < 0.2 % with accuracy class 0.1
< 0.05 %/10 K with accuracy class 0.1
typ. < 0.075 %/10 K with accuracy class 0.1
typ. < 0.1 %/10 K with accuracy class 0.1
Long-term stability
Long-term drift of the zero signal
3)
- D96 (ceramic measuring cell) < 0.1 % per 2 years
- D97 (metal measuring cell) < 0.1 % per 2 years
Other actuating variables
Calibration position upright, diaphragm points downwards Influence of the installation position
- D96 (ceramic measuring cell) < 0.2 mbar
- D97 (metallic measuring cell) < 5.0 mbar Vibration resistance mechanical vibrations with 4 g and
5 100 Hz, tested acc. to the regulations of German Lloyd GL-characteristics 2
1)
Relating to the nominal range.
2)
In compensated temperature range of 0°C +80°C, reference temperature 20°C.
3)
Acc. to IEC 770, item 6.1.2 relating to the nominal range.
8 Pressure transmitter D96/D97 (Profibus PA)
Product description
Operating conditions
Ambient conditions
Ambient temperature -40°C … +85°C
- with indicating module -20°C … +70°C Storage and transport temperature -40°C … +85°C Pressure transmitter D96
Product temperature with Viton seal tube version -20°C … +85°C
FEP suspension hose -20°C … +85°C PE cable -20°C … +60°C
with EPDM seal
tube version -40°C … +85°C FEP suspension hose -40°C … +85°C PE cable -40°C … +60°C
with Hilfuor seal
tube version -10°C … +85°C FEP suspension hose -10°C … +85°C PE cable -10°C … +60°C
with Kalrez seal
tube version 0°C … +85°C FEP suspension hose 0°C … +85°C PE cable 0°C … +60°C
Pressure transmitter D97
Product temperature
tube version -40°C … +85°C FEP suspension hose -40°C … +85°C PE cable -40°C … +60°C

1.4 Approvals and certificates

Approvals
- Ex Zone 2
- CENELEC EEx ia IIC
- ATEX II 1G EEx ia IIC If the use of approved instruments is required for certain applications, the appropriate official documents (test reports, test certificates and conformity certificates) must be ob­served. These are supplied with the respective instrument.
CE conformity
D96 and D97 pressure transmitters meet the requirements of EMC (89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following standards: EMC Emission EN 50 081 - 1: 1992
NSR EN 61 010 - 1: 1993
NAMUR regulations
Full compliance with the NAMUR regulations NE 21, May 1993.
Pressure transmitter D96/D97 (Profibus PA) 9
Susceptibility EN 50 082 - 2: 1995
Product description

1.5 Dimensions

175
C1
52
R 11
49
25
X4 A4 V4
A1, A2, B1, B2
66
ø 76
77
ø 41,6
SW 30
41
14
G 1½ A
39
14
C3 D3
100
77
ø 41,6 ø 41,6
SW 60
39
14
G 1½ A
139
SW 60
1½" NPT
G4 N4
ø 10
K
ø 10 ø 13 ø 28
KS R
XP
110
ø 40
134
ø 44
10 Pressure transmitter D96/D97 (Profibus PA)
Product description
Processing unit
with display module
38 82
5
˘
M20x1,5
with protective cover
135
118
108
139
85
72100
130
Pressure transmitter D96/D97 (Profibus PA) 11