VEGA D77 User Manual

Operating Instructions
Hydrostatic pressure transmitters D76 and D77
Level and Pressure
p
Contents
Note Ex area ................................................................................ 2
1 Product description
1.1 Function and configuration .................................................. 4
1.2 Types and versions ............................................................. 4
1.3 Electronics version without adjustment.............................. 5
1.4 Electronics version with integrated adjustment in
connection housing.............................................................. 6
1.5 Electronics for connection to VEGADIS 12 ........................ 6
2 Technical data
2.1 Data ....................................................................................... 7
2.2 Approvals and certificates ................................................ 10
2.3 Dimensions ......................................................................... 11
Contents

Safety information

Please read this manual carefully, and also take note of country-specific installation standards (e.g. the VDE regulations in Germany) as well as all prevailing safety regulations and acci­dent prevention rules.
For safety and warranty reasons, any internal work on the instruments, apart from that in­volved in normal installation and electrical con­nection, must be carried out only by qualified VEGA personnel.
2 Pressure transmitters D76 and D77

Note Ex area

Please note the approval documents (yellow binder), and especially the included safety data sheet.
Contents
3 Mounting
3.1 Mounting instructions ......................................................... 13
3.2 Compensation of the atmospheric pressure ................... 13
4 Electrical connection
4.1 Connection instructions ..................................................... 14
4.2 Terminal assignment .......................................................... 15
4.4 Connection examples ........................................................ 16
4.3 Connection to VEGABOX 01 ............................................. 16
5 Setup
5.1 Sensor without adjustment ................................................ 18
5.2 Adjustment with the adjustment insert in the sensor ...... 18
6 Diagnostics
6.1 Maintenance ....................................................................... 20
6.2 Failure rectification ............................................................. 20
7 Instrument modification
7.1 Retrofitting of adjustment insert ........................................ 21
Pressure transmitters D76 and D77 3

1 Product description

Product description

1.1 Function and configuration

The pressure transmitters D76 and D77 are efficient, modular instruments for hydrostatic level measurement. A dry, metallic-capacitive cell or the dry, ceramic-capacitive measuring cell CERTEC element.
The hydrostatic pressure of the product causes a capacitance change via the metallic or ceramic diaphragm. This capacitance change is detected by an ASIC (Application specific integrated circuit) and converted by the integrated sensor electronics into a pres­sure-proportional signal. Precise, high-reso­lution digital processing of measured data ensures excellent technical data.
The sensor is powered by a separate VEGA signal conditioning instrument, a stabilised power supply unit or a PLC (active). After adjustment, a standardised 4 … 20 mA cur­rent signal is available.
To improve reliability, the functionality of im­portant electronic components is constantly checked, and internal parameters such as sensor value, temperature and operating voltage are closely monitored.
Output signal
An analogue level or pressure-proportional signal current is used as output signal:
- 5 … 19 mA not standardised (in conjunc­tion with VEGA signal conditioning instru­ment)
- 4 … 20 mA standardised
®
is used as pressure sensor
Adjustment
The sensors are available with or without integrated adjustment functions:
- without adjustment (version A, adjustment via signal conditioning instrument)
- without adjustment (version C)
- with integrated adjustment (version D)
- with adjustment from external indicating instrument (version E)

1.2 Types and versions

Suspension pressure transmitter D76 with CERTEC
Features
- Compact instrument with integrated elec­tronics
- Diameter of the transmitter 32 mm
- Connection housing in protection IP 66/IP 67/IP 68
- Electronics as two-wire system 4 … 20 mA
- Power supply 12 … 36 V
- Adjustment/indication in separate housing VEGADIS 12 possible
Applications
- Level and gauge measurements in water sewage water, flumes, basins, deep wells, vessels and tanks
Suspension pressure transmitter D77 with Duratherm 600 diaphragm
Features
- Compact instrument with integrated elec­tronics
- Diameter of the transmitter 32 mm
- Connection housing in protection IP 66/ IP 67/IP 68
- Electronics as two-wire system 4 … 20 mA
- Power supply 12 … 36 V
- Adjustment/indication in separate housing VEGADIS 12 possible
Applications
- Level and gauge measurements in water/
sewage water, flumes, basins, deep wells, vessels and tanks
®
4 Pressure transmitters D76 and D77
Product description

1.3 Electronics version without adjustment

Electronics version A: Pressure transmitter for connection to VEGA signal conditioning instruments
VEGAMET
VEGABOX 01
VEGALOG
Electronics version C: Pressure transmitter 4 … 20 mA
VEGABOX 01
VEGAMET
VEGALOG
PLC/DCS
PLC/DCS
Pressure transmitters D76 and D77 5
Product description

1.4 Electronics version with integrated adjustment in connection housing

Electronics version D: Pressure transmitter 4 … 20 mA adjustable Adjustment in connection housing
S
Op
Zt
i
43215
+
-
4...20mA 12V...36V DC
Bedieneinsatz
operating unit
PLC/DCS
VEGABOX 01
S
Op
Zt
i
43215
+
-
4...20mA 12V...36V DC
Bedieneinsatz
operating unit
PLC/DCS

1.5 Electronics for connection to VEGADIS 12

Electronics version E: Pressure transmitter 4 … 20 mA Adjustment in VEGADIS 12
6 Pressure transmitters D76 and D77
VEGADIS 12
DISPLAY
TRANSMITTER
DISPLAY
TRANSMITTER
OPERATE
OPERATE
OPERATE
OPERATE
ti
ti
ZERO
ZERO END
END ZERO
ZERO
POINT
SPAN
POINT
SPAN
VEGADIS 12
DISPLAY
DISPLAY
TRANSMITTER
TRANSMITTER
OPERATE
OPERATE
OPERATE
OPERATE
ti
ti
ZERO
ZERO
END
END ZERO
ZERO
POINT
POINT
SPAN
SPAN
PLC/DCS
PLC/DCS
12
300
600
900
18 24 30 36
Product description

2 Technical data

2.1 Data

Supply and signal current circuit (analogue transmission, 4 … 20 mA)
Power supply 12 … 36 V DC Residual ripple of the power supply no influence at U Output signal
- terminal insert analogue transmission (not standardised) 4 … 20 mA
- adjustment insert 4 … 20 mA (adjustable)
Current limitation approx. 22 mA Fault signal 22 mA Integration time 0 … 10 s (adjustment time from 10 % … 90 %
of measuring range final value)
Average delay time 85 ms Connection cable 2-wire Max. permissible load depending on power supply
see following load diagram
Load in W
< 100 mV
SS
Integrated overvoltage protection (option)
Pressure transmitters D76 and D77 7
Nominal d.c. spark-over voltage
- protective diode 40 V
- gas separator 650 V
Nominal discharge current
- gas separator 20 kA
Supply voltage in V
Product description
Measuring ranges
Nominal meas. range Gauge pressure Low pressure Pressure transmitters
resistance resistance D76 D77 D76 / D77
Gauge pressure 0 … 0.1 bar 10 bar / – -0.1 bar
0 … 0.2 bar 15 bar / – -0.2 bar
0 … 0.4 bar 20 bar / 10 bar -0.4 bar
0 … 1.0 bar 25 bar / 25 bar -1.0 bar
0 … 2.5 bar 35 bar / 25 bar -1.0 bar
0 … 5.0 bar 45 bar / 25 bar -1.0 bar
0 … 10.0 bar 60 bar / 25 bar -1.0 bar
0 … 20.0 bar 90 bar / 25 bar -1.0 bar
Zero -20 % … +95 % of nominal measuring range
adjustable
Span 3.3 % … 120 % of nominal measuring range
adjustable Recommended turn down with accuracy class 0.25 up to 1 : 5
Adjustment elements
Pressure transmitters
- terminal insert without adjustment elements
- adjustment insert 2 keys, 1 rotary switch
Measuring accuracy (similar to DIN 16 086, DIN V 19 259-1 and IEC 770)
Deviation
Reference conditions acc. to IEC 770
- temperature 15°C … 35°C
- moisture 45 % … 75 %
- air pressure 860 mbar … 1060 mbar Determination of characteristics limit point adjustment acc. to DIN 16 086 Characteristics linear Deviation in characteristics Hysteresis
Repeatability
1)
1)
Influence of the ambient temperature in general
Average temperature coefficient of the zero signal
1) 2)
1)
< 0.25 % with accuracy class 0.25
< 0.02 % ceramic measuring cell
< 0.05 % metallic measuring cell
< 0.02 % ceramic measuring cell
< 0.05 % metallic measuring cell
< 0.15 %/10 K with accuracy class 0.25
1)
Relating to the nominal measuring range.
2)
In the compensated temperature range of 0°C … +80°C, reference temperature 20°C.
8 Pressure transmitters D76 and D77
Product description
Long-term stability
Longterm drift of the zero signal
1)
- D76 (ceramic measuring cell) < 0.1 %/year
- D77 (metallic measuring cell) < 0.25 %/year
Other actuating variables
Calibration position upright, diaphragm points downwards Influence of the mounting location
- ceramic measuring cell < 0.2 mbar
- metallic measuring cell < 5.0 mbar Vibration resistance mechanical vibrations with 4 g and
5 … 100 Hz, tested acc. to the regulations of German Lloyd, GL regulation 2
Operating conditions
Ambient conditions
Ambient temperature -40°C … +60°C Storage and transport temperature -40°C … +60°C Product temperature -40°C … +60°C
Protective measures
Transmitter IP 68 Housing
2)
IP 66 or IP 67, IP 68 (by fixed connected PE-cable, cable length min. 5 m)
General data
Connection cables
Cable entry
- in connection housing 2 x M20 x 1.5 (for cable ø 5 … 9 mm)
- external housing VEGABOX 01 2 x M20 x 1.5 (for cable ø 5 … 9 mm) Screw terminals
- terminal, adjustment insert for conductor cross-sections up to 2.5 mm
- external connection housing VEGABOX 01 for conductor cross-sections up to 2.5 mm
1)
Acc. to IEC 770, item 6.1.2 relating to the nominal measuring range.
2)
Use of suitable seal in the PG is necessary for maintaining the housing protection IP 65 or IP 67.
Pressure transmitters D76 and D77 9
2
2
Product description
Materials, wetted parts
Pressure transmitters D76
- transmitter stainless steel 1.4571
- diaphragm ceramic (99.9 % Oxideceramic)
- suspension cable PE-LD cable bushing CSM
- measuring cell seal Viton
Pressure transmitters D77
- transmitter stainless steel 1.4571
- diaphragm Duratherm 600
- suspension cable PE-LD cable bushing CSM
Materials, non-wetted parts
Pressure transmitters D76, D77
- housing Alu (sea-water resistant) and powder-
- straining clamp galvanised steel
- closing screw stainless steel 1.4305
Weight
Basic weight without housing
- D76 approx. 0.7 kg
- D77 approx. 0.7 kg
VEGABOX 01 approx. 400 g Suspension cable approx. 0.1 kg/m
coated, stainless steel 1.4571

2.2 Approvals and certificates

Ex approvals
When using pressure transmitters in Ex areas, the instruments must be suitable and ap­proved for these explosion zones and application areas. Special type approvals are available for the use on ships. The suitability is checked by approval authorities and certified by ap­proval documents. Please note the attached approval documents when using a sensor in Ex areas.
Pressure transmitters D7. Ex are approved for Ex Zone 1.
CE conformity
Pressure transmitters D76 and D77 meet the protective regulations of EMC (89/336/EWG) and NSR (73/23/EWG). Conformity has been judged acc. to the following standards: EMC Emission EN 50 081 - 1: 1992
NSR EN 61 010: 1993
NAMUR regulations
Full compliance with the NAMUR regulations NE 21, May 1993.
10 Pressure transmitters D76 and D77
Susceptibility EN 50 082 - 2: 1995
Product description

2.3 Dimensions

C1
52
1
1
R
49
175
41
14
25
X4 A4 V4
ø 8
SW 30
G 1½ A
A1, A2, B1, B2 C3 D3
66
ø 76
77
ø 41,6 ø 41,6 ø 41,6
39
20
77
SW 60 SW 60
G 1½ A
100
39
20
G4 N4
139
1½" NPT
D77: 247
D76: 230
ø 32
D77: 267
D76: 250
ø 32
D77: 285
D76: 268
ø 36
XVP
Pressure transmitters D76 and D77 11
VEGABOX 01 (connection housing with breather facility)
85
108
118
135
38 72
ø 5
Zum Anschluss an
For connection to
Druckmessumformer mit
pressure transmitters with
analogem Ausgangsignal
analog output
-
+
-
TRANSMITTER
VEGABOX 01
+
M20 x 1.5 (cable ø 5 … 9 mm)
with optional protective cover
Product description
72100
139
12 Pressure transmitters D76 and D77
130
Mounting

3 Mounting

3.1 Mounting instructions

Cable entry
The pressure transmitters can be mounted in any position. Cable entries must point down­wards to avoid moisture ingress. For this purpose, the housing can be rotated by 330° in relation to the mounting part.
A seal, appropriate for connection, must be used for mounting. This seal is either sup­plied with the pressure transmitter or must be provided by the customer.
3.2 Compensation of the atmos­pheric pressure
On instruments for gauge pressure meas­urement, the atmospheric pressure is com­pensated in different ways, depending on the pressure transmitter version.
Pressure transmitters with housing
- via an integrated breather facility below the
cable entry (PTFE insert IP 66
- via the capillary tubes of the special ca-
2)
ble
, used with the pressure transmitter,
protection IP 67
Pressure transmitters with direct cable outlet
- via the capillary tubes of the connected
special cable
2)
, protection IP 68
External housing VEGABOX 01
We recommend leading the special cable to the external housing VEGABOX 01 (acces­sory) and carrying out the pressure compen­sation via the integrated breather facility.
Keep the following instructions in mind:
- the same atmospheric pressure as on the
pressure transmitter must also be present on the external housing VEGABOX 01
- the pressure compensation must be made
in a dry environment
- for vertical wall mounting, the cable entries
must point downwards to avoid moisture ingress.
1)
), protection
1)
Air permeable and moisture-blocking
2)
Cable length 5 m (supplied cable)
Pressure transmitters D76 and D77 13

4 Electrical connection

Electrical connection

4.1 Connection instructions

The electronics in the pressure transmitter requires a supply voltage of 12 … 36 V DC. It is provided by two-wire technology, i.e. sup­ply voltage and measuring signal are trans­mitted via the same two-wire connection cable.
The supply voltage is provided via a power supply unit, e.g.:
- power supply unit VEGASTAB 690
- processing unit with integrated DC current source (e.g. active PLC input)
- VEGAMET, VEGALOG or VEGADIS 371
Make sure that the supply voltage is reliably separated from the mains circuits acc. to DIN VDE 0106, part 101. VEGA instruments meet this requirement and protection class III is therefore ensured.
The terminal voltage on the transmitter de­pends on the following factors:
- output voltage U under nominal load.
- electrical resistance of the connected in­struments in the circuit.
Note the following instructions for electrical connection:
- Connection must be made according to the specific installation standards (e.g. in Ger­many acc. to the VDE regulations).
- Terminal voltage must not exceed 36 V, to avoid damage to the electronics.
- Electrical connection must have a pre­ventative measure against inadvertent polarity reversal.
- The pressure transmitter can be connected with standard two-wire cable.
- Screened cable is recommended, if strong electromagnetic interference is to be ex­pected. The screening must be grounded at both ends. Please note the installation regulations for mounting in Ex areas.
of the power supply
H
- If overvoltages are expected, we recom­mend pressure transmitters with integrated overvoltage arrester or the installation of VEGA overvoltage arresters.
- In the cable connection, a seal must be used which fits the cable.
Safety information for Ex applications
As a rule, do all work in the complete ab­sence of line voltage. Always switch off the power supply before you carry out connect­ing work on the sensors. Protect yourself and the instruments.
Qualified personnel
Instruments which are operated in Ex areas, must be connected only by qualified person­nel. The qualified personnel must observe and understand the installation regulations and the attached type approval and con­formity certificates.
In hazardous areas, the required regulations and conformity and type approval certificates of the sensors and separators or safety barriers must be observed (e.g. DIN VDE
0165). Sensors used in Ex areas must be
operated only on intrinsically safe circuits. The permissible electrical values are stated in the type approval or conformity certificate.
Intrinsically safe circuits with more than one active instrument (delivering electrical en-
14 Pressure transmitters D76 and D77
Electrical connection
ergy) must not connected in series. The special installation regulations (DIN VDE
0165) must be observed.
Pressure transmitters in certain versions are equipped with a warning label, informing of measures to be taken to avoid electrostatic discharge. Keep the contents of the warning label in mind.
Connection cable
Make sure that the connection cable is speci­fied for the expected operating temperatures in your systems. The cable must have an outer diameter of 5 … 9 mm. Otherwise the seal effect of the cable connection will not be ensured.
Cables for intrinsically safe circuits must be marked with a blue colour and must not be used for other circuits.
Direct cable outlet

4.2 Terminal assignment

Screen
Breather capillaries
Suspension cable
12 36 V DC
br
+
for supply or to the process-
bl
ing system (4 20 mA)
-
ge
only used in conjunction with VEGADIS 12, if not used, connect to minus
Electronics version A
5 19 mA output signal for connection to VEGA signal conditioning instruments
Zum Anschluss an
For connection to
VEGA-Auswertgeräte
VEGA-signal conditioning instruments
51234
-
+
Klemmeinsatz
terminal
-
Control instrument (5 19 mA measure­ment)
+
Supply or for evaluation
+
of VEGAMET signal conditioning instrument
-
12 36 V DC
Electronics version C
4 20 mA output signal
4-20mA
-
+
4...20mA 12V...36V DC
Klemmeinsatz
terminal
51234
+
Control instrument 4 20 mA
-
-
Power supply 12 36 V DC
+
Electronics version D
4 20 mA output signal with integrated adjustment
S
Zt
+
-
4...20mA 12V...36V DC
Bedieneinsatz
operating unit
Op
i
43215
-
Control instrument 4 20 mA
+
-
Power supply 12 36 V DC
+
Electronics version E
4 20 mA output signal with operatability from VEGADIS 12
Zum Anschluss an
For connetction to
VEGADIS 12
51234
-
+
12V...36V DC
Klemmeinsatz
terminal
Terminal assignment
Ground, cable screen 1 Power supply [+] 2 Power supply [–] 3 Control instrument [–] / VEGADIS 12 4 not assigned, connect via wire bridge 5 not assigned, connect via wire bridge
ge
for indicating instru-
-
ment VEGADIS 12
+
Pressure transmitters D76 and D77 15

4.3 Connection to VEGABOX 01

Pressure transmitters with direct cable outlet
Screen
Pressure transmitters with terminal insert in housing
Breather capillaries
Suspension cable
br
+
bl
-
ge
Zum Anschluss an
For connection to
Druckmessumformer mit
pressure transmitters with
analogem Ausgangssignal
analog output
1
231011 12
TRANSMITTER
VEGABOX 01
-
+
-
+
Electrical connection
For supply or to the
+
processing system
-
(4 20 mA, 12 36 V DC)
4-20mA
-
+
4...20mA 12V...36V DC
Klemmeinsatz
terminal
+
-
51234
+
Control instrument
-
(4 20 mA measure­ment)

4.4 Connection examples

The following connection examples are valid for direct connection to the terminals of the pres­sure transmitter. When using the external connection housing, the connection is made to the respective terminals of the housing.
Powered by a power supply unit
Processing via an indicating instrument.
Ammeter for local control
analogue / digital indicat-
+ - -
1 2 3
Pressure transmitter terminals
U
K
ing instrument
U
4 20 mA
External energy source
A
-
U
H
~
+
16 Pressure transmitters D76 and D77
Electrical connection
Powered by a VEGA signal conditioning instrument
Standard wiring for nonstandardized output.
Ammeter for local control
+ - -
1 2 3
Pressure transmitter terminals
U
K
Analogue transmission, not standardised
0/4 20 mA
U
H
DISBUS
!
Powered by a PLC with active input circuit
Processing via PLC.
Ammeter for local control
+ - -
Pressure transmitter terminals
PLC
1 2 3
U
K
4 20 mA
U
-
H
+
Note:
An ammeter for local control of the output current can be connected to terminals 1 and 3. This measurement can be carried out during operation, without interrupting the supply cable.
Pressure transmitters D76 and D77 17

5 Setup

Setup

5.1 Sensor without adjustment

Sensors with electronics version A and C have no adjustment possibility and are per­manently adjusted to the stated measuring range.

5.2 Adjustment with the adjustment insert in the sensor

Sensors with electronics version D are equipped with a 2-key adjustment insert.
1
2
3
S
Zti
+
Op
-
Procedure
Select the required function with the rotary switch.
With the "+ and "–“ key you modify the signal current to the required values or set the suitable integration time.
Then, you set the rotary switch to position "OPERATE. The set values are transferred to the EEPROM memory and remain there even in case of voltage failure.
Adjustment
For adjustment of zero and span, first of all connect terminals 1 and 3 to an ammeter. The measured value is identical to the output current.
First of all adjust zero (empty vessel)
Set the rotary switch to "zero. Empty the vessel.
Adjust a current of 4 mA by pushing the "+ and "–“ keys.
The adjustment range of zero can be be­tween -20 % and +95 % of the nominal meas­uring range.
12345
+-
4...20mA
12...36 V DC
Then adjust span (full vessel)
Set the rotary switch to "span. Completely fill the vessel.
Adjust a current of 20 mA by pushing the "+ and "–“ keys.
The adjustment range of span can be be­tween 3.3 % and 120 % of the nominal meas-
1 Reduce value 2 Rotary switch 3 Increase value
uring range.
With the rotary switch you can select four switch positions: S - Span (pressure measuring range) Z - Zero (zero adjustment) ti - Time (integration time) Op - Operate (operating status)
18 Pressure transmitters D76 and D77
Setup
Adjustment information:
- A modification of zero does not influence the adjusted span.
- It is also possible to adjust currents for partial fillings, e.g. 8 mA for 25 % and 16 mA for 75 %. Then the electronics auto­matically calculates the current values for 0 % and 100 % (only possible with a differ­ence ³ 3.3 %).
- If the current values react to the key press­ing with a time delay, there can be two reasons:
- the last adjustment was carried out with a
level deviating considerably from the actual level.
Integration time
For damping level fluctuations, an integration time ti of 0 10 sec. can be adjusted.
Adjust integration time
Set rotary switch to "ti“.
By pressing the "- key 10 times make sure
that the integration time is set to 0 sec.
Per 1 sec. requested integration time, the "+ key has to be pushed once.
The integration time is the time required by the current output signal to reach 90 % of the actual level after a sudden change of the level.
Pressure transmitters D76 and D77 19

6 Diagnostics

Diagnostics

6.1 Maintenance

Pressure transmitters D76 and D77 are main­tenance-free.

6.2 Failure rectification

Due to continuous self-monitoring, series D70 pressure transmitters offer maximum reliabil­ity. However, should failures occur, check the following before removing the pressure transmitter:
- the atmospheric pressure compensation,
- the electrical connections.
Checking atmospheric pressure com­pensation
First open the cover of the housing, in which the atmospheric breather facility is located. The displayed measured value must not change. However, if the displayed value changes, compensation of the atmospheric pressure is not ensured, which will lead to distortion of the measured value. Therefore check:
- the breather facility on the housing
- VEGADIS 12 or VEGABOX 01
- the capillary tubes in the special cable.
Note:
There must always be the same atmospheric pressure on the breather facility as in the open vessel.
Checking electrical connections
Pressure transmitter terminals
1 2 3
mA
Current
Voltage Current
V
mA
External energy source
-
~
+
Voltage
- the terminal voltage on the pressure trans­mitters must be at least 12 V DC
Current
Current value Condition
3.8 20.5 mA standard range for the output
0 mA signal cable interrupted
< 3.6 mA sensor electronics or pressure
22 mA sensor electronics or pressure
Note for Ex applications
Deviating from above regulation, here termi­nals 1 and 3 (on VEGADIS 12 terminals 10 and 12) are used only for brief connection to a certified active, floating measuring instru­ment (max. value: 470 mW) or an individual passive, floating ammeter. When connecting, the regulations for wiring of intrinsically safe circuits (measuring instrument, supply and signal circuit) have to be observed.
current
sensor element defective
sensor element defective
20 Pressure transmitters D76 and D77
Instrument modification

7 Instrument modification

7.1 Retrofitting of adjustment insert

Such a retrofitting can be necessary, e.g. if you want to adapt a pressure transmitter to different measurement conditions.
Remove existing terminal insert
1 Disconnect pressure transmitter from
power supply.
2 Unscrew cover of the connection hous-
ing. 3 Remove cover. 4 Pull out connection cables from the termi-
nal insert. 5 Loosen the three screws on the terminal
insert. 6 Remove terminal insert and plug connec-
tion (carefully bend the locking clip to-
ward the centre of the housing).
Fitting new adjustment insert
7 Push plug connection into the adjustment
insert (must snap in). 8 Place adjustment insert in the housing
and fasten with three screws. 9 Reconnect the connection cables to the
terminals. 10 Fasten the cover. 11 Reconnect the pressure transmitter to
power supply.
For setup of pressure transmitters, see chapter "5 Setup“.
Pressure transmitters D76 and D77 21
Notes
22 Pressure transmitters D76 and D77
Notes
Pressure transmitters D76 and D77 23
VEGA Grieshaber KG Am Hohenstein 113 D-77761 Schiltach Phone (0 78 36) 50 - 0 Fax (0 78 36) 50 - 201 e-mail info@vega-g.de
ISO 9001
The statements on types, application, use and operating conditions of the sensors and processing systems correspond to the latest infor­mation at the time of printing.
Technical data subject to alterations
2.22 064 / March 2000
Loading...