This manual and labels on the inverter provide very important information that you should bear in
mind to use the inverter properly and safely, and also to avoid injury to yourself and other people and
damage to property.
Read the safety precautions in the instruction manual for your inverter before reading this manual and
strictly follow the safety instructions given.
E6581222
Notice
♦ Insert an electromagnetic contactor between the inverter and the power supply so that
the machine can be stopped without fail from an external controller in case of an emergency.
♦ Do not write the same parameter to the EEPROM more than 10,000 times. The life time
of EEPROM is approximately 10,000 times.(Some parameters are not limited, please
refer to the “9.Parameter data “)
When using the TOSHIBA inverter protocol and the data does not need to be records,
use P command (the data is written only to RAM).
♦ About the handling of the inverter, please follow the instruction manual of the inverter.
Reference
Inverter instruction
manual
Section 4.2
“Commands”
1
E6581222
Contents
1.General outlines of the communications function........................................................................................................ 3
4.1. Data transmission formats.................................................................................................................................. 8
4.1.1. Data transmission formats used in ASCII mode ....................................................................................... 8
4.1.2. Data transmission formats used in binary mode ..................................................................................... 11
4.1.3. Transmission Format of Block Communication....................................................................................... 14
8.Commands and monitoring from the computer......................................................................................................... 44
8.1. Communication commands (commands from the computer) ........................................................................... 44
8.2. Monitoring from the computer........................................................................................................................... 47
8.3. Control of input/output signals from communication......................................................................................... 53
8.4. Utilizing panel (LEDs and keys) by communication.......................................................................................... 56
8.4.1. LED setting by communication................................................................................................................ 56
8.4.2. Key utilization by communication ............................................................................................................ 59
9.Parameter data ......................................................................................................................................................... 60
Appendix 1 Table of data codes........................................................................................................................................ 63
Appendix 2 Response time ............................................................................................................................................... 64
Appendix 3 Compatibility with the communications function of the VF-S9 ........................................................................ 65
1. General outlines of the communications function
This manual explains the serial communications interface function provided for the TOSVERT VFS11 series of industrial inverters.
The TOSVERT VF-S11 series of inverters can be connected to a computer or a controller (hereinafter referred to as the computer) for data communications via RS232C converter (RS2001Z) or
RS485 converter (RS4001Z, RS4002Z, RS4003Z). By writing computer programs, you can monitor
the operating status of the inverter, control its operation in various ways from the computer, and
change and store parameter settings on storage devices.
The communication protocol is preparing the TOSHIBA Inverter Protocol and the MODBUS-RTU
protocol. Please choose selection of a protocol with a communication protocol selection parameter
().
<Computer link>
By preparing the program (explained later), the following information can be exchanged between the
computer (host) and the inverter.
• Monitoring function (used to monitor the operating status of the inverter: Output frequency, current, voltage, etc.)
• Command function (used to issue run, stop and other commands to the inverter)
• Parameter function (used to set parameters and read their settings)
E6581222
<Inter-drive communication function>
Master inverter sends the data, that is selected by the parameter, to all the slave inverters on the
same network. This function allows a network construction in which a simple synchronous or proportional operation is possible among plural inverters (without the host computer).
As for data communications codes, the TOSVERT VF-S11 series of inverters support the binary
(HEX) code, in addition to the JIS (ASCII) code. The communications function is designed on the assumption that the JIS (ASCII) code is used for communications between the inverter and the personal computer, and the binary (HEX) code for communications between the inverter and the microcomputer built into the controller. A communication number is used to access the desired data item.
* The smallest unit of information that computers handle is called a “bit (binary digit),” which repre-
sents the two numbers in the binary system: 1 or 0. A group of 16 bits is referred to as a “word,”
which is the basic unit of information the VF-S11 series of inverters use for data communications.
One word can handle data items of 0 to FFFFH in hexadecimal notation (or 0 to 65535 in decimal
notation).
BIT15BIT8BIT7BIT0
1 bit
1 word
3
2. Data transmission specifications
ItemsSpecifications
Transmission schemeHalf-duplex
Synchronization schemeStart-stop synchronization
Communication baud rate1200/2400/4800/9600*/19200 bps (selectable using a parameter)
Communication protocolTOSHIBA Inverter Protocol * / MODBUS-RTU
Character transmission<ASCII mode> JIS X 0201 8-bit (ASCII)
<Binary mode, MODBUS-RTU> Binary codes fixed to 8 bits
Stop bit lengthReceived by inverter: 1 bit, Sent by inverter: 2 bits
Error detecting schemeParity *2: Even */odd/non parity (selectable using a parameter) *1,
checksum(Toshiba inverter protocol), CRC(MODBUS-RTU)
Character transmission
11-bit characters *1 (Stop bit=1, with parity)
format
Order of bit transmissionLow-order bits transmitted first
Frame lengthVariable (to a maximum of 17 bytes)
*1: Changes to the communication baud rate and to the parity setting do not take effect until the in-
verter is turned back on or reset.
*3
*1
E6581222
*: Standard
default setting
*2: JIS-X-0201 (ANSI)-compliant 8-bit codes are used for all messages transmitted in ASCII mode
and vertical (even) parity bits specified by JIS-X-5001 are added to them. These even parity bits
can be changed to odd parity bits by changing the parameter setting (a change to the parameter
setting does not take effect until the inverter has been reset.)
*3: Here are the default character transmission formats. (Standard default setting)
Characters received: 11 bits (1 start bit + 8 bits + 1 parity bit + 1 stop bit) ... Standard default setting
START
BITBIT0BIT1BIT2BIT3BIT4BIT5BIT6BIT7
PARITY
BIT
STOP
BIT
The inverter receives one stop bit.
(The computer can be set so as to send 1, 1.5 or 2 stop bits.)
Characters sent: 12 bits (1 start bit + 8 bits + 1 parity bit + 2 stop bits) ... Standard default setting
START
BITBIT0BIT1BIT2BIT3BIT4BIT5BIT6BIT7
PARITY
BIT
STOP
BIT
STOP
BIT
The inverter sends two stop bits.
(The computer can be set so as to receive 1, 1.5 or 2 stop bits.)
4
3. Communication protocol
This communication protocol supports the TOSHIBA Inverter Protocol and part of MODBUS-RTU
protocol.
Select the desired protocol from in the following communication protocol selection parameters
().
“Parameter Name , Communication Number. 0829”
Data Range: 0, 1 (Initial value: 0)
0: TOSHIBA Inverter Protocol (Includes inter-drive communications)
1: MOUBUS-RTU protocol
* A parameter change is reflected when the inverter is reset, such as in power off.
Note : When using the extension panel (RKP001Z) and the parameter writer (PWU001Z), be certain
to set F829=”0” : TOSHIBA inverter protocol.
E6581222
5
4. TOSHIBA Inverter Protocol
Select “TOSHIBA Inverter Protocol” (=) in the communication protocol selection parame-
ters. “TOSHIBA Inverter Protocol” (=) is set for initial communication protocol selection of
shipment setting. (See “3. Communication protocol.”)
■ Exchange of data between the computer and the inverter
In communications between the computer and the VF-S11 (hereinafter referred to as the inverter),
the inverter is always placed in wait states and acts as a slave that operates on a request from the
computer. A start code is used to automatically identify the mode in which data is transmitted: ASCII
mode or binary mode.
A transmission error will result if the transmission format does not match.
■ ASCII mode
(1) In ASCII mode, the start code is “(”
The inverter rejects all data items entered invalid the “(” If two or more “(” are entered, the “(” entered last will be valid and all “(“ entered before will be ignored. If the “(” is not recognized because of a format error or for any other reason, no error code will be returned since the data is not
recognized at all. In such cases, the inverter regards the data received as a transmission error,
rejects it and goes back into a start code wait state.
E6581222
(2) When an inverter number is added behind the “(” communications will take place only in case of
broadcast communication or if the number matches up with that assigned to the inverters. If not,
the inverter will go back into a start code wait state.
(3) The inverter stops receiving data on receipt of the CR (carriage return) code inserted in the des-
ignated position.
If the size of the data transmitted exceeds the maximum allowable size (17 bytes) or if the CR
code cannot be found in the designated position within 0.5 seconds, the inverter will regard the
data received as a transmission error and go back into a start code wait state.
(4) If no communications take place within the time specified using the timer function, the computer
will regard it as a communication error and trip the inverter. The timer setting is cleared when the
timer is turned on or initialized. For more details, see Section 7.3, “Timer function.”
(5) On executing the command received, the inverter returns data to the computer. For the response
time, see Appendix 2, “Response time.”
6
■ Binary mode
E6581222
(1) In binary mode, the start code is “2FH(/).”
The inverter rejects all data items entered before the “2FH(/).”
If two or more “2FH(/)” are entered, the “2FH(/)” entered last will be judged valid and all “2FH(/)”
entered before will be ignored.
If the “2FH(/)” is not recognized because of a format error or for any other reason, no error code
will be returned since the data is not recognized at all. In such cases, the inverter regards the
data received as a transmission error, rejects it and goes back into a start code wait state.
(2) If an inverter number is added behind the “2FH(/),” communications will take place only in case of
broadcast communication or if the number matches up with that assigned to the inverters. If not,
the inverter will go back into a start code wait state.
(3) The inverter stops receiving data on receipt of a command and the number of bytes of data
specified by the command.
If no command is found in the data received or if the specified number of bytes of data cannot be
received within about 0.5 seconds, the inverter will regard the data received as a transmission error and go back into a start code wait state.
(4) If no communications take place within the time specified using the timer function, the computer
will assume that a communication error has occurred and trip the inverter. The timer function is
disabled when the inverter is turned on or initialized. For details, see Section 7.3, “Timer function.”
■ Note
(5) On executing the command received, the inverter returns data to the computer. For the response
time, see Appendix 2, “Response time.”
Communication is not possible for about one second after the power is supplied to the inverter until
the initial setting is completed. If the control power is shut down due to an instantaneous voltage drop,
communication is temporarily interrupted.
7
4.1. Data transmission formats
■ Note: The term “trip status” used in this manual includes retry waiting status and trip retention status.
4.1.1. Data transmission formats used in ASCII mode
A communication number is used to specify a data item, all data is written in hexadecimal, and JISX-0201 (ASCII (ANSI))-compliant transmission characters are used.
■ Computer → VF-S11
Omissible in one-to-one communicationsFor the W and P commands onlyOmissible
E6581222
"("
(28H)
1. “(“ (1 byte): Start code in ASCII mode
2. INV-NO (2 bytes) : Inverter number (Omissible in one-to-one communications) ... 00 (30H, 30H) to 99 (39H,
3. CMD (1 byte): Command (For details, see the table below.)
4. Communication No.(4 bytes)
5. Data (0 to 4 bytes) : Write data (valid for the W and P commands only)
6. “&” (1 byte): Checksum discrimination code (omissible. When omitting this code, you also need to omit
INV-NO
2 bytes
CMD
1 byte
39h), *(2AH)
The command is executed only when the inverter number matches up with that specified
using a parameter.
(When * is specified in broadcast communications, the inverter number is assumed to
match if all numbers except * match. When * is specified instead of each digit (two-digit
number), all inverters connected are assumed to match.)
If the inverter number does not match or if the inverter number is of one digit, the data will be
judged invalid and no data will be returned.
: Communication number (See 11, “Parameter data.”)
the checksum.)
Communication No.
4 bytes
Checksum area
DATA
0 to 4 bytes
"&"
(26H)
SUM
2 bytes
Omissible
")"
(29H)CR(0DH)
7. Sum (2 bytes): Checksum (omissible)
Add the ASCII-coded value of the last two digits (4 bits/digit) of the sum of a series of bits
(ASCII codes) from the start code to the checksum discrimination code.
Ex.: (R0000&??) CR
28H+52H+30H+30H+30H+30H+26H=160H
The last two digits represent the checksum. = 60
When omitting the checksum, you also need to omit the checksum discrimination code.
8. “)” (1 byte): Stop code (omissible)
9. CR (1 byte): Carriage return code
■ Details of commands and data
CMD (1 byte)Write data (0 to 4 bytes) Hexadecimal number
R (52H): RAM read command
W (57H): RAM/EEPROM write command
P (50H) RAM write command
No data
Write data (0 to FFFF)
Write data (0 to FFFF)
8
■ VF-S11 → computer
At time of broadcast communication, returning of data is not executed, except for the inverters to be
returned, when the inverter number is not matched, and the inverter number has only one character.
This is because there will be a risk of that the returned data may be deformed.
• Data returned when data is processed normally (ASCII mode)
OmissibleOmissible
E6581222
"("
(28H)
1. “(“ (1 byte): Start code in ASCII mode
2. INV-NO (2 bytes) : Inverter number (omitted if it is not found in the data received) ... 00 (30H, 30H) to 99 (39H,
3. CMD (1 byte): Command ... The command is also used for a check when an inverter is tripped.
4. Communication No.(4 bytes) :
INV-NO
2 bytes
CMD
1 byte
39H)
If the inverter number matches up with that specified using a parameter, data will be returned to the computer. In broadcast communications, only the destination inverter (with a number matching up with the smallest effective number) returns data to the computer.
In broadcast communications, no data is returned from any inverters except the inverter
bearing a number that matches up with the smallest effective number.
Ex.: (*2R0000) CR -> (02R00000000) CR)
Under normal conditions... The uppercase letter R, W or P is returned, depending on the
command received: R, W or P command.
When an inverter is tripped... The lowercase letter r, w or p is returned, depending on the
command received: R, W or P command.
(The command received is returned with 20H added to it.)
The communication number received is returned.
Communication No.
4 bytes
Checksum area
Data is returned from the inverter with the number 2 only, but no data is returned from
inverters with the number 12, 22 ....
DATA
0 to 4 bytes
"&"
(26H)
SUM
2 bytes
Omissible
")"
(29H)CR(0DH)
5. Data (0 to 4 bytes) : Data ... The data read in is returned for the R command, while the data received is returned
for the W and P commands. If the data received is composed of less than 4 digits, it will be
converted into 4-digit data and returned.
Ex.: (W123412) CR → (W12340012) CR)
6. “&” (1 byte): Checksum discrimination code (omitted if it is not found in the data received)
7. Sum (2 bytes): Checksum ... Omitted if no checksum discrimination code is found in the data received.
ASCII-coded value of the last two digits (4 bits/digit) of the sum of a series of bits (ASCII
codes) from the start code to the checksum discrimination code.
8. “)” (1 byte): Stop code (omitted if it is not found in the data received)
9. CR (1 byte): Carriage return code
9
• Data returned when data is not processed normally (ASCII mode)
In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type number is returned to the computer in addition to the checksum. At time of broadcast communication of
the binary mode, returning of data is not executed except for the inverter to be returned (inverter
number 00H) and when the inverter number is not matched. This is because there will be a risk that
the returned data may be deformed.
OmissibleOmissible
E6581222
“(“
(28H)
INV-NO
2 bytes
“N” or “n”
(4EH) (6EH)
DATA
4 bytes
"&"
(26H)
SUM
2 bytes
")"
(29H)
CR
(0DH)
Checksum area
Omissible
“(“ (1 byte): Start code in ASCII mode
1) N or n (1 byte) :Communication error command ... This is also used for the checking of inverter trip.
“4EH(N)” for the normal communication and “6EH(n)” during the inverter trip.
Data (4 bytes): Error code (0000~0004)
0000 ... Impossible to execute (Although communication is established normally, the com-
mand cannot be executed because it is to write data into a parameter whose setting cannot be changed during operation (e.g., maximum frequency) or the
EEPROM is faulty.)
0001 ... Data error (The data is outside the specified range or it is composed of too many
digits.)
0002 ... Communication number error (There is no communication number that matches.)
0003 ... Command error (There is no command that matches.)
0004 ... Checksum error (The checksum result differs.)
“)” (1 byte): Stop code ... This code is omitted if it is not found in the data received.
■ Examples:
(N0000&5C)CR... Impossible to execute (e.g., a change of maximum frequency data during opera-
tion)
(N0001&5D)
(N0002&5E)
(N0003&5F)
... Data error (Data is outside the specified range.)
CR
... No communication number (There is no communication number that matches.)
CR
... There is no command that matches. (Commands other than the R, W and P com-
CR
mands)
(Ex.: L, S, G, a, b, m, r, t, w ...)
(N0004&60)
... Checksum error (The checksum result differs.)
CR
No data returned ... Format error or invalid inverter number
(Ex.: A code other than the stop code (“)”) (Ex.: ”}”) is entered in the stop code
position or the CR code was not found within 0.5 sec.)
10
4.1.2. Data transmission formats used in binary mode
A communication number is used to specify a data item, data is written in hexadecimal form, and
data in transmission characters are represented by binary codes (HEX codes).
■ Computer → VF-S11 (binary mode)
Omissible in one-to-one communicationsNo data for the 52H (R) command
E6581222
“/”
(2FH)
1. 2FH (“/”) (1 byte) : Start code in binary mode
2. INV-NO (2 bytes) : Inverter number (Omissible in one-to-one communications) ... 00H to 3FH ,FFH
3. CMD (1 byte): Command (For details, see the table below.)
4. Communication No.(2 bytes)
5. Data (2 bytes): 0000H to FFFFH
INV-NO
1 byte
In case the inverter number is other than FFH (broadcast communication), command is ex-
ecuted only when the inverter number coincides with the one designated with the panel. If
the inverter number is not matched, it will be judged invalid and the data is not returned.
52H (R) command: The size of the data following CMD is fixed to 3 bytes. (Communication
number: 2 bytes, checksum: 1 byte)
57H (W), 50H (P) and 47H (G) commands: The size of the data following CMD is fixed to 5
bytes.
(Communication number: 2 bytes, data: 2 byte, checksum: 1 byte)
Any command other than the above is rejected and no error code is returned.
: Communication number (See 11, “Parameter data.”)
57H (W) and 50H (P) commands: Write data (An area check is performed.)
47H (G) command: Dummy data (e.g., 0000) is needed.
52H (R) command: Any data is judged invalid. (No data should be added.)
CMD
1 byte
Communication No.
2 bytes
Checksum areaNot omissible
DATA
2 bytes
SUM
1 byte
6. Sum (2 bytes): Checksum (not omissible) 00H to FFH
Value of the last two digits (1 byte) of the sum of a series of bits (codes) from the start code
of the data returned to the data (or to the communication number for the 52H (R) command)
Ex.: 2F 52 00 ?? ... 2FH+52H+00H+00H=81H
The last two digits (??) represent the checksum. = 81
No data
Write data (0000H to FFFFH)
Write data (0000H to FFFFH)
Dummy data (0000H to FFFFH)
11
■ VF-S11 → computer (binary mode)
At time of broadcast communication of the binary mode, returning of data is not executed except for
the inverter to be returned (inverter number 00H) and when the inverter number is not matched. This
is because there will be a risk that the returned data may be deformed.
• Data returned when data is processed normally (Binary mode)
Omissible
E6581222
“/”
(2FH)
1. 2FH (“/“) (1 byte) : Start code in binary mode
2. INV-NO (2 bytes) : Inverter number... 00H to 3FH (The inverter number is omitted if it is not found in the data
3. CMD (1 byte): Command...The command is also used for a check when the inverter is tripped.
4. Communication No. (4 bytes)
5. Data (2 bytes): Data ... 0000H to FFFFFH
6. Sum (1 bytes): Checksum (not omissible) 00H to FFH
INV-NO
1 byte
received.)
If the inverter number matches up with that specified from the operation panel, data will be
returned from the inverter. If the inverter number does not match, the data will be invalid and
no data will be returned.
Under normal conditions...52H (R), 47H (G), 57H (W) or 50H (P) is returned, depending on
the command received.
When the inverter is tripped...The lowercase letter 72H (r), 67H (g), 77H (w) or 70H (p) is
returned with 20H added to it, depending on the command received.
: The communication number received is returned.
The data read is returned for the 52H (R) and 47H (G) commands, while the data written is
returned for the 57H (W) and 50H (P) commands.
Value of the last two digits (1 byte) of the sum of a series of bits (codes) from the start code
to the data.
CMD
1 byte
Communication No.
2 bytes
Checksum areaNot omissible
DATA
2 bytes
SUM
1 byte
12
2) Error Processing (Binary mode)
In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type number is returned to the computer in addition to the checksum. At time of broadcast communication of
the binary mode, returning of data is not executed except for the inverter to be returned (inverter
number 00H) and when the inverter number is not matched. This is because there will be a risk that
the returned data may be deformed.
Omissible
(1 byte)(1 byte)
“/”
(2FH)
N or n (1 byte): Communication error command ... This command is also used for a check when the inverter
Data (2 bytes): Error code (0000~0004)
INV-NO
1 byte
is tripped.
“4EH (N)” is returned under normal conditions, while “6EH (n)” is returned when the in-
verter is tripped.
0000 ... Impossible to execute (Although communication is established normally, the com-
0001 ... Data error (The data is outside the specified range or it is composed of too many
0002 ... Communication number error (There is no communication number that matches.)
0004 ... Checksum error (The checksum result differs.)
N or n
(4EH)(6EH)
Checksum areaNot omissible
mand cannot be executed because it is to write data into a parameter whose setting
cannot be changed during operation (e.g., maximum frequency) or the EEPROM is
faulty.)
digits.)
DATA
2 bytes
SUM
1 byte
E6581222
■ Examples:
No code returned ...Command error, format error (failure to receive the specified number of
bytes within 0.5 seconds, or an parity, overrun or framing error) or the
inverter number does not match or an inverter in broadcast communication in the binary mode except for the inverter for data returning (thein-
verter numbered 00H).
2FH, 4EH, 00H, 00H, 7DH ... Impossible to execute (e.g., a change of maximum frequency data
during operation)
2FH, 4EH, 00H, 01H, 7EH ... Data setting error (The data specified falls outside the specified
range.)
2FH, 4EH, 00H, 02H, 7FH ... No communication number (There is no communication number that
matches.)
2FH, 4EH, 00H, 04H, 81H ... Checksum error (The checksum result differs.)
13
4.1.3. Transmission Format of Block Communication
What is block communication?
Data can be written in and read from several data groups set in one communication by setting the type of data desired for communication in the block communication parameters (, , to ) in advance. Block communications can save the communication time.
Data is transmitted hexadecimal using the binary (HEX) code transmission characters. “Computer
→ inverter” is for writing only, while “Inverter → computer” for reply is for reading only.
■ Computer → VF-S11 (Block Communications)
E6581222
Number of writing data groups x 2 bytes
Number of
read
data
groups
Write
data1
High
Write
data1
Low
Write
data2
High
Write
data2
Low
Start
Code
“/”
Omissible
INV-NOCMD
“X”
Num-
ber of
write
data
groups
Checksum Area
1. 2FH(“/”) (1 byte) : Start code of binary mode
2. INV-NO (1 byte) : Inverter number. (Can be omitted in 1:1 communications): 00H to 3FH, FFH
Executed only when the inverter number matches the inverter number. Set on the panel, except in FFH (broadcast communication).
Communication data will be invalidated and data will not be returned either if the inverter
number. Does not match.
3. CMD (1 byte): ‘X’ (Block communication command)
4. Number of write data groups (1 byte)
: Specify the number of data groups to be written (00H to 02H).
If specified outside of the range, data will be treated as a format error and data will not be returned.
5. Number of read data groups (1 byte)
: Specify the number of data groups to be read (00H to 05H).
If specified outside of the range, data will be returned as “Number of read data groups = 0”
when returned by the inverter.
SUM
6. Write data1 (2 bytes)
: Needed when the number of write data groups is larger than 1.
Data to be written to the specified parameter selected by
Dummy data is needed if the number of write data groups is larger than 1 even though(none)
is selected for
7. Write data2 (2 bytes)
: Needed when the number of write data groups is 2.
Data to be written to the specified parameter selected by
Dummy data is needed if the number of write data groups is 2 even though(none) is selected
for
8. SUM (1 byte): Checksum (Cannot be omitted) 00H to FFH
Lower two digits (1 byte) of total sum from start code (SUM value not included)
14
E6581222
■ Block Write 1, 2
Select data, which is desired to be written in block communications, in Block Communication Write
Data 1 and 2 Parameters (, ). This parameter becomes effective when the system
is reset, such as when power is turned off. When the setting is completed, turn off and then on the
power.
No.Block Write DataFor data details, see:
0No selection −
1Command 1 (FA00)“8.1 Command by communication”
2Command 2 (FA20)“8.1 Command by communication”
3Frequency Command Value (FA01)“8.1 Command by communication”
4Terminal Board Output Data (FA50)
5Communication Analog Output (FA51)
* When “No selection” is specified in the parameters, no data will be written even though write data is
specified.
■ Block Read 1 to 5
“8.3 Control of input/put signals from communication”
“8.3 Control of input/put signals from communication”
Select read data, which is desired to be read in block communications, in Block Communication
Read Data 1 and 5 Parameters (to). This parameter becomes effective when
the system is reset, such as when power is turned off. When the setting is completed, turn off and
then on the power.
No.Block Read DataFor data details, see:
0No selection −
1Status 1 (FD01)“8.2 Monitoring from communication”
2Output Frequency (FD00)“8.2 Monitoring from communication”
3Output Current (FE03)“9. Parameter data”
4Output Voltage (FE05)“9. Parameter data”
5Alarm Information (FC91)“8.2 Monitoring from communication”
6PID Feedback Value (FE22)“9. Parameter data”
7Input Terminal Board Monitoring (FD06)
8Output Terminal Board Monitoring (FD07)
9Analog Monitoring VIA (FE35)
10Analog Monitoring VIB (FE36)
* Output current (FE03), output voltage (FE05) and PID feedback value (FE22) will become hold data
during a trip. Otherwise, real-time data appears.
* “0000” will be returned as dummy data,if “0 (No selection)” is selected for the parameter and “read”
is specified.
“8.3 Control of input/put signals from
communication”
“8.3 Control of input/put signals from
communication”
“8.3 Control of input/put signals from
communication”
“8.3 Control of input/put signals from
communication”
15
■ VF-S11 → Computer
At time of broadcast communication of the binary mode, returning of data is not executed except for
the inverter to be returned (inverter number 00H) and when the inverter number is not matched. This
is because there will be a risk that the returned data may be deformed.
1) Normal processing
E6581222
Omissible
Start
Code
“/”
INV
No.
CMD
“Y”
Number
of Read
Data
Groups
Write
Status
Read
data1
high
Read
data1
low
Number of read data groups x 2 bytes
Read
data2
high
Read
data2
low
Read
data3
high
Checksum area
1. 2FH “/” (1 byte):Start code in binary mode
2. INV-NO (1Byte):Inverter number・・・00H to 3FH
If the inverter number matches up with that specified from the operation panel, data will
be returned from the inverter. If the inverter number does not match, the data will be
judged invalid and no data will be returned.
Communication data will be invalidated and data will not be returned either if the inverter number does not match.(Inverter number is considered matched if it is omitted
during reception)
3. CMD(1Byte):‘Y’ (Block communication command [monitoring])
Lowercase letter ‘y’ during an inverter trip, including standing by for retrying and during
a trip.
4. Number of read data groups (1 byte)
: Return the number of data groups to be read (00H to 05H).
5. Write status (1 byte) : Return 00H to 03H.
* Failing to write in the specified parameter in the number of write data groups, set “1” in
the corresponding bit for the parameter failed to write. (See below.)
Read
data3
low
Read
data4
high
Read
data4
low
Read
data5
high
Read
data5
low
SUM
Bit Position76543210
Data Type−
6. Read data1 - 5 (2 bytes)
: Return according to the number of read data groups. “0000H” is returned as dummy
data if “0” is selected as a parameter.
Read data1: Data selected by . Read data2: Data selected by .
Read data3: Data selected by . Read data4: Data selected by .
Read data5: Data selected by .
7.SUM(1Byte): Checksum (Cannot be omitted) 00H to FFH
Lower two digits (1 byte) of total sum from start code of return data to read data.
■ Example
(When set as follows: = (Command 1), = (frequency command value),
2) Error Processing (Binary mode)
In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type number is returned to the computer in addition to the checksum. At time of broadcast communication of
the binary mode, returning of data is not executed except for the inverter to be returned (inverter
number 00H) and when the inverter number is not matched. This is because there will be a risk that
the returned data may be deformed.
Omissible
(1 Byte)(1 Byte)
E6581222
“/”
(2FH)
“N” or “n” (1 byte): Communication error command. Also for check during an inverter trip (includes standingby
for retrying and trip holding). “4EH (N)” when normal, “6EH (n)” during an inverter trip.
0004 : Checksum error (The checksum does not match)
No return : Command error, format error (specified number of bytes is not received in 1sec,
“N” or “n”
(4EH)(6EH)
Checksum AreaNot omissible
or parity error, overrun error or framing error), inverter number mismatch, and
inverter number other than 00H in broadcast communication.
DATA
2 Bytes
SUM
1 Byte
17
4.2. Commands
Here are the communication commands available.
CommandFunction
R command Reads the data with the specified communication number.
W command Writes the data with the specified communication number. (RAM and EEPROM).
P commandWrites the data with the specified communication number. (RAM).
G command
X commandBlock communication (Computer -> Inverter)
Y commandBlock communication (Inverter -> Computer)
E6581222
Reads the data with the specified communication number. (For binary mode only.
Dummy data is required for this command.)
W (57H) (RAM
This command is used to write new data into the parameter specified using it communication number.
It writes data into the RAM and EEPROM. For parameters whose settings cannot be stored in the
EEPROM (e.g., parameter with the communication number FA00), the W (57H) command writes
data into the RAM only. It cannot be used to write data into read-only parameters (e.g., parameter
with the communication number FD?? or FE??).
Each time an attempt to write data is made, the inverter checks if the data falls within the specified
range. If this check reveals that the data falls outside the specified range, the inverter will reject it and
return an error code.
- Ex.: Setting the deceleration time (communication number: 0010) to 10 sec.
<ASCII mode>
<Binary mode>
♦ Do not write the same parameter to the EEPROM more than 10,000 times. The life time of EEPROM is
approximately 10,000 times.(Some parameters are not limited, please refer to the “9.Parameter data “)
The lifetime of EEPROM is approximately 10,000 times. When using the TOSHIBA inverter protocol and
the data does not need to be records, use P command (the data is written only to RAM).
■ Explanation of terms
*1: The RAM is used to temporarily store inverter operation data. Data stored in the RAM is cleared
*2: The EEPROM is used to store inverter operation parameter settings, and so on. Data stored in
when the inverter is turned off, and data stored in the EEPROM is copied to the RAM when the
inverter is turned back on.
the EEPROM is retained even after the power is turned off, and it is copied to the RAM when the
inverter is turned on or reset.
18
E6581222
P (50H) (RAM
*1
write)
This command is used to rewrite data into the parameter specified using a communication number. It
writes data into the RAM only. It cannot be used to write data into any read-only parameters. Each
time an attempt to write data is made the inverter checks whether the data falls within the specified
range. If this check reveals that the data falls outside the range, the inverter will reject it and return an
error code.
- Ex.: Entering the emergency stop command (communication number: FA00) from the computer
<ASCII mode>
Computer →
2F 50 FA 00 90 00 092F 50 FA 00 90 00 09
R (52H) (Data read)
This command is used to read the setting of the parameter specified using a communication number.
(When multiple inverters are operated in binary mode via RS485 converter connected to a two-wire
line, the execution of the R command could result in a communication error. To avoid this, use the G
command in binary mode when inverters are connected to a two-wire line.)
- Ex.: Monitoring the electric current (communication number: FE03)
<ASCII mode>
When multiple inverters are operated in binary mode via RS485 converter connected to a two-wire line, use
the G command to read data.
G (47H) (Data read)
This command is used to read the parameter data specified using a communication number.
To send this command to an inverter with two-wire type RS485 network, 2bytes of dummy data are
needed. This command is available only in binary mode.
- Ex.: Monitoring the electric current (communication number: FE03)
Computer → InverterInverter
2F 47 FE 03 00 00 772F 47 FE 03 07 7B F9
* In this example, the data 00H sent from the computer to the inverter is dummy data.
Notice
→ Computer
19
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.