This manual and labels on the inverter provide very important information that you should bear in
mind to use the inverter properly and safely, and also to avoid injury to yourself and other people and
damage to property.
Read the safety precautions in the instruction manual for your inverter before reading this manual and
strictly follow the safety instructions given.
E6581222
Notice
♦ Insert an electromagnetic contactor between the inverter and the power supply so that
the machine can be stopped without fail from an external controller in case of an emergency.
♦ Do not write the same parameter to the EEPROM more than 10,000 times. The life time
of EEPROM is approximately 10,000 times.(Some parameters are not limited, please
refer to the “9.Parameter data “)
When using the TOSHIBA inverter protocol and the data does not need to be records,
use P command (the data is written only to RAM).
♦ About the handling of the inverter, please follow the instruction manual of the inverter.
Reference
Inverter instruction
manual
Section 4.2
“Commands”
1
Page 4
E6581222
Contents
1.General outlines of the communications function........................................................................................................ 3
4.1. Data transmission formats.................................................................................................................................. 8
4.1.1. Data transmission formats used in ASCII mode ....................................................................................... 8
4.1.2. Data transmission formats used in binary mode ..................................................................................... 11
4.1.3. Transmission Format of Block Communication....................................................................................... 14
8.Commands and monitoring from the computer......................................................................................................... 44
8.1. Communication commands (commands from the computer) ........................................................................... 44
8.2. Monitoring from the computer........................................................................................................................... 47
8.3. Control of input/output signals from communication......................................................................................... 53
8.4. Utilizing panel (LEDs and keys) by communication.......................................................................................... 56
8.4.1. LED setting by communication................................................................................................................ 56
8.4.2. Key utilization by communication ............................................................................................................ 59
9.Parameter data ......................................................................................................................................................... 60
Appendix 1 Table of data codes........................................................................................................................................ 63
Appendix 2 Response time ............................................................................................................................................... 64
Appendix 3 Compatibility with the communications function of the VF-S9 ........................................................................ 65
1. General outlines of the communications function
This manual explains the serial communications interface function provided for the TOSVERT VFS11 series of industrial inverters.
The TOSVERT VF-S11 series of inverters can be connected to a computer or a controller (hereinafter referred to as the computer) for data communications via RS232C converter (RS2001Z) or
RS485 converter (RS4001Z, RS4002Z, RS4003Z). By writing computer programs, you can monitor
the operating status of the inverter, control its operation in various ways from the computer, and
change and store parameter settings on storage devices.
The communication protocol is preparing the TOSHIBA Inverter Protocol and the MODBUS-RTU
protocol. Please choose selection of a protocol with a communication protocol selection parameter
().
<Computer link>
By preparing the program (explained later), the following information can be exchanged between the
computer (host) and the inverter.
• Monitoring function (used to monitor the operating status of the inverter: Output frequency, current, voltage, etc.)
• Command function (used to issue run, stop and other commands to the inverter)
• Parameter function (used to set parameters and read their settings)
E6581222
<Inter-drive communication function>
Master inverter sends the data, that is selected by the parameter, to all the slave inverters on the
same network. This function allows a network construction in which a simple synchronous or proportional operation is possible among plural inverters (without the host computer).
As for data communications codes, the TOSVERT VF-S11 series of inverters support the binary
(HEX) code, in addition to the JIS (ASCII) code. The communications function is designed on the assumption that the JIS (ASCII) code is used for communications between the inverter and the personal computer, and the binary (HEX) code for communications between the inverter and the microcomputer built into the controller. A communication number is used to access the desired data item.
* The smallest unit of information that computers handle is called a “bit (binary digit),” which repre-
sents the two numbers in the binary system: 1 or 0. A group of 16 bits is referred to as a “word,”
which is the basic unit of information the VF-S11 series of inverters use for data communications.
One word can handle data items of 0 to FFFFH in hexadecimal notation (or 0 to 65535 in decimal
notation).
BIT15BIT8BIT7BIT0
1 bit
1 word
3
Page 6
2. Data transmission specifications
ItemsSpecifications
Transmission schemeHalf-duplex
Synchronization schemeStart-stop synchronization
Communication baud rate1200/2400/4800/9600*/19200 bps (selectable using a parameter)
Communication protocolTOSHIBA Inverter Protocol * / MODBUS-RTU
Character transmission<ASCII mode> JIS X 0201 8-bit (ASCII)
<Binary mode, MODBUS-RTU> Binary codes fixed to 8 bits
Stop bit lengthReceived by inverter: 1 bit, Sent by inverter: 2 bits
Error detecting schemeParity *2: Even */odd/non parity (selectable using a parameter) *1,
checksum(Toshiba inverter protocol), CRC(MODBUS-RTU)
Character transmission
11-bit characters *1 (Stop bit=1, with parity)
format
Order of bit transmissionLow-order bits transmitted first
Frame lengthVariable (to a maximum of 17 bytes)
*1: Changes to the communication baud rate and to the parity setting do not take effect until the in-
verter is turned back on or reset.
*3
*1
E6581222
*: Standard
default setting
*2: JIS-X-0201 (ANSI)-compliant 8-bit codes are used for all messages transmitted in ASCII mode
and vertical (even) parity bits specified by JIS-X-5001 are added to them. These even parity bits
can be changed to odd parity bits by changing the parameter setting (a change to the parameter
setting does not take effect until the inverter has been reset.)
*3: Here are the default character transmission formats. (Standard default setting)
Characters received: 11 bits (1 start bit + 8 bits + 1 parity bit + 1 stop bit) ... Standard default setting
START
BITBIT0BIT1BIT2BIT3BIT4BIT5BIT6BIT7
PARITY
BIT
STOP
BIT
The inverter receives one stop bit.
(The computer can be set so as to send 1, 1.5 or 2 stop bits.)
Characters sent: 12 bits (1 start bit + 8 bits + 1 parity bit + 2 stop bits) ... Standard default setting
START
BITBIT0BIT1BIT2BIT3BIT4BIT5BIT6BIT7
PARITY
BIT
STOP
BIT
STOP
BIT
The inverter sends two stop bits.
(The computer can be set so as to receive 1, 1.5 or 2 stop bits.)
4
Page 7
3. Communication protocol
This communication protocol supports the TOSHIBA Inverter Protocol and part of MODBUS-RTU
protocol.
Select the desired protocol from in the following communication protocol selection parameters
().
“Parameter Name , Communication Number. 0829”
Data Range: 0, 1 (Initial value: 0)
0: TOSHIBA Inverter Protocol (Includes inter-drive communications)
1: MOUBUS-RTU protocol
* A parameter change is reflected when the inverter is reset, such as in power off.
Note : When using the extension panel (RKP001Z) and the parameter writer (PWU001Z), be certain
to set F829=”0” : TOSHIBA inverter protocol.
E6581222
5
Page 8
4. TOSHIBA Inverter Protocol
Select “TOSHIBA Inverter Protocol” (=) in the communication protocol selection parame-
ters. “TOSHIBA Inverter Protocol” (=) is set for initial communication protocol selection of
shipment setting. (See “3. Communication protocol.”)
■ Exchange of data between the computer and the inverter
In communications between the computer and the VF-S11 (hereinafter referred to as the inverter),
the inverter is always placed in wait states and acts as a slave that operates on a request from the
computer. A start code is used to automatically identify the mode in which data is transmitted: ASCII
mode or binary mode.
A transmission error will result if the transmission format does not match.
■ ASCII mode
(1) In ASCII mode, the start code is “(”
The inverter rejects all data items entered invalid the “(” If two or more “(” are entered, the “(” entered last will be valid and all “(“ entered before will be ignored. If the “(” is not recognized because of a format error or for any other reason, no error code will be returned since the data is not
recognized at all. In such cases, the inverter regards the data received as a transmission error,
rejects it and goes back into a start code wait state.
E6581222
(2) When an inverter number is added behind the “(” communications will take place only in case of
broadcast communication or if the number matches up with that assigned to the inverters. If not,
the inverter will go back into a start code wait state.
(3) The inverter stops receiving data on receipt of the CR (carriage return) code inserted in the des-
ignated position.
If the size of the data transmitted exceeds the maximum allowable size (17 bytes) or if the CR
code cannot be found in the designated position within 0.5 seconds, the inverter will regard the
data received as a transmission error and go back into a start code wait state.
(4) If no communications take place within the time specified using the timer function, the computer
will regard it as a communication error and trip the inverter. The timer setting is cleared when the
timer is turned on or initialized. For more details, see Section 7.3, “Timer function.”
(5) On executing the command received, the inverter returns data to the computer. For the response
time, see Appendix 2, “Response time.”
6
Page 9
■ Binary mode
E6581222
(1) In binary mode, the start code is “2FH(/).”
The inverter rejects all data items entered before the “2FH(/).”
If two or more “2FH(/)” are entered, the “2FH(/)” entered last will be judged valid and all “2FH(/)”
entered before will be ignored.
If the “2FH(/)” is not recognized because of a format error or for any other reason, no error code
will be returned since the data is not recognized at all. In such cases, the inverter regards the
data received as a transmission error, rejects it and goes back into a start code wait state.
(2) If an inverter number is added behind the “2FH(/),” communications will take place only in case of
broadcast communication or if the number matches up with that assigned to the inverters. If not,
the inverter will go back into a start code wait state.
(3) The inverter stops receiving data on receipt of a command and the number of bytes of data
specified by the command.
If no command is found in the data received or if the specified number of bytes of data cannot be
received within about 0.5 seconds, the inverter will regard the data received as a transmission error and go back into a start code wait state.
(4) If no communications take place within the time specified using the timer function, the computer
will assume that a communication error has occurred and trip the inverter. The timer function is
disabled when the inverter is turned on or initialized. For details, see Section 7.3, “Timer function.”
■ Note
(5) On executing the command received, the inverter returns data to the computer. For the response
time, see Appendix 2, “Response time.”
Communication is not possible for about one second after the power is supplied to the inverter until
the initial setting is completed. If the control power is shut down due to an instantaneous voltage drop,
communication is temporarily interrupted.
7
Page 10
4.1. Data transmission formats
■ Note: The term “trip status” used in this manual includes retry waiting status and trip retention status.
4.1.1. Data transmission formats used in ASCII mode
A communication number is used to specify a data item, all data is written in hexadecimal, and JISX-0201 (ASCII (ANSI))-compliant transmission characters are used.
■ Computer → VF-S11
Omissible in one-to-one communicationsFor the W and P commands onlyOmissible
E6581222
"("
(28H)
1. “(“ (1 byte): Start code in ASCII mode
2. INV-NO (2 bytes) : Inverter number (Omissible in one-to-one communications) ... 00 (30H, 30H) to 99 (39H,
3. CMD (1 byte): Command (For details, see the table below.)
4. Communication No.(4 bytes)
5. Data (0 to 4 bytes) : Write data (valid for the W and P commands only)
6. “&” (1 byte): Checksum discrimination code (omissible. When omitting this code, you also need to omit
INV-NO
2 bytes
CMD
1 byte
39h), *(2AH)
The command is executed only when the inverter number matches up with that specified
using a parameter.
(When * is specified in broadcast communications, the inverter number is assumed to
match if all numbers except * match. When * is specified instead of each digit (two-digit
number), all inverters connected are assumed to match.)
If the inverter number does not match or if the inverter number is of one digit, the data will be
judged invalid and no data will be returned.
: Communication number (See 11, “Parameter data.”)
the checksum.)
Communication No.
4 bytes
Checksum area
DATA
0 to 4 bytes
"&"
(26H)
SUM
2 bytes
Omissible
")"
(29H)CR(0DH)
7. Sum (2 bytes): Checksum (omissible)
Add the ASCII-coded value of the last two digits (4 bits/digit) of the sum of a series of bits
(ASCII codes) from the start code to the checksum discrimination code.
Ex.: (R0000&??) CR
28H+52H+30H+30H+30H+30H+26H=160H
The last two digits represent the checksum. = 60
When omitting the checksum, you also need to omit the checksum discrimination code.
8. “)” (1 byte): Stop code (omissible)
9. CR (1 byte): Carriage return code
■ Details of commands and data
CMD (1 byte)Write data (0 to 4 bytes) Hexadecimal number
R (52H): RAM read command
W (57H): RAM/EEPROM write command
P (50H) RAM write command
No data
Write data (0 to FFFF)
Write data (0 to FFFF)
8
Page 11
■ VF-S11 → computer
At time of broadcast communication, returning of data is not executed, except for the inverters to be
returned, when the inverter number is not matched, and the inverter number has only one character.
This is because there will be a risk of that the returned data may be deformed.
• Data returned when data is processed normally (ASCII mode)
OmissibleOmissible
E6581222
"("
(28H)
1. “(“ (1 byte): Start code in ASCII mode
2. INV-NO (2 bytes) : Inverter number (omitted if it is not found in the data received) ... 00 (30H, 30H) to 99 (39H,
3. CMD (1 byte): Command ... The command is also used for a check when an inverter is tripped.
4. Communication No.(4 bytes) :
INV-NO
2 bytes
CMD
1 byte
39H)
If the inverter number matches up with that specified using a parameter, data will be returned to the computer. In broadcast communications, only the destination inverter (with a number matching up with the smallest effective number) returns data to the computer.
In broadcast communications, no data is returned from any inverters except the inverter
bearing a number that matches up with the smallest effective number.
Ex.: (*2R0000) CR -> (02R00000000) CR)
Under normal conditions... The uppercase letter R, W or P is returned, depending on the
command received: R, W or P command.
When an inverter is tripped... The lowercase letter r, w or p is returned, depending on the
command received: R, W or P command.
(The command received is returned with 20H added to it.)
The communication number received is returned.
Communication No.
4 bytes
Checksum area
Data is returned from the inverter with the number 2 only, but no data is returned from
inverters with the number 12, 22 ....
DATA
0 to 4 bytes
"&"
(26H)
SUM
2 bytes
Omissible
")"
(29H)CR(0DH)
5. Data (0 to 4 bytes) : Data ... The data read in is returned for the R command, while the data received is returned
for the W and P commands. If the data received is composed of less than 4 digits, it will be
converted into 4-digit data and returned.
Ex.: (W123412) CR → (W12340012) CR)
6. “&” (1 byte): Checksum discrimination code (omitted if it is not found in the data received)
7. Sum (2 bytes): Checksum ... Omitted if no checksum discrimination code is found in the data received.
ASCII-coded value of the last two digits (4 bits/digit) of the sum of a series of bits (ASCII
codes) from the start code to the checksum discrimination code.
8. “)” (1 byte): Stop code (omitted if it is not found in the data received)
9. CR (1 byte): Carriage return code
9
Page 12
• Data returned when data is not processed normally (ASCII mode)
In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type number is returned to the computer in addition to the checksum. At time of broadcast communication of
the binary mode, returning of data is not executed except for the inverter to be returned (inverter
number 00H) and when the inverter number is not matched. This is because there will be a risk that
the returned data may be deformed.
OmissibleOmissible
E6581222
“(“
(28H)
INV-NO
2 bytes
“N” or “n”
(4EH) (6EH)
DATA
4 bytes
"&"
(26H)
SUM
2 bytes
")"
(29H)
CR
(0DH)
Checksum area
Omissible
“(“ (1 byte): Start code in ASCII mode
1) N or n (1 byte) :Communication error command ... This is also used for the checking of inverter trip.
“4EH(N)” for the normal communication and “6EH(n)” during the inverter trip.
Data (4 bytes): Error code (0000~0004)
0000 ... Impossible to execute (Although communication is established normally, the com-
mand cannot be executed because it is to write data into a parameter whose setting cannot be changed during operation (e.g., maximum frequency) or the
EEPROM is faulty.)
0001 ... Data error (The data is outside the specified range or it is composed of too many
digits.)
0002 ... Communication number error (There is no communication number that matches.)
0003 ... Command error (There is no command that matches.)
0004 ... Checksum error (The checksum result differs.)
“)” (1 byte): Stop code ... This code is omitted if it is not found in the data received.
■ Examples:
(N0000&5C)CR... Impossible to execute (e.g., a change of maximum frequency data during opera-
tion)
(N0001&5D)
(N0002&5E)
(N0003&5F)
... Data error (Data is outside the specified range.)
CR
... No communication number (There is no communication number that matches.)
CR
... There is no command that matches. (Commands other than the R, W and P com-
CR
mands)
(Ex.: L, S, G, a, b, m, r, t, w ...)
(N0004&60)
... Checksum error (The checksum result differs.)
CR
No data returned ... Format error or invalid inverter number
(Ex.: A code other than the stop code (“)”) (Ex.: ”}”) is entered in the stop code
position or the CR code was not found within 0.5 sec.)
10
Page 13
4.1.2. Data transmission formats used in binary mode
A communication number is used to specify a data item, data is written in hexadecimal form, and
data in transmission characters are represented by binary codes (HEX codes).
■ Computer → VF-S11 (binary mode)
Omissible in one-to-one communicationsNo data for the 52H (R) command
E6581222
“/”
(2FH)
1. 2FH (“/”) (1 byte) : Start code in binary mode
2. INV-NO (2 bytes) : Inverter number (Omissible in one-to-one communications) ... 00H to 3FH ,FFH
3. CMD (1 byte): Command (For details, see the table below.)
4. Communication No.(2 bytes)
5. Data (2 bytes): 0000H to FFFFH
INV-NO
1 byte
In case the inverter number is other than FFH (broadcast communication), command is ex-
ecuted only when the inverter number coincides with the one designated with the panel. If
the inverter number is not matched, it will be judged invalid and the data is not returned.
52H (R) command: The size of the data following CMD is fixed to 3 bytes. (Communication
number: 2 bytes, checksum: 1 byte)
57H (W), 50H (P) and 47H (G) commands: The size of the data following CMD is fixed to 5
bytes.
(Communication number: 2 bytes, data: 2 byte, checksum: 1 byte)
Any command other than the above is rejected and no error code is returned.
: Communication number (See 11, “Parameter data.”)
57H (W) and 50H (P) commands: Write data (An area check is performed.)
47H (G) command: Dummy data (e.g., 0000) is needed.
52H (R) command: Any data is judged invalid. (No data should be added.)
CMD
1 byte
Communication No.
2 bytes
Checksum areaNot omissible
DATA
2 bytes
SUM
1 byte
6. Sum (2 bytes): Checksum (not omissible) 00H to FFH
Value of the last two digits (1 byte) of the sum of a series of bits (codes) from the start code
of the data returned to the data (or to the communication number for the 52H (R) command)
Ex.: 2F 52 00 ?? ... 2FH+52H+00H+00H=81H
The last two digits (??) represent the checksum. = 81
No data
Write data (0000H to FFFFH)
Write data (0000H to FFFFH)
Dummy data (0000H to FFFFH)
11
Page 14
■ VF-S11 → computer (binary mode)
At time of broadcast communication of the binary mode, returning of data is not executed except for
the inverter to be returned (inverter number 00H) and when the inverter number is not matched. This
is because there will be a risk that the returned data may be deformed.
• Data returned when data is processed normally (Binary mode)
Omissible
E6581222
“/”
(2FH)
1. 2FH (“/“) (1 byte) : Start code in binary mode
2. INV-NO (2 bytes) : Inverter number... 00H to 3FH (The inverter number is omitted if it is not found in the data
3. CMD (1 byte): Command...The command is also used for a check when the inverter is tripped.
4. Communication No. (4 bytes)
5. Data (2 bytes): Data ... 0000H to FFFFFH
6. Sum (1 bytes): Checksum (not omissible) 00H to FFH
INV-NO
1 byte
received.)
If the inverter number matches up with that specified from the operation panel, data will be
returned from the inverter. If the inverter number does not match, the data will be invalid and
no data will be returned.
Under normal conditions...52H (R), 47H (G), 57H (W) or 50H (P) is returned, depending on
the command received.
When the inverter is tripped...The lowercase letter 72H (r), 67H (g), 77H (w) or 70H (p) is
returned with 20H added to it, depending on the command received.
: The communication number received is returned.
The data read is returned for the 52H (R) and 47H (G) commands, while the data written is
returned for the 57H (W) and 50H (P) commands.
Value of the last two digits (1 byte) of the sum of a series of bits (codes) from the start code
to the data.
CMD
1 byte
Communication No.
2 bytes
Checksum areaNot omissible
DATA
2 bytes
SUM
1 byte
12
Page 15
2) Error Processing (Binary mode)
In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type number is returned to the computer in addition to the checksum. At time of broadcast communication of
the binary mode, returning of data is not executed except for the inverter to be returned (inverter
number 00H) and when the inverter number is not matched. This is because there will be a risk that
the returned data may be deformed.
Omissible
(1 byte)(1 byte)
“/”
(2FH)
N or n (1 byte): Communication error command ... This command is also used for a check when the inverter
Data (2 bytes): Error code (0000~0004)
INV-NO
1 byte
is tripped.
“4EH (N)” is returned under normal conditions, while “6EH (n)” is returned when the in-
verter is tripped.
0000 ... Impossible to execute (Although communication is established normally, the com-
0001 ... Data error (The data is outside the specified range or it is composed of too many
0002 ... Communication number error (There is no communication number that matches.)
0004 ... Checksum error (The checksum result differs.)
N or n
(4EH)(6EH)
Checksum areaNot omissible
mand cannot be executed because it is to write data into a parameter whose setting
cannot be changed during operation (e.g., maximum frequency) or the EEPROM is
faulty.)
digits.)
DATA
2 bytes
SUM
1 byte
E6581222
■ Examples:
No code returned ...Command error, format error (failure to receive the specified number of
bytes within 0.5 seconds, or an parity, overrun or framing error) or the
inverter number does not match or an inverter in broadcast communication in the binary mode except for the inverter for data returning (thein-
verter numbered 00H).
2FH, 4EH, 00H, 00H, 7DH ... Impossible to execute (e.g., a change of maximum frequency data
during operation)
2FH, 4EH, 00H, 01H, 7EH ... Data setting error (The data specified falls outside the specified
range.)
2FH, 4EH, 00H, 02H, 7FH ... No communication number (There is no communication number that
matches.)
2FH, 4EH, 00H, 04H, 81H ... Checksum error (The checksum result differs.)
13
Page 16
4.1.3. Transmission Format of Block Communication
What is block communication?
Data can be written in and read from several data groups set in one communication by setting the type of data desired for communication in the block communication parameters (, , to ) in advance. Block communications can save the communication time.
Data is transmitted hexadecimal using the binary (HEX) code transmission characters. “Computer
→ inverter” is for writing only, while “Inverter → computer” for reply is for reading only.
■ Computer → VF-S11 (Block Communications)
E6581222
Number of writing data groups x 2 bytes
Number of
read
data
groups
Write
data1
High
Write
data1
Low
Write
data2
High
Write
data2
Low
Start
Code
“/”
Omissible
INV-NOCMD
“X”
Num-
ber of
write
data
groups
Checksum Area
1. 2FH(“/”) (1 byte) : Start code of binary mode
2. INV-NO (1 byte) : Inverter number. (Can be omitted in 1:1 communications): 00H to 3FH, FFH
Executed only when the inverter number matches the inverter number. Set on the panel, except in FFH (broadcast communication).
Communication data will be invalidated and data will not be returned either if the inverter
number. Does not match.
3. CMD (1 byte): ‘X’ (Block communication command)
4. Number of write data groups (1 byte)
: Specify the number of data groups to be written (00H to 02H).
If specified outside of the range, data will be treated as a format error and data will not be returned.
5. Number of read data groups (1 byte)
: Specify the number of data groups to be read (00H to 05H).
If specified outside of the range, data will be returned as “Number of read data groups = 0”
when returned by the inverter.
SUM
6. Write data1 (2 bytes)
: Needed when the number of write data groups is larger than 1.
Data to be written to the specified parameter selected by
Dummy data is needed if the number of write data groups is larger than 1 even though(none)
is selected for
7. Write data2 (2 bytes)
: Needed when the number of write data groups is 2.
Data to be written to the specified parameter selected by
Dummy data is needed if the number of write data groups is 2 even though(none) is selected
for
8. SUM (1 byte): Checksum (Cannot be omitted) 00H to FFH
Lower two digits (1 byte) of total sum from start code (SUM value not included)
14
Page 17
E6581222
■ Block Write 1, 2
Select data, which is desired to be written in block communications, in Block Communication Write
Data 1 and 2 Parameters (, ). This parameter becomes effective when the system
is reset, such as when power is turned off. When the setting is completed, turn off and then on the
power.
No.Block Write DataFor data details, see:
0No selection −
1Command 1 (FA00)“8.1 Command by communication”
2Command 2 (FA20)“8.1 Command by communication”
3Frequency Command Value (FA01)“8.1 Command by communication”
4Terminal Board Output Data (FA50)
5Communication Analog Output (FA51)
* When “No selection” is specified in the parameters, no data will be written even though write data is
specified.
■ Block Read 1 to 5
“8.3 Control of input/put signals from communication”
“8.3 Control of input/put signals from communication”
Select read data, which is desired to be read in block communications, in Block Communication
Read Data 1 and 5 Parameters (to). This parameter becomes effective when
the system is reset, such as when power is turned off. When the setting is completed, turn off and
then on the power.
No.Block Read DataFor data details, see:
0No selection −
1Status 1 (FD01)“8.2 Monitoring from communication”
2Output Frequency (FD00)“8.2 Monitoring from communication”
3Output Current (FE03)“9. Parameter data”
4Output Voltage (FE05)“9. Parameter data”
5Alarm Information (FC91)“8.2 Monitoring from communication”
6PID Feedback Value (FE22)“9. Parameter data”
7Input Terminal Board Monitoring (FD06)
8Output Terminal Board Monitoring (FD07)
9Analog Monitoring VIA (FE35)
10Analog Monitoring VIB (FE36)
* Output current (FE03), output voltage (FE05) and PID feedback value (FE22) will become hold data
during a trip. Otherwise, real-time data appears.
* “0000” will be returned as dummy data,if “0 (No selection)” is selected for the parameter and “read”
is specified.
“8.3 Control of input/put signals from
communication”
“8.3 Control of input/put signals from
communication”
“8.3 Control of input/put signals from
communication”
“8.3 Control of input/put signals from
communication”
15
Page 18
■ VF-S11 → Computer
At time of broadcast communication of the binary mode, returning of data is not executed except for
the inverter to be returned (inverter number 00H) and when the inverter number is not matched. This
is because there will be a risk that the returned data may be deformed.
1) Normal processing
E6581222
Omissible
Start
Code
“/”
INV
No.
CMD
“Y”
Number
of Read
Data
Groups
Write
Status
Read
data1
high
Read
data1
low
Number of read data groups x 2 bytes
Read
data2
high
Read
data2
low
Read
data3
high
Checksum area
1. 2FH “/” (1 byte):Start code in binary mode
2. INV-NO (1Byte):Inverter number・・・00H to 3FH
If the inverter number matches up with that specified from the operation panel, data will
be returned from the inverter. If the inverter number does not match, the data will be
judged invalid and no data will be returned.
Communication data will be invalidated and data will not be returned either if the inverter number does not match.(Inverter number is considered matched if it is omitted
during reception)
3. CMD(1Byte):‘Y’ (Block communication command [monitoring])
Lowercase letter ‘y’ during an inverter trip, including standing by for retrying and during
a trip.
4. Number of read data groups (1 byte)
: Return the number of data groups to be read (00H to 05H).
5. Write status (1 byte) : Return 00H to 03H.
* Failing to write in the specified parameter in the number of write data groups, set “1” in
the corresponding bit for the parameter failed to write. (See below.)
Read
data3
low
Read
data4
high
Read
data4
low
Read
data5
high
Read
data5
low
SUM
Bit Position76543210
Data Type−
6. Read data1 - 5 (2 bytes)
: Return according to the number of read data groups. “0000H” is returned as dummy
data if “0” is selected as a parameter.
Read data1: Data selected by . Read data2: Data selected by .
Read data3: Data selected by . Read data4: Data selected by .
Read data5: Data selected by .
7.SUM(1Byte): Checksum (Cannot be omitted) 00H to FFH
Lower two digits (1 byte) of total sum from start code of return data to read data.
■ Example
(When set as follows: = (Command 1), = (frequency command value),
2) Error Processing (Binary mode)
In case an error occurs, communication error command (4EH(N) or 6EH(n)) and the error type number is returned to the computer in addition to the checksum. At time of broadcast communication of
the binary mode, returning of data is not executed except for the inverter to be returned (inverter
number 00H) and when the inverter number is not matched. This is because there will be a risk that
the returned data may be deformed.
Omissible
(1 Byte)(1 Byte)
E6581222
“/”
(2FH)
“N” or “n” (1 byte): Communication error command. Also for check during an inverter trip (includes standingby
for retrying and trip holding). “4EH (N)” when normal, “6EH (n)” during an inverter trip.
0004 : Checksum error (The checksum does not match)
No return : Command error, format error (specified number of bytes is not received in 1sec,
“N” or “n”
(4EH)(6EH)
Checksum AreaNot omissible
or parity error, overrun error or framing error), inverter number mismatch, and
inverter number other than 00H in broadcast communication.
DATA
2 Bytes
SUM
1 Byte
17
Page 20
4.2. Commands
Here are the communication commands available.
CommandFunction
R command Reads the data with the specified communication number.
W command Writes the data with the specified communication number. (RAM and EEPROM).
P commandWrites the data with the specified communication number. (RAM).
G command
X commandBlock communication (Computer -> Inverter)
Y commandBlock communication (Inverter -> Computer)
E6581222
Reads the data with the specified communication number. (For binary mode only.
Dummy data is required for this command.)
W (57H) (RAM
This command is used to write new data into the parameter specified using it communication number.
It writes data into the RAM and EEPROM. For parameters whose settings cannot be stored in the
EEPROM (e.g., parameter with the communication number FA00), the W (57H) command writes
data into the RAM only. It cannot be used to write data into read-only parameters (e.g., parameter
with the communication number FD?? or FE??).
Each time an attempt to write data is made, the inverter checks if the data falls within the specified
range. If this check reveals that the data falls outside the specified range, the inverter will reject it and
return an error code.
- Ex.: Setting the deceleration time (communication number: 0010) to 10 sec.
<ASCII mode>
<Binary mode>
♦ Do not write the same parameter to the EEPROM more than 10,000 times. The life time of EEPROM is
approximately 10,000 times.(Some parameters are not limited, please refer to the “9.Parameter data “)
The lifetime of EEPROM is approximately 10,000 times. When using the TOSHIBA inverter protocol and
the data does not need to be records, use P command (the data is written only to RAM).
■ Explanation of terms
*1: The RAM is used to temporarily store inverter operation data. Data stored in the RAM is cleared
*2: The EEPROM is used to store inverter operation parameter settings, and so on. Data stored in
when the inverter is turned off, and data stored in the EEPROM is copied to the RAM when the
inverter is turned back on.
the EEPROM is retained even after the power is turned off, and it is copied to the RAM when the
inverter is turned on or reset.
18
Page 21
E6581222
P (50H) (RAM
*1
write)
This command is used to rewrite data into the parameter specified using a communication number. It
writes data into the RAM only. It cannot be used to write data into any read-only parameters. Each
time an attempt to write data is made the inverter checks whether the data falls within the specified
range. If this check reveals that the data falls outside the range, the inverter will reject it and return an
error code.
- Ex.: Entering the emergency stop command (communication number: FA00) from the computer
<ASCII mode>
Computer →
2F 50 FA 00 90 00 092F 50 FA 00 90 00 09
R (52H) (Data read)
This command is used to read the setting of the parameter specified using a communication number.
(When multiple inverters are operated in binary mode via RS485 converter connected to a two-wire
line, the execution of the R command could result in a communication error. To avoid this, use the G
command in binary mode when inverters are connected to a two-wire line.)
- Ex.: Monitoring the electric current (communication number: FE03)
<ASCII mode>
When multiple inverters are operated in binary mode via RS485 converter connected to a two-wire line, use
the G command to read data.
G (47H) (Data read)
This command is used to read the parameter data specified using a communication number.
To send this command to an inverter with two-wire type RS485 network, 2bytes of dummy data are
needed. This command is available only in binary mode.
- Ex.: Monitoring the electric current (communication number: FE03)
Computer → InverterInverter
2F 47 FE 03 00 00 772F 47 FE 03 07 7B F9
* In this example, the data 00H sent from the computer to the inverter is dummy data.
Notice
→ Computer
19
Page 22
E6581222
S (53 H)/ s (73 H) Inter-drive communication command(RAM
This command is for using frequency command values in % (1 = 0.01%), instead of in Hz, and is for
synchronous-proportional operation in inter-drive communication. This command can also be used
in ordinary computer link communications.
When writing in the frequency command (FA01) is enabled and a parameter other than it is specified,
a communication number error will result. Data is written in the RAMs only and at this time the data
check such as an upper limit and lower limit checking is not carried out.
Data is not returned from the inverters while this command is used. This command can be used
only in the binary mode.
For the details of the format, see “6.2 Transmission format for inter-drive communication.”
Use (%) as the unit for frequency command values specified by the command S, instead of (Hz), and
the receiving side converts units for frequency values to “Hz” in accordance with the point conversion
parameter. The conversion formula is shown below.
Frequency command value (Hz) =
Point 2 frequency (F813) − Point 1 frequency (F812)
Point 2 (F814) − Point 1 (F811)
− Point 1 (F811)) + Point 1 frequency (F812)
When Command “s” (lowercase letter) is received, the slave side judges that the master side is
tripped and operates in accordance with the inter-drive communication parameter ().
For detail, see "7. Communication parameters ".
- Examples: 50% frequency command
(If maximum frequency = Frequency for operation at 80Hz = 40Hz: 50% = 5000d = 1388H)
Data selected in the block communication write parameters (,) is written in the
RAMs. When returning data, data selected in block communication read parameters ( to
) is read and is returned.
- Examples: 60Hz operation command from communication and monitoring (Monitoring when already operating at 60Hz)
(Parameter Setting:
The command is impossible to execute, though communication was
established normally.
0000
1 Writing data into a parameter whose setting cannot be changed
during operation (e.g., maximum frequency)
*1
2 Writing data into a parameter while “” is in progress
3 The maintenance command is issued.
*2
Data errorInvalid data is specified.0001
Communication
number error
There is no communication number that matches.
Ex.: In the case of (R0)))) CR, 0))) is recognized as a communication
0002
number.
Command errorThe command specified does not exist.0003 (ASCII mode)
No code returned (Binary
mode)
Checksum errorThe Checksum does not match.0004
Format errorThe data transmission format does not match.
No code returned
1 One-digit inverter number (ASCII mode)
2 The CR code is found in the designated position. (ASCII mode)
Ex.:Communication number of 4 digit or less. In the case of (R11)
CR, 11) CR is recognized as a communication number and
the CR code is not recognized, with the result that a format er-
ror occurs.
3 A code other then the stop code (“)”) is entered in the stop code
position.
4 The specified number of bytes of data are not received within 0.5
sec.
Receiving errorA parity, overrun or framing error has occurred.
*3
No code returned
*1: For parameters whose settings cannot changed during operation, see 11.1, Table of parame-
ters.”
*2: In binary mode, no data will be returned if a command error occurs. When the maintenance
command (M) is issued, an impossible-to-execute error occurs and an error code is returned.
*3: Parity error: The parity does not match.
Overrun error : A new data item is entered while the data is being read.
Framing error : The stop bit is placed in the wrong position.
* For the errors with “no code returned” in the above table, no error code is returned to avoid a data
crash.
If no response is received, the computer side recognizes that a communication error has occurred.
Retry after a lapse of some time.
* If the inverter number does not match, no processing will be carried out and no data will be re-
turned, tough it is not regarded as an error.
21
Page 24
4.4. Broadcast communications function
Broadcast communication function can transmit the command (write the data) to multiple inverters by
one communication. Only the write (W, P) command is valid and the read (R, G) command is invalid.
The inverters subject to the broadcast communication are the same to the independent communication; 0 to 99 (00H - 63H) in the ASCII mode, and 0 to 63 (00H - 3FH) in the binary mode.
To avoid data deforming, the inverters to return data will be limited. A RS485 communication converter unit (RS4001Z, RS4002Z or RS4003Z) will be needed to control multiple inverters on the network.
- ASCII Mode
If you enter two asterisks (**) in the inverter number position of the data transmission format, the
computer will send the data simultaneously to all inverters (with an inverter number between 0 and
99 (00 to 63H)) on the network.
- Binary Mode
To put "FF" to the specified place of the inverter number in the communication format validates the
broadcast communication and the command is transmitted to all the applicable inverters in the net-
work (inverter numbers from 0 to 63 (00 to 3FH)).
E6581222
<Inverter that returns data to the computer>
Data is returned from the inverter bearing the inverter number 00 only.
If you do not want inverters to return data, do not assign the number 00 to any inverter on the network.
■ “Group” broadcast communications (ASCII mode only)
If you put “*?” In the inverter number position of the data transmission format, data will be sent
simultaneously to all inverters bearing a number whose digit in the one’s place in decimal notation
is”?”
If you put ”?*” In the inverter number position of the data transmission format, the data will be sent
simultaneously to all inverters bearing a number whose digit in the ten’s place in decimal notation
is”?”.
(“?”: Any number between 0 and 9.)
<Inverter that returns data to the computer>
Data is returned only from the inverter bearing the smallest number in the same group of inverters
(i.e., inverter whose number in the position of ”*” is 0).
If you do not want inverters to return data to the computer, do not assign a number having a 0 in the
position of “*” to any inverter on the network.)
■ Examples of broadcast communications
Ex: Set the frequency setting for communication to 60Hz.
Example of transmission of data from host computer to inverter: (**PFA011770)
Example of data returned from inverter to host computer: (00PFA011770)
Data is returned from the inverter numbered 00 only, while commands are issued to all inverters
connected to the network.
CR
CR
2 Host computer → A specific group of inverters: group communications (ASCII Mode)
Example of transmission of data from host computer to inverters: (*9PFA011770)
Example of data returned from inverter to host computer: (09PFA011770)
CR
CR
Data is returned only the inverter numbered 09 only, while commands are issued to a maximum of
10 inverters bearing the number 09, 19, 29, 39, ... or 99.
Example of transmission of data from host computer to inverters: 2F FF 50 FA 01 17 70 00Example of data returned from inverter to host computer: 2F 00 50 FA 01 17 70 01
Returning is possible only for the inverter that has the number 00, and the command is transmitted
to all the applicable inverter connected in the network.
22
Page 25
•
A
An example of system configuration (schematic diagram)
E6581222
Host
computer
RS485 communication converter unit (RS4001Z,
RS4002Z or RS4003Z) will be needed to control multiple
inverters on the network.
Block 1
Inverter No. 10 Inverter No.11Inverter No.19
VF-S11
VF-S11VF-S11VF-S11VF-S11VF-S11
*1
Inverter No.20 Inverter No.21Inverter No.29
Block 2
*1: Error signal I/F
In broadcast communications, only the representative inverter in each block returns data to the host
computer. However, you can make the representative inverter in each block report the occurrence of
a problem in the block. To do so, follow these steps.
Set the timer function so that, if a time-out occurs, the inverter will trip (Ex.: = (sec)), set the
output terminal selection parameter (FL) so that trip information will be output through the output
terminal (=), and set the input terminal selection parameter (F) of the representative inverter in each block to “external input trip (emergency stop)” (=). Then, connect the input
terminal (F) of the representative inverter to the FL terminal of each of the other inverters in the same
block. In this setting, if an inverter trips, the representative inverter will come to an emergency stop,
and as a result it will report the occurrence of a problem in its block to the computer. (If the representative inverter returns a lowercase letter in response to a command from the computer, the computer will judge that a problem has arisen in an inverter.) To examine details on the problem that has
arisen, the host computer accesses each individual inverter, specifying its communication number.
To make the computer issue a command to all inverters in block 1 or block 2 shown in the figure
above, specify “1*” or “2*”, respectively. In this system, inverter No. 10 will return data to the computer if a problem arises in block 1, or inverter No. 20 if a problem arises in block 2. For overall broadcast communications, specify “**”, in which case the inverter with the communication number “00” will
return data to the computer.
In this example, if you want the computer to maintain communications without bringing an representative inverter to an emergency stop, set its input terminal selection parameter to “disabled
(=) but not to “external input trip (emergency stop).” This setting causes the host computer
to check the setting of the input terminal information parameter (communication number: FE06) of
the representative inverter, and as a result enables the computer to detect the occurrence of a problem.
CAUTION:
Data from inverters will be deformed if inverters of the same number are connected on the network.
Never assign same single numbers to inverters on the network.
23
Page 26
4.5. Examples of the use of communication commands
Here are some examples of the use of communications commands provided for the VF-S11 series of
inverters.
Inverter numbers and checksum used in ASCII mode are omitted from these examples.
■ Examples of communications
- To run the motor in forward direction with the frequency set to 60 Hz from the computer
<ASCII mode>
Computer → InverterInverter → Computer
(PFA011770)CR(PFA011770)CR…Set the operation frequency to 60 Hz.
(60 / 0.01 Hz = 6000 = 1770H)
(PFA00C400)
<Binary mode>
Computer → InverterInverter → Computer
2F 50 FA 01 17 70 012F 50 FA 01 17 70 01
2F 50 FA 00 C4 00 3D2F 50 FA 00 C4 00 3D
CR(PFA00C400)CR…Set to “forward run” with commands and frequency
instruction from the computer enabled.
E6581222
- To monitor the operation frequency (during 60 Hz operation)
<ASCII mode>
Computer → InverterInverter → Computer
(RFD00)CR(RFD001770)CR…Set the operation frequency to 60 Hz.
(60÷0.01Hz=6000=1770H)
<Binary mode>
Computer → InverterInverter → Computer
2F 52 FD 00 7E2F 52 FD 00 17 70 05
- To monitor the status of the inverter
<ASCII mode>
Computer → InverterInverter → Computer
(RFD01)CR(rFD010003)CR…For details on statuses, see 8.2 “Monitoring from
the computer.” (Stop status, FL output status, trip
status (r command))
<Binary mode>
Computer → InverterInverter
2F 52 FD 01 7F2F 72 FD 01 00 03 A2
→ Computer
- To check the trip code (when the inverter is tripped because of )
…For details on trip codes, see “Trip code monitor” in 8.2, “Monitoring
from the computer.” (18H = 24d “” trip status)
<ASCII mode>
Computer → InverterInverter
(RFC90)CR(rFC900018)CR
<Binary mode>
Computer → InverterInverter
2F 52 FC 90 0D2F 72 FC 90 00 18 45
→ Computer
→ Computer
24
Page 27
4.6. Examples of RS232C communication programs
Ex. 1: BASIC program for monitoring the operation frequency continuously (RS232C, ASCII mode)
(Toshiba version of Advanced BASIC-86 Ver. 3.01.05J)
◊ Monitoring the operation frequency continuously
1) Examples of programs
10 OPEN "COM1:9600,E,8,1" AS #1--- 9600 baud, even parity, 8-bit length, 1 stop bit
20 A$=”FE00”--- Specifies the communication number for
monitoring the operation frequency.
30 PRINT #1,"("+”R”+A$+")"--- Transmits data to the inverter.
Note: The carriage return code is added
automatically.
40 INPUT#1,B$--- Receives data returned from the inverter.
50 AAA$=“&H”+MID$(B$,7,4)--- Extracts only data items from the data re-
turned.
60 F$=LEFT$(STR$(VAL(AAA$)/100),6)--- Converts data into decimal form.
70 PRINT " Operation frequency =";F$+“Hz” --- Displays the operation frequency.
80 GOTO 20--- Repeats.
E6581222
2) Examples of program execution results (stop command issued during 80 Hz operation)
Operation frequency = 80 Hz ...
Operation frequency = 79.95Hz
:
:
Operation frequency = 0Hz
25
Page 28
E6581222
Ex. 2: BASIC program for executing an input command with checksum (RS232C, ASCII mode)
(Toshiba version of Advanced BASIC-86 Ver. 3.01.05J)
◊ Checking if the maximum frequency setting has been changed correctly
1) Examples of programs
10 OPEN "COM1:9600,E,8,1" AS #1--- 9600 baud, even parity, 8-bit length, 1 stop bit
20 INPUT"Send Data=";A$--- Reads in data to be sent to the inverter.
30 S$="("+A$+"&"--- Adds “(“ and “&” to the read data in.
40 S=0
50 L=LEN(S$)
60 FOR I=1 TO LCalculates the number of bits (checksum).
70 S=S+ASC(MID$(S$,I,1))
80 NEXT I
90 CHS$=RIGHT$(HEX$(S),2)
100 PRINT #1,"("+A$+"&"+CHS$+")"--- Sends the data including the checksum result
to the inverter.
110 INPUT #1,B$--- Receives data returned from the inverter.
120 PRINT "Receive data= ";B$--- Displays the data received.
130 GOTO 20--- Repeats.
2) Examples of program execution results
Send Data=? R0011--- Reads the maximum frequency (0011).
Receive Data= (R00111F40&3D)--- 1F40 (Maximum frequency: 80 Hz)
Send Data=? W00111770--- Changes the maximum frequency to 60 Hz
(1770).
Receive Data= (W00111770&36)
Send Data=? R0011--- Reads the maximum frequency (0011).
Receive Data= (R00111770&31)--- 1770 (Maximum frequency: 60 Hz)
26
Page 29
Ex. 3 BASIC program for communication tests (RS232C, ASCII mode)
(Toshiba version of Advanced BASIC-86 Ver. 3.01.05J)
◊ Accessing a parameter (with error code.)
1) Examples of programs
100 INPUT "Baud rate=9600/4800/2400/1200";SPEED$
---- Selects a baud rate.
110 INPUT "Parity=even(E)/odd(O)";PARITY$
---- Selects parity.
120 OPEN "COM1:"+SPEED$+","+PARITY$+",8,1"AS #1
130 INPUT "Send data";B$---- Enters a command.
140 PRINT #1,B$
150 C$=""
160 T=TIMER
170 COUNT=(TIMER-T)
180 IF COUNT >3 THEN 270
190 IF COUNT <0 THEN T=TIMER---- Prevents an increase in the number of digits.
200 IF LOC(1)= 0 THEN A$="":GOTO 220
210 A$=INPUT$(1,#1)
220 IF A$ <>CHR$(13) THEN 240---- Carriage return
230 GOTO 290(CR) to finish reading in.
240 IF A$="" THEN 160
250 C$=C$+A$
260 GOTO 160
270 COLOR @0,7:PRINT "!!! There is no data to return. !!! ";:COLOR @7,0:PRINT
280 GOTO 130---- Repeats.
290 PRINT A$;
300 C$=C$+A$
310 PRINT "Return data=";c$;
320 GOTO 130---- Repeats.
E6581222
2) Examples of program execution results (In this example, the inverter number is 00.)
Baud rate=9600/4800/2400? 9600---- Selects 9600 baud.
Parity=even(E)/odd(O)? E---- Select E (even parity).
Send data? (00R0011)---- Carries out test communications.
Return data= (00R00111770)
Send data? ()---- Error
!!! There is no data to return. !!! ---- No data is returned.
Send data? (R0011)
Return data= (R00111770)
Send data?
:
:
27
Page 30
E6581222
r
A
Ex. 4 A VisualBaisc program for the ASCII mode communication
(VisualBaisc is the registered trademark of the U.S. microsoft company.)
◊ Accessing a parameter
1) Sample program executive example (Monitor of the output frequency (FD00))
Transmission and reception of the optional data like in the following example can be done by doing
"the arrangement of the form control" of the explanation and "the description of the code" with
mentioning later.
Reply data from the inverte
are 1770H (6000d) with this
example.
s for the unit of the output
frequency (FD00),1= 0.01Hz,
the Inverter is being operated
in 60.00Hz.
2)Arrangement of the control on the form
Two TextBox, two Labels , three CommandButton and one MsComm are arranged on the form as
follows.
28
Page 31
3)The description of the code
Private Sub Form_Load()
Form1.Show
'**********************************************************************
' Setting the labels (Initialization)
'**********************************************************************
'**********************************************************************
' Setup of communication (Initialization)
'**********************************************************************
'**********************************************************************
' A serial port is opened. (Initialization)
'**********************************************************************
If False = MSComm1.PortOpen Then
MSComm1.PortOpen = True
End If
'**********************************************************************
' Data are received.
'**********************************************************************
Do
dummy = DoEvents()
If MSComm1.InBufferCount Then
Text1.Text = Text1.Text & MSComm1.Input
End If
Loop
End Sub
'**********************************************************************
' The contents of the text box are transmitted.
'**********************************************************************
Private Sub Command1_Click()
MSComm1.Output = Text2.Text & Chr(13)
End Sub
'**********************************************************************
'The contents of the text box are removed.
'**********************************************************************
Private Sub Command2_Click()
Text2.Text = ""
Text1.Text = ""
End Sub
'**********************************************************************
'A serial port is closed, end
'**********************************************************************
Private Sub Command3_Click()
If True = MSComm1.PortOpen Then
MSComm1.PortOpen = False
End If
End
End Sub
29
Page 32
5. MODBUS-RTU protocol
The MODBUS-RTU protocol of VF-S11 supports only part of the MODBUS-RTU protocol. Only two
commands are supported, “03: Multiple data read (limited only to two bytes)” and “06: Word writes.”
All data will be binary codes.
■ Parameter Setting
• Protocol Selection ()
Select “MODBUS-RTU protocol ( = ) in the communication selection parameters. “TOSHIBA Inverter Protocol” (=) is set for communication protocol selection in initial shipment
setting. (See “3. Communication protocol.”)
* Caution when selecting MODBUS-RTU protocol
The extension panel (RKP001Z) and parameter writer (PWU001Z) , these options cannot be used.
Note that Parameter Numbers. , , , and to do not
function.
• Inverter Number ()
Inverter numbers. 0 to 247 can be specified in MODBUS-RTU. “0” is allocated to broadcast communication (no return). Set between 1 and 247.
E6581222
<Related Parameter: Change and set as necessary>
: Communication baud rate
: Parity
: Communication error trip time
■ Timing of Message from Host
MODBUS-RTU sends and receives binary data without a frame synchronization header character
and defines the frame synchronizing system to recognize the start of a frame by no-data time.
MODBUS-RTU initializes frame information and decides the data that is first received subsequently
as the first byte of a frame if data is not communicated within a time for 3.5 bytes, including the start
and stop bits, at the transmission speed of the on-going communication while standing by for data
reception. If a frame is being received before no-data time for 3.5 bytes, this frame will be aborted.
Be sure to provide more than 3.5 bytes for data send interval.
Send data so that the time between characters will not be spaced for more than 1.5 bytes.Other-
wise, MODBUS-RTU will sometimes recognize it as a start of data.
In the case of data to other stations, messages from the host and responses from other stations are
also received. A wait time for 3.5 bytes is needed before starting transmission after own station
completes reception when sending a response to recognize a frame start at this time.
30
Page 33
■ Data Exchange with Inverters
The inverters are always ready to receive messages and perform slave operation in response to
computer requests.
A transmission error will result if the transmission format does not match. The inverters will not respond if a framing error, parity error, CRC error or an inverter number mismatch occurs.
If no response is received, the computer side recognizes that a communication error has occurred.
Transmit data again.
(1) In case spacing for more than 3.5 bytes are provided before characters, all data immediately
preceding it will be aborted. Data will sometimes be aborted if spacing for 1.5 bytes or more is
provided between characters.
(2) Communications will be effective only when inverter numbers match or the communication mode
is broadcast communications. No response will be made if inverter numbers do not match.
(3) Message reception will end if spacing for more than 3.5 bytes are provided at the end of charac-
ters.
E6581222
■ Caution:
(4) If no communications take place within the time specified using the timer function, the computer
will assume that a communication error has occurred and trip the inverter. The timer function is
disabled when the inverter is turned on or initialized. For details, see Section 7.3, “Timer function.”
(5) On executing the command received, the inverter returns data to the computer. For the response
time, see Appendix 2, “Response time.”
Communication is not possible for about one second after the power is supplied to the inverter until
the initial setting is completed. If the control power is shut down due to an instantaneous voltage drop,
communication is temporarily interrupted.
31
Page 34
5.1. MODBUS-RTU transmission format
MODBUS-RTU sends and receives binary data without a frame-synchronizing start code and defines
the blank time to recognize the start of a frame. MODBUS-RTU decides the data that is first received subsequently as the first byte of a frame after a blank time for 3.5 bytes at the on-going communication speed.
5.1.1. Read command (03)
■ Computer → VF-S11 *The text size is 8 bytes fixed.
E6581222
Commu-
(3.5bytes
Blank)
1) Inverter No.. (1 byte): Specify an inverter number between 0 and 247 (00H to F7H).
2) Command (1 byte): Set the read command (03H fixed).
3) Communication No.. (2 bytes): Set in the order of high to low numbers.
4) Number of data groups (2 bytes) : Set the number of data words 0001 (fixed) in the order of high to low numbers.
5) CRC (2 bytes): Set generation results of CRC in the order of low to high numbers.. For the
■ VF-S11 → Computer (Normal return) *The text size is 7 bytes fixed.
(3.5bytes
Blank)
1) Command (1 byte): Read command (03H fixed) will be returned.
2) Number of data: A number of data bytes (02H fixed) will be returned. The number of data groups for
3) Read data (2 bytes): Returned in the order of read data (high) and (low).
Inverter
No.
Inverter
No.
Command
030001
Command
0302
transmission to the inverters is 2 bytes and 01H fixed. Note that the number of data returned by the inverters is 1 byte and 02H fixed.
nication
No.
(high)
Command processing will be executed only broadcast communication “0” and with
those inverters that match set inverter numbers. Data will not be returned if “0”
(broadcast communication) and inverter numbers do not match.
method to generate CRC, see “5.2 CRC Generation.” Note that the setting sequence is reversal to that of others.
Number of
Data
Commu-
nication
No.
(low)
Read data
(high)
Number
of Data
Groups
(high)
Read data
(low)
Number
of Data
Groups
(low)
CRC
(low)
CRC
(low)
CRC
(high)
CRC
(high)
(3.5bytes
Blank)
■ VF-S11 → Computer (Abnormal return) *The text size is 5 bytes fixed.
2) Error code (1 byte): See “4.3 Transmission errors.”
■ Example: Writing in frequency command value (FA01) (60Hz)
(Computer → inverter) 01 06 FA 01 17 70 E6 C6
(Inverter → computer) 01 06 FA 01 17 70 E6 C6
■ Example: Communication number error
(Computer → inverter) 01 06 FF FF 00 00 89 EE
(Inverter → computer) 01 86 02 C3 A1
Inverter No. Command Error Code
86
CRC
(low)
CRC
(high)
Note
▼ The EEPROM life is 10,000 operations.
Do not write in the same parameter that has an EEPROM more than 10,000 times.
The communication commands (FA00, FA20, FA26), communication frequency command (FA01),
terminal output data (FA50) and analog output data (FA50) are stored in the RAMs only and no restrictions are placed on them.
33
Page 36
5.2. CRC Generation
A
“CRC” is a system to check errors in communication frames during data transmission. CRC is
composed of two bytes and has hexadecimal-bit binary values. CRC values are generated by the
transmission side that adds CRC to messages. The receiving side regenerates CRC of received
messages and compares generation results of CRC regeneration with CRC values actually received.
If values do not match, data will be aborted.
■ Flow
E6581222
CRC generation
( )
CRC initial data: FFFF
Byte counter n = 0
Byte counter n < Length
Yes
CRC = (CRC XOR nth send byte
(0 expanded to word (higher 8
bits))
Bit counter = 0
Bit counter < 8
Yes
C = (Remainder of CRC ÷ 2)
CRC>>1
Is remainder (C)
other than 0?
Yes
(CRC XOR generating polyno-
mial (A001))
CRC=
No
No
No
procedure for generating a CRC is:
1, Load a 16–bit register with FFFF hex (all 1’s). Call this
the CRC register.
2. Exclusive OR the first 8–bit byte of the message with the
low–order byte of the 16–bit CRC register, putting the
result in the CRC register.
3. Shift the CRC register one bit to the right (toward the
LSB), zero–filling the MSB. Extract and examine the
LSB.
4. (If the LSB was 0): Repeat Step 3 (another shift).
(If the LSB was 1): Exclusive OR the CRC register with
the polynomial value A001 hex (1010 0000 0000 0001).
5. Repeat Steps 3 and 4 until 8 shifts have been performed. When this is done, a complete 8–bit byte will
have been processed.
6. Repeat Steps 2 through 5 for the next 8–bit byte of the
message. Continue doing this until all bytes have been
processed.
7. The final contents of the CRC register is the CRC value.
Bit counter +1
Byte counter +1
End (Return CRC)
5.3. Error codes
In case of the following errors, the return commands from the inverters are added 80h to the commands received by the inverters. The following error codes are used.
Error CodeDescription
8. When the CRC is placed into the message, its upper and
lower bytes must be swapped as described below.
01Command error (Returned when a command other than 03 or 06 is received)
02
Communication number error (A communication number is not found when Command 03 or 06 is received)
03Data range error (Data range error when Command 03 or 06 is received
Unable to execute (Command 06 is being received and data cannot be written)
04
(1) Writing in write-disable-during-operation parameter
(2) Writing in parameter that is executing TYP
34
Page 37
-
6. Inter-drive communication
A
Inter-drive communication function enables manipulation of multiple inverters without using the host
computer such as the PLC and the PC. This function is utilized for "speed proportional control". The
command is instructed by the operation from the master inverter’s panel or analog input, etc.
With the Inter-drive communication function, the master inverter continues to transmit the data selected by the parameters to all the slave inverters on the same network. The master inverter uses the
S command for outputting instructions to the slave inverters, and the slave inverters do not return the
data. (See chapter 4.2 "Command".) Network construction for a simple synchronized operation and
speed-proportional operation can be created by this function.
The inverters on the slave side are always ready to receive messages during inter-drive communications andperform slave operation in response to requests made by the inverters on the master side
or computer requests during inter-drive communications.The inverters on the master side are always ready to send messages during inter-drive communications and do not receive data.
To use the inter-drive communication function, select “TOSHIBA Inverter Protocol” (=) in
the communication protocol selection parameters.“TOSHIBA Inverter Protocol” (=) is set
for communication protocol selection in Shipment setting. (See “3. Communication protocol.”)
E6581222
<Conceptual illustration>
Master (60Hz)
VF-S11
nalog input
<Notes>
Speed command can be transmitted but the run / stop signal is not issued. Slave station should have an individual
stop signal or the function to stop the action by the frequency reference. (Setting is necessary for : Opera
tion starting frequency, : Operation starting frequency hysteresis .)
Slave 1 (50Hz)
VF-S11VF-S11VF-S11
* A RS485 communication converter unit (RS4001Z,
RS4002Z or RS4003Z) will be needed to control multiple
inverters on the network.
Slave 2 (40Hz)
Slave 3 (30Hz)
For continuing the operation by the last received command value in the case of a communication breakdown,
provide a communication time-out interval () to trip the slave inverters. The master inverter does not trip
even though the communication breakdown happens. To trip the master inverter, provide an interlock mechanism
by installing an FL fault relay point or the like from the slave side.
35
Page 38
■ Setting of parameter
E6581222
●Selection of communication protocol () Shipment setting: 0 (TOSHIBA Inverter Protocol)
Protocol setting with all inverters (both master and slave inverters) engaged in inter-drive communications
0: Set the TOSHIBA Inverter Protocol.
* Inter-drive communications are disabled when the MODBUS-RTU protocol is selected.
* This parameter is validated after resetting the inverter or rebooting the power supply.
● Setting of master and slave inverters for communication between inverters (setting of master and
slave) () ... Shipment setting =
Assign one master inverter in the network. Other inverters should be the slave inverters.
*Specify only one inverter as the master. In case two or more inverters are designated for the
master inverter in the same network, data will collide.
- Setting to the master inverter
Set data desired for sending from the master side to the slave side.
:Master inverter(transmission of frequency commands) : Master inverter (transmission of
output frequency signals)
- Setting to the slave inverters
Set the desired action on the slave side that will be needed when the master trips.
: Sets the frequency command value to 0Hz. (Output frequency is limited by low-limit frequency)
: Normal operation is continued
(If an output frequency is set on the master side, the output frequency of the master side becomes 0Hz due to tripping and the frequency of commands to the slave side becomes 0Hz.)
: Makes an emergency stop (“E” trip).
(The method to stop follows the setting in “Emergency stop selection ()”
*This parameter is validated after resetting the inverter or rebooting the power supply.
• Communication waiting time () ... Shipment setting =
- Setting to the master inverter
Set up more than 0.03 seconds as a transmitting interval on the master side to wait for the processing time on the slave side(= ).
● Speed setting mode selection () ... Shipment setting = : Built-in potentiometer
Designate a target of speed command input for the inverter to the parameter .
- Setting to the master inverter
Designate a number except for “: serial communication ” ( ≠).
- Setting to the slave inverters
Designate “: serial communication ” ( =).
36
Page 39
■ Relating communication parameters
Following parameters should be set or changed if necessary.
• Communication baud rate ()... Shipment setting = : 9600bps
Baud rate of all inverters in the network (master and slave) should be same network.
• Parity () ... Shipment setting = : Even parity
Parity of all inverters in the network (master and slave) should be same network.
• Communication error trip time() ... Shipment setting =
Operation is continued by the last received command value in the case of a communication breakdown. To stop the operation of inverter, provide a communication time-out interval (ex. =)
to the slave inverters. The master inverter does not trip even though the communication breakdown
happens. To trip the master inverter, provide an interlock mechanism by installing a FL fault relay
point or the like from the slave side.
• Frequency point selection ()
Adjusted to the system.
See chapter “6.1 Speed proportional control” for details.
E6581222
■ Setting example of parameters
Parameters relating to the master side (example)
Master (transmission of output frequency
(%) (100% at FH))
Selection of communication protocol
(Toshiba inverter protocol)
Communication baud rate
(ex. 19200bps)
Parity (even parity)
Example: Panel
Example: Built-in potentiometer
Communication waiting time
(ex. 30msec)
Parameters relating to the slave side (example)
Slave (0Hz command issued in case the master inverter
fails)
Selection of communication protocol
(Toshiba inverter protocol)
Communication time-out (ex. 1 second)
Communication baud rate (same to the master side)
Parity (same to the master side)
Terminal block (ex. Driven by F, ST)
( Run and stop of operation is controlled with the frequency
reference value by setting the “run frequency”.)
< For speed control >
Serial communication
? Adjusted to the system Point 1 setting (%)
? Ditto Point 2 frequency (Hz)
? Ditto Point 2 setting (%)
? Ditto Point 2 frequency (Hz)
37
Page 40
6.1. Speed proportional control
Point2
Point1
Various inclinations can be set by frequency point setting.
The frequency command value on the slave side during inter-drive communication can be expressed
by the following formulas.
If inter-drive communication is not selected (=), point conversion is not performed.
Point conversion is performed only when the command “S” is received.
(Ex.) < unit > Frequency unit: 1=0.01(Hz), point setting unit: 1=0.01%
Maximum
frequency
()
Master (Fc)100.00Hz
(10000)
Slave 1100.00Hz
(10000)
Slave 2100.00Hz
(10000)
Point 1
setting
()
Point 1 frequency
()
Point 2
setting
()
−−−−
0.00%
(0)
0.00%
(0)
0.00Hz
(0)
0.00Hz
(0)
100.00%
(10000)
100.00%
(10000)
Point 2
frequency
()
90.00Hz
(9000)
80.00Hz
(8000)
E6581222
Frequency
(Fc)
50.00Hz
(5000)
45.00Hz
(4500)
40.00Hz
(4000)
Sending data from the master:
Master send fc(%) = = = 5000 = 50%
Master side fc×10000
Master side FH
Slave frequency Command(Hz)=
1(F811) point - 2(F814) Point
By the point conversion process,
09000
Hzfc:1 Slave==)−(×
=)(+
Hzfc:2 Slave==)−(×
=)(+
−
010000
−
08000
−
010000
−
【Diagram of speed proportional control】
<Outside>
→<Inverter’s internal computation>
←
Point conversion
5000×10000
10000
F812)frequency( 1 Point - F813)frequency( 2 Point
x (Master command (%) - Point 1(F811)) + Point 1 frequency(F812)
Hz454500005000
Hz404000005000
(Note)fc=frequency reference, FH=Maximum frequency
(Hz)
data= sendMaster ×
Master command (%)
Point2Frequency(
)
Slave command (Hz)
Point1Frequency(
FC Master
01000
FHMaster
=
)
(
)
Master command (%)
F812F814
−
F811F813
−
(
Slave command (Hz)
)
(%) command Master((Hz) command Slave×
(%)
2-F811)+F81
38
Page 41
6.2. Transmission format for inter-drive communication
Data type is handled in hexadecimal notation and the transmission characters are treated with the
binary (HEX) code.
The transmission format is basically the same to the case of binary mode. S command is used and
the slave inverters do not return the data.
■ Master inverter (VF-S11) to slave inverter (VF-S11) (Binary mode)
Omission
E6581222
“/”
(2FH)
1) INV-NO (1 byte): Inverter number
2) CMD (1 byte): Command
3) Communication number (2 bytes):
4) DATA (2 bytes): Data of frequency command value.
As for the S command, see section 4.2 “Commands”, and see chapter “6 Inter-drive communication function” for the
communication of inverters.
INV-NO
1 byte
This is always excluded at the master inverter side at time of inter-drive communication, and
can be added when the user utilize this data for the purpose of proportional operation.
(When this code is added, only the inverter concerned will accept the data.)
53H(“S”) or 73(“s”) command ... command for inter-drive communication
When the master inverter is not tripping, this will be 53H(“S”).
When the master inverter is tripping, this will be 73H(“s”).
Communication number of frequency command (FA01).
(0000H to FFFFH (no range check))
CMD
1 byte
Checksum range
Communication number
2 bytes
DATA
2 bytes
SUM
1 byte
Not omissible
39
Page 42
7. Communications parameters
The settings of communication-related parameters can be changed from the operation panel and the
external controller (computer). Note that there are two types of parameters: parameters whose settings take effect immediately after the setting and parameters whose settings do not take effect until
the inverter is turned back on or reset.
Com-
munica-
tion
Number.
0800
0801
0802
0803
0805
0806
0811
0812
0813
0814
0829
0870
0871
0875
0876
0877
0878
0879
0880
TitleFunctionAdjustment rangeUnit
0: 1200bps
Communication
baud rate
Parity
Inverter number0-25510Real timeSection 7.2
Communication
error trip time
Communication
waiting time
Setting of master
and slave inverters
for communication
between inverters
(setting of master
and slave)
Point 1 setting0-1001%0Real time
Point 1 frequency0.0-500.0Hz0.01Hz0.0Real time
Point 2 setting0-1001%100Real time
Point 2 frequency0.0-500.0Hz0.01Hz60.0Real time
Selection of communication protocol
Block write data 1
Block write data 2
Block read data 1
Block read data 2
Block read data 3
Block read data 4
Block read data 5
Free notes0-6553510Real timeSection 7.5
1: 2400bps
2: 4800bps
3: 9600bps
4: 19200bps
0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
0: No selection
1: Command information 1
2: Command information 2
3: Frequency command
4: Output data on the terminal board
5: Analog output for communications
0: No selection
1: Status information
2: Output frequency
3: Output current
4: Output voltage
5: Alarm information
6: PID feedback value
7: Input terminal board monitor
8: Output terminal board monitor
9: VIA terminal board monitor
10: VIB terminal board monitor
E6581222
Default
setting
-3After reset.Section 7.1
-1After reset.Section 7.1
1s0Real timeSection 7.3
-0After reset.
-0After reset.
-
-0
0
ValidReference
Chapter 6
Section 6.1
Chapter 3
After reset.
Section
4.1.3
After reset.
40
Page 43
7.1. Communication baud rate() , Parity bit()
•Communication baud rate and parity bit should be uniform inside the same network.
•This parameter is validated by resetting the power supply.
7.2. Inverter number()
This parameter sets individual numbers with the inverters.
Inverter numbers should not be duplicate inside the same network.
Receiving data will be canceled if inverter numbers specified in individual communications and set by
a parameter do not match.
This parameter is validated from the communication after change
Data range: 0 to 255 (Initial value: 0)
Parameters can be selected between 0 and 255. Note that the communication protocols limit inverter numbers as follows:
● TOSHIBA Inverter Protocol ASCII mode: 0 to 99
● TOSHIBA Inverter Protocol Binary mode: 0 to 63
● MODBUS Protocol: 0 to 247
E6581222
41
Page 44
7.3. Timer function()
This function detects any normal data that is not detected even once within an arbitrarily predetermined time.
The timer function is used to detect breaks in cables during communications and to trip an inverter
(
) if the inverter has received no data within the time specified using this function. If the in-
verter number does not match or if a format error occurs, preventing the inverter from returning data
to the computer, this function will assume that the inverter has not received any data.
■ How to set the timer
The communication error trip time parameter () is set to 0 (timer off) by default.
* Timer adjustment range
About 1 sec. (01H) to about 100 sec. (64H) / Timer off (0H)
■ How to start the timer
If the timer is set from the operation panel, it will start automatically the instant when communication
is established for the first time after the setting.
If the timer is set from the computer, it will start automatically the instant when communication is established after the setting.
If the timer setting is stored in the EEPROM, the timer will start when communication is established
for the first time after the power has been turned on.
Note that, if the inverter number does not match or if a format error occurs, preventing the inverter
from returning data, the timer function will assume that no communication has taken place and will
not start.
E6581222
■ How to disable the timer
To disable the timer, set its parameter to 0.
Ex.: To disable the timer function from the computer (To store the timer setting in the EEPROM)
■ Timer
Computer link
Computer → InverterInverter
(W08030)CR(W08030000)CR ... Sets the timer parameter to 0 to disable it.
Time-out period
INV → PC
→ Computer
PC → INVPC → INV
The timer measures the time
elapsed before the inverter acknowledges receipt of data after it
acknowledged receipt of the previous data.
42
Page 45
7.4. Setting function of communication waiting time ()
Use this function for the following case:
When the data response from the inverter is too quick after the PC had sent the data to the inverter,
PC process cannot get ready to receive the data, or when the RS485/RS232C converter is used,
changeover of sending and receiving data takes much time in the converter process.
The case of " Inter-drive communication ", set up more than 0.03 seconds as a transmitting interval
on the master side to wait for the processing time on the slave side(
* This function, however, does not operate in case the MODBUS-RTU protocol is selected in com-
munication protocol selection. (
Functional specification:
A time for sending data is prolonged longer than the preset time, until the inverter returns the data to
the PC, after it finishes receiving the data (in case of an inter-drive communication, until the inverter
returns the next data to the PC, after it has sent the data.) In case the inverter's processing capacity
requires longer setting time, the value more than this time will be the set value. (The parameter makes the inverter wait for more than the set time.)
=)
= ).
E6581222
Computer link
Inter-drive
communication
Setting range:
If the set value is
maximum capacity of the inverter. To obtain a quick response for sending data, set value
PC→INV
Master INV
to Slave INV
to seconds (10ms to 2000ms)
, this function becomes invalid and the interval time for sending data is set to the
Time elapses more than
transmission waiting time.
Time elapses more than the
transmission waiting time.
7.5. Free notes()
INV→PC
Master INV to
Slave INV
.
Time from the confirmation of the
data reception (transmission, in the
case of inter-drive communication)
to the transmission of data, is
adjusted.
If the inverter's processing time
requires longer time than the
transmission waiting time, the time
is prolonged.
This parameter allows you to write any data, e.g., the serial number of each inverter or parameter
information, which does not affect the operation of the inverter.
43
Page 46
8. Commands and monitoring from the computer
9
9
9
9
9
9
9
9
9
9
9
Across the network, instructions (commands and frequency) can be sent to each inverter and the
operating status of each inverter can be monitored.
8.1. Communication commands (commands from the computer)
■ Communication command (Communication number: FA00)
Commands can be executed on inverter frequencies and operation stop through communications.
The VF-S11 series can enable command and frequency settings through communications irrespective of settings of the command mode (
Forced change from communication to local,” “52: Forced operation,” or “53: Fire speed” is set by input terminal function selection (
tion and to a frequency command is feasible through a contact on the terminal board.
Once the communication command (FA00) is set to enable communication command priority and
frequency priority, both priorities will be enabled unless OFF is set, power is turned off or is reset, or
standard shipment setting (
terminal output hold are always enabled even though communication command priority is not set.
Table 1 Data construction of communication commands (communication number: FA00)
bit Specifications01S7 S9/nC1/S11Remarks
0 Preset speed operation
frequencies 1
1 Preset speed operation
frequencies 2
2 Preset speed operation
frequencies 3
3 Preset speed operation
frequencies 4
4 Motor selection (1 or 2)
(THR 2 selection)
5 PI controlNormal operationPI OFF-9
6 Acceleration/deceleration
pattern selection (1 or 2)
(AD2 selection)
7 DC brakingOFFForced DC braking
8 Jog runOFFJog run
9 Forward/reverse run
Note: For the reset command, no data will be returned.
Ex.: Forward run: (PFA008400) CR
Preset speed operation is disabled or
preset speed operation frequencies (1-
15) are set by specifying bits for preset
speed operation frequencies 1-4.
(0000: Preset speed operation OFF,
001-1111: Setting of preset speed
operation frequencies (1-15))
Motor 1
(THR 1)
Accelera-
tion/deceleration
pattern 1 (AD1)
Forward runReverse run
OFFEnabled
OFFEnabled
1 is specified for bit 15 (communication command: enabled) and bit 10 (operation command).
FA00:
BIT15BIT0
1000010000000000
to ), a change to a command other than communica-
) is selected. Emergency stop, RY terminal output hold and OUT
tion/deceleration
pattern 2 (AD2)
8
) and frequency mode (). However, if “48:
Motor2
(THR2)
Accelera-
9
-9THR1 : PT=set value, vL, vb, tHr
9AD1 : ACC, DEC,
Preset speed operation can be
disabled or a preset speed operation frequencies (1-15) can
be specified by combining 4 bits
variously.
THR2 : PT=0, F170, F172, F173
AD2 : F500, F501
9
9
9
9
9
9“E” trip
9No data is returned from the
inverter.
9Enabled regardless of the set-
ting of
9Enabled regardless of the set-
ting of
004
E6581222
Ex.: Reverse run: (PFA008600) CR, (PFA00C600) CR
8600H : To disable frequency instructions from the computer
C600H : To enable also frequency instructions from the computer
44
Page 47
Communication command2 (Communication Number : FA20)
This command is enabled only when the communication command is enabled. Set Bit 15 of Communication Command 1 (communication Number: FA00) to “1” (enable). When enabling the communication command by Communication Command 1, commands by communications can be given
the priority irrespective of the setting of the command mode selection parameter (
ever, if “48: Forced change from communication to local,” “52: Forced operation,” or “53: Fire speed”
is set by input terminal function selection (
will be given the priority.
Once enabled, this setting will be enabled till disable is set (0 setting), power is turned off or is reset,
or standard shipment setting (
Table 2 Data construction of serial communication command 2 (FA20)
Note: The acceleration/deceleration change command ORs with Bit 6 of Communication number
FA00. Set Bit 6 of FA00 to “0” and use FA20 when changing acceleration/deceleration in
three types. Acceleration/deceleration 3 will be set when both Bit 8 of Communication number FA20 (or Bit 6 of Communication number FA00) and Bit 9 of Communication number
FA20 are set.
on, a RY terminal
holds that condition.
Once it is turned
on, an OUT terminal holds that
condition.
E6581222
Always enabled even if
communication command
is not enabled
Always enabled even if
communication command
is not enabled
Frequency setting from the computer (communication number: FA01)
Setting range: 0 to Maximum frequency ()
This frequency command is enabled only when the frequency command by communication is en-
abled by setting “serial communication (“3” for Communication Number FA04) by the speed command selection parameter (
FA00 to “1” (enable)) by the communication command. In this case, frequency commands by
communication will be enabled independent of
frequencies are given the priority if “48: Forced change from communication to local,” “52: Forced
operation,” or “53: Fire speed” is set by input terminal function selection (
Once enabled, this frequency setting will be enabled till disable is set (0 setting), power is turned off
or is reset, or standard shipment setting (
Set a frequency by communication hexadecimal in Communication Number FA01. (1 = 0.01Hz
(unit))
Operating status 4(status immediately before the occurrence of a trip):
Communication Number FE49
Operating status 4(current status):Communication Number FD49
BitFunction01Remarks
0RY terminal output holdOFFHolding
1OUT terminal output holdOFFHolding
2 to 15 (Reserved)
−−
48
Page 51
Inverter operating command mode status (FE45)
The monitor of the command mode that the present condition is enabled
DataEnabled command
0Terminal board
1Operation panel
2Serial communication
Inverter operating frequency mode status (FE46)
The monitor of the frequency command mode that the present condition is enabled
Note that Preset speed operation frequencies is given the priority independent of the frequency
mode, in which case this monitor will be disabled, in case Preset speed operation frequencies is selected.
DataEnabled frequency
0Potentiometer at Operation panel
1VIA
2VIB
3Operation panel
4Serial communications
5TB up down frequency
6VIA + VIB
E6581222
49
Page 52
Alarm information monitor (FC91)
E6581222
BitSpecifications01
0Over-current alarmNormalAlarming flickering
1Inverter overload alarmNormalAlarming
2Motor overload alarmNormalAlarming
3Overheat alarmNormalAlarming
4Overvoltage alarmNormalAlarming
5Main circuit undervoltage alarmNormalAlarming-
6(Reserved)---
7Low current alarmNormalAlarming-
8Over-torque alarmNormalAlarming-
Braking resistor overload alarm
9
Cumulative operation hours
10
alarm
11(Reserved)---
12(Reserved)---
13Main-circuit voltage error alarmNormalAlarming“ flickering
At the time of the instant black-
14
out, Forced deceleration/stop
An automatic stop during the
15
lower limit frequency continuance
NormalAlarming-
NormalAlarming-
-
-
Decelerating,
stopping
Decelerating,
stopping
(Code displayed on the panel)
Related: F256 setting
Related: F302 setting
Remarks
flickering
flickering
flickering
flickering
Cumulative operation time alarm monitor (FE79)
BitSpecifications01Remarks
0Fan life alarmNormalAlarm issued-
1Circuit board life alarmNormalAlarm issued-
2Main-circuit capacitor life alarmNormalAlarm issued-
number)
00 No error
11 Over-current during acceleration
22 Over-current during deceleration
33 Over-current during constant speed operation
44 Over-current in load at startup
55 Short circuit in arm
88 Input phase failure
99 Output phase failure
A10 Overvoltage during acceleration
B11 Overvoltage during deceleration
C12 Overvoltage during constant speed operation
D13 Over-LOAD in inverter
E14 Over-LOAD in motor
1016 Overheat trip
1117 Emergency stop
1218 EEPROM fault 1 (writing error)
1319 EEPROM fault 2 (reading error)
1420 EEPROM fault 3 (internal fault)
1521 RAM fault
1622 ROM fault
1723 CPU fault
1824 Communication error trip
1A26 Current detector fault
1B27 Optional circuit board type error
1D29 Small-current trip
1E30 Trip due to undervoltage in main circuit
2032 Over-torque trip
2234 Ground fault trip (hardware detection)
2537 Overcurrent flowing in element during acceleration
2638 Overcurrent flowing in element during deceleration
2739 Overcurrent flowing in element during operation
2941 Inverter type error
2E46 External thermal input
2F 47 PM motor step-out
32 50
3351 CPU fault
3452 Excess torque boost
3553 CPU fault
5484 Auto-tuning error
8.3. Control of input/output signals from communication
The input terminals, output terminals, analog input and output signals of the inverters can be controlled by communications.
Terminal Output Data (FA50)
The output terminals on the inverters can be controlled directly by communications.
Before controlling them, select Function Number 38 to 41 in Output Terminal Function Selection
(
- , ,). Set data (0 or 1) can be output to the output terminals by
setting data of Bit 0 and Bit 1 of terminal output data (FA50) by communications.
Data construction of Terminal Output Data (FA50)
BitOutput Terminal Function01
0Specified data output 1
(Output terminal selection Number : 38, 39)
1Specified data output 2
(Output Terminal Selection Number : 40, 41)
2 to 15
−−−
OFFON
OFFON
E6581222
Example : Controlling only Terminal OUT1 by communication
Set “38” (specified data output 1 [positive logic]) in Output Terminal Selection 1 (
advance and set “0001H” in FA50 to turn Terminal OUT1 on.
FA50:
BIT15BIT0
0000000000000001
Analog Output Data (FA51)
The analog terminals on the inverters, such as Terminal FM can be controlled directly by communications.
Select “18” (communication analog output) in Analog Terminal Connection Selection Parameters
(example: FM terminal connection meter selection [
Data set in Analog Output Data (FA51) can be output from the selected analog terminal. The data
adjustment range is 0 to 1023 (10bit resolution) . Refer to “Meter Setting and adjustment” in the instruction manual for inverters for the complete information.
) in
0
]) before controlling them.
100
53
Page 56
Input terminal board status (FD06, FE06)
Input terminal board status (status immediately before the occurrence of a trip):
Input terminal board status (current status):Communication Number FD06
In case “0: No assignment function” is selected in function selection, inverter operations will not be
affected even when terminals are turned on and off. Therefore, the terminals can be used as input
terminals for customer’s own use.
The input terminal function selection parameter is used to select a function for each input terminal.
When monitoring the operating status, check what function is assigned to each internal terminal.
Data construction of input terminal board (FE06)
BitTerminal name (extended)Function (parameter title)01
1: It is valid only when it is selected as contact input by .
It is effective only when it is chosen with F109 for input of a contact point.
Ex.: FE06 data when the F and S1 terminals are ON: 0009H
BIT15BIT0
FE06:
0000000000001001
0
0
Communication Number FE06
0
9
E6581222
Output terminal board status (FD07, FE07)
Output terminal board status (status immediately before the occurrence of a trip):
Output terminal board status (current status):Communication Number FD07
The output terminal function selection parameter is used to select a function for each output terminal.
When monitoring the operating status, check what function is assigned to each output terminal.
Data construction of output terminal board (FD07,FE07)
BitTerminal nameFunction (parameter title)01
0RY Output terminal selection1(f130)OFF ON
1OUT Output terminal selection1(f131)OFF ON
2FL Output terminal selection3(f132)OFF ON
3 ∼ 15----
Ex.: FE07 data when both the RY and OUT terminals are ON: 0003H
BIT15BIT0
FE07:
0000000000000011
0
0
Communication Number FE07
0
3
54
Page 57
Analog Input Monitors (FE35, FE36)
Analog input value VIA monitor: “Communication Number FE35”
Analog input value VIB monitor: “Communication Number FE36”
Data: 10bit resolution (Data range 0 to 1023)
These monitors can also be used as an A/D converter independent of inverter control.
Setting except for “VIA” as the frequency setting mode will allow analog input (VIA) as an A/D converter independent of inverter control.
Setting other than “VIB” as the frequency setting mode will allow analog input (VIB) as an A/D converter independent of inverter control.
Note, however, input data to analog terminals will be regarded as frequency commands in case
analog input is selected in frequency setting mode selection.
E6581222
55
Page 58
8.4. Utilizing panel (LEDs and keys) by communication
The VF-S11 can display data that is not related to the inverters through an external controller or other
means. Input by key operations can also be executed. The use of inverter resources reduces the
cost for the entire system.
8.4.1. LED setting by communication
Desired LED information can be displayed by communication.
<How to Set>
Set the standard monitor display selection parameter to “communication LED setting (
When in the standard monitor mode status, LED information is displayed according to the setting of
Communication Number FA65. (Is set to Communication Number FA65 = 1 and initial data “dAtA”
inshipment setting)
In case of an alarm while setting communication LEDs, the alarm display will alternately display
specified LED data and alarm message.
For example, if an over-current alarm (alarm display “
function, “
” and “.” will be displayed alternately.
”) occurs while “.” is displayed by this
E6581222
=).”
Commu-
nication
Number.
FA65Select display by communication0: Numeric data (FA66, FA67, FA68)
FA66Numeric display data
(Enabled if FA65=0)
FA67Decimal point position
(Enabled if FA65=0)
FA68LED data 0 for unit
(Enabled if FA65=0)
FA70ASCII display data 1, first digit from
left
(Enabled if FA65=1)
FA71ASCII display data 1, second digit
from left
(Enabled if FA65=0)
FA72ASCII display data 1, third digit from
left
(Enabled if FA65=1)
FA73ASCII display data 1, fourth digit from
left
(Enabled if FA65=1)
FA74LED data 1 for unit
(Enabled if FA65=1)
FA75ASCII display data 2, first digit from
left
(Enabled if FA65=2)
FA76ASCII display data 2, second digit
from left
(Enabled if FA65=2)
FA77ASCII display data 2, third digit from
left
(Enabled if FA65=2)
FA78ASCII display data 2, fourth digit from
left
(Enabled if FA65=2)
FA79LED data 2 for unit
(Enabled if FA65=2)
Parameter NameRange
1: ASCII data 1 (FA70, FA71, FA72, FA73,
FA74)
2: ASCII data 2 (FA75, FA76, FA77, FA78,
FA79)
0-99990
0: No decimal point (xxxx)
1: First digit below decimal point (xxx.x)
2: Second digit below decimal point (xx.xx)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
0 – 256 (0 – FFH)
(See ASCII LED display code chart)
0 – 256 (0 – FFH)
(See ASCII LED display code chart)
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
0 – 256 (0 – FFH)
(See ASCII LED display code chart)
0 – 256 (0 – FFH)
(See ASCII LED display code chart))
0 – 127 (0 – 7FH)
(See ASCII LED display code chart)
0:Hz off, % off, 1:Hz on, % off
2:Hz off, % on, 3:Hz on, % on
Shipment
setting
1
0
0
64H (’d’)
41H (’A’)
74H (’t’)
41H (’A’)
0
30H (’0’)
30H (’0’)
30H (’0’)
30H (’0’)
0
56
Page 59
Block Communication Function for LED Display
To display LED data for ASCII display that is synchronized to each digit, set data for each digit and
validate this set data by display selection by communication (Communication Number FA65).Syn-
chronization can also be achieved by batch writing LED data parameters after changing the following
block communication mode parameters and by sending data by block communication.
Writing in the block communication function will be writing in the RAMs only due to the EEPROM life
for write operations. The LED data will reset to the initial value “
off, in failure resetting or when standardshipment settingsare set.
■ Parameter Setting
“Block communication mode (Communication Number FA80)”
Setting range: 0, 1 (Initial value 0)
0: Block communication parameters (
1: LED display ASCII data is used (When writing, ASCII display data 1 [Communication Number
FA70 - FA74], when reading, LED data displayed before change)
*To validate LED data set by using LED display block communications, set standard monitor display
selection to “communication LED select (
“ASCII data 1 (Communication Number FA65).
- ) is used
= ) and display selection by communication to
E6581222
“ when the power is turned
■ Format
The format is the same as that used in the usual block communication mode. (For the detail information, see “4.1.3 Block communication transmission format”) The block communication parameters (
- ) will become invalid. Write data will become ASCII display data 1 (Commu-
nication Number :FA70 - FA74) fixed. LED display data that is actually being output will be read
during reading. The specification range for write operations is 0 to 5.
■ Example
Assuming:
Communication LED selection (
ASCII data 1 (Communication Number:FA65 = 1) for display selection by communication.
LED display ASCII data (Communication Number: FA80 = 1) for the block communication mode.
Current LED display status is display of initial value “
PC → Inverter: 2F580505003000310032003300035A
Inverter → PC: 2F59050000640041007400410000E7
= ) for standard monitor display selection.
”
・・・“0123” display command
・・ “dAtA” displayed before change
57
Page 60
E6581222
■ ASCII LED display data code (00H-1FH are blank.)
*Dots to show decimal points and other uses can be added by setting (80H) Bit 7 (highest bit).
Example: “0.” to display “60.0” can be added by “30H + 80H = B0H.”
58
Page 61
E6581222
r
8.4.2. Key utilization by communication
The VF-S11 can use the panel keys on the inverters through external communications. This function is available with CPU version 1 (Communication Number: FE08) = 104 or higher.
■ Key Monitoring Procedure
Set panel key selection (Communication Number: FA10) to “1” to set the external key mode. However, if communication duration is less than 1sec to avoid an inverter operation shutdown in communication disruption, communication must always be maintained, such as monitoring key data and
LED data to automatically reset inverter operations to inverter key operation (FA10 = 0). Set to the
external communication key mode (FA10 = 1) to disable the key function of the inverters so that inverter operation will not be affected by pressing of the keys on the inverters. By monitoring key information, which is input by the keys on the inverters in this condition, through inverter key data
(Communication Number; FC01), the keys on the inverters can be operated through a controller and
other devices.
* When the key mode is the external key mode, key operation as an inverter function is disabled and
the inverters cannot be stopped by pressing the STOP key to stop inverter operation. Enable
emergency stop through an external terminal or other device when an inverter stop is desired.
Panel Key Selection (Communication Number:FA10)
The panel key selection parameter (Communication Number; FA10) discriminates which keys are to be used, panel keys
on the inverters or keys sent by external communications, as panel keys used in panel processing of the inverters.
Communication No.:FC01
Panel key data of inverters
Communication No.:FA11
External communication
Keys on inverters enabled (Communication Number; FA10 = 0):
Key data: Data of keys on inverters (Communication Number : FC01)
FA10=”0”
FA10=”1”
Bit7Bit6Bit5Bit4Bit3Bit2Bit1Bit0
KPP
“KPP” for Bit 7 indicates that panel keys are mounted on the inverters.
Information of the enabled keys on the inverters can be monitored.
Bit7Bit6Bit5Bit4Bit3Bit2Bit1Bit0
KPP-ENTMONDOWNUPSTOPRUN
“KPP” for Bit 7 indicates that panel keys are enabled on the inverters.
59
Page 62
9. Parameter data
Explanation of parameters for VF-S11 series is described here. For communication purposes, see
the parameter list on inverter's instruction manual regarding the communication number, adjustment
range and so forth.
■ Referring to the parameter list
<Example of excerpts from the inverter’s instruction manual>
E6581222
Minimum
setting unit
Panel/Com
munication
--
--
Displays parameters in
groups of five in the reverse
order to that in which their
settings were changed.
* (Possible to edit)
0: Disabled (manual)
1: Automatic
2:Automatic (only at accelera-
0:Disabled
1:Automatic torque boost +
2:Vector control + auto-tuning
Title
auh
Communication No.
-History function--
0000
0001
Functionunit
Automatic ac-
celera-
tion/deceleration
Automatic tor-
que boost
:
:
0009
Acceleration
time1
S0.1/0.10.0-320010.05.1.2
:
Adjustment range
tion)
autotuning
3:Energy saving + auto-tuning
Default
setting
-
05.1.1
05.2
User
setting
Reference
4.1.4
- The summary of parameter list relating to the communication is as follows.
(1) “Title” means the display on the inverter panel.
(2) “Communication number” is affixed to each parameter that is necessary for designating the parameter for com-
munication.
(3) "Adjustment range" means a data range adjustable for a parameter, and the data cannot be written outside the
range. The data have been expressed in the decimal notation. For writing the data through the communication
function, take the minimum setting unit into consideration, and use hexadecimal system.
(4) "Minimum setup unit" is the unit of a single data (when the minimum unit is "-", 1 is equal to 1).
For example, the "minimum setup unit" of acceleration time () is 0.01, and 1 is equal to 0.01s. For setting a
data to 10 seconds, transmit 03E8h [10
÷0.01=1000d=03E8h] by communication.
60
Page 63
■ Command parameters
C
-
n
For those parameters that contain data only in the RAM and not in the EEPROM, their data return to
initial values when the power is turned off, in failure resetting, or when standard shipment settings
are set. Note that parameters without data storage in the EEPROMs will be written in the RAMs
only even if the command W (writing in EEPROMs and RAMs) is executed.
E6581222
■ Commands
ommunica
tion
Num-
ber.(HEX)
FA00Command 1 (Communication)
NOTE : Data is expressed in decimal notation.
Function
1
*
FA01Operation frequency command
value (Communication)
FA03Operation frequency command
value (Panel)
FA10
FA11External communication key
FA20Command 2 (Communication)
FA26Command 3 (Communication)
FA50
FA51
FA65Select display by communica-
FA66
FA67
FA68
Panel key selection
4
*
data
1
*
1
*
Terminal output data
Analog output data
4
*
tion
Numerical display data
Decimal point position
LED data for unit 0
FA70ASCII display data 1
First digit from left
FA71ASCII display data 1
Second digit from left
FA72ASCII display data 1
Third digit from left
FA73ASCII display data 1
Fourth digit from left
FA74
LED data for unit1
FA75ASCII display data 2
First digit from left
FA76ASCII display data 2
Second digit from left
FA77ASCII display data 2
Third digit from left
FA78ASCII display data 2
Fourth digit from left
FA79
FA80
LED data for unit 2
Block communication mode
2
*
4
*
3
*
3
*
*
4
*
4
*
4
*
4
*
4
*
4
*
4
*
4
*
4
*
4
*
4
*
4
*
Adjustment Range
0 to 65535
*
)
(
0 to Max. frequency
1
Low-limit frequency
) to High-limit
(
frequency (
)
0 to 1
0 to 65535
0 to 65535
0 to 65535
Min.
Setting
Unit
Initial
Value
−
0.01Hz0yesNone
0.01Hz0yesAvailable
−
−
−
−
Write
During
peratio
EEP
ROM
0yesNone
0yesNone
0yesNone
0yesNone
0yesNone
0 to 6553510yesNone
0 to 1023
10yesNone
(10-bit resolution)
0 to 2
4
0-999910yesAvailable
0 to 2
0 to 3
0 to 127
−
−
−
−
1yesAvailable
0yesAvailable
0yesAvailable
100
yesAvailable
(‘d’)
0 to 255
−
65
yesAvailable
(‘A’)
0 to 255
−
116
yesAvailable
(‘t’)
0 to 127
−
65
yesAvailable
(‘A’)
0 to 3
0 to 127
−
−
0yesAvailable
48
yesAvailable
(‘0’)
0 to 255
−
48
yesAvailable
(‘0’)
0 to 255
−
48
yesAvailable
(‘0’)
0 to 127
−
48
yesAvailable
(‘0’)
0 to 3
4
*
0 to 1
−
−
0yesAvailable
0yesAvailable
1
*
: Enable the communication command or communication frequency setting before setting these
parameters are set. Otherwise, the parameters will not function. See “8.1 Command by communication” for the method to enable them.
2
*
: Note that the Communication Number for operation frequency command values (panel) is FA02
in the VF-S7 and VF-S9 series.
3
*
: See “8.3 Control of input/output signals from communication” for the detail information.
4
*
: See “8.4 Utilizing panel (LEDs and keys) by communication” for the detail information.
61
Page 64
■ Monitor parameters * These parameters are read-only (monitor-only) parameters.
E6581222
Communi-
cation No.
TitleFunctionUnitRemarks
FC00-Monitor of key data (Effective data)-See 8.4.
FC01-Monitor of inverter keypad data-See 8.4.
FC90-Trip code-See 8.2.
FC91-Alarm code-See 8.2.
FD00-Operation frequency (current frequency)0.01Hz
FD01-Inverter status (current status)-See 8.2.
FD06-Input terminal information (current information)-See 8.3.
FD07-Output terminal information (current information)-See 8.3.
FD42-Inverter status2 (current status)-See 8.2.
FD49-Inverter status3 (current status)-See 8.2.
FE00-Operation frequency
FE01-Inverter status
FE02-Operation frequency command (actual instruction)
*5
*5
*5
0.01Hz
-See 8.2.
0.01Hz
FE03-Load current0.01%
FE04-Input Voltage0.01%
FE05-Output voltage
FE06-Input terminal information
FE07-Output terminal information
The communication response time can be calculated from data communication time and inverter
processing time.When wishing to know the communication response time, calculate using the following as a reference
E6581222
Data transmission time
PC → Inverte
Res
■ Data transmission time
* Number of bits = start bit + data frame length + parity bit + stop bit
* Minimum number of bits = 1 + 8 + 0 + 1 = 10 bits
* Maximum number of bits = 1 + 8 + 1 + 2 = 12 bits
<An example of the calculation of the transmission time: 19200 bps, 8 bytes, 11 bits>
■ Data processing time of inverter
Data processing time: maximum 20ms
Data processing time of inverte
Data transmission time
Inverter → PC
onse time
1
time ontransmissi Data××=
time ontransmissi Data=××=
rate baud
1
19200
4.6ms118
bits of numberdtransmitte bytes of number
64
Page 67
E6581222
Appendix 3 Compatibility with the communications func-
tion of the VF-S9
To provide consistency in communications procedures, the communications function of the VF-S11
series of inverters has been designed based on the protocols used for the Toshiba VF-S9 series of
inverters. With regard to compatibility, however, VF-S9 users should check the items described below before using the communications function of their inverters.
■ To VF-S9 inverter users:
Some parameters of the VF-S9 are different from those of the VF-S11 in function or adjustment
range (upper and lower limits), even though they have the same title or the same communication
number. So, when accessing a parameter, consult the VF- S9 inverter’s instruction manual to see if
the parameter is identical to the corresponding parameter of the VF-S11. If the parameter differs,
modify the computer program to suit your inverter. To avoid hazards, never copy parameters from
one model of inverter to another.
■ Comparison of communication-related items
The table below gives a comparison of communication-related items to be kept in mind when re-
placing VF-S9 inverters with VF-S11 inverters or when connecting VF-S9 inverters and VF-S11 inverters to the same network. It does not cover any items common to the VF-S9 and VF-S11 series of
inverters.
Model
Item
Data processing time of
inverter
♦ Do not use communications programs written for another series of inverters.
Even though parameters have the same title and the same communication number, they may be different
in function. When using a parameter, always check its specifications in the instruction manual for your
inverter. If the specifications of the parameter differ, modify the computer program to suit your inverter.
♦ To avoid hazards, do not copy parameters from one model of inverter to another.
Even though parameters have the same titles and communication numbers, they may be different in
function.
VF-S9VF-S11Reference
About 8 ms
(This is only standard time, not guarantee
time.)
Notice
maximum 20msAppendix 2
65
Page 68
Appendix 4 Troubleshooting
If a problem arises, diagnose it in accordance with the following table before making a service call. If
the problem cannot be solved by any remedy described in the table or if no remedy to the problem is
specified in the table, contact your Toshiba dealer.
ProblemRemediesReference
E6581222
Communications will not take
place.
An error code is returned.
The trip occurs.- Check the cable connection and the timer setting.Section 7.3
The slave of " Inter-drive communication " did an
Frequency instructions from the
computer have no effect.
Commands, including the run
and stop commands, from the
commuter have no effect.
A change to a parameter does
not take effect.
The setting of a parameter was
changed, but it returns to its
original setting when the inverter
is turned off.
err5 trip.
- Are both the computer and the inverter turned on?
- Are all cables connected correctly and securely?
- Are the same baud rate, parity and bit length set for every unit on the
network?
- Is the data transmission format correct?
- Does the data written fall within the specified range?
- Some parameters cannot be written during inverter operation.
Changing should be attempted when the inverter is in halt.
- Is a communication waiting time parameter on the master side set up?
Set bigger value than present value on the master's transmitting interval.
- Is the frequency setting mode selection parameter set to “computer”?Section 8.1
- Is the command mode selection parameter set to “computer”?Section 8.1
Some communications-related parameters do not take effect until the
inverter is reset. To make them take effect, turn the inverter off temporarily, then turn it back on.
When using the TOSHIBA Inverter Protocol, use the W command to
write data into the EEPROM. If you use the P command that writes data
into the RAMs only, the data will be cleared when the inverters are
reset.