24 V (ac) Transformer 013
Accessories
07/14
Replaces: New
Installation & Operation Manual
Introduction
The 24 V (ac) Transformer 013 has a 115 V (ac) primary and a 24 V (ac) secondary
with a capacity of 96 VA. A resettable circuit breaker protects the transformer from
overloading. A 4" x 4" electrical junction box is included for mounting.
1 of 4
© 2014
013_D - 07/14
-------------------------------------------------
------------------------------------------------------
It is the installers responsibility to ensure that this device is safely
--------------------------------------------------
installed according to all applicable codes and standards. tekmar
is not responsible for damages resulting from improper installation
and/or maintenance.
Read this Manual BEFORE using this equipment.
Failure to read and follow all safety and use information can result in
personal injury, property damage, or damage to the equipment.
Keep this Manual for future reference.
Disconnect all power before opening the device.
•
Improper installation and operation of this device could result in damage
•
to the equipment and possibly even personal injury or death.
Installation
Check the Contents
Check the contents of this package. If any of the contents listed are missing or
damaged, please refer to the Limited Warranty and Product Return Procedure on
the back of this brochure and contac t your wholesaler or tekmar sales representative
for assistance. Type 013 includes:
One 24 V (ac) Transformer 013
•
One Installation & Operation Manual 013_D
•
Preparation
Tools Required
Phillips screwdriver• Wire Stripper•
Materials Required
Wood screws
•
Wire nuts
•
Installation Location
Choose the placement of the 24 V (ac) early in the construction process to
enable proper wiring during rough-in.
Consider the following:
Keep dry. Avoid potential leakage onto the control.
•
No exposure to extreme temperatures beyond 32-122°F (0 to 50°C).
•
Easy access for wiring.
•
------------------------------------------------------
--------------------------------------------------
2 conductor, 18 AWG LVT solid wire
•
2 conductor with ground, 14 AWG cable
•
-------------------------------------------------
2 of 4
© 2014 013_D - 07/14