This document explains how to install a stand-alone M1500 or M2500.
Note:To install an M1500 or M2500 module in a multiple library stack,
refer to the Tandberg StackLink Installation Instructions
(PN T6423049).
Site Requirements0
When selecting an installation site for the library, consider the following
requirements:
•Space Requirements
•Cooling Considerations
•Environmental Requirements
•Power and Grounding
Space Requireme nts 0Table 1 lists the dimensions of the M1500 and M2500 libraries.
Caution:Allow at least 5 inches (12.7 cm) of space behind the library to
allow proper ventilation.
Table 1 Library
Dimensions
Cooling
Considerations
Height
Width
Depth
Cooling is one of the most important factors to consider when selecting a
0
location for the library. The M1500 and M2500 libraries are force-cooled: air is
drawn into the library through vents at the lower edge of the front bezel and
M1500M2500
6.9 in. (176 mm)23.4 in. (595 mm)
19 in. (482 mm)19 in. (482 mm)
28.6 in. (726 mm)28.6 in. (726 mm)
Introduction3
Tandberg Data M-Series Installation Guide
Vent
Document T6423046-02 A01
February 2004
exhausted through vents at the back of the library. To ensure that the library
is adequately ventilated:
•Place the library on a hard, level surface, or in a standard 19-inch rack.
•If the library will be placed in a rack, the rack must be open or ventilated
•Verify that no cables obstruct the vents at the back of the library (see
•Verify that nothing obstructs the vents at the lower edge of the front
•Allow at least 5 inches (12.7 cm) of space behind the library or rack.
•Do not install the library near a heater or radiator which could warm the
so that the air temperature behind the library at the air outlets is less than
104°F (40°C).
figure 1
and figure 2).
bezel.
air drawn into the library.
Figure 1 Vent Locations,
M1500
Figure 2 Vent Locations,
M2500
s
Vents
4Site Requirements
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Environmental
Requirements
Power and
Grounding
0
0
The installation site (desktop library) or the interior of the rack (rack mount
library) must meet the following environmental requirements:
•Humidity: 20% to 80%, non-condensing
•Temperature: 50°F to 104°F (10°C to 40°C)
•Altitude: -100 to +10,000 feet (-30 to +3,000 meters)
The M1500 and M2500 power supplies accept 88 VAC to 264 VAC input
power at 47 Hz to 63 Hz.
The library must be connected to a grounded power outlet. If the library is
mounted in a rack, the rack must also be grounded.
Installing a Desktop or Deskside Library0
This section explains how to install a desktop M1500 or a deskside M2500. To
install a rack mount library, see Installing a Rack Mount Library
Note:The procedures in this section assume that you have already
unpacked the library. If you have not, do so now, referring to the
Determining the
Position of the
Shelves in the Rack
0
Before starting the rack mount installation:
1 Determine the proper position of the shelves in the rack:
Caution:Take rack stability into account when determining
where to place the library in the rack.
•The rack is measured in rack mount units. Each unit is called a “U,”
and is equal to 1.75 inches (44.45 millimeters). When you look at the
rack rails you will notice that the holes are divided into groups of
three, with each group separated by a slightly smaller space. Each
group of three equally spaced holes is one U (see figure 3
•An M1500 uses 4U of vertical space. The M1500 rack mount shelves
must be installed in a full U position (the bottom of the rack mount
shelf must be aligned with the bottom of a U) (see figure 4
•An M2500 uses 13.5U of vertical space. The M2500 rack mount
shelves can be installed in either a full U or a half U position (the
bottom of the rack mount shelf may be aligned with either the bottom
or the middle of a U) (see figure 5
•The StackLink mounting hardware uses 1U of vertical space at the
top of the rack, and either 1U or .5U at the bottom of the rack (see the
Tandberg M-SeriesStackLink Installation Instructions, PN T6423049, for
more information).
2 Mark the desired shelf position on the rack rails.
).
).
).
6Installing a Rack Mount Library
Figure 3 Example of Full
and Half U Mounting
Positions
In the half U position, the bottom of the
mounting bracket aligns with the center of the
middle hole in the corresponding U. This
position can be used for M2500 rack mount
shelves only.
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
3 equally
spaced holes
equals 1 U
1 U
In the full U position, the bottom of the
mounting bracket aligns with the bottom of the
corresponding U. This position can be used
for either M1500 or M2500 rack mount
shelves
Figure 4 M1500 Shelf
Mounting Positions
M1500
Shelf mounting position
4U
Installing a Rack Mount Library7
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 5 M2500 Shelf
Mounting Positions
Shelf mounting position (half U position)
Installing the M1500
Rack Mount Shelves
M250013.5U
This section explains how to install the M1500 rack mount shelves.
0
Note:To install rack mount shelves for an M2500, see Installing the
M2500 Rack Mount Shelves on page 14.
Checking the Contents of the Rack Mount Kit
M2500
Shelf mounting position (full U position)
13.5U
0
Table 2 lists the contents of the M1500 Universal Rack Mount Kit.
Table 2 Contents, M1500
Universal Rack Mount Kit
Part No.DescriptionQty.
213467Shelf clamp4
213468Insert (9 sq)8
213469Insert (7 sq)8
213471Insert (M6)8
213472Insert (M5 or 12-24UNC)8
8Installing a Rack Mount Library
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Part No.DescriptionQty.
213473Insert (10-32UNF)8
213474Insert (1/4" dia)8
213476Universal shelf, right1
213477Universal shelf, left1
213478Shelf extender #11
213479Shelf extender #21
YS40403Plain washer M54
YS40403Plain washer M52
YS41720Button head socket screw 10-24 UNC x 0.5 ins2
YS41998Nut, M5 full4
YS42008M6 cage nut2
YS42011Button head socket screw M6 x 122
YS42038Countersink hex socket screw M4 X 10 LG4
YS42042Button head socket screw M5 x 122
YS42043Button head socket screw 10-32 UNC x 0.5 ins2
YS42044M5 spire nut2
Verifying That You Have the Required Tools0
The following tools are required to install the rack mount kit:
•8 mm open end wrench
•2.5 mm socket driver (preferably ball headed)
•Flat blade screwdriver
•Tape measure
Assembling the Rack Mount Shelves
1 Measure the distance between the inside surfaces of the front and rear
rack rails, then find the corresponding rack depth in table 3
.
0
2 Assemble the left shelf:
aRefer to the
Left Shelf/Shelf Extender column of table 3 to determine
which shelf extender to combine with the left universal shelf.
bInsert the posts on the left universal shelf into the shelf extender slots
identified in the
Left Shelf/Slots column of table 3.
The slots in the shelf extenders are identified as shown in figure 6
Installing a Rack Mount Library9
.
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
cUse the M5 nuts (PN YS41998) and M5 washers (PN YS40403)
provided in the rack mount kit to fasten the left shelf and shelf
extender together (see figure 7
).
Note:Tighten the nuts to finger-tightness only; you need to be able
to retract and extend the assembled shelves slightly.
Table 3 Shelf Assembly
Matrix
3 Assemble the right shelf in the same manner, referring to the
column of table 3
.
Left ShelfRight Shelf
Rack Depth
(between flanges)
24.50 in. - 26.75 in.
Shelf
ExtenderSlots
#2A & B#1A & B
Shelf
ExtenderSlots
(620 mm - 680 mm)
26.75 in. - 29.125 in.
#1B & C#2A & B
(680 mm - 740 mm)
29.125 in. - 31.50 in.
#2B & C#1B & C
(740 mm - 800 mm)
31.50 in. - 33.875 in
#1C & D#2B & C
(800 mm - 860 mm)
33.875 in. - 36.25 in.
#2C & D#1C & D
(860 mm - 920 mm)
Right Shelf
Figure 6 Identifying the
Shelf Extender Slots
A
B
10Installing a Rack Mount Library
C
D
Figure 7 Attaching the
Shelves to the Extenders
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Extender
Shelf
Installing the Rack Mount Shelves0
To install the rack mount shelves:
1 From the six sizes of inserts provided in the rack mount kit, select the
insert type that best fits the holes in the rack rails. The insert part
numbers are:
•213468 (for rails with 9 mm square holes)
•213469 (for rails with 7 mm diameter unthreaded holes)
•213471 (for rails with M6 threaded holes)
•213472 (for rails with M5 or 12-24 UNC threaded holes)
•213473 (for rails with 10-32 UNF threaded holes)
•213474 (for rails with 1/4 inch diameter unthreaded holes)
The heads of the inserts (not the threads) should fit into the holes in the
rack rails smoothly and with very little play.
2 Once you have selected the inserts for your rack, set the others aside. You
will not need them for this installation.
3 Screw the inserts into the two outer holes on each end of the assembled
shelves (see figure 8
).
Note:Some of the inserts have either no head or a head that has a
smaller diameter than the thread; these need to be left
protruding by about 1/8 in. (3 mm). The inserts with heads
should be tightened fully.
Installing a Rack Mount Library11
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 8 Installing the
Inserts in the Shelves
4 Install the left shelf (see figure 9):
Inserts
Figure 9 Installing the
Shelf in the Rack
aWith the shelf slightly retracted, position the shelf in the rack at the
desired mounting height.
bExpand the shelf so that the inserts on each end of the shelf protrude
into the holes in the rack rails and hold the shelf in place.
5 Repeat the above steps to install the right shelf.
Inserts protrude
through the
holes in the rails
12Installing a Rack Mount Library
Figure 10 Securing the
Shelf Clamp to the Rail
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
6 Secure the shelves (see figure 10):
aPosition a shelf clamp (PN 213467) on the front left rack rail.
The bottom of the shelf clamp should be flush with the bottom of the
shelf.
bSecure the shelf clamp to the rack rail using an M4 countersink screw
(PN YS42038).
cRepeat these steps to install shelf clamps at the front and back of each
shelf.
dTighten the nuts securing the shelves to the shelf extenders.
Shelf clamp
The shelf installation is now complete. Proceed to Installing the Library in
the Rack on page 28 to install the library.
Note:The universal rack mount kit contains screws and nuts for
many different types of rack. You will have many of these
screws and nuts left over after installing the rack mount
shelves and library.
Installing a Rack Mount Library13
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Installing the M2500
Rack Mount Shelves
Table 4 Contents, M2500
Universal Rack Mount Kit
This section explains how to install the M2500 rack mount shelves.
0
Note:To install rack mount shelves for an M1500, see Installing the
M1500 Rack Mount Shelves on page 8.
Checking the Contents of the Rack Mount Kit
Table 4 lists the contents of the M2500 Universal Rack Mount Kit.
Part No.DescriptionQty.
215812Front shelf clamp4
215201/01 Rear shelf clamp2
213468Insert (9 sq)12
213469Insert (7 sq)12
213471Insert (M6)12
213473Insert (10-32 UNF, 12-24 UNC, or M5)12
213474Insert (1/4 inch diameter)12
0
217405Clamp strip2
215197/02Universal shelf, right1
215198/02Universal shelf, left1
215199/01Shelf extender, long #11
215200/01Shelf extender, long #21
YS40403Plain washer M58
YS41998Nut, M5 full8
YS42064Countersink hex socket screw M4 x 12 LG12
Verifying That You Have the Required Tools0
The following tools are required to install the rack mount kit:
•8 mm open end wrench
•2.5 mm socket driver (preferably ball headed)
•Flat blade screwdriver
•Tape measure
14Installing a Rack Mount Library
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Assembling the Rack Mount Shelves0
To assemble the rack mount shelves:
1 Measure the distance between the inside surfaces of the front and rear
rack rails, then find the corresponding rack depth in table 5
.
2 Assemble the left shelf:
Table 5 Shelf Assembly
Matrix
aRefer to the
Left Shelf/Shelf Extender column of table 5 to determine
which shelf extender to combine with the left universal shelf.
bInsert the posts on the left universal shelf into the shelf extender slots
identified in the
Left Shelf/Slots column of table 5.
The slots in the shelf extenders are identified as shown in figure 11
cUse the M5 nuts (PN YS41998) and M5 washers (PN YS40403)
provided in the rack mount kit to fasten the left shelf and shelf
extender together (see figure 12
).
Note:Tighten the nuts to finger-tightness only; you need to be able
to retract and extend the assembled shelves slightly.
3 Assemble the right shelf in the same manner, referring to the
column of table 5
.
Right Shelf
Left ShelfRight Shelf
Rack Depth
(between flanges)
24.25 in. to 26.75 in.
Shelf
ExtenderSlots
Long #2A & BLong #1A & B
Shelf
ExtenderSlots
(617 mm to 680 mm)
.
26.75 in. to 29.125 in.
Long #1B & CLong #2A & B
(680 mm to 740 mm)
29.125 in. to 31.5 in.
Long #2B & CLong #1B & C
(740 mm to 800 mm)
31.5 in. to 33.875 in.
Long #1C & DLong #2B & C
(800 mm to 860 mm)
33.875 in. to 36.25 in.
Long #2C & DLong #1C & D
(860 mm to 920 mm)
Installing a Rack Mount Library15
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 11 Identifying the
Shelf Extender Slots
A
Figure 12 Attaching the
Shelves to the Extenders
B
A
C
B
D
C
D
Shelf
D
C
D
B
C
Extender
A
A
B
Installing the Shelves in a Half U Positi on0
To install the rack mount shelves in a half U position:
Note:The top and bottom libraries in a 3-high M2500 stack are mounted
in a half U position.
1 From the five sizes of inserts provided in the rack mount kit, select the
insert type that best fits into the holes in the rack rails. The heads of the
inserts (not the threads) should fit into the holes in the rack rails smoothly
and with very little play.
The insert part numbers are:
•213468 (for rails with 9 mm square holes)
•213469 (for rails with 7 mm diameter unthreaded holes)
•213471 (for rails with M6 threaded holes)
•213473 (for rails with 10-32 UNF, 12-24 UNC, or M5 threaded holes)
•213474 (for rails with 1/4 inch diameter unthreaded holes)
16Installing a Rack Mount Library
Loading...
+ 36 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.