This document explains how to install a stand-alone M1500 or M2500.
Note:To install an M1500 or M2500 module in a multiple library stack,
refer to the Tandberg StackLink Installation Instructions
(PN T6423049).
Site Requirements0
When selecting an installation site for the library, consider the following
requirements:
•Space Requirements
•Cooling Considerations
•Environmental Requirements
•Power and Grounding
Space Requireme nts 0Table 1 lists the dimensions of the M1500 and M2500 libraries.
Caution:Allow at least 5 inches (12.7 cm) of space behind the library to
allow proper ventilation.
Table 1 Library
Dimensions
Cooling
Considerations
Height
Width
Depth
Cooling is one of the most important factors to consider when selecting a
0
location for the library. The M1500 and M2500 libraries are force-cooled: air is
drawn into the library through vents at the lower edge of the front bezel and
M1500M2500
6.9 in. (176 mm)23.4 in. (595 mm)
19 in. (482 mm)19 in. (482 mm)
28.6 in. (726 mm)28.6 in. (726 mm)
Introduction3
Tandberg Data M-Series Installation Guide
Vent
Document T6423046-02 A01
February 2004
exhausted through vents at the back of the library. To ensure that the library
is adequately ventilated:
•Place the library on a hard, level surface, or in a standard 19-inch rack.
•If the library will be placed in a rack, the rack must be open or ventilated
•Verify that no cables obstruct the vents at the back of the library (see
•Verify that nothing obstructs the vents at the lower edge of the front
•Allow at least 5 inches (12.7 cm) of space behind the library or rack.
•Do not install the library near a heater or radiator which could warm the
so that the air temperature behind the library at the air outlets is less than
104°F (40°C).
figure 1
and figure 2).
bezel.
air drawn into the library.
Figure 1 Vent Locations,
M1500
Figure 2 Vent Locations,
M2500
s
Vents
4Site Requirements
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Environmental
Requirements
Power and
Grounding
0
0
The installation site (desktop library) or the interior of the rack (rack mount
library) must meet the following environmental requirements:
•Humidity: 20% to 80%, non-condensing
•Temperature: 50°F to 104°F (10°C to 40°C)
•Altitude: -100 to +10,000 feet (-30 to +3,000 meters)
The M1500 and M2500 power supplies accept 88 VAC to 264 VAC input
power at 47 Hz to 63 Hz.
The library must be connected to a grounded power outlet. If the library is
mounted in a rack, the rack must also be grounded.
Installing a Desktop or Deskside Library0
This section explains how to install a desktop M1500 or a deskside M2500. To
install a rack mount library, see Installing a Rack Mount Library
Note:The procedures in this section assume that you have already
unpacked the library. If you have not, do so now, referring to the
Determining the
Position of the
Shelves in the Rack
0
Before starting the rack mount installation:
1 Determine the proper position of the shelves in the rack:
Caution:Take rack stability into account when determining
where to place the library in the rack.
•The rack is measured in rack mount units. Each unit is called a “U,”
and is equal to 1.75 inches (44.45 millimeters). When you look at the
rack rails you will notice that the holes are divided into groups of
three, with each group separated by a slightly smaller space. Each
group of three equally spaced holes is one U (see figure 3
•An M1500 uses 4U of vertical space. The M1500 rack mount shelves
must be installed in a full U position (the bottom of the rack mount
shelf must be aligned with the bottom of a U) (see figure 4
•An M2500 uses 13.5U of vertical space. The M2500 rack mount
shelves can be installed in either a full U or a half U position (the
bottom of the rack mount shelf may be aligned with either the bottom
or the middle of a U) (see figure 5
•The StackLink mounting hardware uses 1U of vertical space at the
top of the rack, and either 1U or .5U at the bottom of the rack (see the
Tandberg M-SeriesStackLink Installation Instructions, PN T6423049, for
more information).
2 Mark the desired shelf position on the rack rails.
).
).
).
6Installing a Rack Mount Library
Figure 3 Example of Full
and Half U Mounting
Positions
In the half U position, the bottom of the
mounting bracket aligns with the center of the
middle hole in the corresponding U. This
position can be used for M2500 rack mount
shelves only.
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
3 equally
spaced holes
equals 1 U
1 U
In the full U position, the bottom of the
mounting bracket aligns with the bottom of the
corresponding U. This position can be used
for either M1500 or M2500 rack mount
shelves
Figure 4 M1500 Shelf
Mounting Positions
M1500
Shelf mounting position
4U
Installing a Rack Mount Library7
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 5 M2500 Shelf
Mounting Positions
Shelf mounting position (half U position)
Installing the M1500
Rack Mount Shelves
M250013.5U
This section explains how to install the M1500 rack mount shelves.
0
Note:To install rack mount shelves for an M2500, see Installing the
M2500 Rack Mount Shelves on page 14.
Checking the Contents of the Rack Mount Kit
M2500
Shelf mounting position (full U position)
13.5U
0
Table 2 lists the contents of the M1500 Universal Rack Mount Kit.
Table 2 Contents, M1500
Universal Rack Mount Kit
Part No.DescriptionQty.
213467Shelf clamp4
213468Insert (9 sq)8
213469Insert (7 sq)8
213471Insert (M6)8
213472Insert (M5 or 12-24UNC)8
8Installing a Rack Mount Library
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Part No.DescriptionQty.
213473Insert (10-32UNF)8
213474Insert (1/4" dia)8
213476Universal shelf, right1
213477Universal shelf, left1
213478Shelf extender #11
213479Shelf extender #21
YS40403Plain washer M54
YS40403Plain washer M52
YS41720Button head socket screw 10-24 UNC x 0.5 ins2
YS41998Nut, M5 full4
YS42008M6 cage nut2
YS42011Button head socket screw M6 x 122
YS42038Countersink hex socket screw M4 X 10 LG4
YS42042Button head socket screw M5 x 122
YS42043Button head socket screw 10-32 UNC x 0.5 ins2
YS42044M5 spire nut2
Verifying That You Have the Required Tools0
The following tools are required to install the rack mount kit:
•8 mm open end wrench
•2.5 mm socket driver (preferably ball headed)
•Flat blade screwdriver
•Tape measure
Assembling the Rack Mount Shelves
1 Measure the distance between the inside surfaces of the front and rear
rack rails, then find the corresponding rack depth in table 3
.
0
2 Assemble the left shelf:
aRefer to the
Left Shelf/Shelf Extender column of table 3 to determine
which shelf extender to combine with the left universal shelf.
bInsert the posts on the left universal shelf into the shelf extender slots
identified in the
Left Shelf/Slots column of table 3.
The slots in the shelf extenders are identified as shown in figure 6
Installing a Rack Mount Library9
.
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
cUse the M5 nuts (PN YS41998) and M5 washers (PN YS40403)
provided in the rack mount kit to fasten the left shelf and shelf
extender together (see figure 7
).
Note:Tighten the nuts to finger-tightness only; you need to be able
to retract and extend the assembled shelves slightly.
Table 3 Shelf Assembly
Matrix
3 Assemble the right shelf in the same manner, referring to the
column of table 3
.
Left ShelfRight Shelf
Rack Depth
(between flanges)
24.50 in. - 26.75 in.
Shelf
ExtenderSlots
#2A & B#1A & B
Shelf
ExtenderSlots
(620 mm - 680 mm)
26.75 in. - 29.125 in.
#1B & C#2A & B
(680 mm - 740 mm)
29.125 in. - 31.50 in.
#2B & C#1B & C
(740 mm - 800 mm)
31.50 in. - 33.875 in
#1C & D#2B & C
(800 mm - 860 mm)
33.875 in. - 36.25 in.
#2C & D#1C & D
(860 mm - 920 mm)
Right Shelf
Figure 6 Identifying the
Shelf Extender Slots
A
B
10Installing a Rack Mount Library
C
D
Figure 7 Attaching the
Shelves to the Extenders
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Extender
Shelf
Installing the Rack Mount Shelves0
To install the rack mount shelves:
1 From the six sizes of inserts provided in the rack mount kit, select the
insert type that best fits the holes in the rack rails. The insert part
numbers are:
•213468 (for rails with 9 mm square holes)
•213469 (for rails with 7 mm diameter unthreaded holes)
•213471 (for rails with M6 threaded holes)
•213472 (for rails with M5 or 12-24 UNC threaded holes)
•213473 (for rails with 10-32 UNF threaded holes)
•213474 (for rails with 1/4 inch diameter unthreaded holes)
The heads of the inserts (not the threads) should fit into the holes in the
rack rails smoothly and with very little play.
2 Once you have selected the inserts for your rack, set the others aside. You
will not need them for this installation.
3 Screw the inserts into the two outer holes on each end of the assembled
shelves (see figure 8
).
Note:Some of the inserts have either no head or a head that has a
smaller diameter than the thread; these need to be left
protruding by about 1/8 in. (3 mm). The inserts with heads
should be tightened fully.
Installing a Rack Mount Library11
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 8 Installing the
Inserts in the Shelves
4 Install the left shelf (see figure 9):
Inserts
Figure 9 Installing the
Shelf in the Rack
aWith the shelf slightly retracted, position the shelf in the rack at the
desired mounting height.
bExpand the shelf so that the inserts on each end of the shelf protrude
into the holes in the rack rails and hold the shelf in place.
5 Repeat the above steps to install the right shelf.
Inserts protrude
through the
holes in the rails
12Installing a Rack Mount Library
Figure 10 Securing the
Shelf Clamp to the Rail
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
6 Secure the shelves (see figure 10):
aPosition a shelf clamp (PN 213467) on the front left rack rail.
The bottom of the shelf clamp should be flush with the bottom of the
shelf.
bSecure the shelf clamp to the rack rail using an M4 countersink screw
(PN YS42038).
cRepeat these steps to install shelf clamps at the front and back of each
shelf.
dTighten the nuts securing the shelves to the shelf extenders.
Shelf clamp
The shelf installation is now complete. Proceed to Installing the Library in
the Rack on page 28 to install the library.
Note:The universal rack mount kit contains screws and nuts for
many different types of rack. You will have many of these
screws and nuts left over after installing the rack mount
shelves and library.
Installing a Rack Mount Library13
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Installing the M2500
Rack Mount Shelves
Table 4 Contents, M2500
Universal Rack Mount Kit
This section explains how to install the M2500 rack mount shelves.
0
Note:To install rack mount shelves for an M1500, see Installing the
M1500 Rack Mount Shelves on page 8.
Checking the Contents of the Rack Mount Kit
Table 4 lists the contents of the M2500 Universal Rack Mount Kit.
Part No.DescriptionQty.
215812Front shelf clamp4
215201/01 Rear shelf clamp2
213468Insert (9 sq)12
213469Insert (7 sq)12
213471Insert (M6)12
213473Insert (10-32 UNF, 12-24 UNC, or M5)12
213474Insert (1/4 inch diameter)12
0
217405Clamp strip2
215197/02Universal shelf, right1
215198/02Universal shelf, left1
215199/01Shelf extender, long #11
215200/01Shelf extender, long #21
YS40403Plain washer M58
YS41998Nut, M5 full8
YS42064Countersink hex socket screw M4 x 12 LG12
Verifying That You Have the Required Tools0
The following tools are required to install the rack mount kit:
•8 mm open end wrench
•2.5 mm socket driver (preferably ball headed)
•Flat blade screwdriver
•Tape measure
14Installing a Rack Mount Library
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Assembling the Rack Mount Shelves0
To assemble the rack mount shelves:
1 Measure the distance between the inside surfaces of the front and rear
rack rails, then find the corresponding rack depth in table 5
.
2 Assemble the left shelf:
Table 5 Shelf Assembly
Matrix
aRefer to the
Left Shelf/Shelf Extender column of table 5 to determine
which shelf extender to combine with the left universal shelf.
bInsert the posts on the left universal shelf into the shelf extender slots
identified in the
Left Shelf/Slots column of table 5.
The slots in the shelf extenders are identified as shown in figure 11
cUse the M5 nuts (PN YS41998) and M5 washers (PN YS40403)
provided in the rack mount kit to fasten the left shelf and shelf
extender together (see figure 12
).
Note:Tighten the nuts to finger-tightness only; you need to be able
to retract and extend the assembled shelves slightly.
3 Assemble the right shelf in the same manner, referring to the
column of table 5
.
Right Shelf
Left ShelfRight Shelf
Rack Depth
(between flanges)
24.25 in. to 26.75 in.
Shelf
ExtenderSlots
Long #2A & BLong #1A & B
Shelf
ExtenderSlots
(617 mm to 680 mm)
.
26.75 in. to 29.125 in.
Long #1B & CLong #2A & B
(680 mm to 740 mm)
29.125 in. to 31.5 in.
Long #2B & CLong #1B & C
(740 mm to 800 mm)
31.5 in. to 33.875 in.
Long #1C & DLong #2B & C
(800 mm to 860 mm)
33.875 in. to 36.25 in.
Long #2C & DLong #1C & D
(860 mm to 920 mm)
Installing a Rack Mount Library15
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 11 Identifying the
Shelf Extender Slots
A
Figure 12 Attaching the
Shelves to the Extenders
B
A
C
B
D
C
D
Shelf
D
C
D
B
C
Extender
A
A
B
Installing the Shelves in a Half U Positi on0
To install the rack mount shelves in a half U position:
Note:The top and bottom libraries in a 3-high M2500 stack are mounted
in a half U position.
1 From the five sizes of inserts provided in the rack mount kit, select the
insert type that best fits into the holes in the rack rails. The heads of the
inserts (not the threads) should fit into the holes in the rack rails smoothly
and with very little play.
The insert part numbers are:
•213468 (for rails with 9 mm square holes)
•213469 (for rails with 7 mm diameter unthreaded holes)
•213471 (for rails with M6 threaded holes)
•213473 (for rails with 10-32 UNF, 12-24 UNC, or M5 threaded holes)
•213474 (for rails with 1/4 inch diameter unthreaded holes)
16Installing a Rack Mount Library
Figure 13 Installing Inserts
at the Front of the Shelves
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
These inserts will be screwed into the holes in the front and rear flanges
of the rack mount shelves.
2 Once you have selected the inserts for your rack, set the others aside. You
will not need them for this installation.
3 Screw three inserts into the front flange of each rack mount shelf in
positions 2, 6, and 10 (counting from the bottom up, with 1 being the
lowest hole) (see figure 13
).
Note:Some of the inserts have either no head or a head that has a
smaller diameter than the thread; these need to be left
protruding by about 1/8 in. (3 mm). The inserts with heads
should be tightened fully.
10
6
2
4 Screw three inserts into the rear flange of each rack mount shelf in the
positions shown in figure 14
. If the shelves are oriented so the group of
six holes is at the bottom and the group of four holes is at the top, the
inserts go into holes 2, 6, and 9 (counting from the bottom up, with 1
being the lowest hole).
Note:Some of the inserts have either no head or a head that has a
smaller diameter than the thread; these need to be left
protruding by about 1/8 in. (3 mm). The inserts with heads
should be tightened fully.
10
6
2
Installing a Rack Mount Library17
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 14 Installing Inserts
at the Rear of the Shelves
5 Install the shelves (see figure 15):
Group of 6
2
Group of 4
Group of 4
Group of 6
6
9
9
6
2
aWith the shelf slightly retracted, position the shelf in the rack at the
desired mounting height.
bExpand the shelf so that the inserts on each end of the shelf protrude
into the holes in the rack rails and hold the shelf in place.
Figure 15 Installing the
Shelves
cRepeat these steps to install the remaining shelf.
Inserts protrude
through the
holes in the rails
18Installing a Rack Mount Library
Figure 16 Installing the
Front Shelf Clamps
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
6 Install the front shelf clamps (see figure 16):
aPosition a front shelf clamp (PN 215812) on the front left rack rail.
The square holes in the front shelf clamp should be aligned with the
upper two inserts in the front shelf flange.
bSecure the front shelf clamp to the rack rail using two M4 countersink
screws (PN YS42064).
cRepeat these steps to install a front shelf clamp on the front right rack
rail.
Installing a Rack Mount Library19
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
7 Install the rear shelf clamps (see figure 17):
Figure 17 Installing the
Rear Shelf Clamps
aPosition a rear shelf clamp (PN 215201/01) on the rear left rack rail,
aligning the square hole with the middle insert in the shelf flange.
bVerify that two of the round holes line up with holes in the rack
mount shelf. If two of the holes do not line up, rotate the clamp 180
degrees.
cSecure the rear shelf clamp to the shelf using two M4 countersink
screws (PN YS42064).
dRepeat these steps to install a rear shelf clamp on the rear right rack
rail.
Note:The left and right rear shelf clamps will be oriented differently
from one another.
20Installing a Rack Mount Library
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
8 Install the clamp strips (see figure 18):
aPosition a front shelf clamp (PN 215812) at the front of the front left
rack rail, with the bottom of the clamp approximately 15.5 inches (394
millimeters) above the bottom of the rack mount shelf.
Caution:The top of the front shelf clamp must be no more than 580
mm above the bottom of the rack mount shelf.
bPosition a clamp strip (PN 217405) behind the front left rack rail,
aligning it with the front shelf clamp.
cInsert a screw (PN YS42064) through the upper hole in the front shelf
clamp, through the rack rail, and into the upper hole in the clamp
strip.
dInsert a screw (PN YS42064) through the bottom hole in the front
shelf clamp, through the rack rail, and into the bottom hole in the
clamp strip.
Figure 18 Installing the
Clamp Strips
eRepeat steps 8
a through 8d to install the front shelf clamp and clamp
strip on the right rack rail.
Front shelf clamp
Clamp strip
Installing a Rack Mount Library21
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
9 Tighten the nuts securing the shelves to the shelf extenders.
The shelf installation is now complete. Proceed to Installing the Library in
the Rack on page 28 to install the library.
Note:The universal rack mount kit contains screws and nuts for
many different types of rack. You will have many of these
screws and nuts left over after installing the rack mount
shelves and library.
Installing the Shelves in a Full U Position
To install the rack mount shelves in a full U position:
Note:The middle library in a 3-high M2500 stack is mounted in a full U
position.
1 From the five sizes of inserts provided in the rack mount kit, select the
insert type that best fits into the holes in the rack rails. The heads of the
inserts (not the threads) should fit into the holes in the rack rails smoothly
and with very little play.
The insert part numbers are:
•213468 (for rails with 9 mm square holes)
•213469 (for rails with 7 mm diameter unthreaded holes)
•213471 (for rails with M6 threaded holes)
•213473 (for rails with 10-32 UNF, 12-24 UNC, or M5 threaded holes)
•213474 (for rails with 1/4 inch diameter unthreaded holes)
These inserts will be screwed into the holes in the front and rear flanges of
the rack mount shelves.
2 Screw three inserts into the front flange of each rack mount shelf in
positions 1, 4, and 8 (counting from the bottom up, with 1 being the
lowest hole) (see figure 13
).
0
Note:Some of the inserts have either no head or a head that has a
smaller diameter than the thread; these need to be left
protruding by about 1/8 in. (3 mm). The inserts with heads
should be tightened fully.
22Installing a Rack Mount Library
Figure 19 Installing Inserts
at the Front of the Shelves
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 20 Installing Inserts
at the Rear of the Shelves
8
4
1
3 Screw three inserts into the rear flange of each rack mount shelf in the
positions shown in figure 20
. If the shelves are oriented so the group of
six holes is at the bottom and the group of four holes is at the top, the
inserts go into holes 1, 5, and 10 (counting from the bottom up, with 1
being the lowest hole).
Note:Some of the inserts have either no head or a head that has a
smaller diameter than the thread; these need to be left
protruding by about 1/8 in. (3 mm). The inserts with heads
should be tightened fully.
Group of 6
Group of 4
1
5
8
4
1
10
Group of 4
10
Group of 6
5
1
Installing a Rack Mount Library23
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
4 Install the shelves (see figure 15):
Figure 21 Installing the
Shelves
aWith the shelf slightly retracted, position the shelf in the rack at the
desired mounting height.
bExpand the shelf so that the inserts on each end of the shelf protrude
into the holes in the rack rails and hold the shelf in place.
cRepeat these steps to install the remaining shelf.
Inserts protrude
through the
holes in the rails
5 Install the front shelf clamps (see figure 16):
aPosition a front shelf clamp (PN 215812) on the front left rack rail.
The square holes in the front shelf clamp should be aligned with the
upper two inserts in the front shelf flange.
bSecure the front shelf clamp to the rack rail using two M4 countersink
screws (PN YS42064).
cRepeat these steps to install a front shelf clamp on the front right rack
rail.
24Installing a Rack Mount Library
Figure 22 Installing the
Front Shelf Clamps
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
6 Install the rear shelf clamps (see figure 17):
aPosition a rear shelf clamp (PN 215201/01) on the rear left rack rail,
aligning the square hole with the middle insert in the shelf flange.
bVerify that two of the round holes line up with holes in the rack
mount shelf. If two of the holes do not line up, rotate the clamp 180
degrees.
cSecure the clamp to the shelf using two M4 countersink screws (PN
YS42064).
dRepeat these steps to install a rear shelf clamp on the rear right rack
rail.
Note:The left and right rear shelf clamps will be oriented differently
from one another.
Installing a Rack Mount Library25
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 23 Installing the
Rear Shelf Clamps
7 Install the clamp strips (see figure 24):
aPosition a front shelf clamp (PN 215812) at the front of the front left
rack rail, with the bottom of the clamp approximately 15.5 inches (394
millimeters) above the bottom of the rack mount shelf.
Caution:The top of the front shelf clamp must be no more than 580
mm above the bottom of the rack mount shelf.
bPosition a clamp strip (PN 217405) behind the front left rack rail,
aligning it with the shelf clamp.
cInsert a screw (PN YS42064) through the upper hole in the front shelf
clamp, through the rack rail, and into the upper hole in the clamp
strip.
dInsert a screw (PN YS42064) through the bottom hole in the front
shelf clamp, through the rack rail, and into the bottom hole in the
clamp strip.
eRepeat steps 7
a through 7d to install the front shelf clamp and clamp
strip on the right rack rail.
26Installing a Rack Mount Library
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 24 Installing the
Clamp Strips
Clamp strip
Front shelf clamp
8 Tighten the nuts securing the shelves to the shelf extenders.
The shelf installation is now complete. Proceed to Installing the Library in
the Rack to install the library.
Note:The universal rack mount kit contains screws and nuts for
many different types of rack. You will have many of these
screws and nuts left over after installing the rack mount
shelves and library.
Installing a Rack Mount Library27
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Installing the Library in
the Rack
This section explains how to install the library in the rack. You will need a #2
0
POZIDRIV
Installing an M1500
®
screwdriver for this procedure.
0
To install an M1500 in a rack:
1 Take precautions to ensure that the rack is stable:
•If you are installing the library at the top of a rack with no equipment
at the bottom of the rack, purchase a rack stabilization kit from the
rack manufacturer and install it before installing the library.
•If you are installing the library in a rack with other equipment, place
the heaviest equipment at the bottom of the rack.
2 Verify that the rack mount shelves are level and securely fastened to the
rack.
Caution:The M1500 weighs approximately 75 lbs (35 kg). At least
two people are required to lift and install the library.
3 With the help of another person, lift the library onto the rack mount
shelves.
4 Slide the library all the way into the rack.
Figure 25 Securing the
M1500 to the Rack
5 Press the button next to the left magazine access door and open the door.
6 Notice the hole behind the magazine access door, at the lower edge of the
library (see figure 25
).
This hole provides access to the rack mount clamp screw.
Magazine
access door
Access hole for
rack mount
clamp screw
28Installing a Rack Mount Library
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
7 Insert a #2 POZIDRIV screwdriver into the hole and turn the rack mount
clamp screw clockwise to tighten it.
Caution:Do not over-tighten the rack mount clamp screw. When
the screw begins to feel tight, turn it an additional quarter
turn and then stop.
As you tighten this screw, a lever protrudes from the side of the library
and presses against the back side of the rack rail.
8 Repeat steps 5
through 7 to secure the right side of the library to the rack.
9 Close the magazine access doors.
Proceed to Installing Drives in the Library
on page 31 to continue the
installation procedure.
Installing an M2500
To install an M2500 in a rack:
Warning:The M2500 weighs approximately 152 lbs. (69 kg). At least two
people are required to lift and install the library.
1 Take precautions to ensure that the rack is stable:
•If you are installing the library at the top of a rack with no equipment
at the bottom of the rack, purchase a rack stabilization kit from the
rack manufacturer and install it before installing the library.
•If you are installing the library in a rack with other equipment, place
the heaviest equipment at the bottom of the rack.
2 Verify that the rack mount shelves are level and securely fastened to the
rack.
3 With the help of another person, lift the library onto the rack mount
shelves.
0
4 Slide the library all the way into the rack.
5 Press the two buttons next to the left magazine access doors and open the
doors.
6 Notice the two holes behind the left magazine access doors (see
figure 26
).
These holes provide access to the rack mount clamp screws.
Installing a Rack Mount Library29
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 26 Securing the
Library to the Rack
Magazine
access doors
Access holes
for the rack
mount clamp
screws
7 Insert a #2 POZIDRIV screwdriver into one of the holes and turn the rack
mount clamp screw clockwise to tighten it fully.
Caution:Do not overtighten the rack mount clamp screw. When the
screw begins to feel tight, turn it an additional quarter turn
and then stop.
As you tighten this screw, a lever protrudes from the side of the library
and presses against the back side of the rack rail.
8 Tighten the remaining rack mount clamp screw in the same manner.
9 Press the button next to the right magazine access door.
The right magazine access door opens.
10 Repeat steps 6
through 8 to secure the right side of the library to the rack.
11 Close the magazine access doors.
30Installing a Rack Mount Library
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Installing Drives in the Library0
This section explains how to install tape drives in the library. You will need
the following tools for this procedure:
•#2 PHILLIPS
•TORX
®
•TORX T-8 screwdriver (if you are installing drives in drive bays 3
through 6 of an M2500)
•Flat blade screwdriver
®
screwdriver (if you are installing drives in an M1500)
T-20 screwdriver (if you are installing drives in an M2500)
Installing Tape Drives
in an M1500
Figure 27 Installing a Tape
Drive in an M1500
To install tape drives in an M1500:
0
1 At the back of the library, use a #2 PHILLIPS screwdriver to remove the
cover plate protecting the drive bay in which you will install the tape
drive.
2 Insert the tape drive into the drive bay slowly until the connectors are
seated (see figure 27
).
3 Tighten the tape drive thumbscrew using a flat blade screwdriver.
4 Repeat steps 1
Tape drive
Thumbscrew
through 3 to install another tape drive, if desired.
Installing Drives in the Library31
Tandberg Data M-Series Installation Guide
Dri
2D
1
Document T6423046-02 A01
February 2004
Installing Tape Drives
in an M2500
Figure 28 Drive Bay
Numbering, M2500
To install tape drives in an M2500:
0
1 At the back of the library, use a TORX T-20 screwdriver to remove the
cover plate protecting the drive bay in which you will install the tape
drive.
Note:The cover plates for drive bays 3 through 6 also have a TORX
T-8 screw that must be removed to access the drive bay.
Note:Populate the drive bays in the following order: drive bay 1,
drive bay 2, drive bay 4, drive bay 5, drive bay 6, drive bay 3
(see figure 28
). Drive bay 3 is used only if six drives are
installed in the library.
ve bay
rive bay
Drive bay 3 (this drive
bay is empty unless a
sixth drive is installed)
Drive bay 5Drive bay 6
Drive bay 4
2 Insert the tape drive into the drive bay slowly until the connectors are
seated (see figure 29
).
32Installing Drives in the Library
Figure 29 Installing a Tape
Drive in an M2500
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Tape drive
Thumbscrew
3 Tighten the tape drive thumbscrew using a flat blade screwdriver.
4 Install the appropriate cover plate in the space above the drive.
Note:Two cover plates were provided with the tape drive. The
smaller plate (215982 or 70-87502-01) used with tape drives on
the middle level of the library; the larger plate (215981) is used
with tape drives on the bottom level of the library.
5 Repeat steps 1
through 3 to install any additional tape drives.
Caution:Do not install a drive in drive bay 3. This drive bay is used
only if a sixth drive is installed.
Caution:Do not attempt to install a sixth drive in the M2500. This
procedure requires specialized software tools available
only to Tandberg Data-authorized field service personnel.
If a sixth drive is desired, please contact your local
Tandberg Data office to arrange for a professional
installation.
Installing Drives in the Library33
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Preparing and Inserting Tape Cartridges0
This section explains how to insert tape cartridges into the M1500 and M2500
libraries. This procedure consists of the following steps:
•Labeling the tape cartridges
•Setting the write-protect switch
•Placing cartridges in the library
Labeling Tape
Cartridges
Table 6 Bar Code Label
Requirements
Attaching a bar code label to each cartridge enables the library to identify tape
0
cartridges quickly, speeding the inventory process.
Note:The M1500 and M2500 libraries are capable of reading most
common bar code formats.
Bar Code Label Requirements
Bar code labels must meet the requirements of the latest revision of the ANSI
MH10.8M standard, and should use industry standard Code 39 (3 of 9 code).
The basic requirements are listed in table 6
Label size
Quiet zone
Character height
Bar code characters
Ratio of wide to
narrow element
2.2 x 0.82 inches (5.59 x 2.08 cm)
0.25 inches (6.4 mm) minimum
0.3 inches (7.6 mm)
one start character, one to six alphanumeric
characters, one stop character
2.5:1 minimum
.
0
Applying the Labels0
1 Label the tape cartridges (see figure 30):
•DLT and SDLT cartridges use non-adhesive labels that slide into a
slot at the front of the cartridge.
•LTO cartridges use adhesive labels that adhere to the front of the
cartridge.
34Preparing and Inserting Tape Cartridges
Figure 30 Labeling Tape
Cartridges
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
ABC123L1
Labeling a DLT or SDLT cartridge
Labeling an LTO cartridge
2 Use the same method to apply a cleaning cartridge label to the cleaning
cartridge.
Cleaning cartridge labels are black and white, and their numbers start
with the letters CLN.
Caution:LTO tape drive media cannot be degaussed due to the fact
that it uses magnetic servos. Do not attempt to degauss
LTO tape drive media. If this media is degaussed, it will
no longer work.
Setting the WriteProtect Switch
The write-protect switch (see figure 31) controls whether the tape cartridge is
0
write-protected or write-enabled:
•Write-protecting a cartridge protects the data it contains from being
erased or overwritten. Typically you use this setting when removing the
cartridges for storage outside the library.
•Write-enabling a cartridge allows new data to be written to the cartridge
or existing data to be modified or erased. This is the setting that
cartridges are typically set to when they are inside the library.
Setting the Write-Protect Switch (DLT and SDLT Cartridges)
0
To write-protect a DLT or SDLT cartridge, move the write-protect switch to
the left. An orange tab is visible behind the switch (see figure 31
).
To write-enable a DLT or SDLT cartridge, move the write-protect switch to
the right. The orange tab is not visible when the cartridge is write-enabled.
Preparing and Inserting Tape Cartridges35
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 31 Setting the
Write-Protect Switch (DLT
and SDLT Cartridges)
Write-protect switch
Setting the Write-Protect Switch (LTO Cartridges)0
To write-protect an LTO cartridge, move the write-protect switch to the right
(see figure 32
Orange tab
).
Figure 32 Setting the
Write-Protect Switch (LTO
Cartridges)
Placing Cartridges in
the Library
To write-enable an LTO cartridge, move the write-protect switch to the left.
Write-protect switch
Slide left
Writeenabled
Writeprotected
Slide right
This section explains how to place tape cartridges in the library.
0
Placing Tape Cartridges in an M1500
To place tape cartridges in an M1500:
1 Remove the left magazine:
0
aPress the button next the left magazine access door and open the
door.
bGrasping the handle at the front of the left magazine, pull it forward
until it stops.
36Preparing and Inserting Tape Cartridges
Figure 33 Magazine
Release Button
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
cUsing a slender object such as a pen, press and hold the magazine
release button (see figure 33
).
dPull the left magazine the rest of the way out of the library.
Magazine
release
button
2 Remove the right magazine:
aPress the button next the right magazine access door and open the
door.
bGrasping the handle at the front of the right magazine, pull it forward
and out of the library.
3 Insert the cleaning cartridge into the fixed slot behind the left magazine,
orienting it with the label facing outward and the write-protect switch:
•Down, if it is a DLT or SDLT cartridge
•Up, if it is an LTO cartridge
4 Insert cartridges into each of the magazine slots:
aOrient the cartridges as described in step 3
.
bPush each cartridge into a slot until the cartridge retaining latch clicks
to hold the cartridge in place.
Caution:The magazines are designed so that you cannot insert
cartridges incorrectly. Do not try to force the cartridges
into the slots.
Preparing and Inserting Tape Cartridges37
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 34 Inserting DLT
Cartridges into a Magazine
Cartridge
retaining latch
LabelWrite-protect
switch
5 Insert the magazines into the library, sliding them back until they click
into place.
6 Close the magazine access doors.
Placing Tape Cartridges in an M2500
To place tape cartridges in an M2500:
1 Press the buttons next to the magazine access doors.
The magazine access doors open.
2 Remove the level 1 left magazine:
aGrasping the handle at the front of the level 1 left magazine, pull it
forward until it stops.
bIf the magazine stops after the first slot, perform steps 2
c through 2e
to release it.
cRemove the level 2 left magazine (see figure 35
).
0
38Preparing and Inserting Tape Cartridges
Figure 35 Removing the
Level 2 Left Magazine
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
dReach into the library underneath the level 1 left magazine and pull
down on the release latch (see figure 36
).
Figure 36 Release Latch
Release latch
eWhile holding the release latch, pull the level 1 left magazine forward
and out of the library (see figure 37
).
Preparing and Inserting Tape Cartridges39
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 37 Removing the
Level 1 Left Magazine
3 Remove each remaining magazine by grasping the handle at the front of
4 Insert cleaning cartridges into the fixed slots.
the magazine and sliding it forward and out of the library.
Note:There is one fixed slot behind each left magazine.
Orient the cartridges with the label facing outward and the write-protect
switch:
•Down, if it is a DLT or SDLT cartridge
•Up, if it is an LTO cartridge
5 Insert cartridges into each of the magazine slots (see figure 34
aOrient the cartridges as described in step 4
.
):
bPush each cartridge into a slot until the cartridge retaining latch clicks
to hold the cartridge in place.
Caution:The magazines are designed so that you cannot insert
cartridges incorrectly. Do not force the cartridges into the
slots.
6 Insert the magazines into the library, sliding them back until they click
into place.
7 Close the magazine access doors.
40Preparing and Inserting Tape Cartridges
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Connecting the Library to AC Power0
This section explains how to connect the library to AC power.
M1500 Power
Requirements
Figure 38 Power Inlet
To connect the M1500 to AC power:
0
1 Referring to table 7
library configuration and input voltage.
Warning:AC distribution units (power strips) must be certified for
2 Connect the power cable (provided in the accessories kit) to the power
inlet on the back of the library (see figure 38
unit.
, select appropriate AC distribution unit(s) for your
safety by an agency acceptable to the country of use. For
use in the United States and Canada, distribution units
must be UL listed and CSA certified. For use in Europe,
distribution units must be CE marked. National
certifications for other countries depend on local
requirements.
) and to the AC distribution
Power inlet
Table 7 AC Distribution
Requirements, M1500
Distribution Unit Requirements
# of
Library
Modules
1-2Connect libraries to one AC distribution unit
200-240V 50-60Hz supply voltage (Europe
& international, etc.)
rated minimum 10A, minimum 1.00mm
<HAR> cord with minimum 10A plug. Must
be three wire grounding plug and wall outlet.
Connecting the Library to AC Power41
100-120V 50-60Hz supply voltage (USA,
Canada, Japan, etc.)
2
Connect libraries to one UL Listed AC
distribution unit rated 15A or 20A, with a
minimum 14AWG three wire cord, and a 15A
or 20A plug. Must be three wire grounding
plug and wall outlet.
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
# of
Library
Modules
200-240V 50-60Hz supply voltage (Europe
& international, etc.)
Distribution Unit Requirements
100-120V 50-60Hz supply voltage (USA,
Canada, Japan, etc.)
3-4Select one of the following options:
• Connect no more than two libraries to each
AC distribution unit rated minimum 10A,
minimum 1.00mm
2
<HAR> cord with
minimum 10A plug. Must be three wire
grounding plug and wall outlet. The AC
distribution units must be plugged into
separate outlets served by separate circuit
breakers or fuses.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
<HAR> three wire cord with
three wire IEC60309 rated 16A. Must be
three wire grounding plug and wall outlet
and have a ground warning label.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
<HAR> three wire cord
permanently wired to the electrical supply.
Must be connected with a three wire cable
and have a ground warning label.
5-10Select one of the following options:
Connect all libraries to one UL Listed AC
distribution unit rated 15A or 20A, with a
minimum 14AWG three wire cord, and a 15A
or 20A plug. Must be three wire grounding
plug and wall outlet.
Select one of the following options:
• Connect no more than two libraries to each
AC distribution unit rated minimum 10A,
minimum 1.00mm
2
<HAR> cord with
minimum 10A plug. Must be three wire
grounding plug and wall outlet. The AC
distribution units must be plugged into
separate outlets served by separate circuit
breakers or fuses.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
<HAR> three wire cord with
three wire IEC60309 rated 16A. Must be
three wire grounding plug and wall outlet
and have a ground warning label.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
<HAR> three wire cord
• Connect no more than 4 libraries to each
AC distribution unit rated 15A or 20A, with
a minimum 14AWG three wire cord, and a
15A or 20A plug. Must be three wire
grounding plug and wall outlet.
• Connect all libraries to one AC distribution
unit rated 20A, with a minimum 14AWG
three wire cord, with a 20A plug. Must be
three wire grounding plug and wall outlet
and have a ground warning label.
• Connect all libraries to one AC distribution
unit rated minimum 20A, with a minimum
14AWG three wire cord, permanently
wired to the electrical supply and have a
ground warning label.
permanently wired to the electrical supply.
Must be connected with a three wire cable
and have a ground warning label.
42Connecting the Library to AC Power
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
M2500 Power
Requirements
To connect the M2500 to AC power:
0
1 Referring to table 8
, select appropriate AC distribution unit(s) for your
library configuration and input voltage.
Warning:AC distribution units (power strips) must be certified for
safety by an agency acceptable to the country of use. For
use in the United States and Canada, distribution units
must be UL listed and CSA certified. For use in Europe,
distribution units must be CE marked. National
certifications for other countries depend on local
requirements.
2 Using one of the short AC power cables provided in the accessory kit,
connect the top power supply to the AC distribution panel on the back of
the library (see figure 39
).
3 Using the remaining short AC power cable, connect the bottom power
supply to the AC distribution panel (see figure 39
).
4 Connect the power cable (provided in the accessories kit) to the power
inlet on the back of the library (see figure 39
) and to the wall outlet or AC
distribution unit.
Figure 39 Power Inlet
Connect these
using a short
power cable
Connect this inlet
to the wall outlet
or AC distribution
unit
Connect these
using a short
power cable
Connecting the Library to AC Power43
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Table 8 AC Distribution
Unit Requirements, M2500
Distribution Unit Requirements
# of
Library
Modules
200-240V 50-60Hz supply voltage (Europe
& international, etc.)
100-120V 50-60Hz supply voltage (USA,
Canada, Japan, etc.)
1Connect the library to an AC wall outlet rated
minimum 10A, minimum 1.00mm
2
<HAR>
cord with minimum 10A plug. Must be three
wire grounding plug and wall outlet.
2Connect each library to a separate wall outlet
rated minimum 10A, minimum 1.00mm
2
<HAR> cord with minimum 10A plug. Must
be three wire grounding plug and wall outlet.
3Select one of the following options:
• Connect each library to a separate wall
outlet rated minimum 10A, minimum
1.00mm
2
<HAR> cord with minimum 10A
plug. Must be three wire grounding plug
and wall outlet.
• Connect all libraries to one AC distribution
unit rated minimum 10A, minimum
1.00mm
2
<HAR> three wire cord with three
wire IEC60309 rated 16A. Must be three
wire ground plug and wall outlet and have
a ground warning label.
• Connect all libraries to one distribution unit
rated minimum 10A, minimum 1.00mm
2
<HAR> three wire cord permanently wired
to the electrical supply. Must be connected
with a three wire cable and have a ground
warning label.
Connect the library to one UL listed AC
distribution unit rated 15A or 20A, with a
minimum 14AWG three wire cord, and a 15A
or 20A plug. Must be three wire grounding
plug and wall outlet.
Connect both libraries to one UL listed AC
distribution unit rated 15A or 20A, with a
minimum 14AWG three wire cord, and a 15A
or 20A plug. Must be three wire grounding
plug and wall outlet.
Select one of the following options:
• Connect no more than two libraries to each
of two AC distribution units rated 15A or
20A, with a minimum 14AWG three wire
cord, and a 15A or 20A plug. Must be three
wire grounding plug and wall outlet. The
AC distribution units must be plugged into
separate outlets served by separate circuit
breakers or fuses.
• Connect all libraries to one AC distribution
unit rated 20A, with a minimum 14AWG
three wire cord, with a 20A plug. Must be
three wire grounding plug and wall outlet.
• Connect all libraries to one AC distribution
unit rated minimum 20A, with a minimum
14AWG three wire cord, permanently
wired to the electrical supply.
44Connecting the Library to AC Power
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Connecting the Library to the Host Computer0
The library robotics and tape drives are independent SCSI devices with
independent SCSI connections. The M1500 and M2500 provide two 68-pin
high density connectors for each device. You can connect these devices to a
single SCSI bus or divide them between two or more SCSI buses.
To connect the library or libraries to the host computer(s), refer to the
following sections:
•SCSI Cabling Guidelines
•Terminator Power
•SCSI Cabling Diagrams
SCSI Cabling
Guidelines
Terminator Power0External terminators must be installed at the end of each SCSI bus. Power for
0
Refer to these SCSI cabling guidelines when completing the SCSI cabling:
•Each device on the SCSI bus must have a unique SCSI ID. The default
settings for the M1500 are: library robotics = 0, tape drive 1 = 1, tape drive
2 =2. The default settings for the M2500 are: library robotics = 0, tape
drive 1 = 1, tape drive 2 = 2, tape drive 3 = 3, tape drive 4 = 4, tape drive 5
= 15, tape drive 6 = 14. You can change these SCSI ID settings using the
Drive ID and Library ID options on the GUI Configuration screen.
•Termination must be provided at each end of the SCSI bus (see
Terminator Power
•All SCSI cables must be shielded or double shielded to meet EMI
specifications.
•The maximum total SCSI bus length for an LVD SCSI bus is 40 feet (12
meters).
the terminator must be supplied by at least one device on the SCSI bus.
In the factory default configuration, the library robotics supplies terminator
power. You can turn this terminator power off using the
option on the GUI
).
Terminator Power
Configuration screen.
Connecting the Library to the Host Computer45
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
SCSI Cabling
Diagrams
Figure 40 SCSI Cabling
Diagram, M1500 — Single
SCSI Bus
This section provides sample SCSI cabling configurations for M1500 and
0
M2500 libraries.
SCSI Cabling Diagrams, M1500
0
Figures 40 through 42 illustrate sample SCSI cabling configurations for a
single M1500 module.
To host computer
Terminator
Figure 41 SCSI Cabling
Diagram, M1500 — Two
SCSI Buses
To host computer
Terminator
46Connecting the Library to the Host Computer
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 42 SCSI Cabling
Diagram, M1500 — Three
SCSI Buses
Figure 43 SCSI Cabling
Diagram, M2500
To host computer
Terminator
SCSI Cabling Diagram, M25000
Figures 43 illustrates the recommended SCSI cabling configuration for a
single M2500 module.
Terminators
To host
computer
Connecting the Library to the Host Computer47
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Powering Up the Library0
To power up the library, press the power switch (or switches) on the back
panel of the library (see figure 44
To minimize the effects of inrush current, always turn on the library using
these library power switches instead of using the power switches that may be
on the AC distribution unit.
Figure 44 Power Switch,
M1500
and figure 45).
Figure 45 Power Switches,
M2500
Power switch
Power switches
48Powering Up the Library
Figure 46 Welcome
Screen, M2500
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
The GUI displays a welcome screen (see figure 46) and the library runs a
power-on self-test (POST).
Figure 47 Main Screen,
M2500
When the POST is complete, the GUI displays the main screen (see figure 47).
Powering Up the Library49
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
At the bottom of each GUI screen are up to five button labels. These labels
indicate the functions of the five push buttons below the GUI. To select a
function, press the push button directly below the button label on the GUI
screen (see figure 48
Figure 48 Using the GUI
Buttons
).
To select this
function,
press this
button:
Button
labels
Push
buttons
Disabling Unused Drive Bays0
To complete the library installation, disable any unused drive bays as follows:
1 On the main screen, press
The GUI displays the
Figure 49 Menu Screen
Menu.
Menu screen (see figure 49).
50Disabling Unused Drive Bays
2 Press Config.
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Figure 50
Configuration Screen
The GUI displays the
Configuration screen (see figure 50).
3 Press the Up or Down buttons until the drive ID for the unused drive bay
is highlighted.
4 Press
5 Press the
Select.
Down button until the Disabled setting is selected.
Caution:Set the drive SCSI ID to
Disabled only if there is no drive
installed in the drive bay.
6 Press
7 Repeat steps 3
8 Press
Select.
through 6 to disable any other unused drive bays.
Main to return to the main screen.
Note:This setting takes affect after you reboot the library.
9 Turn the library off and then back on again.
The library is now ready for operation.
Note:It is recommended that you check the library configuration
settings and change them as necessary before configuring your
backup software, especially the
Import/Export option setting.
Disabling Unused Drive Bays51
Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Made in the USA.
Quantum Corporation provides this publication “as is” without warranty of any kind, either express or implied, including but not limited
to the implied warranties of merchantability or fitness for a particular purpose. Quantum Corporation may revise this publication from
time to time without notice.
Your right to copy this document is limited by copyright law. Making copies or adaptations without prior written authorization of
Quantum Corporation is prohibited by law and constitutes a punishable violation of the law.
TRADEMARK STATEMENT
StackLink is a trademark of Quantum Corporation.
Other trademarks may be mentioned herein which belong to other companies.
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.