Spectrum Controls 2080sc-OW2IHC User Manual

Micro800™ 2 Ch High Current Digital Output Module 20
For Technical Support
USA 440-646-6900 United Kingdom 01908 635230 Australia 1800-809-929 Brazil (55) 11 3618 8800 Europe (49) 2104 960 630
Install Guide
Micro800
2 Ch High Current Digital Output Module
(Catalog Number 2080sc-OW2IHC)
Contents
For More Information ................................................................................. 2
Environment and Enclosure ...................................................................... 3
Prevent Electrostatic Discharge ................................................................ 4
Parts List ................................................................................................... 5
Insert Module into Controller ..................................................................... 6
Wire the Module ........................................................................................ 7
Configuring the Module ............................................................................. 7
Module Input Data ..................................................................................... 7
Module Output Data .................................................................................. 8
1705 132nd Ave NE Bellevue, WA 98005 USA Tel: 425-746-9481 Fax: 425-641-9473 Email: spectrum@spectrumcontrols.com Web: www.spectrumcontrols.com
Micro800 is a trademark of Rockwell Automation.
Publication 2080sc-OW2IHC Install Guide – June 2012 © 2012 Spectrum Controls, Inc. Printed in the USA.
Publication 0100188-01 Rev. A
Adding the OW2IHC to CCW .................................................................... 8
Electrical Specifications .......................................................................... 11
Environmental Specifications .................................................................. 13
Hazardous Location Considerations ....................................................... 15
Environnements dangereux .................................................................... 16
Micro800™ 2 Ch High Current Digital Output Module 2
For More Information
PLC sample projects and documentation are available on our website at
http://www.spectrumcontrols.com
Micro800™ 2 Ch High Current Digital Output Module 19
Intentionally Left Blank
Publication 0100188-01 Rev. A
Publication 0100188-01 Rev. A
Micro800™ 2 Ch High Current Digital Output Module 18
Intentionally Left Blank
Micro800™ 2 Ch High Current Digital Output Module 3
Environment and Enclosure
This equipment is intended for use in a Pollution Degree 2 industrial environment, in overvoltage Category II applications (as defined in IEC publication 60664-1), at altitudes up to 2000 meters (6562 ft) without derating.
This equipment is considered Group 1, Class A industrial equipment according to IEC/CISPR Publication 11. Without appropriate precautions, there may be potential difficulties ensuring electromagnetic compatibility in other environments due to conducted as well as radiated disturbance.
This equipment is supplied as open-type equipment. It must be mounted within an enclosure that is suitably designed for those specific environmental conditions that will be present and appropriately designed to prevent personal injury resulting from accessibility to live parts. The enclosure must have suitable flame-retardant properties to prevent or minimize the spread of flame, complying with a flame spread rating of 5VA, V2, V1, V0 (or equivalent) if non-metallic. The interior of the enclosure must be accessible only by the use of a tool. Subsequent sections of this publication may contain additional information regarding specific enclosure type ratings that are required to comply with certain product safety certifications.
In addition to this publication, see:
Industrial Automation Wiring and Grounding
Guidelines, Allen-Bradley publication 1770-
4.1, for additional installation requirements.
NEMA Standards publication 250 and IEC
publication 60529, as applicable, for explanations of the degrees of protection provided by different types of enclosure
Publication 0100188-01 Rev. A
Publication 0100188-01 Rev. A
Micro800™ 2 Ch High Current Digital Output Module 4
Prevent Electrostatic Discharge
Electrostatic discharge can damage integrated circuits or semiconductors if you touch bus connector pins. Follow these guidelines when you handle the module:
Touch a grounded object to discharge static
potential.
Wear an approved wrist-strap grounding
device.
Do not touch connectors or pins on
component boards.
Do not touch circuit components inside the
module.
If available, use a static-safe work station.  When not in use, keep the module in its
static-shield box.
To comply with the CE Low Voltage Directive (LVD), all connected I/O must be powered from a source compliant with the following: Safety Extra Low Voltage (SELV) or Protected Extra Low Voltage (PELV).
Micro800™ 2 Ch High Current Digital Output Module 17
Intentionally Left Blank
Publication 0100188-01 Rev. A
Publication 0100188-01 Rev. A
Micro800™ 2 Ch High Current Digital Output Module 16
Environnements dangereux
Cet équipement est conçu pour être utilisé dans des environnements de Classe I, Division 2, Groupes A, B, C, D endroit dangereux ou non dangereux. La mise en garde suivante s’applique à une utilisation dans des environnements dangereux.
Micro800™ 2 Ch High Current Digital Output Module 5
Parts List
Your package contains one Micro800 High Current Digital Output Plug-in Module and one Quick Start guide.
DANGER D’EXPLOSION
La substitution de composants peut
rendre cet équipement impropre à une utilisation en environnement de Classe 1, Division 2.
Ne pas remplacer de composants ou
déconnecter l'équipement sans s'être assuré que l'alimentation est coupée ou que l’endroit soit depourvu de concentrations inflammables.
Ne pas connecter ou déconnecter des
composants sans s'être assuré que l'alimentation est coupée.
Ce produit doit être installé dans une
armoire.
Tout le cablage doit agreer la norme
N.E.C. article 501-4(b).
Publication 0100188-01 Rev. A
You can choose to wire the plug-in before inserting it onto the controller, or wire it once the module is secured in place.
Publication 0100188-01 Rev. A
This equipment is considered Group 1, Class
A industrial equipment according to IEC/CISPR 11. Without appropriate precautions, there may be difficulties with electromagnetic compatibility in residential and other environments due to conducted and radiated disturbance.
Be careful when stripping wires. Wire
fragments that fall into the controller could cause damage. Once wiring is complete, make sure the controller is free of all metal fragments before removing the protective debris strip.
Do not wire more than 2 conductors on any
single terminal.
If you insert or remove the plug-in module
while power is on, an electrical arc can occur. This could cause an explosion in hazardous location installations. Be sure that power is removed or the area is nonhazardous before proceeding.
Cable length should be less than 10 meters.
Do not insert or remove the plug-in module
while power is applied, otherwise, permanent damage to equipment may occur.
Micro800™ 2 Ch High Current Digital Output Module 6
Micro800™ 2 Ch High Current Digital Output Module 15
Insert Module into Controller
Follow the instructions to insert and secure the plug-in module to the controller.
1. Position the plug-in module with the terminal block facing the front of the controller as shown.
2. Snap the module into the module bay.
3. Using a screwdriver, tighten the 10…12 mm (0.39…0.47 in.) M3 self tapping screw to torque specifications.
Hazardous Location Considerations
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, D hazardous locations or non-hazardous locations only. The following WARNING statement applies to use in hazardous locations.
EXPLOSION HAZARD
Substitution of components may impair
suitability for Class I, Division 2.
Do not replace components or disconnect
equipment unless power has been switched off or the area is known to be free of ignitable concentrations.
Do not disconnect equipment unless
power has been removed or the area is known to be non-hazardous.
This product must be installed in an
enclosure.
All wiring must comply with N.E.C. article
501-4(b).
Publication 0100188-01 Rev. A
Publication 0100188-01 Rev. A
Micro800™ 2 Ch High Current Digital Output Module 14
Environmental Tests Industry Standards Test Level Limits
Signal Ports:
EFT/B immunity IEC 61000-4-4*
± 3 kV @ 5 kHz for 5 minutes
Power Ports:
± 2 kV @ 5 kHz for 5 minutes
Micro800™ 2 Ch High Current Digital Output Module 7
Wire the Module
Follow the wiring diagrams below to wire the module.
CM0 O-0 NC NC CM1 O-1
Surge transient immunity
(Performance Criteria B)
Conducted RF immunity
(Performance Criteria A)
Magnetic Field
(Performance Criteria A)
AC Mains Voltage Dips, Interruptions and Variations
Safety Tests Industry Standards
UL Safety
UL Hazardous Locations
CE Low Voltage Directive
Signal Ports:
± 2 kV line-earth
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8 30Arms/m
IEC 61000-4-11 Standard
UL 508 Industrial Control Equipment Seventeenth Edition Dated January 28 1999, with revisions through July 11, 2005 (ANSI/UL 508-
2005) (NRAQ, NRAQ7)
cUL CSA C22.2 No. 142 -M1987 Process Control Equipment May 1987
ULH ANSI/ISA–12.12.01–2007 Nonincendive Electrical Equipment for Use in Class I, Division 2 Hazardous (Classified) Locations
cULH CSA C22.2 No. 213-M1987 - Non­incendive Electrical Equipment for use in Class I Division 2 Hazardous Locations - March 1987
IEC 61131-2 Programmable Controllers Part 2: Equipment Requirements and Tests; Second Edition 2003-02, Section 11-14
Power Ports
± 2kV CM
± 1kV DM
10V rms with 1 kHz sine wave 80%AM from 150 kHz…80 MHz on signal and power ports
Test Level
Limits
As required
As required
As required
CM0 O-0 NC NC CM1 O-1
L1
or
+DC
L2
or
-DC
Load
L1
or
+DC
Load
L2
or
-DC
Note: In the diagram above, terminals with the same label are internally shorted together. Example, CM0 (Top Row) and CM0 (Bottom Row) are internally shorted together.
Configuring the Module
The 2080sc-OW2IHC doesn’t really require configuration. It only needs to be placed into run mode. Write a value of 165 decimal to memory location 17 (MOD_MODE_CONTROL). See Table 3 for more information.
Micro 800 controllers running OS firmware revision 1.12 or older, require a decimal value of 16 be written to memory location 11 (CONTR_OPS_STATUS) before the module will go into run mode. See program sample on page 9.
Module Input Data
General module status can be read from memory location 16. Refer to table below for possible responses.
Table 1 (General Module Status)
Bit Number Description
These 2 bits define module operation mode,
0-1
0: Idle: Module is ready to RUN, and I/O is off. 1: RUN: Module is under RUN, and I/O is on. 2: Error: Error happens, and I/O is off. 3: Busy: Module is busy, cannot go to RUN, and I/O is off.
Publication 0100188-01 Rev. A
Publication 0100188-01 Rev. A
Micro800™ 2 Ch High Current Digital Output Module 8
Micro800™ 2 Ch High Current Digital Output Module 13
Module Output Data
The two output channels on the OW2IHC are controlled by memory location 64, bits 0 and 1 control channels 0 and 1 respectively. See Table 3 for memory location offsets. The table below describes the state of each output channel in relation to the control bits.
Table 2 (Output States) Channel # Bit state Output State
0 OPEN
0
1 CLOSED
0 OPEN
1
1 CLOSED
Adding the OW2IHC to CCW
The 2080sc-OW2IHC is configured for CCW (Connected Components Workbench) using the PLUGIN_READ and PLUGIN_WRITE instructions for generic plug-in modules.
The configuration, output data, and status structures discussed in the sections above, are stored at different memory locations in the module. The following table lists the memory location offset for each parameter which is used when configuring the PLUGIN_READ, WRITE, and INFO instructions.
Table 3 (Parameter Offset)
Parameter
MOD_ID_LO 0 Module ID MOD_ID_HI 1 VENDOR_ID_LO 2 Vendor ID VENDOR_ID_HI 3 PRODUCT_TYPE_LO 4 PRODUCT_TYPE_HI 5 PRODUCT_CODE_LO 6 PRODUCT_CODE_HI 7 MOD_REV_LO 8 Minor revision, 1-255 MOD_REV_HI 9 Major revision, 1-127 CONTR_OPS_STATUS
MOD_STATUS
Publication 0100188-01 Rev. A
Offset
(Dec) Comments
Controller operation status information
11
(see Table 4)
Module status register
16
(see
Table 1)
Environmental Specifications
Environmental Tests Industry Standards Test Level Limits
IEC60068-2-1: (Test Ad, Operating Cold),
Temperature (Operating)
Temperature
(Non-operating)
Operating Altitude 2000 meters (6561 feet) Not tested
Humidity (Operating)
Vibration (Operating) IEC60068-2-6: (Test Fc, Operating)
Shock (Operating)
Shock (Non-operating) IEC60068-2-27: (Test Ea, Unpackaged Shock) 50 g
Radiated Emissions CSIPR 11; Group 1, Class A 30MHz – 1GHz
Conducted Emissions
ESD immunity IEC 61000-4-2
Radiated RF immunity IEC 61000-4-3: Level 3
IEC60068-2-2: (Test Bd, Operating Dry Heat),
IEC60068-2-14: (Test Nb, Operating Thermal Shock)
IEC60068-2-1:
(Test Ab, Unpackaged Non-operating Cold),
IEC60068-2-2:
(Test Bb, Unpackaged Non-operating Dry Heat),
IEC60068-2-14:
(Test Na, Unpackaged Non-operating Thermal Shock)
IEC60068-2-30:
(Test Db, Unpackaged Damp Heat):
IEC60068-2-27: (Test Ea, Unpackaged Shock) 10 g
IEC 61000-6-4:2007 Group 1, Class A (AC Mains)
Publication 0100188-01 Rev. A
-20 to 65°C (-4 to 149°F)
-40 to 85°C (-40 to 185°F)
5 to 95% non-condensing
5G
150kHz – 30MHz
4kV Indirect (Coupling Plate)
4kV Contact Discharge (to points of initial contact)
8kV Air Discharge (to points of initial contact)
10 V/M with 1 kHz sine-wave 80%AM from 80…2000 MHz
10 V/M with 200 Hz sine-wave 50% Pulse 100%AM @900 MHz
10 V/M with 200 Hz sine-wave 50% Pulse 100%AM @1890 MHz
3 V/M with 1 kHz sine-wave 80%AM from 2000…2700 MHz
Micro800™ 2 Ch High Current Digital Output Module 12
Minimum Load 10mA at 5VDC per point.
Initial Contact Res. of Relay Expected Life of Electrical Contacts
Switching Frequency Bounce Time 1.2 ms average
Maximum Off State Leakage
Output Delay Time (From the time the module receives data) Status Indicators Power source 3.3 VDC, 24 VDC from backplane
Input to backplane isolation
Channel to channel isolation Power consumption Inrush current <120 mA at 3.3V, <120 mA at 24V
Fusing Use external if desired
Terminal block Wire size Terminal block torque Mounting torque Manufacturing RoHS compliant
Dimensions 58.4mm x 29.3mm x 25mm
Status Indicators
(This value can change due to the switching frequency, environmental conditions, and desired reliability level, therefore it is recommended to check this with the actual load.) < 5m typical, 30 m max
100k operations @ 20 times/min, at rated resistive capacity and temperature.
Maximum 1 cycle /3s at rated load (1.5s on, 1.5s off)
1.5mA Maximum
10ms maximum on/off (5 ms typical) excluding bounce time
2 yellow Status Indicators (I/O)
250 VAC continuous, tested at 2300VAC for 1 min.
250 VAC continuous, tested at 1500VAC for 1 minute
<=35 mA at 3.3V, <=20 mA at 24V, <1.5 W
#16 - #30 AWG
0.19 Nm (1.7 lb-in)
0.2 Nm (1.48 lb-in)
Individual OFF/ON Status for each I/O point
Micro800™ 2 Ch High Current Digital Output Module 9
Parameter
MOD_MODE_CONTROL 17 Module Mode Control Register OUTPUT_DATA 64 Output Data Register
Offset
(Dec) Comments
Table 4(Controller Operation Status Register)
Bit Number Description
0-3 Controller Error info:
0x00: no Error; 0x01: Operation Error; 0x02: Fatal Error 0x03-0x0F: reserved ;
4-5 Controller mode:
0x00: non-RUN mode; 0x01: RUN mode; 0x02-0x03 : reserved ;
6-7 Controller Power info:
0x00: Power O.K.; 0x01: power failure triggered; 0x02-0x03: reserved
The following sample program, written in structured text, demonstrates how to configure the module in CCW.
u800Slot := 1; (* Slot number for module. *)
(* This section of code is to handle the controller with Firmware earlier than rev 1.13 *) SYS_INFO_FW(True); IF (SYS_INFO_FW.Sts.OSMajRev = 1 and SYS_INFO_FW.Sts.OSMinRev <=12) THEN IF SYS_INFO_FW.Sts.MajErrCode = 0 THEN ControllerStatus[1] := 2#00010000; WriteControllerStatus(True,u800Slot,11,1,ControllerStatus); END_IF; END_IF;
RunMode[1] := 16#A5; (* Initialize RunMode register *) WriteModModeControl(true,u800Slot,17,1,RunMode); (* Write A5 Hex to MOD_MODE_CONTROL for run mode*) ReadModStatus(true,u800Slot,16,1,OW2IHC_S1_ModStatus); (* Read general module status *) WriteOutputs(True,u800Slot,64,1,OW2IHC_S1_Outputs); (* Write Output states *)
Table 5 (CCW Program Variables)
Variable Name Data Type Dimension
U800Slot UINT NA SYS_INFO_FW SYS_INFO NA ControllerStatus USINT [1..1] WriteControllerStatus Plugin_Write NA WriteModModeControl Plugin_Write NA RunMode USINT [1..1] ReadModStatus Plugin_Read NA OW2IHC_S1_ModStatus USINT [1..1] WriteOutputs Plugin_Write NA OW2IHC_S1_Outputs USINT [1..1]
Publication 0100188-01 Rev. A
Publication 0100188-01 Rev. A
Micro800™ 2 Ch High Current Digital Output Module 10
1
The sample project on the previous page, can be downloaded from our website at http://www.spectrumcontrols.com/downloads.htm
Micro800™ 2 Ch High Current Digital Output Module 11
Electrical Specifications
Relay Output Specifications
Description 2 channel relay output module. Relay Functionality Output Current Rating (at rated power)
Output Power Rating (Resistive
Inductive Loads
UL Pilot Duty Contact Ratings (Power factor 0.35 or less for AC):
Additional UL ratings:
Form A normally open
Resistive load at up to 30° C
10A @ 5-30V dc 10A @ 125V ac 10A @ 250V ac
Resistive load at up to 65° C
6A @ 5-30V dc 6A @ 125V ac 6A @ 250V ac
Resistive load at up to 30° C
300W Maximum for 30.0VDC 1250VA Maximum for 125VAC 2500VA Maximum for 250VAC
Max. current (A)
AC Contact Rating
Code Designation
B300 5 30 3 15 1.5 3600 360
Notes:
a
Power factor 0.35 or less
b
For maximum ratings at voltages between the maximum design value and 120 volts, the maximum make and break ratings are to be obtained by dividing the volt-amperes rating by the application voltage. For voltages below 120 volts, the maximum make current is to be the same as for 120 volts, and the maximum break current is to be obtained by dividing the break volt-amperes by the application voltage, but these currents are not to exceed the thermal continuous test current.
DC Contact
Rating Code
Designation
R150 1.0 0.22 - 28
R300 1.0 0.22 0.11 28
Notes:
c
The maximum make and break ratings are to be obtained by dividing the volt-ampere rating by the application voltage, but the current values are not to exceed the thermal continuous test current.
d
Inductive loads as specified in Section 8.2.7 of Industrial Control and Systems; Control Circuit and Pilot Devices, ANSI/NEMA ICS5-1993.
1/3 hp, 125 V ac, 250V ac 30V dc Make / Break 2A (Pilot Duty) 250V ac, Make 20A / Break 2A (Pilot Duty) 2A, 250V ac, Tungsten Lamp 2A, 30V dc, Tungsten Lamp
Thermal
continuous test
current (A)
Thermal
continuous
test current
(A)
Make Break Make Break Make Break
Max. make/break current (A)
a,b
Max. VA 120 VAC 240VAC
c,d
Max. make / break
VA 125 VDC 250VDC
1
Connecting surge suppressors across your external load will extend the life of the relay
contacts.
Publication 0100188-01 Rev. A
Publication 0100188-01 Rev. A
Loading...