Spectrum Controls 1746sc-INO4vi User Manual

Owner’s Guide 0300128-03 Rev. D
SLC 500 A
NALOG
Catalog Numbers 1746sc-INO4i 1746sc-INO4vi
I
O
SOLATED
M
ODULES
Important Notes
1. Please read all the information in this owner’s guide before installing the product.
2. The information in this owner's guide applies to hardware and firmware version 1.0 or later.
3. This guide assumes that the reader has a full working knowledge of the relevant processor.
Notice
The products and services described in this owner's guide are useful in a wide variety of applications. Therefore, the user and others responsible for applying the products and services described herein are responsible for determining their acceptability for each application. While efforts have been made to provide accurate information within this owner's guide, Spectrum Controls assumes no responsibility for the accuracy, completeness, or usefulness of the information herein.
Under no circumstances will Spectrum Controls be responsible or liable for any damages or losses, including indirect or consequential damages or losses, arising out of either the use of any information within this owner's guide or the use of any product or service referenced herein.
No patent liability is assumed by Spectrum Controls with respect to the use of any of the information, products, circuits, programming, or services referenced herein.
The information in this owner's guide is subject to change without notice.
Limited W arranty
Spectrum Controls warrants that its products are free from defects in material and workmanship under normal use and service, as described in Spectrum Controls literature covering this product, for a period of 1 year. The obligations of Spectrum Controls under this warranty are limited to replacing or repairing, at its option, at its factory or facility, any product which shall, in the applicable period after shipment, be returned to the Spectrum Controls facility, transportation charges prepaid, and which after examination is determined, to the satisfaction of Spectrum Controls, to be thus defective.
This warranty shall not apply to any such equipment which shall have been repaired or altered except by Spectrum Controls or which shall have been subject to misuse, neglect, or accident. In no case shall the liability of Spectrum Controls exceed the purchase price. The aforementioned provisions do not extend the original warranty period of any product which has either been repaired or replaced by Spectrum Controls.
Table Of Contents
Preface
Overview And Specifications
Installing And Wiring Your Module
Things To Consider Before Using Y our Module
Who Should Use This Guide....................................................................... iii
What This Guide Covers ............................................................................. iii
Related Allen-Bradley Documents.............................................................. iii
Terms & Abbreviations You Should Know ................................................... iv
Chapter 1
General Features And Benefits....................................................................1
Detailed Specifications.................................................................................2
Chapter 2
Avoiding Electrostatic Damage.................................................................... 6
Determining Power Requirements............................................................... 6
Setting The DIP Switch ................................................................................ 7
Selecting A Rack Slot ..................................................................................8
Inserting Your Module Into The Rack ........................................................... 8
Wiring Y our Module ....................................................................................10
Chapter 3
How The Processor Communicates With Your Module.............................. 13
Channel Update Time ................................................................................ 13
Temperature Calibration Time.................................................................... 14
Output Mode Change Time (-INO4vi only) ................................................14
Your Module’s Response To Slot Disabling................................................14
Using Your Output Module
Testing Y our Module
Chapter 4
Entering Your Module’s ID Code ................................................................15
Configuring Each Output Channel .............................................................18
Optional: Setting The Output Data Limits (or User-Defined Scale)............21
Controlling Each Output Channel’s Signal.................................................24
Monitoring Each Output Channel............................................................... 25
Checking Each Output Channel’s Configuration And Status..................... 25
Chapter 5
Inspecting Y our Module ..............................................................................29
Disconnecting Prime Movers .....................................................................30
Powering Up...............................................................................................30
Interpreting The LED Indicators .................................................................31
Interpreting I/O Error Codes ......................................................................31
Troubleshooting..........................................................................................32
ii SLC 500™ Isolated Analog Output Modules
Maintaining Your Module And Ensuring Safety
Chapter 6
Preventive Maintenance.............................................................................33
Safety Considerations................................................................................33
Tables
Figures
Table 1. Related Allen-Bradley documents ................................................. iv
Table 2. Electrical specifications—module ................................................... 2
Table 3. Electrical specifications—outputs ................................................... 3
Table 4. Physical specifications....................................................................3
Table 5. Environmental specifications.......................................................... 4
Table 6. Backplane current consumed......................................................... 7
Table 7. Channel update time (channels already enabled) ........................ 14
Table 8. Output module ID code ................................................................15
Table 9. Channel configuration word details, Output Words 4 and 5 ......... 18
Table 10. Data format definitions ............................................................... 20
Table 11. Channel status word details, Input Words 4 through 7 ...............26
Table 12. LED definition .............................................................................31
Figure 1. Ferrite EMI suppressor for CE compliance ................................. 11
Figure 2. Wiring diagrams (showing differential outputs). .......................... 12
Figure 3. Output and input scans............................................................... 13
Figure 4. Output and input words............................................................... 16
Figure 5. Example relationship between output signal and channel data.. 24
Figure 6. LED block ................................................................................... 31
Figure 7. Problem resolution flowchar t ...................................................... 32
Who Should Use This Guide
Preface
Read this preface to familiarize yourself with the rest of the owner’s guide. This preface covers:
• who should use this guide
• what this guide covers
• related Allen-Bradley documents
• terms & abbreviations you should know
Use this guide if you design, install, program, or maintain a control system that uses Allen-Bradley Small Logic Controllers.
You should have a basic understanding of SLC 500 products. You should also understand electronic process control and the ladder program instructions required to generate the electronic signals that control your application. If you do not, contact your local Allen-Bradley representative for the proper training before using these products.
What This Guide Covers
Related Allen-Bradley Documents
This guide covers the 1746sc-INO4i and 1746sc-INO4vi isolated analog output modules. It contains the information you need to install, wire, use, and maintain these modules. It also provides diagnostic and troubleshooting help should the need arise.
Table 1 lists several Allen-Bradley documents that may help you as you use these products.
iv SLC 500™ Isolated Analog Output Modules
Table 1. Related Allen-Bradley documents
Allen-Bradley Doc. No. Title
1747-2.30 SLC 500 System Overview SGI-1.1 Application Considerations for Solid State Controls 1770-4.1 Allen-Bradley Programmable Controller Grounding and
1747-6.2 Installation & Operation Manual for Modular Hardware
1747-NI001 Installation & Operation Manual for Fixed Hardware Style
1747-6.4 Allen-Bradley Advanced Programming Software (APS)
1747-6.11 Allen-Bradley Advanced Programming Software (APS)
1747-6.3 Getting Started Guide for Advanced Programming
Wiring Guidelines
Style Programmable Controllers
Programmable Controllers
User Manual
Reference Manual
Software (APS)
Terms & Abbreviations You Should Know
ABT-1747-TSG001 SLC 500 Software Programmers’s Quick Reference
Guide 1747-NP002 Allen-Bradley HHT (Hand-Held Terminal) User Manual 1747-NM009 Getting Started Guide for HHT (Hand-Held Terminal)
SD499 Allen-Bradley Publication Index AG-7.1 Allen-Bradley Industrial Automation Glossary
To obtain a copy of any of the Allen-Bradley documents listed, contact your local Allen-Bradley office or distributor.
You should understand the following terms and abbreviations before using this guide. For the definitions of terms not listed here, refer to Allen-Bradley’s Industrial Automation Glossary, Publication AG-7.1
Attenuation – The reduction in magnitude of a signal as it passes through a system. The opposite of gain.
Channel – Refers to one of the sets of signal interfaces available on a module’s terminal block.
Channel update time – For analog outputs, the time required for the channel to convert the data received from the processor to analog output signals at the terminals.
Chassis – See rack.
Preface v
Common mode voltage – The voltage difference between the negative terminal and analog common during normal differential operation.
Common mode voltage range – The largest voltage difference allowed between either the positive or negative terminal and analog common during normal differential operation.
Configuration word – Contains the channel configuration information needed by the module to configure and operate each channel. Information is written to the configuration word through the logic supplied in your ladder program.
D/A – Refers to digital-to-analog conversion. The conversion produces an analog output signal whose magnitude is proportional to the digital value.
dB (decibel) – A logarithmic measure of the ratio of two signal levels. Data scaling - The data format that you select to define the logical
increments of the channel data word. Data word – A 16-bit integer that represents the value of the analog
output channel. The channel data word is valid only when the channel is enabled and there are no channel errors.
Differential operation – The difference in voltage between a channel’s positive and negative terminals.
Effective resolution – The number of bits in the channel data word that do not vary due to noise.
Full-scale error (gain error) – The difference in slope between the actual and ideal analog transfer functions.
Full-scale range (FSR) – The difference between the maximum and minimum specified analog values.
Gain drift – The change in full-scale transition voltage measured over the operating temperature range of the module.
LSB (least significant bit) – The bit that represents the smallest value within a string of bits. The “weight” of this value is defined as the full­scale range divided by the resolution.
Maximum differential voltage – The largest voltage difference allowed between the negative terminal and positive terminal during normal differential operation.
Module ID code – A unique number associated with each 1746 I/O module. The code defines for the processor the type of I/O or specialty module residing in a specific slot in the 1746 chassis.
Module update time – See channel update time.
vi SLC 500™ Isolated Analog Output Modules
Overall accuracy – The worst-case deviation of the signal over the full range, expressed in percent of full scale.
Rack – A hardware assembly that houses devices such as I/O modules, adapter modules, processor modules, and power supplies.
Repeatability – The closeness of agreement among repeated measurements of the same variable under the same conditions.
Resolution – The smallest detectable change in a measurement, typically expressed in engineering units (e.g. 0.15 °C) or as a number of bits. For example, a 12-bit system has 4096 possible output states. It can therefore measure 1 part in 4096. See also effective resolution.
Safe state – The state of the analog outputs entered when the processor is not in RUN mode. The user must ensure that this state is a safe state for the application.
Status word – Contains status information about the channel’s current configuration and operational state. You can use this information in your ladder program to determine whether the channel data word is valid.
Step response time – The time required for the output signal to reach 95% of its expected, final value, given a full-scale step change in the output data word.
Useful resolution – See effective resolution.
Chapter
Overview And Specifications
The 1746sc-INO4i provides four isolated channels of current outputs, while the 1746sc-INO4vi provides four isolated channels of current or voltage outputs (in any combination). In both modules, the voltage and/or current ranges are independently configurable for each channel. These modules also provide new, advanced features to make your control systems more dependable and flexible.
1
General Features And Benefits
Read this chapter to familiarize yourself further with your isolated analog module (shown above). This chapter covers:
• general features and benefits
• detailed specifications
Increased System Accuracy and Reliability
Both modules provide 750 Vdc channel-to-channel isolation, which means no electrical noise crosstalk between channels (resulting in a high usable resolution). They also provide 750 Vdc field-wiring-to-backplane isolation to protect the processor and rack. These modules even feature onboard temperature compensation to maintain their accuracy with fluctuating ambient temperatures, which is important for crowded control cabinets.
Reduced System Costs
Because isolation is built into these modules, you can improve system accuracy while saving hundreds of dollars on system installation costs. Expensive, external isolation blocks are simply not required. They also
2 SLC 500™ Isolated Analog Output Modules
provide a single-slot solution for applications requiring up to four, mixed analog outputs, so you don’t have to buy more I/O than you need.
State-of-the-Art Perf ormance
These modules incorporate proprietary Allen-Bradley technology, so they operate and perform like the latest Allen-Bradley products. They also provide 16-bits of resolution, user-programmable range settings, continuous temperature compensation (no field calibration), software configuration, programmable output limits, and programmable safe states in case of a fault.
Detailed Specifications
Table 2. Electrical specifications—module
Backplane Current Consumption (maximum)
1746sc-INO4i 120 mA @ 5 Vdc
250 mA @ 24 Vdc
1746sc-INO4vi 120 mA @ 5 Vdc
250 mA @ 24 Vdc Backplane Power Consumption (typical) 0.6 W Number Of Channels 4 (differential, individually isolated) I/O Chassis Location Any 1746 I/O module slot except slot 0 A/D Conversion Method Sigma-Delta Calibration Factory calibrated
Temperature compensation once a minute
Opto-Electrical Isolation 750 Vdc channel-to-channel
750 Vdc field wiring-to-backplane
Module ID Code
1746sc-INO4i 3521 1746sc-INO4vi 3519
Thermal Dissipation 4.5 W maximum
Chapter 1: Over view And Specifications 3
Table 3. Electrical specifications—outputs
Output Current Ranges (selectable for each channel) 4 to 20 mA
0 to 20 mA 0 to 21 mA
Output Voltage Ranges—INO4vi only (selectable for each channel) -10 to +10 Vdc
0 to 10 Vdc
0 to 5 Vdc 1 to 5 Vdc
SLC Communication Formats (selectable for each channel) Scaled engineering units
Scaled for PID
Proportional counts
1746-NO4 format
User-defined scale Output Impedance
Current Outputs Greater than 1 M Voltage Outputs—INO4vi only Less than 1.0
Load Range
Current Outputs 0 to 500
Voltage Outputs—INO4vi only 1 k and greater Max. Current, Voltage Mode—INI4vi only 10 mA Output Step Response Time 1 ms (0–95% of full scale) Channel Update Time (maximum) 33.7 ms for all 4 channels in parallel Output Resolution 16-bit
Current Outputs 366 nA/count
Voltage Outputs—INO4vi only 320 µV/count Overall Accuracy
Current Outputs 0.08% of full scale @ 25 °C
0.15% of full scale @ 60 °C
Voltage Outputs—INO4vi only 0.08% of full scale @ 25 °C
0.35% of full scale @ 60 °C
Table 4. Physical specifications
LED Indicators Four green channel status indicators, one for each channel
One green module status indicator Recommended Cable Belden 8761 (shielded, twisted-pair) or equivalent Wire Size (maximum) One 12–24 AWG wire per terminal Terminal Block Removable (supplied)
4 SLC 500™ Isolated Analog Output Modules
Table 5. Environmental specifications
Operating Temperature 0 to 60 °C (32 to 140 °F) Storage Temperature -40 to 85 °C (-40 to 185 °F) Relative Humidity 5 to 95% non-condensing Certifications UL/CUL and CE Hazardous Environment Classifications Class I Division 2 Groups ABCD
Chapter
Installing And Wiring Your Module
Read this chapter to install and wire your module. This chapter covers:
• avoiding electrostatic damage
• determining power requirements
• setting the DIP switch
• selecting a rack slot
• inserting your module into the rack
• wiring your module Note that although your module has a jumper on its printed circuit board,
this jumper is for the manufacturer’s use only. Also, your module was calibrated by the manufacturer, so you don’t need to perform this task.
2
Important - For UL and CUL compliance, power and input/output (I/O) wiring must be in accordance with Class I, Division 2, wiring methods [Article 501-4 (b) of the National Electrical Code , NFPA 70] and in accordance with the authority having jurisdiction. Also, you must observe the warnings shown below. Failure to observe these warnings can cause personal injury.
WARNING
!
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I, Division 2;
When in hazardous locations, turn off power before replacing or wiring modules;
Do not disconnect equipment unless power has been switched off or the area is known to be non-hazardous.
6 SLC 500™ Isolated Analog Output Modules
The following documents contain information that may help you as you install and wire your module:
National Electrical Code, published by the National Fire Protection
Association of Boston, MA
• IEEE Standard 518-1977, Guide for the Installation of Electrical
Equipment to Minimize Electrical Noise Inputs to Controllers from External Sources
• IEEE Standard 142-1982, Recommended Practices for Grounding of
Industrial and Commercial Power Systems
Noise Reduction Techniques in Electronic Systems, by Henry W. Ott;
published by Wiley-Interscience of New York in 1976
Avoiding Electrostatic Damage
Guard against electrostatic damage by observing the following precautions:
Determining Power Requirements
CAUTION
!
The backplane of the SLC 500 system can provide both 5 Vdc and 24 Vdc power. The following table shows the maximum current consumed by your module when using these power sources:
ELECTROSTATICALLY SENSITIVE COMPONENTS
• Before handling the module, touch a grounded object to rid yourself of electrostatic charge.
• When handling the module, wear an approved wrist strap grounding device.
• Handle the module from the front, away from the backplane connector. Do not touch backplane connector pins.
• Keep the module in its static-shield container when not in use or during shipment.
Failure to observe these precautions can degrade the module’s performance or cause permanent damage.
Chapter 2: Installing And Wir ing Your Module 7
Table 6. Backplane current consumed
24 Vdc *
Catalog Number 5 Vdc w/o ext. supply w/ ext. supply
1746-sc-INO4i 120 mA 250 mA 0 mA 1746sc-INO4vi 120 mA 250 mA 0 mA
* The 1746sc-INO4i and 1746sc-INO4vi output modules can use an external 24 Vdc power
supply to reduce backplane loading. To use an external 24 Vdc power supply, you must set your module’s DIP switch as indicated in the following subsection.
Use Table 6 to calculate the total load on the system power supply. For more information, see the Allen-Bradley system Installation and Operation Manual.
Setting The DIP Switch
The 1746sc-INO4i and 1746sc-INO4vi output modules have an external 24 Vdc power switch, SW1, giving you the option of using an external power supply:
• With the switch in the RACK position, the module draws all its power
from the backplane of the SLC system.
• With the switch in the EXT position, the module draws its 24 Vdc
power from an external power source; however, the module still draws its 5 Vdc power from the backplane.
The switch, SW1, is located in the bottom corner of the module’s large circuit board.
RACK
1
SW1
EXT
8 SLC 500™ Isolated Analog Output Modules
Selecting A Rack Slot
Inserting Your Module Into The Rack
Two factors determine where you should install your module in the rack: ambient temperature and electrical noise. When selecting a slot for your module, try to position your module:
• in a rack close to the bottom of the enclosure (where the air is cooler)
• away from modules that generate significant heat, such as 32-point input/output modules
• in a slot away from ac or high-voltage dc modules, hard contact switches, relays, and ac motor drives
• away from the rack power supply (if using a modular system)
Remember that in a modular system, the processor always occupies the first slot of the rack.
CA UTION
!
POSSIBLE EQUIPMENT OPERATION
Before installing or removing your module, always disconnect power from the SLC 500 system and from any other source to the module (in other words, don’t “hot swap” your module), and disconnect any devices wired to the module.
Failure to observe this precaution can cause unintended equipment operation and damage.
When inserting your module into the rack, you do not need to remove the supplied 16-position terminal block from the module. If, however, you do remove the terminal block, apply the supplied write-on label to the terminal block, and use the write-on label to identify your module’s location.
To remove the terminal block, unscrew the two retaining screws at the top and bottom of the terminal block, and using a screwdriver or needle­nose pliers, carefully pry the terminal block loose.
Chapter 2: Installing And Wir ing Your Module 9
To insert your module into the rack, follow these steps:
1. Align the circuit board of your module with the card guides at the top and bottom of the chassis.
2. Slide your module into the chassis until both top and bottom retaining clips are secure. Apply firm even pressure on your module to attach it to its backplane connector. Never force your module into the slot.
Cover all unused slots with the Card Slot Filler, Allen-Bradley part number 1746-N2.
To remove your module, press the retaining clips at the top and bottom of your module and slide it out.
10 SLC 500™ Isolated Analog Output Modules
Wiring Y our Module
To wire the terminal block, you need:
• a small, flat-blade screwdriver
• Belden 8761 (shielded, twisted pair) cable or equivalent
CAUTION
!
Before wiring the terminal block, take some time to plan your system:
• Ensure that the SLC 500 system is installed in a NEMA-rated enclosure and that the SLC 500 system is properly grounded.
• Ensure that the load resistance for a current output channel is less than 500 .
POSSIBLE EQUIPMENT OPERATION
Before wiring your module, always disconnect power from the SLC 500 system and from any other source to the module.
Failure to observe this precaution can cause unintended equipment operation and damage.
• Ensure that the load resistance for a voltage output channel is greater than 1 k.
• Route the field wiring away from any other wiring and as far as possible from sources of electrical noise, such as motors, transformers, contactors, and ac devices. As a general rule, allow at lease 6 in. (about 15.2 cm) of separation for every 120 V of power.
• Routing the field wiring in grounded a conduit can reduce electrical noise further.
• If the field wiring must cross ac or power cables, ensure that they cross at right angles.
To wire your module, follow these steps: 1 Determine the length of cable you need to connect a channel to its
field device. Remember to include additional cable to route the drain wire and foil shield to their ground points.
2. At each end of the cable, strip some casing to expose the individual wires.
3. Trim the exposed signal wires to 2 in. lengths. Strip about 3/16 in. (about 5 mm) of insulation away to expose the end of each wire.
Chapter 2: Installing And Wir ing Your Module 11
4. At one end of the cable, twist the drain wire and foil shield together, bend them away from the cable, and apply shrink wrap.
Foil Shield and Drain Wire
Insulation
Clear Wire
Black Wire
5. At the other end of the cable, cut the drain wire and foil shield back to the cable and apply shrink wrap.
Insulation
Clear Wire
Black Wire
6. Connect the wires to the terminal block and field device as shown in the following figures and table. The recommended maximum torque is 5 in-lb (0.565 Nm) for all terminal screws.
To guard against electrostatic damage and improve chassis grounding, connect one of the shield pins on the terminal block of your module to the chassis itself.
Important: For CE compliance, Ferrite EMI Suppressors are needed on each channel’s terminal block connection. Apply the suppressor close to the module terminal block, as shown below. A Steward Part 28B2024-0A0 or equivalent is recommended. The Steward 28B2024­0A0 has an impedance of 157 at 25 MHz, 256 at 100 MHz, and can accommodate one turn of wire.
Figure 1. Ferrite EMI suppressor for CE compliance
Module
7. Repeat steps 1 through 6 for each channel on your module. A system may malfunction due to a change in its operating environment.
After installing and wiring your module, check system operation. See the Allen-Bradley system Installation and Operation Manual for more information.
12 SLC 500™ Isolated Analog Output Modules
Figure 2. Wiring diagrams (showing differential outputs).
-INO4i
-INO4vi
Not used
Current output, ch. 0
Analog ground, ch. 0
Chassis ground
Not used
Current output, ch. 1
Analog ground, ch. 1
Not used
Current output, ch. 2
Analog ground, ch. 2
Chassis ground
Not used
Current output, ch. 3
Analog ground, ch. 3
+24 Vdc external
Ground external
Voltage output, ch. 0 Current output, ch. 0
Analog ground, ch. 0
Chassis ground Voltage output, ch. 1 Current output, ch. 1
Analog ground, ch. 1
Voltage output, ch. 2 Current output, ch. 2
Analog ground, ch. 2
Chassis ground Voltage output, ch. 3 Current output, ch. 3
Analog ground, ch. 3
+24 Vdc external
Ground external
0 1 2 3 4 5 6 7 8
9 10 11 12 13 14 15
0
1
2
3
4
5
6
7
8
9 10 11 12 13 14 15
+
-
+
-
Shielded, twisted-pair cable with shield connected to ground only at one end
To guard against electrostatic damage and improve module grounding, connect a chassis ground pin directly to a rack mounting bolt.
Ext. pwr.
supply
24 Vdc power supply if external power is selected.
+
-
+
-
Shielded, twisted-pair cable with shield connected to ground only at one end
To guard against electrostatic damage and improve module grounding, connect a chassis ground pin directly to a rack mounting bolt.
Ext. pwr.
supply
24 Vdc power supply if external power is selected.
load
load
load
load
Chapter
Things To Consider Before Using Your Module
Read this chapter to familiarize yourself with:
• how the processor communicates with your module
• channel update time
• channel enable and disable times
• temperature calibration time
• output mode change time (-INO4vi only)
• your module’s response to slot disabling
3
How The Processor Communicates With Y our Module
Your processor transfers data to (and receives data from) the processor through an image table residing in the data files of your processor. The processor updates this image table once during each scan of your ladder program. Figure 4 shows the image table for your output module.
Figure 3. Output and input scans
SLC 5/0X
Data Files
Slot e
Output Image
Slot e
Input Image
Output
Scan
Input Scan
-INO4
Output & Input Image
Output Image
8 Words
Input Image
8 Words
Channel Update Time
For an output module, channel update time is the time required for the module to convert the channel data received from the processor to an analog output signal at the terminals.
14 SLC 500™ Isolated Analog Output Modules
In general, you can reduce the channel update time by disabling unused channels, as shown in the following table:
Table 7. Channel update time (channels already enabled ①)
Current output 1 24.3 ms (typical)
Voltage output 1 24.3 (-INO4vi only) 2 26.9
When the module must enable a disabled channel, add 1.2 ms to the time shown.
For the fastest possible channel update time, enable only one channel.
# of ch. enab led Time
2 27.3 3 30.7 4 33.7
3 30.1 4 32.7
Temperature Calibration Time
Output Mode Change Time (-INO4vi only)
Your Module’s Response To Slot Disabling
About once a minute, if no update is occurring, your module performs a temperature calibration. During this time, your module cannot convert the channel data received from the processor to an analog output signal at the terminals. The temperature calibration takes about 56.2 ms.
Whenever the output mode is changed (usually on module start-up), the power supplied to the isolated channels has to go through a power cycle, affecting all 4 channels. During this time, your module cannot convert channel data from the processor to analog output signals at the terminals. The power cycle takes about 5.2 seconds.
By writing to the status file in the modular SLC processor, you can disable any chassis slot. Refer to your SLC programming manual for the slot disable/enable procedure.
CAUTION — POSSIBLE EQUIPMENT OPERATION
!
Always understand the implications of disabling a module before using the slot disable feature.
Failure to observe this precaution can cause unintended equipment operation.
When you disable an output module’s slot, the module holds its outputs in their last state. When you re-enable the output module’s slot, the data that is in the processor image table is converted to an analog output signal during the next scan. Slot disabling only affects enabled channels.
Chapter
Using Your Output Module
Read this chapter to:
• enter your output module’s ID code
• configure each output channel
• set the output data limits or user-defined scale (optional)
• control each output channel’s signal
• monitor each output channel
• check each output channel’s configuration and status To use your module, you need:
4
Entering Y our Module’s ID Code
• programming equipment
• Allen-Bradley Advanced Programming Software (APS) For help with APS, see the Getting Started Guide for APS.
Before using your module, you must configure the slot your module is in by entering your module’s ID code in APS.
When using APS version 6 or later, simply select your module from the list of modules on the system I/O configuration display to automatically enter the ID code.
With earlier versions of APS (4 through 5), you must manually enter the ID code. To enter your module’s ID code, select “other” from the list of modules on the APS system I/O configuration display, and enter your module’s ID code at the prompt. The module ID code for your module is:
Table 8. Output module ID code
Catalog Number Module ID Code
1746sc-INO4i 3521 1746sc-INO4vi 3519
16 SLC 500™ Isolated Analog Output Modules
No special I/O configuration (SPIO CONFIG) information is required. The module ID code automatically assigns the correct number of input and output words for the processor to access.
Figure 4. Output and input words
Address O:e.0
O:e.4
O:e.5
Address I:e.0
15
Channel 1 Configuration Byte
Channel 3 Configuration Byte
Low Value of Output Data Limit (or User-Defined Scale)O:e.6
High Value of Output Data Limit (or User-Defined Scale)O:e.7
15
0
Channel 0 Output Data Word
Channel 1 Output Data WordO:e.1
Channel 2 Output Data WordO:e.2
Channel 3 Output Data WordO:e.3
Channel 0 Configuration Byte
Channel 2 Configuration Byte
0
Channel 0 Data Word
Channel 1 Data WordI:e.1
Channel 2 Data WordI:e.2
Channel 3 Data WordI:e.3
Channel 0 Status WordI:e.4
Channel 1 Status WordI:e.5
Channel 2 Status WordI:e.6
Channel 3 Status WordI:e.7
Example – If you want to reconfigure channel 2 on your module, and it is in slot 4 of the SLC chassis, you would modify the configuration word at address O:4.5. Alternatively, if you want to obtain the status of channel 2, you would check the status word at address I:4.6.
Chapter 4: Using Your Output Module 17
Output Image
The 8-word, output image (defined as the output from the SLC processor to your module) defines how each channel on your module works:
• The output data words control output signal levels for each channel.
• The configuration bytes replace configuration DIP switches on your
module. In your output module, each word configures two channels (one independent byte per channel).
• The output limit values define minimum and maximum output data
values, if output data limits are properly enabled.
• The user-defined scale values define how your module scales output
data values to analog output signals, if the User-Defined Scale data format is selected.
For more information on the user-defined scale and output data limits, see Optional: Setting The Output Data Limits (or User-Defined Scale), later in this chapter.
Input Image
The 8-word, input image (defined as the input from your module to the SLC processor) holds the data received by your module and provides the status (configuration and operational state) of each channel.
Important – A data word is valid only when the channel is enabled and there are no channel errors. A status word is valid only when the channel is enabled and the module has processed all configuration changes.
18 SLC 500™ Isolated Analog Output Modules
Configuring Each Output Channel
After installing your module, you must configure each channel by setting bit values in each configuration word. Output words 4 and 5 of the output image file (addresses O:e.4 and O:e.5) configure channels 0–1 and 2–3, respectively.
Address O:e.4
O:e.5
15
Channel 1 Configuration Byte
Channel 3 Configuration Byte
Channel 0 Configuration Byte
Channel 2 Configuration Byte
A detailed explanation appears in the following table:
Table 9. Channel configuration word details, Output Words 4 and 5 (O:e .4 and O:e.5)
To select… Use these bit settings...
For Channel 1 (and 3) For Channel 0 (and 2)
Bit: 15 14 13 12 11 10 9 8 7654 3210
Output channel disable 0 0 Output channel enable 1 1
±10 Vdc output range (-INO4vi only) 0 0 0 0 0 0 1–5 Vdc output range (-INO4vi only) 0 0 1 0 0 1 0–5 Vdc output range (-INO4vi only) 0 1 0 0 1 0 0–10 Vdc output range (-INO4vi only) 0 1 1 0 1 1 0–20 mA output range 1 0 0 1 0 0 4–20 mA output range 1 0 1 1 0 1 0–21 mA output range 1 1 0 1 1 0 Invalid 1 1 1 1 1 1
Engineering units 0 0 0 0 0 0 Scaled for PID 0 0 1 0 0 1 Proportional counts 0 1 0 0 1 0 1746-NO4 compatible format 0 1 1 0 1 1 User-defined scale 1 1 0 1 1 0 Invalid 1 0 0 1 0 0 Invalid 1 0 1 1 0 1 Invalid 1 1 1 1 1 1
Reset output on fault 0 0 Hold last value on fault 1 1
0
Chapter 4: Using Your Output Module 19
Output Channel Enable (configuration bits 0 and 8)
Use this bit to enable or disable a channel. To minimize update times, disable any unused channels.
When you set the channel enable bit to one, the module reads the configuration word. Before accepting any new data as valid, verify that the status word (described in the last subsection of this chapter) reflects the changes you made.
While the channel enable bit is set to zero, the channel data word and status word are also set to zero. When you reset the channel enable bit to one, the channel data word remains set to zero until your module updates the channel status word.
Output Range (configuration bits 1–3 and 9–11)
Use this bit field to configure the channel for the type of output device you have connected to the module.
Data Format (configuration bits 4–6 and 12–14)
Use this bit field to select one of the following formats:
• engineering units (mV or nA)
• scaled for PID (works with the SLC PID instruction)
• proportional counts (two’s complement binary)
• 1746-NO4 compatible format (the format used by the 1746-NO4)
• user-defined scale These data formats are defined in the following table:
20 SLC 500™ Isolated Analog Output Modules
Table 10. Data format definitions
Selected Data Value (counts) Corresponding Signal
Data Format Output Range Min. Max. Min. Max.
Engineering Units ±10 V -10250 +10250 -10.25 V +10.25 V
0–10 V -500 +10250 -0.50 V +10.25 V 0–5 V -500 +5500 -0.50 V +5.50 V 1–5 V +500 +5500 +0.50 V +5.50 V 0–20 mA 0 +20500 0.0 mA +20.5 mA 0–21 mA 0 +21500 0.0 mA +21.5 mA 4–20 mA +3500 +20500 +3.5 mA +20.5 mA
Scaled for PID ±10 V 0 +16383 -10 V +10 V
0–10 V 0 +16383 0 V +10 V 0–5 V 0 +16383 0 V +5 V 1–5 V 0 +16383 +1 V +5 V 0–20 mA 0 +16383 0 mA +20 mA 0–21 mA 0 +16383 0 mA +21 mA 4–20 mA 0 +16383 +4 mA +20 mA
Proportional Counts ±10 V -32768 +32767 -10.25 V +10.25 V
0–10 V -32768 +32767 -0.50 V +10.25 V 0–5 V -32768 +32767 -0.50 V +5.50 V 1–5 V -32768 +32767 +0.50 V +5.50 V 0–20 mA -32768 +32767 0.0 mA +20.5 mA 0–21 mA -32768 +32767 0.0 mA +21.5 mA 4–20 mA -32768 +32767 +3.5 mA +20.5 mA
1746-NO4- ±10 V -32768 +32767 -10 V +10 V Compatible
User-Defined ±10 V -10.25 V +10.25 V Scale 0–10 V -0.50 V +10.25 V
0–10 V 0 +32767 0 V +10 V 0–5 V 0 +16384 0 V +5 V 1–5 V +3277 +16384 +1 V +5 V 0–20 mA 0 +31208 0 mA +20 mA 0–21 mA 0 +32767 0 mA +21 mA 4–20 mA +6242 +31208 +4 mA +20 mA
0–5 V -0.50 V +5.50 V 1–5 V See note 0–20 mA 0.0 mA +20.5 mA 0–21 mA 0.0 mA +21.5 mA 4–20 mA +3.5 mA +20.5 mA
+0.50 V +5.50 V
Provides direct compatibility with the 1746-NO4 module.
For the user-defined scale, the data in output words 6 and 7 determine the count limits. See the next subsection, for information on the User-Defined Scale data format.
Optional: Setting The Output Data Limits (or User-Defined Scale)
,
Optional: Setting The Output Data Limits (or User-Defined Scale)
Chapter 4: Using Your Output Module 21
Reset Output Or Hold Last Value On Fault (configuration bits 7 and 15)
Use this bit to select how your module responds to a fault:
• If you set this bit to 1, your module holds the output signal at its last
value when it detects a fault.
• If you set this bit to 0, your module resets the output signal to the
power-up setting (0 V or 0 mA) when it detects a fault.
Words 6 and 7 of the output image file (addresses O:e.6 and O:e.7) let you define either:
• the low and high values of the output data limits
or
• the low and high values of the user-defined scale, if the User-Defined
Scale data format is selected
Address O:e.6
15
Low Value of Output Data Limit (or User-Defined Scale)
High Value of Output Data Limit (or User-Defined Scale)O:e.7
If you do not want to use user-defined scaling or output data limiting, set output words 6 and 7 to zero. Setting output words 6 and 7 to zero disables output data limiting and invalidates user-defined scaling.
Because they share the same output words, you cannot use output data limiting with the User-Defined Scale data format.
Important – The values in output words 6 and 7 apply to all four channels. If you want to use user-defined scaling or output data limiting, you must set all four channels to the same data format.
Output Data Limits
For added safety, the 1746sc-INO4i and 1746sc-INO4vi output modules let you define limits for the values in the output data words of all four channels. These data limits, in turn, limit the output signals that your module provides. When an output data word exceeds the data limit, the output value is truncated to the limit.
0
You can use output data limiting to prevent PID loops from exceeding safety limits, to prevent operators from inadvertently setting incorrect values, etc.
To properly enable output data limiting, the low and high output limits (output words 6 and 7, respectively) musts be non-zero and non-equal,
22 SLC 500™ Isolated Analog Output Modules
and the low limit (output word 6) must be lower than the high limit (output word 7).
Example – Suppose you have four valves with a ±10 V operating range, and you want to use the Engineering Units data format. For this application, you would use the following bit settings for the channel configuration bytes (output words 4 and 5):
Address O:e.4
O:e.5
Suppose, also, that you would like to set the output limits to -2 V and +8 V. After entering the above bit settings for output words 4 and 5, you would enter the following for output words 6 and 7:
Address O:e.6
O:e.7
Your module will now limit the output signal as shown below.
+10.25 V
+8 V
Output Signal
15
0000
0000 0001 0000 0001
15
1111
0001 1111 0100 0000
0001 0000
1000 0011
0001
0000
Data Limit High
0
0
-2 V
-10.25 V
Data Limit Low
Note that whenever the requested output data values meet or attempt to exceed the output data limits, your module sets bits 10 or 11 in the channel status word to indicate a limit error. Note also that words 0 through 3 of the input image file (addresses I:e.0 through I:e.3) reflect the requested output data values and are not truncated.
Chapter 4: Using Your Output Module 23
User-Defined Scale
For special applications, the 1746sc-INO4i and 1746sc-INO4vi output modules let you define a custom data format. This “user-defined scale” is very similar to the “proportional counts” data format—except that instead of converting the output data to an output signal using a previously defined scale (-32,768 to 32,767), your module converts the output data using a scale defined by the values in output words 6 (low limit of scale) and 7 (high limit of scale).
The high limit value must be greater than the low limit value for proper operation. Also, the difference between the low and high values should be greater than 1024 counts. If the difference between the low and high values is less than 1024 counts, unexpected results can occur (especially at the extreme ends of the range).
You select the data format for each channel using that channel’s configuration bits, described in the previous subsection, Configuring Each Output Channel.
The following equations show you how to convert user-defined scale units (or any type of units) to engineering units, and vice versa:
S = {(U - U D = {(S - S
) × (S) ÷ (∆U)} + S
low
) × (U) ÷ (∆S)} + U
low
low
low
where S = signal value (in engineering units, such as psi)
S
= low limit of signal value
low
S
= high limit of signal value
high
S= S
high
- S
low
D = data value (user-defined scale)
U
= low value of user-defined scale
low
U
= high value of user-defined scale
high
U= U
high
- U
low
Example – Suppose you have a valve with a 4–20 mA range, and you want your scale to go from 100 to 9999 counts. For a 4–20 mA output with user-defined scaling, your module sets the signal limits to 3.5 mA and 20.5 mA (see Table 14). After entering 100 and 9999 into output words 6 and 7, respectively, the relationship between data value (counts) and output signal would be as follows:
24 SLC 500™ Isolated Analog Output Modules
Figure 5. Example relationship between output signal and channel data
Data Value
9999
Controlling Each Output Channel’s Signal
100
20.5 mA3.5 mA
Signal
Value
In the preceding example...
S
= 3.5 U
low
S
= 20.5 U
high
low
high
= 100 = 9999
S = 17 U = 9899
Output words 0 through 3 determine the output signal levels for channels 0 through 3, respectively. The output signal level depends on the output range and data format selected.
Address O:e.0
15
0
Channel 0 Output Data Word
Channel 1 Output Data WordO:e.1
Channel 2 Output Data WordO:e.2
Channel 3 Output Data WordO:e.3
Monitoring Each Output Channel
Chapter 4: Using Your Output Module 25
The requested output data values are reflected in words 0 through 3 of the input image file (addresses I:e.0 through I:e.3). Whenever a channel is disabled, its data word is reset to zero.
Checking Each Output Channel’s Configuration And Status
Address I:e.0
15
Channel 0 Data Word
Channel 1 Data WordI:e.1
Channel 2 Data WordI:e.2
Channel 3 Data WordI:e.3
Words 4 through 7 of the input image file (addresses I:e.4 through I:e.7) reflect the configuration and status of each channel. Use the data provided in these status words to determine if the configuration data for any channel is valid.
Address I:e.4
15
Channel 0 Status Word
Channel 1 Status WordI:e.5
Channel 2 Status WordI:e.6
Channel 3 Status WordI:e.7
0
0
Whenever a channel is disabled, its status word is set to zero. A detailed explanation appears in Table 12.
26 SLC 500™ Isolated Analog Output Modules
Table 11. Channel status word details, Input Words 4 through 7 (I:e.4 through I:e.7)
These bit settings in the status word Indicate this
Bit: 15 14 13 12 11 10 9 8 7654 3210
0 Output channel disabled 1 Output channel enabled
0 0 1 1–5 Vdc output range 0 1 0 0–5 Vdc output range 0 1 1 0–10 Vdc output range 1 0 0 0–20 mA output range 1 0 1 4–20 mA output range 1 1 0 0–21 mA output range
0 0 0 Engineering units 0 0 1 Scaled for PID 0 1 0 Proportional counts 0 1 1 1746-NO4 format 1 1 0 User-defined scale
0 Reset output on fault 1 Hold last value on fault
0 No output data limiting 1 Output data limiting
0 No error 1 Operating temperature error
0 No error 1 Over-limit error
0 No error 1 Under-limit error
0 No error 1 Over-range error
0 No error 1 Under-range error
0 No error 1 Non-fatal channel error
0 No error 1 Fatal channel error
Chapter 4: Using Your Output Module 27
The first 8 status bits reflect the settings in the channel configuration word. The remaining status bits flag the various errors that the module can detect.
Output Data Limiting Enabled (status bit 8)
This bit is set to one whenever output data limiting is properly enabled. To properly enable output data limiting, the low and high output limits (output words 6 and 7, respectively) musts be non-zero and non-equal, and the low limit (output word 6) must be lower than the high limit (output word 7). See Optional: Setting The Output Data Limits (or User- Defined Scale), earlier in this chapter, for more information.
Operating Temperature Error (status bit 9)
This bit is set to one whenever the operating temperature exceeds the specified range (0 to 60 ˚C). This bit is reset to zero when the operating temperature returns to the specified range.
Over-Limit Error (status bit 10)
This bit is set to one whenever the output data meets or attempts to exceed the output data limit in output word 7, if output data limiting is properly enabled. This bit is reset to zero when the output data falls below the output data limit in output word 7.
Under-Limit Error (status bit 11)
This bit is set to one whenever the output data meets or attempts to exceed the output data limit in output word 6, if output data limiting is properly enabled. This bit is reset to zero when the output data rises above the output data limit in output word 6.
Over-Range Error (status bit 12)
This bit is set to one whenever the output data meets or attempts to exceed the maximum count limit defined by the data format and output range selected (see Table 11). This bit is reset to zero when the output data falls below the maximum count limit.
Under-Range Error (status bit 13)
This bit is set to one whenever the output data meets or attempts to exceed the minimum count limit defined by the data format and output range selected (see Table 11). This bit is reset to zero when the output data rises above the minimum count limit.
Non-Fatal Channel Error (status bit 14)
This bit is set to one whenever your module detects a recoverable channel error, such as an invalid configuration word or an operating temperature error (see above), or while the SLC 500 processor is resetting. This bit is reset to zero when the error no longer exists.
28 SLC 500™ Isolated Analog Output Modules
Fatal Channel Error (status bit 15)
This bit is set to one whenever your module detects a “non-recoverable” channel error, such as a software power-up failure due to corrupt hardware or malfunctioning software. You may be able to recover from this type of error by resetting the SLC 500 processor or cycling power to your module.
Chapter
Testing Your Module
Read this chapter to prevent potential problems. This chapter covers:
• inspecting your module
• disconnecting prime movers
• powering up
• interpreting the LED indicators
• interpreting I/O error codes
• troubleshooting Before testing your module, test your SLC 500 system using the
procedures described in your Allen-Bradley system Installation & Operation Manual.
5
Inspecting Your Module
Important — If your module appears to be functioning, but the terminals aren’t providing an output signal, the 24 Vdc power source (backplane or external) may not be providing enough current (250 mA).
You can prevent many potential problems by simply inspecting your analog module:
1. Ensure that the external 24 Vdc power switch (SW1, located in the
bottom corner of the module’s large circuit board) is set properly:
• With the switch in the RACK position, the module draws all its
power from the backplane of the SLC system.
• With the switch in the EXT position, the module draws its 24 Vdc
power from an external power source; however, the module still draws its 5 Vdc power from the backplane.
2. Ensure that all wire connections are correct and secure and that no
wires are missing or broken. Refer to Chapter 2, Installing And Wiring Your Module, for more information.
3. Ensure that the shield for the cable used to wire your module is
properly grounded.
4. Ensure that the removable terminal block on your module is secure.
30 SLC 500™ Isolated Analog Output Modules
Disconnecting Prime Movers
Before testing your module, ensure that machine motion will not occur:
• Disconnect motor wires at the motor starter or the motor itself. This
lets you test the operation of the starter coil, verifying that the output circuit is wired correctly and functioning.
• Disconnect solenoids by disengaging the solenoid valves, leaving the
coils connected.
If you cannot disconnect a device in the preferred way, open the output circuit as close as possible to the motion-causing device.
Example – If you have a relay coil that in turn energizes a motor starter and you cannot disconnect the motor wires, open the circuit at a point between the motor starter and the relay contact.
WARNING
!
POSSIBLE UNEXPECTED MACHINE MOTION
Powering Up
During all testing, always disconnect all devices that, when energized, might cause machine motion.
Failure to observe this precaution can cause equipment damage or personal injury.
When you apply power to the system, your module’s status LED should illuminate, indicating that your module is receiving power and has completed its onboard self-test. If the LED does not illuminate after several seconds, your module is not functional. Discontinue testing until you can get the LED to illuminate.
The most probable reasons for the LED not illuminating are:
• The SLC 500 system is not receiving power from its power supply.
• The rest of the SLC 500 system is not receiving power.
• The rack slot where your module is located is defective.
• Your module is defective.
Interpreting The LED Indicators
Chapter 5: Testing Your Module 31
Your output module has 5 LEDs: 4 channel status LEDs (numbered 0–3 for channels 0–3, respectively) and 1 module status LED.
Figure 6. LED block
OUTPUT
Status
012
3
Channel
Module Status
Isolated Analog
Use the following table to interpret the LEDs:
Table 12. LED definition
If the module And the channel
status LED is… status LED is… Then...
On On The channel is enabled.
Blinking One of the following channel errors occurred:
circuit open (4–20 mA outputs only)
signal is near or beyond end of range
channel configured incorrectly Refer to the f ollo wing section,
Off Either your module is powering up or the channel
is disabled.
Off Off Either the power is off, the module is powering up,
or a module fault occurred. Cycle power. If the condition persists, call your local distributor or Spectrum Controls for assistance.
Troubleshooting.
Interpreting I/O Error Codes
I/O error codes appear in word S:6 of the SLC processor status file. The first two digits of the error code identify the slot (in hexadecimal) with the error. The last two digits identify the I/O error code (in hexadecimal).
The error codes that apply to your module include (in hexadecimal):
• 50–5E
• 71 (watchdog error)
• 90–94 For a description of the error codes, refer to the Allen-Bradley Advanced
Programming Software (APS) Reference Manual, Allen-Bradley publication 1746-6.11.
32 SLC 500™ Isolated Analog Output Modules
Troubleshooting
Module
Status LED
off.
Module fault
condition.
Check to see
that module is
seated properly
in chassis.
Cycle power.
Figure 7. Problem resolution flowchart
Check LEDs
on module.
Channel
Status LED(s)
blinking.
Fault
condition.
Check channel
status word
bits 9–15.
Module
Status LED
on.
Channel
Status LED(s)
off.
Channel is
not enabled.
Enable channel if desired by setting
channel config.
word (bit 0 = 1).
Retry.
Channel
Status LED(s)
on.
Channel is
enabled but not
working.
Verify module power
(external and/or
rack). Retry
Is problem corrected?
No
Contact you local
distributor or
Spectrum
Controls.
Yes
End
Bit 15
set (1)
Bit 14
set (1)
Bit 13
set (1)
Bit 12
set (1)
Bit 11
set (1)
Bit 10
set (1)
Bit 9
set (1)
Fatal channel error. Reset the processor or cycle power to your module.
Non-fatal channel error . Check the configuration byte. Correct and Retry.
Under-range error. Check the output data word and Table 11. Correct and Retry.
Over-range error. Check the output data word and Table 11. Correct and Retry.
Under-limit error. Check the output data word and limit (O:e.6). Correct and Retry.
Over-limit error. Check the output data word and limit (O:e.7). Correct and Retry.
Operating temperature error. Check the ambient temp. Correct and Retry.
End
Is problem corrected?
No
Contact you local
distributor or
Spectrum
Controls.
Is problem
corrected?
No
Contact you local
distributor or
Spectrum Controls.
Yes
End
Yes
End
Chapter
Maintaining Your Module And Ensuring Safety
Read this chapter to familiarize yourself with:
• preventive maintenance
• safety considerations The National Fire Protection Association (NFPA) recommends
maintenance procedures for electrical equipment. Refer to article 70B of the NFPA for general safety-related work practices.
6
Preventive Maintenance
Safety Considerations
The printed circuit boards of your module must be protected from dirt, oil, moisture, and other airborne contaminants. To protect these boards, install the SLC 500 system in an enclosure suitable for its operating environment. Keep the interior of the enclosure clean, and whenever possible, keep the enclosure door closed.
Also, regularly inspect the terminal connections for tightness. Loose connections may cause a malfunctioning of the SLC system or damage to the components.
WARNING
!
POSSIBLE LOOSE CONNECTIONS
Before inspecting connections, always ensure that incoming power is OFF.
Failure to observe this precaution can cause personal injury and equipment damage.
Safety is always the most important consideration. Actively think about the safety of yourself and others, as well as the condition of your equipment. The following are some things to consider:
Indicator Lights – When the module status LED on your module is illuminated, your module is receiving power.
Activating Devices When Troubleshooting – Never reach into a machine to activate a device; the machine may move unexpectedly. Use a wooden stick.
34 SLC 500™ Isolated Analog Output Modules
Standing Clear Of Machinery – When troubleshooting a problem with any SLC 500 system, have all personnel remain clear of machinery. The problem may be intermittent, and the machine may move unexpectedly. Have someone ready to operate an emergency stop switch.
CAUTION
!
Safety Circuits – Circuits installed on machinery for safety reasons (like over-travel limit switches, stop push-buttons, and interlocks) should always be hard-wired to the master control relay. These circuits should also be wired in series so that when any one circuit opens, the master control relay is de-energized, thereby removing power. Never modify these circuits to defeat their function. Serious injury or equipment damage may result.
Refer to your system’s Installation & Operation Manual for more information.
POSSIBLE EQUIPMENT OPERATION
Never reach into a machine to actuate a switch. Also, remove all electrical power at the main power disconnect switches before checking electrical connections or inputs/ outputs causing machine motion.
Failure to observe these precautions can cause personal injury or equipment damage.
Getting Technical Assistance
Declaration of Conformity
If you need technical assistance, please review the information in Chapter 5, “Testing Your Module,” before calling your local distributor of Spectrum Controls.
Note that your module contains electronic components which are susceptible to damage from electrostatic discharge (ESD). An electrostatic charge can accumulate on the surface of ordinary plastic wrapping or cushioning material. In the unlikely event that the module
should need to be returned to Spectrum Controls, please ensure that the unit is enclosed in approved ESD packaging (such as static-shielding / metallized bag or black conductive container).
Spectrum Controls reserves the right to void the warranty on any unit that is improperly packaged for shipment.
For further information or assistance, please contact your local distributor or call Spectrum Controls Customer Satisfaction department at (425) 746­9481 from 8:00 A.M. to 5:00 P.M. Pacific Time.
A vailable upon request.
The ENCOMPASS logo and SLC 500 are trademarks of Allen-Bradley Company, Inc. Copyright © 1997-2004 Spectrum Controls, Inc. All rights reserved. Printed in U.S.A. Specifications subject to change without notice. Publication 0300128-03 Rev. D May 2004
Corporate Headquarters
Spectrum Controls Inc. P.O. Box 5533 Bellevue, Washington 98006 Fax: (425) 641-9473
Tel: (425) 746-9481
Web Site: http://www.industry.net/spectrum.controls
E-mail: spectrum@spectrumctls.com
Loading...