(Cat. No. Quantum Automation Series 140 AxI 05x 00sc)
Installation Instructions
Input Module Catalog Numbers:
140 ACI 050 00scCurrent Only
140 AVI 050 00scVoltage Only
140 ACI 051 00scSelectable Current or Voltage
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
PREFACE
+ Note: Power, input and output (I/O) wiring must be in accordance with Class 1, Division 2 wiring
methods [Article 501-4 (b) of the National Electrical Code, NFPA 70] and in accordance with the
authority having jurisdiction.”
+ Note: Peripheral equipment must be suitable for the location in which it is used.
WARNING
ELECTROSTATICALLY SENSITIVE COMPONENTS
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I,
Division 2.
WARNING
EXPLOSION HAZARD
Do not disconnect equipment unless power has been switched off or
the area is known to be non hazardous.
WARNING
This equipment is suitable for use in Class I, Division 2, Groups A, B,
C, and D or non-hazardous locations only.
i
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
WARNING
EXPLOSION HAZARD
When in hazardous locations, turn off
power before replacing or wiring modules.
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
Chapter 1
OVERVIEW
Throughout this installation and operation guide, unless reference is being
made to one specific version of the module, the designation 140 AxI 05x
00sc will be used for generic reference purposes. The 140 AxI 05x 00sc
consists of a series of four analog input modules, each with 32 channels
of input. The differentiation between the four different modules is shown
in the table below.
140 ACI 050 00sccurrent only
140 AVI 050 00scvoltage only
140 ACI 051 00sccurrent or voltage combination
*140 ACI 052 00sccurrent or voltage combination with time and date stamping
* The 140 ACI 052 00sc Time Stamp option is covered in a separate manual.
Each module will accept 32 single ended analog inputs. The inputs are
divided into four groups of eight inputs each. Each group has 15V
isolation to the other groups. Analog inputs within a group has 0V of
isolation channel-to-channel. All inputs have 500V ac isolation channelto-backplane.
These modules have been designed for projects that include large quantities of analog inputs. Process control and data acquisition applications for
industries such as utilities, waste water, oil and gas, food and beverage,
and building automation are ideally suited for this module. The time and
date stamp version of the module is perfect for remote terminal unit
(RTU) applications or for supervisory control and data acquisition
(SCADA) applications requiring programmable alarm levels.
Input channels include over voltage circuit protection, over and under
range detection and active notch filtering. The voltage mode of the
module handles four different voltage ranges and the current mode
handles two current ranges. You can configure the module to provide
data in one of four data formats. Set up of the module is very simple
through the use of configuration and status registers using Concept,
Modsoft or Taylor programming software.
1
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
1.1Inputs
The module can be purchased as current only, voltage only, current or
voltage combination, or as a current or voltage combination with a time
stamp option. The 32 channels are separated into four groups of eight.
Each group can be configured for a different voltage or current range.
The ranges available are as follows:
Current Ranges
• 4-20 mA, 0-20 mA
Voltage Ranges:
• ±10VDC, 0-10VDC, 0-5VDC, 1-5VD
The module can provide data to the PLC in the following formats:
• 12 bit (0 to 4095)
• signed 15 bit (-32768 to +32767)
• unsigned 16 bit (0 to 65535)
• DVM (0 to 10000)
• Input Filter Options (10Hz, 50Hz, 60Hz, 1kHz)
2
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
1.2LEDs
The module has a front LED panel that includes 35 LEDs:
Ready LED -
1 Green LED indicates module’s self test has passed and is ready to
communicate.
Active LED -
1 Green LED indicates BUS communication is established between the
module and the rack.
Fault LED -
1 Red LED indicates a module self test error, or fatal H/W error. A blink
code will indicate the type of self test error. Count the number of blinks
before a pause to determine the error code in the table below.
FaultLED Blink Code
Blink #Fault
3DPM Test Error
4CPU Error
5Watchdog Timer Error
6RAM Error
7Flash EPROM CRC Error
8Calibration EEPROM Error
Channel LED -
32 Green LEDs indicates the channel is enabled and a valid input signal
level is present. The LED is off if the channel is disabled. A blinking
LED indicates that the channel has exceeded a range limit.
3
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
1.3Related Publications
•Modicon Modsoft Programmer User Manual. 890 USE 115 00
•Modicon TSX Quantum Automation Series Hardware Reference
Guide. 840 USE 100 00
•IEEE Std 518- 1977, Guide for the Installation of Electrical Noise
Inputs to Controllers from External Sources
•IEEE Std 142- 1982, Recommended Practice for Grounding of
Industrial and Commercial Power Systems
•Noise Reduction Techniques in Electronic Systems, by Henry W.
Ott; published by Wiley-Interscience of New York in 1976
4
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
Chapter 2
MODULE SETUP FOR MODSOFT
2.1General Information
Six steps must be performed in order to fully configure the Quantum
system in preparation for using the AxI 05x 00sc:
Step 1: Modsoft programming software must be updated so that the
140 AxI 05x 00sc is recognized in the software (see Section 2.2).
Step 2: Select the appropriate slot location using the Modsoft I/O map.
Choose the first 3x and 4x level registers to be used in the
system for the module’s data, configuration and status information (see Section 2.3).
Step 3: Zoom screens for the module must be set to match application
requirements (see Section 2.4).
Step 4: The 4x configuration register must be set to meet application
requirements (see Section 4.1).
Step 5: Module status information is available to you. The various
options must be understood and chosen to meet your application
requirements (see Section 4.2 and Section 4.3).
Step 6: Ladder rungs must be written to demultiplex the incoming 8 data
registers to 32 user selected data registers (see Section 6.3).
5
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
2.2Installation of new run time files
If you are using the Modsoft programming software version 2.4 or 2.5, it
is necessary to update the following runtime files in order for Modsoft to
recognize your module. Versions prior to 2.4 are not supported. Version
This may be accomplished by first identifying the pathname where you
have installed your Modsoft programming software and the drive letter of
the floppy drive from which you intend to install. A typical pathname
assuming installation of the C: drive is as follows:
C:\MODSOFT
The new runtime files required to use all versions of this module are
supplied on the 3.5 inch MSDOS formatted floppy disk titled:
“Quantum Runtime Files,” Spectrum Controls, Inc Part Number: 20500121-xx
To install these files, operate your PC in MSDOS mode, perform the
following command:
C:>\COPY A:*.SYS C:\MODSOFT\RUNTIME
+ Note: This assumes you are installing from drive A: and that you have previously installed
Modsoft in the directory C:\MODSOFT . If not, you must make the appropriate substitutions.
2.3General information on data register usage and terminology:
A total of nine 3x level and one 4x level registers are used by the 140 AxI
05x 00sc. After you have completed the runtime file installation, you can
go to the I/O Map screen and choose the 140 AxI 05x 00sc by selecting
the desired slot, pressing <Shift + ?> which will display the modules
available for configuration into that slot. For module specific help, press
<ALT + H>. After selecting the module, you must set the first 3x and 4x
level registers to be used. This will then automatically capture nine
consecutive 3x level and one 4x level register for use by the module. The
architecture for this 32-channel module is as follows:
6
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
4xConfiguration Word
3x + 0Data Input Word 1
3x + 1Data Input Word 2
3x + 2Data Input Word 3
3x + 3Data Input Word 4
3x + 4Data Input Word 5
3x + 5Data Input Word 6
3x + 6Data Input Word 7
3x + 7Data Input Word 8
3x + 8Status Word
The AxI 05x 00sc multiplexes 32 channels of data into four groups of
eight channels. Each group can be selected through the 4x Configuration
Word or can automatically sequence through all four groups of channels.
Group 1Chn 1-8
3x + 0Data Input Word 1
3x + 1Data Input Word 2Group 2Chn 9-16
3x + 2Data Input Word 3
3x + 3Data Input Word 4Group 3Chn 17-24
3x + 4Data Input Word 5
3x + 5Data Input Word 6Group 4Chn 25-32
3x + 6Data Input Word 7
3x + 7Data Input Word 8
2.4Zoom Screen Configuration
For Zoom Screen operation, please refer to Modicon’s Modsoft Programmer User Manual.
Note: T o enter zoom screens from the I/O map menu, highlight the module entry and press the
keys <ALT - Z>.
Most of the module setup will be done through the Modsoft zoom
screens. The zoom screen setup establishes the following parameters:
• Calibration rate
• Filter Frequency Selection
• Input Data Format
• Input Range
7
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
• Differential Mode
The primary zoom screen for this module is shown in Figure 2.1. By
selecting a particular parameter, you will be given the options associated
with that parameter. Note that the calibration rate is set only once for
the entire module, and all other selections are set once for each group of
eight inputs.
Calibration rate: The Quantum module performs an on board
system calibration at power up. The system calibration corrects for
temperature drift of the Analog to Digital Convertor (ADC) and related
circuitry. System calibration can be performed periodically based on the
calibration rate selected below. This can affect the update time for the
module. For installations where the ambient temperature surrounding the
I/O rack can change relatively quickly, the user might consider going to a
more frequent calibration selection in order to improve the accuracy of
the reading being taken. The autocalibration schedule rate may be
selected from the following:
Once at power up only
Every 1 min
Every 10 min[default]
Every 30 min
8
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
Selecting an autocalibration schedule rate is an exercise in tradeoffs.
Performing autocalibration more frequently may result in greater accuracy due to variations caused by environmental factors such as temperature. This accuracy has a cost in the burden imposed by performing the
calibration. The calibration time is a function of the filter frequency.
Calibration times are listed below. The system cannot update the channel
data while performing calibration. In addition, if multiple filter frequencies
are selected, calibrations for each frequency and the execution time is
cumulative. The worst case calibration time is when all filter frequencies
are enabled (10, 50, 60 and 1000 Hz). The time is then the total for all
four times listed below. Also, note that the channel enables have no
effect on the auto calibration feature. If a filter frequency is enabled via
the zoom screens, then the autocalibration is performed for the frequency.
Filter Frequency Selection: The Analog-to-Digital Conversion
performs a filter function on the input signal. One of the following filter frequencies may be selected for each of the four groups
of eight channels:
Filter:10 Hz
50 Hz
60 H z[default]
1000 Hz
Input data format: One of the following data formats may be
selected for each of the four groups of eight channels:
Format:16-bit Format
Voltmeter[default]
12-bit Format
15-bit plus sign Format
Note: The module’s format selection must be compatible with the register format selected
in Modsoft.
9
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
Input Range: Depending on the module that you have purchased,
one of the following input ranges may be selected for each of
the four groups of eight channels:
Range:-10 to +10 V[default V oltage or V/I Modules]
1 to +5V
0 to +5V
0 to +10V
4 to 20mA[default Current Modules]
0 to 20mA
Differential mode: One of the following acquisition modes may
be selected for each of the four groups of eight channels. Differential mode calculates the difference between two consecutive
channel inputs and provides the data to the register assigned for
the first channel in the pair. When differential mode is enabled,
the second channel’s output will be zero. The data acquisition
between the two channels is not synchronized so common mode
noise on the signal pair may not be fully removed, however DC
offsets should be compensated for correctly.
10
Note: The channel pairs are not being updated simultaneously , this could lead to an
error in the actual differential value that is calculated. See figure 2.1
Differential Mode:Disabled [default]
Enabled
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
Chapter 3
MODULE SETUP FOR CONCEPT
3.1General Information
Six steps must be performed in order to fully configure the Quantum
system in preparation for using the AxI 05x 00sc:
Step 1: Concept programming software (Version 2.1 or newer) must be
updated so that the 140 AxI 05x 00sc is recognized in the software (see Section 3.2).
Step 2: Select the appropriate slot location using the Concept I/O map
editor. Choose the first 3x and 4x level registers to be used in the
system for the module’s data, configuration and status information (see Section 3.3).
Step 3: Parameters for the module must be set to match application
requirements (see Section 3.4).
Step 4: The 4x configuration register must be set to meet application
requirements (see Section 4.1).
Step 5: Module status information is available to you. The various
options must be understood and chosen to meet your application
requirements (see Section 4.2 and Section 4.3).
Step 6: Ladder rungs must be written to demultiplex the incoming 8 data
registers to 32 user selected data registers (see Section 6.3).
11
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
3.2Installation of new run time files
The 140 AxI 05x 00sc is manufactured by Spectrum Controls, Inc.
Follow the Concept installation procedure for outsourced modules. This
requires the install disk provided with your module, which includes the
following files (assuming drive A:):
A:\CONCEPT\SPECTRUM.MDC- SpectrumI/O for Quantum Module Definition file.
A:\CONCEPT\SPECTRUM.HLP- Spectrum I/O for Quantum Help file.
To update the Concept database with a new Spectrum I/O module:
1.Insert the install disk into drive A:
2.Start the Concept Modconnect Tool (Modconf.exe).
3.Open the installation file “SPECTRUM.MDC”
4.Select the module to add or press the “Add All” button
5.Save the changes before exiting the Modconnect tool.
This will update the Concept database permanently unless you later undo
the changes using the Modconnect Tool, or perform a new Concept
software install.
3.3General information on data register usage and terminology:
A total of nine 3x level and one 4x level registers are used by the 140 AxI
05x 00sc. After you have completed adding the modules to the Concept
database using the Modconnect tool, you can add a module to a drop by
using the Concept Configurator as follows:
1.Open an existing or create a new project.
2.Select the Configurator from the project pulldown menu.
3.Select Configure then select the I/O map menu.
4.On the I/O map menu, press the EDIT button for the appropriate drop.
5.Push the button in the module select column for the appropriate slot.
6.Select the desired module from the list of available modules.
7.Enter the starting 3x register address (InRef). Nine registers are automatically allocated.
8.Enter the starting 4x register address (OutRef). One register is allocated.
9.Press the parameters button.
10. Verify register values are correct for the desired behavior.
The register data formats are discussed in the following section.
12
Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
4xConfiguration Word
3x + 0Data Input Word 1
3x + 1Data Input Word 2
3x + 2Data Input Word 3
3x + 3Data Input Word 4
3x + 4Data Input Word 5
3x + 5Data Input Word 6
3x + 6Data Input Word 7
3x + 7Data Input Word 8
3x + 8Status Word
The AxI 05x 00sc multiplexes 32 channels of data into four groups of
eight channels. Each group can be selected through the 4x Configuration
Word or can automatically sequence through all four groups of channels.
Group 1Chn 1-8
3x + 0Data Input Word 1
3x + 1Data Input Word 2Group 2Chn 9-16
3x + 2Data Input Word 3
3x + 3Data Input Word 4Group 3Chn 17-24
3x + 4Data Input Word 5
3x + 5Data Input Word 6Group 4Chn 25-32
3x + 6Data Input Word 7
3x + 7Data Input Word 8
13
Loading...
+ 39 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.