Spectrum Controls 140 ACI 051 00sc User Manual

0300168-02 Rev. D
32-Channel Analog Input Module
(Cat. No. Quantum Automation Series 140 AxI 05x 00sc)
Installation Instructions
Input Module Catalog Numbers:
140 ACI 050 00sc Current Only 140 AVI 050 00sc Voltage Only 140 ACI 051 00sc Selectable Current or Voltage
PREFACE
+ Note: Power, input and output (I/O) wiring must be in accordance with Class 1, Division 2 wiring methods [Article 501-4 (b) of the National Electrical Code, NFPA 70] and in accordance with the authority having jurisdiction.”
+ Note: Peripheral equipment must be suitable for the location in which it is used.
WARNING
ELECTROSTATICALLY SENSITIVE COMPONENTS
EXPLOSION HAZARD
Substitution of components may impair suitability for Class I, Division 2.
WARNING
EXPLOSION HAZARD
Do not disconnect equipment unless power has been switched off or the area is known to be non hazardous.
WARNING
This equipment is suitable for use in Class I, Division 2, Groups A, B, C, and D or non-hazardous locations only.
i
WARNING
EXPLOSION HAZARD
When in hazardous locations, turn off power before replacing or wiring modules.
ii
Table Of Contents
CHAPTER 1: OVERVIEW ..................................................................................... 1
1.1 Inputs ............................................................................................................. 2
32-Channel Analog Input Module Quantum Series 140 AxI 05x 00sc
1.2 LEDs ................................................................................................. 3
1.3 Related Publications........................................................................... 4
CHAPTER 2: MODULE SETUP FOR MODSOFT ............................. 5
2.1 General Information ........................................................................... 5
2.2 Installation of new run time files ........................................................ 6
2.3 General information on data register usage and terminology ............. 6
2.4 Zoom Screen Configuration ............................................................... 7
CHAPTER 3: MODULE SETUP FOR CONCEPT ............................ 11
3.1 General Information .......................................................................... 11
3.2 Installation of new run time files ....................................................... 12
3.3 General Information on data register usage and terminology ........... 12
3.4 Concept I/O Map Module Parameters ............................................. 14
3.5 Spectrum I/O Configuration Utility ................................................... 20
3.6 SCIOCGF.EXE Installation: .............................................................. 21
CHAPTER 4: MODULE CONFIGURATION AND STATUS .......... 23
4.1 Configuration word format (Register 4x) ........................................ 23
4.2 Module status information (Register 3x+8) ..................................... 25
CHAPTER 5: INSTALLATION .......................................................... 31
5.1 Field Wiring ...................................................................................... 33
5.2 Single Ended Field Wiring Example ................................................. 34
5.3 Differential Field Wiring................................................................... 35
5.4 Differential Field Wiring Example .................................................... 36
CHAPTER 6: APPLICATION NOTES .............................................. 37
6.1 General Application Tips .................................................................. 37
6.2 Demultiplexing Channel Data - Autosequence Mode ..................... 38
6.3 Using ladder to move data to a block of 32 consecutive reg ........... 38
6.4 Channel Update Rate ...................................................................... 40
iii
6.5 System Resolution and Accuracy .................................................... 41
6.6 Range and Data Format Selection ................................................... 42
CHAPTER 7: TROUBLESHOOTING ................................................ 43
7.1 General information ......................................................................... 43
CHAPTER 8: SPECIFICATIONS ....................................................... 47
iv
Chapter 1
OVERVIEW
Throughout this installation and operation guide, unless reference is being made to one specific version of the module, the designation 140 AxI 05x 00sc will be used for generic reference purposes. The 140 AxI 05x 00sc consists of a series of four analog input modules, each with 32 channels of input. The differentiation between the four different modules is shown in the table below.
140 ACI 050 00sc current only
140 AVI 050 00sc voltage only 140 ACI 051 00sc current or voltage combination *140 ACI 052 00sc current or voltage combination with time and date stamping * The 140 ACI 052 00sc Time Stamp option is covered in a separate manual.
Each module will accept 32 single ended analog inputs. The inputs are divided into four groups of eight inputs each. Each group has 15V isolation to the other groups. Analog inputs within a group has 0V of isolation channel-to-channel. All inputs have 500V ac isolation channel­to-backplane.
These modules have been designed for projects that include large quanti­ties of analog inputs. Process control and data acquisition applications for industries such as utilities, waste water, oil and gas, food and beverage, and building automation are ideally suited for this module. The time and date stamp version of the module is perfect for remote terminal unit (RTU) applications or for supervisory control and data acquisition (SCADA) applications requiring programmable alarm levels.
Input channels include over voltage circuit protection, over and under range detection and active notch filtering. The voltage mode of the module handles four different voltage ranges and the current mode handles two current ranges. You can configure the module to provide data in one of four data formats. Set up of the module is very simple through the use of configuration and status registers using Concept, Modsoft or Taylor programming software.
1
1.1 Inputs
The module can be purchased as current only, voltage only, current or voltage combination, or as a current or voltage combination with a time stamp option. The 32 channels are separated into four groups of eight. Each group can be configured for a different voltage or current range. The ranges available are as follows:
Current Ranges
• 4-20 mA, 0-20 mA
Voltage Ranges:
• ±10VDC, 0-10VDC, 0-5VDC, 1-5VD
The module can provide data to the PLC in the following formats:
• 12 bit (0 to 4095)
• signed 15 bit (-32768 to +32767)
• unsigned 16 bit (0 to 65535)
• DVM (0 to 10000)
• Input Filter Options (10Hz, 50Hz, 60Hz, 1kHz)
2
1.2 LEDs
The module has a front LED panel that includes 35 LEDs:
Ready LED -
1 Green LED indicates module’s self test has passed and is ready to communicate.
Active LED -
1 Green LED indicates BUS communication is established between the module and the rack.
Fault LED -
1 Red LED indicates a module self test error, or fatal H/W error. A blink code will indicate the type of self test error. Count the number of blinks before a pause to determine the error code in the table below.
Fault LED Blink Code
Blink # Fault
3 DPM Test Error
4 CPU Error
5 Watchdog Timer Error
6 RAM Error
7 Flash EPROM CRC Error
8 Calibration EEPROM Error
Channel LED -
32 Green LEDs indicates the channel is enabled and a valid input signal level is present. The LED is off if the channel is disabled. A blinking LED indicates that the channel has exceeded a range limit.
3
1.3 Related Publications
Modicon Modsoft Programmer User Manual. 890 USE 115 00
Modicon TSX Quantum Automation Series Hardware Reference
Guide. 840 USE 100 00
IEEE Std 518- 1977, Guide for the Installation of Electrical Noise
Inputs to Controllers from External Sources
IEEE Std 142- 1982, Recommended Practice for Grounding of
Industrial and Commercial Power Systems
Noise Reduction Techniques in Electronic Systems, by Henry W.
Ott; published by Wiley-Interscience of New York in 1976
4
Chapter 2
MODULE SETUP FOR MODSOFT
2.1 General Information
Six steps must be performed in order to fully configure the Quantum system in preparation for using the AxI 05x 00sc:
Step 1: Modsoft programming software must be updated so that the
140 AxI 05x 00sc is recognized in the software (see Section 2.2).
Step 2: Select the appropriate slot location using the Modsoft I/O map.
Choose the first 3x and 4x level registers to be used in the system for the module’s data, configuration and status informa­tion (see Section 2.3).
Step 3: Zoom screens for the module must be set to match application
requirements (see Section 2.4).
Step 4: The 4x configuration register must be set to meet application
requirements (see Section 4.1).
Step 5: Module status information is available to you. The various
options must be understood and chosen to meet your application requirements (see Section 4.2 and Section 4.3).
Step 6: Ladder rungs must be written to demultiplex the incoming 8 data
registers to 32 user selected data registers (see Section 6.3).
5
2.2 Installation of new run time files
If you are using the Modsoft programming software version 2.4 or 2.5, it is necessary to update the following runtime files in order for Modsoft to recognize your module. Versions prior to 2.4 are not supported. Version
2.6 and newer already include these updates.
LMSFDT.SYS Zoom screens GCNFTCOP.SYS I/O Map module definitions
QUANTUM.SYS Quantum help screens
This may be accomplished by first identifying the pathname where you have installed your Modsoft programming software and the drive letter of the floppy drive from which you intend to install. A typical pathname assuming installation of the C: drive is as follows:
C:\MODSOFT
The new runtime files required to use all versions of this module are supplied on the 3.5 inch MSDOS formatted floppy disk titled:
“Quantum Runtime Files,” Spectrum Controls, Inc Part Number: 20500121-xx
To install these files, operate your PC in MSDOS mode, perform the following command:
C:>\COPY A:*.SYS C:\MODSOFT\RUNTIME
+ Note: This assumes you are installing from drive A: and that you have previously installed
Modsoft in the directory C:\MODSOFT . If not, you must make the appropriate substitutions.
2.3 General information on data register usage and terminology:
A total of nine 3x level and one 4x level registers are used by the 140 AxI 05x 00sc. After you have completed the runtime file installation, you can go to the I/O Map screen and choose the 140 AxI 05x 00sc by selecting the desired slot, pressing <Shift + ?> which will display the modules available for configuration into that slot. For module specific help, press <ALT + H>. After selecting the module, you must set the first 3x and 4x level registers to be used. This will then automatically capture nine consecutive 3x level and one 4x level register for use by the module. The architecture for this 32-channel module is as follows:
6
4x Configuration Word 3x + 0 Data Input Word 1 3x + 1 Data Input Word 2 3x + 2 Data Input Word 3 3x + 3 Data Input Word 4 3x + 4 Data Input Word 5 3x + 5 Data Input Word 6 3x + 6 Data Input Word 7 3x + 7 Data Input Word 8 3x + 8 Status Word
The AxI 05x 00sc multiplexes 32 channels of data into four groups of eight channels. Each group can be selected through the 4x Configuration Word or can automatically sequence through all four groups of channels.
Group 1 Chn 1-8 3x + 0 Data Input Word 1 3x + 1 Data Input Word 2 Group 2 Chn 9-16 3x + 2 Data Input Word 3 3x + 3 Data Input Word 4 Group 3 Chn 17-24 3x + 4 Data Input Word 5 3x + 5 Data Input Word 6 Group 4 Chn 25-32 3x + 6 Data Input Word 7 3x + 7 Data Input Word 8
2.4 Zoom Screen Configuration
For Zoom Screen operation, please refer to Modicon’s Modsoft Program­mer User Manual.
Note: T o enter zoom screens from the I/O map menu, highlight the module entry and press the
keys <ALT - Z>.
Most of the module setup will be done through the Modsoft zoom screens. The zoom screen setup establishes the following parameters:
• Calibration rate
• Filter Frequency Selection
• Input Data Format
• Input Range
7
• Differential Mode
The primary zoom screen for this module is shown in Figure 2.1. By selecting a particular parameter, you will be given the options associated with that parameter. Note that the calibration rate is set only once for the entire module, and all other selections are set once for each group of eight inputs.
Hex Dec Bin Goto Quit
F1 F2 F3 F I/O Map Module Editor F7 Lev 8 F8 OFF F9
Head-Slot: 0 Drop: 1 Slot: 4 Spectrum Controls, Inc
Calibration Rate .............................: Once only P.O. Box 5533
Channels 1 - 8: Filter.....................: 10Hz Bellevue, WA 98006
Channels 9 - 16: Filter .....................: 60Hz
Channels 17 - 24: Filter .....................:50Hz
Channels 25 - 32: Filter .....................: 10Hz
140 ACI 050 00SC 32 CHANNEL ANALOG CURRENT INPUT Screen 1/1
Format..................: 16-Bit Format (425) 746-9481
Range ...................: 0 to 20ma
Differential Mode : Disabled
Format..................: 0 to 20ma
Differential Mode : Disabled
Format..................:16-Bit Format
Range ...................: 0 to 20ma
Differential Mode : Disabled
Format..................: 16-Bit Format
Range ...................: 0 to 20ma
Differential Mode : Disabled
End of 140 ACI 050 00SC Zoom
Figure 2.1
Calibration rate: The Quantum module performs an on board system calibration at power up. The system calibration corrects for temperature drift of the Analog to Digital Convertor (ADC) and related circuitry. System calibration can be performed periodically based on the calibration rate selected below. This can affect the update time for the module. For installations where the ambient temperature surrounding the I/O rack can change relatively quickly, the user might consider going to a more frequent calibration selection in order to improve the accuracy of the reading being taken. The autocalibration schedule rate may be selected from the following:
Once at power up only Every 1 min Every 10 min [default] Every 30 min
8
Selecting an autocalibration schedule rate is an exercise in tradeoffs. Performing autocalibration more frequently may result in greater accu­racy due to variations caused by environmental factors such as tempera­ture. This accuracy has a cost in the burden imposed by performing the calibration. The calibration time is a function of the filter frequency. Calibration times are listed below. The system cannot update the channel data while performing calibration. In addition, if multiple filter frequencies are selected, calibrations for each frequency and the execution time is cumulative. The worst case calibration time is when all filter frequencies are enabled (10, 50, 60 and 1000 Hz). The time is then the total for all four times listed below. Also, note that the channel enables have no effect on the auto calibration feature. If a filter frequency is enabled via the zoom screens, then the autocalibration is performed for the frequency.
10 Hz1,420 msec 50 Hz 397 msec 60 Hz260 msec 1000 Hz45 msec
Filter Frequency Selection: The Analog-to-Digital Conversion
performs a filter function on the input signal. One of the follow­ing filter frequencies may be selected for each of the four groups of eight channels:
Filter: 10 Hz
50 Hz 60 H z [default]
1000 Hz
Input data format: One of the following data formats may be
selected for each of the four groups of eight channels:
Format: 16-bit Format
Voltmeter [default] 12-bit Format 15-bit plus sign Format
Note: The module’s format selection must be compatible with the register format selected
in Modsoft.
9
Input Range: Depending on the module that you have purchased,
one of the following input ranges may be selected for each of the four groups of eight channels:
Range: -10 to +10 V [default V oltage or V/I Modules]
1 to +5V 0 to +5V 0 to +10V 4 to 20mA [default Current Modules] 0 to 20mA
Differential mode: One of the following acquisition modes may
be selected for each of the four groups of eight channels. Differ­ential mode calculates the difference between two consecutive channel inputs and provides the data to the register assigned for the first channel in the pair. When differential mode is enabled, the second channel’s output will be zero. The data acquisition between the two channels is not synchronized so common mode noise on the signal pair may not be fully removed, however DC offsets should be compensated for correctly.
10
Note: The channel pairs are not being updated simultaneously , this could lead to an
error in the actual differential value that is calculated. See figure 2.1 Differential Mode: Disabled [default]
Enabled
Chapter 3
MODULE SETUP FOR CONCEPT
3.1 General Information
Six steps must be performed in order to fully configure the Quantum system in preparation for using the AxI 05x 00sc:
Step 1: Concept programming software (Version 2.1 or newer) must be
updated so that the 140 AxI 05x 00sc is recognized in the soft­ware (see Section 3.2).
Step 2: Select the appropriate slot location using the Concept I/O map
editor. Choose the first 3x and 4x level registers to be used in the system for the module’s data, configuration and status informa­tion (see Section 3.3).
Step 3: Parameters for the module must be set to match application
requirements (see Section 3.4).
Step 4: The 4x configuration register must be set to meet application
requirements (see Section 4.1).
Step 5: Module status information is available to you. The various
options must be understood and chosen to meet your application requirements (see Section 4.2 and Section 4.3).
Step 6: Ladder rungs must be written to demultiplex the incoming 8 data
registers to 32 user selected data registers (see Section 6.3).
11
3.2 Installation of new run time files
The 140 AxI 05x 00sc is manufactured by Spectrum Controls, Inc. Follow the Concept installation procedure for outsourced modules. This requires the install disk provided with your module, which includes the following files (assuming drive A:):
A:\CONCEPT\SPECTRUM.MDC - SpectrumI/O for Quantum Module Definition file. A:\CONCEPT\SPECTRUM.HLP - Spectrum I/O for Quantum Help file.
To update the Concept database with a new Spectrum I/O module:
1. Insert the install disk into drive A:
2. Start the Concept Modconnect Tool (Modconf.exe).
3. Open the installation file “SPECTRUM.MDC”
4. Select the module to add or press the “Add All” button
5. Save the changes before exiting the Modconnect tool.
This will update the Concept database permanently unless you later undo the changes using the Modconnect Tool, or perform a new Concept software install.
3.3 General information on data register usage and terminology:
A total of nine 3x level and one 4x level registers are used by the 140 AxI 05x 00sc. After you have completed adding the modules to the Concept database using the Modconnect tool, you can add a module to a drop by using the Concept Configurator as follows:
1. Open an existing or create a new project.
2. Select the Configurator from the project pulldown menu.
3. Select Configure then select the I/O map menu.
4. On the I/O map menu, press the EDIT button for the appropriate drop.
5. Push the button in the module select column for the appropriate slot.
6. Select the desired module from the list of available modules.
7. Enter the starting 3x register address (InRef). Nine registers are automati­cally allocated.
8. Enter the starting 4x register address (OutRef). One register is allocated.
9. Press the parameters button.
10. Verify register values are correct for the desired behavior.
The register data formats are discussed in the following section.
12
4x Configuration Word 3x + 0 Data Input Word 1 3x + 1 Data Input Word 2 3x + 2 Data Input Word 3 3x + 3 Data Input Word 4 3x + 4 Data Input Word 5 3x + 5 Data Input Word 6 3x + 6 Data Input Word 7 3x + 7 Data Input Word 8 3x + 8 Status Word
The AxI 05x 00sc multiplexes 32 channels of data into four groups of eight channels. Each group can be selected through the 4x Configuration Word or can automatically sequence through all four groups of channels.
Group 1 Chn 1-8 3x + 0 Data Input Word 1 3x + 1 Data Input Word 2 Group 2 Chn 9-16 3x + 2 Data Input Word 3 3x + 3 Data Input Word 4 Group 3 Chn 17-24 3x + 4 Data Input Word 5 3x + 5 Data Input Word 6 Group 4 Chn 25-32 3x + 6 Data Input Word 7 3x + 7 Data Input Word 8
13
3.4 Concept I/O Map Module Parameters:
Concept programming software does not implement zoom screens for ModConnect partner modules and allows only direct editing of the I/O configuration parameters using 16 bit hex values.
From the Concept main screen, highlight the “configure” pull-down menu and choose “I/O Map.” In the I/O Map screen insert the number for the correct “drop” and choose “edit.” Select the Spectrum Controls catalog number that you wish to use from the list presented. When the screen appears, representing the Spectrum module you have selected, highlight the parameters button. You must insert Hex values for registers #1, 2 and 3 to fully configure the module. The format that will instruct you on how to create the I/O map parameters is listed below. For each of the parameters listed we have provided a detailed explanation in Chapter 2. Please refer to detailed functional descriptions in the MODSOFT zoom screen discussions (Section 2.4). You must go through each of the options below to establish the correct pattern for each of these three registers. Once you have the bit pattern, then you can convert each to a four-digit Hex value that is used in the parameters screen.
14
Selecting Input Ranges: Register 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
NU NU Input Range Group 1
Default=0x2000 (0x2924 for 140 ACI 050sc)
Input Range Group 2
Input Range Group 3
Input Range Group 4
Range Selection Bit Pattern:
Range for Group 1 Range for Group 2
Bit 14 Bit 15 Bit 16 Description Bit 11 Bit 12 Bit 13 Description
*0 0 0 -10V to +10V *0 0 0 -10V to +10V
0 0 1 +1V to +5V 0 0 1 +1V to +5V 0 1 0 0V to +5V 0 1 0 0V to +5V 0 1 1 0V to +10V 0 1 1 0V to +10V
*1 0 0 0 to 20mA *1 0 0 0 to 20mA
1 0 1 4 to 20mA 1 0 1 4 to 20mA 1 1 0 Not valid 1 1 0 Not valid 1 1 1 Not valid 1 1 1 Not valid
Range for Group 3 Range for Group 4
Bit 8 Bit 9 Bit 10 Description Bit 5 Bit 6 Bit 7 Description
*0 0 0 -10V to +10V * 0 0 0 -10V to +10V
0 0 1 +1V to +5V 0 0 1 +1V to +5V 0 1 0 0V to +5V 0 1 0 0V to +5V 0 1 1 0V to +10V 0 1 1 0V to +10V
*1 0 0 0 to 20mA *1 0 0 0 to 20mA
1 0 1 4 to 20mA 1 0 1 4 to 20mA 1 1 0 Not valid 1 1 0 Not valid 1 1 1 Not valid 1 1 1 Not valid
* The default range is 0 to 20 mA for the 140 ACI 050sc current only module. Otherwise it is
-10V to +10V
15
Selecting Filter Frequencies: Register 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
NU NU Filter Frequency Group 1
Default=0x2000 (0x2924 for 140 ACI 050sc)
Selecting Filter Frequencies: Register 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x2A92
NU NU NU NU Filter Frequency Group 2
Filter Frequency Group 3
Filter Frequency Group 4
Range Selection Bit Pattern:
Filter for Group 1 Filter for Group 2 Reg 1 Bit 3 Bit 4 Description Reg 2 Bit 15 Bit 16 Description
0 0 10 Hz 0 0 10 Hz 0 1 50 Hz 0 1 50 Hz
*1 0 60 Hz *1 0 60 Hz
1 1 1000 Hz 1 1 1000 Hz
Filter for Group 3 Filter for Group 4
Reg 2 Bit 12 Bit 13 Description Reg 2 Bit 9 Bit 10 Description
0 0 10 Hz 0 0 10 Hz 0 1 50 Hz 0 1 50 Hz
*1 0 60 Hz *1 0 60 Hz
1 1 1000 Hz 1 1 1000 Hz
* The default filter frequency is 60 Hz.
16
Selecting Data Format: Register 2
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x2A92
NU NU NU NU
Selecting Data Format: Register 3
Data Format Group 1
Data Format Group 2
Data Format Group 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Range Selection Bit Pattern:
Data for Group 1 Range for Group 2
Reg 2 Bit 6 Bit 7 Description Reg 2 Bit 4 Bit 5 Description
0 0 16 Bit 0 0 16 Bit
*0 1 DVM *0 1 DVM
1 0 12 Bit 1 0 12 Bit 1 1 15 Bit 1 1 15 Bit
Range for Group 3 Range for Group 4 Reg 2 Bit 2 Bit 3 Description Reg 3 Bit 15 Bit 16 Description
0 0 16 Bit 0 0 16 Bit
*0 1 DVM *0 1 DVM
1 0 12 Bit 1 0 12 Bit 1 1 15 Bit 1 1 15 Bit
* The default data format is 10,000 DVM.
Default=0x0205
Data Format Group 4
17
Selecting Channel Acquisition Mode: Register 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x0205
NU NU NU NU NU NU NU NU
Acquisition Mode Bit Pattern:
Mode for Group 1 Mode for Group 2 Reg 3 Bit 12 Description Reg3 Bit 11 Description
*0 Single Ended *0 Single Ended
1 Differential Pairs 1 Differential Pairs
Mode for Group 3 Mode for Group 4 Reg 3 Bit 10 Description Reg3 Bit 9 Description
*0 Single Ended *0 Single Ended
1 Differential Pairs 1 Differential Pairs
Acquisition Mode Group 1
Acquisition Mode Group 2
Acquisition Mode Group 3
Acquisition Mode Group 4
* The default channel acquisition mode is single ended inputs.
18
Selecting the Calibration Rate: Register 3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 Default=0x0205
NU NU NU NU NU NU NU NU
Calibration Rate
Calibration Rate:
Bit 7 Bit 8 Description:
0 0 Once at power up only . 0 1 Once every 60 seconds.
*1 0 Once every 10 minutes.
1 1 Once every 30 minutes.
* The default calibrate rate is once every 10 minutes.
Once you have established the correct bit pattern for each of these three registers, you can convert each to a four digit Hex value that is used in the parameters screen. A Hex conversion table follows:
0000=0 0001=1 0010=2 0011=3 0100=4 0101=5 0110=6 0111=7 1000=8 1001=9 1010=A 1011=B 1100=C 1101=D 1110=E 1111=F
19
3.5 Spectrum I/O Configuration Utility
“SCIOCFG.EXE” is a utility provided on the install disk under the typical pathname “A:\CONCEPT\SCIOCFG.EXE”. “SCIOCFG.EXE” is intended to help users configure Spectrum I/O when using Concept. This tool is intended to make the configuration of I/O modules supplied by Spectrum Controls easy to accomplish when using Concept.
Version 2.1 of the Concept programming software introduced the tool for importing ModConnect module definition files into the Concept database. This allows Concept users to configure ModConnect I/O such as the 140 AxI 05x 00sc. However, Concept V2.1 does not provide a means for ModConnect I/O developers to design their own I/O configuration menus. Instead, Concept provides a generic interface where the user must enter configuration parameters in hexadecimal values. The Spectrum I/O modules are designed to be feature rich with an efficient use of registers. This requires the user to be intimately aware of the initialization param­eters structure in order to perform simple I/O configuration changes. Simply stated, users can calculate the correct hexadecimal values for the configuration parameters but it is a tedious task, SCIOCFG is designed to relieve the user of this burden.
SCIOCFG presents the user with user friendly selection lists using standard Windows interfaces. SCIOCFG also automatically constrains all parameters to legal values during the data entry process.
SCIOCFG may be run in one of two modes, stand alone mode, or syn­chronous mode. In the stand alone mode, the user configures the data for a given module as desired. SCIOCFG then presents the parameters in hexadecimal values so the user may then manually transfer this data to Concept at a later time.
In the synchronous mode, SCIOCFG runs in the background waiting for the user to select the generic I/O parameters configuration menu for any one of the modules supported. When this occurs, SCIOCFG reads the data from the Concept generic I/O parameter configuration menu, and activates the appropriate I/O parameter configuration menu. When the user clicks on the SCIOCFG OK button, the new data is sent back to Concept.
20
3.6 SCIOCFG.EXE Installation:
SCIOCFG.EXE is a 32-bit Windows program requiring Windows 95 or newer. Installation of SCIOCFG.EXE is simple. Copy the SCIOCFG.EXE file from the installation disk to the desired directory. Then you may add a shortcut to the windows desktop or add the program to the windows taskbar using standard windows techniques.
e.g. From a DOS window:
C:\>MD C:\SCIOCFG C:\> COPY A:\CONCEPT\SCIOCFG.EXE C:\SCIOCFG
To add a shortcut:
1. Place the mouse cursor on an open area of the windows desktop.
2. Click the right mouse button.
3. Select the “New” option.
4. Select the “Shortcut” option.
5. Enter the full install pathname. E.G. C:\SCIOCFG\SCIOCFG.EXE
+
Note: The user may optionally configure SCIOCFG to always run in either the stand alone
mode or the synchronous mode. To do this, place a space in one of the following strings immediately after the full pathname:
NO_SYNC SYNC_WITH_CONCEPT
E.G. C:\SCIOCFG\SCIOCFG.EXE SYNC_WITH_CONCEPT
6. Name as desired.
7. Activate the “Finish” button.
To add to Windows Programs Selections or a Folder:
1. Click and hold the left mouse button on the taskbar start button.
2. Select “Settings, “Taskbar” and release the mouse button.
3. Select the “Start Menu Programs” tab index.
4. Press the Add button.
5. Choose an existing folder (perhaps the Concept programming folder) or create a new folder to hold SCIOCFG.EXE.
6. Add SCIOCFG.EXE as described for adding shortcuts step 5.
SCIOCFG EXE is ready to run.
21
The SCIOCFG.EXE should be running as a background task, whenever Concept software is being used to change the configuration registers of the 140 AxI 05x 00sc series of modules. Start SCIOCFG.EXE by double clicking on the SCIOCFG.EXE icon, then start Concept software.
22
Chapter 4
MODULE CONFIGURATION AND STATUS
The 140 AxI 05x 00sc uses a total of nine 3x level and one 4x level registers. After Modsoft (Section 2.3) or Concept (Section 3.3) soft­ware is installed, additional configuration and status registers are set as follows:
4.1 Configuration word format (Register 4x)
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Select a group
Mode Select
Autosequence Disable
Reserved
Disable channel 1-4
Disable channel 5-8
Disable channel 9-12
Disable channel 13-16
Disable channel 17-20
Disable channel 21-24
Disable channel 25-28
Disable channel 29-32
4x Group Channel Disable: Bits 1-8
These bits are used to fine tune the response time of your system. They enable data acquisition on eight groups of four channels each. A “0” enables the group, a “1” disables the group. Disabling groups of chan­nels improves system response time.
23
Bit 8: Channels 1-4 Bit 7: Channels 5-8 Bit 6: Channels 9-12 Bit 5: Channels 13-16 Bit 4: Channels 17-20 Bit 3: Channels 21-24 Bit 2: Channels 25-28 Bit 1: Channels 29-32
4x Reserved: Bit 9
Bit 9 is reserved. Bit 9 should be set to a “0.”
4x Autosequence Disable: Bit 10
Auto sequence allows the module to automatically sequence through the eight groups of a data presented in the 4x registers. When acquiring data it is necessary to identify which group sequence is currently loaded. This is done by referencing the group number which may be found in the status word group ID (3x+9 Bits 15-16)
When the Autosequence Disable bit is set (Bit 10=1), the module reads only the eight channels identified by the Group Select Bits. If Autosequence Disable is disabled (Bit 10=0), Autosequence mode will be in effect. When in autosequence mode, the module ignores the channel group select in the 4x+0 configuration word, and instead sequences through all four groups automatically. The values in the eight data registers belong to the group identified in the status word group ID (3x+9 bits 15 and 16). The user must set aside 32 registers as a permanent image of the channel data. During run time, the ladder need only deter­mine the current group for the eight data registers (3x+0 through 3x+7) in order to determine where the data should be copied into the 32 register channel image.
When autosequence is disabled, the user must manually increment the group select in the configuration word and the module sends back only the data requested.
Sample ladder logic for both techniques is provided in section 6.3.
24
4x Data Input Mode: Bits 11, 12
The module continuously outputs a group of eight registers worth of data. The data for a given group can be paged between three modes. These are the standard channel input data, channel status data or Time stamp data.
Page Bit 11 Bit 12 Input Modes
0 0 0 Data 1 0 1 Status 2 1 0 Time Stamp
4x Group Select: Bits 13, 14, 15, 16
These four bits are used to select a desired group of channels when the Auto Sequence mode is not used. The group selection is used when autosequnce is disabled to allow ladder to control which group of the module’s input data, status data, and time stamp data (see Time Stamp manual publication #0300169) is being read from the module. The channel Status Mode disables the normal data input mode and reports the status on the selected group of eight channels. The channel status bits echo back the selected input range data format and error status. See description under “Status Mode operation.”
Bit 13 Bit 14 Bit 15 Bit 16 Group
0 0 0 0 Channels 1-8 0 0 0 1 Channels 9-16 0 0 1 0 Channels 17-24 0 0 1 1 Channels 25-32
25
4.2 Module status information (Register 3x+8)
The information provided in this register is generic information about the module. Bits 1-8 and 10 provide error status information. Bits 11-16 echos information present in the current inputs registers.
1 2 3 4 5 6 7 8 910 11121314 1516
Group Select
Data Input Mode Selected
Configuration Error
Reserve
Out of range Channel 1-4
Out of range Channel 5-8
Out of range Channel 9-12
Out of range Channel 13-16
Out of range Channel 17-20
Out of range Channel 21-24
Out of range Channel 25-28
Out of range Channel 29-32
3x+8 Out of Range Error: Bits 1-8
These eight bits indicate that an over or under range condition exists on at least one channel within the group. Bits 1-8 correspond to eight groups of four channels each. When an Out of Range Flag is set, the Channel Status mode (see Section 4.3) can be enabled to report which channel is out of range.
+ Note: An over range error indicates that a channel input is a value greater than or equal to the
maximum for the range selected for that channel group. An under range error indicates that a channel input is a value less than or equal to the minimum for the selected range.
3x+8 Reserved: Bit 9
Bit 9 should always respond with a “0.”
26
3x+8 Configuration Error: Bit 10
An illegal configuration was attempted. When this occurs configuration will not be accepted by the module and this flag will be set. By using 4x register bits 1 and 2 to set the module to “status” individual channels flags can be checked to determine which channel or group is incorrect.
3x+8 Data Input Mode: Bits 11, 12
The module continuously outputs a group of eight registers worth of data. The data for a given group can be paged between three modes. These are the standard channel input data, channel status data or Time stamp data.
Page Bit 11 Bit 12 Input Modes
0 0 0 Data 1 0 1 Status 2 1 0 Time Stamp
3x+8 Group Select: Bits 13-16
These four bits echo the selected channel group.
Bit 13 Bit 14 Bit 15 Bit 16 Group
0 0 0 0 Channels 1-8 0 0 0 1 Channels 9-16 0 0 1 0 Channels 17-24 0 0 1 1 Channels 25-32
27
4.3 Channel Status (Registers 3x+ 0 through 3x+7)
As described in Section 2.5, register 4x bits 1and 2 can be set to allow monitoring of individual channel status (set to “0” and “1” respectively). You will then be displaying eight channels of status information. As described below, bits 1-4 provide four different pieces of error informa­tion specific to that input channel. Bits 5-11 merely confirm what setup has been created for that feature in configuration register 4x. Bits 12-16 will indicate what channel’s status is being displayed.
Channel Status Register:
1 2 3 4 5 6 7 8 9 10 11121314 1516
Channel Number
Filter Selection
Input Data Format
Range Selected
Under range
Over range
Configuration error
Calibration error
3x+0 . . . 7 Calibration Error Flag: Bit 1
The calibration error flag is a fatal error. When the flag is set to “1” the ADC cannot calibrate within specifications.
3x+0 . . . 7 Configuration Error Flag: Bit 2
The calibration error flag is a fatal error. When the flag is set to “1” there is a configuration mismatch. Configuration errors include any illegal configuration, such the selection of an unsupported format or filter option,
28
or configurations that must be the same for all channels within a group of channels.
3x+0 . . . 7 Over Range Flag: Bit 3
This is a nonfatal over range flag. The bit is set to “1” when an input value is read within one count of the maximum range value. When the input value is within normal limits the flag is automatically reset to “0.”
3x+0 . . . 7 Under Range Flag: Bit 4
This is a nonfatal under range flag. The bit is set to “1” when an input value is read within one count of the minimum range value. When the input value is within normal limits the flag is automatically reset to “0.”
3x+0 . . . 7 Range & Mode Selection: Bit 5-7
These three bits confirm which range and mode selection was set in the zoom screen for each group of eight inputs. See 4x register set-up. Range select works in conjunctions with the mode select.
Range & Mode Selection Bits
Bit 5 Bit 6 Bit 7 Mode Range
0 0 0 Voltage ±10 V 0 0 1 Voltage +1 to +5V 0 1 0 Voltage 0 to +5V 0 1 1 Voltage 0 to +10V 1 0 0 Current 0-20 mA 1 0 1 Current 4-20 mA 1 1 0 Current Not used 1 1 1 Current Not used
3x+0 . . . 7 Input Data Format: Bits 8-9
These two bits indicate the data format selection that was set in the zoom screen. One of three input data formats is selected for each of the four groups.
Input Data Format Selection Bits
Bit 8 Bit 9 Data Format
0 0 16 bit unsigned integer 0 1 10,000 Count DVM 1 0 12 bit unsigned integer 1 1 15 bit signed integer
29
3x+0 . . . 7 Filter Selection: Bits 10-1 1
These two bits indicate the filter frequency selection that was set in the zoom screen. One of four filter selections from 10 Hz, 50 Hz, 60 Hz, 1000 Hz is programmed per group of eight inputs. The filter frequency selection will effect channel update time.
Filter Selection Bits
Bit 10 Bit 11 -3db Filter Frequency
0 0 2.62 Hz 10 Hz Notch Filter 0 1 13.1 Hz 50 Hz Notch Filter 1 0 15.72 Hz 60 Hz Notch Filter 1 1 262 Hz 1000 Hz Notch Filter
3x+0 . . . 7 Channel Number: Bit 12-16
These five bits indicates which of the 32 channels is reporting its status.
Bit 12 Bit 13 Bit 14 Bit 15 Bit 16Channel Bit 12 Bit 13 Bit 14 Bit 15 Bit 16 Channel
000001 10 0 00 17 000012 10 0 01 18 000103 10 0 10 19 000114 10 0 11 20 001005 10 1 00 21 001016 10 1 01 22 001107 10 1 10 23 001118 10 1 11 24 010009 11 0 00 25 0100110 11 0 01 26 0101011 11 0 10 27 0101112 11 0 11 28 0110013 11 1 00 29 0110114 11 1 01 30 0111015 11 1 10 31 0111116 11 1 11 32
30
Chapter 5 INSTALLATION
+ Note: When field wiring the I/O modules, the maximum wire size that should
be used is 1-14 AWG or 2-16 AWG; the minimum size is 20 AWG.
+ Note: The field wiring terminal block (Modicon # 140 XTS 002 00) or the 140
CFA040 00 40 pin Cablefast Terminal block must be ordered sepa­rately. (The terminal block includes the removable door label.)
+ Note: Power, input and output (I/O) wiring must be in accordance with Class
1, Division 2 wiring methods [Article 501-4 (b) of the National Electrical Code, NFPA 70] and in accordance with the authority having jurisdiction.”
+ Note: Peripheral equipment must be suitable for the location in which it is
used.
31
WARNING
ELECTROSTATICALLY SENSITIVE COMPONENTS
EXPLOSION HAZARD
Substitution of components may impair suitability for Class 1, Division 2.
WARNING
EXPLOSION HAZARD
Do not disconnect equipment unless power has been switched off or the area is known to be non hazardous.
32
WARNING
This equipment is suitable for use in Class 1, Division 2, Groups A, B, C, and D or non-hazardous locations only.
WARNING
EXPLOSION HAZARD
When in hazardous locations, turn off power before replacing or wiring modules.
3
4
2
32-Channel Analog Input Module Quantum Series 140 AxI 05x 00sc
Before installing the module, you should:
Configure all of the appropriate zoom screen, configuration and other necessary set up according to Chapters 2 and 3.
Field wire the module’s terminal block for your application.
For field wiring, use shielded, twisted-pair cable (such as Belden 9418 for voltage and current applications), and ground each cable’s shield wire at one end only. At the opposite end of each cable, tape the exposed shield wire to insulate it from electrical contact. A good shield wire ground is a rack assembly mounting bolt or stud.
5.1 Field Wiring
+ Note: In the process of wiring the modules, route all signal wires as far as possible from potential
sources of electrical noise, such as motors, transformers, etc., (especially ac devices). As a general rule, allow 15.2 cm (6 in) of separation for every 120V of power. Signal wires must never share the same conduit with ac wiring. Also, when you must route signal wires past ac wiring, do so at right angles.
Single Ended Field Wiring
2
4
6
8
10
12
14
16
18
20
22
24
26
28
30
32
34
36
38
40
(IN+)1
1
(IN+)3
3
COM GROUP 1
5
(IN+)6
7
(IN+)8
9
(IN+)9
11
(IN+)11
13
15
COM GROUP
(IN+)14
17
(IN+)16
19
(IN+)17
21
(IN+)19
23
COM GROUP
25
(IN+)22
27
(IN+)24
29
(IN+)25
31
(IN+)27
33
35
COM GROUP
(IN+)30
37
(IN+)32
39
(IN+)2
(IN+)4
(IN+)5
(IN+)7
COM GROUP 1
(IN+)10
(IN+)12
(IN+)13
(IN+)15
COM GROUP 2
(IN+)18
(IN+)20
(IN+)21
(IN+)23
(IN+)26
(IN+)28
(IN+)29
(IN+)31
COM GROUP 4
33
5.2 Single Ended Field Wiring Example
21
(IN+)1
43
65 87
10 9
Group 1 common
(IN+) 8
12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29
(IN+) 25
32 31 34 33 36 35 38 37 40 39
Group 4
common
(IN+) 32
Group 4
common
+
-
+
-
+
-
+
-
Voltage Source
Voltage Source
Current Source
Current Source
34
3
4
32-Channel Analog Input Module Quantum Series 140 AxI 05x 00sc
5.3 Differential Field wiring
Differential mode performs a software difference of two consecutive channel inputs, and reports the data on the first channel register of the pair. The second channel’s output is zero. The data acquisition between the two channels is not synchronized so common mode noise on the signal pair may not be fully removed, however DC offsets should be compen­sated for correctly.
+ Note: The channel pairs are not being measured simultaneously , this could lead to an error in the
actual differential value that is calculated.
(IN-)1
2
(IN-)2
(IN+)3
(IN+)4
COM GROUP 1
(IN-)5
(IN-)6
(IN+)7
(IN+)8
COM GROUP 2
(IN+)9
(IN+)10
(IN+)11
(IN+)12
COM GROUP 3
(IN-)13
(IN-)28
(IN+)15
(IN+)16
COM GROUP 4
1
4
3
6
5
8
7
10
9
12
11
14
13
15
16
18
17
20
19
22
21
24
23
26
25
28
27
30
29
32
31
34
33
36
35
38
37
40
39
+ Note: Differential mode only applies to voltage inputs.
(IN+)1
(IN+)2
COM GROUP 1
(IN-)3
(IN-)8
(IN+)5
(IN+)6
COM GROUP 2
(IN-)7
(IN-)8
(IN-)9
(IN-)19
COM GROUP
(IN-)11
(IN-)12
(IN+)13
(IN+)14
COM GROUP
(IN-)15
(IN-)16
35
5.4 Differential Field Wiring Example
(IN-) 1
21 43 65
(IN+) 1
Group 1
common
87 10 9 12 11 14 13 16 15 18 17 20 19 22 21 24 23 26 25 28 27 30 29 32 31 34 33 36 35 38 37 40 39
(IN-) 16
(IN+) 16
Group 4
common
+
-
+
-
Voltage Source
Voltage Source
36
Chapter 6 APPLICATION NOTES
6.1 General Application Tips
Select the appropriate 140 AxI 05X 00sc from the I/O map selection screen.
Configure the module using your programming software, make appropriate use of Configuration and Status registers as outlined in Chapters 2 through 4.
Ensure correct units of measure are selected for data type.
Use the lowest filter frequency setting possible for your applica­tion, this ensures the most stable and accurate readings.
Configure the 4x Register.
Check that the Green Ready LED is lit when the module is powered up and has completed its self test.
Check that the Green Active LED is lit when data is being transferred to the Quantum CPU.
37
6.2 Demultiplexing Channel Data - Autosequence Mode
The autosequence mode of operation is intended to simplify the demultiplexing of channel data from the eight input registers into storage for the 32 channels. The Autosequence Mode is enabled under the following conditions:
• Input Mode = Data Mode (Configuration Word Bits 11 & 12 = 0)
• Autosequence Disable is not active (Configuration Word Bit 10 = 0)
In the autosequence mode, the group select bits in the configuration word are ignored. Instead, the module samples channel data in groups of eight (8), presents the data to the PLC and then scans the next group automati­cally.
Scan
Channels 1-8 3x+0 to 3x+7
38
Module Status 3x+8
Channels 9-16 3x+0 to 3x+7
Module Status 3x+8
Channels 17-24 3x+ 0 to 3x+7
Module Status 3x+8
Channels 25-32 3x+0 to 3x+7
Module Status 3x+8
The module update rate is determined by the number of channels enabled and the filter frequencies selected. For example, if all 32 channels are enabled and the filter frequency for all groups is 60 Hz, then the cycle time for a full set of 32 channels is 32 x 58 msec or 1.856 seconds.
It takes four ladder logic scans of the eight registers to see all 32 chan­nels. These four scans must be completed at least twice as fast as the module update time to ensure no data is missed. In the example above the ladder scan time would need to run at 1.856 sec/8 or 232 msec or faster to ensure no data is missed.
The following ladder logic shows how to move data from the 8 multi­plexed input words to a block of 32 output words starting at location 400101 using the autosequence mode. This example file for use only with Modsoft programming software can be formed on the install disk shipped with your module. The file is under the A:\Programs subdirectory. To install:
1. Insert the install disk into drive A:
2. Copy A:\Programs\QAI32_AC.* C:\Modsoft\Programs
3. Select File QAI32_AC under Modsoft to run. The I/O map is as follows:
Rack Slot Module Input Ref Output Ref Description
1 03 ACI 051 00 3000001-3000009 4000001-4000001 ACI05100 AN IN 32CH
300009 300009 300009 300009 300001 NCBT NCBT NCBT NCBT #00011 #00012 #00015 #00016 400101
300009 300009 300009 300009 300001 NCBT NCBT NCBT NOBT #00011 #00012 #00015 #00016 400109
300009 300009 300009 300009 300001 NCBT NCBT NOBT NCBT #00011 #00012 #00015 #00016 400117
300009 300009 300009 300009 300001 NCBT NCBT NOBT NOBT #00011 #00012 #00015 #00016 400125
BLKM #00008
BLKM #00008
BLKM #00008
BLKM #00008
39
6.3 Demultiplexing Channel Data - Manual Mode
Manual mode allows deterministic data acquisition. You may specify the specific group of data you would like to acquire as opposed to the Autosequence Mode which cycles through data blocks. Manual mode
requires that the Autosequence Mode be disabled; Bit 10 = 1.
The following ladder logic shows how to move data from the 8 multi-
plexed input words to a block of 32 output words starting at location 400101 with the manual mode. This example file for use only with Modsoft programming software can be formed on the install disk shipped with your module. The file is under the A:\Programs subdirectory. To install:
1. Insert the install disk into drive A:
2. Copy A:\Programs\QAI32_GI.* C:\Modsoft\Programs
3. Select File QAI32_GI under Modsoft to run.
The I/O map is as follows: (Manual Mode)
40
Rack Slot Module Input Ref Output Ref Description
1 03 ACI 051 00 3000001-3000009 4000001-4000001 ACI05100 AN IN 32CH
300009 300009 300009 300009 300001 NCBT NCBT NCBT NCBT #00011 #00012 #00015 #00016 400101
300009 300009 300009 300009 300001 NCBT NCBT NCBT NOBT #00011 #00012 #00015 #00016 400109
BLKM #00008
400001 400001 RBIT SBIT #00015 #00016
BLKM #00008
400001 400001 SBIT RBIT #00015 #00016
300009 300009 300009 300009 300001 NCBT NCBT NOBT NCBT #00011 #00012 #00015 #00016 400117
BLKM #00008
400001 400001 SBIT SBIT #00015 #00016
300009 300009 300009 300009 300001 NCBT NCBT NOBT NOBT #00011 #00012 #00015 #00016 400125
BLKM #00008
400001 400001 RBIT RBIT #00015 #00016
41
6.4 Channel Update Rate
The module’s channel update rate is determined by the filter frequency selection. A lower filter frequency takes longer to update each channel. The following table shows the single channel update rate and 32 channel update rate for each filter frequency.
Filter -3db 1 channel 32 channel
Frequency Frequency Update Time Update time
10 Hz 2.62 Hz 308 ms 9.9 sec 50 Hz 13.1 Hz 68 m s 2.2 sec 60 Hz 15.7 Hz 58 m s 1.9 sec 1K Hz 262 Hz 12 ms 384 ms
+ Note: Channel update time is the time required for the module to acquire an input sign and update
the module’s data registers. The scan rate of the Quantum system will vary with application ladder and system configuration.
+ Note: Periodic system calibration will also effect channel update times for one scan cycle.
6.5 System Resolution and Accuracy
The system resolution listed below is the smallest input signal change that the ADC can detect. The resolution level is affected by the filter fre­quency selected.
Filter ADC Voltage Current
Frequency Resolution Resolution Resolution
10 Hz 22.5 Bits 3 µV 3 NA 50 Hz 20 Bits 19 µV 19 NA 60 Hz 20 Bits 19 µV 19 NA 1K Hz 10.5 Bits 14 mV 14 µA
The resolution levels for the voltage mode and current mode apply to the full scale input ranges.
System accuracy is the total error between an actual input signal level and the module output data value. System accuracy is effected by external wiring, signal noise, filter frequency, calibration, temperature, and output data formats. The table below lists that system accuracy verses temperature for a 10hz filter with periodic calibration enabled.
42
T emp Voltage Mode Current Mode
25°C T ypical ±0.03% ± 6 mV ±0.05% ±10µA
60°C Max ±0.05% ±1 0 m V ±0.10% ± 20µA
+ Note: Accuracy calculations are based on the full scale current and voltage input range. These are
0 to 20 mA and ±10V respectively.
6.6 Range and Data Format Selection
Each of the module’s input ranges can be viewed in one of the four data in formats below. The table shows the minimum and maximum values are equal to the under range and over range trip points.
Format: Range: Min: Max:
Signed 15 Bit -10 to +10V -32,767 +32,767 Signed 15 Bit 0 to +10V -32,767 +32,767 Signed 15 Bit +1 to +5V -32,767 +32,767 Signed 15 Bit +0 to +5V -32,767 +32,767 Signed 15 Bit +0 to +20mA -32,767 +32,767 Signed 15 Bit +4 to +20mA -32,767 +32,767
Unsigned 16 Bit -10 to +10V 0 +65,535 Unsigned 16 Bit 0 to +10V 0 +65,535 Unsigned 16 Bit +1 to +5V 0 +65,535 Unsigned 16 Bit +0 to +5V 0 +65,535 Unsigned 16 Bit +0 to +20mA 0 +65,535 Unsigned 16 Bit +4 to +20mA 0 +65,535
Unsigned 12 Bit -10 to +10V 0 +4,095 Unsigned 12 Bit 0 to +10V 0 +4,095 Unsigned 12 Bit +1 to +5V 0 +4,095 Unsigned 12 Bit +0 to +5V 0 +4,095 Unsigned 12 Bit +0 to +20mA 0 +4,095 Unsigned 12 Bit +4 to +20mA 0 +4,095
10,000 Count DVM -10 to +10V -10,000 +10,000 10,000 Count DVM 0 to +10V 0 +10,000 10,000 Count DVM +1 to +5 V +1,000 +5,000 10,000 Count DVM +0 to +5V 0 +5,000 10,000 Count DVM +0 to +20mA 0 +2,000 10,000 Count DVM +4 to +20mA +400 +2,000
43
44
Chapter 7 TROUBLESHOOTING
7.1 General Information
Review of the Module Setup Procedures in Section 2.1 is recommended prior to following the troubleshooting steps below to help isolate the problem. The troubleshooting guide lists a variety of possible problems. Step through each item on the list and verify whether or not the module is working. If a particular step is not working, follow the corrective action listed.
STEP 1: Check module power and self test.
VERIFY: The controller module’s READY and RUN LED’s are on.
CORRECTIVE ACTION:
Insure that the rack’s power supply is connected properly and its
PWR OK LED is on.
Place the controller in run mode by using the Modsoft Start Com-
mand.
If the rack’s power will not come up, or the system will not go into
run mode, refer to the Quantum Automation Series Hardware Reference Guide for more information.
STEP 2: Check module power and self test.
VERIFY: The module’s green READY LED is on. This indicates that the module has power and has completed it functional self test.
CORRECTIVE ACTION:
Check rack power, and reinstall the module in the rack.
43
STEP 3: Check the module’s fault LED.
VERIFY: The module’s red FAULT LED is off. This LED indicates a module hardware error.
CORRECTIVE ACTION:
The module has a fatal hardware error. Contact your local distributor
or Spectrum Controls Customer Satisfaction Group listed at the back of this manual.
The module has a front LED panel that includes 35 LEDs:
Ready LED -
1 Green LED indicates module’s self test has passed and is ready to communicate.
Active LED -
1 Green LED indicates BUS communication is established between the module the rack.
Fault LED -
1 Red LED indicates a module self test error, or fatal H/W error. A blink code will be defined that will indicate the type of self test error. Count the number of blinks before a pause to determine the error code in the table below.
Fault LED Blink Code Blink # Fault
3 DPM T est Error 4 CPU Error 5 Watchdog Timer Error 6 RAM Error 7 Flash EPROM CRC Error 8 Calibration EEPROM Error
Channel LED ­32 Green LEDs indicates the channel is enabled and a valid input signal level is present. The LED is off if the channel is disabled. A blinking LED indicates that the channel has exceeded a range limit.
44
STEP 4: Check the module’s communication status.
VERIFY: The module’s green ACTIVE LED is on. This indicates that the module is communicating properly with the rack.
CORRECTIVE ACTION:
Set the rack into run mode.
Reinstall the module in the rack.
STEP 5: Check the module’s health status.
VERIFY: The module is reported as healthy in the Modsoft I/O map Screen. Check to make sure that the module description, slot location, and register assignments are correct. Also, verify that the module is recog­nized and reported as healthy. If an asterisk is present before the module’s name, then the module is not recognized by the rack.
CORRECTIVE ACTION:
Reinstall the module in the rack.
Reselect the module in the I/O Map using the <Shift + ?> key. If the
module is not listed, install the Modsoft Runtime files included with your module.
STEP 6: Check the module’s register operation.
VERIFY: The 4X configuration word and the 3X+8 Status word are setup properly. As a quick check, disable all ladder programming and set the 4X register to 0000 Hex and verify that the 3X+8 Status register cycles through the values 0000, 0001, 0010, and 0011 Hex.
CORRECTIVE ACTION:
Check steps 1 through 6 above and then call Spectrum Controls
Customer Satisfaction at (425) 746-9481.
45
46
Chapter 8 SPECIFICATIONS
Number of Channels 32 Input Registers Required 9 Output Registers Required 1 Input Configuration 32 inputs configured in groups of 8 channels per common LEDs 35 - One each for Ready (Green), Active (Green), Fault
(Red), 32 Channel (Green) Voltage Range ±10VDC, 0 to 10VDC, 0 to 5VDC, 1 to 5VDC Current Range 4 to 20mA, 0 to 20mA Impedance, input Voltage Mode: 10 Megohms, min.
Current Mode: 350 ohms Fault Detection Over & under range status bits, for all current and voltage modes. CMRR 90 d B Power Requirements 630 mA @ 5 V maximum Max Input Current ±50 mA continuous Max Input Voltage ± 20VDC continuous Agency Approvals UL, CUL Class 1 Div II, CE, FCC Class A Accuracy Note: Accuracy is dependent on the filter frequency
selection, range selection, data format, and input noise. Voltage T yp ±0.03% of full scale typical @ 25°C. Voltage Max ±0.05% of full scale Maximum @ 0 to 60°C. Current Typ ±0.05% of full scale typical @ 25°C Current Max ±0.10% of full scale maximum @ 0 to 60°C
Miscellaneous
Display format 12 bit integer, 16 bit integer, 15 bit signed integer,
10000 count DVM
47
Engineering units mV, mA Resolution 10 bits to 22 bits (frequency dependent) Input Filter 10Hz, 50Hz, 60Hz, 1KHz
Digital Notch Filter, Programmable in groups of 8 inputs.
Channel Update Time See Installation Guide for Channel Update Time chart vs
filter selection Single Channel 12 ms to 308 ms (frequency dependent) 32 Channel 384 ms to 9.9 sec (frequency dependent)
Isolation
Channel to Rack 500 VAC Continuous Optical & magnetic Channel to Channel 0 volts, non-isolated within a group Gro up to Gr ou p ±15V
48
Notice The products and services described in this publication are useful in a wide variety of applications. Therefore, the user and others responsible for applying the products and services described herein are responsible for determining their acceptability for each application. While efforts have been made to provide accurate information within this publication, Spectrum Controls assumes no responsibility for the accuracy, complete­ness, or usefulness of the information contained herein. Under no circumstances will Spectrum Controls be responsible or liable for any damages or losses, including indirect or consequential damages or losses, arising out of either the use of any information contained within this publication or the use of any product or service referenced herein. No patent liability is assumed by Spectrum Controls with respect to the use of any of the information, products, circuits, programming, or services referenced herein. The information contained in this publication is subject to change without notice.
Limited Warranty Spectrum Controls warrants that its products are free from defects in material and workmanship under normal use and service, as described in Spectrum Controls literature covering this product, for a period of 1 year. Spectrum Controls obligations under this warranty are limited to replacing or repairing, at its option, at its factory or facility, any product which shall, in the applicable period after shipment, be returned to the Spectrum Controls facility, transportation charges prepaid, and which after examination is deter­mined, to the satisfaction of Spectrum Controls, to be thus defective. This warranty shall not apply to any such equipment which shall have been repaired or altered except by Spectrum Controls or which shall have been subject to misuse, neglect, or accident. In no case shall Spectrum Controls liability exceed the purchase price. The aforementioned provisions do not extend the original warranty period of any product which has either been repaired or replaced by Spectrum Controls.
Declaration Of Conformity
ModSoft is a registered trademark of Schneider Electric, Inc. Copyright © 2000-2003 Spectrum Controls, Inc. All rights reserved. Specifications subject to change without notice. Printed in U.S.A. Publication 0300168-02 Rev. D May 2003.
Corporate Headquarters Northeastern U.S.A. Sales Office Southeastern U.S.A. Sales Office
Spectrum Controls, Inc. Spectrum Controls, Inc. Spectrum Controls, Inc. P.O. Box 5533 48945 Van Dyke, 4B 5300 Regency Lake Ct Bellevue, WA 98006 USA Utica, MI 48317 USA Sugar Hill, GA 30518 USA
Tel: (425) 746-9481 Tel: (586) 731-2397 Tel: (770) 614-5885
Fax: (425) 641-9473 Fax: (586) 731-2715 Fax: (770) 614-5886
Web Site: http://www.spectrumcontrols.com
Email: spectrum@spectrumcontrols.com
Loading...