Siemens SFPO-11,SFP-11,SFPT-11 Installation Instructions Manual

Installation Instructions Model SFPO-11 / SFP-11 / SFPT-11
FirePrint Photoelectric Detector / FirePrint Detector / FirePrint Thermal Detector
These instructions are written in accordance with the instal­lation guidelines of NFPA 72, National Fire Alarm Code, and CAN/ULC-S524, The Installation of Fire Alarm Systems.
Detector Device Storage
DO NOT install this detection device until all construc­tion is completed.
DO NOT store this detection device where it can be con­taminated by dirt, dust, or humidity.
Although no specific spacings are set for the detectors used for a clean air application, use 30 foot center spacing (900 sq ft) from NFPA Standard 72 and CAN/ULC-S524, if practical, as a guide or starting point for a detector installation layout. This spacing, however, is based on ideal conditions–smooth ceil­ing, no air movement, and no physical obstructions. In some applications, therefore, considerably less area is protected ad­equately by each smoke detector. This is why it is mandatory to closely follow the installation drawings. In all installations place the detector on the ceiling, a minimum of 6 inches from a side wall, or on a wall, 4 to 6 inches from the ceiling.
If you have any questions regarding detector placement, fol­low the drawings provided or approved by Siemens Building Technologies, Inc. or by its authorized distributors. This is ex­tremely important! The detector placements shown on these drawings were chosen after a careful evaluation of the area that is protected. Such factors as air currents, temperature, humidity, pressure, and the nature of the fire load were care­fully considered. Especially noted were the room or area con­figuration and the type of ceiling (sloped or flat, smooth or beamed). Siemens Building Technologies, Inc.’s extensive ex­perience in the design of the system assures the best detec­tor placement by following these drawings. Sound engineer­ing judgment by qualified personnel must be followed.
Figure 1 SFP-11 and SFPT-11
Figure 2 SFPO-11
level of smoke or aerosol for an extended period of time, the detector is programmed to make the “safe decision” and sig­nal an alarm condition. Because the amplitude and duration of deceptive phenomena are unbounded, the rule of thumb is to keep detectors as far as practical from sources that can produce an unusually large quantity of smoke for about a minute. This effort during placement of detectors within a FirePrint Application enhances the ability of FirePrint’s decep­tive phenomena rejection. Avoid close proximity of detectors to smoke sources such as oil burners, electric heaters, kitch­ens, garages, and areas of high relative humidity where
condensation may occur.
Air Currents
Before a detector can sense a fire, the products of combustion or smoke must travel from the fire to the detector. This travel is especially influenced by air currents; therefore, consider air movement when designing the system. While combustion products tend to rise, drafts from hallways, air diffusers, fans, etc., may help or hinder the travel of combustion products to the detector. When positioning a detector at a particular loca­tion, give consideration to windows and doors, both open and closed, to ventilating systems, both in and out of opera­tion, and to other factors influencing air movement. Do not install a detector in the air stream of a room air supply dif­fuser. It is better to position a detector closer to an air return.
The distance that products of combustion or smoke travel from a fire to the detector is not usually the shortest linear route. Combustion products or smoke usually rise to the ceil­ing, then spread out. Average ceiling heights of 8 to 10 feet do not abnormally affect detector response. High ceilings, located in churches, warehouses, auditoriums, etc., do affect detector response and should be considered.
Fire Print Detectors and Nuisance Alarms
The neural network within each Model SFP-11 FirePrint de­tector is optimized to reject the most common nuisance alarms for its selected FirePrint Application; e.g. Parking Ga­rage or Health Care. If the detector is exposed to an excess
P/N 315-033290C-7
Special Ceiling Construction Factors
Ceiling obstructions change the natural movement of air and combustion products. Depending on the direction of smoke travel, joists and beams can slow the movement of heated air and smoke, while pockets between them can contain a re-
Siemens Building Technologies
Fire Safety
duced level of smoke. Take obstructions created by girders, joists, beams, air conditioning ducts, or architectural design into consideration when determining area protection. Refer to the Initiating Devices chapter of NFPA Standard 72 for Loca­tion and Spacing requirements for specific types of construc­tion; e.g. beam, suspended, level, sloped and peaked ceilings.
SFPT-11 DETECTOR PLACEMENT
Locate Model SFPT-11 on the ceiling, at least 4 inches from the side walls. For an ideal, smooth ceiling condition, place the de­tectors at a maximum center spacing of 50 feet (2500 square feet). For FM Approved installations, use maximum center spacing of 20 feet (400 square feet). Locate detectors 25 feet from side walls or room partitions.
Actual job conditions and sound engineering judgment must determine detector spacing. Consider environmental factors including ambient temperature fluctuation, and the nature of the fire hazard. Room or area configuration and ceiling type (sloped or flat, smooth or beamed) also dictates placement.
Should questions arise regarding detector placement, follow the drawings provided and/or approved by Siemens Building Technologies, Inc. or by its authorized distributors. This is ex­tremely important! The detector placements shown on these drawings were chosen after a careful evaluation of the area being protected. Siemens Building Technologies, Inc.’s exten­sive experience in design of the system assures the best detector placement by following these drawings.
OPERATION
LED Indicators
The Model SFPO-11 / SFP-11 / SFPT-11 contains an LED indi­cator capable of flashing either one of three distinct colors: green, yellow, or red. During each flash interval, the micro­processor-based detector checks the following:
• For smoke in its sensing chamber
• That its smoke sensitivity is within the range indi­cated on the nameplate label
• That its critical smoke sensing electronics are operating.
Based on the results of these checks, the LED indicator flashes the following:
lavretnIhsalF
)sdnoceS(
hsalF
roloCnoitidnoC
o
*neerG
wolleY
deRmralA4
sehsalFoN
.loot2TC-SF
yrosivrepuslamroN
ytivitisnesekomS.noitarep
.stimildetarnihtiwsi
ecivresseriuqerrotceteD
siro)riaperrogninaelc( stidnoyebgnitarepo icepslatnemnorivne
.snoitacif
.riaperseriuqer
lesybffodenrutebnacDEL*
ro,derewoptonsirotceteD
11-OPFS
11-PFS
4
4
-
ehtni"detavitcaeDDEL"gnitce
Temperature – Humidity – Pressure – Air Velocity
The operating temperature range for the SFPO-11, SFP-11 and SFPT-11 detectors is 32°F (0°C) to 100°F (38°C). The thermal alarm temperature is fixed at 135°F (57°C).Use these detec­tors in environments where the humidity does not exceed 93% (non-condensing). Normal changes of atmospheric pressure do not affect detector sensitivity. For SFPO-11 and SFP-11 open area 0-1200 ft/min applications, use the appropriate applica­tion from the FirePrint ASD application list. Use the ASD duct application for 300-4000 ft/min applications a) in above-ceil­ing and under-floor plenums, b) inside an air duct, and c) in an air duct housing using sampling tubes. Follow detector spac­ing and location requirements in NFPA 72 Chapter 5 for High Air Movement Areas and Control of Smoke Spread.
When installing Model SFPO-11 and SFP-11 in existing installa­tions with an existing duct detector housing, order an AD-11UK Air Duct Upgrade Kit DA-304, P/N 500-695967 and use it in that installation. This kit includes the required housing cover, P/N 305-095676. Do not use Model SFPO-11 and SFP-11 with any other air duct cover.
For air duct and open area applications, the SFPO-11 and SFP-11 smoke sensitivity range is indicated on its nameplate.
DETECTOR PROGRAMMING
Each detector on a loop must be programmed to respond to a unique system address.
• To program the detector address, use the Model SDPU Device Programming Unit. Refer to the SDPU Manual, P/N 315-033260C.
• Record the loop and device number (system address) for the detector on the detector label and on the base to prevent installing the detector in the wrong base. The optional SDPU label printer can be used for this purpose.
WIRING
Detector bases for Model SFPO-11/SFP-11/SFPT-11 should be connected as shown in Figure 3.
Detector Mounting
To ensure proper installation of the detector head into the base, be sure the wires are properly dressed at installation:
• Position all wires flat against the base.
• Take up all slack in the outlet box
• Route wires away from connector terminals.
Siemens Building Technologies Fire Safety
P/N 315-033290C-72
Loading...
+ 2 hidden pages