Selection Guide
Table 4. Valve Assemblies 1½”, 2” With Female NPT End Connectors, With PT Ports
24 Vac Proportional with Position Output Signal
(MP500C)
24 Vac Proportional/Floating with Position Output
Signal Spring Return Open
(MP500C-SRU)
24 Vac Proportional/Floating with Position Output
Spring Return Closed
(MP500C-SRD)
Flow Rate
(GPM)
18 1½ VP220E-40S-018-U131 VP220E-40S-018-U231 VP220E-40S-018-U331
19 1½ VP220E-40S-019-U131 VP220E-40S-019-U231 VP220E-40S-019-U331
20 1½ VP220E-40S-020-U131 VP220E-40S-020-U231 VP220E-40S-020-U331
22 1½ VP220E-40S-022-U131 VP220E-40S-022-U231 VP220E-40S-022-U331
24 1½ VP220E-40S-024-U131 VP220E-40S-024-U231 VP220E-40S-024-U331
26 1½ VP220E-40S-026-U131 VP220E-40S-026-U231 VP220E-40S-026-U331
28 1½ VP220E-40S-028-U131 VP220E-40S-028-U231 VP220E-40S-028-U331
30 1½ VP220E-40S-030-U131 VP220E-40S-030-U231 VP220E-40S-030-U331
32 1½ VP220E-40S-032-U131 VP220E-40S-032-U231 VP220E-40S-032-U331
34 2 VP220E-50S-034-U131 VP220E-50S-034-U231 VP220E-50S-034-U331
36 2 VP220E-50S-036-U131 VP220E-50S-036-U231 VP220E-50S-036-U331
38 2 VP220E-50S-038-U131 VP220E-50S-038-U231 VP220E-50S-038-U331
40 2 VP220E-50S-040-U131 VP220E-50S-040-U231 VP220E-50S-040-U331
44 2 VP220E-50S-044-U131 VP220E-50S-044-U231 VP220E-50S-044-U331
48 2 VP220E-50S-048-U131 VP220E-50S-048-U231 VP220E-50S-048-U331
52 2 VP220E-50S-052-U131 VP220E-50S-052-U231 VP220E-50S-052-U331
a. Factory set. Complete flow ranges shown in tables for 1/2…2" on page 11 and page 18.
Valve
Size
a
(inch)
Table 5. Valve Assemblies 2½"…4” with ANSI Standard B16.1 Flanges, With PT Ports
24 Vac Proportional with Position Output Signal (MP500C)
Flow Rate
(GPM)
56 2½ VP220A-65S-056-U131 VP220A-65S-056-U231 VP220A-65S-056-U331
60 2½ VP220A-65S-060-U131 VP220A-65S-060-U231 VP220A-65S-060-U331
65 2½ VP220A-65S-065-U131 VP220A-65S-065-U231 VP220A-65S-065-U331
70 2½ VP220A-65S-070-U131 VP220A-65S-070-U231 VP220A-65S-070-U331
75 2½ VP220A-65S-075-U131 VP220A-65S-075-U231 VP220A-65S-075-U331
80 2½ VP220A-65S-080-U131 VP220A-65S-080-U231 VP220A-65S-080-U331
90 3 VP220A-80S-090-U131 VP220A-80S-090-U231 VP220A-80S-090-U331
100 3 VP220A-80S-100-U131 VP220A-80S-100-U231 VP220A-80S-100-U331
165 (min. 66) 4 VP220A-100S-165-U131 VP220A-100S-165-U231 VP220A-100S-165-U331
a. Factory set. Complete flow ranges shown in tables for 2½"…4" on page 12 and page 19.
Januar y, 2019 tc © 2019 Schneider Elect ric. All r ights rese rved. A ll trademarks are ow ned by Schne ider Elect ric Indust ries SA S or its aff iliated co mpanies.
Document Number: F-27947-7
Valve
Size
a
(inch)
24 Vac Proportional/Floating with Position Output
Signal Spring Return Open
(MP500C-SRU)
24 Vac Proportional/Floating with Position
Output Signal Spring Return Closed (MP500C-
SRD)
Table 6. Specification 1½”…4” Valve Body Actuators
1½”…4” Valve Body Actuator Part
Number (actuator code)
Input Signal Proportional, 0…10 Vdc, 2…10 Vdc, 4…20 mA, sequencing with selectable input signal action and Floating, DIP switch selectable
Electrical Connection Screw terminal with conduit connector
Position Feedback Output Signal 2…10 Vdc 2…10 Vdc, 0…5 Vdc
Spring Return – Open Valve Close Valve
Auxilary Switch Optional Module
Other Features
Linear/Equal% Valve Flow Curve Selection Yes Yes
Actuator Speed Full Stroke
60 Hz (50 Hz)
Power Consumption Running 15 VA, Transformer Sizing 50 VA Running 30 VA, Transformer Sizing 50 VA
Operating Temperature Limits °F (°C) 14…122 (-10…50)
Actuator Weight (lb.) 4.0 6.0
Regulatory Compliance
Specification Data Sheet F-27944 F-27945
Installation Data sheet F-27942 F-27943
All actuators are 24 Vac. 50/60 HZ with conduit connector holes and wiring terminal block, manual override
Auto calibration, field selectable floating input
signal travel time, powered manual override
Underwriters Laboratory (E9429) compliance as Temperature Indicating & Regulatory Equipment cULus LISTED per UL873 and Canadian
Standard C22.2 No. 24. European Community compliance per EMC directive (2014/30/EU) and LVD directive (2014/35/EU). Australian/New
Zealand community RCM mark.
MP500C
(U131)
Proportional 15 (15)
Floating 60 or 300 (60 or 300)
MP500C-SRU
(U231)
Auto calibration, field selectable floating input signal travel time
Floating 60 or 300 (60 or 300) Spring Return 13 (13)
Proportional 15 (15)
MP500C-SRD
(U331)
Table 7. Valve Assemblies 5” and 6” With PT Ports with ANSI Standard B16.1 Flanges
24 Vac Proportional with Position Output
Signal (MP2000-NSR)
24 Vac Proportional/Floating with Position
Output Signal Spring Return Open
(MP2000-SRU)
24 Vac Proportional/Floating with
Position Output Spring Return Closed
(MP2000-SRD)
Selection Guide
Flow Rate
(GPM)
395 (min. 158) 5 VP220A-125S-395-U161 VP220A-125S-395-U261 VP220A-125S-395-U361
485 (min. 194) 5 VP220A-125H-485-U161 VP220A-125H-485-U261 VP220A-125H-485-U361
640 (min. 256) 6 VP220A-150S-640-U161 VP220A-150S-640-U261 VP220A-150S-640-U361
830 (min. 332) 6 VP220A-150H-830-U161 VP220A-150H-830-U261 VP220A-150H-830-U361
a. Factory set. Complete flow ranges shown in tables for 5"…6" on page 12 and page 19.
Valve
Size
a
(inch)
Table 8. Specification 5”and 6” Valve Body Actuators
5” and 6” Valve Body Actuator Part
Number (actuator code)
Input Signal Proportional, 0…10 Vdc, 2…10 Vdc, 0…20 mA, 4…20 mA, with selectable input signal action and Floating, DIP swtich selectable
Electrical Connection Screw terminal with conduit connector
Position Feedback Output Signal 0…10 Vdc, 2…10 Vdc, 0…20 mA, 4…20 mA
Spring Return – Open Valve Close Valve
Auxilary Switch Yes
Other Features
Linear/Equal% Valve Flow Curve Selection Yes
Actuator Speed s/mm 60 Hz (50 Hz) 3 or 6 (3 or 6) 4 or 6 (4 or 6)
Power Consumption 15.0 VA
Operating Temperature Limits °F (°C) 32…131 (0…55)
Actuator Weight (lb.) 13.8 18.96
Regulatory Compliance
Specification Data Sheet F-27976 F-27969
Installation Data sheet F-27956
a. When used with a proportional input signal. All actuators are 24 Vac. 50/60 HZ with conduit connector holes and wiring terminal block, manual override
© 2019 Schneider Elect ric. All r ights rese rved. A ll trademarks are ow ned by Schne ider Elect ric Indust ries SA S or its aff iliated co mpanies. Janua ry, 2019 tc
Docume nt Number : F-27947-7
cULus according to UL 60730-1A/-2-14 and CAN/CSA E60730-1/-2-14 and CE according to EN 60730-1/-2-14 per EMC [2014/30/EU] and LVD [2014/35/EU]
MP2000-NSR (U161) MP2000-SRU (U261) MP2000-SRD (U361)
a
configurable position outpout signals, selectable speed, adjustable equal percentage flow curve
Auto calibration, 3-color LED indication, powered manual override,