Application
For low or line voltage control of static, velocity or total
pressures, or differential static or total pressures of air and
non-combustible gases only.
Specifications
Setpoint:
Factory Set, 0.07" (1.8 mm) W.C.
Field Adjustable, 0.07 to 1" (1.8 to 25.4 mm) W.C.
Sensing Element: Neoprene diaphragm.
Differential: 0.04" (1 mm) W.C. at minimum setpoint
(3 mm) W.C. at maximum setpoint.
Environment:
Ambient Temperature Limits,
Shipping, -40 to 140°F (-40 to 60°C).
Operating, 35 to 140°F (0 to 60°C).
Humidity, 5 to 95% R.H., non-condensing.
Locations, NEMA Type 1 indoor only.
Maximum Pressure: 12" (305 mm) W.C.
Electrical Switch: Snap action SPDT.
Ratings, See Table-1.
Connections, Code screw terminals
Case: All metal with 1/2" conduit opening.
Mounting: In vertical position on any surface free of
n.
vibratio
Dimensio
mm x 121 mm x 11
Accessories
AP-302 Static probe for turbulent air
AP-305 Static probe for low actuating pressure
AT-208 Duct mtg. kit for remote probes other than
ns: 5-1/8" high x 4-3/4" wide x 4-3/8" deep (130
1 mm).
AP-302 or
AP-305
to 0.1"
Pre-Installation
Inspection
Visually inspect the carton for damage. If damaged, notify the
appropriate carrier immediately. Visually inspect the device
for obvious damage due to shipping. Return damaged parts
to place of purchase.
Required Installation Items
• Wiring or piping diagrams
• Appropriate screwdrivers (not provided) for mounting
screws (provided)
• Conduit fittings (not provided)
PC-301
Differential Pressure Switch
General Instructions
Installation
Caution:
1. Installer must be a qualified, experienced technician.
2. Disconnect power supply before installation to prevent
electrical shock.
3. Make all connections in accordance with the wiring
diagram, and in accordance with national and local
electrical codes. Use copper conductors only.
4. Avoid locations where excessive moisture, corrosive
fumes or vibrations are pre
intended for indoor use primarily to provide a degree of
protection against contact with the enclosed equipment.
5. For use with air or non-combustible gases only.
Table-1 Maximum Electrical Switch Ratings
Full Load
Vac
24V -- -- 60 --
120V 6.25 37.5 300 --
240V 3.1 18.6 300 --
277V 2.7 16.2 300 10
Amps
Locked
Rotor Amps
sent. NEMA 1 devices are
Pilot Duty
(VA)
Non-Inductiv
e
Amps
Printed in U.S.A. 5/10 © Copyright 2010 Schneider Electric All Rights Reserved. F-16160-9