Schneider Electric MA-5200 Series, MA-5300 Series Data Sheet

Application

MA-521X Series
Valve Actuator
MA-533X Series
Damper Actuator

The MA-5200 series and MA-5300 series actuators a re used for two-position control of valves and dampers which require a return to the normal position upon power interruption.

Two-position actuators controlled by an SPST
controller
Spring return
24 Vac, 120 Vac, and 240 Vac mode ls ar e av aila ble
MA-5200 Series MA-5300 Series
Two-Position Actuators
General Instructions
An actuator with the part number suf fix "- 500" has a
built-in, adjust
able, SPDT auxiliary switch
Available in damper models or base models that
re
quire damper or valve linkage
Die cast lower housing with 1/2" conduit opening
and painted steel upper housing
Hydraulic actuator with oil-immersed motor and
pump

Applicable Literature

Pneumatic Products Catalog, F-27383
Environmental Controls Cross-Reference Guide, F-
23638
Environmental Controls Reference Manual,
F-21683
Environmental Controls Application Manual,
F-21335
Material Safety Data Sheet MSDS-3,
(Until Feb. 1989)
Material Safety Data Sheet MSDS-12 (Currently)
Printed in U.S.A. 4/10 Copyright 2010 Schneider Electric All Rights Reserved. F-15070-15

SPECIFICATIONS

Actuator Inputs
Control Circuit: Two wire, SPST. Power Input: Refer to Table-1 and Table-2. Connections: Color-coded 4 ft. (1.2 m) leads.
Actuator Outputs
Electrical:
Auxiliary Switch (MA-5xxx-500), 10 Amps, 120/240 Vac adjustable SPDT, factory set
to close the N.O. contact at the retracted end of stroke.
Mechanical:
Stroke,
Damper Approximately 2" (51 mm) from fully retracted to fully extended (includes
AM-601 linkage).
Valve Approximately 9/16" (14.3 mm) from fully retracted to fully extended. Nominal Damper Area, Actuator sizing should be done in accordance with damper manufacturer’s specifications.
Environment
Ambient Temperature Limits:
Shipping & Storage, -40 to 140° F (-40 to 60° C). Operating,
Damper 0 to 140° F (-18 to 60° C).
Valve Refer to Table-3.
Humidity: 5 to 95% RH, non-condensing. Location: NEMA Type 1. Agency Listings:
UL 873, Underwriters Laboratories (File # E9429 Category Temperature-Indicating and

Regulating Equipment). CSA, Certified for use in Canada by Underwriters Laboratories. Canadian Standard C22.2 No. 24-93. European Community, EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).

Table-1 Model Chart for Damper Actuators.

Actuator Power Input
Part
Number
MA-5330 120 MA-5333 24
AC
Voltage
+10/
-15%
Hz VA Watts
50 60 18 14 60 15 20 (2.3)
Timing in Seconds
@ 72° F (22° C)
To Extend
(No Load
Stroke)
Retract
on Power
Torque Rating
(Extend & Retract)
lb.-in. (N-m)
Loss
2 Copyright 2010 Schneider Electric All Rights Reserved. F-15070-15

Table-2 Model Chart for Valve Actuators. Also for Damper Actuators with Field Assembled Damper Linkages.

Timing in Seconds @
72° F (22° C)
To Extend
(No Load
Stroke)
Retract on
Power
Loss
Required Linkage
Damper Valve
Part Number
MA-5210
AC
Voltage
+10/-15%
Actuator Power Input
Hz VA Watts
10 Amps
Aux
Switch
No
120
MA-5210-500 Yes MA-5211
240
50 60 18 14
MA-5211-500 Yes MA-5213
No
No
60 15 AM-601
AV-600
b
AV-601
24
MA-5213-500 Yes
a
Damper models are provided with factory-installed damper linkages. Only base models require separately-ordered linkages.
b
With the installation of the AM-601 damper linkage, these valve actuat ors beco me fu nctio nally the same a s the d amper actua tors li st ed i n Table- 1. Re fer to
Table-1 for the torque rating.
c
May be required for steam and hot water. Refer to Table-3.

Table-3 Maximum Allowable Ambient Air Temperature for Valve Actuators.

Maximum Temperature of Media
in the Valve Body
(Check the Rating of the Valve)
°F (°C)
366 (186) 90 (32) 90 (32)
Maximum Ambient Temperature
of MA-521x Series
AV-600 (Only)
°F (°C)
AV-600 and AV-601
°F (°C)
a
c
340 (171) 100 (38) 100 (38) 281 (138) 115 (46) 140 (46)
181 (83) 140 (60) 80 (26) 140 (60)
a
Maximum ambient temperature of the actuator must never exceed 140° F (60° C).
a
a
140 (60) 140 (60)
a
a
a
ACCESSORIES Common
11-1612 1/2" conduit bushing
Damper Linkages
AM-111 Crank arm for 5/16" (8 mm) diameter damper shaft AM-112 Crank arm for 3/8" (10 mm) diameter damper shaft AM-113 Crank arm for 1/2" (13 mm) diameter damper shaft AM-115 Crank arm for 7/16" (11 mm) diameter damper shaft AM-122 Linkage connector straight type AM-123 Damper clip AM-125 5/16" diameter x 20" damper rod AM-125-048 5/16" diameter x 48" damper rod AM-132 Ball joint connector AM-161-3 Damper linkage kit AM-601 Device includes mounting bracket, damper linkage with spring, and AM-122
straight connector. Required to modify (MA-521x series) valve actuators into 2" (51
mm) stroke damper actuators.
AM-602 Spacer
Valve Linkages
AV-600 Valve linkage AV-601 Valve linkage extension for hot water and steam applications; use with AV-600
TOOLS (factory-available)
TOOL-12 Wrench for adjustment of auxiliary switch TOOL-19 Spring compression tool for AV-600 TOOL-37 1-5/8" (41 mm) open-ended wrench
F-15070-15 Copyright 2010 Schneider Electric All Rights Reserved. 3

TYPICAL APPLICATIONS (wiring diagrams)

Black
Green
MA-5XXX Actuator
NOTE: Actuator extends when
contacts are closed and retracts when contacts are open
Actuator Voltage
Vac
Color(s) of
L2 Lead
L1
24 120 240
Black/Blue
White
White/Black
L2
Red/White (C)
Thermostat
or Switch
Orange (N.C.)
Brown (N.O.)
Aux. Switch Leads
(-500 Actuators only)

Figure-1 Typical Wiring for MA-5xxx Series Actuators.

INSTALLATION Inspection Inspect the package for damage. If damaged, notify the appropriate carrier immediately.
If undamaged, open the package and inspect the device for obvious damage. Return damaged products.

Requirements Job wiring diagrams.

Tools (not provided):
– Digital Vo lt-ohm Meter (DVM). – Appropriate drill and drill bit for mounting screws. – Appropriate screw drivers and wrenches. – TOOL-12, Wrench for adjustment of auxiliary switch. – TOOL-19, Spring compression tool for AV-600. – TOOL-37, 1-5/8" (41 mm) open-ended wrench.
Training: Installer must be a qualified, experienced technician.
Warning:
Disconnect power supply before installation to prevent electrical shock and equipment
damage.
Make all connections in accordance with the wiring diagram and in accordance with
national and local electrical codes. Use copper conductors only.
Caution:
Static charges produce voltages high enough to damage the electronic components.
Follow static electricity precautions when installing or servicing the device(s). Discharge any static electricity you may have accumulated by using wrist straps, or by touching a known, securely grounded object.
Do not exceed the ratings of the device(s).
Do not apply power to the unit unless the damper linkage and/or the valve assembly
have been installed.
Avoid locations where excessive moisture, corrosive fumes, or vibration is present.
Do not install insulation on any part of the actuator.
4 Copyright 2010 Schneider Electric All Rights Reserved. F-15070-15

Mounting Do not twist or exert any force on the actuator housing during installation. Either turn the

Housing
Base
Wrench Flats
base by hand or, if necessary , use a 1-5/8" (41 mm) open-ended wrench (TOOL-37) on the flats provided on the actuator base or the valve body mounting nut. Refer to

Figure-2 Housing and Base Location.

Dampers
The actuator is not position sensitive. It can be mounted in any position in a NEMA Type 1 location.
Valves
Allow 3" (76 mm) of clearance above the actuator valve assembly for the removal and reattachment of the actuator to the installed valve.

1. Install all two-way valves so that they close against the flow . An arrow o n the valve body or tag indicates proper flow direction.

2. Always install three-way mixing valves with two inlets and one outlet.
3. Always install three-way diverting valves with one inlet and two outlets.
Figure-2.
Caution: For steam applications only, mount the actuator above the valve body at 45° from vertical.
4. Actuators can be mounted in any upright position above the centerline of the valve body.

Wiring Requirements Power Leads

The low voltage (24 Va c) power leads may be connected to a Class 2 circuit if routed separately from Class 1 circuit wiring. The line voltage (120 and 240 Vac) leads must be connected to a Class 1 circuit. Refer to
Refer to T able-4 for the maximum length of run for the power leads, for the given wire size(s). T o determine the allowable maximum power lead run when wiring multiple actuators, divide the maximum run shown in for further details.
Figure-7.
Table-4 by the number of actuators on the run. Refer to Figure-3
F-15070-15 Copyright 2010 Schneider Electric All Rights Reserved. 5
Table-4 Power Wiring Data.
To Vac Power
To Additional MA-52XX
Series Actuators
Black
Green
Green
MA-52XX
MA-52XX
24 Vac Black/Blue 120 Vac White 240 Vac White/Black
Actuator
Voltage
Vac
120
240
24
120
24
Actuator Model
Number
MA-5210 MA-5210-500 MA-5211 MA-5211-500 MA-5213 MA-5213-500 MA-5330 MA-5330-500 MA-5333 MA-5333-500
Power Lead
Colors
Black & White 14 3,500 (1,067)
Black & White/Black 14 6,000 (1,829)
Black & Black/Blue
Black & White 14 3,500 (1,067)
Black & Black/Blue
Wire SizeGAMaximum Wire Run
14 12
14 12
ft. (m)
300 (91.5)
480 (146.3)
300 (91.5)
480 (146.3)
Figure-3 Wiring of Multiple MA-52xx Series Actuators to Single Power Source.
Auxiliary Switch Leads
The low voltage (24 Va c) auxiliary switch leads may be connected to a Class 2 circuit. The line voltage (120 Vac and 240 Vac) a uxiliary switch leads must be connected to a
1 circuit and routed separately from any Class 2 circuit wiring. Refer to Figure-7.
Class

Wiring Connections Wire Lead Connections (No Conduit)

6 Copyright 2010 Schneider Electric All Rights Reserved. F-15070-15
Make connections as required. Refer to Figure-1 for a wiring diagram of a typical application. Refer to Figure-4 for a view of the actuator.
Note: The cover plate and screw supplied with the actuator are not required with this method.
Figure-4 Connection of Wire Leads (No Conduit).
Base
Knockout
Ribs
Cover Plate
Base
or
Installing 3/8" Flexible Conduit Onto One or Both Sides of Actuator
Flexible conduit may be installed onto one or both sides of the actuator (refer to Figure-6 and Figure-7). Install each conduit as follows:
1. Determine the side of the actuator to which the flexible conduit is to be attached.
2. Remove the knockout (e.g., with channel lock pliers) on the selected side of the actuator. Refer to
3. Make the required connections. Refer to Figure-1 for a wiring diagram of a typical application.
4. Slip the conduit onto the base, over the ribs. Refer to Figure-6 and Figure-7.
5. If flexible conduit is to be installed on both sides of the actuator, repeat the preceding steps to install the second conduit.
Figure-5.
Figure-5 Removal of Knockout on Actuator Base.
F-15070-15 Copyright 2010 Schneider Electric All Rights Reserved. 7
Figure-6 Flexible Conduit Installation to Either Side of Actuator.
Figure-7 MA-5200 and MA-5300 Series Wiring with Separation
Transformer
(AM-610 shown)
4 x 4
Conduit
Box
Cover Plate
Leave Knockout in place
Low voltage motor leads may be connected to a Class 2 circuit if routed separately from wiring that is other than Class 2
The line voltage auxiliary switch leads must be separated from Class 2 motor circuit wiring.
Note: Class 2 circuit wiring must be routed separately from the wiring from other circuits. Do not route Class 2 circuit wiring in the same conduit box with the line voltage transformer
Typical for 24 Vac
models (MP-5XX3)

Figure-8 Cover Plate Knockout Removal.

Cover Plate
Knockout
1/8" (3 mm) maximum
Use TAC 11-1612, Bridgeport 1102-DC, or equivalent

Figure-9 1/2" Conduit Bushing.

for Class 2 and Line Voltage Circuits.
6. Install the cover plate with two screws. The cover plate and two screws are supplied with the actuator.
Installing Conduit Box Onto Actuator
Installation of a conduit box allows for the attachment of one or more thin wall conduits to the actuator. This procedure also serves as an optional method for connecting flexible conduit to the actuator.
1. Remove the knockout from the cover plate supplied with the actuator . Refer to Fig ure-8 .
2. Slip the actuator’s leads through a standard 1/2” conduit bushing (Figure-9, not supplied) and the knockout hole in the cover plate. Refer to Figure-10.
8 Copyright 2010 Schneider Electric All Rights Reserved. F-15070-15
3. Seat the conduit bushing in the base.

Figure-10 Conduit Bushing and Cover Plate Installation.

1/2" Conduit Bushing
(not supplied)
Base
Cover Plate

Figure-11 Attachment of Conduit Box to Conduit Bushing.

4. Install the cover plate, using the two screws provided.
5. Loosely install the conduit box and the locknut onto the conduit bushing. Refer to Figure-11.
6. Tighten the locknut as follows: a. Tilt the conduit box approximately 30 degrees counterclockwise, relative to the
actuator. b. Finger-tighten the locknut against the conduit box. c. Rotate the conduit box clockwise until it is aligned with the actuator. This will tighten
the locknut.
7. Make the required wiring connections. Refer to Figure-1 for a wiring diagram of a typical application.
8. Install the conduit to the conduit box as required.
F-15070-15 Copyright 2010 Schneider Electric All Rights Reserved. 9
Note: As shown in Figure-10, the hole in the cover plate of the actuator conduit housing is sized to accept both British standard M20 (20 mm) conduit connectors and 20 mm-to-PG16 adaptors for use with DIN PG16 connectors. (Follow the steps for installing the conduit box to the actuator.)
Linkage Assembly Damper
Spring returns open
on loss of power
Open
Close
ExtendRetract
Damper Shaft
Spring returns open
on loss of power
Open
Close
Extend Retract
Damper Shaft
Note: Each actuator in the MA-5x3x series is provided with a factory-installed damper linkage. No separately-ordered linkage is required.
Caution: Do not twist or exert any force on the actuator housing during installation. Either turn the base by hand or, if necessary, use a 1-5/8" (41 mm) open-ended wrench (TOOL-
37) on the flats provided on the actuator base, or on the valve body mounting nut. (Refer to Figure-2.)
1. Determine the best mounting position for the actuator as follows: a. Determine, from the system requirements, if the damper should spring-return to the
open position (refer to
Figure-12) or closed position (refer to Figure-13) whenever power is lost to the actuator. For example, an outside air damper actuator is typically linked so as to retract (spring-return) to the damper’s fully closed position (safe position).
Figure-12 Dampers Open When Actuator Retracts
(Spring-Returns Open on Power Loss).
Figure-13 Dampers Open When Actuator Extends
(Spring-Returns Closed on Power Loss).
b. Be sure to allow adequate working space around the actuator mounting location to
mount the actuator, link it to the damper, and wire it into the system (refer to Figure-20).
c. If possible, select a mounting position such that, at mid-stroke, the actuator crank
arm and the damper crank arm on the drive shaft are each at a 90° angle to the damper rod (Refer to
Figure-14). This is the recommended mounting position. It
may be necessary to swivel the actuator linkage to arrive at this mounting location.
10 Copyright 2010 Schneider Electric All Rights Reserved. F-15070-15
Mounting
Points
Actuator
Crank Arm
Mid-Stroke Position
Angle from Mid-Stroke Position (See Table)
Position of Linkage Connector (See Table)
Damper
Shaft
Damper
Crank Arm
Linkage
Connectors
Damper
Rod
Mounting
Points
Required
Damper
Rotation
Angle
from
Mid-Stroke
Position
Position of
Linkage
Connector
60° 90°
30° 45°
2" (50 mm)
1-1/2" (38 mm)

Figure-14 Recommended Actuator/Damper Mounting.

d. Consider the damper rod length when positioning the actuator in relation to the
damper. A damper rod that is too long is not rigid enough to provide good control, while a damper rod that is too short makes adjustment difficult.
2. Position the actuator on the duct and mark the location of the mounting holes, using the actuator mounting bracket as a template (refer to Figure-20).
3. Drill or punch the mounting holes in the duct for the appropriate 1/4" (6 mm) diameter screws or bolts. The actuator must be mounted firmly enough to prevent excessive actuator movement under normal damper loading. If there is excessive actuator movement, the damper may not fully open or close.
4. Mount a ball joint connector in the slot on the damper crank arm. To achieve 90° of damper rotation, position the connector 1-1/2" (38 mm) from the centerline of the shaft hole on the crank arm. For 60° of damper rotation, position the connector 2" (50 mm) from the shaft hole centerline. Typically, 60° to 70° of rotation (maximum is 90°) is sufficient to permit almost maximum air flow through the dampers. (Refer to
5. Rotate the damper to its open position. Install and secure the damper crank arm (with ball joint connector) to the damper shaft, positioning the crank arm as fo llows (Refer to Figure-14):
a. To achieve 60° of damper rotation, position the crank arm so that it is pointed
towards the actuator at 30° from its mid-stroke position.
b. To achieve 90° of damper rotation, position the crank arm so that it is pointed
towards the actuator at 45° from its mid-stroke position.
6. Install the damper rod by sliding one end through the ball joint connecto r moun ted on the damper crank arm, and the other end through the straight connector on the actuator crank arm. Tighten the nut on the actuator crank arm’s straight connector. Cut off any excess length of damper rod.
7. For normally open dampers, tighten the nut on the ball joint connector on the damper crank arm. T o ensure that the damper closes completely , make adjustments so that the actuator is 1/16" (1.6
mm) from the extended end of stroke when the damper closes.
Verify and, if necessa ry, make final adjustments during system checkout.
8. For normally closed dampers, rotate the damper crank arm until the damper is closed. While holding the damper closed, tighten the nut on the ball joint connector on the damper crank arm. T o ensure that the damper closes completely , make adjustments so that the actuator is 1/16" (1.6 closes.
Final adjustment of the actuator and damper must be performed when the system is
F-15070-15 Copyright 2010 Schneider Electric All Rights Reserved. 11
powered and functioning. Refer to the CHECKOUT section to ensure that the damper is linked correctly.
mm) from the retracted end of stroke when the damper
Figure-14).
Valve
Position Indication and
Switch Action Cam
Auxiliary Switch
Adjustment Screw
MA-52XX-500
Series
For valve assembly details refer to AV-600, Valve Linkage Kit General Instructions, F-26279 or AV-601, Linkage Extension Kit General Instructions, F-26280. Refer to
Figure-21 for external dimensions of the valve actuator.
Adjustments Auxiliary Switch (MA-5xxx-500)
The switching point is adjustable over the entire actuator stroke and is pre-set at the factory to close the N.C. contacts at the retracted end of stroke. Turning the switch adjustment screw CW (using TOOL-12), adjusts the make (or break) point closer to the extended end of stroke. (Refer to
Figure-15).
Figure-15 Auxiliary Switch Actuation Point Adjustment and
Position Indication for MA-5xxx-500 Series.

CHECKOUT

After the entire system has been installed and the actuator has been powered up, perform the following checks for proper system operation.
Caution: Never power the actuator without a spring return linkage attached.

Positioning with Controller

If the sensed media is within the controller’s setpoint range, the actuator can be positioned by adjusting the controller setpoint up and down. Check for correct operation of the actuator (valve or damper) while the actuator is being stroked.

Go, No-Go Test 1. Apply power to the actuator. The actuator motor should run and the actuator shaft sh ould

extend.
2. Remove power from the actuator. The actuator motor should stop running and the actuator shaft should spring-return to the retracted position.
12 Copyright 2010 Schneider Electric All Rights Reserved. F-15070-15

THEORY OF OPERATION

Hydraulic
Piston Assembly
Oil-Filled Case
Check Valve
Electric Pump
Switch/Thermostat
To AC Power
Source
Orange Brown
Red/White
Auxiliary Switch Wires
Switch Point Adjustment
for Auxiliary Switch
Position Indication and
Switch Action Cam
Auxiliary
Switch
3/4"
(19 mm)
1-5/16"
(33 mm)
1-5/16"
(33 mm)
MA-521X-XXX MA-521X-XXX-2 MA-521X-XXX-3
Obsolete Actuators
Current Actuator
Refer to Figure-16. The permanently sealed, oil-filled case contains a movable hydraulic piston assembly and an electric pump for the hydraulic system. The pump generates a fluid pressure which is transmitted to the top of the piston, creating a hydraulic force which drives the piston downward. Opposing the hydraulic force is the spring of the valve or damper linkage. When the hydraulic force becomes great enough to overcome the opposing spring force, the piston translates downward, extending the output shaft. The electric pump is powered by the input supply voltage and runs whenever the voltage is applied. When power is removed from the pump, it stops running, decreasing the hydraulic force above the piston. This allows the spring force to overcome the hydraulic force, pushing the piston upward and retracting the output shaft. The oil above the piston is allowed to flow backward through the pump by means of a check valve.

REPLACEMENT PARTS

F-15070-15 Copyright 2010 Schneider Electric All Rights Reserved. 13

Figure-16 MA-5xxx Series Actuators.

The installation of replacement actuators, in place of the obsolete series of MA-5xxx actuators (refer to Figure-17), may require additional items. These replacement items are required for the following reasons:

1. The AM-601 damper linkage is used to convert base actuators to damper actuators when damper models are not available.

2. The AM-602 spacer is used when current actuators are installed on old linkages (refer
Figure-18 and Figure-19).
to
3. The AE-249 transformer (208 Vac to 120 Vac) is used when replacing 208 Vac actuators (MA-5xx2) with 120

Figure-17 Current and Obsolete Actuators.

V ac actuators (MA-5xx 0).

MAINTENANCE

Spacer
AM-602
1-5/8"
(41mm approx.)
1-5/8"
(41mm approx.)
Obsolete Linkages
AV-315, AV-317, AV-319-10,
& AV-319-20
Current Linkage
AV-600
2-3/16"
(56mm approx.)
Strap
Obsolete AM-601
Current AM-601-0-0-2
No Strap

TROUBLESHOOTING

Figure-18 Current and Obsolete Valve Linkages.

Figure-19 Current and Obsolete Damper Linkages.

The actuator is sealed in oil and requires no maintenance. Regular maintenance of the total system is recommended to assure sustained, optimum
performance.
Use the following steps to locate malfunctions:

1. Check the actuator by applying the proper supply voltage.

2. The motor should run when power is applied. If it does not run, the actuator is inoperative and should be replaced.

3. While the motor is running, the actuator should extend. If it does not extend, check the mechanical linkage for any damage or misadjustment which could prevent the actuator from extending. If the mechanical linkage is inoperative, adjust the linkage or replace the damaged components, as applicable. If the mechanical linkage moves correctly and freely, the problem lies in the actuator and it must be replaced.

4. If applying power directly to the actuator results in correct operation of the actuator, the actuator and linkage are functional, and the problem lies in the wiring or thermostat. Repair or replace the wiring or thermostat, as applicable.

FIELD REPAIR

14 Copyright 2010 Schneider Electric All Rights Reserved. F-15070-15
None. Replace an inoperative actuator with a functional unit.

DIMENSIONAL DATA

Actuator
(4) 1/4"
(6 mm)
2"
(50 mm)
5/16"
(8 mm)
4-5/8"
(117 mm)
5-3/4"
(146 mm)
8"
(203 mm)
3-1/4"
(83 mm)
4-1/4"
(108 mm)
4-1/4"
(110 mm)
5-1/2"
(140 mm)
4-3/4"
(120 mm)
3-1/4" Dia.
(83 mm)
6-3/4"
(171 mm)
2-9/32"
(58 mm)
3-23/32" (94 mm)
1-3/8"
(35 mm)

Figure-20 Damper Linkage Assembly Dimensions.

Figure-21 Actuator Dimensions.

F-15070-15 Copyright 2010 Schneider Electric All Rights Reserved. 15
On October 1st, 200 9, TA C became the Buildings business of its parent company Sc hneider Electric. This document refle cts the visual identi ty of Sc hneider El ectric, however there r emains r eferences to T AC as a corpor ate brand i n the body copy. As each document is updat ed, the body copy w ill be change d to refl ect appropriate
corporate brand changes.
Copyright 2010, Schneider Electric All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change without notice.
F-15070-15
Loading...