Schneider Electric MA40-704x Series, MA41-707x Series, MA41-715x Series Data Sheet

MA40-704x Series, MA41-707x Series, and MA41-715x Series
Specifications
Inputs
Control signal On-off SPST contacts or Triacs (500 mA).
Power Refer to Model Chart.
Connections
Outputs
Motor Type
Electrical
Mechanical
Environment
Ambient Temperature limits
Humidity 5 to 95% RH, non-condensing.
Locations
Dimensions
Agency Listings
UL
European Community EMC Directive (89/336/EEC). Low Voltage Directive (72/23/EEC).
CUL Canadian Standards C22.2 No. 24-93.
Australia
General Instructions Refer to F-26642.
MA40-704x, MA41-707x: Brush. MA41-715x: Brushless DC.
MA40-7043-501: One auxiliary switch available, SPDT 6A resistive @ 24 Vac, adjustable 0 to 95q (0 to
1 scale). UL listed, switch meets VDE requirements for 6 (1.5)A, 24 Vac. MA40-7040-501 or MA40-7041-50: One auxiliary switch available, SPDT 6A resistive @ 240 Vac,
adjustable 0 to 95q (0 to 1 scale). UL listed, switch meets VDE requirements for 6 (1.5)A, 24 Vac. MA41-715x-502 or MA41-707x-502: Two auxiliary switches available, SPDT 7A resistive @ 250 Vac,
one fixed @5 q and one adjustable 25 to 85q. UL Listed, meets VDE requirements for 7 (2.5)A, 250 Vac.
Direction of rotation: CW or CCW rotation is available through reverse mounting.
Shaft clamp: Direct coupled using a through hole output hub.
MA40-704x: Up to 5/8 in. round, 1/2 in. square shafts. MA41-71xx: Up to 3/4 in. round, 1/2 in. square shafts.
See Accessories for larger shaft options.
Position Indicator: MA40-704x: Visual indicator, 0 to 1 (0 is the spring return position). MA41-707x, MA41-715x: Pointer (-5 to 90°) and scale are provided for position indication (-5 is normal or spring return position).
Shipping and storage: -40 to 160qF (-40 to 71qC). Operating: -22 to 140qF (-30 to 60qC).
MA40-704x: NEMA 2 (IEC 1P54) no restrictions.
MA41-707x: NEMA 1 (IEC IP30), NEMA 2 (IEC IP54) with conduit in the down position.
MA41-715x: NEMA 1 (IEC IP30), NEMA 2 (IEC IP54) with conduit in the down position.
MA41-707x, MA41-715x: 10-1/2 H x 4 W x 3-1/2 D in. (287 x 100 x 89 mm). MA40-704x: 6-51/64 H x 4 W x 3-1/2 D in. (68 x 100 x 89 mm).
UL-873, Underwriters Laboratories Listed (File #E9429 Category Temperature-Indicating and Regulating Equipment).
This product meets requirements to bear the C-Tick mark according to the terms specified by the Communications Authority under the Radio Communications Act 1992.
80
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
MA40-704x Series, MA41-707x Series, and MA41-715x Series
Accessories
Model No. Description
MA41-707x, MA41-715x
abcd
AM-671
abcd
AM-672
a
AM-673 AM-674 Weather shield. AM-675 Weather shield base. AM-676 Universal shaft extension, approximately 9-1/2 in. long (242 mm) for use on 3/8 to 11/1 6 in. (10 to 17 mm)
AM-686 Position indicator. AM-687 V-clamp for 1.05 in. round shafts. AM-688 Replacement universal clamp. AM-689 Rotation limiter. AM-690 Crank arm. AM-691 Crank arm. AM-692 V-bolt.
ef
AM-693 AM-714 Weather shield. AM-756 M etric conduit adaptor M20 x 1.5 to 1/2 in. NPT (two per package). AM-758 Universal short “U” mounting bracket. AM-759 Universal Long “U” mounting bracket. AM-760 Universal slotted “L” mounting bracket. AM-761 Replacement 7-inch anti-rotation bracket. AM-762 Replacement 9-inch anti-rotation bracket. AM-763 1 /8 inch hex crank for manual override. AV-602 Vx-7xxx 1/2 to 2 in. valve linkage. AV-607 Vx-9xxx 2-1/2 to 4 in. valve linkage.
Mounting bracket. Mounting bracket. Mounting bracket.
round shafts, 3/8 t o 9/16 in. square shafts. AM-753 clamps required).
Crank arm kit.
MA40-704x
AM-673 M ounting bracket. AM-674 Weather shield. AM-675 Weather shield base. AM-676 Universal shaft extension, approximately 9-1/2 in. long (242 mm) for use on 3/8 to 11/1 6 in. (10 to 17 mm)
round shafts, 3/8 t o 9/16 in. square shafts. (AM-753 clamps required). AM-709 Position indicator and stroke limiter. AM-710 V-clamp for 3/4 in. round shafts. AM-711 Crank arm adaptor kit.
e
AM-712
e
AM-713 AM-714 Weather shield
e
AM-715
Crank arm adaptor kit
Bracket.
Crank arm adaptor kit. AM-717 Replacement universal clamp AM-756 M etric conduit adapter AM-761 Replacement 7-inch anti-rotation bracket. AM-762 Replacement 9-inch anti-rotation bracket. AV-605 Vx-7xxx 1/2 to 2 in. valve linkage.
a
Drill appropriate mounting holes where n eeded.
b
AM-693 crank arm kit required.
c
Cannot be used with Mx41-634x or Mx40-717x series actuators.
d
The large “C”-shaped clamps included in AM-693 crank arm kit are required for mounting the actuator. Drill appropriate mounting holes where needed.
e
Use the self-tapping screws and flat washers provided in kit to mount actuator.
f
AM-692 V-bolt kit requ ired.
F-27382-1 © Copyright 2006 TAC. All Rights Reserved. 81
MA40-704x Series, MA41-707x Series, and MA41-715x Series
Typical Applications
24 Vac Transformer
or 22-30 Vdc
Line
Volts
1
SPST Control Contact
120 Vac or
24 Vac
230 Vac
L1 N
L2 H
1
Voltage Wire 1 Wire 2
120 Vac White Black
230 Vac Light Blue Brown
Black
Red
Wire No. 1
Wire No. 2
Common
Hot (+DC)
Green/Yellow
Common
Hot
Green/Yellow
MA41-7153
MA41-7073 MA41-7153-502 MA41-7073-502
2
MA41-7150 MA41-7151 MA41-7070
MA41-7071 MA41-7150-502 MA41-7151-502 MA41-7070-502 MA41-7071-502
2
Optional Auxiliary
Switches
Orange
Violet
Yellow
Orange/White
Violet/White
Yellow/White
1 Provide overload protection and disconnect as required.
2 Actuators may be wired in parallel. All actuator black
wires are connected to the transformer common and all red wires are connected to the hot lead. Power consumption must be observed.
3 For end position indication, interlock control, fan startup,
etc., MA41-7153-502 and MA41-7073-502 models incorporate two built-in auxiliary switches.
Com
N.C.
N.O.
Com
N.C.
N.O.
Aux Switches
MA41-7xxx-502
Aux Switch 1
Adjustable
Aux Switch 2
Figure 1 Typical Wiring Diagram for 24, 120, or 240 Vac Basic and Double Auxiliary Switch Models.
120 Vac, or
230 Vac
1
L1 N L2 H
Wire No. 1 Wire No. 2
Neutral
Hot
Green/Yellow
MA40-7040 MA40-7041
2
25 to 85˚
3
5˚ Fixed
120 Vac, or
230 Vac
1
Auxiliary Switch 1
Figure 2 Typical Wiring Diagram for 120 Vac or 230 Vac Basic and Single Auxiliary Switch Models.
L1 N L2 H
Wire No. 1 Wire No. 2
Orange
Violet
Yellow
Neutral
Hot
Green/Yellow
COM.
N.C.
N.O.
MA40-7040-501 MA40-7041-501
2
0 to 1 Scale
Adjustable
3
1 Provide overload protection and disconnect as
required.
2 Actuators may be wired in parallel. Power
consumption must be observed.
3 For end position indication, interlock control, fan
startup, etc., MA41-715x-502 and MA41-707x-502 models incorporate two built-in auxiliary switches. See Specifications section for details.
Voltage Wire 1 Wire 2
120 Vac White Black
230 Vac Light Blue Brown
82
© Copyright 2006 TAC. All Rights Reserved. F-27382-1
Loading...