Schneider Electric Erie PopTop Series Installation Instructions

Erie™ PopTop™ Series
Valve Bodies and Actuators
Installation Instructions
Product Description
Erie™ PopTop™ Series valve bodies and actuators provide easy installation for a variety of heating and cooling applica­tions. The valve’s actuator can be installed after the valve body has been installed onto the fan coil, baseboard or air handler. VS Series valves are available for low pressure steam applications. PopTop Series are two position spring return valves. When powered, the actuator moves to the desired position, tensing the spring return system. When power is removed the actuator retur ns to the normal posi­tion. PopTop Series two position spring return valves can be purchased with an optional built-in auxiliary SPDT end switch for interfacing or signaling; for example, zone pump burner control. Actuators are designed fror cycling applications (not constantly powered).
Specifications
Service Hot and chilled water models, up to
50% glycol. Steam models up to 15 psi
(both valve body and valve actuator must be rated for high temperature)
System Static Pressure Limits
Fluid/Ambient Temperature Limits
Close-off See Table 2
Seat Leakage ANSI class IV (0.01%) with pressure at
inlet (B-port/A-por t, if 3-way)
Body Forged brass
Stem Nickel-plated
Seat Brass
Paddle (VT series) (VS series)
Actuator Voltage
Power Requirements
24 Vac @ 50/60 Hz, 110 Vac @ 50 Hz,
120 Vac @ 60 Hz, 230 Vac @ 50 Hz,
240 Vac @ 60 Hz, 208 Vac @ 50/60 Hz,
400 psi (2758 kPa)
See Table 1
Buna N
Highly saturated nitrile
277 Vac @ 50/60 Hz
6.5 watts, 7.5 Va
VT/VS Series with General Close-Off Actuator
VT/VS Series with High Close-Off Actuator
Features
• Direct replacement for all existing two-position PopTop applications
• Hysteresis synchronous motor for long life
• Spring return operation provides a fail-safe
• Valve body rated for 400 psi static pressure
• Available in a variety of voltages
• Actuator mounts directly onto valve body without need for linkages or calibration
• Manual override lever (normally closed only)
• Actuator can be replaced without any tools, or removal of valve from system
• VS Series available for low pressure steam
Agency Listings UL873
CUL
European Com­munity Australia
Shipping Weight (Actuator/Valve Assembly)
Table 1: Valve Body and Actuator Models
Model Temperature Range
VTxxxx
VSxxxx
Axx3xxx
Axx4xxx
a
For steam applications both valve body and valve actuator must be rated for high temperature. Example: VS2213G14A020 = Assembly. VS2213 = Valve body. AG14A020 = Actuator.
Underwriters laboratories (File #E9429
Catagory Temperature Indicating and
Regulating Equipment).
UL Listed for use in Canada by
Underwriters Laboratory. Canadian
Standards C22.2 No. 24. EMC Directive
(89/336/EEC). Low Voltage Directive
(72/23/EEC).
This product meets requirements
to bear the RSM Mark according
to the terms specified by the Communications Authority under the Radio Communications Act of 1992.
2.25 lbs (1020 g).
32×…200°F (fluid) @ 104 °F (Ambient) (0…93°C @ 40°C)
32×250°F (fluid) @ 169 °F (Ambient) (0…121°C @ 76°C), and/or 15 PSI (103 kPa)
a
Steam
32×…200°F (fluid) @ 104 °F (Ambient) (0…93°C @ 40°C)
32×…250°F (fluid) @ 169 °F (Ambient) \(0… 121°C @ 76°C), and/or 15 PSI (103 kPa)
a
Steam
© 2016 Schne ider Ele ctric. All rights rese rved. All trademar ks are owned by Schneider El ectric Indust ries S AS or its a ffil iated companie s. April , 2019 tc Document Number: F-2649 6-10
Installation Instructions
(61 mm)
Accessories for Inverted Flare Connection Valves
3/4” inverted flare bodies accept the following adapters to copper pipe:
436-214-1 Union nut & elbow assembly, female for 1/2” (5/8” O.D.) copper, 15/16” long
436-220 Union nut & coupling assembly, female for 1/2” (5/8” O.D.) copper, 1-1/16” long
436-252 Union nut & coupling assembly, female for 3/4” (7/8” O.D.) copper, 1-27/32” long
436-229-3 Union nut & nipple assembly, male for 1/2” (5/8” O.D.) copper, 3” long
436-214-4 Union nut & elbow assembly, male for 1/2” (5/8” O.D.) copper, 1-15/16” long
436-256 Union nut & coupling assembly, female for 1” (1-1/8” O.D.) copper, 1-3/8” long
Table 2: Flow Coefficients and Maximum Close-Off Pressure Differentials
Valve Size Connection Type 2-way Cv (kv) 3-way Cv (kv) (G) Close-Off ∆P PSI
(kPa)
1/2" NPT, SW, Rp, SAE
3/4" IFL
1/2" NPT, SW, Rp, SAE
3/4" NPT, SW, IFL, Rp
1.0 (0.9) 1.5 (30) 60 (414) 75 (517)
2.5 (2.2) 3.0 (2.6) 40 (276) 50 (344)
1/2" NPT, SW, SAE, Rp
3.5 (3.0) 4.0 (3.4) 25 (172) 30 (208)3/4" NPT, SW, IFL, Rp
1" SW
3/4" NPT, SW, Rp
1" SW
5.0 (4.3) 5.0 (4.3) 20 (137) 25 (172)
3/4" NPT, SW, Rp 7.5 (6.5) 7.5 (6.5) 17 (117) 20 (137)
1" NPT, SW, Rp
1-1/4" SW
NPT - Threaded (female) SW - Sweat
8.0 (6.9) 8.0 (6.9) 17 (117) 20 (137)
IFL - Inverted Flare SAE - Society of Automotive Engineers Flare (male) Rp - “Metric” Threaded (female) G - General close off acutuator H - High close off actuator
(H) PSI Close-Off ∆P (kPa)
Table 3: Water Valve Sizing*
∆P 1.0 Cv 1.5 Cv 2.5 Cv 3.0 Cv 3.5 Cv 4.0 Cv 5.0 Cv 7.5 Cv 8.0 Cv
1 PSI
2 PSI
3 PSI
4 PSI
5 PSI
1.0 1.5 2.5 3.0 3.5 4.0 5.0 7.5 8.0
1.4 2.1 3.5 4.2 4.9 5.7 7.1 10.6 11.3
1.7 2.6 4.3 5.2 6.1 6.9 8.7 13.0 13.9
2.0 3.0 5.0 6.0 7.0 8.0 10.0 15.0 16.0
2.2 3.4 5.6 6.7 7.8 8.9 11.2 16.8 17.9
* Water capacity in gallons per minute (GPM)
Dimensions
General Close-Off High Close-Off
3-11/16” (94 mm)
3-1/4”
(83 mm)
1-1/8”
(29 mm)
2-3/8”
(61 mm)
3-3/16” (81 mm)
B-PORT
A A
© 2016 Schne ider Ele ctric. All rights rese rved. All trademar ks are owned by Schneider El ectric Indust ries S AS or its a ffil iated companie s. April , 2019 tc Document Number: F-2649 6-10
A-PORT
D
B 2-WAY
C 3-WAY
7/16”
(12 mm)
2.-3/8”
(61 mm)
2-7/16”
B-PORT
A A
3-11/16” (94 mm)
3-1/4”
(83 mm)
(32 mm)
1-1/4”
D
A-PORT
2-7/16”
(62 mm)
B 2-WAY
3-3/16”
(82 mm)
C 3-WAY
2 5/8”
(67 mm)
(14 mm)
9/16”
2-7/16”
(62 mm)