Schneider Electric ASCO 7000, ASCO 7ATB, ASCO 7ACTB, ASCO 7ADTB Installation Manual

Page 1
A
ASCO 7000 SERIES 7ATB, 7ACTB, 7ADTB Automatic Transfer & Bypass–Isolation Switches G, Q, S, & U design Installation Manual
381333-415 A 9/2016
An experienced licensed electrician must install
WARNING is used in this manual to warn of a hazardous situation which, if not avoided, could result in death or serious injury.
the ATB.
The Transfer Switch nameplate includes data for each specific 7000 Series ATB Use the switch only within the limits shown on this nameplate. A typical Catalog Number is shown below with its elements explained:
Nameplate
CAUTION is used in this manual to warn of a hazardous situation which, if not avoided, could result in minor or moderate injury.
Refer to the outline and wiring drawings provided with your 7000 Series ATB for all installation and connection details and accessories.
Refer to Group 5 Controller User’s Guide 381333–126 for ATS status display messages, time delays, pickup & dropout settings, and adjustments.
Rating Label
Each 7000 Series ATB contains a rating label to define the load and fault circuit withstand/closing ratings. Refer to the label on the Transfer Switch for specific values.
Do not exceed the values on the rating label. Exceeding the rating can cause personal injury or serious equipment damage.
typical 4000
Page 2
Installation Manual 7000 Series ATB, ACTB, ADTB
Table of Contents
Rating Label.............................................................................................................................................................. 1
Nameplate ................................................................................................................................................................ 1
Catalog Number Identification .................................................................................................................................. 3
Installation .............................................................................................................................................................. 4-7
Remove the Shipping Skid ....................................................................................................................................... 4
Supporting Foundation and Mounting ...................................................................................................................... 4
Mounting ................................................................................................................................................................... 4
Remove Shipping Brackets/Angles from the Transfer Switch .................................................................................. 4
Testing Power Conductors ....................................................................................................................................... 5
Connecting Power Conductors ................................................................................................................................. 5
Bus Connections ...................................................................................................................................................... 5
Harnesses ................................................................................................................................................................. 5
Harnesses ................................................................................................................................................................. 5
Engine Starting & Auxiliary Circuits .......................................................................................................................... 5
Functional Test ......................................................................................................................................................... 6
Functional Test – Voltage Checks ............................................................................................................................ 6
Functional Test - -Electrical Operation .................................................................................................................... 6
Testing & Service ...................................................................................................................................................... 8
Transfer Test ............................................................................................................................................................ 8
Preventive Maintenance ........................................................................................................................................... 8
Replacement Parts ................................................................................................................................................... 8
Manual Load Transfer .............................................................................................................................................. 8
Maintenance Handle ................................................................................................................................................. 8
Trouble-Shooting ...................................................................................................................................................... 9
Bypassing & Isolating ............................................................................................................................................. 10
Bypassing the ATS ................................................................................................................................................. 10
To Bypass Normal Source ...................................................................................................................................... 10
To Bypass Emergency Source ............................................................................................................................... 10
Isolating the ATS .................................................................................................................................................... 11
Return to Service .................................................................................................................................................... 13
Index .......................................................................................................................................................................... 15
2 381333-415 B
Page 3
7000 Series ATB, ACTB, ADTB Installation Manual
Catalog Number Identification
Typical 7000 Series G7ATB catalog no. for overlapping neutral, 3 pole, 4000 A, 480 V, in a Type 1 enclosure:
G 07A TB C 3 4000 N 5
Design prefix letter
G Q S U
Transition
Type
07A open 7AC closed 7AD delayed
Neutral Phase
A- solid B- switching C- overlapping* blank-none
* Overlapping neutral
not available for Q, S, & U-designs
Poles
single
2 3 three
Amperes
600
800 1000 1200 1600 2000 2600 3000
Voltage Controller
A 115 B 120 C 208 D 220 E 230 F 240 G 277 H 380
J 400 K 415 L 440 M 460 N 480 P 550 Q 575 R 600
4000
Status Lights
&
Engine
Control
Bypass Handle
Transfer Control
5 standard
if
5X
accessories ordered
& Lights
C
Enclosure
C type 1 F type 3R G type 4 L type 12
blanc – open type
Isolation
Handle
Group 5 Controller
Transfer Switch
Typical G7ATB with lower doors open (transfer switch shown)
381333-415 B 3
Page 4
Installation Manual Installation
INSTALLATION
The ASCO 7000 Series Automatic Transfer & Bypass–Isolation Switch (ATB) consists of an upper bypass–isolation switch, a lower transfer switch, a monitoring and transfer controller, and door–mounted controls. The ATB is factory wired and tested. Installation requires removal of the shipping skid then securing the enclosure to the supporting foundation.
Remove the Shipping Skid
Open the front lower door and remove the two front lag screws securing the enclosure to the wood skid. Next remove the rear lower panel and remove the two rear lag screws securing the enclosure to the wood skid.
Supporting Foundation and Mounting
The supporting foundation for the enclosure must be level and straight. Allow at least 35 inches in front of the enclosure for draw out of the Transfer Switch. Refer to the enclosure outline drawing included with the 7000 Series ATB for all mounting details including door opening space.
To prevent serious damage, remove three or four shipping brackets or L–angles from the Transfer Switch carriage. Do not turn the Isolation Handle until they are removed!
If bottom cable entry is used, the foundation must be prepared so that the conduit stubs are located correctly. Refer to the appropriate enclosure outline drawing for specified cable entrance area and location. Provide cable bending space and clearance to live metal parts. When a concrete floor is poured, use interlocking conduit spacer caps or a wood or metal template to maintain proper conduit alignment.
Mounting
Refer to the enclosure outline drawing furnished with this switch and mount the 7000 Series ATB according to the details and instructions shown on the drawing.
Remove Shipping Brackets / Angles
from the Transfer Switch
Open the lower front door(s). The Transfer Switch carriage is secured to the frame for shipment. Remove the three or four shipping brackets or L– angles: (1 upper left, 1 upper right, and 2 lower).
remove 3 or 4 shipping brackets ( L–angles)
Figure 1. 600–3000 A remove shipping brackets.
remove 2 upper shipping brackets
remove 2 lower shipping brackets
Figure 2. 4000 A remove four shipping brackets.
4 381333-415 B
Page 5
Installation Installation Manual
Bus Connections
De–energize the conductors before making any line or auxiliary circuitry connections. Be sure that Normal and Emergency line connections are in proper phase rotation. Place engine generator starting control in the OFF position. Make sure engine generator is not in operation.
If bus connection is used, use SAE grade 5 hardware to connect bus to appropriate terminal plates on bypass switching device. Wipe off bus surfaces before they are joined. If bus is dirty, gently clean surfaces with a non-flammable solvent. Avoid touching cleaned surfaces.
Testing Power Conductors
Do not connect the power conductors to the ATB until they are tested. Installing power cables in conduit, cable troughs, and ceiling-suspended hangers often requires considerable force. The pulling of cables can damage insulation and stretch or break the conductor’s strands. For this reason, after the cables are pulled into position, and before they are connected they should be tested to verify that they are not defective or have been damaged during installation.
Protect the switch from construction grit and metal chips to prevent malfunction or shortened life of the ATB switch.
Connecting Power Conductors
A Wiring Diagram is furnished with the ATB. All wiring must be made in accordance with the local codes. After the power cables have been tested, connect them to the appropriate terminal lugs on the Bypass Switch as shown on the wiring diagram provided with this ATB. Make sure that the lugs provided are suitable for use with the cables being installed. Standard terminal lugs are solderless screw type and will accept the wire sizes listed on the drawings provided with the ATB. Be careful when stripping insulation from conductors; avoid nicking or ringing the conductor. Remove surface oxides from conductors by cleaning with a wire brush. Follow conductor manufacturer’s instructions when aluminum conductor is used. Apply joint compound to conductor, then carefully wipe away excess compound. Tighten the cable lugs to the torque specified on the rating label.
Do not breathe cleaning solvent vapors.
Use SAE grade 5 hardware and tighten the bolted joints to the torque specified in Table A.
The reliability of the connection depends on how clean and how tight the joint is.
Table A. Tightening torque values for bolted joints.
Bolt Diameter
(Grade 5 hardware)
in inches
5/16 12
3/8 20 1/2 50 5/8 95
Recommended
Tightening Torque
in foot pounds
Harnesses
All internal connections are made at the factory. The bypass switch, transfer switch, and control panel are joined together by an interconnecting wire harness. The disconnect plugs are already engaged on enclosed switches. For open–type switches, the plugs must be engaged after installation is completed. Align harness plugs with sockets in the control and push them together until they are secure.
Controller Ground
A grounding wire must be connected to the controller’s lower left mounting stud. Because the controller is mounted on the enclosure door, a conductive strap must be used between the enclosure and the door. This connection provides proper grounding which does not rely upon the door hinges.
Engine Starting Contacts
and Auxiliary Circuits
Be sure that the Normal and Emergency power connections are in proper phase rotation.
381333-415 B 5
The engine control contact signal connections and auxiliary circuits are located on terminal block TB as shown on the Wiring Diagram provided with the ATB. Connect the signal wires to the appropriate terminals.
Page 6
Installation Manual Installation
1 Close the normal source circuit
breaker. The Transfer Switch
Connected To Normal and the
Normal Source Accepted lights
should come on.
2 Use an accurate voltmeter to
observe these lights
Figure 3. Standard controls and indicators.
Functional Test
Read all instructions on the Wiring Diagrams and labels affixed to the ATB. Note the control features that are provided and review their operation before proceeding. After installing the ATB check the following: – Bypass Handle should be in the OPEN position. – Isolation Handle should be in the CLOSED
position.
– Transfer switch should be in NORMAL position.
(For ACTB and ADTB the CN transfer switch should be CLOSED and the CE transfer switch should be OPEN).
If handles are not in correct positions, follow instructions for Bypassing and Isolating the automatic transfer switch (pages 10-12). Do not force the handles. Electrical interlocks prevent a wrong sequence of operation.
check phase to phase and phase
to neutral voltages present at the
transfer switch normal source
terminals.
3 Close the emergency source
circuit breaker. Turn the Engine
Control switch to Run to start
the generator. The Transfer
Switch Connected To Normal &
Emergency Source Accepted
lights should come on.
4 Use an accurate voltmeter to
check phase to phase and phase
to neutral voltages present at the
transfer switch emergency
source terminals.*
C
B
5 Use a phase rotation meter to
check phase rotation of
emergency source; it must be
the same as the normal source.
6 Turn Engine Control switch to
Auto to stop the generator. The
Emergency Source Accepted
light should go off. Then put the
starting control selector switch
(on generator set) in automatic
position. Close enclosure door.
A
2 – Electrical Operation
This procedure checks electrical operation of the ATS.
1 – Voltage Checks
First check nameplate on transfer switch; rated voltage must be the same as normal and emergency line voltage.
Use extreme caution when using a meter to measure voltages. Do not touch power terminals; shock, burns, or death could result! Perform steps 1–6 at the right. Observe the status lights. See Figure 3.
Black square means light is on.
White square means light is off.
* If necessary, adjust voltage regulator on generator per the manufacturer’s recommendations. The ATB will respond only to rated voltage specified on the nameplate.
Now continue to 2 – Electrical Operation.
Be sure to close the enclosure doors before proceeding to prevent person injury in case of electrical system fault.
Transfer Test
The ATS should be bypassed and isolated. Follow instructions for Bypassing and Isolating the automatic transfer switch (pages 10-12). Both normal and emergency sources must be available and the emergency source generator (if used) must be capable of being started; put engine starting control in
automatic position. The Transfer Switch Connected to Normal light and the Normal Source Accepted light
should be on.
6 381333-415 B
Page 7
Installation Installation Manual
7ACTB alarm lights (see troubleshooting)
7ACTB buttons
7ADTB light is on when load is disconnected
observe these lights
Figure 5. 7ACTB controls. Figure 6.
operate this switch
7ADTB controls
1 The Transfer Switch Connected to
Normal and Normal Source Accepted lights should be on.
Load
Disconnect
Active
Figure 4. Standard controls and indicators.
(Transfer Test continued from page 6)
1. Turn the Isolation Handle counterclockwise (approximately 12 turns) until the window shows TEST position.
NOTE: The engine generator may be signaled to start while turning the Isolation Handle. If emergency source is available, the ATS may operate to the emergency position. If it does, operate Retransfer Delay Bypass switch.
2 Perform steps 1–5 at right. Observe the status
lights.
Black square means light is on.
 White square means light is off.
7ACTB
The load is transferred via overlap (closed) transition. Transfer switch CE closes, then transfer switch CN opens. The operation is reversed for retransfer back to normal. If you do not want closed–transition transfer, press the Closed Transition Bypass button (Figure 5) while the controller display shows Waiting for In–Sync. This action causes open–transition (momentary load interruption) transfer to the opposite source, if conditions permit.
7ADTB
The load is disconnected and light (Figure 6) comes on during the delayed–transition transfer delay.
3. Turn the Isolation Handle clockwise (approximately 12 turns) to the CONN (connected) position.
2 Turn and hold Transfer Control
switch clockwise to Transfer Test until the engine starts and runs (within 15 sec.). The Emergency Source Accepted light should come on.
3 Transfer switch will operate to the
Emergency position after Feature 2B time delay. The Transfer Switch Connected to Emergency light should come on and the
Transfer Switch Connected to Normal light should go off (7ACTB
you might see and hear the brief overlap transfer).
4 Transfer switch will operate back
to Normal position after Feature 3A time delay. For immediate retransfer turn Transfer Control counterclockwise to Retransfer
Delay Bypass. The Transfer Switch Connected To Normal light should come on; Transfer Switch Connected to Emergency light
should go off.
5 The engine–generator will stop
after the Feature 2E time delay (unloaded running engine cooldown). The Emergency Source Accepted light should go off.
This completes the Functional Test of the ATB.
Load
Disconnect
Active
Load
Disconnect
Active
Load
Disconnect
Active
Load
Disconnect
Active
4. Push in the Bypass Handle and turn it counterclockwise until the OPEN indicator shows green.
381333-415 B 7
Page 8
Installation Manual Testing & Service
TESTING & SERVICE
TRANSFER TEST
Test the Automatic Transfer Switch portion of the 7000 Series ATB at least once a month. This procedure checks the electrical operation of the Transfer Switch and Controller. Turn the Engine Control switch to Auto and put the engine–generator starting control (at the engine–generator set) in automatic mode.
In the test the generator will start, the load will be transferred to the Emergency source, then back to the Normal source. An interruption to the load will occur, unless the Transfer Switch contacts are bypassed before the test. See pages 10 and 1 for bypassing and isolating instructions if no interruption of load is required.
Be sure to close the enclosure doors before proceeding to prevent person injury in case of electrical system fault.
Perform the Electrical Operation – Transfer Test procedure on pages 6 and 7.
PREVENTIVE MAINTENANCE
Reasonable care in preventive maintenance will insure high reliability and long life for the 7000 Series ATB. An annual preventive maintenance program is recommended.
ASCO Services, Inc. is ASCO Power Technologies’ national service organization. They can be contacted at 1-800-800-2726 for information on preventive maintenance agreements
YEARLY INSPECTION
Hazardous voltage capable of causing shock, burns, or death is used in this switch. Deenergize both Normal – Emergency power sources before performing inspections!
Clean the ATS enclosure. Brush and vacuum away any excessive dust accumulation. Remove any moisture with a clean cloth.
Check the transfer switch contacts. Remove transfer switch barriers and check the condition of the contacts. Replace contacts when pitted or worn excessively. Reinstall the barriers carefully.
Maintain transfer switch lubrication. If switch is subjected to severe dust or abnormal operating conditions, renew factory lubrication on all movements and linkages. Re-lubricate solenoid operator if TS coil is replaced. Don’t use oil; order lubrication kit 75-100.
Check all cable connections & retighten them.
REPLACEMENT PARTS
Replacement parts are available in kit form. When ordering parts provide the Serial No., Bill of Material No. (BOM), and Catalog No. from the transfer switch nameplate. For service call ASCO Services at 1–800– 800–2726; you will be put in contact with your local ASI office.
MANUAL LOAD TRANSFER
This procedure manually transfers load to other source if the Transfer Switch or Control Panel are out of service.
Close enclosure doors to prevent personal injury in case of electrical system fault.
1. Be sure that the Bypass Handle is CLOSED on either Emergency or Normal (see page 10).
2. Be sure that the Isolation Handle is in the TEST or ISOLATE position (see page 11).
3. Turn the Bypass Handle counterclockwise to OPEN the Bypass Switch. Then Bypass to the other source (see page 10).
MAINTENANCE HANDLE
Bypass and isolate the Transfer Switch before using the maintenance handle! See pages 10 and 11. Remove the hub and handle after using them and store on frame.
for 7ATB
Turn counterclockwise to Emergency.
Turn clockwise to Normal.
slide hub onto shaft
for 7ACTB & 7ADTB
slide hub onto shaft & insert pin
Pull out shaft to operate Emergency contacts.
Turn counterclockwise to OPEN contacts.
Turn clockwise to CLOSE contacts.
Push in Normal contacts.
Figure 7. Maintenance handle and hub.
insert handle into hole
Grasp handle firmly
shaft to operate
8 381333-415 B
Page 9
Troubleshooting Installation Manual
g
y
)
g
g
g
A
g
TROUBLESHOOTING
Note any optional accessories that may be furnished on the ATB and review their operation. Refer to any separate drawings and/or instructions that may be packed with the ATB.
Table B. TroubleShooting Checks.
PROBLEM CHECK IN NUMERICAL SEQUENCE
1 OPERATION 2 GEN-SET 3 VOLTAGE
Engine–generator set does not start when the Transfer Control switch is turned and held in Transfer Test position or when normal source fails. Transfer switch does not transfer the load to the emergency source after the engine–generator set starts.
Transfer switch does not transfer the load to normal source when normal returns or when the Transfer Control switch is released.
Gen. does not stop after load retransfer to normal source.
7ACTB
Failure to Synchronize
li
ht comes on.
7ACTB
Extended Parallel Time
li
ht comes on.
7ACTB
TS Locked Out
li
ht comes on.
7ADTB
Load Disconnect Active
li
ht comes on.
Hold Transfer Test switch 15 seconds or the outage must be long enough to allow for Feature 1C time delay plus engine cranking and startin Wait for Feature 2B time delay to time out.
Wait for Feature 3A time delay to time out.
Wait for Feature 2E time delay to time out.
Conditions of Normal or Emergency Sources not suitable for closed transition transfer. Recheck voltage and frequency of both sources. Press Alarm Reset pushbutton. CN and CE contacts are closed longer than setting in the controller. Open the disconnected source circuit breaker, then call your nearest ASCO Service Center for assistance. Transfer lockout operation has occurred; transfer switch is disabled from automatic operation. Open the disconnected source circuit breaker, then call your nearest
SCO Power Services, Inc for assistance. Delayed transition transfer operation. If load is disconnected longer than the setting in Group 5 controller (see User’s Guide 381333–126), then contact ASCO Power Services, Inc for assistance.
.
Hazardous voltage capable of causing shock, burns, or death is used in this switch. Do not touch the power or load terminals of the bypass switch or transfer switch!
Starting control must be in the automatic position. Batteries must be charged and connected. Check wiring to engine starting contacts. Generator output circuit breaker must be closed. Generator frequency must be at least 95% of nominal (57 Hz for a 60 Hz s
stem.) *
Voltmeter should read at
Starting control must be in the automatic position.
Voltmeter should read at least 90% of nominal phase to phase voltage between terminals EA and EC (or EL1 and EL2 for 2 pole switches)*
least 90% of nominal phase to phase voltage between terminals NB and NC, NC and NA, and NA and NB (or NL1 and NL2 for 2 pole switches
.
* These are factory settings. Refer to Controller User’s Guide.
If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies sales office or ASCO Power Services, Inc at 1–800–800–2726. Furnish the Serial No. and Catalog No. from the transfer switch nameplate.
381333-415 B 9
Page 10
Installation Manual Bypassing & Isolating
BYPASSING & ISOLATING
BYPASSING THE ATS*
This procedure explains how to Bypass the closed automatic transfer switch contacts. Bypassing is required before the ATS can be tested or isolated. The Bypass Handle must be in the OPEN position (green indicator) and the Isolation Handle must be in the CLOSED position (window). See Figures 8, 9 and
10.
Indicator shows: green
ATS is not
OPEN when the
bypassed.
You can only bypass to the same source that the Transfer Switch is connected. Solenoid interlock prevents incorrect operation.
1 .Observe which Transfer Switch Connected To light
is on (Normal or Emergency) on the door. This is the position of the automatic transfer switch.
2.Bypass to the same source as connected to transfer switch as follows (select Normal or Emergency).
Indicator shows: yellow
when ATS is bypassed to Emergency or yellow
ATS is bypassed to Normal Source.
EMERGENCY CLOSED
NORMAL CLOSED when
To Bypass Normal push in handle all the way & turn it clockwise.*
Figure 8. Bypass Handle and position indicators.
To Bypass Normal Source*
(Load connected to Normal Source)
The Transfer Switch Connected To Normal light is
on and Transfer Switch Connected To Emergency
light is off.
Push in* the Bypass Handle all the way, then turn it clockwise until Bypass Switch Position shows CLOSED on NORMAL (yellow indicator). The red light Unit Not In Automatic will flash.
Push in Bypass Handle & turn it clockwise.
Bypass Switch
E
L
To Bypass Emergency pull out han dle all the way & turn it clockwise.*
To Bypass Emergency Source*
(Load connected to Emergency Source)
The Transfer Switch Connected To Emergency light
is on and Transfer Switch Connected To Normal
light is off.
Pull out* the Bypass Handle all the way, then turn it clockwise until Bypass Switch Position shows CLOSED on EMERGENCY (yellow indicator). The red light Unit Not In Automatic will flash.
Pull out Bypass Handle & turn it clockwise.
Bypass Switch
E
L
N
ATS
Figure 9. Bypass to Normal.
The automatic transfer switch can now be put in the TEST or OPEN position. See ISOLATING on page 11.
* NOTE: When Accessory 66A (reversed Normal & Emergency connections) is specified,
the handle push–pull operation is reversed. Follow instructions on the door.
10 381333-415 B
Figure 10. Bypass to Emergency.
ATS
N
Page 11
Bypassing & Isolating Installation Manual
ISOLATING THE ATS
Isolating is required before any service work can be performed on the automatic transfer switch (ATS). Refer to Figures 11,12, 13, 14 and 15..
1. Bypass the closed automatic transfer switch contacts. See BYPASSING on page 10.
Align the position indicator. Do not leave the handle in an intermediate position.
2. Turn the Isolation Handle counterclockwise (approx. 16 turns, approx. 12 turns for 4000A) until window shows TEST. The ATS can be tested now without load interruption (see page 8).
Bypass Switch
Turn crank counter clockwise until window shows TEST.
E
L
position. The transfer switch can also be removed for easier maintenance operations.
position
CONN TEST ISOLATE
counterclockwise – draws out transfer switch
window
unfold crank
Figure 13. Isolation Handle.
In the TEST position the transfer switch solenoid operator circuit is energized through secondary disconnect contacts.
Hazardous voltage capable of causing electrical shock, burns, or death; do not touch any control circuit terminals.
Figure 11.
Figure 34.
CONNECTED to
CONNECTED to
TEST position.
TEST position.
Automatic Transfer Switch
N
3. Continue turning the Isolation Handle counterclockwise (approx. 7 turns, approx. 8 turns for 4000 A) until the window shows ISOLATE.
Bypass Switch
E
Turn crank counter clockwise until
L
window shows ISOLATE.
Figure 12
Figure 35.
TEST to
TEST to
ISOLATE position.
ISOLATE
position.
Automatic Transfer Switch
N
4. Open the lower enclosure doors(s). Pull out the side rail carriage. On 4000 A extend two support legs. See Figures 14 and 15. Then roll out the transfer switch. It can be safely inspected in this
Figure 14. 600–3000 A transfer switch
isolated and pulled out for inspection.
See page 8 for maintenance handle use. Lifting yokes are available to facilitate lifting transfer switch by using an overhead crane or similar equipment.
600–3000 A transfer switches weigh 350-450 lbs.; use lifting yoke kit 607064 or other device capable of lifting this weight to avoid personal injury or equipment damage.
Continued on next page
381333-415 B 11
Page 12
Installation Manual Bypassing & Isolating
grasp two handles
locking pin
with clevis pin
rail support
left support leg
adjust length to touch floor
4000 A transfer switch draw–out procedure
1. Bypass and Isolate the ATS, then open both lower doors.
2. Pull out the rail support carriage all the way.
3. Remove left & right clevis and locking pins, drop two support legs, reinstall locking and clevis pins (to lock in place), and adjust both leg lengths to extend to the floor.
4. Stand directly in front of transfer switch. Grasp both handles, and pull straight out (detents on the rails require high initial force to overcome resistance).
carriage
Figure 15. 4000 A transfer switch isolated and pulled out for inspection.
locking pin
with clevis pin
right support leg
adjust length to touch floor
For the 4000 A transfer switch, to avoid personal injury and equipment damage, two support legs must be extended as shown in Figure 15. Substantial initial force is required to pull out the
The 4000 A transfer switch weighs approx. 600 lb.; use lifting yoke 835745–001 or other device capable of lifting this weight to avoid personal injury or equipment damage
transfer switch (there are detents on rail).
12 381333-415 B
Page 13
Bypassing & Isolating Installation Manual
 to 
y By
(
g
RETURN TO SERVICE
This procedure explains how to return the automatic transfer switch (ATS) to service after inspection and maintenance. Observe the Bypass Switch Position indicator and lights). Refer to Figures 14 through 18.
1. Slide the transfer switch (ATS) into the enclosure
(isolation contacts facing inward) until its crank pins engage the latch plates on both sides. Substantial force is required to overcome detents on the rails. Next push in side rail carriage. On 4000 A first retract the two legs and lock them in place. See Figures 14 and 15. Then close enclosure door(s).
Close the enclosure door to prevent personal injury in case of electrical system fault.
Align the position indicator. Do not leave the handle in an intermediate position.
position
CONN TEST ISOLATE
window
Solenoid interlock prevents closing the isolation contacts until the ATS is in the same position as the Bypass Switch.
3. Observe which Bypass Switch Position indicator is black (NORMAL or EMERGENCY) at Bypass Switch Handle. This shows the source connected to the load.
4. Observe which Transfer Switch Connected To light is on (Normal or Emergency) on the door. This is the position of the Transfer Switch. If it is not in the same position as the Bypass Handle change the position of the Transfer Switch as follows:
To change the position of transfer switch
Operate to NORMAL Operate
Turn Transfer Control switch to Retransfer
Dela
pass.
Connected To Normal
li
ht should come on.
Turn Transfer Control switch to Transfer Test
hold 15 seconds).* Connected To Emergency light should comes on.
EMERGENCY
* If Feature 2B time delay is used, there will be a delay before transfer to Emergency.
With Normal available, the ATS will not stay in the emergency position unless Feature 3A time delay is used (at least 30 seconds).
unfold crank
clockwise – draws in the Transfer Switch
Figure 16. Isolation Handle.
2. Turn the Isolation Handle clockwise (approx. 7 turns, approx. 8 turns for 4000 A) until the window shows TEST. The ATS can be tested now without load interruption (see page 8).
Bypass Switch
E
Turn crank clockwise
L
until window shows TEST.
N
ATS
Figure 17. ISOLATE to TEST position.
Do not close the isolation contacts unless the Transfer Switch (ATS) and Bypass Switch are in the same position!
5. .When the transfer switch is in the same position as the Bypass Switch handle, continue turning the Isolation Handle clockwise (approx. 16 turns, approx. 12 turns for 4000 A) until the window shows CONN (connected).
Bypass Switch
Turn crank clockwise until window shows CONN (connected).
Figure 18. TEST to CONNECTED position.
ATS
Continued on next page
E
L
N
381333-415 B 13
Page 14
Installation Manual Bypassing & Isolating
RETURN TO SERVICE continued*
This procedure explains how to return the Bypass Switch Handle to the OPEN position. The Bypass Handle must be in the CLOSED position (yellow indicator on NORMAL or EMERGENCY) and the Isolation Handle must be in the TEST position (window). If the handles are not in these positions, refer to Return to Service on page 13. See Figures 19, 20 and 21.
Indicator shows: green
ATS is not
To un–Bypass Normal push in handle all the way & turn it counterclockwise.*
OPEN when the
bypassed.
Figure 19. Bypass Handle and position indicators.
You can only bypass to the same source that the ATS is connected. Solenoid interlock prevents incorrect operation.
1. Observe which Bypass Switch Position indicator is yellow (NORMAL or EMERGENCY) at the Bypass Switch Handle. This indicates the source connected to the load.
2. Un–Bypass to same source as the Bypass Switch Position as follows (select Normal or Emergency).
Indicator shows: yellow
when ATS is bypassed to Emergency or yellow
bypassed to Normal Source.
To un
handle all the way & turn it counterclockwise.*
EMERGENCY CLOSED
NORMAL when ATS is
Bypass Emergency pull out
To Un–Bypass Normal Source*
(Load connected to Normal Source)
The Transfer Switch Connected To Normal light is
on and Transfer Switch Connected To Emergency
light is off.
Push in* the Bypass Handle then turn it counterclockwise until Bypass Switch Position shows OPEN (green indicator). The Unit Not in Automatic light should be off.
Push in Bypass Handle & turn it counter clockwise.
Bypass Switch
E
L
N
To Un–Bypass Emergency Source*
(Load connected to Emergency Source)
The Transfer Switch Connected To Emergency light
is on and Transfer Switch Connected To Normal
light is off.
Pull out* the Bypass Handle then turn it counterclockwise until Bypass Switch Position shows OPEN (green indicator). The Unit Not in Automatic light should be off.
Pull out Bypass Handle & turn it counter clockwise.
Bypass Switch
E
L
N
ATS
Figure 20. Un–Bypass Normal.
The Automatic Closed–Transition Transfer & Bypass–Isolation Switch should be left in this position.
Figure 21. Un–Bypass Emergency.
ATS
When Accessory 40*B (reversed Normal & Emergency connections) is specified, the handle push–pull operation is reversed. Follow instructions on the door.
14 381333-415 B
Page 15
Installation Manual Index
A
Alarm Reset pushbutton, 7, 9
ASCO Power Services Inc. customercare@ascopower.com 800–800–2726(ASCO)
auxiliary circuits, 5
B
bus connections, 5
bypassing the ATS, 10
harness, 5
HELP customercare@ascopower.com 800–800–2726(ASCO)
inspection, 10
installation, 4 through 7
isolating the ATS, 11
C
catalog number, 3
cleaning, 8
closed–transition transfer, 7
connections line, 5
controller see Controller User’s Guide
381333–126
D
delayed–transition transfer, 7
drawout, transfer switch, 11, 12
lights, 1–3, 1–4
Load Disconnect Active
7, 9
lubrication, 8
maintenance, preventive, 8
maintenance handle, 9
warning, 9
manual load transfer, 8
warning, 9
E
electrical operation, 6, 7
Emergency Source Accepted light, 6, 7
Engine Control selector switch
Auto position, 8
engine starting contacts, 5
Extended Parallel Time light, 7, 9
F
Failure to Synchronize light, 7, 9
foundation, 4 frequency, generator, 9 functional test, 6, 7
nameplate, cover Normal Source Accepted light, 6
operation
electrical, 7
manual, 9
warning, 9
parts, 8
phase rotation check, 7
preventive maintenance, 8
problem, 9
INDEX
H
I
L
M
N
O
P
light,
R
rating label, cover
removal of shipping angles, 4
removal of shipping skid, 4
replacement parts, 8
return to service, 13
S
service ASCO Power Services, Inc., 8 customercare@asco.com 800–800–2726(ASCO)
settings see Controller User’s Guide
381333–126
shipping angles, 4 warning, 4
shipping skid, 4
support legs, 12
T
test, functional, 6, 7
testing power cables, 5
time delays, 8 see Controller User’s Guide
TS Locked Out light, 7, 9
Transfer Control selector switch Retransfer Delay Bypass, 7 Transfer Test, 7
Transfer Switch Connected To Emergency light, 7
Transfer Switch Connected To Normal light, 7
transfer test, 6, 7, 8
transfer to emergency, 7, 8
transfer to normal, 7, 8
troubleshooting, 9
V
voltage checks, 6
voltage, pickup and dropout settings see Controller User’s
Guide
381333-415 B 15
Page 16
Printed in U.S.A.
ASCO Power Technologies 160 Park Avenue Florham Park, NJ 07932-1591 USA Phone: 1 800 800-2726 (ASCO) for sales or service
www.ascopower.com
©2016 ASCO Power Technologies. All Rights Reserved
Loading...