Schneider UPS User Manual

Schneider UPS Monitoring
Software
User’s Manual
Management Software for Uninterruptible Power Supply Systems
1. SchneiderUPS Overview ..................................................................................... 4
1.1. Introduction ...................................................................................................... 4
1.2. Structure.............................................................................................................. 4
1.3. Features ............................................................................................................... 5
2. SchneiderUPS Install and Uninstall ............................................................. 5
2.1. System requirement ..................................................................................... 5
2.2. Software Install .............................................................................................. 6
2.3. Software Uninstall ....................................................................................... 10
3. Service Tray Application .................................................................................. 10
3.1. Start Monitor ................................................................................................... 10
3.2. Stop Monitor .................................................................................................... 11
3.3. SNMP Manager ............................................................................................... 11
3.3.1. SNMP Device List ................................................................................. 12
Add ........................................................................................................................ 12
Delete .................................................................................................................. 12
SNMP Status .................................................................................................... 13
Reset .................................................................................................................... 13
Use system time ............................................................................................ 16
3.3.2. Function Menu ....................................................................................... 16
3.3.2.1. System .............................................................................................. 16
3.3.2.2. Settings ............................................................................................ 16
3.3.2.3. Language ........................................................................................ 22
3.4. Https .......................................................................................................................... 24
4. SchneiderUPS GUI ............................................................................................. 26
5. SchneiderUPS Menu ............................................................................................ 27
5.1. Configuration .................................................................................................. 27
5.1.1. Password Setting ................................................................................. 27
5.1.2. Group area ............................................................................................... 28
5.1.3. UPS setting .............................................................................................. 29
5.1.4. SMS .............................................................................................................. 30
5.1.5. E-mail.......................................................................................................... 31
5.1.6. Load configuration .............................................................................. 32
5.1.7. Event action ............................................................................................ 34
5.1.8. Com. Port Plug And Play Setting ................................................ 36
5.1.9. Log setting ............................................................................................... 36
5.1.10. EMD Manager ...................................................................................... 37
5.1.11. Modbus communication setting ............................................... 39
5.2. Schedule ............................................................................................................ 40
5.2.1. Scheduled on/off ................................................................................. 40
5.2.2. Scheduled battery self-test ........................................................... 42
5.2.3. Wake on LAN schedule ..................................................................... 43
5.3. View ...................................................................................................................... 43
5.3.1. Centralized monitoring .................................................................... 43
5.3.1.1. Status ............................................................................................. 46
5.3.1.2. Basic information .................................................................... 48
5.3.1.3. Parameters setting ................................................................. 49
5.3.1.4. Real-time control ..................................................................... 51
5.3.1.5. Purchasing information ....................................................... 51
5.3.2. History ........................................................................................................ 52
5.3.2.1. Event Log...................................................................................... 52
5.3.2.2. Event Statistics ......................................................................... 53
5.3.2.3. Data ................................................................................................. 54
5.3.2.4. Diagram ......................................................................................... 55
5.3.2.5. EMD Logs ...................................................................................... 56
5.4. Format ................................................................................................................. 57
5.4.1. Temperature Unit ................................................................................ 57
5.4.2. Date Format ............................................................................................ 57
5.5. Language ........................................................................................................... 58
5.6. Help ...................................................................................................................... 58
5.6.1. About........................................................................................................... 58
5.6.2. Online help .............................................................................................. 58
1. SchneiderUPS Overview
1.1. Introduction
Schneider UPS is an advanced UPS management software which is perfect
for home users and enterprises. It can monitor and manage from one to
multiple UPSs in a networked environment including LAN, INTERNET and
RS485-based networks. Integrated with Shutdown Wizard, it can not only
prevent data loss from power outage and safely shutdown systems, but also
store programming data and scheduled shut down UPSs. All UPS working
data and event records can be kept in local database systems.
1.2. Structure
SchneiderUPS includes monitor service, WEB service and tray service.
Monitor service: It is the core of SchneiderUPS software. Monitor service
automatically finds UPSs in the networks, stores UPS working data and
event information. It will communicate with the UPS, record events,
notify users with events, and execute commands according to the users’
requests.
WEB service: It offers Http or Https service for local or remote users.
Users can manage and monitor UPSs for real-time status, information
and modify UPS setting parameters via browser such as IE and Firefox.
Tray service: It is a management tool for SchneiderUPS software. It
includes start monitor, stop monitor, SNMP manager and so on.
1.3. Features
Centralized control and monitor up to 1000 UPSs via SNMP or Modbus
networks.
Offers WEB service to allow remote monitoring service via Intranet or
Internet.
Offers quick overview for UPS monitoring in Text and Graphic view. Offers user-customized background picture for graphic view with simple
drag and drop.
Scheduled UPS on/off, battery test, and scheduled wake on LAN
programs.
2. SchneiderUPS Install and Uninstall
2.1. System requirement
1 GB physical memory at least (2 GB is recommended) 2 GB hard disk space at least Administrator authority is required More than 16-bit colors and 800 x 600 or above resolution display is
recommended
TCP/IP protocol must be installed for network management Platforms supported by software are listed below:
Windows XP/7/ 8/10 (32-bit & x64-bit) Windows server 2008/2008R2 (32-bit & x64-bit) Windows server 2012 /2016/2019 (x64-bit)
2.2. Software Install
Step 1 Insert the software CD into CD ROM. Installation menu will be
automatically displayed, or you can run autorun.exe to start the installation
in CD directory. Refer to the diagram 2-1.
Diagram 2-1
Step 2 It will show the following screen as Diagram 2-2. Then click
SchneiderUPS” button to start the installation.
Diagram 2-2
Step 3 After clicking install, it will display the installation in process. Refer
to the diagram 2-3.
Diagram 2-3
Step 4 Click Next to proceed to the next screen as Diagram 2-4.
Diagram 2-4
Step 5 Click “Choose” button to change the default folder. After choosing
the installed folder, click “Next” button. Refer to the following diagram 2-5.
Diagram 2-5
NOTE: For installing on non-default directories, please ensure you do not
have blank characters or non-English characters in the installation directory.
And the directory path cannot be more than 20 characters.
Step 6 Choose the shortcut folder and click “Next” button. Refer to the
following diagram 2-6.
Diagram 2-6
Step 7 It will display the software summary before installation. Click
“Install” button to start the installation and refer to Diagram 2-7.
Diagram 2-7
Step 8 Click “Done” button to confirm the installation completely. Refer to
Diagram 2-8.
Diagram 2-8
Note:
1. Please uninstall the previous version before installing the new
version of the software.
2. Modify the SNMP operating protocol from V2 to V3 and change the
default password to enable the SNMP security features.
2.3. Software Uninstall
Please choose Start>>All Programs>>SchneiderUPS>>Uninstall. Then
follow the on-screen instruction to uninstall the software. Before uninstalling
software, you must stop all software programs first and then log in as
“Administrator”! Otherwise, it can't be uninstalled completely.
3. Service Tray Application
The Installer will leave a shortcut icon on your desktop. Simply click the
shortcut. Then it will start the software and display an orange plug icon
located in the taskbar. To launch the GUI, double click the plug icon or
choose “Open Monitor” by clicking right button of the mouse. Refer to below
diagram. Or, use the Start Menu method; Start >> All Programs >>
SchneiderUPS >> SchneiderUPS.
Shortcut icon SchneiderUPS icon
3.1. Start Monitor
This software will be automatically activated when installing it as a service
application. At this time, users can remotely monitor UPSs through the web
browser even though users do not login into the operation system.
If the service application can not be registered successfully, when starting
up the tray service, it will automatically activate the monitoring application.
If its failed or stopped manually, simply click Start Monitor to activate it.
Start Monitor will check if monitoring application is registered as a service
application. If its successful, this software will be activated from the service
mode. If not, this software will be activated as monitoring mode. Users can
identify the application mode from tray icon as below:
Monitoring application is not activated successfully: Monitoring application is activated as service mode: Monitoring application is activated as monitoring mode:
3.2. Stop Monitor
Click Stop Monitor to stop monitoring application.
3.3. SNMP Manager
SNMP Manager is a plug-in utility for SchneiderUPS to search and operate all
SNMP devices in the LAN.
Click the “SNMP Manager” to access SNMP management tool.
It has four sections as marked in the illustration below:
Diagram 3-1
A. Function menu offers tool-set for setting SNMP devices.
B. SNMP device list can list down all SNMP devices with IP address.
C. Configuration area includes IP settings, online upgrade, password
management, and static trap address.
D. Output window displays all messages for operations
3.3.1. SNMP Device List
The default value in the window list would be current PC IP address. For
example, if IP address of current PC is “192.168.102.10”, it will display
“192.168.102” in list when first enabling SNMP Manager.
Scan
You may enter a specific IP address and then click “Scan” button to search.
Add
Click “Add” button and it will pop up a window to ask for entering a specific
IP address. Then, click “Apply” button to add IP address (Subnet). Refer to
Diagram 3-2.
Diagram 3-2
Delete
You may select an IP address from the list and remove it by clicking “Del”
button.
SNMP Status
It will display SNMP status, 0 or 1, after selecting IP from the IP list. If there is
a program inside of the selected SNMP card, the status becomes 1. If not, it will
display 0. If no IP address is selected, it will display --- as default. Refer to
Diagram 3-3.
Diagram 3-3
Reset
If it is required to restart the IP addresses of devices, please select the
checkbox of "SNMP reset enable" and click "Reset" button. Then, if login is
confirmed, you can restart the device. Steps are as follows:
Step1: Select IP address needed to restart IP from the list. Then, "SNMP
reset enable" will become available to select. Refer to Diagram 3-4.
Diagram 3-4
Step2: Click checkbox of "SNMP reset enable". Then, "Reset" button will
become available to click. Refer to Diagram 3-5.
Diagram 3-5
Step3: Click "Reset" button and it will pop up a message to confirm this
operation. Refer to Diagram 3-6.
Diagram 3-6
Step4: If "Yes" is selected, its requested to log in first. If "No" is selected, it
will stop this operation. Refer to Diagram 3-7.
Diagram 3-7
Step5: Enter the correct password and click "Login" button. The target
device will be restarted.
NOTE: If changing the MAC address of current device before reboot and the
current device is applying DHCP (Automatically obtain IP address) method, you
need to manually click "Scan" button to scan.
Use system time
If “Use system time is selected, the SNMP card will apply PC system time. Refer
to Diagram 3-8.
Diagram 3-8
3.3.2. Function Menu
3.3.2.1. System
Quit
Select “Quit” to exit SNMP Manager.
3.3.2.2. Settings
Basic Info
User can manually enter basic information of SNMP cards such as UPS name,
Address, and Note for verification. Refer to Diagram 3-9.
Diagram 3-9
IP Setting
Diagram 3-10
Part A: There are two methods to obtain IP address. Refer to section A in
Diagram 3-10.
Automatically obtain IP address (DHCP)
It will allow system to automatically obtain IP addresses. If there is not
this kind of service provided in LAN, the default IP will display as
“192.168.102.230”, Subnet mask as “255.255.255.0” and default
gateway as “0.0.0.0”. Simply click Apply” button to apply this change.
Use a static IP address
It will allow users to enter a static IP address for SNMP devices. When
entering the IP address, Subnet mask, and gateway address, simply
click “Apply button to apply this change.
Part B: Enter the DNS and click Apply button. Refer to section B in
Diagram 3-10.
Online upgrade
Diagram 3-11
There are three methods for online upgrade:
FTP server IP address: If applying upgrade for Modbus Web Server in
LAN, FTP server IP address will be IP address of current PC in LAN. If
applying upgrade for Modbus Web Server in specific networking, FTP
server IP address will be IP address of current PC in Internet.
Upgrade the selected devices: It will upgrade all SNMP devices listed in
the IP list.
Upgrade all devices not already upgraded: It will only upgrade SNMP
devices which are not using the latest version.
Force to upgrade all devices: No matter what kind of version is being
used for SNMP devices listed in the IP list, it will upgrade to the latest
version for all SNMP devices. Refer to Diagram 3-11.
Step 1: Click “Browse” button to choose program file. Refer to Diagram
3-12.
Diagram 3-12
Step2: Click “Upgrade” button to execute upgrade action. Refer to Diagram
3-13.
Diagram 3-13
Step3: When upgrade is complete, you may check the message in output
window. Refer to Diagram 3-14.
Diagram 3-14
NOTE: If an abnormal situation occurs during upgrade process, the system
will automatically re-start the upgrade operation. If this interruption occurs
five times, then the system will automatically stop this operation. At this
time, please check if LAN is working well.
System management
Diagram 3-15
Part A: You can set SNMP protocol version for selected or all devices. Simply
choose SNMP protocol version first. The default setting is V2. If choosing V3,
it’s also necessary to set encrypt. Select devices to apply this setting.
Select device: Set SNMP protocol version for selected SNMP devices
from device list.
Select all: Set SNMP protocol version for all SNMP devices from device
list.
Then, click “Apply button to complete version setting.
Part B: You may modify a single password for one SNMP device or all
passwords for all SNMP devices. Please enter original password, new
password and re-enter new password. Select devices to apply this setting.
Select device: Choose to change password for selected SNMP device
from device list.
Select all: Choose to change passwords for all SNMP devices on the
window list
Then, click “Apply” button to change password.
NOTE: The length of password is 8~15 digits. If this change is applied for all
SNMP devices, the password will be consistent for all SNMP devices.
Static trap address and Community String
You may configure two static trap addresses and change trap port and
Community String in SNMP Manager. The default trap port is 162. The
default community string is “public”, Refer to Diagram 3-16.
Diagram 3-16
NOTE: This software allows SNMP device to send trap messages to 2 static
trap addresses and 8 dynamic trap addresses. It will default define host
computer with software installed as a dynamic trap address. If
communication failure occurs between the SNMP card and host computer for
over 10 minutes, it will stop sending trap message.
3.3.2.3. Language
SNMP Manager offers 12 languages:
Chinese(Simplified) Chinese(Traditional) English German Italian Polish
Portuguese Russian Spanish Turkish Ukrainian French
The default language setting is English”.
3.4. Https
Https section includes Certificate Generation and Import Certificate.
Certificate Generation: it will automatically generate a numeral
certificate according to the information users enter. Refer to
Diagram 3-18:
Diagram 3-18
Note 1: Please enter internet domain name and IP address in First and
last name column.
Import Certificate: It will import a https certificate from a third party.
It supports JKS and PCKS12 types of certificate. Refer to Diagram
3-19.
Diagram 3-19
3.5. Open Monitor
Click Open Monitor to open monitoring webpage.
3.6. Exit
Click Exit to exit service application.
4. SchneiderUPS GUI
SchneiderUPS GUI includes function menu, shortcut button, login section
and main screen. Refer to diagram 4-1:
Diagram 4-1
A .Function Menu
It offers complete tool-set for navigation and setting the GUI.
B .Login section
It shows user type for current login user.
C .Shortcut button
Centralized monitoring.
Password, group area, UPS setting, SMS, E-mail, load
configuration, event action, log setting, EMD manager, modbus
communication setting.
Scheduled on/off, scheduled battery self-test, and scheduled
wake-on-LAN setting.
Event log, event statistics, data, diagram, and EMD log.
Refresh.
D. Main Screen
It will display information and/or control alternatives according to function
menu or shortcut menu selected.
5. SchneiderUPS Menu
5.1. Configuration
5.1.1. Password Setting
It’s password configuration for administrator only. The default user name
and password is “administrator”. Before operating and configuring the
software, please login and modify the default password first for security.
Users can only browse the UPS status and information as Guest status
without login as an Administrator. Guest can NOT control or execute any
setting.
Step 1 Select Configuration>>Password. Refer to Diagram 5-1.
Diagram 5-1
Step 2 Enter old password and type twice new password to modify
password for administrator. (The password should be at least 6 digits) Then
click “Apply” button to successfully modify password for administrator.
NOTE1: Simply click “Login” button on the top right corner to login to
the software.
NOTE2: If password is forgotten, its necessary to re-install the
software.
5.1.2. Group area
Select Configuration>>group area, user can assign monitored UPSs into
different groups for best management. SchneiderUPS has a default group
called “Unassigned”. When a UPS is detected, it will automatically put in the
Unassigned group. Users are able to not only create and customize groups
here, but also assign groups in UPS setting”. Refer to diagram 5-2.
Diagram 5-2
Section A Group list: Shows group information;
Section B Group editor: add/delete, set up and modify group;
Background image: Click “Customize button to import preferred image
into software as background for graphic view. Or users can simply select
preferred photos from default image database by clicking Select
button.
Add group: Add group into group list in section B. Then click “Add
button to add.
Modify group: Select a group from the list in section A to modify the
current setting and it will show the current setting in section B directly.
After entering new data, simply click Modify button to update setting.
Delete group: Select the group which needs to be deleted from the list
on section A. Then click delete button to delete.
Note1: Default group can only be modified, it cannot be deleted.
Note2: When Add button is disabled, first execute Clear operation.
Section C Maximum numbers for a device group: It means maximum
numbers will be shown in each group.
5.1.3. UPS setting
Select Configuration >> UPS setting. It helps users to assign or re-assign
groups for monitored UPSs. When a new UPS is detected, it will
automatically put in default group - Unassigned”. Refer to diagram 5-3:
Diagram 5-3
Query
User can query information according to the Group area, Port, UPS name
by clicking each column tab.
Modify
Select UPS that needs to be modified from the list and click Modify
button for modification. It will pop up information board of each
monitored UPS and users can assign or re-assign UPSs to group area. It
also can enter the UPS location and name here for internal reference.
Click Apply button to save all changes. Refer to diagram 5-4:
Diagram 5-4
Delete
Select UPS and click Delete button to remove it from the list.
5.1.4. SMS
It’s for entering SMS receiver list. In the event of an alarm condition
occurring, a message about UPS status will be sent to the specified users via
mobile phone. For the event receiving list, please configure in “Event Action”
page (refer to section 5-8-7).
1. Choose Configuration >> SMS. Refer to Diagram 5-5:
Diagram 5-5
2. Select communication port and baud rate.
3. Enter mobile phone numbers in “Phone no.” column and click “Add”
button to add phone no. in Receivers List. To delete numbers, simply
select phone no. from “Receivers list” and click “Delete”.
4. Click “Apply” button to save all changes. The “Test” button can be
used to send tests SMS to confirm the correct operation. If all
parameters are set up correctly, system will send a test message to
all receivers and pop up a successful message. Otherwise, it will pop
up a failure dialog to indicate there is an error for parameter setting.
NOTE: It’s required to plug-in a GSM Modem if sending SMS to mobile
phones.
5.1.5. E-mail
This feature enables the configuration to send alarm mail by SMTP server.
For the event receiving list, please configure in “Event Action” page. Refer to
5-8-7. To use this function, the e-mail service must be correctly configured
in the computer. All values in this function page are default empty. This
action can’t be executed without the SMTP information, e-mail account and
password. Besides, the sender account should be allowed for SMTP/POP3
forwarding.
Select Configuration >> E-mail. Refer to Diagram 5-6
Diagram 5-6
1. Enter SMTP server, SMTP port, Send from E-mail address, User name
and password. Click the checkbox of password authentication needed for
password verification. If using Exchange Server for mailbox system, it’s
required to configure Exchange server domain name in SMTP sever and
select “Exchange server”. Then, click “Apply” button.
2. Enter correct e-mail accounts in E-mail column. Then click “Add” to
add into receivers list. To delete e-mail account, simply select accounts
from Receivers list and click “Delete” button.
3. Click “Apply” to save all changes. The “Test” button can be used to
send a test e-mail to all receivers to confirm correct operation. When the
test e-mails are successfully sent to specific recipients, it will pop up a
successful message on operated PC. Otherwise, it will pop up a failure
dialog to indicate there is an error for parameter setting.
5.1.6. Load configuration
Load configuration can remotely manage other computers via intranet or
internet. It can set up remote computers in power-off options, MAC address,
execute file action, whether accept scheduled UPS shutdown or not, waiting
time for load shutdown and so on. In addition, it also allows one computer to
communicate with multiple UPSs. When any event occurs on the UPS, the
software can configure reactions of the monitored UPS via communicated
computer.
1. Select Configuration>>load configuration, refer to diagram 5-7:
Diagram 5-7
2. Add: Add load information (one computer) by clicking “Add” button.
Refer to diagram 5-8:
Diagram 5-8
Enter the IP address of this computer. Then, enter MAC address of
this computer. Users also can get MAC address by clicking “Auto
match” button when the connection is good.
Power-off option: Selecting power-off method for above shutdown
system.
Shutdown: When clicking the checkbox, the selected system will
shut down. The default setting is clicked.
Sleep mode: When clicking the checkbox, selected system will
suspend the system instead of a normal shutdown. But this
function is only supported by Windows 2000 or higher on
supported hardware.
On shutdown execute file: Enter the path of execute file. Waiting time for load shutdown: If selecting Accepts scheduled
UPS shutdown”, enter the waiting time for load shutdown before
shutting down UPS.
Selected UPS: Select UPSs to execute shutdown action when
entered PC is shut down.
Click “Apply” button to save all changes.
3. Modify: Select one from list to modify configuration by clicking
Modify button. User can also click “Delete” button to delete this
information.
4. Export: Users can export load setting table in CSV format by clicking
Export button.
5.1.7. Event action
It is to set up reactions after events occur. Select Configuration>>Event
action, refer to diagram 5-9:
Diagram 5-9
Section A: List all detected UPSs. The system default is all UPSs.
Section B: UPS event list.
Section C: Event action editor
Select UPS from section A and then select event from section B. When
selecting event, its necessary to set up at least one reaction from
section C. Click “Apply button to save setting.
This software provides seven reactions for UPS events.
Wake on LAN: It is a technology to remotely wake up one computer by
a network message. It is also required to have ATX power and hardware
support for remote PCs to implement this function. When event occurs,
this software will wake up PC by clicking this checkbox.
Execute file: When event occurs, it will request connected computer to
execute file.
Event record: When event occurs, it will save the event records to the
database.
Audible alarm: When an event occurs, it will play a selected media file.
If the user wants to use customized sound, its necessary to import the
media file into the software by clicking the Customize button. Select
this imported media file by clicking Select button.
Load shutdown: When an event occurs, it will the Shutdown wizard on
remote PCs to shut down computer.
Warning dialog (local): When an event occurs, it will pop up message
box to notify users.
SMS: When an event occurs, it will send event message to receivers via
mobile phone.
E-mail: When an event occurs, it will send mail to receivers via email.
And you can edit E-mail.
UPS shutdown: When an event occurs, it will shut down the UPS.
Note 1: When editing receiver list in SMS or e-mail columns, it’s
necessary to refresh the event action page to update receiver list.
Note 2: Event list will be different according to different types of UPS.
Note 3: When one or more of the following three conditions are met, the
total of the delays are added together to get the total UPS shutdown
delay.
3. The Load Configuration page is configured for 'Waiting time for
load Shutdown'.
4. The event is configured for 'load shutdown'.
5. The event is configured for 'UPS shutdown'.
If this total delay is under 600 seconds, the value is set according to the
following table.
With the total delay adding to anything from...
...the value is set to...
20 -180
180 seconds
181-300
300 seconds
301-600
600 seconds
5.1.8. Com. Port Plug And Play Setting
To real-time monitor UPS device, it will scan each com. port anytime. In this
way, it will occupy communication ports. This function will release some
communication ports which are not connected with devices. To avoid any
improper operation, unused communication ports will be displayed in
disabled grey icons. Users can select "Allow scanned" to re-scan or "No
scanning to release communication ports based on requirements.
Step 1: Select configuration>>Com. port plug and play setting. Refer to
Diagram 5-10.
Diagram 5-10
Step 2: Click Refresh to reload the status of com. ports.
Step 3: Click Forbid scanned to stop scanning on this com. port. Click
Allow scanned to start scanning on this com. port.
5.1.9. Log setting
Refresh frequency: The setting range for “Refresh frequency” is 2~600
seconds. It will affect the displayed data refreshed in software screen.
Record interval: Users can set up “Record Interval”, “The max. Numbers
of logs for historical data” and “The max. Numbers of logs for historical
events according to a real situation.
The setting range for Record interval is 30~600 seconds. It will effect
history data displayed under View >> History >>Data.
1. Select configuration>>Log setting. Refer to Diagram 5-11:
Diagram 5-11
2. Enter time interval and click “Apply” button to save all settings.
3. Click “Default” button to recover the default setting.
5.1.10. EMD Manager
EMD Manager is used to manage Environmental Monitoring Devices. Users
can define events and set message texts for each event. It also can set up
warning points for temperature, humidity and smoke of devices.
Dry contact event: Users can define events and set event level. After
event is successfully added, users can configure and set alarm. Refer
to Diagram 5-12.
Diagram 5-12
Text Message: The description of the dry contact event. Default dry Contact: Define dry contact no. to send event
message. There are five selections: none, 1, 2, 3 and 4. If selecting
any value from 1 to 4, the defined event will send the event message
for any environmental monitoring device(EMD) which is detected. If
selecting none, it means this event is defined as special event.
Then, users can assign specific environmental monitoring device
(EMD) to receive this event message. Please refer this special event
setting in Dry contact configuration section.
Dry contact configuration: Users can define special events with
assigned dry contact no. for specific environmental monitoring
device (EMD). If any defined event is detected by assigned device
via assigned dry contact no., it will send alarm message via software.
Refer to Diagram 5-13.
Diagram 5-13
Alarm Settings: Set up alarm range for temperature and humidity. If
detected figures are out of setting range, it will send alarm message.
Refer to Diagram 5-14.
Diagram 5-14
5.1.11. Modbus communication setting
It will display all connected PCs through ModBus.
Step 1 Select configuration>> ModBus Communication Setting. Refer to
Diagram 5-15.
Diagram 5-15
Step 2 Com. port setting:
The default ID for nominated com. port is 0; Selectable baud rates are 1200, 2400, 4800, 9600, and 19200.
The default setting is 19200;
Selectable data bit is 7 and 8. The default setting is 8; Selectable stop bit is 1 and 2. The default setting is 1; Supported parity is ODD parity, event parity and NONE. The
default setting is NONE.
NOTE: This function is only available for the UPS with ModBus
communication port.
5.2. Schedule
5.2.1. Scheduled on/off
Scheduled UPS on/off can be executed once, daily, weekly. Users can select
UPS and time parameters. It is recommended to set only one action in the
same time. If multiple actions have been applied at the same time, some of
these actions may be ignored. Any action will be ignored when the action is
not supported by the UPS.
Step 1 Select “Schedule” >> Scheduled on/off. Refer to Diagram 5-16.
Diagram 5-16
Step 2 Set frequency and setting time on the right column.
NOTE: Please be aware following rules while setting time.
Once – Power-off time should be earlier than power-on time.
Daily schedule – Power-off time should be earlier than power-on time.
Power-on time and power-off time should be set on same day.
Weekly schedule –Power-off time should be earlier than power-on
time. Power-on time and power-off time should be within the same
week.
Power off at - This time is an approximation. It is the starting point
for delays before the UPS powers off. This UPS power off time
incorporates delays such as "waiting time for load shutdown" if it is
configured.
Power on at - This time is an approximation. The UPS will turn on
after the delay of "waiting time for load shutdown" (if configured) + the
time difference between power on and power off.
The setting for "waiting time for load shutdown" is found in the Load
configuration page. The default value for UPS power off delay is 180s
(applies if "waiting time for load shutdown" is not configured).
Step 3 Click “Add” to add task. If task is successfully set, it will display on
the task table on the left-hand side. Select specific task and click “Delete”
button to delete the task.
Note 1If there is a plan which shares the same time, it will execute only one
of them.
Note 2If the UPS which accepts scheduled on/off setting is connecting with
a load, it can also allow to set load shutdown reminder.
5.2.2. Scheduled battery self-test
Scheduled battery self-test can be executed once, daily, weekly, or monthly.
Users can select UPS and time parameters. It is recommended to set only
one action for a specific time. If multiple actions have been applied at the
same time, some of these actions may be ignored. Any action will be ignored
when the action is not supported by the UPS.
Select Control >> Battery Self-Test. Refer to Diagram 5-17.
Diagram 5-17
1. Select method and time parameters. There are three self-test
methods:
Self-test: Users can set battery discharge time for self-test. Deep test: This test will allow battery to discharge until low
battery level.
2. Click “Add” to add task. If task is successfully added, it will display on
the task table on the left-hand side. Select task from table list and
click “Delete” button to delete the task.
5.2.3. Wake on LAN schedule
It supports wake-on-LAN schedule for one or multiple computers at once,
daily, and weekly frequency.
1. Select Schedule >> Wake on LAN schedule, refer to diagram 5-18:
Diagram 5-18
2. Select IP, Cycle, Date and Time, and then click “Add” button to add
plan.
3. Select one plan from schedule list, and then click “Delete” to delete
plan.
5.3. View
5.3.1. Centralized monitoring
It includes Text view and Graphic view. Users can exchange view mode by
clicking “Text view” button and “Graphic view” button.
Text view: Each UPS is displayed in the panel form and it shows UPS
working status and data. Multiple UPSs will be displayed with multiple
UPS panels. Refer to diagram 5-19-a:
Diagram 5-19-a
List view: It will show UPS working data and status in a table. Refer to
5-19-b.
Diagram 5-19-b
Graphic view: Each UPS is displayed as a simple icon. It shows its
status icon with background picture. To avoid any mistakes, it also
supports security function. Only when user type is administrator, it’s
allowed to unlock these icons. Then, administrator can drag and drop
the icon anywhere freely. The default setting is in lock status. Refer to
diagram 5-20-a and diagram 5-20-b.
Diagram 5-20-a
Diagram 5-20-b
UPS detail information: On the Text view mode, users can enter
individual UPS monitoring interface by double clicking each UPS panel. On
the Graphic view mode, users can enter individual UPS monitoring interface
by double clicking each UPS icon. Refer to diagram 5-21:
Diagram 5-21
5.3.1.1. Status
5.3.1.1.1. Power Flow
Select Status >> Power Flow. Refer to diagram 5-22.In the Power Flow
window, it’s shown the internal dynamic working flow of the UPS is shown.
Diagram 5-22
Green/black flow means working well. Grey bar means that the object is
present but not in use at the moment. There are four information blocks to
display details about input, output, UPS and battery information.
Input information includes input voltage and input frequency. Output information includes output voltage, output frequency, load
level, and output current.
UPS information includes UPS operation mode and UPS temperature. Battery information includes battery voltage, battery capacity and
remaining backup time.
5.3.1.1.2. UPS Info
Select Status >> UPS Info. Refer to Diagram 5-23.
In the “UPS Info” window, it shows real-time monitored UPS data including input, output, UPS, and battery information in text and bar.
Diagram 5-23
5.3.1.1.3. Diagram
Select View >> Status >> Diagram. Refer to Diagram 5-24.
In the Diagram window, it shows real-time monitored UPS data including
voltage, frequency, load, battery, temperature information in diagram.
Diagram 5-24
5.3.1.1.4. Environmental information
In the Environmental information window, it shows the current temperature
and humidity.
Select Status >> Environmental information. Refer to Diagram 5-25
Diagram 5-25
Note: This information is only available when SNMP card is connected with
Environmental monitoring device (EMD).
5.3.1.2. Basic information
It includes UPS basic information, battery information, UPS purchasing
information, and UPS rated information. Refer to diagram 5-26.
Diagram 5-26
5.3.1.3. Parameters setting
Some UPS functions can be set and changed via software. Parameter setting
includes backup time setting for programmable outlet (P1), battery number
setting, voltage and frequency range setting for bypass mode, and voltage
range setting for ECO mode.
Diagram 5-27
Note: Different UPSs may access different parameter settings.
1. Select the functions by clicking “Enable” or “Disable” button. Change the
numbers by clicking up-down arrows or modify the numbers directly in
the number column.
2. Click “Apply” button to save the settings. Each function setting is saved
by clicking “Apply” button in each section.
3. Click “Default” button to recover the default setting.
Note: If functions are not supported by the UPS, they will not be accessible.
UPS alarm: If enabled, UPS alarm will be activated. Vice versa. Alarm at bypass mode: If enabled, UPS alarms when it’s working at
bypass mode. Vice versa.
Auto reboot: If enabled, UPS will auto recover when AC is recovering.
Vice versa.
Bypass when UPS is off: If enabled, AC will directly provide power to
connected devices when UPS is off. Vice versa.
Converter mode: If enabled, the UPS will operate in converter mode.
Vice versa.
ECO mode: If enabled, the UPS will operate in ECO mode when input
voltage is within acceptable range. Vice versa.
Cold start: If disabled, the UPS can be turned on only when AC is
normally connected to UPS. Vice versa.
Bypass not allowed: If enabled, the UPS will not transfer to bypass
mode under any conditions. If disabled, the UPS will be allowed to
transfer to bypass mode according to UPS internal setting.
Set Unit Battery Capacity(AH):
Unit Battery Capacity: set battery capacities.
Battery numbers setting:
Numbers in parallel: set battery numbers in parallel
Voltage and frequency range for bypass mode: Set acceptable voltage
and frequency range in bypass mode
Maximum and minimum voltage: When UPS is on bypass mode and
input voltage is out of setting range, UPS will enter battery mode.
Maximum and minimum frequency: When UPS is on bypass mode
and input frequency is out of setting range, UPS will enter battery
mode.
Voltage range for ECO mode: Set acceptable voltage range for ECO
mode.
5.3.1.4. Real-time control
Refer to diagram 5-28:
Diagram 5-28
1. Choose real-time control function by clicking “Start” button on each
function section. You can real-time control the UPS by executing
following operation:
UPS turn On/Off: Click “On” to turn on the UPS and “Off” to turn off
the UPS immediately.
Battery Self-Test: Software offers three types of battery self-test:
10-second self-test, deep discharge test, and self-defined self-test.
Simply clicking “Start” button from each type. It will execute the
self-test immediately.
Note: Different UPSs may access different parameter setting.
5.3.1.5. Purchasing information
Users can enter UPS purchasing date, battery purchasing date, UPS
warranty time, battery warranty time, battery lifecycle, and battery
replacement reminder for future reference.
Diagram 5-29
1. Please fill out purchasing information.
2. Click “Apply” button to save all data.
5.3.2. History
5.3.2.1. Event Log
In the Event Log window, it’s shown all history events. Users can analyze the
history data and improve the current electricity environment according to
history data.
1. Select View >> History >> Event Log. Refer to Diagram 5-30
Diagram 5-30
2. Select UPS from com. port list. Users still can retrieve old data saved
in the software even though the UPS is no longer connected to local
system.
3. Select time period by clicking calendar icon. Then click “Browse”
button to get list of all history events during selected period time.
4. Print/Delete/Export function keys
“Print”: Click “Print” button to print the current event log. “Delete/Delete all”: To delete specific event, simply select that
event and then click “Delete” button. Or click “Delete all” button to
delete all history events on the listed table.
“Export”: Click “Export” button to save listed table to local PC
in .CSV file.
5.3.2.2. Event Statistics
It will list down and provide all event statistics for UPSs with software
installed based on time period A and time period B, and the change
percentage [= 100*(B/A – 1)%].
NOTE: Event types include UPS internal event, bypass event, battery event,
software event, load event, input event, parallel system event and
communication event.
Step 1 Select History >> Event Statistics. Or click shortcut icon .
Refer to Diagram 5-31.
Diagram 5-31
Step 2 Select UPS from com. port list. Users still can retrieve old data
saved in the software even though the UPS is no longer connected
to the local system.
Step 3 Select two periods from clicking “calendar” icon. Then click
“Browse” button. The statistics result will be listed in below table
according to event types. Refer to Diagram 5-32.
Diagram 5-32
Click “Print” button to print event statistics.
5.3.2.3. Data
In the window of Data, it shows UPS power data in figures during selected
period time. Software also offers print, save as, and delete functions. User
can customize record intervals and default data is recorded in 60 seconds
intervals.
Step 1 Select View >> History >> Data. Refer to Diagram 5-33.
Diagram 5-33
NOTE: This screen may be different for different types of UPSs.
Step 2 Select UPS from com. Port list. Users still can retrieve old data
saved in the software even though the UPS is no longer connected
to the local system.
Step 3 Select the starting time and ending time by clicking calendar icon.
Then click “Browse” button to get the data table.
“Print”: Print the listed data table. “Delete”: Select specific data and click “Delete” button to delete the
record.
“Delete all”: Click “Delete all” button to delete all records on the
listed table.
“Export”: Click “Export” button to save listed table to local PC
in .CSV file.
5.3.2.4. Diagram
In the Diagram window, it shows UPS power data in diagram during selected
period time. UPS power data includes input voltage, output voltage, input
frequency, output frequency, load level, battery capacity, and UPS
temperature.
Step 1 Select View >> History >> Diagram. Refer to Diagram 5-34.
Diagram 5-34
NOTE: This screen may be different for different types of UPSs.
Step 2 Select UPS from com. Port list. Users still can retrieve old data
saved in the software even though the UPS is no longer connected
to the local system.
Step 3 Select cycle and period time. Then click “Browse” button to get the
diagram.
Step 4 Select monitoring parameters on left-hand tab to switch diagram.
5.3.2.5. EMD Logs
In the EMD logs window, it shows the environment data in figures detected
by the environmental monitoring device (EMD) during the selected period
time.
Step 1 Select View >> History >> EMD logs. Refer to Diagram 5-35.
Diagram 5-35
Step 2 Select UPS and select the starting time and ending time by clicking
calendar icon. Then click “Browse” button to get the data table.
Delete/Delete all
“Delete”: Select specific data and click “Delete” button to delete
the record.
“Delete all”: Click “Delete all” button to delete all records on the
listed table.
5.4. Format
5.4.1. Temperature Unit
There are two temperature units for selecting: Centigrade and Fahrenheit.
Default setting is centigrade.
5.4.2. Date Format
There are nine formats for date display:
YYYY-MM-DD YYYY/MM/DD YYYY:MM:DD MM-DD-YYYY MM/DD/YYYY MM:DD:YYYY
DD-MM-YYYY DD/MM/YYYY DD:MM:YYYY
Default setting is YYYY-MM-DD.
5.5. Language
SchneiderUPS offers thirteen languages for selection:
English French German Italian Polish Portuguese Russian Spanish Ukrainian Turkish Czech Chinese(Simplified) Chinese(Traditional)
5.6. Help
5.6.1. About
Click “Help” menu and select “About. It represents the information about
software.
5.6.2. Online help
Click “Help” menu and select the Online help item. It will open the user
manual. Before operating the software, please read the manual carefully.