Schneider ATV312H055M2, ATV312HU30N4, ATV312H037M2, ATV312HU15N4, ATV312H055N4 User Manual

...
Quick Start Guide - ATV312
ENGLISH
1
2
3
S1A1094203
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Only appropriately trained persons who are familiar with and understand the contents of this manual and all other pertinent product documentation and who have received safety training to recognize and avoid hazards involved are authorized to work on and with this drive system. Installation, adjustment, repair and maintenance must be performed by qualified personnel.
• The system integrator is responsible for compliance with all local and national electrical code requirements as well as all other applicable regulations with respect to grounding of all equipment.
• Many components of the product, including the printed circuit boards, operate with mains voltage. Do not touch. Use only electrically insulated tools.
• Do not touch unshielded components or terminals with voltage present.
• Motors can generate voltage when the shaft is rotated. Prior to performing any type of work on the drive system, block the motor shaft to prevent rotation.
• AC voltage can couple voltage to unused conductors in the motor cable. Insulate both ends of unused conductors of the motor cable.
• Do not short across the DC bus terminals or the DC bus capacitors or the braking resistor terminals.
• Before performing work on the drive system:
- Disconnect all power, including external control power that may be present.
- Place a "Do Not Turn On" label on all power switches.
- Lock all power switches in the open position.
- Wait 15 minutes to allow the DC bus capacitors to discharge. The DC bus LED is not an indicator of the absence of DC bus voltage that can exceed 800 Vdc.
- Measure the voltage on the DC bus between the DC bus terminals using a properly rated voltmeter to verify that the voltage is < 42 Vdc.
- If the DC bus capacitors do not discharge properly, contact your local Schneider Electric representative.
• Install and close all covers before applying voltage.
Failure to follow these instructions will result in death or serious injury.
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel. No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this product.
Information below is designed to use single drive connected to single motor with a motor cable length less than 50 meters (164 ft). In any other case, consult the ATV312 installation manual (BBV46391) and programming manual (BBV46385) on www.schneider-electric.com.

Check the delivery of the drive

WARNING
DAMAGED DRIVE EQUIPMENT
Do not operate or install any drive or drive accessory that appears damaged.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
• Check that the drive reference printed on the label matches the delivery note and corresponding purchase order.
Write the drive Model Reference: _____________ ___________and Serial Number: ____________________________

Check the line voltage compatibility

• Check that the line voltage is compatible with the supply range of the drive.
Line voltage _______ Volts / Drive voltage range _______ Volts Drive range: ATV312ppppM2 = 200/240 V single phase / ATV312ppppM3=200/240 V three-phase ATV312ppppN4 = 380/500 V three-phase / ATV312ppppS6 = 525/600 V three-phase

Mount the drive vertically

For a surrounding air temperature up to 50 °C (122 °F)
8B0917121134
(a)
(a)
(a)
See installation manual (BBV46391) on www.schneider-electric.com for other thermal conditions.
www.schneider-electric.com 1/4 S1A10942 - 04/2014
(a)
(a) 50 mm (2 in.)
(b)
(b) 10 mm (0.4 in.)
4
ATV312 M2
ATV312 M3
ATV312 N4
ATV312 S6
200/240 V
380/500 V
525/600 V
REF
RUN CAN ERR
MON
CONF
200/240 V
or
See
SCCR annex
5
5.1
+10 v
AI 1
COM
2.2 KΩ
24 V
LI2
LI1
LIx
ATV 312
LI1: forward LI2: reverse
LI1: stop
Control command 2-wire:
Control command 3-wire:
LI2: forward LIx: reverse
OR
5.2
6
7
8
7
5.1
5.2
6
9.2
ENT

Connect power wiring

• Wire the drive to the ground.
• Check circuit breaker rating or fuse rating (see SCCR annex)
• Check that the motor voltage is compatible with the drive voltage. Motor voltage ______Volts.
• Wire the drive to the motor.
• Wire the drive to the line supply.

Connect control wiring and select control configuration: or

[REMOTE configuration]
(Control by external reference)
Source
• Ensure SW1 = ‘’SOURCE’’
• Wire the speed reference:
Wire the command:
ATV 312
LI1
24 V
LI2
CLI SINK
•Next steps, do:
+ + +
6
9.1
[LOCAL configuration]
(control by internal reference)
CONF
RUN
REF
CAN
MON
ERR
.
Do: + + +

Apply power to the drive

• Ensure that Logic Inputs are not active (see Li1, Li2, Lix ).
• Apply power to the drive.
• At first power up, the drive displays nSt (3-wire control) or rdY(2 -wire control), after pushed drive displays bFr.
• On next start-ups, the drive displays nStor rdY .

Set motor parameters

• Refer to the motor nameplate for the following parameter settings.
[MOTOR CONTROL]
www.schneider-electric.com 2/4 S1A10942 - 04/2014
Menu Code Description Factory setting
drC-
[Standard mot. freq]:
bFr
UnS
FrS
nCr
nSP
COS
Standard motor frequency (Hz)
[Rated motor volt.]:
Nominal motor voltage on motor nameplate (V)
[Rated motor freq.]:
Nominal motor frequency on motor nameplate (Hz)
[Rated mot. current.]:
Nominal motor current on motor nameplate (A)
[Rated motor speed]:
Nominal motor speed on motor nameplate (rpm)
[Motor 1 Cosinus Phi.]:
Nominal motor cos
50.0
drive rating
50.0
drive rating
drive rating
ϕ on motor nameplate
drive rating
87