SARGENT AL User Manual

Instructions for Installation and Wiring Remote Options to AL- Prefix 80 Series Alarmed Exit Devices using the 546 Wiring Harness to ElectroLynx™ Connector System
For assistance, contact SARGENT at 800-810-WIRE (9473) or www.sargentlock.com
Instructions for Installation and Wiring Remote Options to SARGENT AL-Prefix 80 Series Alarmed Exit Devices using the 546 Wiring Harness to ElectroLynx System
FOR ASSISTANCE CONTACT SARGENT AT 800-810-WIRE (9473) or www.sargentlock.com
®
Connector
A. General
These instructions cover installing and wiring remote options to the AL- 80 Series Alarmed Exit Device using the 546
wiring harness. Refer to instruction A7224B for additional instructions. Remote options include Remote Power, Remote Monitor, Request to Exit (REX), Door Status and Remote Reset. In addition, there are field selectable options: REX/Passage Time Delay, Automatic Alarm Reset and Remote Monitor Relay Enable/Disable
B. Important
1. Caution: Disconnect all input power before beginning installation to prevent electrical shock and
equipment damage
2. Installer must be a trained, experienced service person
3. All wiring must comply with applicable local electrical codes, ordinances and regulations
2
4
6
2
4
3 1
4, Tan (RR)
8
75
7, Brown (RM - NO)
8, Yellow (RM - NC)
1, Violet (DS)
2, Grey (DS)
3, Pink (RR)
1
3
1, Black (RP, -9v)
2, Red (RP, +9v) 3, White (Rex)
4, Green (EG)
5, Orange (Rex)
6, Blue (RM - C)
546-F, -J or -G harness with 8 and 4-pin connectors
AL- 80 Series Rail
RP - Remote Power Rex - Request to Exit EG - Earth Ground RM - Remote Monitior DS - Door Status RR - Remote Reset
C. Connector System Notes: The system is designed to be installation friendly with
pluggable connectors from the electric hinge through the door to the rail. The only wiring required is to the loose wires on the pigtail harness assembly on the frame side of the electric hinge
IMPORTANT:
The plug and receptacle connectors are designed to mate and lock together as shown in the figure. Plug the connectors into each other with the locking mechanism aligned as indicated
Do NOT force connectors on any other way.
Receptacle
Locking mechanism
Plug
D. Installation Notes
1. With new applications, a raceway harness with 8 & 4-pin connectors will be pre-installed inside the door by ASSA ABLOY door manufacturers when specified during the ordering process. Raceway harness kits are also available for retrofit applications. For retrofit applications, refer to retrofit instructions
2. If door does not have a raceway harness with connectors, either consult factory for raceway retrofit kit or cut the connectors off product and hard wire as required
3. Wiring to pigtail harness is per facility wiring requirement. The rail, raceway, electric hinge and pigtail connector terminations and wire colors all match
Copyright © 2004, 2006, 2008, 2009, 2012, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved. Reproduction in whole or in part without the express written permission of Sargent Manufacturing Company is prohibited.
A7251C
1
E. Remote Options - Input/Out Descriptions
Note: Refer to instruction A7224B REX/Passage and Automatic Alarm Reset Tables
Pigtail Circuit Board Remote Connector Connector Option Description
Black (-9v), 8-1 J1 - 2 Remote Power Allows unit to be connected to 9vdc power supply Model 3267 Red (+9v), 8-2 J1 - 1 (Input) Refer to 3267 instructions A7477
White, 8-3 J4 - 1 REX Wired to normally open external switch or relay contact. Orange, 8-5 J4 - 2 (Request to exit) Momentary switch closure shunts rail, allows egress for selectable (Input) time of 7, 10, 15 or 20 seconds (see Passage Table), then rail rearms. Maintained switch closure shunts rail, allows egress until switch opens, then rail rearms after selectable passage delay of 7, 10, 15 or 20 seconds or portion of selected passage delay Note: LED flashes yellow during switch closure
Green, 8-4 Earth Ground Use to connect rail to 3267 power supply earth ground terminal
Blue (C), 8-6 J3 - 2 Remote Monitor With unit armed, depressing push bar shall sound the alarm Brown (NO), 8-7 J3 - 3 (Output Relay) and the output relay will change state until the unit is disarmed with a Yellow (NC), 8-8 J3 - 1 cylinder key, remote reset, or automatically reset after selectable time delay of 2, 5 or 10 minutes (see Automatic Alarm Reset Table). Note: Dip Switch SW-2 position 6 must be ON (Refer to SW-2 Table). SW-2 position 6 OFF disables output relay
Violet, 4-1 J4 - 3 Tamper/Door Status With door closed, wire to door status switch open contacts. With rail armed, Grey, 4-2 J4 - 4 (Input) the alarm will sound when door is opened (switch is electrically closed). Alarm will sound until reset with cylinder key or automatic alarm reset time
Pink, 4-3 J4 - 5 Remote Reset/Arm Wired to normally open external switch or relay contact. When rail is Tan, 4-4 J4 - 6 (Input) violated (alarm on), the rail alarm is reset and rail is rearmed as follows: Momentary switch closure resets alarm, then rail is rearmed after selected passage time of 7, 10, 15 or 20 sec (see Passage Table). Maintained switch closure resets alarm/keeps rail disarmed. When switch is reopened, the rail rearms after selected passage time Note: LED remains OFF. Recommended for remotely disarming rail long term
Red (+), J2 - 1 Battery Connects 9vdc battery to circuit board Black(-), J2 - 2 (Input)
Gray, J2 - 3 To Internal Wired normally open and mechanically held (maintained) closed. Black,J2 - 4 Rail Switch Alarm activates when switch is electrically opened (when push (Input) bar is depressed)
2
A7251C
Copyright © 2004, 2006, 2008, 2009, 2012, Sargent Manufacturing Company, an ASSA ABLOY Group company. All rights reserved. Reproduction in whole or in part without the express written permission of Sargent Manufacturing Company is prohibited.