SARGENT 4000 User Manual

5 (1)
SARGENT 4000 User Manual

R

Low Energy Door Operators

Wiring Instructions For 4051, 4052, 4060, 4067

80-9369-0901-021 (12-02 )

120 VOLT POTENTIAL PRESENT. MAKE SURE POWER INPUT TO UNIT IS TURNED OFF DURING INSTALLATION AND WIRING PROCEDURE.

REQUIREMENTS:

U.L. labeled fire or smoke barrier door assemblies require that the 120VAC, 60Hz power input to the Power Door

Operator be supplied through normally closed alarm contacts of the alarm system/alarm panel.

All wiring and connections use standard wiring practice conforming with local wiring codes.

Power inputs at terminal strip T1 and at terminal strip JP4 must be made with copper wire only.

Maximum wire size is:

12 AWG at Power Input Terminal Strips

14 AWG at Terminal Strips JP1 And JP4

Note: No power/voltage inputs are to be made to the Door Operator unit except 120VAC, 60Hz (+10% -15%) at terminals HOT and COM of the Power Input Terminal Strip T1.

Typical field connections for flexible conduit illustrated on page 2.

Power input terminal strip T1 at terminals Hot and COM must be 120VAC at 60Hz (+10% -15%).

Current draw at auxiliary contact JP4 – 2 must not exceed 0.500 amps, for auxiliary devices.

GENERAL DATA:

Maximum current draw of Door Operator units without peripheral sensors or scanners is 1.5 amps when motor is operating, .050 amps in standby.

Maximum current draw from auxiliary devices is 0.500 amps (terminals JP4 – 1 and JP4 – 2).

Fuse “F2” protects the Electronic Control Module and Transformer circuit and is a 3 amp slow blow fuse.

Requirements

 

1

 

Unit Wiring

 

2

 

Control Module Layout and (Input/Output Connections; Functions)

3-5

 

Typical Application – Point to Point Wiring Diagrams

6-15

SW1

 

 

 

Dip

 

 

 

Switches

 

 

 

Main Board

 

 

Rotary Switches/

 

 

 

Timer Pots

 

Field Reversible

JP2

 

 

Unit Shown

Terminal

 

 

Square Spindle End

Strip

 

 

 

 

 

Protrudes

ELS Board

 

 

 

LED

 

 

Spindle Timing

 

 

 

Pulley for Field

 

 

 

Reversible

 

 

 

Units

 

 

 

Timing Belt

 

 

 

 

C

 

JP3

ELS Board w/

S

 

 

 

 

 

Terminal

ELS Board

 

 

 

 

Strip

Pulley

 

 

 

 

 

 

 

(SC) Speed

 

 

H

Control Valve

 

 

US

 

 

 

P

 

 

 

 

Application

 

 

Solenoid

(REF)

 

Door Calibrate

Close Position

Door Calibrate

Handed Unit

Open Position

11/16" Power

Shown

Adjustment Nut

 

Bracket for

Input Power

Terminal Strip

T1

Fuse

F2

JP1

Terminal

Strip

JP4

Terminal

Strip

JP5

Terminal

Strip

Spindle Timing

Pulley

Handed Units

80-9369-0901-021 (12-02 )

1

A7666A

CONCEALED WIRING

Thread conduit fitting(s) into backplate as shown. A second conduit fitting is required for low voltage control wiring. CHECK LOCAL CODES. Pull conduit out of header and attach to conduit fittings before mounting Operator to door frame. Attach incoming ground wire to backplate with ground screw as illustrated below.

Low Voltage

Control

Wiring

Incoming

Power

Cable

Clamps

SURFACE WIRING

An optional bracket is provided for use with surface wiring. Remove the two cable clamps screws and slip the bracket under the cable clamps. Push the cable clamp screw through the bracket holes and tighten. ½” conduit fittings can now be installed on the bracket.

Conduit by Others (from top)

(Green) Ground Screw

“T1” Power

Input

Terminal Strip

Bracket

Optional Bracket

Ground

Power

(for surface wiring)

Lead

Leads

INSTALLER / USER INFORMATION

Input Power Terminal Strip – 120VAC, (+10% - 15%) Input Voltage. Maximum wire size 12 AWG at terminals HOT and COM. Terminals 22 through 25 are factory wired using 18AWG wire.

Earth Ground Wire Connection – Ground wire must be secured to backplate under head of (green) ground screw nearest to “T1” Power InputTerminal Strip bracket. Screw labeled “GND”.

Terminal

Description

 

Fuse F2*

 

 

 

 

COM

Common power lead

 

 

(Neutral)

 

 

 

 

 

HOT

Hot power lead

 

 

(Line)

 

 

 

 

 

25

Fuse connection

 

 

 

 

 

24

Hot connection to PC board JP5 – 2 and to hot

 

primary side of 120V / 24V transformer.

 

 

 

 

 

23

Fuse connection

 

 

 

 

 

 

22

Common connection to PC board JP5 – 1 and

to

 

common primary side of 120V / 24 V transformer.

 

 

 

 

 

24

23

22

25

HOT

COM

Left Hand Double Lever, Push Side Right Hand Slide Track, Pull Side

22

23

24

Fuse F2*

COM

HOT

25

 

Right Hand Double Lever, Push Side Left Hand Slide Track, Pull Side

2

80-9369-0901-021 (12-02 )

SW5 Rotary

Switch/Timer

Pot

JP2 Terminal

Strip

SW3 Rotary

Switch/Timer

Pot

JP3 Terminal

Strip

Fuse F1 1.5 amp, 2AG Slo-Blo

JP2

G

E

M

G

H

+V L2 G L1

JP3

MOTOR/SOLENOID

 

 

SW4 Rotary

SW2 Rotary

 

 

 

SW1 Dip

 

 

 

 

 

 

 

Switch/Timer

Switch/Timer

 

 

 

Switches

 

 

 

 

 

 

 

 

Pot

 

 

Pot

 

 

 

 

 

 

 

 

 

 

 

 

CL/AS DLY

VEST DLY

DOOR OPERATOR

 

 

 

OFF SW1 ON

 

 

41-6700-0056 REV A

MADE IN USA

 

 

 

 

2

3

 

 

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

4

1

 

4

 

 

 

 

 

 

 

 

 

P/A

JP1

 

 

 

5

 

 

 

5

 

 

 

 

 

 

 

 

 

 

0

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

A/D

 

AUX1

9

 

6

9

 

 

6

 

 

 

 

 

 

 

 

 

14

 

8

7

 

 

8

7

 

 

 

 

 

 

 

 

 

 

RES1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

GND

EXSOL DLY

M. DLY

 

 

 

 

 

 

 

 

 

RES2

 

2

3

 

 

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

4

1

 

4

 

 

 

 

 

 

 

 

 

 

 

 

PDET

 

 

5

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

0

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

 

9

 

6

9

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

8

7

 

 

8

7

 

 

 

 

 

 

 

 

 

 

 

 

11

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

AUX2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

TFR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6

OUTV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay

 

Relay

 

 

 

5

INV

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

GND

 

 

 

 

 

 

 

 

 

 

 

K3

 

 

K4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

AUX2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

RES1

 

K2

 

 

 

 

 

 

JP5

 

 

 

 

 

 

 

 

 

1

 

 

 

 

 

Relay

 

 

 

 

 

 

 

 

 

 

0/0

 

 

 

 

 

 

 

 

NEU HOT GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

18VAC

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

K1

 

 

1

2

3

4

5

6

7

8

JP4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND +24V NO1 CO1

NC1 NO2

CO2 NC2

 

 

 

Electronic Control Module (Main PC Board)

JP1 Terminal

Strip

JP4 Terminal

Strip

JP1 Terminal Strip – Maximum wire size 14AWG. For signaling only, do not make power input connections.

 

TERMINAL

 

D E S C R I P T I O N

 

 

 

 

 

 

 

 

 

 

Override Open – This terminal has two possible functions that can be used together or separately.

 

 

 

 

1. Smoke Ventilation Door or Blow Open Door – Upon initiation of a closed signal from a fire/ smoke alarm

 

 

1

0/0

panel, door will open and remain open until signal is terminated. Use with any JP1 ground.

 

 

 

 

2. Alarm Delay (30 second or 60 second time period) – Time is set with dip switch SW1 – 2 A/D. (OFF = 30

 

 

 

 

second delay, ON = 60 second delay) Use with any JP1 ground.

 

 

 

 

 

 

 

 

2

RES1

This is not an active contact.

 

 

 

 

 

 

 

 

 

 

Auxiliary 2 – This is one of two secondary initiating switch contacts (JP1 – 10 is the other.)

 

 

3

AUX2

For most applications it is equivalent to AUX1 JP1 – 14. For Vestibule Function use, it is the contact for a switch

 

 

 

 

located within the vestibule. Use with any JP1 ground.

 

 

 

 

 

 

 

 

4

GND

Ground

 

 

 

 

 

 

 

 

 

 

In Vestibule – Used for Vestibule Function. This contact must be connected to the JP1 – 6 terminal from another

 

 

 

 

 

 

 

 

5

INV

unit to receive an initiating signal. The signal is then programed to initiate the unit by setting the VEST DLY rotary

 

 

 

 

switch/timer pot of the receiving unit. Use this contact with any JP1 ground.

 

 

 

 

 

 

 

 

6

OUTV

Out Vestibule – Used for Vestibule Function. This contact must be connecter to terminal JP1 – 5 of another unit to

 

 

send an initiating signal. Use with any JP1 ground.

 

 

 

 

 

 

 

 

 

 

 

7

GND

Ground

 

 

 

 

 

 

 

 

 

Maintain Hold Open – With the unit’s 3 Position Slide Switch in the “ON” position, a signal will open the door and

 

 

8

RFT

maintain an indefinite hold open until a second signal releases the door from hold open. Use with any JP1 ground.

 

 

 

 

This feature recommended for Power Operator Function. If using with the Power Assist Function, consult factory.

 

 

 

 

 

 

 

9

GND

Ground

 

 

 

 

 

 

 

10

AUX2

Auxiliary 2 – Same as JP1 – 3 / AUX2 above.

 

 

 

 

 

 

 

11

GND

Ground

 

 

 

 

 

 

 

12

PDET

Presence Detector – Permits wiring of a presence detector to prevent a closed door from opening or a door that is

 

 

fully open from closing. Use with any JP1 ground.

 

 

 

 

 

 

 

 

 

 

 

13

GND

Ground

 

 

 

 

 

 

 

 

 

Auxiliary 1 – Primary initiating switch contact. Initiates door power cycle. Must be Normally Open Momentary Dry

 

 

14

AUX1

Contact. For Vestibule Function, the switch at outside of vestibule is connected to this terminal. (Outside switch to

 

 

 

 

outside unit’s JP1 – 14. Inside switch to inside unit’s JP1 – 14). Use with any JP1 ground.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

80-9369-0901-021 (12-02 )

3

JP4 Terminal Strip – Maximum wire size 14AWG.

 

TERMINAL

 

 

 

 

 

 

 

D E S C R I P T I O N

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

GND

 

Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

24VDC (unregulated) output to a maximum current draw of 0.500 amps. Use with ground terminal JP4 – 1.

 

 

 

 

 

 

2

 

+24

DO NOT use this supply with 56Latch Retraction Exit Device.

 

 

 

 

 

 

 

 

 

 

 

 

 

A separate 24VDC filtered and regulated supply must be used.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control (Relay Contact Only – 5Amp @ 24VDC) – Normally open contact that is switched by Relay K3 (on main

 

 

 

 

 

3

 

NO1

 

board) to close. Relay K3 will remain switched for a period set by SW – 3 EXSOL DLY rotary switch / timer pot.

 

 

 

 

 

 

 

Use with terminal JP4 – 4 CO1. Coordinate use of this terminal with delayed start of motor using rotary timer pot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW – 2 M DLY.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

CO1

Control (Relay Contact Only – 5Amp @ 24VDC) – Common contact for use with terminals JP4 – 3 NO1 and JP4 - 5

 

 

 

 

 

Nc1.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Control (Relay Contact Only – 5Amp @ 24VDC) – Normally closed contact that is switched by Relay K3 (on main

 

 

 

 

 

5

 

NC1

 

board) to open. Relay K3 will remain switched for a period set by SW – 3 EXSOL DLY rotary switch / timer pot.

 

 

 

 

 

 

 

Use with terminal JP4 – 4 CO1. Coordinate use of this terminal with delayed start of motor using rotary timer pot

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW – 2 M DLY.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Delay (Switching Contact Only – 5Amp @ 24VDC) – Normally open contact that is switched by relay K4 (on

 

 

 

6

 

NO2

 

main board) to close. Relay K4 will remain switched for a period set by Dip Switch SW1 – 2 A/D (OFF = 30 second

 

 

 

 

 

 

delay; ON = 60 second delay). Use with terminal JP4 – 7 Co2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

CO2

 

Alarm Delay (Switching Contact Only – 5Amp @ 24VDC) – Common contact for use with terminals JP4 – 6 NO2

 

 

 

 

 

 

 

and JP4 – 8 NC2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Delay (Switching Contact Only – 5Amp @ 24VDC) – Normally closed contact that is switched by relay K4 (on

 

 

 

8

 

NC2

 

main board) to open. Relay K4 will remain switched for a period set by Dip Switch SW1 – 2 A/D (OFF = 30 second

 

 

 

 

 

 

delay; ON = 60 second delay). Use with terminal JP4 – 7 Co2.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Main Board Switches

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIP SWITCHES (MAIN BOARD)

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

 

 

P/A

Door Operator Function Switch – OFF position selects the Power Operator Function. On

 

 

 

 

 

 

 

 

 

 

position sets the Power Assist Function.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2

 

 

 

A/D

Alarm System Delay Timer – This switch is used in conjunction with terminal Jp1– 1, 0/0 for

 

 

 

 

 

 

 

 

 

optional function 2. (OFF = 30 second delay, ON = 60 second delay).

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

RES1

DIAGNOSTIC USE. FOR FACTORY AUTHORIZED PERSONAL.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

RES2

DIAGNOSTIC USE. FOR FACTORY AUTHORIZED PERSONAL.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROTARY SWITCHES

 

 

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW2

 

 

 

M DLY

This rotary switch or timer pot sets the length of delay for motor start up to allow for “unlocking”

 

 

 

 

 

 

 

of exit devices, electric strikes, magnetic locks, etc. See Chart 1 for delay times.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

This rotary switch or timer pot sets the length of time that a solenoid remains either energized or

 

 

 

 

SW3

 

 

 

EXSOL DLY

de-energized to allow “unlocking”. Used in conjunction with terminals JP4 – 3, JP4 – 4, JP5 – 5.

 

 

 

 

 

 

 

 

 

See Chart 2 for length of time.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

SW4

 

 

 

VEST DLY

This switch or timer pot sets the length of time between receipt of the “In Vestibule” signal

 

 

 

 

 

 

 

 

 

 

 

(terminal JP1 – 5) and motor start-up. See Chart 3 for delay times.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Controls either one of two function times:

 

 

 

 

 

 

 

 

 

 

 

 

SW5

 

 

 

CL/AS DLY

Power Operator Function – Sets length of time door holds open at fully “taught” open position.

 

 

 

 

 

 

Power Assist Function – Sets length of time motor and pump will operate to reduce opening

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

force. When time elapses, the door force reverts to full opening spring force set.

 

 

 

 

 

 

 

 

 

 

 

 

 

Chart 1 – SW2, M DLY

Chart 2 – SW3, EXSOL DLY

Chart 3 – SW4, VEST DLY

Chart 4 – SW5, CL/AS DLY

 

Length of Time

 

 

Settings

 

 

Length of Time

Settings

 

Length of Time

Settings

 

Length of Time

 

Settings

 

 

 

(Seconds)

 

 

 

 

 

(Seconds)

 

(Seconds)

 

(Seconds)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.0

 

 

0

 

 

0

0

 

0

0

 

0

 

 

0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.2

 

 

1

 

 

1

1

 

1

1

 

2

 

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.5

 

 

2

 

 

2

2

 

3

2

 

5

 

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

 

 

3

 

 

4

3

 

6

3

 

10

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

 

 

4

 

 

6

4

 

9

4

 

15

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.5

 

 

5

 

 

8

5

 

14

5

 

20

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3.5

 

 

6

 

 

10

6

 

21

6

 

25

 

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.5

 

 

7

 

 

12

7

 

30

7

 

30

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

80-9369-0901-021 (12-02 )

JP2 Terminal Strip – Factory Wired Connections.

TERMINAL

D E S C R I P T I O N

 

 

L1

White Wire – High side of L1 Input signal from ELS Board. Detects door motion to open door when door is pushed

or pulled in the open direction. Movement of potentiometer on ELS Board signals L1 input.

 

 

 

G

Black Wire – Ground. Common connection for L1 and L2 inputs.

 

 

L2

Blue Wire – High side of L2 Input signal for ELS Board. Detects the Fully Open Position stored in the ELS Board

during the teaching mode.

 

 

 

+V

Yellow Wire +24VDC. This terminal is used to supply power to the ELS Board.

 

 

H

Violet Wire – Hold Open contact of “OFF” “ON” “H/O” switch assembly.

 

 

G

White Wire – Ground. Common contact of “OFF” “ON” “H/O” switch assembly.

 

 

M

Orange Wire – ON contact of “OFF” “ON” “H/O” switch assembly.

 

 

 

Red Wire – Emergency Hold Open Release. This contact is used in conjunction with the ELS board to close the

E

door immediately at any point of door opening once an obstruction on opening is encountered. It is used with

 

terminal JP2 – G.

 

 

G

Black Wire – Ground. Use with terminal Jp2 – E for Emergency Hold Open Release.

 

 

JP5 Terminal Strip – Factory Wired Connections.

TERMINAL

D E S C R I P T I O N

 

 

 

1

NEU

Common 120V connection to Input Power Terminal 22.

 

 

 

2

HOT

Hot 120V connection to Input Power Terminal 24.

 

 

 

3

GND

Ground connection secured to backplate under head of (green) ground screw that is located under Main PC Board.

Screw Labeled “GND”

 

 

 

 

 

4

18VAC

From secondary of 120V / 24V transformer.

 

 

 

5

18VAC

From secondary of 120V / 24V transformer.

 

 

 

JP3 Terminal Strip – Factory Wired Connections.

TERMINAL

D E S C R I P T I O N

 

 

MOTOR

Motor Connection.

 

 

SOLENOID

Solenoid coil connection.

 

 

80-9369-0901-021 (12-02 )

5

Loading...
+ 10 hidden pages