SANDPIPER RHDB2 User Manual

SERVICE & OPERATING MANUAL
II 2GD T5
RHDB2 Hazardous Duty Heavy Duty Ball Valve AirVantage Design Level 1
SAFETY PRECAUTIONS
Engineering, Performance and Construciton Data ............................................................................ 1
Explanation of Pump Nomenclature .................................................................................................. 2
Performance Curve ........................................................................................................................... 3
Dimensions ........................................................................................................................................ 4
Important Installation Information ...................................................................................................... 5
Principle of Pump Operation .............................................................................................................. 7
Principle of AirVantage ...................................................................................................................... 7
Installation and Start-Up .................................................................................................................... 7
Air Supply .......................................................................................................................................... 7
Air Line Moisture ................................................................................................................................ 7
Air Valve Lubrication .......................................................................................................................... 7
Air Inlet and Priming .......................................................................................................................... 7
Between Uses ................................................................................................................................... 7
Pump Troubleshooting ....................................................................................................................... 9
AirVantage Troubleshooting ...................................................................................................... 10-11
Composite Repair Parts List ........................................................................................................... 12
Composite Repair Parts Kits ........................................................................................................... 13
Composite Repair Parts Drawing: Wetted Side ............................................................................... 14
Diaphragm and Check Valve Servicing ........................................................................................... 15
Composite Repair Parts Drawing: Air Side ...................................................................................... 16
BOTTOM PORTED
Intermediate and AirVantage Sensor Servicing ............................................................................... 17
Air Valve Servicing, Assembly Drawings and Parts List .................................................................. 18
Air Valve Servicing with Stroke Indicators, Assembly Drawings and Parts List .............................. 19
Pilot Valve and Actuator Plunger Servicing .................................................................................... 20
Pulse Output Kits and Drawing ....................................................................................................... 21
Composite Repair Parts Drawing - AirVantage Unit ........................................................................ 23
AirVantage Servicing - Pilot Valve and Pressure Regulator ............................................................ 24
AirVantage Servicing - Power Generation Module .......................................................................... 25
AirVantage Servicing - Control Module ........................................................................................... 26
AirVantage Servicing - Sensor Assembly ....................................................................................... 27
AirVantage Servicing - Poppet Valve Drawing ................................................................................. 28
AirVantage Servicing - Poppet Valve .............................................................................................. 29
AirVantage Servicing - Check Valve ............................................................................................... 30
Grounding the Pump ...................................................................................................................... 31
Pumping Hazardous Liquids - Shutdown Procedure ...................................................................... 32
Converting the Pump for Piping Exhaust Air ................................................................................... 32
Material Codes for the Last 3 Digits of the Part Number ................................................................ 33
CE Declaration of Conformity - Machinery ...................................................................................... 34
CE Declaration of Conformity - ATEX .............................................................................................. 35
Declaration of Conformity - IECEx ................................................................................................... 36
US Patent # 6,241,487 US Patent # 7,521,921 Pending
TOP PORTED
II 2GD T4
Ex d ib IIB T4 Gb Ex tb IIIC 135°C Db IP66
-20°C to +40°C Sira 10ATEX1151X IECEx SIR 10.0110X
2350863
Class I Div 1 - Groups C,D T4 Class II Div 1 - Groups F,G Class I Zone 1, Ex d ib IIB T4 Class I Zone 1, AEx d ib IIB T4 Enclosure Type 4X 12 Volt (2 - 8) mA
rhdb2dl1sm_haz duty-rev0614
Warren Rupp, Inc.® • A Unit of IDEX Corporation • 800 N. Main St., Manseld, Ohio 44902 USA
Telephone (419) 524-8388 • Fax (419) 522-7867 • warrenrupp.com
©Copyright 2014 Warren Rupp, Inc. All rights reserved.
Cautions - Read Operating and Safety Precautions First
IMPORTANT
Before installation and
start-up of the pump read
these safety warnings and instructions in this
responsibility of the purchaser to retain this manual for reference. Failure to comply with the recommendations stated in this manual will damage the pump, and void factory warranty.
manual completely. It is the
CAUTION
Before pump operation, inspect all gasketed
fasteners for looseness
caused by gasket creep. Re-
prevent leakage. Follow recommended torques
torque loose fasteners to
stated in this manual.
CAUTION
Pump not designed,
tested or certified to be
powered by compressed natural gas. Powering the pump with natural gas will void the warranty.
WARNING
Before maintenance or repair, shut off the compressed air line, bleed the pressure, and disconnect the air line from the pump. The discharge line may be pressurized and must be bled of its pressure.
Recycling
Warren Rupp is committed to protecting the environment and preventing pollution
for the benet of our employees, as well as local and global communities, now
and in the future.
Many components of SANDPIPER® Metallic AODD pumps are made of recy-
clable materials (see chart on page 32 for material specications). We encourage
pump users to recycle worn out parts and pumps whenever possible. Follow all applicable guidelines if hazardous material has been pumped.
WARNING
In the event of diaphragm rupture, pumped material may enter the air end of the pump, and be discharged into the atmosphere. If
is hazardous or toxic, the air exhaust must be piped to an appropriate area for safe disposition.
pumping a product which
WARNING
Take action to prevent static sparking. Fire or explosion can result, especially when handling ammable liquids.
The pump, piping, valves, containers or other miscellaneous equipment must be grounded. (See page 30)
WARNING
This pump is pressurized
internally with air during
operation. Always make
certain that all bolts are in good condition and that all of the correct bolts are
reinstalled during assembly. Do not open when an explosive atmosphere may be present.
Users of electrical and electronic equipment (EEE) with the WEEE marking per Annex IV of the WEEE Directive must not dispose of end of life EEE as unsorted municipal waste, but use the collection framework available to them for the return, recycle, recovery of WEEE and minimize any potential effects of EEE on the environment and human health due to the presence of hazardous substances. The WEEE marking applies only to countries within the European Union (EU) and Norway. Appliances are labeled in accordance with European Directive 2002/96/EC. Contact your local waste recovery agency for a designated collection facility in your area.
None of the equipment supplied within the AirVantage unit either use of exceed the amounts stated above hazardous substances. A signed declaration from our supplier of the electronic/electrical portion of the
AirVantage unit will be held on le stating their adherence to the RoHS,
2002/95/EC regulation.
The enclosure is non-conducting and may generate an ignition-capable level of electrostatic charges under certain extreme conditions. The user should ensure that the equipment is not installed in a location where it may be sub­jected to external conditions (such as high-pressure steam) which might cause a build-up of electrostatic charges on non-conducting surfaces. Additionally, cleaning of the equipment should be done only with a damp cloth.”
WARNING
When used for toxic or
aggressive uids, the pump should always be ushed clean prior to disassembly.
WARNING
Before doing any
maintenance on the pump, be certain all pressure is completely vented from the pump, suction, discharge,
piping, and all other openings and connections. Be certain the air supply is locked out or made non-operational, so that it cannot be started while work is being done on the pump. Be certain that approved eye protection and protective clothing are worn at all times in the vicinity of the pump. Failure to follow these recommendations may result in serious injury or death.
WARNING
Airborne particles and loud noise hazards.
Wear ear and eye
protection.
WARNING
Substitution of components may impair intrinsic safety.
WARNING
Use safe practices
when lifting
kg
Quality System
II 2GD T5
ISO9001 Certied
Environmental
Management System
ISO14001 Certied
BOTTOM PORTED
US Patent # 6,241,487 US Patent # 7,521,921 Pending
TOP PORTED
II 2GD T4
Ex d ib IIB T4 Gb Ex tb IIIC 135°C Db IP66
-20°C to +40°C Sira 10ATEX1151X IECEx SIR 10.0110X
2350863
Class I Div 1 - Groups C,D T4 Class II Div 1 - Groups F,G Class I Zone 1, Ex d ib IIB T4 Class I Zone 1, AEx d ib IIB T4 Enclosure Type 4X 12 Volt (2 - 8) mA
RHDB2
Hazardous Duty
AirVantage Design Level 1
Heavy Duty Ball
Air-Operated Double Diaphragm Pump
ENGINEERING, PERFORMANCE & CONSTRUCTION DATA
INTAKE/DISCHARGE PIPE SIZE
2" NPT (internal)
CAUTION! Operating temperature limitations are as follows:
CAPACITY
0 to 130 gallons per minute
(0 to 492 liters per minute)
AIR VALVE
No-lube, no-stall
design
SOLIDS-HANDLING
Up to 3/8 in. (9mm)
HEADS UP TO
125 psi or 289 ft. of water
(125 psi or 8.6 bar inlet) (8.6 bar or 88 meters)
Operating Temperatures
DISPLACEMENT/STROKE
.47 Gallon / 1.77 liter
Materials Maximum Minimum
Nitrile: General purpose, oil-resistant. Shows good solvent, oil, water and hydraulic uid resistance. Should not be used with highly polar
solvents like acetone and MEK, ozone, chlorinated hydrocarbons and nitro hydrocarbons.
EPDM: Shows very good water and chemical resistance. Has poor resistance to oil and solvents, but is fair in ketones and alcohols.
Neoprene: All purpose. Resistant to vegetable oil. Generally not affected by moderate chemicals, fats, greases and many oils and solvents. Generally
attacked by strong oxidizing acids, ketones, esters, nitro hydrocarbons and chlorinated aromatic hydrocarbons.
Santoprene®:: Injection molded thermoplastic elastomer with no fabric layer. Long mechanical ex life. Excellent abrasion resistance.
Virgin PTFE: Chemically inert, virtually impervious. Very few chemicals are known to react chemically with PTFE- molten alkali metals, turbulent liquid or
gaseous uorine and a few uoro-chemicals such as chlorine triuoride or oxygen diuoride which readily liberate free uorine at elevated temperatures.
FKM (Fluorocarbon): Shows good resistance to a wide range of oils and solvents; especially all aliphatic, aromatic and halogenated hydrocarbons, acids, animal and vegetable oils. Hot water or hot aqueous solutions (over 70°F) will attack FKM.
Polypropylene:
UHMW Polyethylene:
For specic applications, always consult The Warren Rupp Chemical Resistance Chart
SANDPIPER® pumps are designed to be powered only by compressed air.
190° F
88° C
280° F 138° C
200° F
93° C
275° F 135° C
220° F 104° C
350° F 177° C
180° F
82° C
180° F
82° C
-10° F
-23° C
-40° F
-40° C
-10° F
-23° C
-40° F
-40° C
-35° F
-37° C
-40° F
-40° C
32° F
0° C
32° F
0° C
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 1
Explanation of Pump Nomenclature, RHDB2 Hazardous Duty Ball Valve
Outer Inner Ball Manifold Manifold Shipping Shipping Top Bottom Manifold Outer Inner Diaphragm Diaphragm Intermediate Diaphragm Valve Hard- Diaphragm Valve Seat Sealing Wt. (lbs.) Wt. (lbs.) AirVantage Porting Porting Chamber Chamber Plate Plate Housing Rod Seat ware Material Gasket Rings Top P Bottom P Options
TB-3-A DB-3-A AL AL AL CI PS AL SS SS PS B B CB B 105 112 Y TC-3-A DC-3-A AL AL AL CI PS AL SS SS PS V T CT V 105 112 Y TI-3-A DI-3-A AL AL AL CI PS AL SS SS PS I I CT I 105 112 Y TN-3-A DN-3-A AL AL AL CI PS AL SS SS PS N N CN N 105 112 Y TGI-3-A DGI-3-A AL AL AL CI PS AL SS SS PS I/T T CT V 105 112 Y TGN-3-A DGN-3-A AL AL AL CI PS AL SS SS PS N/T T CT V 105 112 Y TGR-3-A DGR-3-A AL AL AL CI PS AL SS SS PS H/T T CT V 105 112 Y TS-3-A DS-3-A AL AL AL CI PS AL SS SS PS S S CT I 105 112 Y TB-3-I DB-3-I CI CI AL CI PS AL SS SS PS B B CB B 151 161 Y TC-3-I DC-3-I CI CI AL CI PS AL SS SS PS V T CT V 151 161 Y TI-3-I DI-3-I CI CI AL CI PS AL SS SS PS I I CT I 151 161 Y TN-3-I DN-3-I CI CI AL CI PS AL SS SS PS N N CN N 151 161 Y TGI-3-I DGI-3-I CI CI AL CI PS AL SS SS PS I/T T CT V 151 161 Y TGN-3-I DGN-3-I CI CI AL CI PS AL SS SS PS N/T T CT V 151 161 Y TGR-3-I DGR-3-I CI CI AL CI PS AL SS SS PS H/T T CT V 151 161 Y TS-3-I DS-3-I CI CI AL CI PS AL SS SS PS S S CT I 151 161 Y TB-3-S DB-3-S TC-3-S DC-3-S TI-3-S DI-3-S TN-3-S DN-3-S TGN-3-S DGN-3-S TGR-3-S DGR-3-S TS-3-S DS-3-S
Meanings of Abbreviations:
SS SS AL SS PS AL SS SS PS B B CB B 166 173 YSS SS AL SS PS AL SS SS PS V T CT V 166 173 YSS SS AL SS PS AL SS SS PS I I CT I 166 173 YSS SS AL SS PS AL SS SS PS N N CN N 166 173 YSS SS AL SS PS AL SS SS PS N/T T CT V 166 173 YSS SS AL SS PS AL SS SS PS H/T T CT V 166 173 YSS SS AL SS PS AL SS SS PS S S CT I 166 173 Y
A = Compressed Fibre AL = Aluminum B = Nitrile CB
= Conductive Nitrile
CI = Cast Iron
CN = Conductive Neoprene CT = Conductive PTFE DC = Die Cast H/T
= Hytrel® Backup/PTFE
Overlay
I = EPDM I/T = EPDM Backup/PTFE Overlay N = Neoprene N/T
= Neoprene Backup/ PTFE Overlay PS = Plated Steel
S = Santoprene SS = Stainless Steel T = PTFE V = FKM
®
X = AirVantage
  ATEXCertied
Y = US Hazardous Duty
CF-8M Stainless SteelequaltoorexceedingASTMspecicationA743forcorrosionresistantironchromium,ironchromiumnickel,andnickelbasedalloycastingsfor
generalapplications.Commonlyreferredtoas316StainlessSteelinthepumpindustry.
Santoprene is a registered tradename of Exxon Mobil Corp. Hytrel is a registered tradename of E.I. du Pont.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 2
Performance Curve,
Model RHDB2 Performance Curve
Performace based on the following: elastomer fitted pump, flooded suction, water at ambient conditions.
BAR
100
7
6
5
4
HEAD
3
2
1
RHDB2 Hazardous Duty Ball Valve
The use of other materials and varying hydraulic conditions may result in deviations in excess of 5%.
15
10
PSI
(17)
100 PSI (6.9 Bar)
90
80
80 PSI (5.5 Bar)
70
60
60 PSI (4.1 Bar)
50
40
40 PSI (2.8 Bar)
30
20
20 PSI (1.4 Bar)
10
(25)
20
(34)
30 (51)
40 (68)
50 (85)
60 (102)
70 (119)
80
(136)
0
0
0 20 40 60 80 100 120 140
U.S. Gallons per minute
500400300200100
Liters per minute
CAPACITY
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 3
Dimensions: RHDB2 Hazardous Duty
15.50
Dimensions: RHDB2 Hazardous Duty
Bottom Ported
Dimensions are ± 1/8"
Figuresinparenthesis=millimeters
394
AIR INLET 1" FNPT
22.63 575
14.93 379
16.07 408
.18
5
16.43 417
SUCTION AND DISCHARGE PORTS ARE AVAILABLE WITH 2" BSP CONNECTIONS
SUCTION AND DISCHARGE PORTS CAN BE ROTATED 90
26.40 671
FOR VERTICAL PORTING
9.59
Top Ported
Dimensions are ± 1/8"
Figuresinparenthesis=millimeters
15.50 394
3/4" NPT EXHAUST
DISCHARGE PORT 2" FNPT
22.45 570
15.27 388
3.43 87
SUCTION PORT
243
2" FNPT
7.06 179
4X
1.00 25
AIR INLET 1" NPT
8X
.44
[11] MTG.HOLE
16.07 408
.18
5
16.43 417
SUCTION AND DISCHARGE PORTS ARE AVAILABLE WITH 2" BSP CONNECTIONS
SUCTION AND DISCHARGE PORTS CAN BE ROTATED 90
26.40 670
FOR VERTICAL PORTING
9.59 243
DISCHARGE PORT 2" NPT
SUCTION PORT 2" NPT
9.05 230
3/4" NPT EXHAUST
20.89 531
8X
.44
[11] MTG. HOLE
12.50 318
12.50 318
10.50 267
8.63 219
8.63 219
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 4
Important Installation Information
Use of the standard AODD Installation Guide is recommended for pumps
tted with AirVantage technology. Install shut-off valves on both the suction and discharge of the pump. (This will help limit the amount of product that enters the center section of the pump in the event of a diaphragm failure.) Using shut-off valves in conjunction with a drain port also provides a means of allowing the lines to be drained when maintenance needs to be conducted.
When the supply liquid level is above the air inlet of the pump, and a diaphragm fails, the pumped liquid or fumes can enter the air end through the point of failure. When a diaphragm failure is detected, it is best to close the shut-off valves and bleed the lines of product. This will limit the ability of the material being pumped to enter the AirVantage. Failure to do so may result in damage to the AirVantage and air distribution components.
If a diaphragm failure has been detected in pumps tted with AirVantage, the following procedure for shut-down must be used:
1. Close the suction shut-off valve (this will limit any new product from entering the pump)
2. Close the discharge shut-off valve (this will stop any product from reentering the pump)
3. Close the air supply shut-off valve
4. Drain the discharge line
5. Drain the suction line
6. Perform maintenance
Shut O Valve
Shut-O Valve
Suction Port
Dessicant Dryer (Optional)
Unregulated Air Supply to Tranquilizer Filter Regulator PN: 020.107.000
Vacuum Gauge
Drain Port
Flexible Connection
Suggested Installation Guide
Pipe Connection (Style Optional
Flexible Connector
(Optional Piped Exhaust)
Muer
Warren Rupp Tranquilizer Limited to 125 psi (Optional)
Pressure Gauge
Shut-O Valve
Discharge Port
Caution: When performing a direct spray washdown, a
plug must be installed in place of the AirVantage mufer.
Failure to do so may damage internal components. (See page 23)
Flexible Connector
Pipe Connection (Style Optional)
Drain Port
Note: Pipe weight should not be supported by pump connections.
WARNING
In the event of diaphragm rupture, pumped material may enter the air end of the pump, and be discharged
pumping a product which is hazardous or toxic, the air exhaust must be piped to an appropriate area for safe disposition.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 5
into the atmosphere. If
This Page Intentionally Blank
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 6
PRINCIPLE OF PUMP OPERATION
This ball valve tted pump has been equipped with IDEX’s patented AirVantage equipment. To fully understand the operation of the AirVantage, one must rst understand the basics of Air Operated Double Diaphragm (AODD) pumps. AODD’s are powered by compressed air. The compressed air is directed behind each of the exible diaphragms by a
Main Air Valve. Once the diaphragm has reached the end of its stroke, a Pilot Valve is mechanically actuated, sending an air signal back to the Main Air Valve which redirects air to the opposite diaphragm. This causes the diaphragm assemblies, which are connected by a common Diaphragm Rod, to move in a reciprocating action. Air is directed to the inboard side of the diaphragm, which is closest to the center of the pump. This is referred to
as the air side of the diaphragm. The opposite side is commonly called the uid side. Most AODD pumps have a 1:1
ratio design. This means, when the discharge of the pump is closed completely (dead headed), the maximum pressure the pump will create will be equal to the air pressure being applied to the pump. At this point, and only at this point, the
diaphragm will be completely balanced. The air pressure is equivalent to the uid pressure and there will be no movement
of the diaphragm. If the pump is stroking, then the system is not balanced. There will be more pressure applied to the air
side than uid pressure on the uid side.
During each stroke of the pump there are two distinct operations that occur. One diaphragm is moving away from
the center of the pump, moving uid out of the Discharge Manifold, while the other diaphragm is moving toward the center, bringing uid into the Suction Manifold. Considering that the pump has a common suction and discharge port,
these two operations are separated from each other through a series of Check Valves.
PRINCIPLE OF AIRVANTAGE
AirVantage is a special air side device which uses equipment that can accurately monitor the operation of the pump. Based on the monitored information, air is metered to the correct amount to perform the work required, and NOTHING MORE. Once the pump starts up, and the AirVantage is turned on, the LED indicator light will go through a series of patterns. Initially the light will be solid green. This indicates the AirVantage is allowing the pump to reach a steady state. Next, the light will pulse at a very rapid rate. This is called the learn phase. Learn is where the AirVantage monitors the pump in non-AirVantage mode. This will set the parameters for operation in AirVantage mode. In less than one minute, the pump will change tones. The LED indicator light will start an uneven blink when optimization has started. Optimization will be completed once the LED light is blinking in unison with the stroke rate of the pump. All this is completed without
sacricing a signicant amount of ow.
AIR LINE MOISTURE
Water in the compressed air supply can create problems such as icing and freezing of the exhaust air. The
formation of ice in the exhaust can cause the pump to cycle erratically, degrade efciency, or even stop the pump. Fitting
the pump with the AirVantage technology reduces the exhaust temperature. This is due to more energy being extracted from every pulse of air. When more energy is extracted, the temperature of the air is reduced. Some method of air drying will be necessary. Most refrigerant dryers installed on compressors can reduce the dewpoint to about 40° F. This is normally adequate for most pumping applications. If further drying needs to occur due to internal ice build-up, a desiccant dryer can be installed. These air line dryers can lower the dewpoint to around -40° F.
AIR VALVE LUBRICATION
The air valve and pilot valve are designed to operate without lubrication. There may be instances of personal preference or when extremely dry air is being used (instrument quality or nitrogen) that a small amount of lubrication will improve the life of the rubber components being used on the air side of the pump. The lubrication may be added using an air line lubricator (¾” PN: 020.051.001 – 1” PN: 020.052.001). At the point of operation use SAE 10 weight, non detergent oil at a maximum rate of 1 drop per hour for every 20 scfm (9.4 liters/sec) of air consumption. Consult the pump curve to determine this value. The smallest amount needed is preferred.
AIR INLET AND PRIMING
To start the pump, make sure the AirVantage switch is in the off position. Increase the pressure until the pump starts to cycle. The pump stroke rate should slow slightly when the pump is primed. Once the pump is fully primed, increase
the pressure at the regulator until the desired ow rate is achieved. Again, the pump curve can be used to derive this value. If increasing the pressure to the pump does not generate a higher ow rate, then cavitation has occurred. Back the regulator off slightly. To gain the most efciency from the pump, try to run the pump fully primed at all times.
BETWEEN USES
When the pump is being used to move materials that tend to settle out or solidify, the pump should be ushed to
prevent damage. The product that remains in the pump could dry and settle out. This could potentially cause damage to the diaphragms and/or check valves during restart. In freezing temperatures the pump must be completely drained between uses. Due to the addition of the new technology, it is recommended the air supply to the pump be shut off if the pump is going to be shut down for an extended length of time.
INSTALLATION AND START-UP
The pump should be located near the product being pumped, in order to keep the suction line as short as possible.
Minimize the number of ttings between the product and the pump and maintain the line size, if possible. Better results
will always be realized if the line size of the suction line is increased by one size. It's not recommended to hook up rigid pipe directly to the pump. Some method of expansion joint or vibration isolator should be used. A Warren Rupp Tranquilizer the level of the pump, a pressure regulating device may need to be added to the exhaust of the pump (Consult the factory for recommendations).
AIR SUPPLY
The air supply pressure cannot exceed 125 psi (8.6 bar). The air line and associated components (lters,
regulators, solenoid valves, etc.) should not be less than ½” (13 mm). However, 3/4" (19mm) or greater is preferred. An
air line lter-regulator is necessary for the AirVantage installation. The required component (PN: 020.107.000) is available through the distributor. Rigid pipe should not be hooked directly to the air inlet of the AirVantage. A exible hose should be
installed to reduce the strain. Do not let the weight of the air line components be supported by the air inlet of the pump. Failure to provide a means of supporting the weight may result in damage to the pump. If the pump will be shut down for any extended length of time, it is recommended that the air supply to the pump should be shut off.
SPECIAL CONDITIONS FOR SAFE USE For the safe operation of the equipment, it is necessary for the air supply to come from a safe area, therefore, the supplied air shall be clean.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 7
®
is recommended to reduce the pulsation in the ow. If the uid level is more than 10 feet (3 meters) above
WARNING
Hazardous Duty Rating
This pump is certied to be operated in the hazardous areas
listed on the front cover. To maintain this certification, only genuine, approved parts must be used and assembled in accordance to the instructions detailed in this manual by a competent person. Any deviation or modication to this will invalidate certication and may result in serious injury or death.
This Page Intentionally Blank
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 8
PUMP TROUBLESHOOTING
CAUTION! WHENEVER TROUBLESHOOTING OR PERFORMING ANY REPAIRS ON ANY WARREN RUPP, INC. EQUIPMENT, ALWAYS REMOVE THE AIR SUPPLY LINE TO THE PUMP AND WEAR PROPER PERSONAL PROTECTIVE EQUIPMENT.
PUMP WILL NOT CYCLE
What to Check: • The system head exceeds the air supply pressure to the pump. Corrective Action: • Increase the air inlet pressure to the pump. Most diaphragm pumps are
designed for 1:1 pressure at zero ow.
What to Check:• Check ESADS+, including pilot valve assembly and main air valve assembly. Corrective Action: • Disassemble and inspect the main air distribution valve, pilot valve, and
pilot valve actuator pins. Check for scores, wear, or damaged o-rings. Replace parts as necessary. Refer to the exploded view drawing and air valve section (P.18 & 20).
What to Check: • Blocked discharge line. Corrective Action: • Check for obstruction or closed discharge line.
What to Check: • Blocked pumping chamber. Corrective Action: • Disassemble and inspect wetted chambers of the pump. Remove or ush
any obstructions. Refer to page 14 for disassembly.
PUMP CYCLES, BUT WILL NOT FLOW OR FLOW RATE IS UNSATISFACTORY
What to Check: • Restricted or undersized air line. Corrective Action: • Make sure there are no obstructions or restrictions in the air inlet to the
pump. Install proper size air line and/or air line equipment. Refer to air supply section (p.7) air inlet plumbing recommendations.
What to Check: • Restricted or undersized suction piping. Corrective Action: • Make sure there are no obstructions or restrictions in the suction line or
related suction components such as screens or strainers. Install the proper size suction line and/ or equipment. It is recommended that any suction line components and pipe size be at least the same size as the suction line thread size to the pump. Though best results will always be realized if the line size of the suction line is increased by one size. Refer to the installation section (p.5) for recommended suction plumbing recommendations.
What to Check: • Excessive Suction Lift. Corrective Action: • For lifts exceeding 20 feet (6 meters), lling the pump chambers with liquid
will prime the pump in most cases. If not, place pump closer to uid level.
What to Check: • Suction line cavitation. Corrective Action: • If no obstructions are in the suction line of the pump, decrease the inlet
air pressure and/or volume to the pump. This will slow down the diaphragm speed and reduce the cavitation.
What to Check: • Partially blocked exhaust mufer. Corrective Action: • Remove mufer and make sure that some of the material being pumped has
not migrated into the mufer element. If it has, replace the element or clean it and reinstall. If product has made it to the mufer, then the diaphragm assembly will need to be inspected. Refer to the
Diaphragm Replacement section (p.15).
What to Check: • Suction side air leakage or air in the product. Corrective Action: • Visually inspect all suction side gaskets, seals, as well as pipe and pipe
connections.
PUMP CYCLE SEEMS UNBALANCED OR PRODUCES EXCESSIVE VIBRATION
What to Check: • Excessive ooded suction in system. Corrective Action: • Check height of uid above pump. For ooded conditions, exceeding 10 feet
(3 meters) of liquid, install a back pressure device in the exhaust side of the pump.
What to Check: • Worn or misaligned check valve or check valve seat. Corrective Action: • Disassemble the wet end of the pump and inspect check valves and seats
for wear and proper seating. Replace them if necessary. Refer to the Check Valve section (p.15) for disassembly instructions.
What to Check: • Obstructed check valves. Corrective Action: • Disassemble the wet end of the pump and look for obstructions that may
prevent the check valve from seating on the seat. Look for damage on the valve and the seat. Replace them as necessary. Refer to the Check Valve section for disassembly (p.15).
What to Check: • Rigid pipe connections. Corrective Action: • Install exible pipe isolators or expansion joints between the plumbing and
the pump.
What to Check: • Blocked air exhaust mufer. Corrective Action: • Remove mufer, clean or de-ice and reinstall.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 9
What to Check: • Pulsation in the discharge line. Corrective Action: • Excessive pulsation in the discharge line may be corrected by installing a
Warren Rupp Tranquilizer Surge Suppressor.
AirVantage Troubleshooting
Caution! Whenever troubleshooting or performing any repairs on any Warren Rupp, Inc. equipment, always remove air supply line to the pump and wear proper personal protective equipment.
LED OUTPUT FOR AirVantage UNIT
STAT E LED OUTPUT
Startup/Settle/Deadhead Solid Standby/Low Flow 1 Second ON / 1 Second OFF Learn Mode 0.1 Seconds ON / 0.1 Seconds OFF Seek/Optimize 1 Second ON / 0.1 Seconds OFF Steady State/Air Savings OFF / ON in rhythm with Cycle Rate of Pump
AirVantage LED DOES NOT LIGHT UP AT ALL
What to Check:
• Make sure power switch on the control module is turned on, (depressed to the left)
• Make sure air is being supplied to pump or make sure 110 VAC unit has power being supplied to it
Corrective Action:
• Cycle power switch off/on
• Unplug patch cable and cycle power switch off/on
• Consult Factory After Sales Support team
AirVantage LED LIGHTS UP AND STAYS ON SOLID
What to Check:
• Make sure patch cable is plugged in and locked
Corrective Action:
• Consult Factory After Sales Support team
VALVE FIRES ONCE AND IMMEDIATELY RESETS
Corrective Action:
• Consult Factory After Sales Support team
VALVE LED NEVER LEAVES SEEK MODE - AirVantage LED PULSING IN TIME TO PUMP, BUT VALVE NOT ACTUATING AND THE PUMP IS NOT SAVING AIR
Corrective Action:
• Consult Factory After Sales Support team
UNEXPECTED OPERATING CONDITION (AIR SAVINGS OR FLOW RATE)
What to Check:
• Check for varying environmental pumping conditions (changing head or suction)
• Check ice buildup in exhaust area
• Inspect sleeve and spool set for damage
Corrective Action:
• Consult Factory After Sales Support team
PUMP CYCLING IS UNSTABLE OR ERRATIC
What to Check:
• Run pump without AirVantage and check pump operation
• Make sure pump has correct sleeve and spool set installed
• Make sure patch cable plug is connected and locked
• Make sure power wire connectors are tight
Corrective Action:
• Consult Factory After Sales Support team
PUMP RUNNING SLOWLY
What to Check:
• Run pump without AirVantage and check operation
• Cycle the power off/on to the control module to reset controller
• Check ice buildup in exhaust area
• Inspect sleeve and spool set for damage
Corrective Action:
• Consult Factory After Sales Support team
• Cycle the power switch on the control module off/on
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 10
AirVantage Troubleshooting Continued
Page 28
ITEM NO.
PART NUMBER
DESCRIPTION
032.054.000
1 171.092.115
CAPSCREW, HEX SOC, M6 X 35mm
8
2 258.020.147
COVER, END, ATEX
1
3 720.071.360
SEAL, O-RING
4
4 765.004.000
VALVE, SOLENOID
1
5 893.104.000
VALVE, POPPET
1
6 171.091.115
CAPSCREW, HEX SOC, M6 X 25mm
8
7 031.202.000
POWER GENERATION MODULE, ATEX
1
8 258.022.147
COVER, END, ATEX
1
9 020.069.000
REGULATOR
1
10 560.200.360
O-RING
2
11 249.019.000
CONTROL MODULE, RS20 HAZ. DUTY
1
12 560.104.360
O-RING
1
13 165.135.330
CAP, SWITCH
1
14
B27.7M - 3BM1-25
RING, RETAINER
1
15 430.050.147
HOUSING, MUFFLER
1
16 720.073.365
SEAL, DUST VALVE
1
17
HX-SHCS 0.125-40x0.188x0.188-N
CAPSCREW, HEX SOC HD, 5-40 X .25
1
18
BSI 4518 0221-16
O-RING
1
19 530.045.115
MUFFLER, SPARK ARRESTOR
1
20 165.137.115
PLATE, PERFORATED
1
21 535.096.000
TAG, WARNING
1
22 710.010.115
SCREW, SELF TAPPING, 4-24 X .25 LG
6
23 901.051.115
WASHER, FLAT, M6
8
24 535.094.000
TAG, NAME
1
AirVantage RESETS AND ENTERS LEARN MODE TOO FREQUENTLY
What to Check:
• Check for excessive varying environmental pumping conditions (changing head or suction)
• Check ice buildup in exhaust area
• Inspect sleeve and spool set for damage
• Make sure patch cable plug is connected and locked
Corrective Action:
• Consult Factory After Sales Support Team
PUMP STALLS, RESETS, LEARNS, SEEKS AND REPEATS
What to Check:
• Make sure patch cable plug is connected and locked
• Check ice buildup in exhaust area
Corrective Action:
• Consult Factory After Sales Support Team
PUMP MOVES OUT OF STEADY STATE AND NEVER ATTEMPTS TO RELEARN (LED ON)
What to Check:
• Make sure patch cable plug is connected and locked
• Cycle the power off/on to the control module
Corrective Action:
• Consult Factory After Sales Support Team
• Cycle the power switch on the control module off/on
WHAT TO DO IN THE EVENT OF A DIAPHRAGM FAILURE
If a diaphragm failure has been detected in pumps tted with AirVantage,
see page 5 for shut-down procedure. What to Check:
• Has product migrated to the sensor?
Corrective Action:
• If the sensor has been submerged in product, the sensor will need to be replaced. Consult the AirVantage servicing section of the manual for detailed instructions.
What to Check:
• Has product contaminated the check valve cartridge?
Correct Action:
• If a signicant amount of product has made it into the check valve assembly, then the unit will need to
be disassembled for inspection. If the check valve assembly is damaged, then it will need to be replaced. Consult parts list for information.
REGULATOR
O-RING
CONTROL MODULE
O-RING
CAP, SWITCH
O-RING
WASHER, FLAT, M6
CAPSCREW, HEX SOC, M6 X 35mm
WASHER, FLAT, M6
COVER
SEAL, O-RING
VALVE, SOLENOID
VALVE, POPPET
SEAL, O-RING
SEAL, O-RING
CAPSCREW, HEX SOC, M6 X 25mm
POWER GENERATOR MODULE
CAPSCREW, HEX SOC, M6 X 25mm
SEAL, O-RING
COVER
CAPSCREW, HEX SOC, M6 X 35mm
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 11
Composite Repair Parts List
Item Part Number Description Qty
1 031.019.004 Ass’y - Air Valve 1
031.098.001 Ass’y - Air Valve (Pulse Output Application) 1 2 032.063.000 Ass’y - AirVantage 1
3 050.017.360W Ball, Check 4
050.017.364W Ball, Check 4
050.017.365W Ball, Check 4
050.017.354 Ball, Check 4
050.018.354 Ball, Check 4 4 070.006.170 Bearing 2 5 095.073.001 Pilot Valve Assembly 1 6 114.032.156 F Bracket, Intermediate 1 7 115.057.080 Bracket, Mounting, Bottom Port 2
115.176.080 Bracket, Mounting, Top Port 2 8 115.172.159 Bracket, Mounting, R.H. 1 9 115.173.159 Bracket, Mounting, L.H. 1 10 132.002.360 Bumper, Diaphragm 2 11 135.016.162 Bushing, Threaded, W/ O-Ring 560.001.360 2 12 165.138.150 Cap, End, Sensor, Hd Est 2 13 170.024.330 Capscrew, Hex Hd, 7/16-14 X 1 12 14 170.025.330 Capscrew, Hex Head 7/16-14 X 3.00 4 15 170.030.330 Capscrew, Hex Head 1/2-13 X 2.00 4 16 170.045.115 Capscrew, Hex Head 5/16-18 X 1 1/4 4 17 170.060.330 Capscrew, Hex Hd, 7/16-14 X 2.00 12 18 170.125.330 Capscrew, Hex Hd, 5/16-18 X 6 4 19 171.100.115 Capscrew, Hex Hd, 5/16-18 X 2.50 4 20 196.001.157 Chamber, Inner 2 21 196.035.156 Chamber, Outer 2
196.035.010 Chamber, Outer 2
196.035.110 Chamber, Outer 2
196.035.112 Chamber, Outer 2 22 258.023.147 Cover, Sensor 1 23 286.007.354 Diaphragm 2
286.007.356 Diaphragm 2
286.007.360 Diaphragm 2
286.007.363 Diaphragm 2
286.007.364 Diaphragm 2
286.007.365 Diaphragm 2 24 286.020.604 Diaphragm, Overlay 2 25 312.033.156 Elbow, Manifold 2
312.033.010 Elbow, Manifold 2
312.033.110 Elbow, Manifold 2
312.033.112 Elbow, Manifold 2 26 312.121.330 Elbow, Pipe, 45deg, 3/4 NPT 1 27 334.025.156 Flange, Threaded 2
334.025.010 Flange, Threaded 2
334.025.110 Flange, Threaded 2
334.025.112 Flange, Threaded 2 28 334.026.156 Flange, Porting, Suction 1
334.026.010 Flange, Porting, Suction 1
334.026.110 Flange, Porting, Suction 1
334.026.112 Flange, Porting, Suction 1 29 334.027.156 Flange, Porting, Discharge 1
334.027.010 Flange, Porting, Discharge 1
334.027.110 Flange, Porting, Discharge 1
334.027.112 Flange, Porting, Discharge 1 30 360.041.379 Gasket, Pilot Valve 1 31 360.048.425 Gasket, Main Air Valve 1 32 360.049.425 Gasket, Flange 2
360.049.603 Gasket, Flange 2 33 360.050.379 Gasket, Manifold 4
360.050.384 Gasket, Manifold 4
360.050.608 Gasket, Manifold 4
Item Part Number Description Qty
34 518.027.156 Manifold 1
518.027.010 Manifold 1
518.027.110 Manifold 1
518.027.112 Manifold 1
35 530.041.000 Mufer 1
36 538.108.110 Nipple, Pipe 1 37 545.004.330 Nut, Hex, 5/16-18 2 38 545.005.330 Nut, Hex, 3/8-16 4 39 545.007.330 Nut, Hex, 7/16-14 4 40 545.008.330 Nut, Hex, 1/2-13 12 41 560.001.360 O-Ring 2 42 560.011.360 O-Ring 2 43 560.022.360 O-Ring 2 44 560.033.360 O-Ring 2 45 560.047.360 O-Ring 2 46 560.200.360 O-Ring 1 47 560.201.360 O-Ring 2 48 560.203.360 O-Ring 2 49 570.009.360 Pad, Wear 2
570.009.363 Pad, Wear 2
570.009.364 Pad, Wear 2
570.009.365 Pad, Wear 2 50 612.047.330 Plate, Diaphragm 2 51 612.241.147 Plate, Adapter 1 52 612.039.157 Plate, Outer Diaphragm 2
612.039.010 Plate, Outer Diaphragm 2
612.097.110 Plate, Outer Diaphragm 2
612.097.112 Plate, Outer Diaphragm 2 53 618.003.330 Plug, Pipe, 1/4 2 54 618.003.330 Plug, Pipe, 1/4 4
618.003.110 Plug, Pipe, 1/4 4 55 620.011.114 Plunger, Actuator 2 56 675.013.360 Ring, Sealing 2
675.013.363 Ring, Sealing 2
675.013.364 Ring, Sealing 2
675.013.365 Ring, Sealing 2
675.013.600 Ring, Sealing 2 57 685.007.120 Rod, Diaphragm 1 58 685.032.080 Rod, Connecting 1 59 720.004.360 Seal, U-Cup 2 60 722.035.110 Seat, Check Valve (for use with PTFE balls only) 2
722.035.112 Seat, Check Valve (for use with PTFE balls only) 2
722.097.110 Seat, Check Valve 2
722.097.112 Seat, Check Valve 2 61 724.008.000 Sensor, Feed Back 1 62 770.074.159 Spacer 8 63 807.026.330 Stud, 5/8-11 X 2 2 64 807.038.330 Stud, 3/8-16 X 2.75 4 65 807.039.330 Stud, 1/2-13 X 2.50 12 66 846.001.167 Probe Tip 2 67 894.014.000 Valve, Check 1 67a 031.206.000 Cartridge, Check Valve 1 68 900.003.330 Washer, Lock, 1/2 20 69 900.004.330 Washer, Lock - 5/16 4 70 900.005.330 Washer, Lock, 3/8 4 71 900.006.330 Washer, Lock, 7/16 12 72 901.022.330 Washer, Flat, 7/16 8 73 902.003.000 Washer, Sealing 2 74 P126-0011 Foam, Sensor, Est 2 75 P126-0032 Capscrew, Soc Hd, 8-32 X 7/16 8 76 475.101.000 Rubber Foot Kit 1
Note: The only difference between this and RHDF2 Parts list is the change to item 2, and removing item 68 (920.028.000), bumping up the last 2 parts
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 12
Composite Repair Parts Kits
Available Service And Conversion Kits
Air End Kit - 476.247.162
Seals, O-rings, Gaskets, Air Valve Sleeve and Spool Set, and Pilot Valve Assembly
Wet End Kit – 476.245.354 (RHDB2, HDB2)
Santoprene Diaphragms, Balls and EPDM Wear Pads, Sealing Rings, and PTFE Gasket
Wet End Kit – 476.245.360 (RHDB2, HDB2) Nitrile Diaphragms, Balls, Wear Pads, Gasket, and Sealing Rings Wet End Kit – 476.245.364 (RHDB2, HDB2)
EPDM Diaphragms, Balls, Wear Pads, and Sealing Ring, and PTFE Gasket
Wet End Kit – 476.245.365 (RHDB2, HDB2)
Neoprene Diaphragms, Balls, Wear Pads Gasket, and Sealing Ring (Note: All Wetted End Kits listed above contain Fiber Gaskets, and Nitrile O-Rings
Wet End Kit – 476.245.633 (RHDB2, HDB2)
FKM Diaphragms, Wear Pads, and Sealing Rings, and PTFE Balls, O-Rings, & Gaskets
Wet End Kit – 476.043.635 (RHDB2, HDB2)
Neoprene Diaphragms, and PTFE Overlay Diaphragm, Balls, Sealing Rings, O-Rings, & Gaskets
Wet End Kit – 476.043.663 (RHDB2, HDB2)
Hytrel Diaphragms, and PTFE Overlay Diaphragm, Balls, Sealing Rings, O-Rings, & Gaskets
Sealing RingsSensor Kit - 476.307.000
(Sensor, Probe Tips and O-rings)
Poppet Valve Kit
(Poppet Valve Assembly, O-ring)
Poppet Valve Assembly Kit
(Poppet Valve Assembly, O-ring, Regulator and Pilot Valve)
Control Module Kit – 476.303.000 (Power Gen AirVantage Only)
(Control Module Assembly, Gaskets, Hardware and O-rings)
Power Gen Kit – 476.293.000 (Power Gen AirVantage Only)
(Power Gen, Gasket, Hardware and O-ring)
Seal Kit – 476.280.000
O-rings and Gaskets
Probe Tip Kit – 476.283.000
(Probe Tips and O-rings)
Midsection Upgrade Kit – 475.XXX.000 Consult Factory
(Replaces S20 Metallic Midsection with AirVantage Components)
Electronic Leak Detector Kits
032.037.000 100-120/220-240 VAC
032.045.000 12-32 VDC
GASKET, PILOT VAVLVE
PILOT VALVE
GASKET, MAIN AIR VALVE
BUMBER, AIR VALVE
GASKET, AIR VALVE
SEAL, U-CUP
O-RING
BUSHING
PLUNGER, ACTUATOR
O-RING
AIR END KIT
DIAPHRAGM
PAD, WEAR
O-RING
GASKET, MANIFOLD
DIAPHRAGM, OVERLAY
BALL, CHECK
WETTED END KIT
RING, SEALING
GASKET, MANIFOLD
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 13
Composite Repair Parts Drawing: Wetted Side
MANIFOLD ASSEMBLY
BOTTOM PORTED CONFIGURATION
26
35
13
68
27
40
68
29
3
336033
65
34
65
3
60
33
33
28
68
40
27
68
13
39
17
1414
17
21
32
25
68
64
15
38
2
18
51
42
54
14
36
EST UNIT ASSEMBLY
TOP PORTED CONFIGURATION
Note: Refer to Composite Repair Parts List on page 12 for part numbers
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 14
DIAPHRAGM AND CHECK VALVE SERVICING
To service the diaphragms, rst shut off and bleed the air being supplied to the pump. For safety purposes the air supply line should be disconnected from the pump.
• Then shut off the suction and discharge lines to the pump.
• Bleed the pressure from the pump suction and discharge lines and remove the lines from the pump.
• Drain any remaining liquid from the pump.
• During the servicing of the diaphragms, consult the “Composite Repair Parts Drawing” (p.7).
Step #1: Removing the Manifolds
• Using a 9/16" wrench or socket, remove the 16 cap-screws, hex-nuts, and lockwashers that fasten the manifolds to the outer chambers.
• Remove the manifolds.
Step #2: Inspect Check Valve Components
• Inspect the four check balls for wear, abrasion or cuts on the spherical surface. Also inspect the four check valve seats for cuts, abrasive wear or embedded material around the area where the ball contacts the seat.
For maximum pump performance and efciency, the surface of the ball must seal against the seat without any gaps.
• Replace worn or damaged parts as necessary. Consult the “Composite Repair Parts Drawing” for part numbers and quantities.
Step #3: Removing the Outer Chambers
• Using an 11/16" and a 5/8" wrench or socket, remove the 16 cap-screws, and hexnuts that fasten the outer chambers, diaphragms, and inner chambers.
Step #4: Removing the Diaphragm Assemblies
• Once the outer chambers are removed, use a 1-1/16” (27mm) wrench or six-pointed socket to remove the diaphragm assemblies (outer plate, diaphragm, and inner plate) from the diaphragm rod by turning counterclockwise.
• “AirVantage CAUTION” – When diaphragm assemblies are removed, watch for the brass probe tips located on the end of the sensor rod. There is one brass probe tip and one o-ring per side. Inspect the probe tips and o-rings for wear. For every diaphragm service, these parts should be replaced and are available in kit form. Consult the “Composite Repair Parts Drawing” for part numbers and quantities.
• The diaphragm connecting rod will usually stay with one of the diaphragm assemblies. Install the rod in
a vise tted with soft jaws and loosen the diaphragm assembly from the rod. Take care not to scar the
surface of the rod.
• Insert a 1/4-20 capscrew or set screw into the smaller tapped hole in the inner diaphragm plate.
• Insert the protruding stud and the 1/4-20 fastener loosely into a vise. Use the 1-1/16" wrench or socket to remove the outer diaphragm plate by turning counter-clockwise.
Step #5: Inspect Diaphragms, Diaphragm Connecting Rod, U-cup Seals and Bumpers
Inspect the diaphragms for cuts and/or punctures in the exing area. Even the smallest hole or crack can allow product to get to the air side of the pump. If there is product noticed on the air side of the diaphragm, there is a good possibility the diaphragm needs to be replaced.
• “AirVantage CAUTION” – If product is observed on the air side of the diaphragm, refer to the “AirVantage Servicing” section of the service manual.
• Abrasive wear of the diaphragm needs to be inspected at the point where the diaphragm contacts the outer chamber or where the diaphragm plates contacts the diaphragm. Chemical attack of a diaphragm will usually result in swelling or deformity. Replace the diaphragms if necessary. Inspect the diaphragm connecting rod for scars, nicks or any imperfection that could cause damage to the u-cup seal. Inspect the u-cup seal for imperfections on the sealing lip. Inspect the bumpers for damage on the face.
Replace components as necessary. Consult the “Composite Repair Parts Drawing” for part numbers and quantities.
Step #6: Assemble the Diaphragms
• Push the threaded stud of the outer diaphragm plate through the center hole of the diaphragm. Thread the inner plate clockwise onto the stud.
• Insert the loose assembly with the above 1/4-20 fastener back into the vise. Use a torque wrench and 1-1/16” socket (27 mm) to tighten the diaphragm assembly together to 480 in.-lbs. (54.23 Newton meters).
• Allow a torqued assembly to set for 15-minutes. This will allow the diaphragm to relax. Re-torque the assembly to compensate for stress relaxation in the clamped assembly.
Step #7: Installing the Diaphragm Assemblies to the Pump
• Make sure the bumper is installed over the diaphragm rod. Thread the stud of the one diaphragm assembly clockwise into the tapped hole at the end of the diaphragm rod until the inner diaphragm plate
is ush to the end of the rod.
• “AirVantage CAUTION” – With the pump lying on one inner chamber, pull the sensor rod UP the full length of its stroke. Insert the brass probe tip and o-ring into the sensor rod. Insert rod and diaphragm assembly into pump, taking care not to damage the u-cup seal. Make sure the diaphragm plate contacts the brass probe tip and stays in contact with it. This will help make sure the probe tip does not fall out during reassembly.
• Align the bolt holes in the diaphragm with the bolt pattern in the inner chamber. Fasten the outer chamber to the pump, using the cap screws, and hex nuts, but do not tighten. Flip the pump over so that it is now setting on the outer chamber. Pull the diaphragm rod out as far as possible. Make sure the bumper is installed over the diaphragm rod.
• “AirVantage CAUTION” – Install the second brass probe tip and o-ring on the sensor rod.
• Thread the stud of the remaining diaphragm assembly clockwise into the tapped hole at the end of the diaphragm rod (item 34) until the diaphragm plate contacts the end surface of the diaphragm rod. If the bolt holes in the diaphragm do not line up with the inner chamber, use a 1-1/16” (27 mm) socket or wrench to tighten the assembly until they line up.
• Fasten the remaining outer chamber to the pump, using the cap screws and hex nuts, and once again,
do not tighten at this point. Tip the pump 90° and set it on a at surface with the discharge side of the
chambers down. This will allow the outer chambers to be aligned with each other. Tighten the sixteen fasteners. Make sure to use a cross tightening pattern to ensure an even sealing on the diaphragm.
Step #8: Re-install the Check Valve Components and Manifolds
• While the pump is setting on the discharge side, insert the check balls and seats on the suction side of
the pump. Make sure the seats t within the counter bore of the chambers. The suction manifold can
now be installed, using the eight cap screws, hex nuts and lock washers.
• Flip the pump 180° and install the seats and check balls on the discharge side.
• Now the discharge manifold can be installed and fastened using the remaining cap screws, hex nuts, and lock washers.
OVERLAY DIAPHRAGM SERVICING
The overlay diaphragm is a PTFE diaphragm
that ts over the exterior of the diaphragm. The
PTFE diaphragm is used to protect the standard diaphragm from the chemicals being pumped. Repeat step #6 when diaphragms need to be serviced.
this manual for reference. Failure to comply with the recommendations stated in this manual will damage the pump, and void factory warranty.
IMPORTANT
Read these instructions completely, before installation and start-up. It is the responsibility of the purchaser to retain
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 15
Composite Repair Parts Drawing: Air Side
24
22
33
INTERMEDIATE ASSEMBLY
(SHOWN ROTATE 180
5
4
6
7
18
17
14
3
)
4
1
10
8
5
4
PTFE OVERLAY
CONFIGURATION
13
71
31
27
28
26
1
30
7
12
13
11
20
35
18
17
21
32
16
15
35
2
19
22
24
23
25
34
33
Note: Refer to Composite Parts List on page 12 for part numbers
7676767676
36
37
38
BOTTOM PORTED CONFIGURATION
TOP PORTED CONFIGURATION
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 16
A
BRACKET, INTERMEDIATE, ASSEMBLY
SENSOR, FEEDBACK
NUT
SEAL
DIAPHRAGM
PLATE, OUTER DIAPHRAGM
PLATE, INNER DIAPHRAGM
PROBE TIP
O-RING
SENSOR, FEEDBACK
BUMPER
DETAIL A
FLAT EDGE
INTERMEDIATE AND AirVantage SENSOR SERVICING
To service the intermediate and AirVantage sensor, rst shut off and bleed the air being supplied to the pump. For safety purposes, the air supply line should be disconnected from the pump. Shut off both the suction and discharge lines to the pump. Consult the “Composite Repair Parts Drawing”.
Step #1: Remove the Patch Cable
• Twist the ribbed portion of the patch cable connector in a counterclockwise direction, until it unthreads from the connector. The cable can either be removed from the intermediate or from the control module.
Step #2: Remove the AirVantage from the Pump
• Use a ½” socket and remove the four 5/16-18 x 5 ½ cap screws that hold the AirVantage to the pump. Be sure to support the weight of the AirVantage while removing the last cap screw. After the AirVantage is removed from the pump, set the unit down on the plastic cover located on the bottom.
Step #3: Remove the Manifolds, Chambers, and Diaphragms (See Diaphragm Servicing Section)
Step#8: Reinstallation
• Slide the new sensor assembly in the intermediate.
“AirVantage CAUTION” – Make sure the cable assembly ts into the groove machined in the intermediate. Failure to do so may damage the cable during assembly.
• Feed the connector through the hole in the intermediate, making sure the gasket is on the connector
before installation. The at edge on the connector should line up with the inside of the intermediate.
Install the nut and hand tighten it using a 13/16" socket.
• The inner chambers and gaskets can now be reinstalled. Use blue thread locker on the inner chamber bolts and torque them to 300 in-lbs.
Refer to the “Diaphragm Servicing” section of the manual to nish the diaphragm installation procedure.
Step #4: Remove the Diaphragm Assemblies
• Refer to the “Diaphragm Servicing” section of the manual to remove diaphragm assembly from the pump.
• “AirVantage CAUTION” – When the diaphragm assembly is removed, watch for the brass probe tips located on the end of the sensor rod. There is one brass probe tip and one o-ring per side. Inspect the probe tips and o-rings for wear. For every diaphragm service, these parts should be
replaced and are available in kit form. Consult the “Composite Repair Parts Drawing” for part numbers and quantities.
• Note: For AirVantage sensor servicing, refer to page 27.
Step #5: Remove the End Caps
• Use an Allen wrench and remove the two screws from the End Caps on either side of the intermediate.
Use two small at-head screw drivers to simultaneously pry the End Caps up at the ends.
• “AirVantage CAUTION” – Remove the End Caps from the intermediate with caution, taking care not to damage the sensor. Inspect the gaskets and u-cup seals under each End Cap and replace them as necessary.
Step #6: Accessing the Actuator Plunger Bushings and O-rings
• The actuator plunger pin bushings and o-rings can now be accessed. If it is determined that these parts need to be replaced, use a small screwdriver and remove the retaining rings.
• NOTE: It is recommended that new retaining rings be installed after disassembly. The bushing and o-ring can now be removed and inspected.
Step #7: Accessing the AirVantage Sensor
• If the sensor needs to be replaced, use a 13/16” socket and remove the plastic nut securing the connector to the intermediate. Slide the connector out of the hole, taking care not to lose/misplace the gasket on the connector.
• The sensor can now be removed from the intermediate assembly.
JAM NUT
O-RING
FOAM BUMPER
BEARING
SENSOR COVER
CAPSCREW
INTERMEDIATE
SEAL
FEED BACK SENSOR
O-RING
Note: Refer to Composite Repair Parts List on page 12 for part numbers
END CAP
CAPSCREW
CAPSCREW
PLATE,
OUTER DIAPHRAGM
PAD, WEAR
DIAPHRAGM
PLATE, DIAPHRAGM
WASHER, SEALING
PROBE TIP
O-RING
SENSOR, FEED BACK
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 17
Page 17
Air Valve Servicing, Assembly Drawing & Parts List
1.B
1.A1.A
1.C
1.F
1.D
1.E
1.F
1.C
1.F
1.D
Note to Trent: Do not paste this table in S/M. Only use to modify on on page 18
ITEM
NO.
PART NUMBER DESCRIPTION
QTY.
1.A
031.012.162
SLEEVE & SPOOL SET
1
1.B
095.043.156
DESCRIPTION
1
1.C
132.014.358
BUMBER, AIR VALVE
2
1.D
165.011.157
CAP, END
2
1.E
170.032.330
CAPSCREW, HEX HEAD 1/4-20 X 3/4
8
1.F
360.010.427
BODY, AIR VALVE
2
1.F
560.020.360
O-RING
6
AIR VALVE ASSEMBLY PARTS LIST Item Part Number Description Qty 1 031-183-003 Air Valve Assembly 1
1-A 031.012.162 Sleeve and Spool Set 1 1-B 095.043.156 Description 1 1-C 132-014.358 Bumper, Air Valve 2 1-D 165.011.157 Cap, End 2 1-E 170.032.330 Capscrew, Hex Head 1/4-20 x 3/4 8 1-F 360.010.427 Body, Air Valve 2 1-F 560.020.360 O-ring 6
AIR DISTRIBUTION VALVE SERVICING STEP #1: Remove Air Valve
The main air valve sleeve and spool set is located in the valve body mounted on the pump with four hex head cap-screws. The valve body assembly is removed from the pump by removing these four hex head cap-screws.
STEP #2: Disassembly of the Air Valve
With the valve body assembly off the pump, access to the sleeve and spool set is made by removing four hex head cap-screws (each end) on the end caps of the valve body assembly. With the end caps removed, slide the spool back and forth in the sleeve. The spool is closely sized to the sleeve and must move freely to allow for proper pump operation. An accumulation of oil, dirt or other
contaminants from the pump’s air supply, or from a failed diaphragm, may prevent the spool from moving
freely. This can cause the spool to stick in a position that prevents the pump from operating. If this is the case, the sleeve and spool set should be removed from the valve body for cleaning and further inspection. Remove the spool from the sleeve. Using an arbor press or bench vise (with an improvised mandrel), press the sleeve from the valve body. Take care not to damage the sleeve. At this point, inspect the o-rings on the sleeve for nicks, tears or abrasions. Damage of this sort could
happen during assembly or servicing. A sheared or cut o-ring can allow the pump’s compressed air supply
to leak or bypass within the air valve assembly, causing the pump to leak compressed air from the pump
air exhaust or not cycle properly. This is most noticeable at pump dead head or high discharge pressure conditions. Replace any of these o-rings as required or set up a routine, preventive maintenance schedule to do so on a regular basis. This practice should include cleaning the spool and sleeve components with a safety solvent or equivalent, inspecting for signs of wear or damage, and replacing worn components.
Reassembly of the Air Valve
To re-install the sleeve and spool set, lightly lubricate the o-rings on the sleeve with an o-ring assembly lubricant or lightweight oil (such as 10 wt. air line lubricant). Re-install one end cap, gasket and bumper on the valve body. Using the arbor press or bench vise that was used in disassembly, carefully press the sleeve back into the valve body, without shearing the o-rings. You may have to clean the surfaces of the valve body where the end caps mount. Material may remain from the old gasket. Old material not cleaned from this area may cause air leakage after reassembly. Take care that the bumper stays in place allowing the sleeve to press in all the way. Reinstall the spool, opposite end cap, gasket and bumper on the valve body. After inspecting and cleaning the gasket surfaces on the valve body and intermediate, reinstall the valve body on the pump using new gaskets. Tighten the four hex head cap-screws evenly and in an alternating cross pattern.
IMPORTANT
Read these instructions completely, before
installation and
start-up. It is the responsibility of the
purchaser to retain this manual for reference. Failure to comply with the recommendations stated in this manual will damage the pump, and void factory warranty.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 18
Air Valve with Stroke Indicator Assembly Drawing and Parts List
1.D
1.F
1.C
1.A1.A
1.F
1.B
1.G
1.D
1.E
1.H
Note to Trent: Do not paste this table in S/M. Only use to modify on on page 19
AIR VALVE ASSEMBLY PARTS LIST
Item Part Number Description Qty 1 031-147-003 Air Valve Assembly 1
1-A 031-012.162 Sleeve and Spool Set 1 1-B 095-043.156 Description 1 1-C 132-014.358 Bumper, Air Valve 2 1-D 165-065.010 Cap, End 2 1-E 170.032.330 Capscrew, Hex Head 1/4-20 x 3/4 8 1-F 360.010.427 Body, Air Valve 2 1-F 560.020.360 O-Ring 6 1-G 210-008-330 Clip, Safety 1 1-H 560-029-360 O-Ring 2
Air Distribution Valve With Stroke Indicator Option Servicing
To service the air valve rst shut off the compressed air supply, bleed the pressure from the pump, and
disconnect the air supply line from the pump.
Step #1: See COMPOSITE REPAIR PARTS DRAWING.
Using a 5/16" Allen wrench, remove the four hex socket capscrews and four at washers. Remove the air valve assembly from the pump.
• Remove and inspect gasket for cracks or damage. Replace gasket if needed.
Step #2: Disassembly of the air valve.
To access the internal air valve components rst remove the two retaining rings from each end of the air valve assembly using clip ring pliers.
• Next remove the two end caps. Inspect the o-ring for cuts or wear. Replace the o-rings if necessary.
• Remove the two bumpers. Inspect the bumpers for cuts, wear or abrasion. Replace if necessary.
• Remove the spool from the sleeve. Be careful not to scratch or damage the outer diameter of the spool. Wipe spool with a soft cloth and inspect for scratches or wear.
• Inspect the inner diameter of the sleeve for dirt, scratches, or other contaminants. Remove the sleeve if needed and replace with a new sleeve and spool set.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 19
Step #3: Reassembly of the air valve.
• Install one bumper and one end cap with o-rings into one end of the air valve body. Install one retaining ring, into the groove on the same end. Insert the safety clip through the smaller unthreaded hole in the endcap.
• Remove the new sleeve and spool set from the plastic bag. Carefully remove the spool from the sleeve. Install the six o-rings into the six grooves on the sleeve. Apply a light coating of grease to the o-rings before installing the sleeve into the valve body. Align the slots in the sleeve with the slots in the valve body. Insert the spool into the sleeve. Be careful not to scratch or damage the spool
IMPORTANT
during installation. Push the spool in until the pin touches the safety clip on the opposite end.
• Install the remaining bumper, end cap with o-rings and retaining ring.
• Fasten the air valve assembly and gasket to the pump.
• Connect the compressed air line to the pump. Remove the safety clip. The pump is now ready for operation.
manual for reference. Failure to comply with the recommendations stated in this manual will damage the pump, and void factory warranty.
Read these instructions completely, before
installation and
start-up. It is the responsibility of the purchaser to retain this
Pilot Valve and Actuator Plunger Servicing
Step #1: Remove the Patch Cable
• Twist the ribbed portion of the patch cable connector in a counterclockwise direction, until it unthreads from the connector. The cable can either be removed from the intermediate or from the control module.
Step #2: Remove the AirVantage from the Pump
• Use a ½” socket and remove the four 5/16-18 x 5½ cap screws that hold the AirVantage to the pump. Be sure to support the weight of the AirVantage while removing the last cap screw. After the AirVantage is removed from the pump, carefully set the unit down on the plastic cover located on the bottom.
STEP #3: Remove the Pilot Valve
• Remove the main air distribution valve body from the pump.
• Lift the pilot valve body out of the intermediate housing. (Most problems with the pilot valve can be corrected by replacing the o-rings.)
STEP #4: Dissasemble the Pilot Valve
• Remove the pilot spool and wipe it clean. Inspect the spool and o-rings for dirt, cuts or wear. Replace parts if necessary.
• Use a set of outside snap ring pliers and remove the retaining ring holding the sleeve in the pilot valve body.
• Gently push the sleeve from the body and wipe it clean. Inspect the sleeve and o-rings.
• Replace parts if necessary
STEP #5: Inspect the Actuator Plungers
Remove the plungers by sliding them out of the bushings. It may be necessary to use a ne piece of wire to pull them out.
STEP #6: Reassemble the Pilot Valve
• Generously lubricate the o-rings on the pilot sleeve with multipurpose grease (BP-LSEP-2 or equivalent).
• Carefully insert the sleeve in the pilot valve body on the chamfered side, taking care not to shear any of the o-rings.
• Securely insert the retaining ring around the sleeve.
• Generously lubricate the o-rings on the pilot spool. Carefully insert the spool in the sleeve.
If the pilot valve does not t ush against the gasket, check to make sure the actuator plunger are pushed all the way. Failure to do so may cause damage to the pilot valve or the actuators.
• Insert the pilot valve body onto the intermediate housing.
• Reinstall the main air distribution valve body onto the pump.
Step #8: Reassemble AirVantage and Cable
• Reinstall the AirVantage using the four 5/16-18 x 5½ cap screws and torque to 90 in-lbs.
• Reattach the patch cable connector that connects the AirVantage module to the intermediate.
Item Part Number Description Qty
4.A 095.070.558 BODY, Pilot VALVE 1
4.B 755.025.162 SLEEVE, Pilot VALVE 1
4.C 560.033.360 O-RING 4
4.D 775.026.115 SPOOL, Pilot VALVE 1
4.E 560.023.360 O-RING 2
4.F 675.037.080 RING, RETAINING 1
5
28
4.A
4.F
15
49
35
4.B
4.D
10
STEP #7: Reinstall the Pilot Valve
• Push both plungers (located inside the intermediate bracket) out of the path of the pilot valve spool ends to avoid damage.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 20
29
1
4.C
4.E
Note: Refer to Composite Repair Parts List on page 12 for part numbers
Pulse Output Kit Drawing
PULSE OUTPUT KIT OPTION
This pump can be tted with a Pulse Output Kit. This converts the mechanical strokes of the
pump to an electrical signal which interfaces with the Stroke Counter/ Batch Controller or user control devices such as a PLC.
The Pulse Output Kits mount directly onto the Mufer Cap on the Air Distribution Valve Assembly
or onto the air valve and senses each stroke of the main spool.
Consult the factory for further information and availability.
Pulse Output Kits
475-244-001 10-30 VDC
475-244-002 110/220 VAC
475-244-003 10-30VDC, 110VAC and 220 VAC
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 21
This Page Intentionally Blank
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 22
Composite Repair Parts Drawing: AirVantage Unit
Page 23
ITEM NO.
PART NUMBER
DESCRIPTION
032.054.000
1 171.092.115
CAPSCREW, HEX SOC, M6 X 35mm
8
2 258.020.147
COVER, END, ATEX
1
3 720.071.360
SEAL, O-RING
4
4 765.004.000
VALVE, SOLENOID
1
5 893.104.000
VALVE, POPPET
1
6 171.091.115
CAPSCREW, HEX SOC, M6 X 25mm
8
7 031.202.000
POWER GENERATION MODULE, ATEX
1
8 258.022.147
COVER, END, ATEX
1
9 020.069.000
REGULATOR
1
10 560.200.360
O-RING
2
11 249.019.000
CONTROL MODULE, RS20 HAZ. DUTY
1
12 560.104.360
O-RING
1
13 165.135.330
CAP, SWITCH
1
14
B27.7M - 3BM1-25
RING, RETAINER
1
15 430.050.147
HOUSING, MUFFLER
1
16 720.073.365
SEAL, DUST VALVE
1
17
HX-SHCS 0.125-40x0.188x0.188-N
CAPSCREW, HEX SOC HD, 5-40 X .25
1
18
BSI 4518 0221-16
O-RING
1
19 530.045.115
MUFFLER, SPARK ARRESTOR
1
20 165.137.115
PLATE, PERFORATED
1
21 901.051.115
WASHER, FLAT, M6
8
22 535.096.000
TAG, WARNING
1
23 710.010.115
SCREW, SELF TAPPING, 4-24 X .25 LG
6
24 535.094.000
TAG, NAME
1
1
21
2
3
9
10
11
12
13
10
14
15
16
17
18
19
20
4
5
3
3
6
7
6
3
8
21
1
ITEM No. PART NUMBER DESCRIPTION QTY.
3 720.004.360 SEAL, O-RING 4
4 765.004.000 VALVE, SOLENOID 1
5 893.104.000 VALVE, POPPET 1
8 258.019.000 COVER, END 1
9 020.069.000 REGULATOR 1
10 560.200.360 SEAL, O-RING 2
11
13 165.135.330 CAP, SWITCH 1
171.092.115
171.091.115
031.202.000
249.028.000
560.104.360
675.067.115
430.050.147
720.073.365
171.093.115
560.205.360
530.045.115
165.137.115
,WERCSPAC1 HEX SOC HD, M6-1.0 x 35 8
,WERCSPAC6 HEX SOC HD, M6-1.0 x 25 8
REWOP7 GENERATION MODULE 1
LORTNOC MODULE
, RHDF2 Hazardous Duty
,LAES21 O-RING 1
RING, RETAINING
,WERCSPAC71 HEX SOC HD, 5-40 x .25 1
,PAC51 DUST 1
,EVLAV61 DUST 1
,
LAES81 O-RING 1
,ROTSERRA91 SPARK 1
,ETALP02 PERFORATED 1
1REVOC000.020.8522
1
Substitution of components may impair intrinsic safety.
141
WARNING
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 23
AirVantage Servicing ­Pilot Valve and Pressure Regulator
Pilot Valve and Pressure Regulator
To service the pilot valve or the pressure regulator, rst shut off and bleed the air being supplied to the
pump. For safety purposes the air supply line should be disconnected from the pump. Then shut off the suction and discharge lines to the pump. Bleed the pressure from the pump suction and discharge lines and remove the lines from the pump. During the servicing of the AirVantage, consult the “AirVantage Composite Repair Parts Drawing”.
Step #1: Remove the Patch Cable
• Twist the ribbed portion of the patch cable connector in a counterclockwise direction, until it unthreads from the connector. The cable can be removed only from the intermediate.
CAPSCREW, HEX SOC HD M6 X 1.0 X 35
WASHER, FLAT, M6
COVER
SEAL, O-RING
Step #2: Remove the AirVantage from the Pump
• Use a ½” socket and remove the four 5/16-18 x 5 cap screws that hold the AirVantage to the pump. Be sure to support the weight of the AirVantage while removing the last cap screw. After the AirVantage is removed from the pump, set the unit down on the plastic cover located on the bottom. Inspect the o-ring between the poppet valve and the adapter plate for damage.
Step #3: Access the Pilot Valve and Pressure Regulator
• Use a 5mm hex-key wrench and remove four M6 x 35mm socket head cap screws & washers securing the top cover on. Lift the cover off, exposing the pilot valve and pressure regulator. There is a molded o-ring seal located on the underside of the cap. Make sure the o-ring stays located within the groove.
• If the pilot valve needs to be replaced, unplug the connector attached to it. Use a miniature 4-way Phillips screwdriver and remove the two screws holding the pilot valve to the plate. The valve and gasket can now be removed and/replaced. When reinstalling the pilot valve, tighten the screws to snug with a miniature 4-way Phillips screwdriver.
• “AirVantage CAUTION” – Be sure to reattach the connector to the pilot valve.
• If the pressure regulator needs to be replaced, use slip-joint pliers to unscrew the regulator from the body by turning it in a counterclockwise direction.
• “AirVantage CAUTION” – Do not loosen or tighten the regulator by turning the knurled portion of the unit. Place the slip-joint pliers on the smooth area underneath the knurled area of the regulator.
Step #4: Reinstallation
• Reinstall the top cover, making sure the o-ring seal is still in the groove. Tighten the four M6 screws.
• Reinstall the AirVantage using the four 5/16-18 x 5 cap screws and torque to 90 in-lbs.
• “AirVantage CAUTION” – Be sure to reattach the patch cable connector that connects the AirVantage module to the intermediate.
Note: Ensure all mating faces are free from scores or damage prior to re-assembly.
Check each metallic face joint with a 0.003” feeler gage to ensure all ange
faces are fully closed after assembly. Failure to do so may compromise the
ameproof design of the assembly.
REGULATOR
O-RING
CAP, SWITCH
WARNING
Substitution of components may impair intrinsic safety.
VALVE, SOLENOID
VALVE, POPPET
Note: Refer to Composite Repair Parts List on page 12 for part numbers
WARNING
Do not open when an explosive atmosphere may be present.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 24
AirVantage Servicing ­Power Generation Module
To service the power generation module, rst shut off and bleed the air being supplied to the pump. For safety purposes the air supply line should be disconnected from the pump. Then shut off the suction and discharge lines to the pump. Bleed the pressure from the pump suction and discharge lines and remove the lines from the pump. During the servicing of the AirVantage, consult the “AirVantage Composite Repair Parts Drawing”.
Step #1: Remove the Patch Cable
• Twist the ribbed portion of the patch cable connector in a counterclockwise direction, until it unthreads from the connector. The cable can be removed only from the intermediate.
Step #2: Remove the AirVantage from the Pump
• Use a ½” socket and remove the four 5/16-18 x 5 cap screws that hold the AirVantage to the pump. Be sure to support the weight of the AirVantage while removing the last cap screw. After the AirVantage is removed from the pump, set the unit down on the plastic cover located on the top of the unit. Inspect the o-ring between the poppet valve and the adapter plate for damage.
Step #3: Access the Power Generation Module
• Use a 5mm hex-key wrench and remove four M6 x 35mm socket head cap screws & washers securing the bottom cover. Lift the bottom cover off, exposing the power generation module. There is a molded o-ring seal located on the underside of the cap. Make sure the o-ring stays located within the groove.
• If the power generation module needs to be replaced, unplug the connector that connects
• the power generator to the control board. Use a 5mm hex-key wrench and remove four M6 x 25mm socket head cap screws. The power generation module should now be loose. Carefully lift the power generation module off the rest of the assembly, making sure that the control board wire and connector slips through the hole in the power generation case.
• "AirVantage CAUTION" - Take caution not to loosen the o-ring that seals between the components.
Step #4: Reinstallation
• When reinstalling the new module make sure to feed the control module wire through the hole in the power generation case. Install the four M6 x 25mm socket head cap screws and tighten to 6.8 N-M.
• “AirVantage CAUTION” – Be sure to reattach the connector from the power generator to the control board.
• Reinstall the bottom cover, making sure the o-ring seal is still in the groove. Tighten the four M6 x 35 socket head cap screws to 3.4 N-M.
• Reinstall the top cover, making sure the o-ring seal is still in the groove. Tighten the four M6 screws. Reinstall the AirVantage using the four 5/16-18 x 5 cap screws and torque to 90 in-lbs.
• “AirVantage CAUTION” – Be sure to reattach the patch cable connector that connects the AirVantage module to the intermediate.
SEAL, O-RING
CONNECTOR (Power Generation Module to Control Module)
BREATHER ASSEMBLY
CAPSCREW, HEX SOC HD
M6 X 1.0 X 25
SEAL, O-RING
CAPSCREW, HEX SOC HD M6 X 1.0 X 35
WASHER, FLAT, M6
COVER
CAPSCREW, HEX SOC HD M6 X 1.0 X 25
CASE, POWER GENERATOR, ATEX
CONNECTOR (To Intermediate)
CONNECTOR (Control Module to Power Generation Module)
CONTROL MODULE
O-RING
VALVE, POPPET
Note: Refer to Composite Repair Parts List on page 12 for part numbers
Note: Ensure all mating faces are free from scores or damage prior to re-assembly.
Check each metallic face joint with a 0.003” feeler gage to ensure all ange
faces are fully closed after assembly. Failure to do so may compromise the
ameproof design of the assembly.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 25
WARNING
Substitution of components may impair intrinsic safety.
WARNING
Do not open when an explosive atmosphere may be present.
AirVantage Servicing - Control Module
To service the control module, rst shut off and bleed the air being supplied to the pump. For safety purposes the air supply line should be disconnected from the pump. Then shut off the suction and discharge lines to the pump. Bleed the pressure from the pump suction and discharge lines and remove the lines from the pump. During the servicing of the AirVantage, consult the “AirVantage Composite Repair Parts Drawing”.
Step #1: Remove the Patch Cable
• Twist the ribbed portion of the patch cable connector in a counterclockwise direction, until it unthreads from the connector. The cable can be removed only from the intermediate.
Step #2: Remove the AirVantage from the Pump
• Use a ½” socket and remove the four 5/16-18 x 5 cap screws that hold the AirVantage to the pump. Be sure to support the weight of the AirVantage while removing the last cap screw. After the AirVantage is removed from the pump, set the unit down on the plastic cover located on the bottom. Inspect the o-ring between the poppet valve and the adapter plate for damage.
Step #3: Access the Pilot Valve
• Use a 5mm hex-key wrench and remove four M6 x 35mm socket head cap screws & washers securing the top cover on. Lift the cover off, exposing the pilot valve. There is a molded o-ring seal located on the underside of the cap. Make sure the o-ring stays located within the groove. The connector will need to be removed from the pilot valve. Once the plug has been removed, feed the wire assembly into the hole in the valve body to the point where the connector just enters the valve body. Reinstall the top cover and loosely reinstall the bolts. The connector will eventually need to be reconnected.
Step #4: Access the Control Module
• Use a 5mm hex-key wrench and remove four M6 x 35mm socket head cap screws & washers securing the bottom cover on. Lift the bottom cover off, exposing the power generation module. There is a molded o-ring seal located on the underside of the cap. Make sure the o-ring stays located within the groove.
• Unplug the connector that connects the power generator to the control board. Use a 5mm hex-key wrench to loosen the four M6 x 25mm socket head cap screws. The power generation module should now be loose. Carefully lift the power generation module off the rest of the assembly, making sure that the control board wire and connector slips through the hole in the power generation case.
• "AirVantage CAUTION" - Take caution not to lose the o-ring that seals between the components.
• If the control module needs to be replaced, use a 5mm hex-key wrench to loosen the four M6 x 25mm socket head cap screws holding the control module to the poppet assembly. The control module should now be loose. Carefully lift the control module off the poppet assembly, making sure that the pilot valve connector wire slips through the hole in the poppet valve assembly.
• "AirVantage CAUTION" - Take caution not to loosen the o-ring that seals between the components.
Step #5: Reinstalling
• When reinstalling the new control module, make sure to feed the pilot valve connector wire through the hole in the poppet valve assembly. Install the four M6 x 25mm socket head cap screws and tighten to 3.4 N-M.
• Reinstall the power generation module. Make sure to feed the control module wire through the hole in the power generation case. Install the four M6 x 25mm socket head cap screws and tighten to 6.8 N-M.
• “AirVantage CAUTION” – Be sure to reattach the connector from the power generator to the control board.
• Reinstall the top cover, making sure the o-ring seal is still in the groove. Tighten the four M6 screws. Reinstall the AirVantage using the four 5/16-18 x 5 cap screws and torque to 90 in-lbs.
• “AirVantage CAUTION” – Be sure to reattach the patch cable connector that connects the AirVantage module to the intermediate.
CAPSCREW, HEX SOC HD M6 X 1.0 X 35
WASHER, FLAT, M6
SEAL, O-RING
CONNECTOR (Power Generation Module to Control Module)
CAPSCREW, HEX SOC HD
M6 X 1.0 X 25
SEAL, O-RING
SEAL, O-RING
COVER
CAPSCREW, HEX SOC HD M6 X 1.0 X 25
POWER GENERATION MODULE
CONNECTOR (To Intermediate)
CONNECTOR (Control Module to Power Generation Module)
CONTROL MODULE
O-RING
VALVE, POPPET
O-RING
Note: Refer to AirVantage Composite Repair Parts List on page 23 for part numbers
Note: Ensure all mating faces are free from scores or damage prior to re-assembly.
Check each metallic face joint with a 0.003” feeler gage to ensure all ange
faces are fully closed after assembly. Failure to do so may compromise the
ameproof design of the assembly.
WARNING
Substitution of components may impair intrinsic safety.
WARNING
Do not open when an explosive atmosphere may be present.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 26
AirVantage Servicing ­Sensor Assembly
To service the control module, rst shut off and bleed the air being supplied to the pump. For safety purposes the air supply line should be disconnected from the pump. Then shut off the suction and discharge lines to the pump. Bleed the pressure from the pump suction and discharge lines and remove the lines from the pump. During the servicing of the AirVantage, consult the “AirVantage Composite Repair Parts Drawing”.
Step #1: Remove the Patch Cable
• Twist the ribbed portion of the patch cable connector in a counterclockwise direction, until it unthreads from the connector. The cable can either be removed from the intermediate or from the control module.
Step #2: Remove the AirVantage from the Pump
• Use a ½” socket and remove the four 5/16-18 x 5 cap screws that hold the AirVantage to the pump. Be sure to support the weight of the AirVantage while removing the last cap screw. After the AirVantage is removed from the pump, set the unit down on the plastic cover located on the bottom. Inspect the o-ring between the poppet valve and the adapter plate for damage.
SENSOR, FEEDBACK
A
BRACKET, INTERMEDIATE, ASSEMBLY
Note: Refer to Composite Parts List on page 12 for part numbers
NUT
PLATE,
OUTER DIAPHRAGM
Step #3: Diaphragm Disassembly
• Refer to the “Diaphragm Servicing” section (p.15) of the manual to remove diaphragm assembly from the pump.
• “AirVantage CAUTION” – When the diaphragm assembly is removed, watch for the brass probe tips located on the end of the sensor rod. There is one brass probe tip and one o-ring per side. Inspect the probe tips and o-rings for wear. For every diaphragm service, these
SEAL
FLAT EDGE
DIAPHRAGM
PLATE,
INNER DIAPHRAGM
parts should be replaced and are available in kit form. Consult the “Composite Repair Parts Drawing” for part numbers and quantities.
Step #4: Accessing the Sensor Assembly
Use a ¼” hex key wrench and remove the four, at head socket cap screws on each inner chamber. These bolts have been assembled using blue thread locker, so they may be difcult to remove. The
inner chambers and gaskets can now be removed.
• “AirVantage CAUTION” – Remove the inner chamber from the intermediate with caution,
BUMPER
DETAIL A
PROBE TIP
O-RING
taking care not to damage the sensor.
• If the sensor needs to be replaced, use a 13/16” socket and remove the plastic nut holding the connector to the intermediate. Slide the connector out of the hole.
• The sensor can now be removed from the intermediate assembly.
Step #5: Reinstallation
• Slide the new sensor assembly in the intermediate.
“AirVantage CAUTION” – Make sure the cable assembly ts into the groove machined in the intermediate. Failure to do so may damage the cable during assembly.
• Feed the connector through the hole in the intermediate and install the plastic nut. Hand tighten the nut using a 13/16" socket. Make sure the gasket is to the inside of the intermediate.
• The inner chambers and gaskets can now be reinstalled. Use blue thread locker on the inner chamber bolts and torque them to 300 in-lbs.
Refer to the “Diaphragm Servicing” section of the manual to nish the diaphragm installation
WARNING
Do not open when an explosive atmosphere may be present.
procedure.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 27
AirVantage Servicing -
Page 28
ITEM NO.
PART NUMBER
DESCRIPTION
032.054.000
1 171.092.115
CAPSCREW, HEX SOC, M6 X 35mm
2 258.020.147
COVER, END, ATEX
3 720.071.360
SEAL, O-RING
4 765.004.000
VALVE, SOLENOID
5 893.104.000
VALVE, POPPET
6 171.091.115
CAPSCREW, HEX SOC, M6 X 25mm
7 031.202.000
POWER GENERATION MODULE, ATEX
8 258.022.147
COVER, END, ATEX
9 020.069.000
REGULATOR
10 560.200.360
O-RING
11 249.019.000
CONTROL MODULE, RS20 HAZ. DUTY
12 560.104.360
O-RING
13 165.135.330
CAP, SWITCH
14
B27.7M - 3BM1-25
RING, RETAINER
15 430.050.147
HOUSING, MUFFLER
16 720.073.365
SEAL, DUST VALVE
17
HX-SHCS 0.125-40x0.188x0.188-N
CAPSCREW, HEX SOC HD, 5-40 X .25
18
BSI 4518 0221-16
O-RING
19 530.045.115
MUFFLER, SPARK ARRESTOR
20 165.137.115
PLATE, PERFORATED
21 535.096.000
TAG, WARNING
22 710.010.115
SCREW, SELF TAPPING, 4-24 X .25 LG
23 901.051.115
WASHER, FLAT, M6
24 535.094.000
TAG, NAME
Poppet Valve Drawing
Note: Refer to AirVantage Composite Repair Parts
List on page 23 for part numbers
REGULATOR
O-RING
CONTROL MODULE
O-RING
CAP, SWITCH
O-RING
WASHER, FLAT, M6
CAPSCREW, HEX SOC, M6 X 35mm
WASHER, FLAT, M6
COVER
SEAL, O-RING
VALVE, SOLENOID
VALVE, POPPET
SEAL, O-RING
SEAL, O-RING
CAPSCREW, HEX SOC, M6 X 25mm
POWER GENERATOR MODULE
CAPSCREW, HEX SOC, M6 X 25mm
SEAL, O-RING
COVER
CAPSCREW, HEX SOC, M6 X 35mm
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 28
AirVantage Servicing - Poppet Valve
Step #1: Remove the Patch Cable
• Twist the ribbed portion of the patch cable connector in a counterclockwise direction, until it unthreads from the connector. The cable can either be removed from the intermediate or from the control module.
Step #2: Remove the AirVantage from the Pump
• Use a ½” socket and remove the four 5/16-18 x 5 ½ cap screws that hold the AirVantage to the pump. Be sure to support the weight of the AirVantage while removing the last cap screw. After the AirVantage is removed from the pump, set the unit down on the bottom cover. Inspect the o-ring between the poppet valve and the adapter plate for damage.
Step #3: Access the Solenoid Valve and Pressure Regulator
• Use a 5/32 hex-key wrench and loosen the four 10-32 x .50 socket head cap screws securing the top cover on. Lift the cover off, exposing the solenoid valve and pressure regulator. There is a molded o-ring seal located on the underside of the cap. Make sure the o-ring stays located within the groove.
• Unplug the connector attached to it. Use a miniature 4-way Phillips screwdriver and remove the two screws securing the solenoid valve to the plate. The valve and gasket can now be removed and/or replaced.
• Use slip-joint pliers to unscrew the regulator from the body by turning it in a counterclockwise direction.
• “AirVantage CAUTION” – Do not loosen or tighten the regulator by turning the knurled portion of the unit. Place the slip-joint pliers on the smooth area underneath the knurled area of the regulator. Reinstall the top cover and loosely reinstall the bolts.
Step #4: Access the Power Generation Module
• Turn the assembly over and let it now rest on the top cover.
• Use a 5/32 hex-key wrench and remove the four 10-32 x .50 socket head cap screws securing the bottom cover on. Lift the bottom cover off, exposing the power generation module. There is a molded o-ring seal located on the underside of the cap. Make sure the o-ring stays located within the groove.
• Unplug the connector that connects the power generator to the control board. Use a 5/32 hex-key wrench to loosen the four 10-32 x 2 ¼ socket head cap screws. The power generation module should now be loose. Carefully lift the power generation module off the rest of the assembly, making sure that the control board wire and connector slips through the hole in the power generation case.
Step #6: Reinstallation
• Install the control module on the poppet valve assembly. Make sure to feed the solenoid valve connector wire through the hole in the poppet valve assembly. Install the two 10-32 x 1.00 socket head cap screws and tighten to 30 in-lbs.
• Install the power generation module onto the control module. Make sure to feed the control module wire through the hole in the power generation case. Install the four 10-32 x 2 ¼ socket head cap screws and tighten to 60 in-lbs.
• “AirVantage CAUTION” – Be sure to reattach the connector from the power generator to the control board.
• Install the bottom cover, making sure the o-ring seal is still in the groove. Tighten the four 10-32 screws. The unit can now be turned over and set on the bottom cover.
• Install the solenoid valve, tighten the screws snug with a miniature 4-way Phillips screwdriver.
• “AirVantage CAUTION” – Be sure to reattach the connector to the solenoid valve.
• “AirVantage CAUTION” – Be sure to reattach the patch cable connector that connects the AirVantage module to the intermediate.
• If the pressure regulator needs to be replaced, use slip-joint pliers to unscrew the regulator from the body by turning it in a counterclockwise direction.
• “AirVantage CAUTION” – Do not loosen or tighten the regulator by turning the knurled portion of the unit. Place the slip-joint pliers on the smooth area underneath the knurled area of the regulator.
Step #7: Reinstallation
• Reinstall the top cover, making sure the o-ring seal is still in the groove. Tighten the four 10-32 screws.
• Reinstall the AirVantage using the four 5/16-18 x 5 ½ cap screws and torque to 90 in-lbs.
• “AirVantage CAUTION” – Be sure to reattach the patch cable connector that connects the AirVantage module to the intermediate.
• Refer to Page 28 for Illustration
Note: Ensure all mating faces are free from scores or damage prior to re-assembly.
Check each metallic face joint with a 0.003” feeler gage to ensure all ange
faces are fully closed after assembly. Failure to do so may compromise the
ameproof design of the assembly.
Step #5: Access the Control Module
• Use a 5/32 hex-key wrench and loosen the two 10-32 x 1.00 socket head cap screws securing the control module to the poppet assembly. The control module should now be loose. Carefully lift the control module off the poppet assembly, making sure that the solenoid valve connector wire slips through the hole in the poppet valve assembly.
• The Poppet valve assembly can now be replaced.
WARNING
Substitution of components may impair intrinsic safety.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 29
WARNING
Do not open when an explosive atmosphere may be present.
AirVantage Servicing - Check Valve
AirVantage - Check Valve Assembly
To service the check valve, rst shut off and bleed the air being supplied to the pump. For safety
purposes the air supply line should be disconnected from the pump. Then shut off the suction and discharge lines to the pump. Bleed the pressure from the pump suction and discharge lines and remove the lines from the pump. During the servicing of the AirVantage, consult the “AirVantage Composite Repair Parts Drawing” (Page 11)
Step #1: Remove the Patch Cable
Twist the ribbed portion of the patch cable connector in the counterclockwise direction, until it un-threads from the connector. The cable can be either be removed from the intermediate or from the control module.
Step #2: Remove the AirVantage from the Pump
Use a ½” socket and remove the four 5/16 x 5 ½ cap screws that hold the AirVantage to the pump. Remove the two chamber bolts/nuts that are holding the right side bracket to be able to remove the right bracket and the AirVantage unit from the pump. Be sure to support the weight of the AirVantage while removing the last cap screw. After the AirVantage is removed from the pump, set the unit down on the plastic cover located on the bottom. Inspect the o-ring between the poppet valve and adapter plate for damage.
Step 3: Remove the Check Valve from the Pump
Use a ½” socket and remove the four 5/16 x 2 ½ cap screw that holds the check valve to the pump.
Step 4: Inspect Check Valve
Using a 1 ¼” open socket wrench, remove the cartridge valve. Inspect o-rings and mechanism for any signs of wear, degradation, or damage. If any is present, replace with new cartridge valve
assembly. Remove any remaining uid contamination on inside of body and/or cartridge valve.
Be careful not to lose the large and small o-rings on either face of the check valve body.
Step 5: Re-assembly of Check Valve
Apply a thin layer of white lithium grease to the threads on the valve cartridge. Insert cartridge valve into body and hand-tighten being careful not to pinch o-ring. Using a 9” torque wrench with crow-foot, torque cartridge vale to 250 in-lbs. Re-apply o-rings, as necessary, to both faces of check valve. After applying Blue Loctite 248, 222 (or equivalent) secure check valve back to pump with four 5/16 x 2 ½ cap screws, re-torque to 90 in-lbs.
To secure the AirVantage, re-install the four 5/16 x 5 ½ cap screws, torquing to 90 in-lbs. Re­install Patchcable.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 30
Grounding The Pump
One eyelet is fastened to the pump hardware.
One eyelet is installed to a true earth ground. (Requires a 5/16 or 8mm maximum diameter bolt)
This 8-foot long (244 centimeters) Ground Strap, part number 920-025-000, can be ordered as a service item.
To reduce the risk of static electrical sparking, this pump must be grounded. Check the local electrical code for detailed grounding instruction and the type of equipment required.
WARNING
Take action to prevent static sparking. Fire or explosion can result, especially when handling flammable liquids. The pump, piping, valves, containers or other miscellaneous equipment must be grounded.
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 31
PUMPING HAZARDOUS LIQUIDS
• When a diaphragm fails, the pumped liquid or fumes enter the air end of the pump. Fumes are exhausted into the surrounding environment. When pumping hazardous or toxic materials, the exhaust air must be piped to an appropriate area for safe disposal. See illustration #1 at right.
• Piping used for the air exhaust must not be smaller than 1" (2.54 cm) diameter. Reducing
the pipe size will restrict air ow and reduce pump performance. When the pumped product source is at a higher level than the pump (ooded suction condition), pipe the
exhaust higher than the product source to prevent siphoning spills. See illustration #2 at right.
CONVERTING THE PUMP FOR PIPING THE EXHAUST AIR
• The following steps are necessary to convert the pump to pipe the exhaust air away from the pump.
Remove the mufer. The air distribution valve has 1" NPT threads for piped exhaust.
CONVERTED EXHAUST ILLUSTRATION
PUMP INSTALLATION AREA
1" DIAMETER AIR
EXHAUST PIPING
SAFE AIR EXHAUST DISPOSAL AREA
MUFFLER
IMPORTANT INSTALLATION NOTE:
The manufacturer recommends installing a exible conductive hose or connection between the pump and any rigid plumbing. This reduces stresses on the molded threads of the air exhaust port. Failure to do so may result in damage to the air distribution valve body.
• Failure to support these connections could also result in damage to the air distribution valve body.
Illustration #1
Illustration #2
LIQUID LEVEL
SUCTION
LINE
MUFFLER
1" DIAMETER AIR EXHAUST PIPING
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 32
Material Codes
The Last 3 Digits of Part Number
000 Assembly, sub-assembly;
and some purchased items 010 Cast Iron 012 Powered Metal 015 Ductile Iron 020 Ferritic Malleable Iron 025 Music Wire 080 Carbon Steel, AISI B-1112 100 Alloy 20 110 Alloy Type 316 Stainless Steel 111 Alloy Type 316 Stainless Steel
(Electro Polished) 112 Alloy C 113 Alloy Type 316 Stainless Steel
(Hand Polished) 114 303 Stainless Steel 115 302/304 Stainless Steel 117 440-C Stainless Steel (Martensitic) 120 416 Stainless Steel
(Wrought Martensitic) 123 410 Stainless Steel
(Wrought Martensitic) 147 Clear Anodized Aluminum 148 Hardcoat Anodized Aluminum 149 2024-T4 Aluminum 150 6061-T6 Aluminum 151 6063-T6 Aluminum 152 2024-T4 Aluminum (2023-T351) 154 Almag 35 Aluminum 155 356-T6 Aluminum 156 356-T6 Aluminum 157 Die Cast Aluminum Alloy #380 158 Aluminum Alloy SR-319 159 Anodized Aluminum 162 Brass, Yellow, Screw Machine Stock 165 Cast Bronze, 85-5-5-5 166 Bronze, SAE 660 167 Bronze, Alloy 954, ASTM B505 170 Bronze, Bearing Type,
Oil Impregnated
175 Die Cast Zinc 180 Copper Alloy 305 Carbon Steel, Black Epoxy Coated 306 Carbon Steel, Black PTFE Coated 307 Aluminum, Black Epoxy Coated 308 Stainless Steel, Black PTFE Coated 309 Aluminum, Black PTFE Coated 310 PVDF Coated 330 Zinc Plated Steel 331 Chrome Plated Steel 332 Aluminum, Electroless Nickel Plated 333 Carbon Steel, Electroless
Nickel Plated 335 Galvanized Steel 336 Zinc Plated Yellow Brass 337 Silver Plated Steel 340 Nickel Plated 342 Filled Nylon 353 Geolast; Color: Black 354 Injection Molded #203-40 Santoprene- Duro 40D
+/-5; Color: RED 355 Thermal Plastic 356 Hytrel 357 Injection Molded Polyurethane 358 Urethane Rubber
(Some Applications) (Compression Mold) 359 Urethane Rubber 360 Nitrile Rubber. Color coded: RED 361 FDA Accepted Nitrile 363 FKM (Fluorocarbon).
Color coded: YELLOW 364 E.P.D.M. Rubber. Color coded: BLUE 365 Neoprene Rubber.
Color coded: GREEN 366 Food Grade Nitrile 368 Food Grade EPDM 370 Butyl Rubber. Color coded: BROWN 371 Philthane (Tuftane) 374 Carboxylated Nitrile
375 Fluorinated Nitrile 378 High Density Polypropylene 379 Conductive Nitrile 405 Cellulose Fiber 408 Cork and Neoprene 425 Compressed Fiber 426 Blue Gard 440 Vegetable Fiber 465 Fiber 500 Delrin 500 501 Delrin 570 502 Conductive Acetal, ESD-800 503 Conductive Acetal, Glass-Filled 505 Acrylic Resin Plastic 506 Delrin 150 520 Injection Molded PVDF Natural color 521 Conductive PVDF 540 Nylon 541 Nylon 542 Nylon 544 Nylon Injection Molded 550 Polyethylene 551 Glass Filled Polypropylene
552 Unlled Polypropylene 553 Unlled Polypropylene
555 Polyvinyl Chloride 556 Black Vinyl 557 Conductive Polypropylene 558 Conductive HDPE 559 Glass-Filled Conductive Polypropylene 570 Rulon II 580 Ryton 590 Valox 591 Nylatron G-S 592 Nylatron NSB 600 PTFE (virgin material)
Tetrauorocarbon (TFE)
601 PTFE (Bronze and moly lled)
602 Filled PTFE
603 Blue Gylon 604 PTFE 606 PTFE 607 Envelon 608 Conductive PTFE 610 PTFE Integral Silicon 611 PTFE Integral FKM 632 Neoprene/Hytrel 633 FKM (Fluorocarbon)/PTFE 634 EPDM/PTFE 635 Neoprene/PTFE 637 PTFE, FKM (Fluorocarbon)/PTFE 638 PTFE, Hytrel/PTFE 639 Nitrile/TFE 643 Santoprene/EPDM 644 Santoprene/PTFE 650 Bonded Santoprene and PTFE 654 Santoprene Diaphragm, PTFE Overlay Balls and
seals
656 Santoprene Diaphragm and
Check Balls/EPDM Seats
661 EPDM/Santoprene
Delrin and Hytrel are registered tradenames of E.I. DuPont.
Gylon is a registered tradename of Garlock, Inc.
Nylatron is a registered tradename of Polymer Corp.
Santoprene is a registered tradename of Exxon Mobil Corp.
Rulon II is a registered tradename of Dixion Industries Corp.
Ryton is a registered tradename of Phillips Chemical Co.
Valox is a registered tradename of General Electric Co.
SANDPIPER, PortaPump, Tranquilizers and SludgeMaster are registered tradenames of Warren Rupp, Inc
rhdb2dl1sm_haz duty-rev0614 Model RHDB2 Hazardous Duty Page 33
Declaration of Conformity
Manufacturer: Warren Rupp, Inc.®, 800 N. Main Street
Mansfield, Ohio, 44902 USA
Certifies that Air-Operated Double Diaphragm Pump Series: HDB, HDF, M Non-Metallic,
S Non-Metallic, M Metallic, S Metallic, T Series, G Series, U Series, EH and SH High Pressure,
RS Series, W Series, SMA and SPA Submersibles, and Tranquilizer Surge Suppressors comply with
the European Community Directive 2006/42/EC on Machinery, according to Annex VIII.
This product has used Harmonized Standard EN809:1998+A1:2009, Pumps and Pump Units
for Liquids - Common Safety Requirements, to verify conformance.
October 20, 2005
Signature of authorized person
Date of issue
David Roseberry Printed name of authorized person
Revision Level: F
Engineering Manager Title
August 23, 2012 Date of revision
EC Declaration of Conformity
In accordance with ATEX Directive 94/9/EC,
Equipment intended for use in potentially explosive environments.
®
Manufacturer: Warren Rupp, Inc.
800 North Main Street, P.O. Box 1568, Mansfield, OH 44902 USA
, A Unit of IDEX Corportion
Airvantage-equipped ATEX-Certified Air-Operated Double Diaphragm Pump Models RHDB2. RHDF2, RS20, and RS30.
Certificate Number: Sira 10ATEX1151X Issue: 2 Equiptment: AirVantage Air Flow Control Unit
Sira Certification Service
Rake Lane Eccleston Chester CH4 SJN United Kingdom
DATE/APPROVAL/TITLE: 27 MAY 2010
0518
Applicable Standard:
AirVantage Marking:
EN 60079-0:2009 II 2 G D EN 60079-1:2007 Ex d ib IIB T4 Gb IEC 60079-31:2006 Ex tb IIIC 135° C Db IP66
Position Sensor Rating (not marked):
EN 60079-0:2006 II 2 G D EN 60079-11:2007 Ex ib IIB T4 EN 61241-0:2006 Ex ibD 21 T132° C EN 61242-11:2006
David Roseberry, Engineering Manager
Declaration of Conformity
INTERNATIONAL ELECTROTECHNICAL COMMISSION
IEC Certification Scheme for Explosive Atmospheres
®
Manufacturer: Warren Rupp, Inc.
800 North Main Street, P.O. Box 1568, Mansfield, OH 44902 USA
, A Unit of IDEX Corportion
Airvantage-equipped Air-Operated Double Diaphragm Pump Models RHDB2, RHDF2, RS20 and RS30.
Certificate Number: IECEx SIR 10.0110X Issue: 2 Equiptment: AirVantage Air Flow Control Unit
Sira Certification Service
Rake Lane Eccleston Chester CH4 SJN United Kingdom
DATE/APPROVAL/TITLE: 27 MAY 2010
Applicable Standard:
AirVantage Marking:
IEC 60079-0:2004 Ex d ib IIB T4 Gb IEC 60079-1:2007-4 Ex tb IIIC 135° C Db IP66 IEC 60079-31:2008
Position Sensor Rating (not marked):
IEC 60079-0:2007-10 Ex ib IIB T4 IEC 60079-11:2006 Ex ibD 21 T132° C IEC 61241-0:2004 IEC 61242-11:2005
David Roseberry, Engineering Manager
Loading...