Improve energy efficiency and environmental compliance with acoustic monitoring of steam traps and
pressure relief valves
Gain instant visibility to all of your critical steam traps and PRVs through a non-intrusive, WirelessHART
monitoring system
Backed by proven experience in wireless field instrumentation and expert technical support from
Emerson
™
®
Page 2
Rosemount 708
Emerson’s Wireless Solution
IEC 62591 (WirelessHART)... The industry standard
Self-organizing, adaptive mesh routing
Know you are backed by Emerson’s proven
experience in Wireless field instrumentation and
expert technical support
The self-organizing, self-healing network manages
multiple communication paths for any given
device. If an obstruction is introduced into the
network, data will continue to flow because the
device already has other established paths.
Reliable wireless architecture
Standard IEEE 802.15.4 radios
2.4 GHz ISM band sliced into 15 radio-channels
February 2017
Time Synchronized Channel Hopping
Direct sequence spread spectrum (DSSS)
technology delivers high reliability in challenging
radio environment
Emerson’s Wireless
Seamless integration to all existing host systems
Native integration into DeltaV
Gateways interface with existing host systems using industry standard protocols including OPC, Modbus
and EtherNet/IP
™
Layered security keeps your network safe
Ensures data transmissions are received only by the wireless Gateway
Network devices implement industry standard Encryption, Authentication, Verification, Anti-Jamming, and Key Management
Third party security verification including Achilles and FIPS197- User based login and enforced password strength. Password
strength monitoring, user based log in, password reset requirements, automatic lockout, password expiration requirements.
Based on guidelines from ISA99.03.03 standard approved level two.
SmartPower™ solutions
™
and Ovation™ is transparent and seamless
®
TCP/IP, Modbus RTU,
Optimized Emerson instrumentation, both hardware and software, to extend power module life
SmartPower technologies enable predictable power life
Reliably detects and transmits information about acoustic events such as leaks
Transmitter output includes acoustic level (0 to 255 counts) and temperature
(–40 to 260 °C)
Transmitter communicates process variable and status information via the wireless
network for integration into existing host systems
Monitor steam traps
Steam Trap Monitoring application provides critical, real-time information on the
condition of your monitored steam trap population
Real-time monitoring provides instantaneous feedback for system maintenance and
optimization
Monitor pressure relief valves or pressure safety
Rosemount 708
valves
Turbulence generated by a leaky valve can be detected using the acoustic transmitter
Notification when release is occurring and when the release has stopped
Emerson Wireless network provides timestamped information to the host
Automated data enables reporting of a tamper-proof data log
Mounting flexibility
The wireless acoustic transmitter can be directly mounted to process piping without
cutting pipes or changing pipe configurations allowing for a flexible, easy installation.
Reliable transmitter performance
The rugged and robust design of the transmitter ensures reliable performance in harsh
environments.
Emerson.com/Rosemount
3
Page 4
Rosemount 708
February 2017
Ordering Information
Table 1. Rosemount Product Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
ModelProduct description
708Acoustic Transmitter
Output protocol
X Wireless
Measurement
1Steam Traps with Steam Trap Monitoring Software (order with 7001X)
2Other measurements
Housing
PEngineered polymer
Waveguide configuration
A1Acoustic waveguide
Product certifications
NANo hazardous location approval
I1ATEX Intrinsic Safety
I2INMETRO Intrinsic Safety
I3China Intrinsic Safety
I4TIIS Intrinsic Safety
I5USA Intrinsically Safe
I6Canada Intrinsically Safe
I7IECEx Intrinsic Safety
IMEAC Intrinsically Safe
IPKorea Intrinsically Safe
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
★
Mounting hardware
NA00No mounting hardware
HC01Stainless steel mounting band, nominal pipe size 1/2- to 21/2-in.
HC02Stainless steel mounting band, nominal pipe size 3- to 4-in.
HC03Stainless steel mounting band, nominal pipe size 4- to 10-in.
HT01High temperature stainless steel mounting hardware, nominal pipe size 1/2- to 11/4-in. (260 to 550 °C)
4
Emerson.com/Rosemount
★
★
★
★
Page 5
February 2017
Rosemount 708
Table 1. Rosemount Product Ordering Information
The starred offerings (★) represent the most common options and should be selected for best delivery. The non-starred offerings are subject
to additional delivery lead time.
Wireless options(include with selected model number)
Extended product warranty
WR33-year limited warranty
WR55-year limited warranty
Wireless update rate, operating frequency and protocol
Omni-directional wireless antenna and SmartPower solutions
(1)
WP5Internal antenna, compatible with green power module (I.S. power module sold separately)
Configuration
C1Factory configure date, descriptor, message fields and wireless parameters
Typical model number: 708 X 1 P A1 NA HC01 WA3 WP5
1.Power module must be shipped separately, order 701PGNKF.
Table 2. Spare Parts and Accessories
00708-9010-0001High temperature mounting hardware
★
★
★
★
★
★
Emerson.com/Rosemount
5
Page 6
Rosemount 708
Specifications
February 2017
Functional specifications
Output
IEC 62591 (WirelessHART) 2.4 GHz DSSS
Humidity limits
0–100 percent relative humidity
Tra nsmit rate
User selectable 1 second to 60 minutes
Radio frequency power output from antenna
Internal (WP option) antenna:
Maximum of 10 mW (10 dBm) EIRP
Physical specifications
Material selection
Emerson provides a variety of Rosemount products with various
product options and configurations including materials of
construction that can be expected to perform well in a wide
range of applications. The Rosemount product information
presented is intended as a guide for the purchaser to make an
appropriate selection for theapplication.Itisthepurchaser’s sole
responsibility to make a careful analysis of all process
parameters (such as all chemical components, temperature,
pressure, flow rate, abrasives, contaminants, etc.), when
specifying product materials, options, and components for the
particular application. is not in a position to evaluate or
guarantee the compatibility of the process fluid or other process
parameters with the product options, configuration, or
materials of construction selected.
Ten-year power module life at reference conditions
Field Communicator connections
Communication Terminals - Clips permanently fixed to power
module
(1)
Materials of construction
Housing
PBT/PC
Cover O-ring
Silicone
Power module housing
PBT/PC
Wave guide
Machined 316L SST
Mounting
Transmitters are directly attached to process piping using two
stainless steel mounting bands.High temperature mounting
hardware should be used when process temperatures exceed
260 °C (500 °F).
Weight
Rosemount 708 with power module –1.31 lb (0.595 kg)
Rosemount 708 without power module –0.98 lb (0.445 kg)
Enclosure ratings
®
NEMA
4X and IP66/67
Performance specifications
Vibration effect
Tested per the requirements of IEC60770-1 field or pipeline with
high vibration level (10–60 Hz 0.21 mm displacement peak
amplitude/60–2000 Hz 3 g).
Temperature limits
Ambient limit: –40 to 85 °C (–40 °F to 185 °F)
Storage limit: –40 to 85 °C (–40 °F to 185 °F)
Heat from the process is transferred to the transmitter housing.
If the process temperature is high, the ambient temperature will
need to be lower to account for heat transferred to the
transmitter housing. (see Table 3 on page 7)
1.Reference conditions are 70 °F (21 °C), transmit rate of once per minute,
and routing data for three additional network devices.
6
Emerson.com/Rosemount
Page 7
February 2017
Rosemount 708
Table 3. Temperature Derating — Direct Mount
Process temperature (°C)Max ambient (°C)
26041
24045
22049
20053
18057
16061
14064
12068
10072
8575
Table 4. High Temperature — High Temperature Mounting
Option
Process temperature (°C)Max ambient (°C)
55041
52045
49047
46049
Electro Magnetic Compatibility (EMC)
Meets all relevant requirements of EN 61326-2-3:2013
Wireless output specifications
Acoustic output
0 to 255 counts
Temperature output
–40 to 260 °C (–104 to 500 °F)
43051
40053
37056
34058
31060
28062
26063
Emerson.com/Rosemount
7
Page 8
Rosemount 708
Product Certifications
Rev 2.1
February 2017
European Union Directive Information
A copy of the EU Declaration of Conformity can be found at the
end of the Quick Start Guide. The most recent revision of the EU
Declaration of Conformity can be found at
Emerson.com/Rosemount
.
Telecommunication Compliance
All wireless devices require certification to ensure that they
adhere to regulations regarding the use of the RF spectrum.
Nearly every country requires this type of product certification.
Emerson is working with governmental agencies around the
world to supply fully compliant products and remove the risk of
violating country directives or laws governing wireless device
usage.
FCC and IC
This device complies with Part 15 of the FCC Rules. Operation is
subject to the following conditions: This device may not cause
harmful interference. This device must accept any interference
received, including interference that may cause undesired
operation. This device must be installed to ensure a minimum
antenna separation distance of 20 cm from all persons.
Ordinary Location Certification
As standard, the transmitter has been examined and tested to
determine that the design meets the basic electrical,
mechanical, and fire protection requirements by a nationally
recognized test laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
Installing in North America
USA
I5U.S.A. Intrinsically Safe (IS)
Certificate: (FM) 3043245
Standards: FM Class 3600 – 1998, FM Class 3610 – 2010,
FM Class 3810 – 2005, NEMA 250 – 2003,
ANSI/IEC 60529 – 2004
Markings: IS CL I, DIV 1, GP A, B, C, D T4;
CL 1, Zone 0 AEx ia IIC T4;
T4(–40 °C ≤ T
Rosemount drawing 00708-1000; Type 4X
Special Conditions for Safe Use (X):
1. The Rosemount 708 Wireless Acoustic Transmitter shall
only be used with the 701PGNKF Rosemount SmartPower
battery pack.
2. Potential Electrostatic charging Hazard – See instructions.
Markings: I.S. CL I, DIV 1, GP A, B, C, D when installed per
Rosemount drawing 00708-1001; T3C; Type
4X
Europe
I1ATEX Intrinsic Safety
Certificate: Baseefa11ATEX0174X
Standards: EN 60079-0: 2012, EN 60079-11: 2012
Markings: II 1 G Ex ia IIC T4 Ga, T4 (–40 °C ≤ T
≤ +70 °C)
a
The US National Electrical Code® (NEC) and the Canadian
Electrical Code (CEC) permit the use of Division marked
equipment in Zones and Zone marked equipment in Divisions.
The markings must be suitable for the area classification, gas,
and temperature class. This information is clearly defined in the
respective codes.
8
Special Conditions for Safe Use (X):
1. The plastic enclosure of the Rosemount 708 may
constitute a potential electrostatic ignition risk and must
not be rubbed or cleaned with a dry cloth.
2. The Model 701PGNKF Power Module may be replaced in a
hazardous area. The power module has a surface resistivity
greater than 1GΩ and must be properly installed in the
wireless device enclosure. Care must be taken during
transportation to and from the point of installation to
prevent electrostatic charge build-up.
Emerson.com/Rosemount
Page 9
February 2017
Rosemount 708
International
I7IECEx Intrinsic Safety
Certificate: IECEx BAS 11.0091X
Standards: IEC 60079-0:2011, IEC 60079-11:2011
Markings: Ex ia IIC T4 Ga, T4(–40 °C ≤ T
Special Condition for Safe Use (X):
1. The plastic enclosure of the Rosemount 708 may
constitute a potential electrostatic ignition risk and must
not be rubbed or cleaned with a dry cloth.
Standard Terms and Conditions of Sale can be found on the Ter ms a nd
Conditions of Sale page.
The Emerson logo is a trademark and service mark of Emerson Electric
Co.
Ovation, SmartPower, SteamLogic, DeltaV, Rosemount, and Rosemount
logotype are trademarks of Emerson.
WirelessHART is a registered trademark of the FieldComm Group.
Modbus is a registered trademark of Gould Inc.
NEMA is a registered trademark and service mark of the National
Electrical Manufacturers Association.
National Electrical Code is a registered trademark of National Fire
Protection Association, Inc.
All other marks are the property of their respective owners.