Solid state equipment has operational characteristics differing from those of
electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (Publication SGI-1.1
available from your local Rockwell Automation sales office or online at http://www.rockwellautomation.com/literature) describes some important differences
between solid state equipment and hard-wired electromechanical devices.
Because of this difference, and also because of the wide variety of uses for solid
state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is
acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect
or consequential damages resulting from the use or application of this
equipment.
The examples and diagrams in this manual are included solely for illustrative
purposes. Because of the many variables and requirements associated with any
particular installation, Rockwell Automation, Inc. cannot assume responsibility
or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use
of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without
written permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of
safety considerations.
WARNING: Identifies information about practices or
circumstances that can cause an explosion in a hazardous
!
environment, which may lead to personal injury or death, property
damage, or economic loss.
Important: Identifies information that is critical for successful application and
understanding of the product.
ATT E NT I ON : Identifies information about practices or
circumstances that can lead to personal injury or death, property
!
damage, or economic loss. Attentions help you identify a hazard,
avoid the hazard, and recognize the consequences.
Shock Hazard labels may be located on or inside the equipment
(e.g., drive or motor) to alert people that dangerous voltage may be
present.
Burn Hazard labels may be located on or inside the equipment
(e.g., drive or motor) to alert people that surfaces may be at
dangerous temperatures.
Allen-Bradley, PLC, DriveExplorer, DriveExecutive, DriveLogix, SCANport, and SynchLink are either registered
trademarks or trademarks of Rockwell Automation, Inc.
Summary of Changes
The information below summarizes the changes to this manual since the last
release (July 2005):
Description of ChangesPage
In Table 1.A, changed column heading from “Output Current at 2 kHz (Amps)” to “Output
Current at 4 kHz (Amps).” Changed the last sentence in footnote 2 from “…also capable of
running at 3 kHz or 4 kHz…” to “…also capable of running at 2 kHz or 3 kHz.”
Changed Table 3.A columns and information.3-7
Deleted Table 3.B, and added replacement fuses subheading and reference to the drive
wiring diagram.
In the“Control” category specifications section for the “Carrier Frequency,” changed the
statement “Drive rating based on 2 kHz” to “Drive rating based on 4 kHz.”
The information below summarizes the changes to this manual since the last
release (January 2005):
Description of ChangesPage
Deleted Chapter 3 - Programming and Parameters. The active converter information
formerly contained in Chapter 3 is now contained in the PowerFlex 700 Active Converter Power Module User Manual (Publication No. PFLEX-UM002…), which is referenced in the
Preface.
Changed the following catalog string information:
• In Digits 4 through 7 (Input Voltage & Output Current Rating), deleted Cat. Code D405.
Also removed all “405A” drive information from Table 1.A, Table 1.B, Table 1.C, Table
3A, Table 3B, and the VFD Power Module Table on page C-11.
• In Digit 12 (Input Filter Items), deleted Cat. Code C.
Added a reference to the PowerFlex 700 Active Converter Power Module User Manual
(Publication No. PFLEX-UM002…) for more information about active converter
communication.
Added a reference to the PowerFlex 700 Active Converter Power Module User Manual
(Publication No. PFLEX-UM002…) for more information about wiring the active converter
control board I/O terminals.
Re-numbered Chapter 4 - Troubleshooting to be Chapter 3.Chapter 3
Added a reference to the PowerFlex 700 Active Converter Power Module User Manual
(Publication No. PFLEX-UM002…) for active converter fault descriptions and related
troubleshooting information.
In Table 3.B, changed replacement Voltage Feedback Resistor Assembly, 460 V kit
number from “180924-A03” to “180923-A03.”
The purpose of this manual is to provide you with the basic information
needed to install and troubleshoot the LPM20 Liquid-Cooled AC Drive with
High Performance Drive Control.
For information on ...See page ...
Who Should Use this Manual?
What Is Not in this ManualP-1
Reference MaterialsP-2
Manual ConventionsP-3
General PrecautionsP-4
Catalog Number ExplanationP-5
P-1
Who Should Use this
Manual?
What Is Not in this Manual
This manual is intended for qualified personnel. You must be able to mount
and wire Adjustable Frequency AC Drive devices.
This manual is designed to provide only installation, wiring, and
troubleshooting information.
PowerFlex 700 Active Converter Power Module Information
LPM20 Liquid-Cooled Adjustable Frequency AC Drives are equipped with
a PowerFlex 700 Active Converter Power Module. For details on active
converter I/O wiring, start-up, programming, and other related information,
please refer to the PowerFlex 700 Active Converter Power Module User Manual (Publication No. PFLEX-UM002…).
PowerFlex 700S Phase II Control Information
LPM20 Liquid-Cooled Adjustable Frequency AC Drives are equipped with
a PowerFlex 700S Phase II control cassette. Please refer to the Power Fl ex
700S High Performance AC Drive — Phase II Control User Manual
(Publication No. 20D-UM006…) in the locations shown in parenthesis
below for information on:
• Start-up (Chapter 2).
• Drive programming and parameters (Chapter 3).
• Application notes (Appendix C).
P-2Overview
Reference Materials
Publications can be obtained online at
http://www.rockwellautomation.com/literature
The following manuals are recommended for general drive information :
Title Publication
Wiring and Grounding Guidelines for Pulse Width Modulated (PWM) AC Drives DRIVES-IN001…
Preventive Maintenance of Industrial Control and Drive System EquipmentDRIVES-TD001…
Safety Guidelines for the Application, Installation and Maintenance of Solid
State Control
A Global Reference Guide for Reading Schematic Diagrams0100-2.10
Guarding Against Electrostatic Damage8000-4.5.2
The following publications provide specific feedback card information:
Title Publication
Hi-Resolution (Stegmann) Feedback Option Card Installation Instructions for
PowerFlex 700S Drives (also LPM20 with High Performance Drive Control)
Resolver Feedback Option Card Installation Instructions for
PowerFlex 700S Drives (also LPM20 with High Performance Drive Control)
Multi-Device Interface Option Card Installation Instructions for
PowerFlex 700S Drives (also LPM20 with High Performance Drive Control)
The following publication provides information that is necessary when
applying the 700S Phase II Control DriveLogix5730 Controller:
.
SGI-1.1
20D-IN001 …
20D-IN002 …
20D-IN004 …
TitlePublication
DriveLogix5730 Controller User Manual20D-UM003 …
The following publications provide information that is useful when
planning and installing communication networks:
TitlePublication
ControlNet Coax Tap Installation Instructions1786-5.7
ControlNet Cable System Planning and Installation Manual1786-6.2.1
ControlNet Fiber Media Planning and Installation GuideCNET-IN001 …
SynchLink Design Guide1756-TD008 …
• In this manual we refer to the LPM20 Liquid-Cooled AC Drive as; drive,
LPM20 or LPM20 Drive.
• To help differentiate parameter names and LCD display text from other
text, the following conventions will be used:
– Parameter Names will appear in [brackets].
For example: [DC Bus Voltage].
– Display Text will appear in “quotes.” For example: “Enabled.”
• The following words are used throughout the manual to describe an
action:
WordMe aning
CanPossible, able to do something
CannotNot possible, not able to do something
MayPermitted, allowed
MustUnavoidable, you must do this
ShallRequired and necessary
ShouldRecommended
Should NotNot recommended
P-4Overview
General Precautions
Class 1 LED Product
ATTENTION: Risk of permanent eye damage exists when using
optical transmission equipment. This product emits intense light
!
and invisible radiation. Do not look into module ports or fiber
optic cable connectors.
ATTENTION: This drive contains ESD (Electrostatic Discharge)
sensitive parts and assemblies. Static control precautions are
!
required when installing, testing, servicing or repairing this
assembly. Component damage may result if ESD control
procedures are not followed. If you are not familiar with static
control procedures, refer to Allen-Bradley publication 8000-4.5.2,
“Guarding Against Electrostatic Damage” or any other applicable
ESD protection handbook.
ATTENTION: An incorrectly applied or installed drive can
result in component damage or a reduction in product life. Wiring
!
or application errors, such as, undersizing the motor, incorrect or
inadequate AC supply, or excessive ambient temperatures may
result in malfunction of the system.
ATTENTION: Only qualified personnel familiar with adjustable
frequency AC drives and associated machinery should plan or
!
implement the installation, start-up, and subsequent maintenance
of the system. Failure to comply may result in personal injury and/
or equipment damage.
ATTENTION: To avoid an electric shock hazard, verify that the
voltage on the bus capacitors has discharged before performing
!
any work on the drive. After removing power to the drive, wait 5
minutes for the bus capacitors to discharge. Measure the DC bus
voltage at the locations shown in Figure 3.2
zero.
ATTENTION: Risk of injury or equipment damage exists. DPI
or SCANport host products must not be directly connected
!
together via 1202 cables. Unpredictable behavior can result if two
or more devices are connected in this manner.
ATTENTION: Risk of injury or equipment damage exists.
Parameters 365 [Fdbk LsCnfg Pri] - 394 [VoltFdbkLossCnfg] let
!
you determine the action of the drive in response to operating
anomalies. Precautions should be taken to ensure that the settings
of these parameters do not create hazards of injury or equipment
damage.
ATTENTION: Risk of injury or equipment damage exists.
Parameters 383 [SL CommLoss Data] - 392 [NetLoss DPI Cnfg]
!
let you determine the action of the drive if communications are
disrupted. You can set these parameters so that the drive continues
to run. Precautions should be taken to ensure that the settings of
these parameters do not create hazards of injury or equipment
damage.
. The voltage must be
OverviewP-5
Catalog Number
Explanation
18171920
The LPM20 with High Performance Drive Control catalog numbering
scheme is shown below.
L
ENo
K
Cat.
Code
Comm.
No
Embedded
Options
CONTROL CONFIGURATIONS
Ethernet/IP
700S Phase II Control
700S Phase II Control w/DriveLogix™
700S Phase II Control w/DriveLogix™
1B 1
C 1E
A
Cat. CodeType
FEEDBACK OPTIONS
NoneN
Resolver
Stegmann Encoder
Multi-Device Interface
Cat.
1
2nd Encoder
Requires Expanded Cassette.
1
Logix
CONTROL OPTIONS
Control
Code
NoA
SyncLink
No
Expansion
Cassette
Expanded
Option
700S Phase II
D
2D 2
B
C
YesNoYes
No
Yes
Yes
Expanded
Expanded
Expanded
700S Phase II
700S Phase II
700S Phase II
2
C
Q
Requires DriveLogix™5730 Controller.
42 43 44 45 46 4
1
E
E
N
Q
No
Yes
Yes
Ship CartonDocument(s)Cat. Code
Cat.
Code
DOCUMENTS & SHIPPING CARTON
English Doc Set
No Doc Set
HP
(Ref.)
Cat.
Code
Output
Current
Type
Source
No Doc Set
HIM
Coat
None
LPM20 with High Performance Drive Control
PRODUCT CATALOG NUMBER EXPLANATION
068
Conformal
Rating
Enclosure
Open Chassis / IP00N
ENCLOSURE TYPE AND CONFORMAL COATING
A
N
OptionsCat. Code
INPUT FILTER ITEMS
Replacement Power Module Only
Assembled Input Filter with Power Module
NoneN
VersionCat. Code
Note: HIM is ordered separately.
DPICat. Code
3
NoneN
DeviceNet
RIOR
ControlNet (Coax)
COMM SLOTS
DriveLogix (NetLinx)
None
N/A
N/A
N/A
NoNoN
EMC Cat. Code
INTERNAL EMC FILTERING
NoneNoneN
Brake ResistorBrake IGBTCat. Code
DYNAMIC BRAKE IGBT & BRAKE RESISTOR
Common Mode
N/A
ControlNet (Fiber)
N/A
N/A
RS485 DF-1S
Ethernet
N/A
N/A
ControlNet (Coax)
ControlNet Redundant (Coax)
N/A
ControlNet (Fiber)
N/A
N/A
N/A
DeviceNet
ControlNet Redundant (Fiber)
EtherNet/IP (Twisted Pair)
Note that selections are mutually exclusive. For two Comm devices
Requires 700S Phase II Control with Logix Expansion.
(DPI and NetLinx), select the NetLinx Comm option and order the
DPI Comm kit separately.
3
4
12345678910111213141516
20NDNNENNNNANE
PRODUCT
LPM2020N
ProductCat. Code
Input
608 A3 PH.608 AD608500
Current
INPUT VOLTAGE & OUTPUT CURRENT RATING
Input
380 - 480 VAC
Voltage Range
P-6Overview
Notes:
Chapter 1
Installation/Wiring
This chapter provides information on mounting and wiring the LPM20 Drive.
For information on ...See page ...
Powe r R at in gs
Enclosure Ratings1-2
Drive Component Locations1-2
AC Supply Source Considerations1-11
Mounting the Drive, Determining Wire Routing, and Grounding1-12
Coolant Considerations1-14
Installing Input Power Wiring1-17
Installing Output Power Wiring1-19
Powe r W ir ing1-20
Using Input/Output Contactors1-22
I/O Wiring1-23
Main Control Board I/O and Encoder Settings1-31
Connecting SynchLink1-32
Active Converter Communication1-33
Auto Tune Operation1-33
Pre-charge Operation1-34
Wiring the Active Converter Control Board I/O Terminals1-34
CE Conformity1-36
C-Tick Conformity1-37
1-1
Power Ratings
Catalog Number
(positions 1-7 only)
20ND608505380 to 4806086085009000/3000
(1)
110% output current capability for one minute, 150% output current capability for 5 seconds.
(2)
Note that LPM20 drives are rated for use with water at specified temperatures and pressures as the coolant. Some coolant fluids may allow an increased
output rating while others may require the output to be derated. LPM20 drives are also capable of running at 2 kHz or 3 kHz.
Input
Power (KVA)
Most start-up difficulties are the result of incorrect wiring. Every precaution
must be taken to assure that the wiring is done as instructed. All items must
be read and understood before the actual installation begins.
ATTENTION: The following information is merely a guide for
proper installation. The Allen-Bradley Company cannot assume
!
responsibility for the compliance or the noncompliance to any
code, national, local or otherwise for the proper installation of this
drive or associated equipment. A hazard of personal injury and/or
equipment damage exists if codes are ignored during installation.
LPM20 Drives with High Performance Drive Control have power ratings as
described in Tabl e 1.A
Table 1.A Power Ratings
Input
Vol t a g e ( V )
Input
Current (Amps)
below:
(1)
Output Current
(2)
at 4 kHz
(Amps)
HP Ratings
Full Load Power Loss
Watts Fluid/Air
1-2Installation/Wiring
Enclosure Ratings
Drive Component Locations
LPM20 drives have the following enclosure rating:
• Open-Chassis Style: Intended to be installed in an enclosure.
LPM20 drives must be placed in an enclosure.
LPM20 Liquid-Cooled AC drives with High Performance Drive Control are
comprised of an input components section and a power module section.
Drive Input Component Locations
The input components section contains the following main components.
The numbered items listed below correspond to the numbers used in
Figure 1.1
1.Main Circuit Breaker
2.Circuit Breaker Operating Mechanism
3.Capacitor Bank Filter
4.Fan Tray
5.Precharge AC Contactors (3)
6.Fuses, 15A, Primary Control Transformer (2)
7.Control Transformer, 120 VAC, 1 Phase, 3 KVA
8.Ground Lug, 2-600 MCM
9.Inductor
10. Fuses, Precharge Resistors, 20A, 600V (3)
11. Terminal Block, 4-Position
12. Precharge Resistors (3)
13. 115V Fans (2)
. Replacement parts are listed in Chapter 3.
Figure 1.1 Drive Input Components
Installation/Wiring1-3
13
1
2
3
8
7
6
101112
SECTION A-A
5
9
A
A
4
See SECTION A-A
1-4Installation/Wiring
Power Module Component Locations
The power module section contains the following main components. The
numbered items listed below correspond to the numbers used in Figure 1.2
and Figure 1.3
1.Cable Assembly, 40-pin, 0.050 in. Pitch, Flex Film (1)
2.Cable Assembly, 30-pin, 0.050 in. Pitch, Flex Film (1)
3.Cable Assembly, 40-pin, 0.050 in. Pitch, Flex Film (1)
4.Wire Harness Assembly, Power Supply, Upper Gate (2)
5.Inverter Power Interface Assembly
6.Wire Harness Assembly, Power Supply, Lower Gate, PF700S (1)
7.80 W Power Supply Assembly (2)
8.Insulation Sheet (2)
9.Cable Assembly, 40-pin, 0.050 in. Pitch, Flex Film (1)
10. Cable Assembly, 30-pin, 0.050 in. Pitch, Flex Film (1)
11. Wire Harness Assembly, Power Supply, Logic (2)
12. Wire Harness Assembly, Power Supply, Lower Gate (1)
13. Rectifier Power Interface Assembly
14. Current Feedback Device, 1000A (6)
15. Wire Harness Assembly, Gate Driver
16. Wire Harness Assembly, Current Feedback Device
17. Wire Harness Assembly, Input Filter (1)
18. Wire Harness Assembly, DC Bus Bleeder Resistors (1)
19. High Voltage Interconnect Assembly (1)
20. PF700S Voltage Feedback, 400V Class, Assembly (1)
21. Terminal Block, 2-Position (1)
22. Cable Assembly, 10-Position, Ribbon (1)
23. PF700S Control Cassette
24. Active Converter Assembly
25. Connector, Terminal Block, 15-pin
26. Connector, Terminal Block, 7-pin
27. Voltage Feedback Resistor, 460V, Assembly
28. Internal Fan
29. Communications Interface Assembly
30. Cable Assembly, 20-pin, 0.050 in. Pitch, Flex Film (optional)
31. Communications Module (optional)
. Replacement parts are listed in Chapter 3.
Figure 1.2 Power Module Component Locations – Door Open
Installation/Wiring1-5
19
1
2
3
4
5
6
7
8
9
20
11
10
11
4
12
7
8
13
4
14
15
16
17
18
1-6Installation/Wiring
Figure 1.3 Power Module Component Locations – Door Closed
29
21
1
22
23
30
31
22
24
25
26
27
28
Installation/Wiring1-7
DPI Communication Port
The Communication Interface PCB contains an eight-position, female,
locking mini-DIN connector that is used as a DPI communication port. This
port (DPI Port 4 shown in Figure 1.4
between the LPM20 drive and another DPI device (for example, a HIM).
Figure 1.4 DPI Communication Interface Board
DPI
Port 3
below) provides communication
DPI
Port 4
DPI
Port 5
For more information regarding operating LPM20 drives with a HIM, refer
to Appendix
Determining Total Area Required Based on Drive Dimensions
Overall drive dimensions are illustrated in Figure 1.5 and Figure 1.6 as an
aid in calculating the total area required by the LPM20 drives.
B.
1-8Installation/Wiring
Figure 1.5 Power Module Dimensions and Mounting
1.19
0.80
0.88
0.75
1.50
0.25
Ø.472
DETAIL A
Input and Output Wiring Connection
SCALE 1:2
Coolant Connections
See Notes 2 and 3
OUT
4.76
13.72
IN
8.96
1.25
4.75
Ø.213 Thru
For M6 TAPTITE
Screw with Enclosure
Mounting Bracket
Lifting
Ø1.00
Both Sides
W
V
U
L3
A1-P1
L2
Input Filter
Harness
Connector
L1
9.03
36.04
4.48
20.66
Output
Wiring
to Motor
4.48
4.48
6.66
3.05
Drive
Drive
Input
Wiring
21.97
16.00
1.92
1.75
2.65 From Back of
Chassis to ORFS of
Sealing Surfaces
6.84
1.98
SEE DETAIL A
Lifting Ø1.00 Both Sides
LEFT SIDE VIEW
NOTES:
1. Floor Mounting Flange Holes:
A. Accept M8 Thread-Rolling Screws per SAE J1237.
B. Tightening Torque: 20-24 [N-M], 15-17 [FT-LBF].
2. Inlet and Outlet Coolant Connection Hardware Provided With Unit:
A. ORFS Braze Sleeve:
a. Material: Brass; for 5/8" O.D. Copper Tube.
b. Reference: Parker Hannifin P/N 10 TL-B, or equivalent.
B. ORFS Nut:
a. Material: Brass; for 5/8" O.D. Copper Tube, 1-14 UN/UNF-2B Thread.
b. Tightening Torque: 37-45 [N-M], 27.1-33.3 [FT-LBF].
c. Reference: Parker Hannifin P/N 10 BL-B, or equivalent.
3. Coolant Connection Hardware Provided by User:
A. ORFS Braze Adapter:
a. Material: Brass; for 5/8" O.D. Copper Tube, 1-14 UN/UNF-2A Thread.
b. Reference: Parker Hannifin P/N 10 LHB3-B, or equivalent.
B. ORFS O-Ring:
a. Material: Neoprene Rubber.
b. Size: 0.614 I.D., 0.070 Width.
c. Reference: Parker Hannifin P/N 2-016-C0873-70, or equivalent.
C. O-Ring Lubricant: Parker Hannifin Super-O-Lube, or equivalent.
9.25
6.75
1.56
2.08
1.43
0.50
3.88
2.31
FRONT
VIEW
3.64
6.05
18.49
4.81
Installation/Wiring1-9
Neg (-)
4.12
DC
A31
A32
A33
DC
Pos (+)
2.92
DC Bus Measurement
1.15
Points on Laminated
Bus Ass'y 0.25" x 0.032"
Male Faston. Accessible
by Removal of Top Cover.
SEE DETAIL
GATE KILL
A22-TB1 & TB2
Main Control Ass'y
Terminal Blocks
32.16
A12-P1 Active
Converter Control
Ass'y Terminal
Block 15-Pos.
A11-P2 Voltage
Feedback
Resistor Ass'y
Terminal
Block 7-Pos.
13.47
10.32
8.27 (A33)
6.17 (A22-TB1 & TB2)
5.54 (DC Bus Measurement Points)
SEE DETAIL COG
25.90
2.96
OUT
9.50
0.44
DETAIL COG
SCALE 5:16
CENTER OF GRAVITY:
X = 17.5"
Y = 3.1"
Z = 7.4" (into Plane
of Drawing)
WEIGHT:
162 LBS.
Verifying that Site Provides for Recommended Air Flow Clearances
Be sure there is adequate clearance for air circulation around the
user-supplied enclosure. A 6-inch minimum clearance is required wherever
vents are located in the cabinet.
For proper cabinet ventilation, roof spacers must be field installed as shown
in Figure 1.6
.
Installation/Wiring1-11
Verifying Power Module Input Ratings Match Supplied Power
It is important to verify that plant power will meet the input power
requirements of the LPM20 drive’s Power Module circuitry. See Ta ble 1 . A
for input power rating specifications. Be sure input power to the drive
corresponds to the drive nameplate voltage and frequency.
AC Supply Source
Considerations
LPM20 drives are suitable for use on a circuit capable of delivering up to a
maximum of 100,000 rms symmetrical amperes, and a maximum of 480 volts.
A circuit breaker with shunt trip as supplied with input drive components with
the appropriate kAIC rating must always be used upstream of the power module.
ATTENTION: To guard against personal injury and/or equipment
damage caused by improper circuit breaker selection, use only the
!
recommended circuit breakers specified in Tab le 1 . B
Unbalanced or Ungrounded Distribution Systems
LPM20 drives should not be used with a supply system that is ungrounded and
when the phase-to-phase voltage exceeds 125% of normal line-to-line voltage.
ATTENTION: LPM20 drives contain protective MOVs on the
drive’s printed circuit boards. The MOVs are referenced to ground.
!
The MOVs should not be disconnected.
Input Power Conditioning
Certain events on the power system supplying a drive can cause component
damage or shortened product life. They are:
.
• The power system has power factor correction capacitors switched in and
out of the system, either by the user or by the power company.
• The power source has intermittent voltage spikes in excess of 6000 volts.
These spikes could be caused by other equipment on the line or by events
such as lightning strikes.
• The power source has frequent interruptions.
Wiring Requirements for the Drive
Certain drive requirements should be checked before continuing with the
drive installation. Wire sizes, branch circuit protection, encoder feedback (for
FVC regulation), and wiring to disable the drive are all areas that need to be
evaluated.
Operation of the drive can be disabled in two locations. Gate Kill terminal
block (A33) on the front of the power structure can be used to disable the
firing of inverter IGBTs. When the connection between terminals 1 and 2 is
opened, inverter IGBTs are disabled independent of any software control.
This action also generates fault 207 in the inverter to enunciate this
1-12Installation/Wiring
condition. As a result of this fault, the active converter is also turned off, but
this is done via software operation. The firing of IGBTs in the active
converter can be disabled independently of any software control by opening
the connection between terminals 13 and 14 on the active converter control
assembly terminal block A12-P1. This action also genrates a fault in the
inverter to enunciate this condition. Wiring diagrams are shown in
Figure 1.5
Input Line Branch Circuit Protection
!
Table 1.B AC Input Circuit Breaker Values
and on page C-3.
ATTENTION: Most codes require that upstream branch
circuit protection be provided to protect input power wiring.
The circuit breaker values provided in the Drive Input
Components are listed in Tabl e 1.B
.
Mounting the Drive,
Determining Wire Routing,
and Grounding
LPM20 Drive Catalog Number
(positions 1-7 only)
20ND608380-480 VAC800 A
Note: One 120 VAC shunt trip to be installed as shown in the drive wiring
diagram on page C-2
This section shows how to mount the drive and properly ground it. Also
described is the wiring to be routed in and out of the drive.
Lifting and Mounting the Power Module
Use the following procedure to lift the LPM20 power module and mount it
in the required enclosure:
1. Install two s-hooks into the power module to serve as lifting points. Two
1-inch through holes are provided in the sheet metal chassis.
2. Connect 18 inches (nominal) of chain between the s-hooks and secure
them with a clevis clamp.
3. Using an overhead or portable hoist (minimum 1/2-ton rated capacity),
attach a free-fall chain to the chain secured to the drive. Take up any
vertical slack in the chain.
Input Voltage
.
Circuit Breaker
Provided
4. Using the hoist, lift the power module from the horizontal shipping pallet.
5. Position the power module in the enclosure.
6. In order to maintain a flat mounting surface and to ensure that bolt tightness
is maintained, use flat washers and split-ring lock washers under the bolt
heads. Refer to Figure 1.5
7. Remove the s-hooks and chain.
for power module mounting dimensions.
Installation/Wiring1-13
Verifying the Drive’s Watts Loss Rating
When mounting the drive inside of an enclosure, you should determine the
watts loss rating of the drive from Tabl e 1.A
load power loss watts value at 2 kHz (rated carrier frequency). Ensure that
the enclosure is adequately ventilated with 0
the drive’s watts loss rating.
Determining Input, Motor Output, Ground, and Control Wire Routing for
the Drive
All wiring should be installed in conformance with the applicable local,
national, and international codes (e.g., NEC/CEC). Signal wiring, control
wiring, and power wiring must be routed in separate conduits to prevent
interference with drive operation. Use grommets, when hubs are not
provided, to guard against wire chafing. Figure 1.5
wire routing, grounding terminal, and power terminal strips of LPM20
drives with High Performance Drive Control.
. This table lists the typical full
° to 40° C ambient air based on
and Figure 1.6 show the
ATTENTION: Do not route signal and control wiring with
!
Do not route more than three sets of motor leads through a single conduit.
This will minimize cross-talk that could reduce the effectiveness of noise
reduction methods. If more than three drive/motor connections per conduit
are required, shielded cable must be used. If possible, each conduit should
contain only one set of motor leads.
!
Grounding the Drive
power wiring in the same conduit. This can cause interference
with drive operation. Failure to observe this precaution could
result in damage to, or destruction of, the equipment.
ATTENTION: Unused wires in conduit must be grounded at
both ends to avoid a possible shock hazard caused by induced
voltages. Also, if a drive sharing a conduit is being serviced or
installed, all drives using this conduit should be disabled to
eliminate the possible shock hazard from cross-coupled motor
leads. Failure to observe these precautions could result in bodily
injury.
ATTENTION: The user is responsible for conforming with
!
Use the following steps to ground the drive:
1. Open the door of the enclosure.
all applicable local, national, and international codes. Failure to
observe this precaution could result in damage to, or
destruction of, the equipment.
1-14Installation/Wiring
2. Run a suitable equipment grounding conductor unbroken from the drive
to the motor’s ground terminal and then to earth ground. Use one of the
bolts that pass through the drive baseplate and are used to fasten the drive
to the wall or cabinet. See Figure 1.6
connections to the proper torque as shown in Table 1 . D
3. Connect a suitable grounding conductor to the motor frame and the
remote control station (if used). Run each conductor unbroken to earth
ground. When adding more than one grounding conductor wire to a
single chassis ground, twist the conductors together. Tighten these
grounding connections to the proper torque as shown in Table 1.D
4. Close the door of the enclosure.
. Tighten these grounding
.
.
Coolant Considerations
LPM20 drives use o-ring face seal fittings for connection to the coolant
supply. The coolant is typically clean water with a corrosion inhibitor as
described in this section.
LPM20 drive coolant connections are made with o-ring face seal fittings.
The copper tube running from the heatsink to the o-ring fittings is covered
with closed cell foam insulation.
The mating connection is shown in Figure 1.7
the following steps:
1. Coat the o-ring with the o-ring lubricant. The goal is a thin film covering
the entire o-ring surface. Avoid excess globs of lubricant.
2. Insert the o-ring into the o-ring groove in the external thread-side fitting
on the user side. Avoid any twisting of the o-ring.
3. Assemble the fittings and tighten to a torque of 37 to 45 N-m (or 27 to 33
lb.-ft.). Use a backup wrench on the user side fitting to avoid twisting the
drive side tubing.
Figure 1.7 Mating Connection
DRIVE SIDE CONNECTION
ORFS Braze Sleeve
5/8-inch O.D.
Copper Tube
(Parker p/n 10-TL-B)
. The mating process includes
USER SIDE CONNECTION
ORFS Braze Adapter
(Parker p/n 10-LOHB3-B)
ORFS Nut
(Parker p/n 10-BL-B)
O-Ring, Neoprene
(Parker p/n 2-016-CO873-70)
(Parker p/n 884-2GRAMS-LUBE)
O-Ring Lubricant
5/8-inch O.D.
Copper Tube
Backup Wrench
(Use to prevent twisting
during nut tightening.)
Installation/Wiring1-15
Other recommendations include:
1. The allowable coolant temperature range is 0°C to 40°C (32°F to 105°F).
When using coolant at a temperature below the dew point of the
surrounding air, condensation could accumulate on the drive heatsink
and/or circuit boards and damage the drive. In this situation, install a
coolant flow regulating device and tube/hose insulation. A flow
regulating device modulates the coolant flow rate to a level that permits
the drive heatsink temperature to rise above the dew point. Insulation for
customer side tube or hose may be closed-cell foam insulation with
minimum 1/2-inch wall thickness.
2. Install a flow switch after the coolant outlet connection to shutoff the
drive if coolant flow drops below 4 gpm.
3. Circulate water through the drive only when the drive is also powered.
Failure to do this may result in condensation accumulating on the drive
heatsink and/or circuit boards, which could damage the drive.
4. For applications requiring a closed loop coolant system, ensure the
system is vented to remove air that would otherwise degrade the
performance of the drive heatsink.
Coolant Connections
LPM20 drives with High Performance Drive Control have inlet and outlet
connections as shown in Figure 1.5
are bolted to the heatsink.
The rated working pressure of the drive is 185 psig. Coolant supply and
return lines should be sized for 10 gpm/185 psig service with a maximum
operating temperature of 40°C (105°F). The required operating flow rate
and pressure drop is specified in Tabl e 1.C
Coolant Requirements
LPM20 drives are rated for use with coolant consisting of clean water with a
corrosion inhibitor. Deionized water is prohibited. Use distilled water or
water with the following concentrations:
• Less than 50 ppm of sulfate and chloride.
• Less than 50 ppm of hard water ions such as Mg++ and Ca++.
Coolant must be properly strained and/or filtered to ensure it is free of
contamination.
. Tube assemblies with O-ring fittings
.
The coolant must be compatible with the following materials: Copper,
brass, aluminum, and neoprene.
1-16Installation/Wiring
Table 1.C Coolant Requirements for LPM20 Drives
LPM20 Drive
Catalog Number
(positions 1-7 only)
20ND608
(1)
Water equals good quality or distilled water with Chemtool, Inc. corrosion inhibitor, 2% inhibitor by volume.
(2)
WEG25 equals good quality or distilled water with approved ethylene glycol, 25% glycol by volume.
(3)
WEG50 equals good quality or distilled water with approved ethylene glycol, 50% glycol by volume.
Max. Output
Current (Amps)
6085 to 40710Water
6080 to 40710WEG25
5500 to 40710WEG50
6080 to 401022WEG50
6080 to 30710WEG50
Corrosion Inhibitor
A corrosion inhibitor is required. The following two options are approved
sources:
1. Chemtool, Inc. (www.chemtool.com) part number Watertool 4435-C.
The recommended concentration of the inhibitor is 8 to 10% by volume.
2. Dow Chemical (www.dow.com) Dowtherm
glycol. The recommended concentration of the inhibitor is 25% by
volume.
Coolant
Temperature
Range (°C)
Minimum
Coolant Flowrate
(GPM)
Pressure Drop From Drive
Inlet to Drive Outlet (PSIG) at
Minimum Coolant Flow Rate
®
SR-1 inhibited ethylene
Coolant
Typ e
(1)
(2)
(3)
(3)
(3)
Dowtherm is a registered trademark of the Dow Chemical Company.
ATTENTION: Ethylene glycol must be inhibited and silicate
!
Biocide
A biocide may be needed to control biological growth. Use of a biocide is
permitted. For specific recommendations, consult a reputable water
treatment company.
free. Use of common silicate-containing, automotive-type
ethylene glycol solutions is prohibited as they may damage the
drive and cooling module equipment.
Loading...
+ 64 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.