Rockwell Automation 1769-L23E-QB1B, L23E-QBFC1B, L23-QBFC1B User Manual

1769 CompactLogix Packaged Controllers
Catalog Numbers 1769-L23-QBFC1B
Quick Start and User Manual
1769-L23E-QB1B, 1769-L23E-QBFC1B,
Important User Information
WARNING
IMPORTANT
ATTENTION
SHOCK HAZARD
BURN HAZARD
Solid state equipment has operational characteristics differing from those of electromechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid State Controls (publication SGI-1.1 Automation sales office or online at http://www.rockwellautomation.com/literature/ between solid state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for indirect or consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes. Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written permission of Rockwell Automation, Inc., is prohibited.
Throughout this manual, when necessary, we use notes to make you aware of safety considerations.
) describes some important differences
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
Identifies information that is critical for successful application and understanding of the product.
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequence
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that dangerous voltage may be present.
Labels may be on or inside the equipment, for example, a drive or motor, to alert people that surfaces may reach dangerous temperatures.
Allen-Bradley, Rockwell Automation, Rockwell Software, CompactLogix, Point I/O, PowerFlex 40, PanelView Plus, Stratix 6000, Logix5000, RSLinx, RSLinx Enterprise, FactoryTalk View SE, and TechConnect are trademarks of Rockwell Automation, Inc.
Trademarks not belonging to Rockwell Automation are property of their respective companies.

Summary of Changes

Introduction

Updated Information

The release of this document contains new and updated information. Change bars on the side of the page indicate new and updated information.
This document contains the following changes.
Topic Page
DH-485 Network Communication 184 Determine Expansion Module Limits 230 Expansion I/O RPI 231 Program the Packaged Controller 233
3Publication IASIMP-QS010B-EN-P - October 2009 3
Summary of Changes
Notes:
4 Publication IASIMP-QS010B-EN-P - October 2009
CompactLogix L23E
QBFC-1B
Chapter 3
Create a Project Using
RSLogix 5000 Software
Chapter 1
Assemble the CompactLogix
Hardware
Chapter 2
Prepare the Computer, Network, and
Controller
Chapter 7
Optional ­Configuration of the DeviceNet Network
Chapter 4
Add POINT I/O
Modules to the Project
Chapter 5
Add a PowerFlex 40
Drive
Chapter 6
Add a PanelView Plus
600 Terminal
Optional
Depending on your system.
page 23
page 29
page 125
page 53
page 83
page 97
Optional Network
(not used to complete examples)
For general information about your packaged controller, start with the User Manual on page 151
.
To begin using your packaged controller, start here.
page 73
CompactLogix L23E
Where to Start
QBFC-1B
5Publication IASIMP-QS010B-EN-P - October 2009 5
Where to Start
PanelView Plus 600PanelView Plus 600
PV+ 600
Stratix 6000 Switch
PowerFlex 40
Component Class
Drive
POINT I/O Modules
I/O
I/O
CompactLogix L23E
1769-L23E-QBFC1 or 1769-L23E-QB1B
Workstation

Configurations for Quick Start

This quick start demonstrates the use of this hardware and network configuration.

Option 1: 1769-L23E Packaged Controller with an EtherNet/IP Network

An Ethernet switch other than the Stratix 6000 switch may be used. For this quick start, the Stratix 6000 switch is recommended.
6 Publication IASIMP-QS010B-EN-P - October 2009
Where to Start
PanelView Plus 600PanelView Plus 600
PV+ 600
DeviceNet Network
PowerFlex 40
Component Class Drive
CompactLogix L23
POINT I/O Modules
1606
Power Supply
Workstation

Option 2: 1769-L23-QBFC1B Packaged Controller with a Serial Network

(1)
This option shows an example DeviceNet network that could be configured by using the chapter, Optional - Configuration of the DeviceNet Network
(on page 125). While that chapter provides a brief description of how to use a DeviceNet network with a 1769-L23 packaged controller, full details for using a DeviceNet network with any Logix5000 controller are contained in the DeviceNet Modules in Logix5000 Control Systems User Manual, publication DNET-UM004
Once you have selected your configuration, use the Parts List
.
on page 18 to determine what hardware you need.
If you already have your hardware, proceed to Chapter 1
Hardware, on page 23.
, Assemble the CompactLogix
(1)
Publication IASIMP-QS010B-EN-P - October 2009 7
Where to Start
Notes:
8 Publication IASIMP-QS010B-EN-P - October 2009
Quick Start
Table of Contents
Preface
Assemble the CompactLogix Hardware
About This Quick Start . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Required Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
CompactLogix Packaged Controller Software Requirements . . . . 16
POINT I/O Modules and PowerFlex 40 Drive Software
Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
PanelView Plus Terminal Software Requirements. . . . . . . . . . . . . 16
DeviceNet Network Software Requirements. . . . . . . . . . . . . . . . . 17
Parts List. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Conventions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Chapter 1
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Connect the Battery to the Packaged Controller . . . . . . . . . . . . . . . . . 25
Record the Ethernet Address (MAC) . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Make Network Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Wire Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
Prepare the Computer, Network, and Controller
Create a Project Using RSLogix 5000 Software
Chapter 2
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Terminology . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Make Network Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Install RSLogix 5000 Programming Software. . . . . . . . . . . . . . . . . . . . 33
Configure a Serial Driver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Set the IP Address for the Computer . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Assign an IP Address to the Packaged Controller . . . . . . . . . . . . . . . . 42
Configure the EtherNet/IP Driver in RSLinx Software . . . . . . . . . . . 44
Browse the EtherNet/IP Network in RSLinx Software . . . . . . . . . . . 45
Load Firmware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Install Additional Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
Chapter 3
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Create a Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
9Publication IASIMP-QS010B-EN-P - October 2009 9
Add POINT I/O Modules
Configure the Packaged Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Configure Embedded I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Add Ladder Logic to Test the Embedded Outputs . . . . . . . . . . . . . . . 59
Set the Communication Path and Download to the Controller . . . . . 62
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Chapter 4
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Mount and Connect the Network Adapter. . . . . . . . . . . . . . . . . . . . . . 67
Mount the POINT I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
Mount and Wire the POINT I/O Power Supply. . . . . . . . . . . . . . . . . 69
Wire the Adapter and I/O Modules to the Power Supply. . . . . . . . . . 70
Assign an IP Address to the POINT I/O Adapter . . . . . . . . . . . . . . . 71
Add POINT I/O Modules to the Project . . . . . . . . . . . . . . . . . . . . . . 73
Add Ladder Logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 76
Download the Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Set the POINT I/O Chassis Size . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Test the POINT I/O Light . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Add a PowerFlex 40 Drive
Add a PanelView Plus 600 Terminal
Chapter 5
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Mount the PowerFlex 40 Drive. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Wire Power. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Connect the Communication Adapter . . . . . . . . . . . . . . . . . . . . . . . . . 86
Assign an IP Address to the PowerFlex 40 Drive . . . . . . . . . . . . . . . . 88
Add the Drive to the Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Download the Project . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 92
Edit PowerFlex 40 Parameter Values . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Reference for Editing Parameters . . . . . . . . . . . . . . . . . . . . . . . . . 93
Test the PowerFlex 40 Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 96
Chapter 6
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 97
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Mount the PanelView Plus Terminal . . . . . . . . . . . . . . . . . . . . . . . . . . 99
Wire the PanelView Plus Terminal for Power . . . . . . . . . . . . . . . . . . . 99
Make Network Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Assign an IP Address to the Terminal . . . . . . . . . . . . . . . . . . . . . . . . 101
10 Publication IASIMP-QS010B-EN-P - October 2009
Optional - Configuration of the DeviceNet Network
Create a New Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 102
Create an RSLinx Enterprise Configuration in FactoryTalk View ME
Software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 103
Create Device Shortcuts to the Controller . . . . . . . . . . . . . . . . . . . . . 105
Create the OB16_Light Indicator . . . . . . . . . . . . . . . . . . . . . . . . . . . . 110
Create a Push Button . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 113
Test the Indicator and Push Button . . . . . . . . . . . . . . . . . . . . . . . . . . 115
Add a Goto Configuration Mode Button . . . . . . . . . . . . . . . . . . . . . . 117
Assign Keys . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 118
Assign an Initial Screen . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 120
Transfer to the PanelView Plus Terminal . . . . . . . . . . . . . . . . . . . . . . 121
Test the Application on the PanelView Plus Terminal . . . . . . . . . . . 123
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 124
Chapter 7
Before You Begin. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
What You Need . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 125
Follow These Steps . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 126
Attach the 1769-SDN Module to the Packaged Controller . . . . . . . . 127
Connect the 1769-SDN Module to the Network. . . . . . . . . . . . . . . . 128
Connect and Apply Power to the DeviceNet Network . . . . . . . . . . . 129
Set the 1769-SDN Module’s Node Address. . . . . . . . . . . . . . . . . . . . 130
Create a DeviceNet Scanlist. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 132
Create a DeviceNet Configuration File. . . . . . . . . . . . . . . . . . . . . . . . 135
Add the 1769-SDN Module to the RSLogix 5000 Project. . . . . . . . . 138
Create DeviceNet Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 140
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 142
Publication IASIMP-QS010B-EN-P - October 2009 11
User Manual
Preface
Overview of the CompactLogix Packaged Controllers
Network Communication
About This User Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Additional Resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 151
Chapter 1
Features of the Packaged Controllers . . . . . . . . . . . . . . . . . . . . . . . . . 153
1769-L23E-QB1B Packaged Controller . . . . . . . . . . . . . . . . . . . . . . . 154
1769-L23E-QBFC1B Packaged Controller . . . . . . . . . . . . . . . . . . . . 154
1769-L23-QBFC1B Packaged Controller . . . . . . . . . . . . . . . . . . . . . . 155
Chapter 2
EtherNet/IP Network Communication . . . . . . . . . . . . . . . . . . . . . . . 158
Software for an EtherNet/IP Network . . . . . . . . . . . . . . . . . . . . 158
EtherNet/IP Network Features . . . . . . . . . . . . . . . . . . . . . . . . . . 159
EtherNet/IP Network Connections. . . . . . . . . . . . . . . . . . . . . . . 159
Configure the 1769-L23E Ethernet Interface . . . . . . . . . . . . . . . 161
Additional Resources for EtherNet/IP Networks. . . . . . . . . . . . 163
DeviceNet Network Communication. . . . . . . . . . . . . . . . . . . . . . . . . 164
CompactLogix DeviceNet Scanner. . . . . . . . . . . . . . . . . . . . . . . . 164
Software for a DeviceNet Network . . . . . . . . . . . . . . . . . . . . . . . 164
DeviceNet Network Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . 165
Using DeviceNet Modules with the CompactLogix Controller . 165
Additional Resources for DeviceNet Networks. . . . . . . . . . . . . . 165
Serial Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 166
Determine Need for Isolator and Cable for Connection. . . . . . . 167
Communicate with DF1 Devices . . . . . . . . . . . . . . . . . . . . . . . . . 169
Communicate with ASCII Devices. . . . . . . . . . . . . . . . . . . . . . . . 172
ASCII Instructions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 174
Modbus Support . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 176
Broadcast Messages Over a Serial Port. . . . . . . . . . . . . . . . . . . . . 176
DH-485 Network Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . 184
Additional Resources for DH-485 Communication . . . . . . . . . . 188
Additional Resources for Serial Communication. . . . . . . . . . . . . 189
Chapter 3
Embedded I/O
12 Publication IASIMP-QS010B-EN-P - October 2009
Embedded I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 191
Embedded I/O Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 192
Digital Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
DC Input Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 194
DC Input Filtering. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
Configure the DC Inputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 195
DC Input Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 197
Digital Outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
DC Output Wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 198
Add Additional Local I/O
Configure the DC Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
DC Output Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 199
Analog I/O. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Analog I/O Wiring Diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . 200
Configure the Analog I/O . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 203
Analog I/O Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 205
High-speed Counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 207
High-speed Counters Wiring Diagrams . . . . . . . . . . . . . . . . . . . . 207
Configure the High-speed Counters. . . . . . . . . . . . . . . . . . . . . . . 212
High-speed Counter Tags . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 216
Range Control of the HSC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 225
Other Configuration Parameters. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 226
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 227
Chapter 4
Expansion Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 229
Determine Expansion Module Limits. . . . . . . . . . . . . . . . . . . . . . . . . 230
Add Expansion I/O Modules . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Expansion I/O RPI. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 231
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 232
Program the Packaged Controller
Battery Maintenance
Network Worksheet
Index
Chapter 5
Program the Controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Tasks. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 234
Programs and Equipment Phases . . . . . . . . . . . . . . . . . . . . . . . . . 234
Trends. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Monitoring Controller Status . . . . . . . . . . . . . . . . . . . . . . . . . . . . 235
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 236
Chapter 6
Battery for Use with Packaged Controllers. . . . . . . . . . . . . . . . . . . . . 237
Check Battery Power Level . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 237
Estimate 1769-BA Battery Life . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
Store Batteries. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
Additional Resources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 238
EtherNet/IP Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
DeviceNet Network. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
1769-SDN Module Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 239
RSNetWorx for DeviceNet Configuration File Information. . . . . . . 239
Publication IASIMP-QS010B-EN-P - October 2009 13
Notes:
14 Publication IASIMP-QS010B-EN-P - October 2009
Preface

About This Quick Start

This quick start provides examples and procedures for the use of a CompactLogix packaged controller system. This publication also includes RSLogix 5000 programming software version 18 updates.
The procedures cover many of the most common user tasks, such as:
• connecting the controller to multiple devices (local and distributed I/O, a drive, and a PanelView Plus terminal).
• connecting and configuring networks (EtherNet/IP, DeviceNet, and serial) for use with CompactLogix systems.
• creating and monitoring controller programs.
The examples are designed to get devices installed and communicating with each other in the simplest way possible. The programming examples are not complex, and offer easy solutions to verify that devices are functioning and communicating properly.
The beginning of each chapter contains the following information. Read these sections carefully before beginning work in each chapter:
Before You Begin - This section lists the steps that must be completed and decisions that must be made before starting that chapter. The chapters in this quick start do not have to be completed in the order in which they appear, but this section defines the minimum amount of preparation required before completing the current chapter.
What You Need - This section lists the tools that are required to complete the steps in the current chapter. This includes, but is not limited to, hardware and software.
Follow These Steps - This illustrates the steps in the current chapter and identifies which steps are required to complete the examples for specific networks or configurations.
Also, additional resources, such as websites, technical notes, and other Rockwell Automation publications are listed in the Additional Resources tables at the end of each chapter.
15Publication IASIMP-QS010B-EN-P - October 2009 15
5

Required Software

Your software requirements depend upon the CompactLogix system components you are using. Use the sections below to determine the software required for your system components.
CompactLogix Packaged Controller Software Requirements
To complete any of the examples in this quick start, you need one of these editions of RSLogix 5000 programming software, version 17 or later:
•Lite
•Mini
•Full
•Standard
•Professional
You install and use these utilities included with the RSLogix 5000 programming software to complete the examples in this quick start:
•BootP-DHCP server
• ControlFlash
• RSLinx Classic, version 2.54 or later
Verify that these utilities are included with your RSLogix 5000 software package.
POINT I/O Modules and PowerFlex 40 Drive Software Requirements
If you are using POINT I/O modules or a PowerFlex 40 drive to complete examples in this quick start, only the software listed for the CompactLogix packaged controllers is required.
PanelView Plus Terminal Software Requirements
If you plan to complete the PanelView Plus examples within this quick start, FactoryTalkView Machine Edition software is required in addition to the software required for the use of the packaged controller.
16 Publication IASIMP-QS010B-EN-P - October 2009
DeviceNet Network Software Requirements
If you plan to use a DeviceNet network with your packaged controller, this software is required:
• RSNetWorx for DeviceNet
• DeviceNet Tag Generator (included with RSLogix 5000 programming software)
5
Publication IASIMP-QS010B-EN-P - October 2009 17
5

Parts List

Hardware Used in This Quick Start
Quantity Cat. No. Description
General Configuration
1 1769-L23E-QB1B,
1769-L23E-QBFC1B, or
1769-L23-QBFC1B 1 1769-ECR Compact I/O Right End Cap/Terminator (included with packaged controller) 1
1
1
1-3
1 1794-PS13 FLEX I/O 85…264V AC to 24V DC 1.3 A Power Supply 1 22B-V2P3N104 PowerFlex 40 Drive 1 22B-CCB PowerFlex 40 Communication Adapter Cover 1 2711P-T6C20A PanelView Plus 6-inch Color Keypad Terminal with EtherNet/IP and RS-232 Networks
1734-IB4
1734-OB4E
1734-OE2C
1734-TB
(1)
(2)
(1)
(3)
This table lists the hardware used in this quick start. The hardware you need depends on the options and examples you choose to complete. Specific hardware requirements are listed at the beginning of each chapter.
CompactLogix Packaged Controller
POINT I/O 4 Sink Input Module
POINT I/O 4 Protected Output Module
POINT I/O 2 Current Output Analog Module
Wiring Base w/ Removable IEC Screw Terminals
1 1794-PS3 or
2711P-RSACDIN 2 1756-CP3 RS-232 Cable 1 2706-NC13 PanelView Plus Serial Cable 2…3 N/A DIN Rail (steel not aluminum) 1 1606-XLS80E DC Power Supply
EtherNet/IP Configuration
1 1734-AENT POINT I/O EtherNet/IP Adapter 1 22-COMM-E EtherNet/IP Adapter for Use With the PowerFlex 40 Drive 1 1783-EMS08T Stratix 6000 Ethernet Switch (recommended), Stratix 2000 Ethernet Switch (for
6 1585J-M8
Serial Configuration
1 1756-CP3 RS-232 cable 1 2706-NC13 Point-to-point RS-232 Cable (required with 1769-L23-QBFC1B packaged controllers,
Flex I/O Power Supply or Other General-use Power Supply to supply 70 W DC power to PanelView Plus (if DC power is required for your terminal)
applications without remote I/O), or other Ethernet Switch
(5)
Industrial-grade Ethernet Cables
optional with 1769-L23E packaged controllers)
or Other Standard Ethernet Cables
18 Publication IASIMP-QS010B-EN-P - October 2009
Hardware Used in This Quick Start
Quantity Cat. No. Description
DeviceNet Configuration
1 1769-SDN Compact I/O DeviceNet Scanner 1
1734-ADNX
(4)
POINT I/O DeviceNet Adapter
1 22-COMM-D DeviceNet Adapter for Use with the PowerFlex 40 Drive 1 1606-XLDNET8 DeviceNet Power Supply N/A 1485C-P1E75 KwikLink Flat Cable 2 1485A-T1E4 KwikLink Terminator/Resistor 4 1485P-P1E4-R5 KwikLink Sealed Micro Connector 4 1485K-P1F5-C KwikLink Right-angle Male to Cable 1 1485T-P1E4-B1 KwikLink Power Tap Module
(1)
Use POINT I/O modules at series C or later to complete examples in this quick start.
(2)
The 1734-OB4E module is the only POINT I/O module used in this quick start. The other modules are added only as examples and are not required.
(3)
The number of wiring bases you need depends upon the number of POINT I/O modules you use in your system.
(4)
The examples in this quick start use the 1734-ADNX POINT I/O adapter. However, you may choose to use the 1734-ADN adapter instead.
(5)
For more information about industrial grade cables, see the Ethernet Connectivity product profile, publication
1585-PP001
.
5
Publication IASIMP-QS010B-EN-P - October 2009 19
5

Conventions

Convention Meaning Example bold Bold text denotes menus, menu items, buttons, or options. Click OK.
Check/uncheck Click to activate/deactivate a checkbox. Check the Open Module Properties checkbox. Click Click left mouse button once. (Assumes cursor is positioned on
object or selection.)
Courier font
Double-click Click left mouse button twice in quick succession. (Assumes
Expand Click the + to the left of a given item /folder to show its
Right-click Click right mouse button once. (Assumes cursor is positioned on
Select Click to highlight a menu item or list choice. Select Properties from the pull-down menu. > Shows nested menu selections as menu name followed by menu
Type or enter text exactly as shown. Type cmd.
cursor is positioned on object or selection.)
contents.
object or selection.)
selection.
This manual uses the following conventions.
Click Browse.
Double-click the H1 icon.
In the H1-1 window, expand the FFLD.
Right-click the Fieldbus Networks icon.
Click File
> Page Setup > Options.
20 Publication IASIMP-QS010B-EN-P - October 2009

Additional Resources

Resource Description
1769 CompactLogix Controllers Selection Guide, publication 1769-SG001
1769 Compact I/O Selection Guide, publication
1769-SG002
NetLinx Selection Guide, publication
NETS-SG001
Provides information and specifications for consideration when selecting CompactLogix controllers and software.
Provides information and specifications for consideration when selecting I/O modules for use with the CompactLogix system. It includes Compact I/O, POINT I/O, and FLEX I/O modules.
Provides information and specifications for consideration when selecting a network to use and which hardware and cables you need.
5
EtherNet/IP Media Planning and Installation Manual, publication
Ethernet Connectivity Product Profile, publication
1585-PP001
ENET-IN001
Provides information about how to select and install your EtherNet/IP network physical media.
Provides information specific to the industrial-grade Ethernet Connectivity products, including RJ45 cables, offered by Rockwell Automation.
Publications are available for viewing or electronic download at
http://literature.rockwellautomation.com
.
Publication IASIMP-QS010B-EN-P - October 2009 21
5
Notes:
22 Publication IASIMP-QS010B-EN-P - October 2009

Assemble the CompactLogix Hardware

In this chapter, you install your CompactLogix hardware packaged controller.

Before You Begin

Determine which of these networks and appropriate hardware to use:
For the EtherNet/IP network (option 1), use either the 1769-L23E-QB1B or
1769-L23E-QBFC1B controller.
Chapter
1
For a serial connection (option 2), use the 1769-L23-QBFC1B controller.

What You Need

CompactLogix packaged controller: 1769-L23E-QB1B, 1769-L23E-QBFC1B, or
1769-L23-QBFC1B.
CompactLogix controller battery: 1769-BA (included with your controller).
Power supply: This quick start uses the 1606-XLS80E supply, but any DC power supply
that meets the requirements for the 1769-L23 controllers may be used.
Compact I/O end cap: 1769-ECR (included with your controller).
Compact I/O DeviceNet scanner module: 1769-SDN (only if you are using a
DeviceNet network).
Network cable: Ethernet (1585J-M8 or similar), serial (1756-CP3).
Stratix 6000 or other Ethernet switch.
23Publication IASIMP-QS010B-EN-P - October 2009 23
Chapter 1 Assemble the CompactLogix Hardware
Connect the Battery
to the Packaged
Controller
1769-L23E 1769-L23
Record the
Ethernet Address
(MAC)
Make Network
Connections
Wire Power
Connect the Battery
to the Packaged
Controller
Make Network
Connections
Wire Power
page 25
page 25
page 27
page 26
page 25
page 27
page 26

Follow These Steps

Complete the steps shown for your controller.
24 Publication IASIMP-QS010B-EN-P - October 2009
Assemble the CompactLogix Hardware Chapter 1
1. Remove the battery door and connect the battery to the controller.
2. Insert the battery into the slot on the battery door.
3. Close the battery door.
00:00:BC:21:D7:BE
Ethernet Address

Connect the Battery to the Packaged Controller

Battery

Record the Ethernet Address (MAC)

1769-L23E controllers
The Ethernet address (MAC) is found on a label near the power-supply wiring terminal. This is an example address.
Record the Ethernet address (MAC) for the CompactLogix controller on the
Network Worksheet
address later.
at the back of this quick start. This address may be used to set the IP
Publication IASIMP-QS010B-EN-P - October 2009 25
Chapter 1 Assemble the CompactLogix Hardware
CompactLogix L23E
QBFC-1B
CompactLogix L23E
1. Insert an Ethernet cable with an RJ45 connector.
2. Connect the other end of the cable
to the Ethernet switch
.
Ethernet Ports
1. Connect the 1756-CP3 cable to the channel 0 serial port on the controller.
2. Connect the other end of the cable to a COM port on the computer.
CompactLogix L23
1769-L23-QBFC1B

Make Network Connections

1769-L23E packaged controllers, option 1
1769-L23 packaged controllers, option 2
26 Publication IASIMP-QS010B-EN-P - October 2009

Wire Power

CompactLogix L23E
QBFC-1B
1. Insert the +24V DC, DC neutral, and ground wires and tighten the terminal screws.
2. Turn on incoming power.
WARNING
Verify that all incoming power is turned off before wiring power.
No Connection
+24V DC
DC Neutral
System Power Ground
No Connection
Power supply for all packaged controllers
Assemble the CompactLogix Hardware Chapter 1
Publication IASIMP-QS010B-EN-P - October 2009 27
Chapter 1 Assemble the CompactLogix Hardware

Additional Resources

Resource Description
Chapter 6
CompactLogix Packaged Controllers Installation Instructions, publication 1769-IN082
of the user manual, page 237 Provides detailed information about the use of the 1769-BA with the packaged
controllers. Provides details about assembling and mounting the controller and upgrading firmware
as well as controller technical specifications.
Publications are available for viewing or electronic download at http://literature.rockwellautomation.com.
28 Publication IASIMP-QS010B-EN-P - October 2009
Chapter
2

Prepare the Computer, Network, and Controller

In this chapter, you configure network communication on your computer and install the necessary programming and configuration software.
In this chapter, you also assign IP addresses to devices on an EtherNet/IP network. For more information about using the packaged controllers on an EtherNet/IP network, see Chapter 2 of the user manual, titled Network Communication
(page 157).

Before You Begin

Verify that your computer meets the software’s system requirements for your edition of
RSLogix 5000 software.

What You Need

RSLogix 5000 software (see the Preface for version and edition information).
ControlFlash software (packaged with RSLogix 5000 software).
RLinx Classic software, version 2.54 or later (packaged with RSLogix 5000 software).
BOOTP/DHCP server utility
The computer needs a Network Interface Card (NIC) and its associated Windows driver
installed (the NIC and driver are standard on most computers).
An Ethernet Address (MAC) for each device. You recorded these addresses in the
Network Worksheet
on the back cover.
(packaged with RSLogix 5000 software).
A planned IP Address for each device. If you are using an isolated network, determine a
numbering convention for your IP addresses. Record these addresses on the
Network Worksheet
29Publication IASIMP-QS010B-EN-P - October 2009 29
inside the back cover.
Chapter 2 Prepare the Computer, Network, and Controller
Make Network
Connections
Install RSLogix
5000 Programming
Configure a Serial
Driver
Set the IP Address
for the Computer
Configure the
EtherNet/IP Driver
in RSLinx Software
Install Additional
Software
Browse the
EtherNet/IP Network
in RSLinx Software
page 31
page 40
page 50
page 44
page 45
page 38
page 33
Assign an IP
Address to the
Packaged Controller
page 42
Serial
EtherNet/IP
Make Network
Connections
Install RSLogix
5000 Programming
page 31
page 33
Install Additional
Software
page 50
Optional
Install additional software
specific to your system.
Optional
Install additional software
specific to your system.

Follow These Steps

Complete these steps.
30 Publication IASIMP-QS010B-EN-P - October 2009
Prepare the Computer, Network, and Controller Chapter 2
1. Connect one end of the Ethernet cable to the computer.
2. Connect the other end to the Ethernet switch
Stratix 6000 Switch
Computer with a standard Ethernet port.
1769-L23E-QB1B

Terminology

Ethernet networks use these types of addresses.
Term Definition
Ethernet Address Each Ethernet device has a unique Ethernet address (sometimes called a MAC address). The
address appears as twelve digits separated by colons (for example, xx:xx:xx:xx:xx:xx). It is usually on a label on the device itself.
Each digit is a number in hexadecimal (0 to 9 or A through F). No other device in the world will have the same address, and it can not be changed.
You use the Ethernet address to identify a device so you can assign it an IP address.
IP Address In addition to the Ethernet address, an IP address identifies a node on an Ethernet network.
The IP address can be manually set. or you can use special software to automatically assign it.
An IP Address consists of four decimal integers separated by periods (xxx.xxx.xxx.xxx). Each xxx is a decimal value from 0…255. For example, an IP Address could be 192.168.1.092 The selection of IP Addresses is beyond the scope of this quick start, so please contact your network administrator or use the ones provided in the examples.
Once you set an IP address for a device, you generally reference the device by its IP address. The examples in this quick start use IP Addresses to define communication paths to the devices.

Make Network Connections

Required for option 1
CompactLogix L23E
Publication IASIMP-QS010B-EN-P - October 2009 31
Chapter 2 Prepare the Computer, Network, and Controller
TIP
Verify that you connected a 1756-CP3 cable to a COM port on the computer and to the CH0 port on the controller as described in Chapter 1.
1756-CP3 serial cable to CH0 of an 1769-L23 controller.
This connection will be used to update the controller firmware later in this chapter.
Serial connection - Required for option 2
If you are using an 1769-L23E packaged controller, you may choose to upgrade your controller firmware by using your Ethernet connection instead. If you use the Ethernet connection, you do not have to make this serial connection.
32 Publication IASIMP-QS010B-EN-P - October 2009
Prepare the Computer, Network, and Controller Chapter 2
3. Accept the default software products for installation and click Next.
Throughout the installation, click Next to use default RSLogix 5000 programming software installation settings except when indicated in the steps below.
1. Begin the RSLogix 5000 programming software installation.
2. Choose your language and click Continue.
4. Enter your user name, organization, and software serial number, then click Next.

Install RSLogix 5000 Programming Software

Required for all controllers
Publication IASIMP-QS010B-EN-P - October 2009 33
Chapter 2 Prepare the Computer, Network, and Controller
7. Select your activation type and click Next.
This quick start uses FactoryTalk Activation software to activate RSLogix 5000 programming software. For more information, see the FactoryTalk Activation FAQ, publication
FT00-FA001.
5. Accept the license agreement and click Next.
8. Click Next to install only the latest version of RSLogix 5000 programming software (version
17).
9. Verify that RSLogix 5000 Tools and Files is checked and click
Next.
6. Click Next to install the program
files to the default directory.
34 Publication IASIMP-QS010B-EN-P - October 2009
10. Click Next to install the typical firmware kits.
11. Click Next to install typical RSLogix Architect tools.
12. Click Next to install the typical set of EDS files and RSLinx software.
Prepare the Computer, Network, and Controller Chapter 2
Publication IASIMP-QS010B-EN-P - October 2009 35
Chapter 2 Prepare the Computer, Network, and Controller
13. Click Install to complete the installation.
The installation dialog box displays progress while the software installs.
TIP
As the installation progresses, you may be prompted to complete additional set-up tasks depending on your system configuration. Follow those prompts and enter information as indicated in the dialog boxes to complete your installation.
After a few moments, the FactoryTalk Installation Wizard starts.
14. Click Next.
15. Enter the Serial number
and Product key from the certification letter packaged with your software.
16. Click Next.
36 Publication IASIMP-QS010B-EN-P - October 2009
17. Select your host ID and click Next.
The activation completes if the computer is connected to the Internet.
If Internet access is not available, call Rockwell Automation Technical Support to complete your activation.
18. Click Finish to close the Activation Wizard.
Prepare the Computer, Network, and Controller Chapter 2
Publication IASIMP-QS010B-EN-P - October 2009 37
Chapter 2 Prepare the Computer, Network, and Controller
1. Launch RSLinx software.
2. From the Communications menu, choose Configure Drivers.
3. Select RS-232 DF1 devices.
4. Click Add New.

Configure a Serial Driver

Required for serial network (option 2)
38 Publication IASIMP-QS010B-EN-P - October 2009
The Serial driver is added to the Configured Drivers list.
10. Verify that the Status of the driver is Running, and click
Close.
11. Click the RSWho icon to
view the driver.
All of the configured, active drivers display.
6. Select the Comm Port to which you connected the 1756-CP3 cable.
7. From the Device pull-down, select Logix5550/CompactLogix.
8. Click Auto Configure.
9. Click OK.
Expand the serial driver to see connected devices.
Prepare the Computer, Network, and Controller Chapter 2
Publication IASIMP-QS010B-EN-P - October 2009 39
Chapter 2 Prepare the Computer, Network, and Controller
1. On your desktop, right-click My Network Places and choose Properties.
2. Double-click the Local Area
Connection.
3. Click Properties.
4. On the General tab, select
Internet Protocol (TCP/IP) and click
Properties.
5. Select Use the following IP address and enter an IP
address and Subnet mask for your computer.
6. Click OK. For more information about selecting an IP Address, see the information on page 31
.
7. Record the IP address and subnet mask in the Network Worksheet
inside the back
cover.
8. Click OK.

Set the IP Address for the Computer

Required for EtherNet/IP network (option1)
40 Publication IASIMP-QS010B-EN-P - October 2009
9. Click the Support tab.
10. Verify that the IP Address and Subnet
Mask match what you entered on the
Network Worksheet
.
If these numbers do not match what you entered, contact your network administrator to verify that your IP address is correct.
11. Close the Local Area Connection Status dialog box.
Prepare the Computer, Network, and Controller Chapter 2
Publication IASIMP-QS010B-EN-P - October 2009 41
Chapter 2 Prepare the Computer, Network, and Controller
TIP
Devices on the EtherNet/IP network broadcast requests for IP addresses until the IP addresses have been assigned.
The procedure in this chapter uses the BOOTP server packaged with RSLogix 5000 programming software to assign IP addresses, however, any industry-standard BootP server can be used.
1. After you have installed and connected your packaged, launch the BOOTP/DHCP Server utility.
2. From the Tools menu, choose Network
Settings.
3. Enter the Subnet Mask from the
Network Worksheet
.
4. Click OK.

Assign an IP Address to the Packaged Controller

1769-L23E packaged controllers
In this chapter, you use the BOOTP/DHCP server to assign an IP address to the packaged controller. You use the BOOTP server that you installed with RSLogix 5000 software.
42 Publication IASIMP-QS010B-EN-P - October 2009
The Request History displays all the devices, including the packaged controller, on your network that need an IP address. The Ethernet address (Mac ID) of the packaged controller corresponds with the address you recorded on
Network Worksheet.
5. Double-click the request from your packaged controller.
6. Enter the IP address and record it on the
Network Worksheet
inside the
back cover.
If you are not using an isolated network, obtain these numbers from your network administrator.
7. Click OK.
8. Disable BootP/DHCP by selecting the packaged controller from the Relation List and
clicking Disable BOOTP/DHCP.
[Disable BOOTP/DHCP] Command successful appears in the Status bar.
9. Close the BOOTP/DHCP Server utility.
If you are prompted to save changes, click No.
IMPORTANT
For a device to retain its IP address through a power cycle, BootP/DHCP must be disabled. Complete step
8 to disable BootP/DHCP for the packaged controller.
IP Addresses Assigned Successfully
Prepare the Computer, Network, and Controller Chapter 2
Publication IASIMP-QS010B-EN-P - October 2009 43
Chapter 2 Prepare the Computer, Network, and Controller
1. If RSLinx software is not open, launch RSLinx software.
2. From the Communications menu, choose Configure Drivers.
3. From the Available
Driver Types, choose
Ethernet/IP Driver.
4. Click Add New.
5. Click OK to keep the
default name.
6. Click OK to Browse Local Subnet.

Configure the EtherNet/IP Driver in RSLinx Software

Required for EtherNet/IP network (option 1)
44 Publication IASIMP-QS010B-EN-P - October 2009
Prepare the Computer, Network, and Controller Chapter 2
The EtherNet/IP driver is added to the Configured Drivers list.
7. Verify that the driver’s Status is Running, and click
Close.
1. In RSLinx Classic
software, click the RSWho button.
The EtherNet/IP driver and network devices display.
2. Expand the Ethernet Port and the backplane to view the packaged controller.
3. Close or minimize the RSLinx Classic window.

Browse the EtherNet/IP Network in RSLinx Software

Publication IASIMP-QS010B-EN-P - October 2009 45
Chapter 2 Prepare the Computer, Network, and Controller
1. Launch ControlFlash software.
2. Click Next.
3. Select the controller catalog
number and click Next.

Load Firmware

Required for all packaged controllers
46 Publication IASIMP-QS010B-EN-P - October 2009
4. Expand the driver associated with your packaged controller.
5. Select your packaged controller.
6. Click OK.
Ethernet
8. If the Current Revision matches the revision of firmware you want, click Cancel and skip to Chapter 3.
Otherwise, select the desired firmware revision and click Next.
Packaged Controller
7. Move the keyswitch on the controller to PROG.
Serial
Prepare the Computer, Network, and Controller Chapter 2
Publication IASIMP-QS010B-EN-P - October 2009 47
Chapter 2 Prepare the Computer, Network, and Controller
9. Click Finish and then click Yes.
The firmware upgrade begins.
IMPORTANT
Do not interupt the firmware upgrade once it has begun.
Interrupting the firmware upgrade may result in an inoperable packaged controller. After the Upgrade Status dialog box indicates the upgrade is complete, you may proceed.
10. If updating a 1769-L23E packaged controller, click OK after reading the release notes.
If using this connection The estimated time to upgrade firmware is
Ethernet 10 min Serial 40…60 min
1769-L23E Only
48 Publication IASIMP-QS010B-EN-P - October 2009
During the firmware upgrade, these Progress dialog boxes display 2 or 3 times.
Do not take any action while these status dialog boxes display.
These status changes indicate that the packaged controller is self-cycling (Polling for power-up) and continuing with the firmware upgrade (Transmitting block).
Status change.
Status change.
The Upgrade Status dialog box indicates that the firmware upgrade has been successfully completed.
11. Click OK.
12. To close the ControlFlash utility,
click Cancel and then click Yes.
Prepare the Computer, Network, and Controller Chapter 2
Publication IASIMP-QS010B-EN-P - October 2009 49
Chapter 2 Prepare the Computer, Network, and Controller
If you are completing the PanelView Plus chapters in this quick start, install
FactoryTalkView Machine Edition and RSLinx Enterprise software from the FactoryTalkView Machine Edition package. This software must be installed before you install any additional software.
If you are using a DeviceNet network, install RSNetWorx for DeviceNet software.

Install Additional Software

50 Publication IASIMP-QS010B-EN-P - October 2009

Additional Resources

Resource Description
Prepare the Computer, Network, and Controller Chapter 2
CompactLogix Packaged Controllers Installation Instructions, publication 1769-IN082
CompactLogix Packaged Controllers Release Notes, publication 1769-RN012
FactoryTalk Activation FAQ, publication
FT00-FA001
ControlFlash Firmware Upgrade Kit, publication
1756-QS105
Logix5000 Controllers Quick Start, publication
1756-QS001
EtherNet/IP Modules in Logix5000 Control Systems, publication ENET-UM001
Provides details about assembling and mounting the controller and upgrading firmware as well as controller technical specifications.
Provides descriptions of enhancements, anomalies (known and corrected), and restrictions specific to the firmware revision.
Provides answers to FactoryTalk Activation questions, including how the FactoryTalk Activation differs from master disk activation.
Provides details regarding the installation of ControlFlash software and execution of firmware upgrades.
Provides start-up procedures for all Logix5000 controllers with RSLogix 5000 software.
Provides details about using EtherNet/IP modules and devices with RSLogix 5000 and related software.
Publications are available for viewing or electronic download at http://literature.rockwellautomation.com.
Publication IASIMP-QS010B-EN-P - October 2009 51
Chapter 2 Prepare the Computer, Network, and Controller
Notes:
52 Publication IASIMP-QS010B-EN-P - October 2009
Chapter
3

Create a Project Using RSLogix 5000 Software

In this chapter you create a project in RSLogix 5000 programming software. In the project you use ladder logic to create a push button that controls a light on a digital output of the controller. This project is used in subsequent chapters to test communication with other devices.
For a programming quick reference and more information about programming your CompactLogix packaged controller, see Chapter 5
Controller, on page 233.
of the user manual, Program the Packaged

Before You Begin

Install the required software, see Chapter 2.
Configure your network, see Chapter 2
.

What You Need

A CompactLogix packaged controller (1769-L23E-QB1B, 1769-L23-QBFC1B, or
1769-L23E-QBFC1B).
53Publication IASIMP-QS010B-EN-P - October 2009 53
Chapter 3 Create a Project Using RSLogix 5000 Software
Create a Project
Configure the
Packaged Controller
Configure
Embedded I/O
Add Ladder Logic to
Test the Embedded
Outputs
Set the
Communication Path
and Download to
the Controller
page 55
page 57
page 58
page 59
page 62
Optional
Not required to complete the
examples in this quick start.

Follow These Steps

Complete these steps.
54 Publication IASIMP-QS010B-EN-P - October 2009
Create a Project Using RSLogix 5000 Software Chapter 3
1. Open RSLogix 5000 software by clicking Start > Programs > Rockwell Software > RSLogix 5000 Enterprise Series > RSLogix 5000.
The Quick Start window displays in the RSLogix workspace.
Navigation tabs for Quick Start, Learning Center, and Resource Center pages.
The Quick Start pages provide useful links, tutorials, training videos, and other tools you may choose to view before beginning your project.
2. Click New Project.

Create a Project

All controllers
Publication IASIMP-QS010B-EN-P - October 2009 55
Chapter 3 Create a Project Using RSLogix 5000 Software
3. Choose your controller and revision number.
1769-L23E-QB1B
4. Enter a unique controller name.
5. Click OK.
1769-L23E-QBFC1B
1769-L23-QBFC1B
56 Publication IASIMP-QS010B-EN-P - October 2009

Configure the Packaged Controller

1. Right-click the Ethernet Port and choose Properties.
2. Enter the controller’s IP address (recorded on the
Network Worksheet
) and
click OK.
All 1769-L23E controllers
Create a Project Using RSLogix 5000 Software Chapter 3
Publication IASIMP-QS010B-EN-P - October 2009 57
Chapter 3 Create a Project Using RSLogix 5000 Software
1. Double-click the embedded I/O you need to configure.
2. Use the tabs and boxes within the Module Properties dialog box to specify your configuration parameters.
For detailed information about configuring your embedded I/O, see
Chapter 3 of the user
manual, Embedded
I/O (page 191).

Configure Embedded I/O

Not required for quick start examples
The quick start examples use the default configuration of the embedded I/O. Before you use the embedded I/O in your application, you may choose to configure the embedded I/O specific to your application.
58 Publication IASIMP-QS010B-EN-P - October 2009

Add Ladder Logic to Test the Embedded Outputs

1. Expand the Tas ks folders and double-click MainRoutine.
A blank MainRoutine opens.
2. From the Element Toolbar, drag and drop an Examine On and an Output Energize element onto the rung.
All controllers
Create a Project Using RSLogix 5000 Software Chapter 3
Publication IASIMP-QS010B-EN-P - October 2009 59
Chapter 3 Create a Project Using RSLogix 5000 Software
3. Double-click the ? in the
Examine On.
4. Type PB (for push button).
5. Press Enter.
6. Right-click PB and choose New
‘PB’.
7. Click OK to keep the defaults.
60 Publication IASIMP-QS010B-EN-P - October 2009
9. Right-click the Output_Light tag name and choose New ‘Output_Light’.
Output_Light is an alias tag for the I/O point tag name. This lets you assign a simple name to a physical I/O point address.
10. From the Type pull-down menu, select Alias.
11. In the Alias For pull-down menu, browse to a local output point and select any bit.
In this example, Local:2:O.Data.0 is
used.
12. Click OK.
The output shows the specified output.
8. Name the Output Energize Output_Light.
IMPORTANT
Do not use spaces in the tag name. Use underscores ( _ ) instead.
Create a Project Using RSLogix 5000 Software Chapter 3
Publication IASIMP-QS010B-EN-P - October 2009 61
Chapter 3 Create a Project Using RSLogix 5000 Software
4. Expand the network tree.
5. Select your controller and click Set Project
Path.
6. Click Download.
1. Save your changes.
3. Click the RSWho
button.
EtherNet/IP
Serial
2. Move the keyswitch on your controller to Program.

Set the Communication Path and Download to the Controller

All 1769-L23 controllers
62 Publication IASIMP-QS010B-EN-P - October 2009
8. Move the keyswitch on your controller to Run.
9. Select the PB Examine On instruction and press Ctrl+T.
This toggles the state from 0 to 1 (off to on).
10. Verify that the LED indicator on the digital output of the controller turns on.
11. Press Ctrl+T to toggle the state back to 0 (off).
12. Go Offline.
Off
On
The project Path updates.
EtherNet/IP
7. Click Download.
Serial
Create a Project Using RSLogix 5000 Software Chapter 3
Publication IASIMP-QS010B-EN-P - October 2009 63
Chapter 3 Create a Project Using RSLogix 5000 Software

Additional Resources

Resource Description
Chapter 5 Packaged Controller, on page 233
Logix5000 Controllers Common Procedures Programming Manual, publication 1756-PM001
of the user manual, Program the
Provides detail information about programming the packaged controllers, including available user memory, available programming languages, use of programs and equipment phases, and monitoring controller status.
Provides details about creating and editing a program, communicating with modules, and configuring modules.
These manuals are available for viewing or electronic download at http://literature.rockwellautomation.com.
64 Publication IASIMP-QS010B-EN-P - October 2009
Chapter
4

Add POINT I/O

In this chapter, you install the 1734 POINT I/O network adapter and the 1734 POINT I/O modules. You then add POINT I/O modules to your project using RSLogix 5000 programming software. You also add ladder logic and download the project to the controller so you can test communication with an I/O module. This project builds upon the program created in Chapter 3

Before You Begin

.
Create a project in RSLogix 5000 programming software, see Chapter 3.
Select the appropriate mounting base for I/O modules:
if you use a 1734-IT2I module, then use the 1734-TBCJC.for all other I/O modules, use the 1734-TB or 1734-TBS.

What You Need

POINT I/O adapter: 1734-AENT for Ethernet./IP network.
POINT I/O mounting bases: 1734-TB or 1734-TBS, and 1734-TBCJC.
A digital-output POINT I/O module. The examples use a 1734-OB4E.
Power supply: 1794-PS3 or 1794-PS13.
This chapter also uses the 1734-IB4 module as an example, however, use of the module
is not required.
65Publication IASIMP-QS010B-EN-P - October 2009 65
Chapter 4 Add POINT I/O
Add Ladder Logic
page 76
Download the
Project
page 78
Test the POINT I/O
Light
page 80
Add POINT I/O
Modules to the
Project
page 73
Mount and Connect
the Network
Adapter
Mount the POINT
I/O Modules
Mount and Wire the
POINT I/O Power
Supply
Assign an IP
Address to the
POINT I/O Adapter
page 67
page 69
page 68
page 71
Set the POINT I/O
Chassis Size
page 79

Follow These Steps

If you are using POINT I/O modules, complete these steps.
66 Publication IASIMP-QS010B-EN-P - October 2009

Mount and Connect the Network Adapter

1. Locate the Ethernet address (MAC), found next to the label. Record the Ethernet address (MAC) for the POINT I/O adapter on the
Network Worksheet
.
This address is used to set the IP address later in the quick start.
2. Set the address to a value greater than or equal to 256.
This example uses 999.
3. Remove the safety end cap.
4. Press the adapter onto the DIN rail.
5. Insert an Ethernet cable.
00:00:BC:21:8A:B6
Ethernet Address
Example Address
(Found on the right side of the module.)
Ethernet Port
EtherNet/IP network
Add POINT I/O Chapter 4
Publication IASIMP-QS010B-EN-P - October 2009 67
Chapter 4 Add POINT I/O
1. Using a small, flathead screwdriver, rotate the keyswitch to match the figure on the I/O module.
2. Press the module into the wiring base.
3. Snap the handle up.
4. Complete steps 1–3 with all POINT I/O
modules.
5. Slide the first module and wiring base assembly along the adapter and press it onto the DIN rail.
6. Repeat with all of the I/O assemblies.
Handle
Tongue-and-groove Slots
IMPORTANT
The 1734-IT2I module must be mounted in the 1734-TBCJC wiring base. All other modules can be mounted in either of the 1734-TB or 1734-TBS wiring bases.
Figure on Module
Wiring Base
Module

Mount the POINT I/O Modules

All controllers, POINT I/O modules, and wiring bases
68 Publication IASIMP-QS010B-EN-P - October 2009

Mount and Wire the POINT I/O Power Supply

1. Hook the upper-lip of the DIN rail latch onto the DIN rail.
2. Press the module onto the DIN rail.
3. Connect the 120/230V AC power,
120/230V AC common and AC Ground wires.
Ground
Common Power
WARNING
Verify that all incoming power is turned off before wiring power.
Upper-lip of DIN-rail latch.
TIP
You can choose to power your POINT I/O with the listed POINT I/O power supplies, or, use the DC power supply powering your packaged controller. Any 24V DC power supply can be used with the POINT I/O.
Verify that any power supply you use is disconnected before wiring power.
1794-PS3 or 1794-PS13 power supplies
Add POINT I/O Chapter 4
Publication IASIMP-QS010B-EN-P - October 2009 69
Chapter 4 Add POINT I/O
Common Power
1. Connect the 12/24V DC common and 12/24V DC power wires from the power supply to the adapter.
2. Refer to the individual POINT I/O installation instructions for wiring the I/O modules.
3. Turn on incoming power.

Wire the Adapter and I/O Modules to the Power Supply

POINT I/O adapter, I/O modules, and power supply
70 Publication IASIMP-QS010B-EN-P - October 2009
Add POINT I/O Chapter 4
TIP
Devices on the EtherNet/IP network broadcast requests for IP addresses until the IP addresses have been assigned.
The procedure in this chapter uses the BOOTP server packaged with RSLogix 5000 software to assign IP addresses, however, any industry-standard BootP server can be used.
1. After you have installed and connected your adapter, launch the BOOTP/DHCP
Server utility.
2. From the Tools menu, choose Network Settings.
3. Enter the Subnet Mask from the
Network Worksheet
.
4. Click OK.

Assign an IP Address to the POINT I/O Adapter

EtherNet/IP network
In this chapter, you use the BOOTP/DHCP server to assign an IP address to the POINT I/O adapter. You use the BootP server that was installed with RSLogix 5000 programming software.
Publication IASIMP-QS010B-EN-P - October 2009 71
Chapter 4 Add POINT I/O
The Request History displays all the devices, including the packaged controller, on your network that need an IP address. The Ethernet address (MAC ID) of the adapter corresponds with the address you recorded on
Network Worksheet.
5. Double-click the request from your adapter.
6. Enter the IP address and record it on the
Network Worksheet
inside
the back cover.
If you are not using an isolated network, obtain these numbers from your network administrator.
7. Click OK.
8. To disable BootP/DHCP, select the adapter from the Relation List and click Disable BOOTP/DHCP.
[Disable BOOTP/DHCP] Command successful appears in the Status bar.
9. Close the BOOTP/DHCP Server utility.
If you are prompted to save changes, click No.
IMPORTANT
For a device to retain its IP address through a power cycle, BootP/DHCP must be disabled. Complete step 8 to disable BootP/DHCP for the adapter.
IP Addresses Assigned Successfully
72 Publication IASIMP-QS010B-EN-P - October 2009

Add POINT I/O Modules to the Project

3. Select the 1734-AENT POINT I/O network adap and click OK.
1. Verify that your project is Offline.
2. Right-click the network port and choose New Module.
4. Specify the major revision and click OK.
Module Properties dialog box opens.
Add POINT I/O Chapter 4
Publication IASIMP-QS010B-EN-P - October 2009 73
Chapter 4 Add POINT I/O
5. Type a name for the adapter.
6. Type the IP address.
Use the
Network Worksheet
located inside the back cover as a reference.
7. Select the Chassis Size (exact number of
POINT I/O modules
+ 1 for the adapter).
8. Verify that Open Module Properties is
unchecked and click OK.
The adapter is added to the I/O configuration.
9. Right-click the 1734 POINT network adapter module and choose New Module.
74 Publication IASIMP-QS010B-EN-P - October 2009
11. Enter a name.
12. Click OK.
10. Select the left-most
POINT I/O module in your chassis and click OK.
The module is added to the I/O Configuration.
13. Repeat steps 9…12 until all of your POINT I/O modules are added in order from left to right.
After you have completed adding your POINT I/O modules, go to Add Ladder Logic on page 76
.
Completed Configuration of POINT I/O Modules
Add POINT I/O Chapter 4
Publication IASIMP-QS010B-EN-P - October 2009 75
Chapter 4 Add POINT I/O
1. In the Main Routine, drag and drop a Branch onto the rung.
2. Expand the branch to the right side of Output _Light.
3. Drag and drop another Output Energize element
onto the Branch and name it xxxx_Light (where xxxx identifies your output module).

Add Ladder Logic

76 Publication IASIMP-QS010B-EN-P - October 2009
5. From the Type pull-down, choose Alias.
6. From the Alias For pull-down
menu, browse to find your 1734 output module.
7. Click the output point you want to use.
8. Click OK.
9. Click Save.
4. Right-click the Light and choose New ‘xxxx_Light’.
Add POINT I/O Chapter 4
Publication IASIMP-QS010B-EN-P - October 2009 77
Chapter 4 Add POINT I/O
3. Click Download.
If you have no loads wired to your output modules, the red status LEDs indicators may start blinking.
2. Click the Controller Status icon and choose Download.
If you are using an EtherNet/IP network, after you download to the controller, the 1734 modules may show faults. Setting the chassis size as shown in the next section should resolve these faults.
1. Move the keyswitch on your controller to Program.

Download the Project

78 Publication IASIMP-QS010B-EN-P - October 2009

Set the POINT I/O Chassis Size

1. Right-click the 1734-AENT and choose Properties.
If the both the chassis sizes match, skip to step 1 on page 80
.
If the numbers do not match, continue with step 3.
3. On the Connection tab, check the Inhibit Module checkbox and click Apply.
4. Click Yes.
2. Click the Chassis
Size tab.
Set Chassis Size in Module.
6. Click OK at the warning.
The Module chassis size updates.
7. On the Connection Tab, uncheck the Inhibit Module checkbox and click OK.
8. Click Yes.
You have set the POINT I/O chassis size.
9. Click Save.
5. On the Chassis size tab, click
Add POINT I/O Chapter 4
Publication IASIMP-QS010B-EN-P - October 2009 79
Chapter 4 Add POINT I/O
1. Move the keyswitch on your controller to RUN.
2. Select the PB and press Ctrl+T.
This toggles the state from 0 to 1 (off to on).
3. Verify that the lights on both the embedded and POINT digital output modules turn on.
4. Press Ctrl+T to toggle the state back to 0 (off).
5. Choose Go Offline.
Off
On

Test the POINT I/O Light

80 Publication IASIMP-QS010B-EN-P - October 2009

Additional Resources

Resource Description
Add POINT I/O Chapter 4
Point I/O Ethernet Adapter Installation Instructions, publication 1734-IN590
1734 Point I/O ControlNet Adapter Installation Instructions, publication 1734-IN582
Point I/O DeviceNet Adapter Installation Instructions, publication 1734-IN026
POINT I/O Wiring Base Assembly Installation Instructions, publication 1734-IN511
Cold Junction Compensated Terminal Block Installation Instructions, publication
1734-IN583
Point I/O Protected Output Module Installation Instructions, publication 1734-IN056
FLEX I/O DC Power Supply Modules Installation Instructions, publication 1794-IN069
ControlLogix Controllers Common Procedures Programming Manual, publication 1756-PM001
Provides details regarding installation of the adapter and technical specifications.
Provides details regarding installation of the adapter and technical specifications.
Provides details regarding installation of the adapter and technical specifications.
Provides details regarding installation of the POINT I/O wiring base.
Provides details regarding installation of the Cold Junction Compensated Terminal Block wiring base.
Provides details about the installation and wiring of POINT I/O Protected Output Modules.
Provides details about the installation and wiring of FLEX I/O power supplies.
Provides details about adding and configuring modules, establishing communication, and writing ladder logic.
Publications are available for viewing or electronic download at http://literature.rockwellautomation.com.
Publication IASIMP-QS010B-EN-P - October 2009 81
Chapter 4 Add POINT I/O
Notes:
82 Publication IASIMP-QS010B-EN-P - October 2009
Chapter
5

Add a PowerFlex 40 Drive

In this chapter, you mount and wire power to a PowerFlex 40 drive, configure your communication adapter, and make network connections. You then configure a PowerFlex 40 drive using the drive keypad and add the drive to your project using RSLogix 5000 programming software. This project builds upon the project created in Chapter 3

Before You Begin

Create a project using RSLogix 5000 programming software, see Chapter 3.

What You Need

PowerFlex 40 drive
Communication adapter for use with the PowerFlex 40 drive (22-COMM-E,
EtherNet/IP adapter)
Communication adapter cover for use with the PowerFlex 40 drive
No additional software required
.
83Publication IASIMP-QS010B-EN-P - October 2009 83
Chapter 5 Add a PowerFlex 40 Drive
Add the Drive to
the Project
page 90
Download the
Project
page 92
Edit PowerFlex 40 Parameter Values
page 93
Test the PowerFlex
40 Tags
page 95
Assign an IP Address
to the PowerFlex 40
Drive
page 88
Mount the
PowerFlex 40 Drive
Wire Power
Connect the
Communication
Adapter
page 85
page 85
page 86

Follow These Steps

If you have a PowerFlex 40 drive, complete these steps for your network.
84 Publication IASIMP-QS010B-EN-P - October 2009
Add a PowerFlex 40 Drive Chapter 5
1. Remove the cover.
V/T2T/L3S/L2R/L1 U/T1 W/T3
BR+ BR-DC- DC+
2. Remove the terminal block cover to access the power connections.
3. Insert the 120/240V AC, V AC COM and chassis ground wires and tighten the terminal screws.
Connect To
120/240V AC
R/L1
V AC COM
S/L2
Chassis ground
WARNING
Verify that all incoming power is turned off before wiring power.

Mount the PowerFlex 40 Drive

For this quick start, the PowerFlex 40 drive is simply placed on a desktop.
For complete mounting instructions, see the PowerFlex 40 Drive User Manual, publication
22B-UM001
.

Wire Power

Publication IASIMP-QS010B-EN-P - October 2009 85
Chapter 5 Add a PowerFlex 40 Drive
1. Record the Ethernet address (MAC ID) of the Ethernet adapter on the Network Worksheet
.
The Ethernet address is found on the label on the back of the Ethernet adapter.
1. Attach the extending screws.
0.8…1 Nm (7…9 lb-in)
Allen-Bradley
22-COMM-E
SERIES A FRN: V1.003 SN: 40018FB6 DEVICE: 5vDC 350mA HW ADDRESS: 00:00:BC:08:85:B6
Ethernet Adapter Label
2. Snap the adapter into the cover and connect the cable from the adapter to the PowerFlex 40 drive.

Connect the Communication Adapter

86 Publication IASIMP-QS010B-EN-P - October 2009
Add a PowerFlex 40 Drive Chapter 5
0.5-0.6 N-m (4-5 lb.-in.)
3. Place the adapter cover on the PowerFlex drive.
4. Tighten the screws.
5. Connect the network cable to the adapter.
6. Apply power to the PowerFlex 40 drive.
0.5…0.6 Nm (4…5 lb-in)
Publication IASIMP-QS010B-EN-P - October 2009 87
Chapter 5 Add a PowerFlex 40 Drive
TIP
Devices on the EtherNet/IP network broadcast requests for IP addresses until the IP addresses have been assigned.
The procedure in this chapter uses the BOOTP server packaged with RSLogix 5000 programming software to assign IP addresses, however, any industry-standard BootP server can be used.
1. After you have installed and connected your adapter, launch the BOOTP/DHCP Server utility.
2. From the Tools menu, choose Network
Settings.
3. Enter the Subnet Mask from the
Network Worksheet
.
4. Click OK.

Assign an IP Address to the PowerFlex 40 Drive

EtherNet/IP network
In this chapter, you use the BOOTP/DHCP server to assign an IP address to the PowerFlex 40 drive. You use the BootP server that was installed with RSLogix 5000 programming software.
88 Publication IASIMP-QS010B-EN-P - October 2009
The Request History displays all the devices, including the drive, on your network that need an IP address. The Ethernet address (MAC ID) of the drive corresponds with the address you recorded on
Network Worksheet.
5. Double-click the request from your adapter.
6. Enter the IP address and record it on the
Network Worksheet
inside the back cover.
If you are not using an isolated network, obtain these numbers from your network administrator.
7. Click OK.
8. To disable BootP/DHCP, select the drive from the Relation List and click Disable BOOTP/DHCP.
[Disable BOOTP/DHCP] Command successful appears in the Status bar.
9. Close the BOOTP/DHCP Server utility.
If you are prompted to save changes, click No.
IMPORTANT
For a device to retain its IP address through a power cycle, BootP/DHCP must be disabled. Complete step 8 to disable BootP/DHCP for the drive.
IP Addresses Assigned Successfully
Add a PowerFlex 40 Drive Chapter 5
Publication IASIMP-QS010B-EN-P - October 2009 89
Chapter 5 Add a PowerFlex 40 Drive
1. Verify that you are not online with the packaged controller.
2. Right-click your network port and choose New Module.
3. Expand Drives.
4. Select the PowerFlex 40-E.
5. Click OK.
6. In the Name box, type
a name for the drive.
7. Enter the IP Address for your drive.
Use the
Network Worksheet
as a reference.
8. Click Change.

Add the Drive to the Project

90 Publication IASIMP-QS010B-EN-P - October 2009
9. From the Electronic Keying pull-down menu, select
Disable Keying.
10. Click OK.
11. Click OK again.
The PowerFlex 40 drive is added to the controller organizer.
Add a PowerFlex 40 Drive Chapter 5
Publication IASIMP-QS010B-EN-P - October 2009 91
Chapter 5 Add a PowerFlex 40 Drive
TIP
2. Click the Controller Status icon and choose
Download.
3. Click Download.
The project downloads to the controller.
1. If you have not already done so, move the keyswitch on your controller to PROG.

Download the Project

If you receive a fault message on your PowerFlex 40 drive, press on the keypad to clear the fault.
92 Publication IASIMP-QS010B-EN-P - October 2009

Edit PowerFlex 40 Parameter Values

TIP
Step Displayed
1. Press . The parameter number is displayed and blinks.
2. Press to select the group letter.
The group letter blinks.
3. Press or to scroll through the group letters.
4. Press to select the desired group letter.
The parameter number blinks.
5. Press or to scroll through the parameter numbers.
6. Press to select the desired parameter number.
The parameter value is displayed.
7. Press or to scroll through the parameter values.
The values blink as you scroll through them.
8. Press to select the desired parameter value.
The parameter stops blinking.
9. Press to return to the parameter number.
10.Follow this procedure to change other parameter values, or
press repeatedly to return to the value display.
VOLTS AMPS HERTZ
FAULTPROGRAM
VOLTS AMPS HERTZ
FAULTPROGRAM
VOLTS AMPS HERTZ
FAULTPROGRAM
VOLTS AMPS HERTZ
FAULTPROGRAM
VOLTS AMPS HERTZ
FAULTPROGRAM
Use the table below as a reference when editing parameter values as instructed on
Add a PowerFlex 40 Drive Chapter 5
page 94
.
When power is first applied to the PowerFlex 40 drive, the display defaults to the current value.
Reference for Editing Parameters
VOLTS AMPS HERTZ
FAULTPROGRAM
VOLTS AMPS HERTZ
FAULTPROGRAM
VOLTS AMPS HERTZ
FAULTPROGRAM
Publication IASIMP-QS010B-EN-P - October 2009 93
Chapter 5 Add a PowerFlex 40 Drive
Use the reference on page 93 to make the following parameter value edits on your PowerFlex 40 drive.
1. If your PowerFlex 40 drive has been previously used, reset it to factory defaults.
a. Change the value of parameter P041 from 0 to 1.
The drive is reset and fault F048 is displayed and blinks.
b. Press to clear the fault.
c. Press to return to editing parameters.
2. Change the value of parameters P036 and P038 from 0 to 5.
Changing these parameters switches control the Start Source and the Speed Reference from the keypad to the communication port. This enables you to control these functions by using RSLogix 5000 tags.
3. Press to accept parameter edits.
4. Press to return to the speed display.
94 Publication IASIMP-QS010B-EN-P - October 2009

Test the PowerFlex 40 Tags

2. Double-click Controller Tags.
3. Expand the PowerFlex 40
output tag.
4. At the O.FreqCommand Tag, enter 555.
The value 555 equals 55.5 Hz.
1. Move the controller keyswitch to RUN.
TIP
To change a tag in RSLogix 5000 software:
1. Select the tag value.
2. Enter or select the desired value.
3. Press <Enter>.
Add a PowerFlex 40 Drive Chapter 5
Publication IASIMP-QS010B-EN-P - October 2009 95
Chapter 5 Add a PowerFlex 40 Drive
4. At the O.Start tag, enter 1.
The drive begins to run and the display registers the drive’s speed until it reaches 55.5 Hz.
5. After the drive has reached 55.5 Hz, enter 0 at the O.Start tag.
6. At the O.Stop tag, enter 1.
The drive begins to slow until reaching 0.0 Hz.
7. When the drive reaches 0.0 Hz, enter 0 at the O.Stop tag.
8. Go Offline.
By starting and stopping the drive, you verified that:
the controller is correctly communicating with the drive.
the drive can receive simple commands.

Additional Resources

Resource Topic
Logix5000 Controllers Common Procedures Programming Manual, publication 1756-PM001
PowerFlex 40 Adjustable Frequency AC Drive User Manual, publication 22B-UM001
Provides details about adding and configuring modules, establishing communication, and writing ladder logic.
Provides information about installing, programming, editing parameters, and troubleshooting the PowerFlex 70 drive.
Publications are available for viewing or electronic download at http://literature.rockwellautomation.com.
96 Publication IASIMP-QS010B-EN-P - October 2009
Chapter
6

Add a PanelView Plus 600 Terminal

In this chapter, you mount and wire power to a PanelView Plus terminal, configure network communication, and make network connections. You also use RSView software to create indicators to represent the push button and output you created in Chapter 3 application to the PanelView Plus terminal so you can test communication with the controller.

Before You Begin

Create a project in RSLogix 5000 programming software, see Chapter 3.
. You transfer the
Install and configure your network, see Chapter 1
and 2.

What You Need

FactoryTalk View Studio Machine Edition software.
PanelView Plus terminal - this quick start uses a PanelView Plus 600 terminal.
One power supply, if you are using a PanelView Plus powered by DC power. We
recommend either a 1794-PS3 or a 2711P-RSACDIN, but any DC power supply can be used.
Ethernet cable and switch.
For a serial connection, 2706-NC13 cable.
97Publication IASIMP-QS010B-EN-P - October 2009 97
Chapter 6 Add a PanelView Plus 600 Terminal
Create a New
Application
Create an RSLinx
Enterprise
Configuration in
FactoryTalk View ME
Create Device
Shortcuts to the
Controller
Create the
OB16_Light
Indicator
Create a Push
Button
Test the Indicator
and Push Button
page 102
page 103
page 105
page 110
page 113
page 115
Add a Goto
Configuration Mode
Button
page 117
Assign Keys
page 118
Assign an Initial
Screen
page 120
Transfer to the
PanelView Plus
page 121
Test the Application
on the PanelView
Plus Terminal
page 123
Mount the
PanelView Plus
Terminal
page 99
Wire the PanelView
Plus Terminal for
Power
page 99
Make Network
Connections
page 100
Assign an IP
Address to the
page 101

Follow These Steps

If you have a PanelView Plus terminal, complete these steps.
98 Publication IASIMP-QS010B-EN-P - October 2009
Add a PanelView Plus 600 Terminal Chapter 6
For additional information about wiring power for the PanelView Plus 600 terminal, see the PanelView Plus 400 and 600 Terminals Installation Instructions, publication 2711P-IN002.
WARNING
Verify that all incoming power is turned off before wiring power.
1. Remove the wiring terminal block using a flat-blade screwdriver to gently pry the terminal block from the slot.
2. Connect power wires as shown in the diagram.
3. Insert the wiring terminal block and press it into place.
AC Power Wiring
L1
L2/N
Protective Earth Ground

Mount the PanelView Plus Terminal

2711P-K10C4D1 terminal and all packaged controllers
For the purpose of this quick start, the PanelView Plus terminal can be propped on a desktop.
For further mounting instructions, see the PanelView Plus Terminals User Manual, publication 2711P-UM001
.

Wire the PanelView Plus Terminal for Power

Publication IASIMP-QS010B-EN-P - October 2009 99
Chapter 6 Add a PanelView Plus 600 Terminal
Ethernet cable connection.
Serial cable connection (from 1769-L23-QBFC1B serial port).

Make Network Connections

Required for all controllers
100 Publication IASIMP-QS010B-EN-P - October 2009
Loading...