Rockwell Automation 871P User Manual

BULLETIN
871P
INDUCTIVE PROXIMITY SENSOR
133–551(C)
Load Current ≤ 300mA. . . . . . . . . . . . . . . .
Leakage Current 1.7mA at 132 VAC. . . . . . . . . . . . .
Operating Voltage 24–250 VAC. . . . . . . . . . . .
Voltage Drop 11 V. . . . . . . . . . . . . . . .
Hysteresis 20% Typical. . . . . . . . . . . . . . . . . . .
Transient Noise Protection INCORPORATED. . . .
Enclosure NEMA 1, 2, 3, 4, 12, 13. . . . . . . . . . . . . . . . . . .
Barrel Plastic. . . . . . . . . . . . . . . . . . . . . . .
Cable Version 2 Meter (6.5 ft.), 2 Conductor. . . . . . . . . . . . . . . .
LED Red: Output Energized. . . . . . . . . . . . . . . . . . . . . . . .
IP67 IEC 529
(–13
o
C to + 55o C. . . . . .
o
F to + 131o F)
WIRING DIAGRAMSPECIFICATIONS
Load can be switched to brown wire
BLACK
BLUE
LOAD
INSTALLATION INSTRUCTIONS
133–551(C)
CAUTION; Solid state devices can be susceptible to radio frequency (RF) interference, depending on the frequency of the transmitting source. If RF transmitting equipment is to be used in the vicinity of the solid state devices, thorough testing should be performed to assure that the transmitter operation is restricted to a safe operating distance from the control equipment and wiring.
WARNING: Do not let METAL objects that are not to be sensed come within three times the sensing distance of this device. Unintended process activation may result in a hazardous condition.
IMPORTANT: Save these instructions for future use. For additional information and proper operating guidance, refer to the Allen-Bradley Proximity Catalog 871-1.2 or the product data sheet.
EFFECTS OF NEARBY METAL SURFACES
Metals immediately opposite the sensing face should be no closer than three times the rated operating distance of the sensor.
3
d d
25mm
Sn = nominal sensing distance
3 Sn
METAL FREE
ZONE
SPACING BETWEEN SENSORS
When installing side by side, the minimum spacing distance should be maintained. When mounting face to face, use two times the diameter.
d
2 x d
4 x d
SENSING DISTANCE
The standard target is a square of mild steel (ST37), 1mm thick. The side of the square is equal to the diameter of the sensor. Targets smaller than standard size may shorten the sensing distance. Targets larger than standard may lengthen the sensing distance.
CORRECTION FACTORS
To determine the sensing distance for materials other than the standard mild steel, multiply the sensing distance by the factor given below:
Steel 1.0. . . . . . . . . . . . . . . . .
Stainless Steel 0.7 to 0.8. . . . . . . . .
Brass 0.4 to 0.5. . . . . . . . . . . . . . . . .
Aluminum 0.3 to 0.4. . . . . . . . . . . . .
Copper 0.3 to 0.4. . . . . . . . . . . . . . .
SERIES CONNECTED SWITCHES
When connected in series, the operating load voltage must be less than or equal to the minimum supply voltage, minus the voltage drops across the proximity switches connected in series. The load will energize when the connected outputs of all proximity switches are energized.
PARALLEL CONNECTED SWITCHES
To determine the maximum number of switches for an application, the sum of the maximum OFF-state currents of the switches connected in parallel must be less than the maximum OFF-state current of the load device. The load will be energized when the output of any proximity switch energizes. NOTE: Parallel operation of switches does not provide higher load current capability.
Loading...