For Motor, Transformer and Generator Dierential Protection
Bulletin 865, Series A
User Manual
Solid-state equipment has operational characteristics differing from those of electro-
Important User
Information
mechanical equipment. Safety Guidelines for the Application, Installation and
Maintenance of Solid-State Controls (Publication SGI-1.1 available from your local
Rockwell Automation sales office or online at http://literature.rockwellautomation.com)
describes some important differences between solid-state equipment and hard-wired
electromechanical devices. Because of this difference, and also because of the wide variety of
uses for solid-state equipment, all persons responsible for applying this equipment must
satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for any indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes.
Because of the many variables and requirements associated with any particular installation,
Rockwell Automation, Inc. cannot assume responsibility or liability for actual use, based on
the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written
permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety
considerations.
W A R N I N GW A R N I N G
Identifies information about practices or circumstances that can
cause an explosion in a hazardous environment, which may lead
to personal injury or death, property damage, or economic loss.
I M P O R T A N TI M P O R T A N T
Identifies information that is critical for successful application
and understanding of the product.
A T T E N T IO NA T T E N T I O N
Identifies information about practices or circumstances that can
lead to personal injury or death, property damage, or economic
loss. Attentions help you identify a hazard, avoid a hazard, and
recognize the consequences.
S H O C KH A ZA RDS H O C K H A Z A R D
Labels may be on or inside the equipment (for example, drive or
motor) to alert people that dangerous voltage may be present.
B U R N H A ZA R DB U R N H A Z A R D
Labels may be on or inside the equipment (for example, drive or
motor) to alert people that surfaces may reach dangerous
temperatures.
Introduction The Allen-Bradley 865 differential protection system includes all the
essential protection functions needed to protect transformers for
distribution networks of utilities, industry, power plants and offshore
applications as well as motor and generator differential protection.
Further, the device includes several programmable functions, such as
thermal and circuit breaker protection and communication protocols
for various protection and communication situations. An optional
arc flash protection feature is also available.
The Allen-Bradley 865 can be used for selective differential
overcurrent, short-circuit protection of generators, transformers
and motors in solidly or impedance earthed power systems. The
relay can also be used for single, two or three-phase overcurrent
and/or sensitive earth fault protection.
The modern technology in association with an extensive self-
supervision system and a reliable construction ensures extremely
high system availability for the Allen-Bradley 865 protection
relay.
Main Relay Features The main features of Allen-Bradley 865 are:
• Fully digital signal handling with a powerful 16-bit
microprocessor, and high measuring accuracy on all the setting
ranges due to an accurate 16-bit A/D conversion technique
• Wide setting ranges for the protection functions, e.g. the earth
fault protection can reach a sensitivity of 0.5%
• The device can be matched to the requirements of the application
by disabling the functions that are not needed
• Flexible control and blocking possibilities due to digital signal
control inputs (DI) and outputs (DO)
• Easy adaptability of the relay to various substations and alarm
systems due to flexible signal-grouping matrix in the relay
• Freely configurable display with six measurement values
865-UM001A-EN-P – July 2009
1-2 Overview
Main Features (cont.)
• Freely configurable interlocking schemes with basic logic
functions
• Recording of events and fault values into an event register from
which the data can be read via a keypad and a local HMI or by
means of a PC based SetPointPS user interface
• Latest events and indications are in non-volatile memory.
• Easy configuration, parameter setting and reading of information
via local HMI, or with the SetPointPS programming software
• Easy connection to power plant automation system due to a
versatile serial connection and several available communication
protocols
• Built-in, self-regulating ac/dc converter for auxiliary power
supply from any source within the range from 40 to 865 V dc or
ac. The alternative power supply is for 18 to 36 V dc
• Built-in disturbance recorder for evaluating all the analogue and
digital signals
• Eight (8) programmable stages for alarming or protection
purposes
The Allen-Bradley 865 differential protection relay is ideal for
transformer, motor, generator and short cable (100) differential
protection. The relay features the following protection functions.
Further the relay includes a disturbance recorder. Arc protection
is optionally available.
The relay communicates with other systems using common
protocols, such as the Modbus RTU, ModbusTCP, Profibus DP,
Ethernet, DeviceNet, IEC 60870-5-103, SPA bus and DNP 3.0,
IEC 61850 and IEC 60870-5-101.
IEC symbol Function name
>,
I
0
>>,
I
0
I
>>>,
0
>>>>
I
0
ArcI>, ArcI’>
>, ArcI02>
ArcI
01
Earth fault protection
Optional arc fault protection
865-UM001A-EN-P – July 2009
Overview 1-3
User Interface
The relay can be controlled in three ways:
• Locally with the push-buttons on the relay front panel
• Locally using a PC connected to the serial port on the front panel
or on the rear panel of the relay (both cannot be used
simultaneously)
• Via remote control over the remote control port on the relay rear
panel.
Operating Safety
A T T E N T IONA T T E N T I O N
The terminals on the rear panel of the relay may
carry dangerous voltages, even if the auxiliary
voltage is switched off. A live current
transformer secondary circuit must not be
opened. Disconnecting a live circuit may cause
dangerous voltages! Any operational measures
must be carried out according to national and
local handling directives and instructions.
Carefully read through all operation instructions before any
operational measures are carried out.
865-UM001A-EN-P – July 2009
1-4 Overview
865-UM001A-EN-P – July 2009
Chapter 2
Local Panel User Interface
Relay Front Panel The figure below shows, as an example, the front panel of the
Allen-Bradley 865 relay and the location of the user interface
elements used for local control.
Figure 2.1 – Front Panel of Allen-Bradley 865 Relay
1. LCD dot matrix display
2. Keypad
3. LED indicators
4. RS 232 serial communication port for PC
Display
The relay is provided with a backlit 128x64 LCD dot matrix
display. The display enables showing 21 characters in one row
and eight rows at the same time. The display has two different
purposes: one is to show the single line diagram of the relay with
the object status, measurement values, identification etc. (Figure
2.2). The other purpose is to show the configuration and
parameter setting values of the relay (Figure 2.3).
865-UM001A-EN-P – July 2009
2-2 Local Panel User Interface
4
5
K00 0 6
2
Q4
Q1
Q0
Q3
Q9
3
AR : 1
50.02 Hz
L
6
1
7
Figure 2.2 – Sections of the LCD Matrix Display
1. Freely configurable single-line diagram
2. Five controllable objects
3. Status for six independent objects
4. Bay identification
5. Local/Remote selection
6. Auto-reclose on/off selection (if applicable)
7. Freely selectable measurement values (max. six values)
Figure 2.3 – Sections of the LCD Matrix Display
1. Main menu column
2. The heading of the active menu
3. The cursor of the main menu
4. Possible navigating directions (push buttons)
5. Measured/setting parameter
6. Measured/set value
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-3
Backlight Control
Display backlight can be switched on with a digital input, virtual
input or virtual output. LOCALPANEL CONF/Display backlight ctrl setting is used for selecting trigger input for backlight control.
When the selected input activates (rising edge), display backlight is
set on for 60 minutes.
Menu Navigation and Pointers
1. Use the arrow keys UP and DOWN to move up and down in the
main menu, that is, on the left-hand side of the display. The
active main menu option is indicated with a cursor. The options
in the main menu items are abbreviations, e.g. Evnt = events.
2. After any selection, the arrow symbols in the upper left corner of
the display show the possible navigating directions (applicable
navigation keys) in the menu.
3. The name of the active submenu and a possible ANSI code of
the selected function are shown in the upper part of the display,
e.g. CURRENTS.
4. Further, each display holds the measured values and units of one
or more quantities or parameters, e.g. ILmax 300A.
Keypad
You can navigate in the menu and set the required parameter
values using the keypad and the guidance given in the display.
Furthermore, the keypad is used to control objects and switches
on the single line diagram display. The keypad is composed of
four arrow keys, one cancel key, one enter key and one info key.
4. Keys for selecting submenus [selecting a digit in a numerical
value] (LEFT/RIGHT)
5. Additional information key (INFO)
NOTE: The term, which is used for the buttons in this manual,
is inside the rounded brackets.
Operation Indicators
The relay is provided with eight LED indicators:
Power
Error
Com
Alarm
Trip
A
B
C
Figure 2.5 – Operation Indicators of the Relay
Table 2.1 – Operation Indicators
LED indicator Meaning Measure/ Remarks
Power LED lit The power has been switched on Normal operation state
Error LED lit Internal fault, operates in parallel with
the self supervision output relay
Com LED lit or flashing The serial bus is in use and
transferring information
Alarm LED lit One or several signals of the output
relay matrix have been assigned to
output LA and the output has been
activated by one of the signals. (For
more information about output matrix,
please see page 2-24).
Trip LED lit One or several signals of the output
relay matrix have been assigned to
output Tr, and the output has been
activated by one of the signals. (For
more information about output relay
configuration, see “Configuring Digital
Outputs DO” on page 2-24).
A- C LED lit Application-related status indicators. Configurable
The relay attempts to reboot
[REBOOT]. If the error LED
remains lit, call for maintenance.
Normal operation state
The LED is switched off when the
signal that caused output Al to
activate, e.g. the START signal, is
reset. The resetting depends on the
type of configuration, connected or
latched.
The LED is switched off when the
signal that caused output Tr to
activate, e.g. the TRIP signal, is
reset. The resetting depends on the
type of configuration, connected or
latched.
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-5
Resetting Latched Indicators and Output Relays
All the indicators and output relays can be given a latching
function in the configuration.
There are several ways to reset latched indicators and relays:
• From the alarm list, move back to the initial display by pushing
the CANCEL key for approx. 3 s. Then reset the latched
indicators and output relays by pushing the ENTER key.
• Acknowledge each event in the alarm list one by one by pushing
the ENTER key equivalent times. Then, in the initial display,
reset the latched indicators and output relays by pushing the
ENTER key.
The latched indicators and relays can also be reset via a remote
communication bus or via a digital input configured for that
purpose.
Adjusting Display Contrast
The readability of the LCD varies with the brightness and the
temperature of the environment. The contrast of the display can
be adjusted via the PC user interface, and SetPointPS software.
Local Panel Operations The front panel can be used to control objects, change the local/
remote status, read the measured values, set parameters, and to
configure relay functions. Some parameters, however, can only be
set by means of a PC connected to one of the local communication
ports. Some parameters are factory-set.
Navigating in Menus
All the menu functions are based on the main menu/submenu structure:
1. Use the arrow keys UP and DOWN to move up and down in the
main menu.
2. To move to a submenu, repeatedly push the RIGHT key until the
required submenu is shown. Correspondingly, push the LEFT
key to return to the main menu.
3. Push the ENTER key to confirm the selected submenu. If there
are more than six items in the selected submenu, a black line
appears to the right side of the display (Figure 2.6). It is then
possible to scroll down in the submenu.
4. Push the CANCEL key to cancel a selection.
865-UM001A-EN-P – July 2009
2-6 Local Panel User Interface
Local Panel Operations
(cont.)
5. Pushing the UP or DOWN key in any position of a sub-menu,
when it is not selected, brings you directly one step up or down
in the main menu.
The active main menu selection is indicated with black background
color. The possible navigating directions in the menu are shown in
the upper-left corner by means of black triangular symbols.
Figure 2-6 – Example of Scroll Indication
Figure 2.7 – Principles of the Menu Structure and Navigation in the Menus
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-7
6. Push the INFO key to obtain additional information about any
menu item.
7. Push the CANCEL key to revert to the normal display.
Main Menu
The general menu structure is shown in Figure 2.7. The menu is
dependent on the user's configuration and the options according to
the order code. For example only the enabled protection stages will
appear in the menu.
Table 2.2 – List of the Local Main Menu
Main menu
1 Interactive mimic display 1
5 Double size measurements defined by the user 1
1 Title screen with device name, time and firmware version.
P 14 Power measurements
E 4 Energy measurements
I 13 Current measurements
U 15 Voltage measurements
Dema 15 Demand values
Umax 5 Time stamped min & max of voltages
Imax 9 Time stamped min & max of currents
Pmax 5 Time stamped min & max of power and frequency
Mont 21 Maximum values of the last 31 days and the last twelve months
Evnt 2 Events
DR 2 Disturbance recorder 2
Runh 2 Running hour counter. Active time of a selected digital input and
TIMR 6 Day and week timers
DI 5 Digital inputs including virtual inputs
DO 4 Digital outputs (relays) and output matrix
ExtAI 3 External analogue inputs 3
ExDI 3 External digital inputs 3
ExDO 3 External digital outputs 3
Prot 27 Protection counters, combined overcurrent status, protection
ArcIo> 3 Optional arc protection stage for earth faults. Current input = I01 50NARC 4
ArcIo2> 3 Optional arc protection stage for earth faults. Current input = I02 50NARC 4
OBJ 11 Object definitions 5
Lgic 2 Status and counters of user's logic 1
CONF 10+2 Device setup, scaling etc. 6
Bus 13 Serial port and protocol configuration 7
Diag 6 Device selfdiagnosis
Number of
menus
Description ANSI code Note
50ARC 4
delayed light signal.
NOTES:
1. Configuration is done with SetPointPS.
2. Recording files are read with SetPointPS.
3. The menu is visible only if protocol ”External IO” is selected for one of the serial ports.
Serial ports are configured in menu ”Bus”.
4. The menu is visible only if the stage is enabled.
5. Objects are circuit breakers, disconnectors, etc. Their position or status can be displayed
and controlled in the interactive mimic display.
6. There are two extra menus, which are visible only if the access level ”operator” or
”configurator” has been opened with the corresponding password.
7. Detailed protocol configuration is done with SetPointPS.
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-9
Menu Structure of Protection Functions
The general structure of all protection function menus is similar
although the details do differ from stage to stage. As an example the
details of the second overcurrent stage I>> menus are shown below:
F
IRST MENU OF I>>50/51 STAGE
I>> STATUS50/51
Off
5
2
1
-
ExDO
Prot
I>
I>>
Iv>
Figure 2.8 – First Menu of I>>50/51 Stage
I>j
Status
SCntr
TCntr
SetGrp
SGrpDI
Force
This is the status, start and trip counter and setting group menu. The
content is:
• Status – The stage is not detecting any fault at the moment. The
stage can also be forced to pick-up or trip if the operating level is
"Configurator" and the force flag below is on. Operating levels
are explained in section “Operating Levels”.
• SCntr 5 – The stage has picked-up a fault five times since the
last reset of restart. This value can be cleared if the operating
level is at least "Operator".
• TCntr 1 – The stage has tripped two times since the last reset of
restart. This value can be cleared if the operating level is at least
"Operator".
• SetGrp 1 – The active setting group is one. This value can be
edited if the operating level is at least “Operator”. Setting groups
are explained in section “Setting Groups”.
• SGrpDI – The setting group is not controlled by any digital
input. This value can be edited if the operating level is at least
“Configurator”.
• Force Off – The status forcing and output relay forcing is
disabled. This force flag status can be set to “On” or back to
“Off” if the operating level is at least “Configurator”. If no front
panel button is pressed within five minutes and there is no
SetPointPS communication, the force flag will be set to “Off”
position. The forcing is explained in section “Forced Control
(Force)”.
865-UM001A-EN-P – July 2009
2-10 Local Panel User Interface
Local Panel Operations
(cont.)
S
Figure 2.9 – Second Menu (next to the right) of I>>50/51 Stage
This is the main setting menu. The content is:
• Stage setting group 1 – These are the group 1 setting values.
ECOND MENU OF I>>50/51 STAGE
I>> SET50/51
Stagesettinggroup1
ExDI
ExDO
Prot
I>>
CBWE
OBJ
ILmax
Status
I>>
I>>
t>>
403A
-
1013A
2.50xIgn
0.60s
The other setting group can be seen by pressing push buttons
ENTER and then RIGHT or LEFT. Setting groups are explained
in section “Setting Groups”.
• Ilmax 403A – The maximum of the three measured phase
currents is at the moment 403 A. This is the value the stage is
supervising.
• Status – Status of the stage. This is just a copy of the status
value in the first menu.
• I>> 1013 A – The pick-up limit is 1013 A in primary value.
• I>> 2.50xIn – The pick-up limit is 2.50 times the rated current
of the protected object. This value can be edited if the operating
level is at least "Operator". Operating levels are explained in
section “Operating Levels”.
• t>> 0.60s – The total operation delay is set to 600 ms. This value
can be edited if the operating level is at least "Operator".
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-11
T
HIRD MENU OF I>>50/51 STAGE
I>> LOG50/51
FAULT LOG 1
ExDI
ExDO
Prot
I>>
CBWE
OBJ
Figure 2.10 – Third and Last Menu (next to the right) of I>>50/51 Stage
2006-09-14
12:25:10.288
Type
Flt
Load
EDly
1-2
2.86xIgn
0.99xIgn
81%
SetGrp1
This is the menu for registered values by the I>> stage. Fault logs are
explained under “Fault Logs” on page 2-13.
• FAULT LOG 1 – This is the latest of the eight available logs.
You may move between the logs by pressing push buttons
ENTER and then RIGHT or LEFT.
• 2006-09-14 – Date of the log.
• 12:25:10.288 – Time of the log
• Type 1-2 – The overcurrent fault has been detected in phases L1
and L2 (A & B, red & yellow, R&S, u&v).
• Flt 2.86xIn – The fault current has been 2.86 per unit.
• Load 0.99xIn – The average load current before the fault has
been 0.99 pu.
• EDly 81% – The elapsed operation delay has been 81% of the
setting 0.60 s = 0.49 s. Any registered elapsed delay less than
100 % means that the stage has not tripped, because the fault
duration has been shorter than the delay setting.
• SetGrp 1 – The setting group has been 1. This line can be
reached by pressing ENTER and several times the DOWN
button.
865-UM001A-EN-P – July 2009
2-12 Local Panel User Interface
Local Panel Operations
(cont.)
Setting Groups
Most of the protection functions of the relay have two setting groups.
These groups are useful for example when the network topology is
changed frequently. The active group can be changed by a digital input,
through remote communication or locally by using the local panel.
The active setting group of each protection function can be selected
separately. Figure 2.11 shows an example where the changing of the
I> setting group is handled with digital input one (SGrpDI). If the
digital input is TRUE, the active setting group is group two and
correspondingly, the active group is group one, if the digital input is
FALSE. If no digital input is selected (SGrpDI = -), the active group
can be selected by changing the value of the parameter SetGrp.
Figure 2.11 – Example of Protection Submenu with Setting Group
The changing of the setting parameters can be done easily. When the
desired submenu has been found (with the arrow keys), press the
ENTER key to select the submenu. Now the selected setting group is
indicated in the down-left corner of the display (See Figure 2.12).
Set1 is setting group one and Set2 is setting group two. When the
needed changes, to the selected setting group, have been done, press
the LEFT or the RIGHT key to select another group (the LEFT key
is used when the active setting group is 2 and the RIGHT key is used
when the active setting group is 1).
Figure 2.12 – Example of I> Setting Submenu
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-13
Fault Logs
All the protection functions include fault logs. The fault log of a
function can register up to eight different faults with time stamp
information, fault values etc. Each function has its own logs (See
Figure 2.13).
Figure 2.13 – Example of Fault Log
To see the values of, for example, log two, press the ENTER key to
select the current log (log one). The current log number is then
indicated in the down-left corner of the display (See Figure 2.14,
Log2 = log two). The log two is selected by pressing the RIGHT key
once.
Figure 2.14 – Example of Selected Fault Log
865-UM001A-EN-P – July 2009
2-14 Local Panel User Interface
Operating Levels
Local Panel Operations
(cont.)
The relay has three operating levels: User level, Operator level
and Configurator level. The purpose of the access levels is to
prevent accidental change of relay configurations, parameters or
settings.
USER level
Use: Possible to read e.g. parameter values,
measurements and events
Opening: Level permanently open
Closing: Closing not possible
OPERATOR level
Use: Possible to control objects and to change e.g. the
settings of the protection stages
Opening: Default password is 1
Setting State: Push ENTER
Closing: The level is automatically closed after 10 minutes
idle time. Giving the password 9999 can also close
the level.
CONFIGURATION level
Use: The configurator level is needed during the
commissioning of the relay. E.g. the scaling of the
voltage and current transformers can be set.
Opening: Default password is 0002Setting State: Push ENTER
Closing: The level is automatically closed after 10 minutes
idle time. Giving the password 9999 can also close
the level.
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-15
Opening Access
1. Push the INFO key and the ENTER key on the front panel.
ENTER PASSWORD
0
***
Figure 2.15 – Opening the Access Level
2. Enter the password needed for the desired level: the password
can contain four digits. The digits are supplied one by one by
first moving to the position of the digit using the RIGHT key and
then setting the desired digit value using the UP key.
3. Push the ENTER key.
Password Handling
The passwords can only be changed using SetPointPS software
connected to the local RS-232 port on the relay.
It is possible to restore the password(s) in case the password is lost or
forgotten. In order to restore the password(s), a relay program is
needed. The serial port settings are 38400 bps, 8 data bits, no parity
and one stop bit. The bit rate is configurable via the front panel.
Command Description
get pwd_break Get the break code (Example: 6569403)
get serno Get the serial number of the relay (Example: 12345)
Send both the numbers to Rockwell Automation and ask for a
password break. A device specific break code is sent back to you.
That code will be valid for the next two weeks only for this specific
device.
Command Description
set pwd_break=4435876 Restore the factory default passwords (“4435876” is
just an example. The actual code should be
requested from Rockwell Automation.)
Now the passwords are restored to the default values (See section
“Operating Levels”).
865-UM001A-EN-P – July 2009
2-16 Local Panel User Interface
Operating Measures Control Functions
The default display of the local panel is a single-line diagram
including relay identification, Local/Remote indication, Auto-reclose
on/off selection and selected analogue measurement values.
Please note that the operator password must be active in order to be
able to control the objects. Please refer to ‘Opening Access’ on
page 2-15.
Toggling Local/Remote Control
1. Push the ENTER key. The previously activated object starts to
blink.
2. Select the Local/Remote object (“L” or “R” squared) by using
the arrow keys.
3. Push the ENTER key. The L/R dialog opens. Select “REMOTE”
to enable remote control and disable local control. Select
“LOCAL” to enable local control and disable remote control.
4. Confirm the setting by pushing the ENTER key. The
Local/Remote state will change.
Object Control
1. Push the ENTER key. The previously activated object starts to
blink.
2. Select the object to control by using the arrow keys. Please note
that only controllable objects can be selected.
3. Push the ENTER key. A control dialog opens.
4. Select the “Open” or “Close” command by using the UP and
DOWN arrow keys.
5. Confirm the operation by pushing the ENTER key. The state of
the object changes.
Toggling Virtual Inputs
1. Push the ENTER key. The previously activated object starts to
blink.
2. Select the virtual input object (empty or black square)
3. The dialog opens
4. Select “VIon” to activate the virtual input or select “VIoff” to
deactivate the virtual input
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-17
Measured Data
The measured values can be read from the main menus and their
submenus. Furthermore, any measurement value in the following
table can be displayed on the main view next to the single line
diagram. Up to six measurements can be shown.
Table 2.3 – Measured Values
Value Menu/Submenu Description
f P/POWER Frequency [Hz]
IL1 I/PHASE CURRENTS Phase current IL1 [A]
IL2 I/PHASE CURRENTS Phase current IL2 [A]
IL3 I/PHASE CURRENTS Phase current IL3 [A]
IL1da I/PHASE CURRENTS 15 min average for IL1 [A]
IL2da I/PHASE CURRENTS 15 min average for IL2 [A]
IL3da I/PHASE CURRENTS 15 min average for IL3 [A]
I’L1 I/PHASE CURRENTS Phase current I’L1 [A]
I’L2 I/PHASE CURRENTS Phase current I’L2 [A]
I’L3 I/PHASE CURRENTS Phase current I’L3 [A]
I’L1da I/PHASE CURRENTS 15 min average for I’L1 [A]
I’L2da I/PHASE CURRENTS 15 min average for I’L2 [A]
I’L3da I/PHASE CURRENTS 15 min average for I’L3 [A]
Io I/SYMMETRIC CURRENTS Primary value of zero sequence/ residual current Io [A]
Io2 I/SYMMETRIC CURRENTS Primary value of zero-sequence/residual current Io2 [A]
IoC I/SYMMETRIC CURRENTS Calculated Io [A]
I1 I/SYMMETRIC CURRENTS Positive sequence current [A]
I2 I/SYMMETRIC CURRENTS Negative sequence current [A]
I2/I1 I/SYMMETRIC CURRENTS Negative sequence current related to positive sequence current
(for unbalance protection) [%]
I’1 I/SYMMETRIC CURRENTS Positive sequence current [A]
I’2 I/SYMMETRIC CURRENTS Negative sequence current [A]
I’2/I’1 I/SYMMETRIC CURRENTS Negative sequence current related to positive sequence current
(for unbalance protection) [%]
THDIL I/HARM. DISTORTION Total harmonic distortion of the mean value of phase currents [%]
THDIL1 I/HARM. DISTORTION Total harmonic distortion of phase current IL1 [%]
THDIL2 I/HARM. DISTORTION Total harmonic distortion of phase current IL2 [%]
THDIL3 I/HARM. DISTORTION Total harmonic distortion of phase current IL3 [%]
THDI’L1 I/HARM. DISTORTION Total harmonic distortion of phase current I’L1 [%]
THDI’L2 I/HARM. DISTORTION Total harmonic distortion of phase current I’L2 [%]
THDI’L3 I/HARM. DISTORTION Total harmonic distortion of phase current I’L3 [%]
Diagram I/HARMONICS of IL1 Harmonics of phase current IL1 [%] (See Figure 2.16)
Diagram I/HARMONICS of IL2 Harmonics of phase current IL2 [%] (See Figure 2.16)
Diagram I/HARMONICS of IL3 Harmonics of phase current IL3 [%] (See Figure 2.16)
Diagram I/HARMONICS of I’L1 Harmonics of phase current I’L1 [%] (See Figure 2.16)
Diagram I/HARMONICS of I’L2 Harmonics of phase current I’L2 [%] (See Figure 2.16)
Diagram I/HARMONICS of I’L3 Harmonics of phase current I’L3 [%] (See Figure 2.16)
865-UM001A-EN-P – July 2009
2-18 Local Panel User Interface
Operating measures (cont.)
Figure 2.16 – Example of Harmonics Bar Display
Reading Event Register
The event register can be read from the EVNT submenu:
1. Push the RIGHT key once.
2. The EVENT LIST appears. The display contains a list of all the
events that have been configured to be included in the event
register.
Figure 2.17 – Example of an Event Register
3. Scroll through the event list with the UP and DOWN keys.
4. Exit the event list by pushing the LEFT key.
It is possible to set the order in which the events are sorted. If the
“Order” -parameter is set to “New-Old”, then the first event in
the EVENT LIST is the most recent event.
865-UM001A-EN-P – July 2009
Loading...
+ 156 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.