Rockwell Automation 865 User Manual

865 Differential Protection Relay
For Motor, Transformer and Generator Dierential Protection Bulletin 865, Series A
User Manual
Solid-state equipment has operational characteristics differing from those of electro-

Important User Information

mechanical equipment. Safety Guidelines for the Application, Installation and Maintenance of Solid-State Controls (Publication SGI-1.1 available from your local Rockwell Automation sales office or online at http://literature.rockwellautomation.com) describes some important differences between solid-state equipment and hard-wired electromechanical devices. Because of this difference, and also because of the wide variety of uses for solid-state equipment, all persons responsible for applying this equipment must satisfy themselves that each intended application of this equipment is acceptable.
In no event will Rockwell Automation, Inc. be responsible or liable for any indirect or
consequential damages resulting from the use or application of this equipment.
The examples and diagrams in this manual are included solely for illustrative purposes.
Because of the many variables and requirements associated with any particular installation, Rockwell Automation, Inc. cannot assume responsibility or liability for actual use, based on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, Inc. with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of the contents of this manual, in whole or in part, without written
permission of Rockwell Automation, Inc. is prohibited.
Throughout this manual, when necessary we use notes to make you aware of safety
considerations.
W A R N I N GW A R N I N G
Identifies information about practices or circumstances that can cause an explosion in a hazardous environment, which may lead to personal injury or death, property damage, or economic loss.
I M P O R T A N TI M P O R T A N T
Identifies information that is critical for successful application and understanding of the product.
A T T E N T I O NA T T E N T I O N
Identifies information about practices or circumstances that can lead to personal injury or death, property damage, or economic loss. Attentions help you identify a hazard, avoid a hazard, and recognize the consequences.
S H O C K H A Z A R DS H O C K H A Z A R D
Labels may be on or inside the equipment (for example, drive or motor) to alert people that dangerous voltage may be present.
B U R N H A Z A R DB U R N H A Z A R D
Labels may be on or inside the equipment (for example, drive or motor) to alert people that surfaces may reach dangerous temperatures.

Table of Contents

Chapter 1 Overview Introduction ............................................................................. 1-1
User Interface ...........................................................................1-3
Operating Safety ..................................................................... 1-3
Chapter 2 Relay Front Panel ....................................................................2-1
Display ............................................................................. 2-1
Menu Navigation and Pointers ......................................... 2-3
Keypad ............................................................................. 2-3
Operation Indicators ......................................................... 2-4
Resetting Latched Indicators and Output Relays ............. 2-5
Adjusting Display Contrast .............................................. 2-5
Local Panel Options ................................................................ 2-5
Navigating in Menus ........................................................ 2-5
Main Menu ....................................................................... 2-7
Menu Structure of Protection Functions .......................... 2-9
Setting Groups ................................................................ 2-12
Fault Logs ....................................................................... 2-13
Operating Levels ............................................................ 2-14
Opening Access .............................................................. 2-15
Password Handling ......................................................... 2-15
Operating Measures .............................................................. 2-16
Control Functions ........................................................... 2-16
Measured Data ............................................................... 2-17
Reading Event Register .................................................. 2-18
Forced Control (Force) ................................................... 2-19
Configuration and Parameter Setting .................................... 2-20
Parameter Setting ........................................................... 2-21
Setting Range Limits ...................................................... 2-22
Disturbance Recorder Menu DR .................................... 2-23
Configuring Digital Inputs DI ........................................ 2-23
Configuring Digital Outputs DO .................................... 2-24
Protection Menu Prot ..................................................... 2-24
Configuration Menu CONF ........................................... 2-25
Protocol Menu Bus ......................................................... 2-27
Single Line Diagram Editing .......................................... 2-30
SetPointPS PC Software ....................................................... 2-31
Local Panel User Interface
Chapter 3 Protection Functions Maximum Number of Protection Stages ................................ 3-1
Protection Functions ............................................................... 3-1
General Features of Protection Stages .................................... 3-1
Setting Groups .................................................................. 3-1
Forcing Start or Trip Condition for Testing ..................... 3-2
Forcing Start or Trip Condition for Testing Purposes ...... 3-2
Start and Trip Signals ....................................................... 3-2
Output Matrix ................................................................... 3-2
Blocking ........................................................................... 3-3
Main Relay Features ................................................................1-1
865-UM001A-EN-P – July 2009
ii Table of Contents
Retardation Time .............................................................. 3-3
Chapter 3 Protection Functions
Reset Time (Release Time) .............................................. 3-4
(cont.)
Hysteresis or Dead Band .................................................. 3-5
Differential Overcurrent Protection ΔI> (87) ......................... 3-6
Parameters of the Differential Overcurrent Stages ......... 3-10
Overcurrent Protection I> (50/51) ........................................ 3-11
Two Independent Stages ................................................ 3-11
Inverse Operation Time .................................................. 3-11
Inverse Time Limitation ................................................. 3-11
Setting Groups ................................................................ 3-11
Recorded Values of the Latest Eight Faults ................... 3-14
Current Unbalance Protection I
>, I’2 (46) ........................... 3-15
2
Inverse Delay ................................................................. 3-15
More Stages (Definite Time Delay only) ....................... 3-15
Setting Groups ................................................................ 3-15
Recorded Values of the Latest Eight Faults ................... 3-17
Earth Fault Protection I
> (50N/51N) ................................... 3-17
0
Input Signal Selection .................................................... 3-18
Intermittent Earth Fault Detection .................................. 3-18
Four Independent Undirectional Earth Fault
Overcurrent Stages ................................................... 3-18
Inverse Operation Time (I
> stage only) ........................ 3-19
0
Inverse Time Limitation ................................................. 3-19
Setting Groups ................................................................ 3-19
Recorded Values of the Latest Eight Faults ................... 3-22
Thermal Overload Protection T> (49) .................................. 3-22
Thermal Model ............................................................... 3-22
Time Constant for Cooling Situation ............................. 3-23
Heat Capacitance, Service Factor and Ambient Temp. ... 3-23
Example of a Behavior of the Thermal Model ............... 3-24
Initial Temperature Rise after Restart ............................ 3-24
Alarm Function .............................................................. 3-24
Circuit-Breaker Failure Protection CBFP (50BF) ................ 3-26
Recorded Values of the Latest Eight Faults .......................... 3-27
Arc Fault Protection (50ARC/50NARC) - Optional ............ 3-28
Three Stages for Arc Faults ............................................ 3-28
Light Channel Selection ................................................. 3-28
Binary Input ................................................................... 3-28
Binary Output ................................................................. 3-29
Delayed Light Indication Signal .................................... 3-29
Pick Up Scaling .............................................................. 3-29
Recorded Values of the Latest Eight Faults ................... 3-30
Programmable Stages (99) .................................................... 3-31
Available Signals to be Supervised by the
Programmable Stages .............................................. 3-31
Eight Independent Stages ............................................... 3-31
Setting Groups ................................................................ 3-31
Recorded Values of the Latest Eight Faults ................... 3-32
865-UM001A-EN-P – July 2009
Table of Contents iii
Inverse Time Operation ........................................................ 3-33
Chapter 3 Protection Functions
Stage Specific Inverse Delay .......................................... 3-33
(cont.)
Operation Modes ............................................................ 3-33
Local Panel Graph .......................................................... 3-33
Inverse Time Setting Error Signal .................................. 3-34
Limitation ....................................................................... 3-34
Standard Inverse Delays IEC, IEEE, IEEE2, RI ............ 3-35
IEC Inverse Time Operation .................................... 3-36
IEEE/ANSI Inverse Time Operation ....................... 3-38
IEEE2 Inverse Time Operation ............................... 3-42
RI and RXIDG type Inverse Time Operation .......... 3-43
Free Parametrisation using IEC, IEEE and IEEE2
Equations ................................................................. 3-45
Programmable Inverse Time Curves .............................. 3-46
Inverse Time Setting Error Signal .................................. 3-47
Limitations ..................................................................... 3-47
Chapter 4 Supporting Functions Event Log ................................................................................4-1
Event Enabling/Masking .................................................. 4-1
Event Buffer Overflow ..................................................... 4-2
Disturbance Recorder ............................................................. 4-2
Triggering the Recorder ................................................... 4-2
Reading Recordings ......................................................... 4-2
Number of Channels ........................................................ 4-3
Available Channels .......................................................... 4-3
Current Transformer Supervision ........................................... 4-5
Circuit Breaker Condition Monitoring ................................... 4-6
Breaker Curve and its Approximation ............................. 4-6
Setting Alarm Points ........................................................ 4-7
Clearing “Operations Left” Counters ............................... 4-8
Operation Counters to Monitor the Wearing .................... 4-8
Logarithmic Interpolation ................................................ 4-8
Example of the Logarithmic Interpolation ....................... 4-9
Example of Operation Counter Decrementing ................. 4-9
System Clock and Synchronization .......................................4-11
Adapting Auto Adjust .................................................... 4-11
Time Drift Correction Without External Sync ............... 4-11
System Clock Parameters ..................................................... 4-13
Running Hour Counter ......................................................... 4-14
Timers ................................................................................... 4-14
Combined Overcurrent Status ............................................... 4-16
Self-Supervision ................................................................... 4-17
865-UM001A-EN-P – July 2009
iv Table of Contents
Chapter 5 Measurement Functions Measurement Accuracy ...........................................................5-1
Harmonics and Total Harmonic Distortion (THD) ................. 5-2
RMS Values ............................................................................ 5-3
RMS Currents ................................................................... 5-3
Demand Values ....................................................................... 5-3
Maximum and Maximum Values ........................................... 5-3
Maximum Values of the last 31 days and 12 months ............. 5-4
Primary, Secondary and per unit Scaling ................................ 5-4
Current Scaling ................................................................. 5-4
Chapter 6 Control Functions Output Relays ..........................................................................6-1
Digital Inputs .......................................................................... 6-2
Virtual Inputs and Outputs ...................................................... 6-3
Output Matrix ......................................................................... 6-4
Blocking Matrix ...................................................................... 6-5
Controllable Objects ............................................................... 6-5
Object States ..................................................................... 6-6
Basic Settings for Controllable Objects ........................... 6-6
Output Signals of Controllable Objects ........................... 6-6
Settings for Read-only Objects ........................................ 6-7
Controlling with DI (Firmware version >= 5.53) ............. 6-7
Local/Remote Selection ................................................... 6-7
Logic Functions ...................................................................... 6-8
Chapter 7 Communications Communication Ports ..............................................................7-1
Local Port X4 ................................................................... 7-2
Remote Port X5 ................................................................ 7-4
Extension Port X4 ............................................................ 7-6
Optional Inbuilt Ethernet Port .......................................... 7-7
Optional 61850 Interface .................................................. 7-7
Communication Protocols ...................................................... 7-8
PC Communication .......................................................... 7-8
Modbus TCP and Modbus RTU........................................ 7-8
Probibus DP ..................................................................... 7-9
SPA-bus .......................................................................... 7-10
IEC 60870-5-103 ............................................................ 7-11
DNP 3.0 .......................................................................... 7-13
IEC 60870-5-101 .............................................................7-14
TCP/IP ............................................................................ 7-16
External I/O (Modbus RTU master) ............................... 7-16
IEC 61850 ...................................................................... 7-16
865-UM001A-EN-P – July 2009
Table of Contents v
Chapter 8 Applications Restricted Earth Fault Protection .............................................8-1
Restricted Earth Fault Protection for a Transformer
With Neutral Connection ................................................. 8-2
CT Requirements ............................................................. 8-2
Calculating the Stabilizing Resistance R
, VDR Value,
S
and Actual Sensitivity ................................................ 8-3
Value of Stabilizing Resistor R
...................................... 8-3
S
Voltage Limitation ........................................................... 8-3
Actual Operating Sensitivity ............................................ 8-4
Current Transformer Selection ............................................... 8-5
CT Classification according IEC 60044-1, 1996 ............. 8-5
CT Requirement for Protection ........................................ 8-8
Protection of a Dyn11 Transformer ...................................... 8-11
Protection of a YNd11 Transformer ..................................... 8-13
Protection of Generator and Block Transformer .................. 8-14
Application Example of Differential Protection
using Allen-Bradley 865 Relay ...................................... 8-15
Trip Circuit Supervision ...................................................... 8-16
Chapter 9 Connections Rear Panel View ......................................................................9-1
Auxiliary Voltage ................................................................... 9-5
Serial Communication Connectors ......................................... 9-5
Front Panel Connector ...................................................... 9-5
Rear Panel Connector X5 (REMOTE) ............................. 9-5
X4 Rear Panel Connector (Local RS232 and
Extension RS485 ports) ............................................. 9-7
Optional Two-Channel Arc Protection Card .......................... 9-8
Optional Digital I/O Card (DI19/DI20) .................................. 9-8
Connection Examples ............................................................. 9-9
865-UM001A-EN-P – July 2009
vi Table of Contents
Chapter 10 Technical Data Connections .......................................................................... 10-1
Measuring Circuitry ....................................................... 10-1
Auxiliary Voltage ........................................................... 10-1
Digital Inputs .................................................................. 10-2
Trip Contacts .................................................................. 10-2
Alarm Contacts ............................................................... 10-2
Local Serial Communication Port .................................. 10-3
Remote Control Connection ........................................... 10-3
Arc Protection Interface (Option) .................................. 10-3
Tests and Environmental Conditions .................................... 10-4
Disturbance Tests ........................................................... 10-4
Test Voltages .................................................................. 10-4
Mechanical Tests ............................................................ 10-4
Environmental Conditions .............................................. 10-4
Casing ............................................................................. 10-5
Package .......................................................................... 10-5
Protection Stages .................................................................. 10-5
Differential Protection .................................................... 10-5
Differential Overcurrent Stage ΔI> (87) .................. 10-5
Differential Overcurrent Stage ΔI>> (87) ............... 10-5
Non-Directional Current Protection ............................... 10-6
Overcurrent Stage I>, I’> (50/51) ............................ 10-6
Overcurrent Stage I>> and I’>> (50/51) .................. 10-6
Thermal Overload Stage T> (49) ............................. 10-7
Unbalance Stage I Earth Fault Stage I Earth Fault Stage I
>, I’2> (46) ................................. 10-7
2
> (50N/51N) ............................. 10-8
0
>>, I0>>>, I0>>>> (50N/51N) .. 10-8
0
Circuit-breaker Failure Protection .................................. 10-9
Arc Fault Protection Stages (Option) ............................. 10-9
Arc Protection Stage Arcl> (50AR), Option ........... 10-9
Arc Protection Stage Arcl Arc Protection Stage Arcl
> (50AR), Option .......... 10-9
0
> (50AR), Option ....... 10-10
02
Supporting Functions ................................................... 10-10
Disturbance Recorder (DR) ................................... 10-10
Chapter 11 List of Abbreviations and Symbols .......................................11-1
Abbreviations and Symbols
Chapter 12 Installation Mounting Instructions ........................................................... 12-1
865-UM001A-EN-P – July 2009
Chapter 1
Overview

Introduction The Allen-Bradley 865 differential protection system includes all the

essential protection functions needed to protect transformers for distribution networks of utilities, industry, power plants and offshore applications as well as motor and generator differential protection. Further, the device includes several programmable functions, such as thermal and circuit breaker protection and communication protocols for various protection and communication situations. An optional arc flash protection feature is also available.
The Allen-Bradley 865 can be used for selective differential
overcurrent, short-circuit protection of generators, transformers and motors in solidly or impedance earthed power systems. The relay can also be used for single, two or three-phase overcurrent and/or sensitive earth fault protection.
The modern technology in association with an extensive self-
supervision system and a reliable construction ensures extremely high system availability for the Allen-Bradley 865 protection relay.

Main Relay Features The main features of Allen-Bradley 865 are:

Fully digital signal handling with a powerful 16-bit
microprocessor, and high measuring accuracy on all the setting ranges due to an accurate 16-bit A/D conversion technique
Wide setting ranges for the protection functions, e.g. the earth
fault protection can reach a sensitivity of 0.5%
The device can be matched to the requirements of the application
by disabling the functions that are not needed
Flexible control and blocking possibilities due to digital signal
control inputs (DI) and outputs (DO)
Easy adaptability of the relay to various substations and alarm
systems due to flexible signal-grouping matrix in the relay
Freely configurable display with six measurement values
865-UM001A-EN-P – July 2009
1-2 Overview
Main Features (cont.)
Freely configurable interlocking schemes with basic logic
functions
Recording of events and fault values into an event register from
which the data can be read via a keypad and a local HMI or by means of a PC based SetPointPS user interface
Latest events and indications are in non-volatile memory.
Easy configuration, parameter setting and reading of information
via local HMI, or with the SetPointPS programming software
Easy connection to power plant automation system due to a
versatile serial connection and several available communication protocols
Built-in, self-regulating ac/dc converter for auxiliary power
supply from any source within the range from 40 to 865 V dc or ac. The alternative power supply is for 18 to 36 V dc
Built-in disturbance recorder for evaluating all the analogue and
digital signals
Eight (8) programmable stages for alarming or protection
purposes
The Allen-Bradley 865 differential protection relay is ideal for
transformer, motor, generator and short cable (100) differential protection. The relay features the following protection functions.
Table 1-1 – List of Protection Functions
IEEE/
ANSI code
50/51 3I>, 3I>>, 3I’>, 3I’>> Overcurrent protection
87 ∆I>, ∆I>> Differential overcurrent protection
46 I2>, I’2> Current unbalance protection
49 T> Thermal overload protection
50N/51N
50BF CBFP Circuit-breaker failure protection
99 Prg1...8 Programmable stages
50ARC
50NARC
Further the relay includes a disturbance recorder. Arc protection
is optionally available.
The relay communicates with other systems using common
protocols, such as the Modbus RTU, ModbusTCP, Profibus DP, Ethernet, DeviceNet, IEC 60870-5-103, SPA bus and DNP 3.0, IEC 61850 and IEC 60870-5-101.
IEC symbol Function name
>,
I
0
>>,
I
0
I
>>>,
0
>>>>
I
0
ArcI>, ArcI’>
>, ArcI02>
ArcI
01
Earth fault protection
Optional arc fault protection
865-UM001A-EN-P – July 2009
Overview 1-3

User Interface

The relay can be controlled in three ways:
Locally with the push-buttons on the relay front panel
Locally using a PC connected to the serial port on the front panel
or on the rear panel of the relay (both cannot be used simultaneously)
Via remote control over the remote control port on the relay rear
panel.

Operating Safety

A T T E N T I O NA T T E N T I O N
The terminals on the rear panel of the relay may carry dangerous voltages, even if the auxiliary voltage is switched off. A live current transformer secondary circuit must not be opened. Disconnecting a live circuit may cause dangerous voltages! Any operational measures must be carried out according to national and local handling directives and instructions.
Carefully read through all operation instructions before any
operational measures are carried out.
865-UM001A-EN-P – July 2009
1-4 Overview
865-UM001A-EN-P – July 2009
Chapter 2
Local Panel User Interface

Relay Front Panel The figure below shows, as an example, the front panel of the

Allen-Bradley 865 relay and the location of the user interface elements used for local control.
Figure 2.1 – Front Panel of Allen-Bradley 865 Relay
1. LCD dot matrix display
2. Keypad
3. LED indicators
4. RS 232 serial communication port for PC

Display

The relay is provided with a backlit 128x64 LCD dot matrix
display. The display enables showing 21 characters in one row and eight rows at the same time. The display has two different purposes: one is to show the single line diagram of the relay with the object status, measurement values, identification etc. (Figure
2.2). The other purpose is to show the configuration and parameter setting values of the relay (Figure 2.3).
865-UM001A-EN-P – July 2009
2-2 Local Panel User Interface
4
5
K00 0 6
2
Q4
Q1
Q0 Q3
Q9
3
AR : 1
50.02 Hz
L
6
1
7
Figure 2.2 – Sections of the LCD Matrix Display
1. Freely configurable single-line diagram
2. Five controllable objects
3. Status for six independent objects
4. Bay identification
5. Local/Remote selection
6. Auto-reclose on/off selection (if applicable)
7. Freely selectable measurement values (max. six values)
Figure 2.3 – Sections of the LCD Matrix Display
1. Main menu column
2. The heading of the active menu
3. The cursor of the main menu
4. Possible navigating directions (push buttons)
5. Measured/setting parameter
6. Measured/set value
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-3
Backlight Control
Display backlight can be switched on with a digital input, virtual
input or virtual output. LOCALPANEL CONF/Display backlight ctrl setting is used for selecting trigger input for backlight control. When the selected input activates (rising edge), display backlight is set on for 60 minutes.

Menu Navigation and Pointers

1. Use the arrow keys UP and DOWN to move up and down in the main menu, that is, on the left-hand side of the display. The active main menu option is indicated with a cursor. The options in the main menu items are abbreviations, e.g. Evnt = events.
2. After any selection, the arrow symbols in the upper left corner of the display show the possible navigating directions (applicable navigation keys) in the menu.
3. The name of the active submenu and a possible ANSI code of the selected function are shown in the upper part of the display, e.g. CURRENTS.
4. Further, each display holds the measured values and units of one or more quantities or parameters, e.g. ILmax 300A.

Keypad

You can navigate in the menu and set the required parameter
values using the keypad and the guidance given in the display. Furthermore, the keypad is used to control objects and switches on the single line diagram display. The keypad is composed of four arrow keys, one cancel key, one enter key and one info key.
Figure 2-4 – Keys on the Keypad
1. Enter and confirmation key (ENTER)
2. Cancel key (CANCEL)
3. Up/Down [Increase/Decrease] arrow keys (UP/DOWN)
865-UM001A-EN-P – July 2009
2-4 Local Panel User Interface
4. Keys for selecting submenus [selecting a digit in a numerical value] (LEFT/RIGHT)
5. Additional information key (INFO)
NOTE: The term, which is used for the buttons in this manual,
is inside the rounded brackets.

Operation Indicators

The relay is provided with eight LED indicators:
Power
Error Com
Alarm Trip A B C
Figure 2.5 – Operation Indicators of the Relay
Table 2.1 – Operation Indicators
LED indicator Meaning Measure/ Remarks
Power LED lit The power has been switched on Normal operation state Error LED lit Internal fault, operates in parallel with
the self supervision output relay
Com LED lit or flashing The serial bus is in use and
transferring information
Alarm LED lit One or several signals of the output
relay matrix have been assigned to output LA and the output has been activated by one of the signals. (For more information about output matrix, please see page 2-24).
Trip LED lit One or several signals of the output
relay matrix have been assigned to output Tr, and the output has been activated by one of the signals. (For more information about output relay configuration, see “Configuring Digital Outputs DO” on page 2-24).
A- C LED lit Application-related status indicators. Configurable
The relay attempts to reboot [REBOOT]. If the error LED remains lit, call for maintenance.
Normal operation state
The LED is switched off when the signal that caused output Al to activate, e.g. the START signal, is reset. The resetting depends on the type of configuration, connected or latched.
The LED is switched off when the signal that caused output Tr to activate, e.g. the TRIP signal, is reset. The resetting depends on the type of configuration, connected or latched.
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-5

Resetting Latched Indicators and Output Relays

All the indicators and output relays can be given a latching
function in the configuration.
There are several ways to reset latched indicators and relays:
From the alarm list, move back to the initial display by pushing
the CANCEL key for approx. 3 s. Then reset the latched indicators and output relays by pushing the ENTER key.
Acknowledge each event in the alarm list one by one by pushing
the ENTER key equivalent times. Then, in the initial display, reset the latched indicators and output relays by pushing the ENTER key.
The latched indicators and relays can also be reset via a remote
communication bus or via a digital input configured for that purpose.

Adjusting Display Contrast

The readability of the LCD varies with the brightness and the
temperature of the environment. The contrast of the display can be adjusted via the PC user interface, and SetPointPS software.

Local Panel Operations The front panel can be used to control objects, change the local/

remote status, read the measured values, set parameters, and to configure relay functions. Some parameters, however, can only be set by means of a PC connected to one of the local communication ports. Some parameters are factory-set.

Navigating in Menus

All the menu functions are based on the main menu/submenu structure:
1. Use the arrow keys UP and DOWN to move up and down in the main menu.
2. To move to a submenu, repeatedly push the RIGHT key until the required submenu is shown. Correspondingly, push the LEFT key to return to the main menu.
3. Push the ENTER key to confirm the selected submenu. If there are more than six items in the selected submenu, a black line appears to the right side of the display (Figure 2.6). It is then possible to scroll down in the submenu.
4. Push the CANCEL key to cancel a selection.
865-UM001A-EN-P – July 2009
2-6 Local Panel User Interface
Local Panel Operations (cont.)
5. Pushing the UP or DOWN key in any position of a sub-menu, when it is not selected, brings you directly one step up or down in the main menu.
The active main menu selection is indicated with black background
color. The possible navigating directions in the menu are shown in the upper-left corner by means of black triangular symbols.
Figure 2-6 – Example of Scroll Indication
Figure 2.7 – Principles of the Menu Structure and Navigation in the Menus
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-7
6. Push the INFO key to obtain additional information about any menu item.
7. Push the CANCEL key to revert to the normal display.
Main Menu
The general menu structure is shown in Figure 2.7. The menu is
dependent on the user's configuration and the options according to the order code. For example only the enabled protection stages will appear in the menu.
Table 2.2 – List of the Local Main Menu

Main menu

1 Interactive mimic display 1 5 Double size measurements defined by the user 1 1 Title screen with device name, time and firmware version. P 14 Power measurements E 4 Energy measurements I 13 Current measurements U 15 Voltage measurements Dema 15 Demand values Umax 5 Time stamped min & max of voltages Imax 9 Time stamped min & max of currents Pmax 5 Time stamped min & max of power and frequency Mont 21 Maximum values of the last 31 days and the last twelve months Evnt 2 Events DR 2 Disturbance recorder 2 Runh 2 Running hour counter. Active time of a selected digital input and
TIMR 6 Day and week timers DI 5 Digital inputs including virtual inputs DO 4 Digital outputs (relays) and output matrix ExtAI 3 External analogue inputs 3 ExDI 3 External digital inputs 3 ExDO 3 External digital outputs 3 Prot 27 Protection counters, combined overcurrent status, protection
ΔI> 7 1st differential stages ΔI>> 5 2nd differential stage I> 5 1st overcurrent stage (primary side) 50/51 4 I>> 3 2nd overcurrent stage (primary side) 50/51 4 I’> 5 1st overcurrent stage (secondary side) 50/51 4 I’>> 3 2nd overcurrent stage (secondary side) 50/51 4 I2> 3 Current unbalance stage (primary side) 46 4 I’2> 3 Current unbalance stage (secondary side) 46 4
Number of
menus
Description ANSI code Note
time stamps of the latest start and stop.
status, protection enabling, cold load and inrush detectionIf2> and block matrix
865-UM001A-EN-P – July 2009
2-8 Local Panel User Interface
Local Panel Operations (cont.)
Table 2.2 – List of the Local Main Menu (cont.)
Main menu
T> 3 Thermal overload stage 49 4 Io> 5 1st earth fault stage 50N/51N 4 Io>> 3 2nd earth fault stage 50N/51N 4 Io>>> 3 3rd earth fault stage 50N/51N 4 Io>>>> 3 4th earth fault stage 50N/51N 4 Prg1 3 1st programmable stage 4 Prg2 3 2nd programmable stage 4 Prg3 3 3rd programmable stage 4 Prg4 3 4th programmable stage 4 Prg5 3 5th programmable stage 4 Prg6 3 6th programmable stage 4 Prg7 3 7th programmable stage 4 Prg8 3 8th programmable stage 4 CBFP 3 Circuit breaker failure protection 50BF 4 CBWE 4 Circuit breaker wearing supervision 4 CTSV 1 CT supervisor 4 CT’SV 1 CT’ supervisor 4 ArcI> 4 Optional arc protection stage for phase-to-phase faults and
ArcIo> 3 Optional arc protection stage for earth faults. Current input = I01 50NARC 4 ArcIo2> 3 Optional arc protection stage for earth faults. Current input = I02 50NARC 4 OBJ 11 Object definitions 5 Lgic 2 Status and counters of user's logic 1 CONF 10+2 Device setup, scaling etc. 6 Bus 13 Serial port and protocol configuration 7 Diag 6 Device selfdiagnosis
Number of
menus
Description ANSI code Note
50ARC 4
delayed light signal.
NOTES:
1. Configuration is done with SetPointPS.
2. Recording files are read with SetPointPS.
3. The menu is visible only if protocol ”External IO” is selected for one of the serial ports. Serial ports are configured in menu ”Bus”.
4. The menu is visible only if the stage is enabled.
5. Objects are circuit breakers, disconnectors, etc. Their position or status can be displayed and controlled in the interactive mimic display.
6. There are two extra menus, which are visible only if the access level ”operator” or ”configurator” has been opened with the corresponding password.
7. Detailed protocol configuration is done with SetPointPS.
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-9

Menu Structure of Protection Functions

The general structure of all protection function menus is similar
although the details do differ from stage to stage. As an example the details of the second overcurrent stage I>> menus are shown below:
F
IRST MENU OF I>> 50/51 STAGE
I>> STATUS 50/51
Off
­5 2 1
-
ExDO Prot I>
I>>
Iv>
Figure 2.8 – First Menu of I>>50/51 Stage
I>j
Status SCntr TCntr SetGrp SGrpDI Force
This is the status, start and trip counter and setting group menu. The
content is:
Status – The stage is not detecting any fault at the moment. The stage can also be forced to pick-up or trip if the operating level is "Configurator" and the force flag below is on. Operating levels are explained in section “Operating Levels”.
SCntr 5 – The stage has picked-up a fault five times since the last reset of restart. This value can be cleared if the operating level is at least "Operator".
TCntr 1 – The stage has tripped two times since the last reset of restart. This value can be cleared if the operating level is at least "Operator".
SetGrp 1 – The active setting group is one. This value can be edited if the operating level is at least “Operator”. Setting groups are explained in section “Setting Groups”.
SGrpDI – The setting group is not controlled by any digital input. This value can be edited if the operating level is at least “Configurator”.
Force Off – The status forcing and output relay forcing is disabled. This force flag status can be set to “On” or back to “Off” if the operating level is at least “Configurator”. If no front panel button is pressed within five minutes and there is no SetPointPS communication, the force flag will be set to “Off” position. The forcing is explained in section “Forced Control (Force)”.
865-UM001A-EN-P – July 2009
2-10 Local Panel User Interface
Local Panel Operations (cont.)
S
Figure 2.9 – Second Menu (next to the right) of I>>50/51 Stage
This is the main setting menu. The content is:
Stage setting group 1 – These are the group 1 setting values.
ECOND MENU OF I>> 50/51 STAGE
I>> SET 50/51 Stage setting group 1 ExDI ExDO Prot
I>>
CBWE OBJ
ILmax Status I>> I>> t>>
403A
-
1013A
2.50xIgn
0.60s
The other setting group can be seen by pressing push buttons ENTER and then RIGHT or LEFT. Setting groups are explained in section “Setting Groups”.
Ilmax 403A – The maximum of the three measured phase currents is at the moment 403 A. This is the value the stage is supervising.
Status – Status of the stage. This is just a copy of the status value in the first menu.
I>> 1013 A – The pick-up limit is 1013 A in primary value.
I>> 2.50xIn – The pick-up limit is 2.50 times the rated current of the protected object. This value can be edited if the operating level is at least "Operator". Operating levels are explained in section “Operating Levels”.
t>> 0.60s – The total operation delay is set to 600 ms. This value can be edited if the operating level is at least "Operator".
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-11
T
HIRD MENU OF I>> 50/51 STAGE
I>> LOG 50/51
FAULT LOG 1 ExDI
ExDO Prot
I>>
CBWE OBJ
Figure 2.10 – Third and Last Menu (next to the right) of I>>50/51 Stage
2006-09-14 12:25:10.288 Type Flt Load EDly
1-2
2.86xIgn
0.99xIgn 81%
SetGrp 1
This is the menu for registered values by the I>> stage. Fault logs are
explained under “Fault Logs” on page 2-13.
FAULT LOG 1 – This is the latest of the eight available logs. You may move between the logs by pressing push buttons ENTER and then RIGHT or LEFT.
2006-09-14 – Date of the log.
12:25:10.288 – Time of the log
Type 1-2 – The overcurrent fault has been detected in phases L1 and L2 (A & B, red & yellow, R&S, u&v).
Flt 2.86xIn – The fault current has been 2.86 per unit.
Load 0.99xIn – The average load current before the fault has been 0.99 pu.
EDly 81% – The elapsed operation delay has been 81% of the setting 0.60 s = 0.49 s. Any registered elapsed delay less than 100 % means that the stage has not tripped, because the fault duration has been shorter than the delay setting.
SetGrp 1 – The setting group has been 1. This line can be reached by pressing ENTER and several times the DOWN button.
865-UM001A-EN-P – July 2009
2-12 Local Panel User Interface
Local Panel Operations (cont.)

Setting Groups

Most of the protection functions of the relay have two setting groups.
These groups are useful for example when the network topology is changed frequently. The active group can be changed by a digital input, through remote communication or locally by using the local panel.
The active setting group of each protection function can be selected
separately. Figure 2.11 shows an example where the changing of the I> setting group is handled with digital input one (SGrpDI). If the digital input is TRUE, the active setting group is group two and correspondingly, the active group is group one, if the digital input is FALSE. If no digital input is selected (SGrpDI = -), the active group can be selected by changing the value of the parameter SetGrp.
Figure 2.11 – Example of Protection Submenu with Setting Group
The changing of the setting parameters can be done easily. When the
desired submenu has been found (with the arrow keys), press the ENTER key to select the submenu. Now the selected setting group is indicated in the down-left corner of the display (See Figure 2.12). Set1 is setting group one and Set2 is setting group two. When the needed changes, to the selected setting group, have been done, press the LEFT or the RIGHT key to select another group (the LEFT key is used when the active setting group is 2 and the RIGHT key is used when the active setting group is 1).
Figure 2.12 – Example of I> Setting Submenu
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-13

Fault Logs

All the protection functions include fault logs. The fault log of a
function can register up to eight different faults with time stamp information, fault values etc. Each function has its own logs (See Figure 2.13).
Figure 2.13 – Example of Fault Log
To see the values of, for example, log two, press the ENTER key to
select the current log (log one). The current log number is then indicated in the down-left corner of the display (See Figure 2.14, Log2 = log two). The log two is selected by pressing the RIGHT key once.
Figure 2.14 – Example of Selected Fault Log
865-UM001A-EN-P – July 2009
2-14 Local Panel User Interface

Operating Levels

Local Panel Operations (cont.)
The relay has three operating levels: User level, Operator level
and Configurator level. The purpose of the access levels is to prevent accidental change of relay configurations, parameters or settings.
USER level
Use: Possible to read e.g. parameter values,
measurements and events Opening: Level permanently open Closing: Closing not possible
OPERATOR level
Use: Possible to control objects and to change e.g. the
settings of the protection stages Opening: Default password is 1 Setting State: Push ENTER Closing: The level is automatically closed after 10 minutes
idle time. Giving the password 9999 can also close
the level.
CONFIGURATION level
Use: The configurator level is needed during the
commissioning of the relay. E.g. the scaling of the
voltage and current transformers can be set. Opening: Default password is 0002 Setting State: Push ENTER Closing: The level is automatically closed after 10 minutes
idle time. Giving the password 9999 can also close
the level.
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-15

Opening Access

1. Push the INFO key and the ENTER key on the front panel.
ENTER PASSWORD
0
***
Figure 2.15 – Opening the Access Level
2. Enter the password needed for the desired level: the password can contain four digits. The digits are supplied one by one by first moving to the position of the digit using the RIGHT key and then setting the desired digit value using the UP key.
3. Push the ENTER key.

Password Handling

The passwords can only be changed using SetPointPS software
connected to the local RS-232 port on the relay.
It is possible to restore the password(s) in case the password is lost or
forgotten. In order to restore the password(s), a relay program is needed. The serial port settings are 38400 bps, 8 data bits, no parity and one stop bit. The bit rate is configurable via the front panel.
Command Description
get pwd_break Get the break code (Example: 6569403) get serno Get the serial number of the relay (Example: 12345)
Send both the numbers to Rockwell Automation and ask for a
password break. A device specific break code is sent back to you. That code will be valid for the next two weeks only for this specific device.
Command Description
set pwd_break=4435876 Restore the factory default passwords (“4435876” is
just an example. The actual code should be requested from Rockwell Automation.)
Now the passwords are restored to the default values (See section
“Operating Levels”).
865-UM001A-EN-P – July 2009
2-16 Local Panel User Interface

Operating Measures Control Functions

The default display of the local panel is a single-line diagram
including relay identification, Local/Remote indication, Auto-reclose on/off selection and selected analogue measurement values.
Please note that the operator password must be active in order to be
able to control the objects. Please refer to ‘Opening Access’ on page 2-15.
Toggling Local/Remote Control
1. Push the ENTER key. The previously activated object starts to blink.
2. Select the Local/Remote object (“L” or “R” squared) by using the arrow keys.
3. Push the ENTER key. The L/R dialog opens. Select “REMOTE” to enable remote control and disable local control. Select “LOCAL” to enable local control and disable remote control.
4. Confirm the setting by pushing the ENTER key. The Local/Remote state will change.
Object Control
1. Push the ENTER key. The previously activated object starts to blink.
2. Select the object to control by using the arrow keys. Please note that only controllable objects can be selected.
3. Push the ENTER key. A control dialog opens.
4. Select the “Open” or “Close” command by using the UP and DOWN arrow keys.
5. Confirm the operation by pushing the ENTER key. The state of the object changes.
Toggling Virtual Inputs
1. Push the ENTER key. The previously activated object starts to blink.
2. Select the virtual input object (empty or black square)
3. The dialog opens
4. Select “VIon” to activate the virtual input or select “VIoff” to deactivate the virtual input
865-UM001A-EN-P – July 2009
Local Panel User Interface 2-17

Measured Data

The measured values can be read from the main menus and their
submenus. Furthermore, any measurement value in the following table can be displayed on the main view next to the single line diagram. Up to six measurements can be shown.
Table 2.3 – Measured Values
Value Menu/Submenu Description
f P/POWER Frequency [Hz] IL1 I/PHASE CURRENTS Phase current IL1 [A] IL2 I/PHASE CURRENTS Phase current IL2 [A] IL3 I/PHASE CURRENTS Phase current IL3 [A] IL1da I/PHASE CURRENTS 15 min average for IL1 [A] IL2da I/PHASE CURRENTS 15 min average for IL2 [A] IL3da I/PHASE CURRENTS 15 min average for IL3 [A] I’L1 I/PHASE CURRENTS Phase current I’L1 [A] I’L2 I/PHASE CURRENTS Phase current I’L2 [A] I’L3 I/PHASE CURRENTS Phase current I’L3 [A] I’L1da I/PHASE CURRENTS 15 min average for I’L1 [A] I’L2da I/PHASE CURRENTS 15 min average for I’L2 [A] I’L3da I/PHASE CURRENTS 15 min average for I’L3 [A] Io I/SYMMETRIC CURRENTS Primary value of zero sequence/ residual current Io [A] Io2 I/SYMMETRIC CURRENTS Primary value of zero-sequence/residual current Io2 [A] IoC I/SYMMETRIC CURRENTS Calculated Io [A] I1 I/SYMMETRIC CURRENTS Positive sequence current [A] I2 I/SYMMETRIC CURRENTS Negative sequence current [A] I2/I1 I/SYMMETRIC CURRENTS Negative sequence current related to positive sequence current
(for unbalance protection) [%] I’1 I/SYMMETRIC CURRENTS Positive sequence current [A] I’2 I/SYMMETRIC CURRENTS Negative sequence current [A] I’2/I’1 I/SYMMETRIC CURRENTS Negative sequence current related to positive sequence current
(for unbalance protection) [%] THDIL I/HARM. DISTORTION Total harmonic distortion of the mean value of phase currents [%] THDIL1 I/HARM. DISTORTION Total harmonic distortion of phase current IL1 [%] THDIL2 I/HARM. DISTORTION Total harmonic distortion of phase current IL2 [%] THDIL3 I/HARM. DISTORTION Total harmonic distortion of phase current IL3 [%] THDI’L1 I/HARM. DISTORTION Total harmonic distortion of phase current I’L1 [%] THDI’L2 I/HARM. DISTORTION Total harmonic distortion of phase current I’L2 [%] THDI’L3 I/HARM. DISTORTION Total harmonic distortion of phase current I’L3 [%] Diagram I/HARMONICS of IL1 Harmonics of phase current IL1 [%] (See Figure 2.16) Diagram I/HARMONICS of IL2 Harmonics of phase current IL2 [%] (See Figure 2.16) Diagram I/HARMONICS of IL3 Harmonics of phase current IL3 [%] (See Figure 2.16) Diagram I/HARMONICS of I’L1 Harmonics of phase current I’L1 [%] (See Figure 2.16) Diagram I/HARMONICS of I’L2 Harmonics of phase current I’L2 [%] (See Figure 2.16) Diagram I/HARMONICS of I’L3 Harmonics of phase current I’L3 [%] (See Figure 2.16)
865-UM001A-EN-P – July 2009
2-18 Local Panel User Interface
Operating measures (cont.)
Figure 2.16 – Example of Harmonics Bar Display

Reading Event Register

The event register can be read from the EVNT submenu:
1. Push the RIGHT key once.
2. The EVENT LIST appears. The display contains a list of all the events that have been configured to be included in the event register.
Figure 2.17 – Example of an Event Register
3. Scroll through the event list with the UP and DOWN keys.
4. Exit the event list by pushing the LEFT key.
It is possible to set the order in which the events are sorted. If the
“Order” -parameter is set to “New-Old”, then the first event in the EVENT LIST is the most recent event.
865-UM001A-EN-P – July 2009
Loading...
+ 156 hidden pages