This instruction sheet is available in multiple languages at www.rockwellautomation.com/literature. Se lect
publication language and type "SensaGuard" in the search field.
Dieses Instruktio nsblatt kann in mehreren Sprachen unter ww w.rockwellautomation.com/ literature gelesen
werden. Bitte Ihre Sprache anwähl en und "SensaGuard" im Suchfeld eintippen.
Ces instructions sont disponibles dans différentes langues à l'adresse suivante www.rockwellautomation.com/
literature. Sélectionner la langue puis taper “SensaGuard” dans le champ de recherche.
La presente scheda d'istruz ione è disponibile in varie lingue sul sito w ww.rockwellautomation.com/literature.
Selezionare la lingua desiderata e digitare "SensaGuard" nel campo di ri cerca.
Puede encontrar esta hoja de i nstrucciones en varios idiomas en www.rockwel lautomation.com/literature.
Seleccione el idioma de pu blicación y escriba "SensaGuard" en el campo de búsque da.
Esta folha de instruções está disponível em várias línguas em www.rockwell automation.com/literature.
Seleccione a língua de publicação e entre com "SensaGuard" no espaço de busca.
Ta kartka z instrukcjami jest dostepna w wielu jezykach na stronie: www.rockwellautomation.com/literature
Wybierz jezyk publikacji i wpisz w polu poszukiwania "SensaGuard".
Sensing Distance18 mm Actuator30 mm Actuator
Assured Make15 mm25 mm
Assured OFF25 mm35 mm
Typical Misalignment(±7 mm in both axes)
Repeat Accuracy10% of sensing range
Max. output current (all outputs)200 mA
Input Current50 mA (no load supply current)
Installation Instructions
Installation must be in accordance with the following steps and
stated specifications and should be carried out by suitable
competent personnel. The unit is not to be used as a mechanical
stop. Guard stops and guides must be fitted. Adherence to the
recommended maintenance instructions forms part of the
warranty.
This device is intended to be part of the safety related control
system of a machine. Before installation, a risk assessment should
be performed to determine whether the specifications of this
device are suitable for all foreseeable operational and
environmental characteristics of the machine to which it is to be
fitted. Refer to Technical Specifications below for certification
information and ratings.
ATTENTION
The presence of spare actuators compromise the
integrity of the safety systems. Personal injury or
death, property damage or economic loss can
result. Appropriate management controls, working
procedures and alternative protective measures
should be introduced to control their use and
availability.
Do not defeat, tamper, remove or bypass this unit.
Severe injury to personnel could result. The sensor
MUST be connected to a Class 2 SELV 24V DC,
+10%/-15% power supply.
Technical Specifications
Type 4 Interlocking Device per ISO 14119 (High Coding)
Safety Classification
Standards
CertificationsTÜV, CE Marked for all applicable directives, cULus
Functional Safety Data
PLe, Cat 4 per ISO 13849-1
SIL CL3 per IEC 62061 and IEC 61508
ISO 14119, IEC 60947-5-3, IEC 61508, IEC 62061, ISO138491, UL 508, CSA 22.2 No. 14
-9
: 1.12 - 10
PFH
D
Operational Current, Min.1 mA DC
Off-state Current<0.5 mA DC
Max. no. of switches, connected in
series
Operating Voltage
Unlimited. See Unit Response Time section on
page 5.
24V DC +10%/-15%
Class 2 SELV power supply
Frequency of operating cycle1 Hz
Response Time (Off )
54 ms first switch,
18 ms for each additional switch
Case MaterialPolycarbonate
Actuator MaterialPolycarbonate
Outputs (guard door closed, actuator in place)
OutputsDescriptionStatus
Safety2 x PNP, 0.2 A max.ON (+24V DC)
Auxiliary1 x PNP, 0.2 A max.OFF (0V DC)
Environmental
Operating Temperature [C (F)]-10…+55° (14…131°)
Operating Humidity5…95% relative
Washdown RatingNEMA 3, 4X, 12, 13, IP69k
Shock & Vibration
Radio Frequency
IEC 68-2-27 30 g, 11 ms/IEC 68-2-6
10…55 Hz
IEC 61000-4-3
IEC 61000-4-6
Rockwell Automation 440N-IN013A-EN-P—October 2014
Page 2
2 SensaGuard™ 18 mm Plastic Barrel Unique Coding
Sensor
18 mm Actuator
67.06
[2.640]
2.03
[.080]
M18X1
36.47
[1.436]
13.72
[0.54]
15.87
[0.625]
36.47
[1.436]
13.72
[0.54]
15.87
[0.625]
4.57
[0.180]
DIA
19.81
[0.78]
3.17
[0.125]
15.42
[0.607]
2 PLACES
18 mm Actuator
75 mm
Sensor
1
Sensor
2
30 mm Actuator
100 mm
Sensor
1
Sensor
2
IMPORTANT
Protection
Short-circuit Incorporated
Current LimitationIncorporated
OverloadIncorporated
False PulseIncorporated
Tra nsi ent Noi seIn cor por ated
Reverse PolarityIncorporated
OvervoltageIncorporated
Thermal Shutdown/RestartIncorporated
Electrical Life
10 x 10
Dimensions [mm (in.)]
16.84
[0.663]
3.17
[0.125]
22.22
[0.875]
48.92
30.40
[1.197]
[1.926]
19.81
[0.78]
Mounting Information
Use non-removable screws, bolts, or nuts to mount the switch and
actuator. Do not over torque the mounting hardware.
Position the switch and actuator so they are aligned with each
other.
Mount the switch and actuator to removable guard, door, or gate.
Keep the switch and actuator within the sensing range below.
This switch is not meant to be fully embedded in metal. Use the
stainless steel version (440N-Z21S17* or 440N-Z21U17*) for
embedding.
• “Power/Fault” LED illuminates green: Door/guard closed,
safety outputs active.
• “Power/Fault” LED illuminates red: Door/guard open,
safety outputs off.
• “Power/Fault” LED flashes red: Unit failure. See Diagnostic
section on page 3.
• “Power/Fault” LED flashes green: Safety inputs off.
Misalignment Curve
18 mm Unit with 18 mm Target
25
20
OFFOFF
15
10
Face to Face Distance—mm
5
Side LobeSide Lobe
0
-25
(-0.98)
-20
(-0.787)
-15
(-0.59)
Lateral Misalignment Tolerance—mm (in)
There must be a minimum spacing of 4 mm
(0.157in.) if actuator and sensor face approaches
laterally. This will prevent false triggering due to
the side lobe areas.
Assured Sensing
Assured Sensing
-10
(-0.39)-5(-0.19)
Distance
OFF
Distance
ON
0
5
(0.19)10(0.39)15(0.59)
20
(0.787)25(0.98)
Rockwell Automation 440N-IN013A-EN-P—October 2014
Page 3
SensaGuard™ 18 mm Plastic Barrel Unique Coding 3
IMPORTANT
476
8
1
5
2
3
Brown
White
Blue
Pink
Grey
Green
Red
Yellow
18 mm Unit with 30 mm Target
35
30
25
OFFOFF
20
15
10
Face to Face Distance—mm
Side LobeSide Lobe
5
0
-30
(-1.18)
-20
(-0.787)
(-0.39)
Lateral Misalignment Tolerance—mm (in)
There must be a minimum spacing of 7 mm
(0.275in.) if actuator and sensor face approaches
laterally. This will prevent false triggering due to
the side lobe areas.
Assured Sensing
Distance
Assured Sensing
Distance
-10
OFF
ON
010
(0.39)20(0.787)30(1.18)
Wiring Diagram
8-Pin Unit
Pin NumberWire ColorSignal
1WhiteAux. Outputs
2Brown+24V
3GreenNA
4YellowOSSD 2, +24V Input
5GreyOSSD 1
6PinkOSSD 2
7Blue0V
8RedOSSD 1, +24V Input
Recommended mating cable, 2 m (6.5 ft)—889D-F8AB-2.
Replace the 2 with 5 (5 m) or 10 (10 m) for standard cable lengths.
5-Pin Unit
Pin NumberSignal
1+24V
2OSSD 1
30V
4OSSD 2
5Aux.
Recommended cordset, 2m (6.5 ft) - 889D-F5AC-2. Replace the
2 with 5 (5 m) or 10 (10 m) for standard cable lengths.
Note: If the user does not require the Auxiliary signal, a 4-pin
cordset (889D-F4AC-2) can be used.
Recommended patchcord for use with ArmorBlock® Guard
Safety I/O, 2 m (6.5 ft) - 889D-F4ACDM-2. Replace the 2 with
0M3 (0.3 m), 1 (1 m), 5 (5 m), or 10 (10 m) for standard cable
lengths.
Note: Do not use a 5-pin patchcord with the ArmorBlock.
2
15
3
4
Diagnostic
Unit Indicators (per IEC 60073)
StateStatusTroubleshooting
OffNot PoweredNA
RedNot Safe, OSSD not activeNA
GreenSafe, OSSD activeNA
Device
Output
LED
Green
Flash
Flash
Power up test or OSSD inputs
not valid
Red
1 Hz Flash Recoverable Fault
4 Hz Flash Non-recoverable Fault
Check 24V DC or OSSD inputs
(yellow and red wire)
Recoverable fault —check
OSSD outputs are not shorted
to GND, 24V DC or each other.
Cycl e pow er.
Rockwell Automation 440N-IN013A-EN-P—October 2014
IMPORTANT
Refer to Technical Specifications (page 1) for
certification information and ratings.
Page 4
4SensaGuard™ 18 mm Plastic Barrel Unique Coding
IMPORTANT
IMPORTANT
IMPORTANT
IMPORTANT
Commissioning
Power the Sensor
Connect the sensor to 24V DC. See "Typical Wiring Diagram"
section for help.
The sensor "Status/Diag" LED will begin to blink
Green eight times then repeat, indicating that
the sensor has not yet learned an actuator.
The sensor can be commissioned to either have the ability to
learn another actuator or be locked for a one time learn only. See
“Teaching in the Actuator” section.
Teaching in the actuator (ability to learn an additional
actuator)
Quick Start
1. Power up the sensor and bring an actuator into the sensing
range.
2. Leave the actuator in the sensing field for two minutes or
longer.
3. Learn is complete.
The sensor can learn a new actuator up to eight
times. The "Status/Diag" LED will blink the
number of actuators left that a sensor can learn.
Initially teaching in the actuator
The sensor will automatically start the learning process as soon as
an actuator is brought into the sensing range.
The actuator must not be removed from the
sensing field during the learning procedure or
the ability to learn additional actuators will be
disabled.
Learning Sequence
1. Target present:"Status/Diag" LED blinking Green 1 Hz rate
2. Verifying actuator:"Status/Diag" LED blinking Green/RED 1 Hz rate (15sec)
3. Program sensor:"Status/Diag" LED blinking Green/RED 4 Hz rate (15sec)
4. Program complete: "Status/Diag" LED blinking Green (# of learns left) (15 sec)
5. Ready state:"Status/Diag" LED solid Green
6. Learn is complete
Teaching in the Actuator (one time learn only; unit
locked)
Initially teaching in the actuator
The sensor will automatically start the learning process as soon as
an actuator is brought into the sensing range.
Learning Sequence
1. Target present:"Status/Diag" LED blinking Green 1 Hz rate
3. Program Sensor: "Status/Diag" LED blinking Green/RED 4 Hz rate (15 sec)
4. Program Locking: "Status/Diag" LED blinking Green (# of learn left) (15 sec)
During the Program Locking Stage, perform the following steps:
a. Remove the actuator from the sensing field, until the
"Status/Diag" LED changes to solid red.
b. Replace the actuator back into the sensing field and the
"Status/Diag" LED will continue blinking green (number of
learns remaining).
5. Ready state:"Status/Diag" LED solid green
6. Learn is complete
Learning a new actuator:
To learn a replacement actuator, bring the actuator to be taught
into the sensing range of the safety switch.
The learn sequence is the same as the sequence for
commissioning the first actuator.
IMPORTANT
A sensor can not re-learn a previously learned actuator or a
standard SensaGuard actuator.
The sensor will only recognize the most recently learned actuator.
Unique Coded Diagnostic:
Error codes for learning process. Repeat until the unit is power
cycled.
Status/Diag LED—Flashes (4 Hz)Error Code
Green OSSD inputs not valid
A sensor can be locked so it can not learn
another actuator by removing the actuator from
the sensing field during the 15 second "Program
Complete" sequence.
A sensor can be locked so it can not learn
another actuator; see teaching in the actuator
(one time learn only) section.
Red-Red-Red-Green
Can not learn a standard SensaGuard
Actuator
Red-Red-Red-Green-GreenActuator already learned
Red-Red-Red-Green-Green-GreenBad RFID; Target moved out of range
Actuator 2 is in sensing range.
Switch
2 is functioning properly
OSSDs are energize to 24 V
Green LED is ON.
Actuator 3 is in sensing range.
Switch
3 has fault.
See Table Above—Red LED is flashing
Actuator 1 is in sensing range.
Switch
1 is functioning properly
OSSDs are energize to 24 V
Green LED is ON.
Actuator 4 is in sensing range.
Switch
4 is functioning properly.
Series inputs are 0 V.
OSSDs are de-energized to 0V .
Green LED is Flashing to indicate
Series inputs are not 24V.
Actuator 5 is in sensing range.
Switch
5 is functioning properly .
Series inputs are 0V .
OSSDs are de-energized to 0V.
Green LED is Flashing to indicate
Series inputs are not 24V.
OSSD’s are OFF
Recoverable fault
IMPORTANT
Yel
Red
White
Gray
Pink
Blue
24V DC
Power
Supply
1606
Sensor 1
+24
RT
Sensor 2
Brown
Brown
Gray
Pink
White
Yel
Red
Blue
Sensor 3
Brown
Yel
Red
White
Gray
Pink
Blue
A1
S21
S1141332313S12S52
42342414A2S34S22
MSR127TP
Actuator 1
Actuator 2
Actuator 3
Initial Conditions:
All actuators are in sensing
distance.
Actuator 1 is moved out of
sensing range.
Sensor 2 drops the 24 volts
(red and yellow) from Sensor 1
OSSD outputs.
Green LED flashes.
Sensor 3 drops the 24 volts
(red and yellow) from Sensor 2
OSSD outputs.
Green LED flashes.
0 ms
54 ms72 ms90 ms
Actuator 1 is out of sensing
range.
Actuator 2 and 3 are in
sensing range.
Actuator 1 is moved into sensing
range.
Sensor 1 OSSD outputs are
energized.
Sensor 2 OSSD inputs (red and yellow)
transition to 24V DC from Sensor 1
OSSD outputs.
Sensor 2 OSSD outputs are energized
Sensor 3 OSSD inputs (red and
yellow) transition to 24V DC from
Sensor 2 OSSD outputs.
Sensor 3 OSSD outputs are
energized.
0 ms
360 ms378 ms396 ms
OFF
ON
IMPORTANT
Troubleshooting
Series Circuit
Refer to Technical Specifications (page 1) for
certification information and ratings.
Unit Response Time (does not include safety control system response time)
Refer to Technical Specifications (page 1) for
certification information and ratings.
Rockwell Automation 440N-IN013A-EN-P—October 2014
Page 6
6SensaGuard™ 18 mm Plastic Barrel Unique Coding
K1
+24V DC
MSR127RP with 1 sensor, monitored manual reset, driving 100S or 700S safety controllers.
A1 S11
S52 S121323 33
41
S21
S22
S34A214 24 34 42
MSR127RP
Reset
GND
Blue
Gray
Pink
Yellow
Red
Brown
SensaGuard
Unit 1
K2
+24V DC
GND
MSR127RP with 3 sensors in series, monitored manual reset, driving 100S or 700S safety controllers
Blue
Gray
Pink
Yellow
Red
Brown
SensaGuard
Unit 1
SensaGuard
Unit 2
SensaGuard
Unit 3
K1
A1 S11
S52 S121323 33
41
S21 S22 S34 A2 14 24 34 42
MSR127RP
Reset
K2
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Yellow
Red
Brown
MSR127RP with 3 sensors and 1 440L light curtain in series, monitored manual reset, driving 100S or 700S safety relays.
Note: Light curtain must be last (farthest from MSR127).
GND
A1 S11
S52 S121323 33
41
S21 S22 S34 A2 14 24 34 42
MSR127RP
Reset
K1
K2
+24V DC
Blue
Gray
Pink
Yellow
Red
Brown
SensaGuard
Unit 1
SensaGuard
Unit 2
SensaGuard
Unit 3
GuardShield
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Brown
A1 S11
S52 S121323 33
41
S21
S22
S34A214 24 34 42
MSR127TP
GND
MSR127RP with 1 sensor, automatic reset, driving 100S or 700S safety controllers
+24V DC
SensaGuard
Unit 1
K1
K2
Blue
Gray
Pink
Yellow
Red
Brown
MSR127TP with 3 sensors in series, automatic reset, driving 100S or 700S relays.
MSR127TP
+24V DC
GND
Blue
Gray
Pink
Yellow
Red
Brown
SensaGuard
Unit 1
K1
A1 S11
S52 S121323 33
41
S21 S22 S34 A2 14 2434 42
K2
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Yellow
Red
Brown
SensaGuard
Unit 3
SensaGuard
Unit 2
MSR127TP with 3 sensors and 1 440L light curtain in series, automatic reset, driving 100S or 700S safety contactors.
Note: Light curtain must be last (farthest from MSR127)
MSR127TP
GND
A1 S11
S52 S121323 33
41
S21 S22 S34 A2 14 2434 42
K1
K2
+24V DC
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Yellow
Red
Brown
Blue
Gray
Pink
Brown
GuardShield
SensaGuard
Unit 1
SensaGuard
Unit 3
SensaGuard
Unit 2
IMPORTANT
Application Wiring Examples
Refer to Technical Specifications (page 1) for
certification information and ratings.
Rockwell Automation 440N-IN013A-EN-P—October 2014
Page 7
SensaGuard™ 18 mm Plastic Barrel Unique Coding 7
A1
S11
S21
S12
S22
S32
L11Y32L121314
S42
2324S34
A2
DI
440R-D22R2
0
1
2
3
4
56
7
8
LOGIC
K1
K2
SensaGuard
SensaGuard
+24V DC
K1
K2
Reset
889D-F4AC-*
889D-F5AC-*
24V Com
Brown
Blue
Black
White
Brown
Blue
Grey
Black
White
Gate
Open
889D-F5AC-*
K1
K2
S11
S12
S21
S22
S34A1 13
L11A2 142324Y32
SI
440R-S12R2
RESET
0
MM
AM
24V DC
24V DC Com
Brown
Blue
White
Black
SensaGuard Integrated Latch
Reset
Gate
Open
Grey
IMPORTANT
889D-F8AB-*
A1
S11
S21
S12
S22
S32
L11Y32L121314
S42
2324S34
A2
DI
440R-D22R2
0
1
2
3
4
56
7
8
LOGIC
K1
K2
K1
K2
S11
S12
S21
S22
S34A1 13
L11A2 142324Y32
SI
440R-S12R2
RESET
0
MM
AM
SensaGuard
SensaGuard
+24V DC
K1
K2
Reset
889D-F8AB-*
889D-F8AB-*
24V Com
Note: The Green wire is connected to the housing of the Stainless Steel
SensaGuard only; it has no connection for plastic SensaGuard.
Brown
Yellow
Yel lo w
Red
Red
Blue
Pink
Grey
Pink
Grey
Brown
Blue
Green
White
Green
White
Gates
Open
24V
D
C
24V DC Com
Brown
Yellow
Red
Blue
White
Pink
SensaGuard Integrated Latch
Reset
Gate
Open
Grey
Green
Application Wiring Examples
Rockwell Automation 440N-IN013A-EN-P—October 2014
Refer to Technical Specifications (page 1) for
certification information and ratings.
Check the machine is
isolated and stopped
whenever the interlocked
guard door is open.
IMPORTANT: After
installation and
commissioning, the
actuator, switch and switch
lid fixing screws should be
coated with tamper evident
varnish or similar compound.
Maintenance
Monthly
Check the correct operation of the switching circuit. Also check
for signs of abuse or tampering. Inspect the switch casing for
damage.
Repair
If there is any malfunction or damage, no attempts at repair
should be made. The unit should be replaced before machine
operation is allowed.
Declaration of Conformity
This is to declare that the products shown in this document
conform with the Essential Health and Safety Requirements
(EHSRs) of the European Machinery Directive. These products also
conform to EN60947-5-3, EN ISO 14119, and have third-party
approval.
For a comprehensive certificate please visit: www.ab.com/safety.
Rockwell Automation maintains current product environmental information on its website at
http://www.rockwellautomation.com/rockwellautomation/about-us/sustainability-ethics/product-environmental-c ompliance.page
Allen-Bradley and Rockwell Automation are trademarks of Rockwell Automation, Inc. Trademarks not belonging to Rockwell Automation are property of their respective companies.
Publication 440N-IN013A-EN-P—PN-243710—10000979536 Ver 00—October 2014