Rockwell Automation 42DRP User Manual

INSTALLATION INSTRUCTIONS PHOTOSWITCH
DIFFUSE/ANALOG CONTROL, BULLETIN 42DRP-5400
IMPORTANT: SAVE THESE INSTRUCTIONS FOR FUTURE USE. FOR ADDITIONAL INFORMATION REFER TO PUBLICATION PG-9000
BULLETIN NUMBER
PHOTOHEAD POWERBASE
VOLTAGE
SUPPLY
42DRP- 5400
SUPPLY
CURRENT
TYPE RATING LEAKAGE
Analog Voltage 1--10VDC — Analog Current 1--20mA
Two Adjustable Set
Points NPN
42DTB-5000
TERMINAL
42DCB-5000
CABLE
22--28
VDC
70mA
SPECIFICATIONS:
Voltage Supply to Analog Output (Terminal 2):
Current Output 40VDC Max............................
Voltage Output 0V....................................
Output Indicators
Setpoint A Red LED...................................
Setpoint B Green LED.................................
Setpoint Adjustment Ye s................................
Setpoint Output Differential 15%.........................
Slope Selectable Positive or Negative.......................
Reverse Polarity Protection Ye s...........................
Transient Noise Protection Ye s...........................
Short Circuit Protection Analog Output only................
Analog Output Calibration Ye s...........................
Sensing Range Adjustment Ye s...........................
Temperature Compensation Yes..........................
Field of View 3........................................
Transmitting LED Infrared, 880nm........................
Operating Environment: NEMA 3, 4, 12, 13, and IP66 (IEC529)
Approvals UL Listed and CSA Certified....................
Housing Material High impact chemically resistant Valox Ambient Temperature Range -- 4 0
.....
o
Fto150oF(--40oCto65oC)..
Relative Humidity 90%.................................
Te rm i na t io n s
Cable Base: Supplied with 10(3m) of 5-conductor,..........
flexible, vinyl-covered cable
Terminal Base: Supplied with #6/32 nickel plated brass.......
pressure type terminals
ACCESSORIES
Optional Mounting Assemblies
PAR T NU MBER DESCRIPTION
60-1577 Armored Cable Adapter 60-1785 Universal Mounting Assembly
60-1748 Heavy Duty Mounting Assembly 60-2014 Flexi-mount Mounting Assembly 60-2083 Photoguard Heavy Duty Protection
60-2213 Conduit Mounting Adapter 60-2230 Limit Switch Type Mounting Assembly
61--5540 NEMA 7 & 9 Enclosure
(OFF STATE)
RESPONSE
TIME
100ms 2-- 1 5
WHITE PAPER
15X15 (.38 X .38)
(.61m--4.57m)
OPERATING DISTANCE
WITH
100mA 10A
OPERATING DISTANCE SELECTION
The maximum operating distance is based on installing the con­trol in a relatively clean environment. Normal industrial environment actually ranges from moderately Dusty to extremely Dirty.
Greater operating margin (excess gain) may be required, which can be obtained by reducing the operating distance of the control.
TYPICAL RESPONSE CURVES
CURRENT OUTPUT SLOPE
20
18
16
14
POSITIVE
SLOPE
12
10
8
6
DC CURRENT (mA)
4
2
0
6”
0
(15.24cm)
(.3m)
1’
(.6m)
2’
(.9m)
3’
OPERATING DISTANCE
10
DC VOLTAGE
9
8
7
6
5
4
3
2
1
0
0
VOLTAGE OUTPUT SLOPE
POSITIVE
SLOPE
(.3m)
1’
(.6m)
2’
(.9m)
3’
OPERATING DISTANCE
NEGATIVE
SLOPE
4’
(1.2m)
NEGATIVE
SLOPE
4’
(1.2m)
LINEAR
RESPONSE
5-- 1 3
(1.22m--4.27m)
5’
(1.5m)
5’
(1.5m)
CALIBRATION PROCEDURES
Before starting the calibration procedures for Analog Output or Setpoint Output, be sure the control is at the same temperature as it’s environment; it adjusts after approximately 15 minutes. Setpoint Cal­ibration is best performed after calibration of the Analog Output has been completed.
Calibration of Analog Output
Calibration of the Analog Output is done with a Voltmeter or an Ammeter. When calibrating the Voltage Output, connect the Voltme­ter between Terminal 2 (+) and the negative power supply, terminal 1 (--). Select the Voltmeter Scale for 10VDC. When calibrating the Cur­rent Output, install the Ammeterbetween Terminal2 (--) and the posi­tive power supply Terminal (+), or the positive of a separate power supply when used. Select the Ammeter scale for 20mA (DC).
1. With Selector Switches 1 and 2, select Analog Current or Voltage Output.
2. With Selector Switches3 and 4, selectPositive or Negative Slope operation.
3. Set retroreflective target at 2(.61m). Adjust the Analog Output Calibration pot. for 10VDC or 20mA (2%) when in Negative Slope operation to 1VDC or 1mA (10%) when in Positive Slope operation.
4. Set the retroreflective target at the desired range. 15(4.57m) maximum, 5(1.52m) minimum. Adjust the Sensing Range Ad­justment pot. for 1VDC or 1mA (10%) when using Negative
5. Bring the object to be detected at 1(.3m). Re-adjust the Analog Output Calibration pot. for 10VDC or 20mA (2%) when using Negative Slope operation or to 1VDC or 1mA when using Posi­tive Slope operation if necessary.
6. Place the object to be detected at the desired range. Re-adjust the Sensing Range Adjustment pot. for 1VDC or 1mA (10%) when using Negative Slope operation or to 10VDC or 20mA (2%) when using Positive Slope operation if necessary.
The Analog Output is now calibrated.
Calibration of Setpoint Outputs
1. Place the object at the distance where the Setpoint Output A is to come on.
2. Adjust the Setpoint pot. A to turn on Output A at this point. (Red LED turns on.)
3. Place the object at the distance where the Setpoint Output B is to come on.
4. Adjust the Setpoint B to turn on Output B at this point. (Green LED turns on.)
This completes the calibration of Setpoint Outputs.
Slope operation or to 10VDC or 20mA (2%) when using Posi­tive Slope operation.
INSTALLATION
The control must be securely mounted on a firm, stable surface or support. A mounting
which is subject to excessive vibration or shifting may cause intermittent operation.
OUTLINE DIMENSIONS
GENERAL PURPOSE MOUNTING 60-1785
(7.10)
Control with Cable Base
39/64 (15.4)
.280
15/32 (11.9)
27/8
(73.0)
MATERIAL
#11 GA CRS
61/64 (24.2)
2
(50.8)
2 21/32
(67.5)
4.0
(101.6)
11/ 32 (8.73)
57/16
(138.1)
.325
(8.26)
2 57/64 (73.42)
13/4 DIA.
CLEARANCE FOR
#1/4--20 HDW
3/4
3/4
(19.0)
(19.0)
61/64
39/64
(15.4)
.280
(7.10)
15/32 (11.9)
(106.5)
41/4
(24.2)
(50.8)
2 21/32
(67.5)
11/3 2 (8.73)
5 25/64 (136.9)
1 11/16
(42.9)
2
Control with Terminal Base
.325
(8.26)
HEAVY DUTY MOUNTING 60-1748
39/64 (15.4)
61/64
15/32 (11.9)
2
5/32
(54.7)
21/64
(8.3)
2 27/32
(72.3)
11/2
(38.1)
(24.2)
FOR #10-32 HDW
CLEARANCE
11/2
(38.1)
1/4 (6.3)
1 14/32
(61.9)
11/3 2 (8.73)
1 53/64 (46.43)
47/64
(104.4)
1
(25.4)
CLEARANCE
FOR #10-32 HDW
21/2
(63.5)
39/64 (15.4)
#10-32 THREAD 2HOLES
21/2
(63.5)
21/64
(8.3)
Control with Cable Base Control with Terminal Base
15/32 (11.9)
11/4
(31.7)
1/4
(6.3)
11/2
(38.1)
61/64 (24.2)
1/4 (6.3)
1 14/32
(61.9)
11/3 2
(8.73)
(25.4)
1
59/64 (23.4)
WIRING
All external wiring should conform to the National Electric Code and applicable local codes. See wiring diagrams for external connectins.
ANALOG CURRENT OUTPUT CONNECTIONS
TERMINAL
BASE
CABLE BASE
RED
+
GRAY
2
RMAX =
BLACK
--
(+) 22 -- 28
VDC
CURRENT
SENSOR
(+) 40 VDC
SUPPLY VOLTAGE --
20MA
FLOATING
SHIELD
ANALOG VOLTAGE OUTPUT CONNECTIONS
TERMINAL
BASE
+
MAX
10V
(--)
2
--
CABLE BASE
RED
GRAY
BLACK
(+) 22--28
VDC
VOLTAGE
SENSOR
R=3k
Ohm MIN
(--)
FLOATING
SHIELD
NPN SET POINT OUTPUT CONNECTIONS
TERMINAL
BASE
+
3
1
--
CABLE BASE
RED
ORANGE
BLUE
BLACK ( --)
LOAD
100mA MAX
LOAD
100mA MAX
4 11/32 (110.3)
25/32 (54.7)
(+)22--28
5 24/32 (146.4)
21/2
(63.5)
VDC
(+)10--30
VDC
(+)10--30
VDC
(--)
FLOATING
SHIELD
Publication PA--9171(A)
September 1992
Loading...