Rockwell Automation 36С47 User Manual

INSTRUCTION SHEET D2Ć3017Ć2
OUTPUT
F
or use with 300, 350, 400 and 500 HP
460 V
General Purpose or Variable Torque
CONT
ACTOR KIT
Models 36C47
AĆC VLSR
Drives
WARNING
BEFORE INST
ALLING
AND/OR
OPERA
TING THIS KIT, THE QUALIFIED ELECTRICAL MAINTENANCE
PERSON WHO IS F
AMILIAR WITH THIS TYPE OF EQUIPMENT AND THE HAZARDS INVOLVED SHOULD READ THIS ENTIRE INSTRUCTION SHEET. FAILURE
TO OBSERVE THIS PRECAUTION COULD REĆ SULT IN BODILY INJURY.
DESCRIPTION
The Reliance Electric Output Contactor Kit provides a positive AĆC VLSR Drive Controller and the Drive Motor. A controller Start command will cause the contactor to be energized. the AĆC Contactor's auxiliary contact does not close (N" auxiliary the AĆC Contactor will drop out immediately if the controller speed is reached if the controller is set will drop out after zero speed is reached if the controller is set (IET)
Upon the clean and dry area until ready to use. The ambient temperature of the storage area must not exceed 65oC (149oF) or go below -40oC (-40oF).
disconnect (contactor) between the output of the
The controller start sequence will be inhibited
signal). When the Stop rocker switch is pressed,
is set for coastĆtoĆrest or will drop
for rampĆtoĆrest. When an instantaneous electronic trip
occurs,
receiving, check the contents of the
contents as listed in Table 1. Store this equipment in a
the AĆC Contactor will drop out immediately
out after zero
for coastĆtoĆrest or
kit received with
if
INSTALLATION
NOTE:
mounted in a clean and dry environment. Maximum ambient temperature must not exceed 40oC outside the cabinet (55oC inside the cabinet).
WIRE SIZING NOTE: Care should be taken to see that all interconnecting wiring is sized and installed in
All components of the Output Contactor Kit must be
conformance with the National Electric Code (NEC), published by the National Fire Protection Association, or the
Canadian Electrical Code (CEC),
local codes.
Table 1 Complete parts listing.
Description Qty. Part Number
Contactor Auxiliary Contact (NO) Connector Control Transformer Fuse Block Fuse Relay Socket Relay Cover Wire Harness Wire Harness Wire Harness Wire Assembly Wire Assembly Wire Assembly Wire Assembly Hex Washer Head Screw
.
ăă(5/16Ć18 x 1/2") Hex Head Cap Screw ăă(1/4Ć20 x 3/4") Flat Washer (1/4") Lock Washer (1/2") Hex Head Cap Screw ăă(1/2Ć13 x 1 1/4") Flat Washer (1/2") Lock Washer (1/2") Taptite
Screw (10Ć32 x Taptite Screw (8Ć32 x 1/2") Taptite Screw (6Ć32 x 1/2") Hex Head Cap Screw ăă(1/4Ć20 x 1 1 /4") Spacer TyĆRap
1/2")
and other applicable
1
705310Ć9R
1
76624ĆX
3
610290Ć57A
1
417155ĆS
1
49454ĆA
1
64676Ć1P
1
600434Ć5R
1
600434Ć6R
1
705321Ć15R
1
705337Ć35R
1
801553Ć34R
1
801553Ć35R
1
608809Ć12SA
1
608809Ć12X
1
608809Ć12RX
1
608809Ć12SC
4
601741Ć73B
6
601741ĆC
8
601748Ć1E
8
601748Ć3J
3
601741Ć8AB
3
601748Ć1J
3
601748Ć3N
5
601741Ć63C
2
601741Ć62D
2
601741Ć61D
2
601741ĆAB
2
400684ĆB
10
69306Ć3D
1. Disconnect all power to the AĆC VLS Drive before
installing this kit.
DANGER
EQUIPMENT IS AT LINE VOLTAGE WHEN
INPUT DISCONNECT IS ON. THE
THE
INPUT
DISCONNECT MUST BE OFF BEFORE IT IS
TO TOUCH ANY INTERNAL P
SAFE
ARTS
OF THIS EQUIPMENT. AFTER POWER IS REMOVED, THE COMMUTATION CAPACIĆ TORS CAN REMAIN CHARGED. ALLOW TWO MINUTES BEFORE TOUCHING ANY INTERNAL PARTS OF THE CONTROLLER. FAILURE TO OBSERVE THESE PRECAUĆ TIONS COULD RESULT IN FATAL INJURY.
NOTE: If the Output Contactor Kit and the Control Circuit Transformer Kit are to be installed, mount the Output Contactor Kit normally occupies the same location as the Output Contactor Kit. The Control Circuit Transformer relocated as defined in Instruction Sheet D2Ć3014.
2. Disconnect
Kit first because the
Control Circuit T
ransformer
Kit must be
motor leads T1, T2 and T3 from the output bus bar assembly (Figure 1). Disconnect bus bars 601, 602 and 603 from the output bus bar assembly (Figure 1). Remove the output bus bar assembly by removing the four taptite screws. This assembly will not
be used while the Output Contactor
Kit is installed.
TAPTITE
SCREW (4)
DISCONNECT MOTOR
LEADS T1, T2, T3
BUS BARS
601, 602, 603
SIDE VIEW
OUTPUT
FRONT VIEW
BUS BAR
ASSEMBLY
Figure 1. Removing output bus bar assembly.
CONTROL TRANSFORMER
AUXILIARY CONTACT
CONTACTOR
3.
Snap the Auxiliary Contact (76624Ć
X) into the cavity on the front left of the Contactor (Figure 2). Secure with the captive lock screw provided.
4. Using the four furnished 5/16Ć18 x 1/2" hex washer head
screws, mount
the Contactor (705310Ć9R) in the controller as shown in Figure 2. The mounting holes are preĆdrilled in the back panel.
5. Using the six furnished 1/4Ć20 x 3/4" hex head cap screws and six 1/4" flat washers and 1/4" lock washers, install the three identical Connectors (610290Ć57A) to the line side of the Contactor. See Figure 2.
6. Using
the three furnished 1/2Ć13 x
1 1/4" hex head cap screws and the three 1/2" flat washers and 1/2" lock washers, attach the Connectors to the 601, 602 and 603 bus bars.
7. Using
four of the furnished 10Ć32 x 1/2" taptite screws, mount the Control Transformer (417155ĆS) to the left of
the motor overload relay block as shown in Figure 2.
The
mounting holes are preĆdrilled in
the back panel. (It might be helpful to preĆthread the screws in the mounting holes.)
8. connect the metal jumper supplied with the transformer H2)
on the input side of the transformer
between the two center
terminals (H
. See Figure
3
and
2.
CONNECTOR (3)
METAL JUMPER
FUSE
IN FUSE BL
OCK
MOTOR OVERL RELA
Y BL
OCK
Figure 2. Controller right bay components.
OAD
ă9. Using the two furnished 8Ć32 x 1/2" taptite screws,
mount the Fuse Block (49454ĆA) to the left of the Control Transformer. See Figure 2. The mounting holes are preĆdrilled in the back panel. Insert the 3.2
F
use (64676Ć1P), 250Ćvolt, UL Class RK5) into the
amp Fuse Block.
115
VOL
T
TERMINAL B
RELA RELA
OARD
Y IN Y SOCKET
OUTLET AIR DUCT REMOVED
SIDE W OPENINGS
ALL
10. Using
two
furnished 6Ć32 x 1/2" taptite screws, mount the Relay Socket (600434Ć5R) in the left bay of the controller as shown in Figure 3. The mounting holes are preĆdrilled in the back panel. Insert the Relay (600434Ć6R) into the Relay Socket.
11. Remove
the outlet air duct (Figure 3) by loosening the nine hex head cap screws. Set aside for later reĆinstallation.
12. Remove
the factory
Ćinstalled wiring between
terminals 43 and 53 on TB1 and terminals 1 and 2 on the faceplate of the CSS-* card. See Figure 4.
13. Connect Wire Harness 705337Ć35R. Connect leads 189 and 2 to terminals 1 and 2, respectively, on the faceplate
of the CSS- card. Connect the other end of lead 189 to the 115Ćvolt terminal board and the other end
of the lead 2 to the Relay
* The
fourth letter of this regulator PC board designation indicates a difference in the PC board.
Refer to the specific controller to identify the fourĆletter PC board designation.
. See Figures 3, 4 and 7.
CS
S -*CARD
FACEPLATE
CHANNELS
POWER MODULE
Figure 3. Controller left bay components.
RELAY
WIRE
AS
SEMBLY
608809Ć12SA
115 VOL
TERMINAL
WIRE HARNES
705337Ć35R
CSS-*CARD FACEPLATE
* The fourth letter of this regulator PC board designation indicates a difference in the PC board. Refer to the specific controller to identify the fourĆletter PC board designation .
T
BOARD
S
TB1
Figure 4. Connecting Wire Harness 705337Ć35R and Wire Assembly 608809Ć12SA.
14. Connect Wire Assembly 608809Ć12SA (labeled 188) between the 115Ćvolt terminal board and the Relay. See Figures 4 and 7.
15. Connect Wire Assembly 608809Ć12X (the green ground wire labeled 289) to the Control Transformer. Using the remaining 10Ć32 x 1/2" taptite screw,